Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING TRAINING MANUAL Embraer ERJ-190 Series (GE CF34) B1.1 and B2 (-sub) categories AIR CONDITIONING (ATA 21) Level 3 ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 1 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING THIS PAGE IS INTENTIONALLY LEFT BLANK ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 2 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING TABLE OF CONTENTS ATA 21-00 AIR CONDITIONING GENERAL .................................................. 6 INTRODUCTION ........................................................................................ 6 ELECTRONIC COMPARTMENTS VENTILATION ................................... 10 CONTROLS ............................................................................................. 14 INDICATIONS .......................................................................................... 16 ATA 21-20 AIR CONDITIONING DISTRIBUTION ........................................ 18 INTRODUCTION ...................................................................................... 18 DESCRIPTION ......................................................................................... 20 ATA 21-29 LOW PRESSURE GROUND SUPPLY ....................................... 30 COMPONENTS ........................................................................................ 32 OPERATION ............................................................................................ 40 DIAGNOSTIC AND TESTS ...................................................................... 46 ATA 21-26 AVIONICS COMPARTMENT ..................................................... 48 INTRODUCTION, DESCRIPTION ............................................................ 48 COMPONENTS ........................................................................................ 50 OPERATION ............................................................................................ 54 DIAGNOSTIC AND TEST......................................................................... 58 FORWARD CARGO COMPARTMENT VENTILATION ................................ 60 INTRODUCTION, DESCRIPTION ............................................................ 60 COMPONENTS ........................................................................................ 62 OPERATION ............................................................................................ 64 DIAGNOSTIC AND TEST......................................................................... 66 ELECTRONIC RACK VENTILATION SYSTEM ........................................... 68 INTRODUCTION ...................................................................................... 68 DESCRIPTION ......................................................................................... 70 COMPONENTS ........................................................................................ 72 OPERATION ............................................................................................ 74 DIAGNOSTIC AND TEST......................................................................... 80 ATA 21-30 PRESSURIZATION .................................................................... 82 INTRODUCTION ...................................................................................... 82 DESCRIPTION ......................................................................................... 84 COMPONENTS ........................................................................................ 86 OPERATION ............................................................................................ 98 DIAGNOSTIC AND TEST....................................................................... 114 ATA 21-50 COOLING ................................................................................ 116 INTRODUCTION .................................................................................... 116 DESCRIPTION ....................................................................................... 118 ISSUE 1, 24 Sep 2014 COMPONENTS ...................................................................................... 122 OPERATION .......................................................................................... 136 TRAINING INFORMATION POINTS....................................................... 140 DIAGNOSTIC AND TEST ....................................................................... 142 ATA 21-60 TEMPERATURE CONTROL .................................................... 144 INTRODUCTION .................................................................................... 144 DESCRIPTION ....................................................................................... 146 COMPONENTS ...................................................................................... 152 OPERATION .......................................................................................... 154 DIAGNOSTIC AND TEST ....................................................................... 156 ATA 21-00 MEL.......................................................................................... 158 FOR TRAINING PURPOSES ONLY Page: 3 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING TABLE OF FIGURES THE AIR CONDITIONING SYSTEM .............................................................. 7 AIR CONDITIONING BLOCK DIAGRAM ...................................................... 9 PASSENGER-CABIN ZONE TEMPERATURE CONTROL BLOCK DIAGRAM .................................................................................................... 11 PASSENGER-CABIN ZONE TEMPERATURE CONTROL BLOCK DIAGRAM .................................................................................................... 13 INDICATION PANELS ................................................................................. 15 INDICATION ................................................................................................ 17 AIR CONDITIONING SCHEMATIC ............................................................. 19 AIR SUPPLY TO THE FLIGHT DECK ......................................................... 21 CABIN AIR DISTRIBUTION SYSTEM ......................................................... 23 GASPER VENTILATION SYSTEM .............................................................. 25 CABIN AIR RE CIRCULATION DIAGRAM ................................................. 27 RAM AIR VENTILATION SYSTEM ............................................................. 29 LOW PRESSURE SUPPLY ......................................................................... 31 THE DISTRIBUTION DUCT SYSTEM ......................................................... 33 MIXER ......................................................................................................... 35 SMOKE DETECTOR ................................................................................... 37 EMERGENCY RAM AIR VALVE ................................................................. 39 RECIRCULATION FANS ............................................................................. 41 RAM AIR VALVE OPERATION ................................................................... 43 SMOKE REMOVAL ..................................................................................... 45 CMC TESTS ................................................................................................ 47 FORWARD ELECTRONIC BAY .................................................................. 49 FAN FAILURES ........................................................................................... 51 FAN FAILURES ........................................................................................... 53 FORWARD ELECTRONIC FAN OPERATION ............................................ 55 MIDDLE ELECTRONIC BAY ....................................................................... 57 DIAGNOSTIC AND TEST ............................................................................ 59 FORWARD CARGO COMPARTMENT ....................................................... 61 FWD CARGO COMPARTMENT.................................................................. 63 OPERATING LOGIC ................................................................................... 65 DIAGNOSTIC AND TEST ............................................................................ 67 ELECTRONIC RACK VENTILATION LAYOUT .......................................... 69 COMPONENTS VIEW ................................................................................. 71 COMPONENTS VIEW ................................................................................. 73 OPERATION................................................................................................ 75 ISSUE 1, 24 Sep 2014 OPERATION ................................................................................................77 MAINTENANCE TEST PANEL OPERATION ..............................................79 MAINTENANCE TEST PANEL ....................................................................81 CABIN PRESSURE CONTROL SYSTEM ...................................................83 CABIN PRESSURE CONTROL SYSTEM COMPONENTS .........................85 PRESSURIZATION CONTROL PANEL ......................................................87 CABIN PRESSURIZATION CONTROLLER ................................................89 CPCS CONTROLLER .................................................................................91 OUTFLOW VALVE ......................................................................................93 POSITIVE PRESSURE RELIEF VALVE ......................................................95 NEGATIVE PRESSURE RELIEF .................................................................97 GROUND AND TAKEOFF MODES .............................................................99 CLIMB AND CRUISE MODES ................................................................... 101 DESCENT AND ABORT MODES .............................................................. 103 MANUAL MODE ........................................................................................ 105 ABNORMAL OPERATION ........................................................................ 107 EICAS INDICATIONS ................................................................................ 109 EICAS INDICATIONS (CONTINUED) ........................................................ 111 EICAS INDICATIONS (CONTINUED) ........................................................ 113 BUILT-IN TEST.......................................................................................... 115 AIR CONDITIONING SYSTEM .................................................................. 117 ECS PACK ................................................................................................ 119 FLOW CONTROL ...................................................................................... 121 FLOW CONTROL VALVE ......................................................................... 123 DUAL HEAT EXCHANGER ....................................................................... 125 AIR CYCLE MACHINE COMPONENTS .................................................... 127 CONDENSER ............................................................................................ 129 BYPASS VALVE ....................................................................................... 131 LOW LIMIT BYPASS VALVE, ADD HEAT VALVE AND ECS PACK BYPASS VALVE ....................................................................................... 133 TEMPERATURE SENSORS...................................................................... 135 AIR CYCLE MACHINE OPERATION ........................................................ 137 ECS OFF LOGIC ....................................................................................... 139 PACK RELATED MESSAGES .................................................................. 141 PACK TESTS ............................................................................................ 143 AMS TEMPERATURE CONTROLLER...................................................... 145 COCKPIT ZONE CONTROL...................................................................... 147 FOR TRAINING PURPOSES ONLY Page: 4 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING SINGLE CABIN ZONE CONFIGURATION ................................................ 149 TWO CABIN ZONE CONFIGURATION..................................................... 151 TRIM MODULATING VALVES .................................................................. 153 AUTOMATIC TEMPERATURE CONTROL ............................................... 155 CMC DIAGNOSTIC ................................................................................... 157 MEL - EXAMPLE ....................................................................................... 159 MEL - EXAMPLE ....................................................................................... 160 MEL - EXAMPLE ....................................................................................... 161 MEL - EXAMPLE ....................................................................................... 162 MEL - EXAMPLE ....................................................................................... 163 ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 5 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ATA 21-00 AIR CONDITIONING GENERAL INTRODUCTION The Environmental Control System (ECS) provides air conditioning for the flight deck and passenger cabin, filtered cabin air re circulation, conditioned air supply for gaspers, fan air cooling for avionics and emergency ram air ventilation for flight deck smoke clearance. The ECS provides cargo bay ventilation. The cargo bay ventilation system is optional. Two identical ECS packs which condition fresh bleed air for cabin and flight deck heating and cooling Optional trim air system to provide two cabin zone temperature control Flow control valves to provide accurate modulation of pack air flow, and all associated valves and sensors used for system built in test Avionic fan control and cargo compartment ventilation Cockpit smoke removal Provides environmental control system flow rate data used by the cabin pressure control system to anticipate changes in cabin pressure. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 6 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING THE AIR CONDITIONING SYSTEM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 7 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING AIR CONDITIONING PACKS Two ECS packs are installed in the wing-to-fuselage fairing. The AMS controller controls the bleed airflow to each pack independently, through the respective pack flow control valve (FCV). Engine # 1 supplies bleed air to the pack # 1 while engine # 2 supplies bleed air to pack # 2. A single pack is capable of keeping adequate cabin/cargo hold pressurization and temperature. Single engine bleed can supply both ECS packs using the cross bleed. RE CIRCULATION FANS Re circulated air from the passenger cabin and cockpit is ducted to the mixing manifold via two re circulation fans located in the pressurized section of the airplane. The re circulation fans draw air from the re circulation bays and impel the air back into the flight deck and cabin distribution system.The total flow entering the cockpit and the passenger cabin is made up of approximately 52% fresh air and 48% of re circulating air. The re circulation fans are commanded off when DUMP button is pressed or smoke is detected in the re circulation bay. GASPER VENTILATION The gasper air distribution system provides air to each pilot and passenger positions.Air flowing from the mixing manifold through the gasper ducts supplies the gasper ventilation system. TRIM AIR (OPTIONAL) The trim air system controls the amount of hot bleed air from the pack 2 into the mixer for independent control of forward and aft cabin zones temperatures. The trim air system is used for temperature control improvement. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 8 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING AIR CONDITIONING BLOCK DIAGRAM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 9 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ELECTRONIC COMPARTMENTS VENTILATION FORWARD ELECTRONIC BAY (E-BAY) EMERGENCY RAM AIR VENTILATION The forward e-bay comprises three fans, which provide forced cooling air for # 1 Secondary Power Distribution Assembly (SPDA 1), Emergency Integrated Control Centre (EICC) and all other avionics located in this e- bay. The fans draw air from the cockpit and expel air toward the underfloor re circulation bay. A flow sensor is used for fan/flow health monitoring to ensure forward e-bay flow requirements. The pack 1 ram air ventilation consists of a ventilation valve installed in emergency ram ducting that connects the ram air duct to the pack 2 outlet ducting. The emergency ram air valve is commanded open any time the airplane is in flight and both air conditioning packs are commanded OFF or failed OFF and the airplane’s flight altitude is less than 25000 ft. CENTRE ELECTRONIC BAY (E-BAY) The centre e-bay comprises three fans, which provide forced cooling air for the centre e-bay electronics, Left Integrated Control Centre (LICC), Right Integrated Control Centre (RICC) and SPDA 2. The fans draw air from the rear cabin return and expel it toward the underfloor re circulation bay. Flow sensors are used for fan/flow health monitoring. The pack 2 ram air ventilation consists of a check valve installed in the emergency ram air ducting that connects the ram air duct to the pack 2 outlet ducting. The emergency ram air check valve does not require electronic control. The emergency ram air check valve will be open whenever the pressure in the ram air circuit is greater than cabin pressure. FORWARD CARGO BAY VENTILATION (OPTIONAL) The ECS provides ventilation for live animals in the forward cargo bay. This optional system contains a fan on the side of the bay to provide underfloor re circulation air into the bay. The system also contains a shutt off valve at the outlet of the bay that closes in the event of fire and thus preventing halon from leaving the bay. In addition, in the event of fire, forward cargo compartment fans are commanded OFF to prevent halon from entering the cabin. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 10 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING PASSENGER-CABIN ZONE TEMPERATURE CONTROL BLOCK DIAGRAM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 11 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DISTRIBUTION The distribution system receives airflow from the re circulation fans, cooling packs, ram air system and ground equipment and distributes this air to the cockpit, passenger cabin, gaspers, avionics compartments and forward cargo compartment. PRESSURIZATION CONTROL The aircraft operates at altitudes where the oxygen density is not sufficient to sustain life. The pressurization control keeps the aircraft cabin interior at a safe pressure altitude. This protects the passengers and crew from the effects of hypoxia (oxygen starvation). COOLING The cooling system receives hot bleed air from the APU (Auxiliary Power Unit) or engines and supplies conditioned air to the distribution system. TEMPERATURE CONTROL The temperature control system provides independent closed loop temperature control for the cockpit and one or two separate passenger cabin zones. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 12 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING PASSENGER-CABIN ZONE TEMPERATURE CONTROL BLOCK DIAGRAM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 13 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CONTROLS The air conditioning controls and indications are: PRESSURIZATION CONTROL PANEL Controls the pressurization of the aircraft, in AUTO and MANUAL mode. The mode selector switch facilitates auto, manual mode selection or landing field elevation settings. Manual selector enables direct control of the outflow valve. Dump switch controls auto depressurization of the aircraft. AIR CONDITIONING PANEL PACK 1 switch controls the left Cooling Pack (AUTO-OFF) CKPT knob Controls the cockpit between 19 and 30 ∞C. RECIRC switch - Controls the re circulation system (AUTO - OFF) PAX CABIN knob - Controls the passenger cabin temperature between 19 and 30 ∞C. PACK 2 switch - Controls the right Cooling Pack (AUTO - OFF) FLIGHT ATTENDANT PANEL Zone temperature control selector enables attendant cabin temperature control for zone 1, zone 2 when on the cockpit temperature selector knob the ATT position is selected. MCDU DATA SET MENU Take off data set menu enables pilot selection of the ECS system for take off, ON or OFF. FEET VALVES SELECTOR Purely mechanical control of the feet valves to direct more warm air to the pilot feet. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 14 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING INDICATION PANELS ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 15 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING INDICATIONS Four typed of indication are used to monitor Environmental Control System operation: The EICAS provides indication of the pressurization system parameters The CAS field display shows warning, caution and advisory messages By selecting the MFD menu bar, the ECS synoptic page will provide system status and indications concerning the environmental control system CMC messages can be viewed on the co-pilot multi-function display by selecting maintenance on the menu bar. TRAINING INFORMATION POINTS Caution: THE MODULE OR UNIT CONTAINS ELECTROSTATIC DISCHARGE SENSITIVE (ESDS) ITEMS. OBEY THE APPROVED INDUSTRY PRECAUTIONS WHEN YOU TOUCH, REMOVE, OR INSERT PARTS OR ASSEMBLIES. DAMAGE CAN OCCUR FROM ELECTROSTATIC DISCHARGE. Caution: DO NOT TOUCH THE ELECTRICAL PINS OF THE CONNECTORS. DAMAGE CAN OCCUR TO THE INTERNAL ESDS COMPONENTS. The AMS modules must be handled using ESDS (Electrostatic Discharge Susceptible). The AMS controller processor modules incorporate a field-loadable software named Black Label. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 16 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING INDICATION ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 17 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ATA 21-20 AIR CONDITIONING DISTRIBUTION INTRODUCTION The air that is already pressure-regulated by the pneumatic system passes through the two packs where duct flow and temperature are adjusted to the required level. At the packs outlet, temperature sensors monitor duct temperature. Before the distribution ducts enter the pressurized area, there are ground and ram air connections. Check valves make sure that there is no back- flow into the packs. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 18 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING AIR CONDITIONING SCHEMATIC ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 19 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DESCRIPTION FLIGHT DECK SUPPLY Air supplied to the flight deck is distributed through ducts which run along the left-hand side of the cabin under floor area. These ducts then form a loop to supply the following outlets and areas: The raiser will direct air to the rear ceiling outlets, from the main and the cross feed supply, air is directed to the side windows The front section of the distribution loop provides display ventilation through the piccolo duct. The pilot and first officer positions have handle-actuated butterfly valves that provide air for foot warming or cooling. Normally 60% of the mixed air from the left side ECU (Environmental Control Unit) goes to the cockpit and 40% goes to the passenger cabin through the mixing manifold (H-duct). Air passages located in the cockpit floor, under the pilots seats, lateral consoles, and the control column opening let the air return to the re circulation fans and to the aircraft outflow and pressure relief valves. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 20 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING AIR SUPPLY TO THE FLIGHT DECK ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 21 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CABIN AIR DISTRIBUTION SYSTEM The cabin air distribution system starts at the mixer duct. From this point the conditioned air is distributed to the gasper system, and to the front and rear passenger cabin sections. Ducts from the mixer duct direct air to the raisers and to the upper plenums. In the gasper system the air exits through the individual outlets above the passenger seats. For the main distribution system, the air exits above and below the overhead bins. Return air passes to the under floor areas through "DADO" panels located just above the floor on the fuselage side panels. TRAINING INFORMATION POINTS The passenger cabin distribution ducts are installed in the aircraft with tiedown straps. During removal/installation procedures you must use an appropriate tool to install and tension the tie-down straps that attach the cabin distribution ducts to the adjacent components and structure supports. The ducts are made of composite material. If you do not apply the correct tension to the tie-down straps, damage to the ducts might occur. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 22 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CABIN AIR DISTRIBUTION SYSTEM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 23 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING GASPER VENTILATION SYSTEM The gasper ventilation system is supplied by air flowing from the mix manifold through the gasper check valve. The check valve allows air flow to the front and rear gasper ducts, and through the gasper plenum to the gasper outlets. TRAINING INFORMATION POINTS Caution: TO PREVENT DAMAGE TO THE AIR CONDITIONING SYSTEM COMPONENTS, APPLY THE ELECTRICAL POWER BEFORE YOU APPLY THE PNEUMATIC POWER AND REMOVE THE PNEUMATIC POWER BEFORE YOU REMOVE THE ELECTRICAL POWER. The gasper ducts are installed in the aircraft with tie-down straps. During removal/installation procedures you must use an appropriate tool to install and tension the tie-down straps that attach the gasper ducts to the adjacent components and structure supports. The ducts are made of composite material. If you do not apply the correct tension to the tie-down straps, damage to the ducts can occur. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 24 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING GASPER VENTILATION SYSTEM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 25 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING RECIRCULATION SYSTEM Re circulation of the cabin air is controlled by two re circulation fans. The fans draw air from the re circulation bay through glass-fibre filter elements and direct the air back to the mixer duct. The re circulation fans are single-speed fans driven by three-phase 115/ 200V AC motors. The motors contain internal thermal protection circuits to shut down the fan in case of an over temperature condition. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 26 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CABIN AIR RE CIRCULATION DIAGRAM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 27 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING RAM AIR VENTILATION SYSTEM The ram air ventilation system allows outside ambient air to enter the flight deck and passenger compartment when the air conditioning packs are shut down. The system is normally not actuated when packs are operating, and ram air is passing through the heat exchangers to provide duct cooling. The ram air system includes a ram air valve installed in the left ram air inlet duct, and ram air check valve installed in the right ram air duct. The ram air ventilation valve is a butterfly valve powered by 28 VDC. Micro switches are provided for position indication. The manual override feature allows manual opening and closing of the valve. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 28 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING RAM AIR VENTILATION SYSTEM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 29 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ATA 21-29 LOW PRESSURE GROUND SUPPLY The low pressure ground supply consists of an air conditioning subsystem built to receive conditioned air from a ground cart. The LP (Low Pressure) ground connection port, ducts and valves are located in the wing-to-fuselage fairing forward panel area. Two small ducts connect the LP ground connection port (nipple) to the aircraft air conditioning pack outlet ducts. Two check valves prevent the air from the air conditioning packs from leaking to the nipple in normal operation. TRAINING INFORMATION POINTS Warning: DO NOT TOUCH THE AIR-CYCLE MACHINE OR ITS COMPONENTS IMMEDIATELY AFTER THE OPERATION STOPS. INJURIES CAN OCCUR TO YOU BECAUSE OF THE HIGH TEMPERATURE. Warning: STAY AT A SAFE DISTANCE FROM THE ENGINE AIR INTAKE AND EXHAUST AREAS DURING THE START AND GROUND OPERATIONS. THESE AREAS ARE DANGEROUS. IF YOU STAY NEAR THEM, INJURIES CAN OCCUR TO YOU. LP ground connection ducts: connect the nipple to the pack outlet ducts and conduct the airflow from the external source. LP ground connection check valves: are five inch diameter twin petal check valves, which are located in the low pressure ground connection ducts. The two LP ground check valves, one for each duct, prevent LP air from exiting the aircraft through the LP ground connection port, when the ECS (Environmental Control System) packs are in use. The conditioned air coming from the ground cart through the nipple, ducts and the check valves goes into the pack outlet ducts to the aircraft distribution system. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 30 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING LOW PRESSURE SUPPLY ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 31 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING COMPONENTS DISTRIBUTION DUCTS FUSELAGE DRAIN VALVE The distribution duct system has the following main sections: mixer duct, cockpit distribution ducts, cabin front zone distribution ducts and cabin rear distribution ducts. The valve assembly consists of a Valve retainer that is fastened to the inner fuselage wall. A valve housing is inserted (or removed) through this hole from the aircraft exterior. The valve housing consists of a pre- assembled valve, which is made of piston-like reciprocating cylinder, a helical compression spring and an aperture-retaining cap. The ducts are made of composite material and are protected by adhesive tape to retain thermal energy. When the valve is in the OPEN position, collected condensed water (or whatever other fluid inside the fuselage) and air are free to flow overboard through cutouts in the valve housing, and out the open valve (between the upwardly biased valve member and valve seat on the inside surface of the bottom of the valve housing). The ducts are designed to handle temperatures from -40∞C to +70∞C. (8) Duct connections are elastomeric sleeves or metal clamps, with ports provided to drain condensation. Training Information Points FUSELAGE THERMAL ACOUSTIC INSULATION Caution: This material has the following functions: Reduce heat transmissions through fuselage for thermal comfort. Noise attenuation through fuselage. It is made of fiberglass and non-hygroscopic blankets. The blankets are involved by a thin, film for mechanical protection and better workmanship, forming thus a bag. Each bag has a breather, always facing down, to allow for pressure equalization during aircraft operation. Placement of breather intends to prevent water penetration into the bags. TO PREVENT DAMAGE TO THE AIR CONDITIONING SYSTEM COMPONENTS, APPLY THE ELECTRICAL POWER BEFORE YOU APPLY THE PNEUMATIC POWER AND REMOVE THE PNEUMATIC POWER BEFORE YOU REMOVE THE ELECTRICAL POWER. The cockpit ducts are installed in the aircraft with tie-down straps. During removal/installation procedures you must use an appropriate tool to install and tension the tie-down straps that attach the ducts to the adjacent components and structure supports. The ducts are made of composite material. If you do not apply the correct tension to the tie-down straps, the ducts might be damaged. The pressurized zone is internally insulated with this material, except in the zones where frame systems installations required differently and in some case the insulation is not installed for specific purposes (for example E-Bays). The lower part of electronic bays has a non-insulated area of 41.4ft2 for the mid E-Bay, 42.3ft2 for the forward E-Bay and 15ft2 for the aft E-Bay where neither acoustic nor thermal requirements is needed for occupants. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 32 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING THE DISTRIBUTION DUCT SYSTEM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 33 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MIXER The mixer is a composite component, which has no valves or moving part inside. It has the following input ducts; Flow from PACK 1 Flow from PACK 2 Pack flow is controlled by the AMS controlled, modulating the flow control valve. Flow and therefore valve position based on available bleed source and users. Flow from RECIRC FAN 1 Flow from RECIRC FAN 2 Fans are normally selected on for the flight. Can be selected of or in case of failure RAM AIR VALVE will automatically open and ensure cabin ventilation or in case DUMP has been selected on the Pressurization panel SMOKE REMOVAL will be initiated. The total air flow entering the flight deck, the cabin compartments and the gaspers is made up of approximately 50% fresh air and 50% re circulated air. Hot air from TRIM VALVE 1 (optional) Hot air from TRIM VALVE 2 (optional) Mixer can receive hot air from RH engine supply via TRIM VALVE 1 or 2 but never from both at the same time. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 34 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MIXER ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 35 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING RECIRCULATION FANS TRAINING INFORMATION POINTS The re circulation fan is a 7.25 in diameter single-speed mixed flow fan. Each aircraft is provided with two re circulation fans. Caution: The fan has the following features: The fan wheel is contained in a cylindrical aluminum housing. It incorporates a twin flapper check valve design to prevent flow in reverse direction. It is driven by a three-phase 115/200 VAC, 400 Hz motor. It contains an internal thermal protection circuit which is used to shut down the fan in the event of an over temperature condition. BE CAREFUL WHEN YOU DO MAINTENANCE ON THE RECIRCULATION BAY. DAMAGE TO THE RECIRCULATION AIR FILTER CAN OCCUR. Each duct-to-duct interface consists of a bead, a mating elastomeric endconnection which is an integral part of the duct and a tie-down strap. The connection is formed by sliding the elastomeric cuff over the bead and clamping the joint using the tie-down strap. There must be a distance of approximately 1.5 in between the bead and the cuff end to provide space for the correct attachment of the tie-down strap. There must be no signs of folds or wrinkles on the cuff. RECIRCULATION FAN FILTER The HEPA (High Efficiency Particulate-Air) type filters, located before the recirculation fans remove 99.999% of the bacteria and viruses produced by the passengers and airborne dust and particulates. The recirculation fan filter assembly consists of an 11.5 in diameter cylindrical glass-fiber filter element which is encased in a protective aluminum grid. The filter is mounted on a bracket in line with both the left and right circulation fans (two per aircraft). The filters cannot be bypassed and become more efficient with increased service life. During removal/installation procedures you must use an appropriate tool to install and tension the tie-down straps that attach the recirculation ducts to the adjacent components and structure supports. The ducts are made of composite material. If you do not apply the correct tension to the tie-down straps, the ducts might be damaged. The fan filter has the following features: An upper-and-lower composite flange connects the filter element and protective grid as one assembly. A rubber gasket is mounted on the lower flange to provide the sealing mechanism for installation on the aircraft. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 36 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING SMOKE DETECTOR ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 37 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING EMERGENCY RAM AIR VALVE RAM AIR CHECK VALVE The AMS controller controls the emergency ram air valve. The emergency ram-air ventilation system allows outside ambient air to enter the cockpit and passenger cabin when the air conditioning pack is shut down. The emergency ram-air check-valve is a five inch diameter twin petal check valve which is located in the right pack ram air inlet ducting. The emergency ram-air check-valve does not require electronic control. It will be open whenever the cabin ECS (Environmental Control System) cooling pack is off and the pressure in the ram air circuit is greater than cabin pressure. The valve has: Two aluminum check valve petals retained in the check valve housing by a common hinge pin; A wire retention spring used to hold the check valve petals in the closed position; A mechanical bar type stop. The emergency ram air valve is commanded open whenever the ram air valve is commanded open whenever both packs are commanded off or failed off, the aircraft is below 25000 ft and is weight off wheels. During smoke removal both packs will be shut off, and therefore the ram air valve and the ram air check valve will open. EICAS advisory and CMC messages are provided if one or more of the valves fail closed. The synoptic page shows the ram air valve in green when the valve is open, and in red when the ram air valve is closed. The emergency ram-air valve is a 5-inch diameter electrically-actuated butterfly valve. The valve is opened and closed by a 28 VDC (Volt Direct Current) electric actuator which rotates a splined butterfly shaft. This shutoff valve also contains a manual actuation lever which can be used to manually position the valve in the event of actuator electrical failure. The valve and actuator require no lubrication or servicing. The emergency ram-air valve is tested each time the AMS (Air Management System) controller is powered up. The AMS controller commands the valve full open and then closed. This valve has position switch feedback for position indication. The EICAS (Engine Indicating and Crew Alerting System) message RAM AIR FAULT will be displayed if the valve has failed in the closed position. The emergency ram-air valve actuator moves the emergency ram-air valve through a movable arm. When ram air flows to the heat exchanger, the flow to the ram air duct closes, and vice-versa. The electric actuator utilizes a 28 VDC motor which acts on a worm type gear and wheel assembly to rotate the valve shaft. The actuator contains two sets of micro switches which are used for valve open/ close indication and actuator over travel protection. The linear actuator electrical travel is limited by two limit switches, one in the retracted position and the other in the extended position. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 38 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING EMERGENCY RAM AIR VALVE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 39 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OPERATION RECIRCULATION FANS The recirculation fans are controlled by the Air Management System controller, through the selector switch located in the cockpit. They are powered by the Secondary Power Distribution Assembly2. During single pack condition: In flight, only with left pack is OFF AND the aircraft is in the AIR AND airspeed > 50 knots (left fan only), the left recirculation fan should be commanded OFF On ground, only with left pack is OFF AND the aircraft is on the ground AND right pack is ON, the left recirculation fans should be commanded OFF The fans are commanded ON when the RECIRC switch is in the AUTO position (latched). Exceptions are: Both fans will be commanded OFF if the Cabin Pressure ControlSystem dump switch is latched. Both fans will be commanded OFF if smoke is detected in the recirculation bay by the recirculation-bay smoke detector or the smoke detected signal is invalid or the smoke detector is failed. The AMS controller will generate an EICAS message RECIRC SMOKE when the smoke alarm signal is received for the recirculation-bay smoke detector. Both fans will be commanded OFF if the cargo-bay fire signal is true or invalid; Both fans will be commanded OFF as a function of ambient temperature and altitude while on the ground, during the pull-up mode, when the APU is supplying bleed air as the left bleed source; The fans will also be commanded OFF under over temperature conditions. The right recirculation fan may remain on when the cabin pack is OFF On the ECS synoptic page the re circulation fans will be indicated in green when they operate and in red if they are switched off. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 40 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING RECIRCULATION FANS ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 41 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING RAM AIR VALVE The emergency ram-air valve is commanded open by the AMS controller when both cooling packs are commanded or failed off and the aircraft altitude is less than 25000 ft. When the emergency ram-air valve is commanded open, fresh air entering the left ram air inlet flows through the valve, bypassing the air conditioning pack, to provide ventilation for the flight deck. This provides additional fresh air ventilation. On the ground, the valve will be closed if the aircraft speed is less than 50 kts. In order to avoid unnecessary message, the emergency ram-air valve is also commanded closed when the aircraft is in Ground Service Mode. The ram-air ventilation system is also used for emergency cockpit smoke removal. If there is evidence of smoke in the cockpit, the flight crew will latch the cabin pressure-control-system dump-switch. Upon receipt of the dump switch signal the AMS controller will command both the left and right pack flow control valves closed. The left and right recirculation fans will be commanded off to eliminate recirculation of cockpit air flow. The forward electronics compartment backup ventilation fan will be commanded on to increase ventilation flow through the cockpit area. The emergency ram-air valve will be commanded open. These actions will permit the flow of fresh air through the emergency ram-air valve to clear smoke in the cockpit area. Fresh air will also flow through the emergency ram-air check-valve to equalize pressure in the mixing duct and provide emergency ventilation for the passenger cabin zones. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 42 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING RAM AIR VALVE OPERATION ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 43 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING SMOKE REMOVAL The ram ventilation system is also used for cockpit smoke removal. Flight crew will depress cockpit DUMP switch as an emergency procedure for cockpit smoke removal. When the dump switch is depressed the CPCS (Cabin Pressure Control-System) will depressurize the cabin at a rate of 2000 ft/min. The AMS (Air Management System) controller will then shut down both air conditioning packs, turn off both re circulation fans and open the emergency ram air check valve. This will allow fresh air to flow through the cockpit. TRAINING INFORMATION POINTS Warning: DO NOT GO NEAR THE OPENING OF THE HIGHPRESSURE GROUND CONNECTOR DUCT WHEN YOU PRESSURIZE THE PNEUMATIC DUCT. THE BLEED AIR THAT COMES OUT OF THE OPENING CAN CAUSE INJURY TO PERSONS. Warning: DO NOT TOUCH THE DUCTS OR COMPONENTS OF THE AIR BLEED SYSTEM IMMEDIATELY AFTER THE SYSTEM STOPS ITS OPERATION. THE HIGH AIR TEMPERATURE CAN CAUSE INJURY TO PERSONS. Caution: MAKE SURE THAT THE RAM AIR INLET DUCTS AND THE NACA SCOOP DUCTS ARE ALIGNED. IF NOT, DAMAGE TO THE BELLOWS CAN OCCUR. There must be no twists or bends on the bellows. In addition to that, the ducts and bellows must be aligned with the adjacent components. This is to avoid damage to the ducts installation and to the air conditioning packs during operation. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 44 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING SMOKE REMOVAL ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 45 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DIAGNOSTIC AND TESTS The recirculation bay smoke detector is tested by the AMS controller using the recirculation bay smoke detectors automated BIT function. The BIT is performed whenever the AMS controller is powered up (after shut down) and two minutes after each aircraft landing. The AMS controller sends a test signal to the recirculation bay smoke detector that causes the recirculation bay smoke detector to perform an internal BIT: The recirculation bay smoke detector BIT sequence includes fan current monitoring and a test of the smoke detecting and alarm capability. If the recirculation bay smoke detector does not pass the BIT sequence the AMS controller will generate the EICAS message RECIRC SMK DET FAIL to alert the flight crew that the recirculation bay smoke detector is inoperative. In addition, continuous BIT monitors sets the RECIRC SMK DET FAIL EICAS Message if the recirculation bay smoke detector has been failed due to an electrical power supply lost (open circuit) or Smoke Detected signal is not valid for 10 or more seconds. The emergency ram air ventilation valve is tested each time the AMS controller is powered up. The AMS controller commands the valve full OPEN and then CLOSED. This valve has position switch feedback for position indication. EICAS message RAM AIR FAULT will be displayed if the valve has failed in the CLOSED position. System reset System reset can be performed with the channel transfer preconditions. Reset will be only successful when there are no active fault conditions. EICAS and Maintenance Messeges should be checked in ATA 36,21,30 and 35 chapters. Smoke test IBIT Test can be performed when , A/C is WONW, Channel in control and smoke detector signal is valid. Only on A/C with animal bay optional fan and shut off valve installed. RECIRC fan parameters Beside recirc fan status and parameters the page also allows to view emrg ram air valve status and discrete inputs from cockpit switchesRAM AIR VALVE IBIT can be performed whem WONW, channel in control, Aircraft speed below 50knots conditions are true and Pack is selected off- Channel Transfer During the test the valve will be commanded open and closed. Channel status and therefore channel transfer is continuously monitored. AMS status page Preconditions are: WON W Airspeed below 50knots Channel not in control already Allows to view FADEC commands, AMS system valves positions and APU bleed valve position. Please do not forget and it is valid for all IBITS: during test AMM II operational or functional test instructions has to be followed. Beside all above the channel should be healthy inclusive no fault on processor, control input output and motor drive card. Also important and condition no pressure sensor failure. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 46 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CMC TESTS ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 47 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ATA 21-26 AVIONICS COMPARTMENT INTRODUCTION, DESCRIPTION The avionics compartment ventilation system incorporates forward and middle compartments. The main function of the forward avionics compartment ventilation system is to provide a reliable ventilation source that will maintain a safe temperature in the forward avionics compartment. The forward avionics compartment ventilation system utilizes three 4.5 in diameter single- speed fans to pull air from the avionics compartment to the re circulation area. The fans contain an integral check valve to prevent reverse flow when the fan is not in use. The fans are connected in parallel to a common supply duct. An electronic flow sensor is mounted in the main ventilation supply duct and is used for system health monitoring. The main function of the middle avionics compartment ventilation system is to provide a reliable ventilation source that will maintain a safe temperature in the middle avionics compartment. The middle avionics compartment ventilation system utilizes two single-speed fans and one 2- speed fan to pull air from the middle avionics compartment to the re circulation area. The fans contain an integral check valve to prevent reverse flow when the fan is not in use. The fans are connected in parallel to a common distribution duct. An electronic flow sensor is mounted in the main ventilation duct and is used for system health monitoring. The aft avionics compartment does not have a dedicated fan. A duct is routed from the aft avionics compartment to the middle avionics compartment inlet duct. This duct draws air from the passenger cabin through the aft avionicscompartment area using the middle avionics compartment fan as a driven source. This duct improves the performance of the aft avionics- compartment ventilation and also the smoke containment in that area. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 48 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING FORWARD ELECTRONIC BAY ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 49 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING COMPONENTS FORWARD AVIONICS COMPARTMENT FAN The forward avionics compartment fan is a 4.5 in diameter single-speed axial flow fan, weighing 4.5 lb with an overall length of 6.5 in,and produces a volumetric flow rate of 224 ft3/min. The fan wheel is contained in a cylindrical aluminium housing which incorporates a twin flapper check valve design to prevent flow in the reverse direction. The fan is driven by a 3 - phase 115/200 VAC 400 Hz motor. The motor contains an internal thermal protection circuit which is used to shut down the fan in the event of an over temperature condition. Maintenance of the fan is on condition. FORWARD AVIONICS COMPARTMENT VENTILATION DUCTS A common supply duct has three fans that are connected in parallel to it. An electronic flow sensor is mounted in the main ventilation supply duct and is used for system health monitoring. The ducts are made of composite materials. FORWARD AVIONICS COMPARTMENT FLOW SENSOR The forward avionics compartment flow sensor consists of a CRH (Constant Resistance Heating) element and a platinum RTD (Resistance Temperature Device) mounted in a stainless steel probe. A constant voltage is applied to heat the CRH element to a known value. The CRH element temperature and electrical resistance will change with variations in mass flow rate. The RTD element measures the ambient air temperature in the duct. The AMS (Air Management System) controller uses the CRH element resistance changes, along with the ambient temperature from the RTD element to calculate a local mass flow rate in the duct. If the local mass flow rate falls below a certain level (indicating no duct flow), the AMS controller, through the EICAS (Engine Indicating and Crew Alerting System), alerts the flight crew of a low flow condition. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 50 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING FAN FAILURES ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 51 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MIDDLE AVIONICS BAY FANS The centre avionics bay ventilation system contains fans that pull air from the passenger cabin under floor areas through the centre avionics compartment, and exhaust the air into the re circulation bay. The motor contains an internal thermal protection circuit which is used to shut down the fan in the event of overtemperature. Maintenance of the fan is on condition. The two single-speed fans and one two-speed fan are connected in parallel to a common distribution duct, and contain integral check valves in order to prevent reverse flow. A sensor mounted in the fan supply duct provides system health monitoring. MIDDLE AVIONICS COMPARTMENT FLOW SENSOR The middle avionics compartment flow sensor consists of a CRH element and a platinum RTD element collocated in a stainless steel probe. A constant voltage is applied to heat the CRH element to a known value. MIDDLE AVIONICS COMPARTMENT FAN The middle avionics compartment single-speed fan is a 5.25 in diameter axial flow fan, weighing 6.1 lb with an overall length of 7.25 in, and produces a volumetric flow rate of 547 ft3/min. The fan wheel is contained in a cylindrical aluminum housing which incorporates a twin flapper check valve design to prevent flow in the reverse direction. The fan is driven by a 3-phase 115/200 VAC 400 Hz motor. The CRH elements temperature and electrical resistance will change with variations in mass flow rate. The RTD element measures the ambient air temperature in the duct. The AMS controller uses the CRH element resistance changes, along with the ambient temperature from the RTD element to calculate a local mass flow rate in the duct. If the local mass flow rate falls below a certain level (indicating no duct flow) the AMS controller will alert the flight crew of a low flow condition using the EICAS The motor contains an internal thermal protection circuit which is used to shut down the fan in the event of overtemperature. Maintenance of the fan is on condition. MIDDLE AVIONICS COMPARTMENT FAN (2-SPEED) The middle avionics compartment 2-speed fan is a 5.25 in diameter axial flow fan, weighing 6.7 lb with an overall length of 7.25 in, and produces a volumetric flow rate of 370 ft3/min in low speed operation and 547 ft3/min in high speed operation. The fan wheel is contained in a cylindrical aluminum housing which incorporates a twin flapper check valve design to prevent flow in the reverse direction. The fan is driven by a 3-phase 115/200 VAC 400 Hz motor. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 52 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING FAN FAILURES ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 53 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OPERATION FORWARD AVIONIC COMPARTMENT The forward avionics compartment architecture consists of one flow sensor, two fans for normal operation and one emergency backup fan. During normal system operation, the left fan operates and the right and the emergency backup fan (center) remain in standby mode. If there is a failure of the left fan, the right fan is commanded on. If there are failures of both left and right fans, the emergency fan (center) is commanded on. This also turns on, in low speed mode, the emergency backup fan in the middle avionics compartment. The system utilizes an electronic flow sensor, installed on the ventilation duct, to detect a low flow condition. The low flow sensor switch set point is adjusted for the flow of one fan in the forward avionics compartment. Hot Day Ground Operation For ground operation with the ambient temperature above 86 Deg F (30 Deg C) both Fan 1 and Fan 2 will be turned on to meet a two fan flow threshold. Fan 3 will be in standby mode and will be turned on only if Fan 1 or Fan 2 has failed. The FWD E-BAY FANS FAIL messages shows on the EICAS if: the two fans for normal operation (left and right) are failed AND the aircraft is on ground, OR; The emergency backup fan is failed AND the aircraft is on ground, OR; The flow sensor is failed AND the aircraft is on ground, OR; The flow sensor indicates that there is NOT at least one fan operating (low-flow sensor reading),OR; All three fans are failed AND the aircraft is in flight. A single fan failure results in only one CMC (Central Maintenance Computer) message. It is important to note that the forward avionics compartment ventilation system can maintain adequate compartment cooling with one fan operational. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 54 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING FORWARD ELECTRONIC FAN OPERATION ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 55 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MIDDLE AVIONICS COMPARTMENT The middle avionics compartment architecture consists of one flow sensor, two single-speed fans for normal operation and one 2-speed emergency backup fan. A single fan failure will result in only one CMC message. It is important to note that the middle avionics compartment ventilation system can maintain adequate compartment cooling with one fan operational. During normal system operation, fan 1 (left) operates and fan 2 (center) and the emergency backup fan (right) remain in standby mode. If there is a failure of fan 1, fan 2 is commanded on. If there are failures of both fan 1 and 2, the emergency backup fan is commanded on in high speed mode. The system utilizes an electronic flow sensor, installed in the ventilation duct, to detect a low flow condition. The low flow sensor switch set point is adjusted for the flow of one fan in the middle avionics compartment. Note: Hot Day Ground Operation For ground operation with the ambient temperature above 86 Deg F (30 Deg C) both Fan 1 and Fan 2 will be turned on to meet a two fan flow threshold. When the RAT is deployed, the middle avionics compartment emergency fan uses the low speed setting to minimize power consumption. TRAINING INFORMATION POINTS The avionics compartment ducts are installed in the aircraft with tie-down straps. For removal/installation procedures, you must use an appropriate tool to install and tension the tie-down straps that attach the avionics compartment ducts to the adjacent components and structure supports. The ducts are made of composite material. Damage to them can occur if you do not apply the correct tension to the tie-down straps. Fan 3 will be in standby mode and will be turned on (high speed) only if Fan 1 or Fan 2 has failed. The CENTER E-BAY FANS FAIL message shows on the EICAS if: The two fans for normal operation (left and center) are failed AND the aircraft is on ground, OR; The emergency backup fan (right) is failed AND the aircraft is on ground, OR; The flow sensor is failed AND the aircraft is on ground, OR; The flow sensor indicates that there is NOT at least one fan operating (low-flow sensor reading), OR; All three fans are failed, the aircraft is in flight AND the RAT (Ram Air Turbine) is not deployed. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 56 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MIDDLE ELECTRONIC BAY ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 57 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DIAGNOSTIC AND TEST E-Bay fans in the forward and mid E-Bays are continuously monitored by the AMS controller using load current monitoring and overheat detection. E-Bay flow sensors are also used to verify that there is adequate airflow in the EBay ventilation duct. In addition, the E-Bay fans in the forward and mid EBays are checked for proper operation each time the AMS controller is powered up, and two minutes after each aircraft landing. This BIT is automatically initiated by the AMS controller to ensure that each fan is operational and is capable of providing adequate airflow. This test will detect fan failures that are not detected by continuous load current monitoring. During this power up/ post landing fan operational test the AMS controller commands only one E-Bay fan on in each E-Bay and uses the E-Bay flow sensor to verify that the fan is operating. This test is performed on each fan. If all the fans in a common electronics bay (forward or mid) do not meet the minimum flow requirements of this test, the AMS controller will determine that the E-Bay flow sensor in the associated bay has failed. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 58 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DIAGNOSTIC AND TEST ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 59 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING FORWARD CARGO COMPARTMENT VENTILATION INTRODUCTION, DESCRIPTION The forward cargo compartment ventilation system draws air from the cabin underfloor area by means of a single fan, and exhaust the air through the cargo compartment shut-off valve into the re circulation bay area to the outflow valve. During normal operation the fan is operating, and the shut-off valve is open and monitored by the AMS controller. In case of fire, the fan is turned off and the valve is immediately closed. A check valve ensures that there is no airflow toward the passenger compartment. Note: This cargo compartment ventilation system is optional. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 60 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING FORWARD CARGO COMPARTMENT ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 61 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING COMPONENTS FORWARD CARGO COMPARTMENT FAN The forward cargo compartment fan is a 4.5 in diameter single-speed axial flow fan. The fan is driven by a 3-phase 115/200 VAC 400 Hz motor. The motor contains an internal thermal protection circuit which is used to shut down the fan in the event of an over temperature condition. The fan wheel is contained in a cylindrical aluminium housing. FORWARD CARGO COMPARTMENT CHECK VALVE The forward cargo compartment check valve is a 3.5 in diameter dual- flapper check valve. The valve is mounted downstream of the forward cargo ventilation fan in the forward cargo compartment supply duct. FORWARD CARGO COMPARTMENT SHUT OFF VALVE The forward cargo compartment shut off valve is a 3.5 in diameter pneumatic actuated valve. The valve is mounted in the forward cargo ventilation system outlet duct and utilizes a 28 VDC (Volt Direct Current) solenoid for open/close function. FORWARD CARGO COMPARTMENT VENTILATION DUCTS Air is distributed to the forward cargo compartment by underfloor ducts, on the LH side of the cargo compartment (upstream and downstream of the fan) and one in the right aft bulkhead of the cargo compartment. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 62 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING FWD CARGO COMPARTMENT ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 63 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OPERATION TRAINING INFORMATION POINTS The function of the forward-cargo-compartment ventilation system is to provide adequate airflow in the cargo compartment to support the transportation of live animals. The AMS controller determines if the aircraft is equipped with the forward-cargo-compartment ventilation system via the aircraft configuration inputs. During all normal aircraft operating conditions, the forward-cargo-compartment ventilation fan is commanded on and the forward-cargo-compartment exhaust valve is commanded open. The fan is commanded off and the exhaust valve is commanded closed in response to a fire in the cargo compartment as reported by the cargo compartment fire extinguishing system Warning: TO CLOSE THE CARGO DOOR, DO NOT LET IT FALL FREELY TO PREVENT DAMAGE TO MATERIAL AND INJURY TO PERSONS. The cargo compartment ducts are installed in the aircraft with tiedown straps. On removal/installation procedures you must use an appropriate tool to install and tension the tie-down straps that attach the cargo compartment ducts to the adjacent components and structure supports. The ducts are made of composite material. Damage to them can occur if you do not apply the correct tension to the tie-down straps. The CRG FWD VENT FAIL message will display on the EICAS (Engine Indicating and Crew Alerting System) any time the forward cargocompartment fan is failed ON or the forward cargo-compartment shutoff valve is failed OPEN. It is also required that there is an associated forward-cargocompartment fire signal, or smoke detected, or either one of these signals invalid to set the message. This message is intended to inform the crew that a fire in the cargo compartment may possibly not be able to be extinguished (inability to retain Halon). The CRG FWD VENT FAIL message will also be displayed on the ground if the fan is failed OFF or the shutoff valve is failed CLOSED. This will allow the crew to remove the live cargo prior to the flight. It is important to highlight that, in this condition, the CRG FWD VENT FAIL message will not be latched and it will be cleared once the conditions are corrected. For any other condition, the CRG FWD VENT FAIL message is latched. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 64 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OPERATING LOGIC ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 65 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DIAGNOSTIC AND TEST The forward cargo compartment shutoff valve is tested each time the AMS controller is powered up. The AMS controller commands the valve full OPEN and then CLOSED. This valve has position switch feedback for position indication. EICAS message CRG FWD VENT FAIL will be displayed if the valve has failed in the OPEN position. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 66 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DIAGNOSTIC AND TEST ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 67 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ELECTRONIC RACK VENTILATION SYSTEM INTRODUCTION The electronic-equipment-rack ventilation system provides airflow for cooling of nonessential electronic equipment installed in a dedicated equipment rack. In the event of smoke resulting from failure of electronic equipment, the rack ventilation system provides means to discharge the smoke overboard.The electronic-equipment-rack is installed in the lower compartment, behind the aft partition of the aft cargo compartment. The shelves of the rack contain the several units required for the proper functioning of the in-flight entertainment system. Some of these units require forced ventilation, supplied by a dedicated and independent ventilation system, in order to minimize effects on air-conditioning distribution, pressurization and smoke management. The rack ventilation system comprises: One electric-motor-driven fan An overboard air-discharge port Two electric-motor-driven air shutoff valves One smoke detector One airflow switch Three airflow-limiting venturis Associated air collection and conveyance ducts. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 68 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ELECTRONIC RACK VENTILATION LAYOUT ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 69 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DESCRIPTION Plenums and ducts collect air from the rack and discharge it overboard forced by a fan (on-ground) or by cabin differential pressure through a venturi (inflight). The discharge duct system splits into three branches and later joins together to form a common exhaust duct. The branches are called: ground line, vent line and bypass line. The ground line has an electric- motor-driven air shutoff valve. The ground valve is always open on ground when the fan is ON. It closes in flight to prevent excessive flow leakage. The vent line is the main path for the ventilation flow in flight. It contains an electric-motor-driven air shutoff valve and a flow limiting venturi. The vent valve is always open, except under certain conditions when evacuation of smoke generated in other aircraft regions could be affected. The bypass line is always open to ensure a minimum amount of cooling flow, whenever the vent valve is closed. It contains a flow-limiting device to prevent excessive flow leakage that could jeopardize the smoke containment in other areas of the airplane. An additional venturi is installed in the common exhaust duct, downstream of the valves. Its purpose is to minimize the impact on the cabin pressurization control system. The venturi is sized to ensure that cabin pressure remains below the “HI CABIN” indication set point, even in single-pack mode with the ground valve failed open. There is also an airflow switch used to detect loss of cooling flow. Exhaust air or smoke is captured from the upper part of the rack and discharged overboard through a dedicated fuselage port located at the RH (Right-Hand) side, aft part of the aircraft fuselage, opposite to the vacuum and waste fuselage port. The cooling air is enclosed and does not enter the cargo compartment. It is totally exhausted overboard on the ground and in flight. Control function, fault indication, and testing of the electronic-equipment-rack ventilation system operation is accomplished by dedicated electrical circuits that are independent of other aircraft control circuits. A smoke detector is installed in the rack ventilation duct. In the event of smoke resulting from failure of electronic equipment, the smoke detector generates an EICAS (Engine Indicating and Crew Alerting System) message for the crew, and automatically shuts down the electronic equipment rack. The pilot is also required to manually shut off the rack as an added precaution. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 70 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING COMPONENTS VIEW ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 71 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING COMPONENTS AIRFLOW SWITCH The airflow switch is a flow-sensing unit that uses thermal dispersion technology where two platinum RTD (Resistance Temperature Detector) are located in the airflow element. It is a solid state unit powered by 28 VDC (Volt Direct Current). The airflow switch is installed in the rack exhaust-air discharge-line (upstream the smoke detector) and has the function of protecting the electronic equipment from an overheat condition due to lack of air cooling. It is only deactivated (without shutting down the system) during an aircraft single pack operation. At this time, both shutoff valves are closed and the minimum required airflow to cool the rack is obtained through the bypass line. FAN The function of the fan (brushless type) is to provide ventilation to the electronic equipment rack when the aircraft is on the ground. The fan draws air from the rack and discharges it overboard through the ground and vent shutoff valves. The ventilation fan is of the 4.5 in diameter, single speed and axial flow type. It is driven by a 3-phase 115/200 VAC/ 400 Hz motor. The motor contains an internal thermal protection circuit which is used to shut down the fan in the event of an overtemperature condition. The fan wheel is installed in a cylindrical aluminium housing. The fan is attached to a structure support and stays on aircraft during the rack removal. A rubber flexible sleeve makes the connection to the exhaust duct of the rack and absorbs excessive vibration. VENTILATION DUCTS The air/smoke extracted from the electronic equipment rack passes the fan and reaches the shutoff valves through a set of 4.5 in diameter aluminium ducts. Then the air/smoke is directed to the atmosphere through a vent duct and a fuselage port located at the right hand side of the fuselage, behind the aft avionics compartment. ISSUE 1, 24 Sep 2014 The 3 in diameter vent duct is also made of aluminium and runs from the shutoff valves to a 2.5 in diameter vent port at the right side of the fuselage skin. The vent duct has an upward loop to avoid de-icing fluids ingestion and water ingression during ditching. A venturi in the overboard exhaust duct prevents excess loss of cabin pressure in case of a duct failure. A duct bypasses the ground shutoff valve and prevents excessive loss of cabin pressure in case of duct failure. It also keeps a minimum required airflow for the rack cooling when the vent shutoff valve is closed due to smoke detection in the air conditioning system (basically in the recirculation bay), single pack operation or for dispatch ability when one pack is inoperative. SHUTOFF VALVES The ground and vent shutoff valves are identical. They are attached to the aft floor panel (aft avionics compartment) close to the aft pressure bulkhead. These valves are of the electric-motor-driven butterfly type and consists of two major subassemblies: an actuator and a butterfly valve. The actuator assembly controls the position of the valve. It comprises of an electric motor, a gear train, position control/indication switches, an electrical connector, and a housing. The actuator moves the valve to each of the two desired discrete positions, fully closed and fully open, based on command from the aircraft. The motor is a precision, aircraft-quality, brush-type 28 VDC permanent magnet. The valves contain limit switches that control the motor and provide valve position indication. FOR TRAINING PURPOSES ONLY Page: 72 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING COMPONENTS VIEW ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 73 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OPERATION During ground operation, the fan draws the air from the underflow compartment through the rack equipment and exhausts it to the outside. The ground valve and vent valve are open. The airflow switch monitors the airflow rate to ensure adequate cooling capacity for the electronic units. During takeoff, when the TLA (Thrust Lever Angle) is moved above 60 degrees and the parking brake is released, the ventilation system is automatically configured to the flight mode. During descent and landing, this configuration will remain until 20 s after touchdown, when the system reverts back to ground mode. In the flight mode, the ground valve is closed and the fan is shut off. The vent valve and the bypass line are open. The pressure difference between the cabin and the outside air serves as the driver for cabin air to flow through the rack ventilation system discharging the exhaust air to the outside. The airflow switch monitors the airflow rate to ensure adequate cooling capacity for the electronic units. Its signal is inhibited during flight. FAN During normal ground operation, the fan is commanded ON and both shutoff valves are commanded OPEN. After takeoff or in response to a smoke detection on ground, the fan is commanded OFF and the ground shutoff valve is commanded CLOSED. The fan operates on the ground even when only the ground service power bus is available, in order to ventilate the Wireless Aircraft Unit (WAU). ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 74 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OPERATION ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 75 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING GROUND SHUTOFF VALVE AIR FLOW SWITCH When the aircraft is on the ground, the normal rack ventilation system operation uses the ambient air from the under-floor compartment. A dedicated electric fan draws this ambient air through the rack equipments and discharge it overboard through the ground shutoff valve. The airflow switch is a unit installed in the rack exhaust line, upstream of the smoke detector. The function of the airflow switch is to protect the rack equipments from an overheat due to a lack of air cooling. The ground shutoff valve is commanded to the open position after the following conditions have been achieved: TLA < 60∞ Time delay after WOW (Weight-on-Wheels) - 20s Parking brake switch - ON Rack power - ON At the same time, the ground shutoff valve is commanded OPEN, the fan is commanded ON. Upon detection, the signal from the switch is sent via relays to the SPDA (Secondary Power Distribution Assembly), which then automatically removes the electrical power to the rack to protect the LRU (Line Replaceable Units). Logic is built into the SPDA to ignore the transient conditions during electronic-equipment-rack start up on the ground or the fan activation soon after touch down (during landing, when the ventilation flow falls below the flow switch “LOW FLOW” set point). This inhibition is 70 s at system start-up and 40 s after touch down. The flow switch signal is also inhibited in flight. The ground shutoff valve is commanded to the closed position after the following conditions have been achieved: TLA > 60∞ Parking brake switch - OFF At this time, the electrical power is removed from the fan. A bypass line around the ground shutoff valve allows a minimum airflow required for the rack equipment cooling when the aircraft is dispatched with single pack operation and the vent shutoff valve is in the closed position. VENT SHUTOFF VALVE The vent shutoff valve is normally in the OPEN position. In flight conditions, the cabin differential pressure draws air from the rack and discharge it overboard through the vent shutoff valve and the fuselage port. The vent shutoff valve is commanded to the closed position after the following conditions have been achieved: single pack operation smoke detected in the recirculation bay ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 76 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OPERATION ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 77 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MAINTENANCE TEST PANEL The maintenance test panel is installed in the aft electronics- compartment rack on the right-hand side at the upper shelf. It provides a mean for testing the smoke detector and also to verify the operation of the shutoff valves (ground/vent). The panel also indicates failures of the smoke detector, vent shutoff valve, ground shutoff valve and rack cooling system (fan and airflow switch) through 4 LED (Light-Emitting Diode)s (amber color). These failure indications are latched in order to enable the maintenance crew to evaluate the problem on the ground. The single 3- position momentary toggle switch (with normal central position lever-lock) provides a mean for operationally checking the vent shutoff valve and the ground shutoff valve. When the aircraft is on the ground, in normal operation condition, both SOV (Shutoff Valve)s must be in the OPEN position, confirmed by the LED “OPEN” indication illuminated in green color. There are four failure indication LEDs (amber color) on the maintenance test panel: vent valve, ground valve, smoke detector (auto test) and rack cooling system (ducting, fan or airflow switch). They are intended to help the ground crew to determine which LRU needs troubleshooting. These failure indications are latched once they occur. The circuit breaker is installed to permit maintenance on the applicable LRU powered by 28VDC such as: smoke detector, airflow switch, SOVs, relays and LEDs. The operational checks are achieved by lifting the toggle switch and moving it UP (to test the vent valve) and DOWN (to test the ground valve). At this time the LED “OPEN” indication will turn OFF and after a few seconds (5-8 s) the LED “CLOSED” indication will turn ON indicating full traveling of the applicable shutoff valve. When you release the toggle switch and locks it in the central position, that will open the applicable shutoff valve and the LED “CLOSED” indication will turn OFF. Consequently, the LED “OPEN” indication will turn ON. The AMBER LEDS TEST switch (press-to-test type), when activated, will send a ground and indicate that all LEDs (amber) are operational. The other five LEDs (green) can be tested during the ground and vent valve operational checks and the smoke detector test. The smoke detector test switch allows complete testing of the smoke detection and indication system for the electronic equipment rack. When the test switch is momentarily pressed, it illuminates in white color indicating that the test has initiated. When the test is successfully completed, the LED “PASS” indication will illuminate in green color and the “IFE RACK SMOKE” caution message is displayed on the EICAS. At the same time, an aural warning activated in the cockpit. The LED RESET 2-position momentary toggle switch (with normal position lever-lock) allows the LED “FAIL” indication (amber color) to be cleared after the cause of the fault indication has been fixed. EFFECTIVITY: 190:00004-00035 EFFECTIVITY: ON ACFT 190:00039-99999 The LEDS TEST switch (press-to-test type), when activated, will send a ground and indicate that all LEDs (amber and green), except the SMK DET PASS, are operational. The SMK DET PASS LED (green) can be tested during the smoke detector test. When the test switch is held pressed longer than 10 s, the auto shutdown function is checked. In this case, the power is removed from rack components and the IFE RACK SMOKE message is displayed on EICAS. At the same time a aural warning is activated in the cockpit. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 78 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MAINTENANCE TEST PANEL OPERATION ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 79 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DIAGNOSTIC AND TEST MAINTENANCE TEST PANEL The maintenance test panel is installed in the aft electronics- compartment rack on the right-hand side at the upper shelf. It provides a mean for testing the smoke detector and also to verify the operation of the shutoff valves (ground/vent).The panel also indicates failures of the smoke detector, vent shutoff valve, ground shutoff valve and rack cooling system (fan and airflow switch) through 4 LED (Light-Emetting Diode)s (amber color).These failure indications are latched in order to enable the maintenance crew to evaluate the problem on the ground. MONITORING PANEL (LEDS) The ventilation system monitoring panel consists of 4 LEDs installed near the G2 Galley, on the side panel, forward of the LH passenger entry- door: COOLING FAIL SMOKE DETECTOR FAIL GROUND VALVE FAIL VENT VALVE FAIL Just like the maintenance test panel, these LEDs also indicate eventual failures of the rack ventilation system LRU (Line Replaceable Unit)s. The main difference is that the monitoring panel has an easier access and is much simpler (it does not have test functions, for instance).The monitoring panel is used for maintenance purposes only (such as troubleshooting). ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 80 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MAINTENANCE TEST PANEL ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 81 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ATA 21-30 PRESSURIZATION INTRODUCTION The Cabin Pressure Control System is designed for completely automatic operation. The pressurization controller has two fully independent channels, which alternate after each flight (70 seconds after touchdown). Both channels provide a manual back up function. The system utilizes digital electronics to communicate with the other aircraft systems via ARINC 429 buses and discrete signals. The Cabin Pressure Control System, in automatic mode, will control the pressurization in the cabin to a maximum cabin altitude of 8,000ft. The system will also control the maximum differential pressure of 8.32 psi up to 41,000ft aircraft altitude with a comfortable rate of change in climb and descent modes. The CPCS provides two different nominal differential pressures. For cruises below 37000 ft, the nominal differential pressure is scheduled to 7.77 psid. For cruises above 37000 ft, the nominal differential pressure is scheduled to 8.32 psid. These limits are achieved by modulating the airflow through the outflow valve. Separate mechanical positive and negative relief valves satisfy the safety relief functions. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 82 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CABIN PRESSURE CONTROL SYSTEM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 83 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DESCRIPTION CABIN PRESSURE CONTROL The Cabin Pressure Control System includes the following components: The pressurization controller, the cabin outflow valve, the negative pressure relief valve and safety valve. For BITE purposes and cockpit indication on EICAS, the position of the outflow valve is taken from one channel of a dual potentiometer. Speed control is achieved via a motor revolution counter fed by signals from the three hall sensors in the motor. The flight deck interface contains the pressurization control panel, including an auto and manual selector rotary switch, the EICAS display with Cabin Pressure Control System related messages, and the EICAS display lower section where cabin altitude, rate of change, maximum differential pressure and landing field elevation are displayed. The system also includes the multi-function display, for viewing CMC messages, and the Multi function Display ECS synoptic page to monitor the outflow valve position. AUTO PRESSURE CONTROL LOOP The CPCS controller controls the cabin pressure by generating a speed command for the outflow valve. The outflow valve maintains a safe cabin pressure by modulating the rate at which the air flows out of the cabin. The CPCS controller calculates a cabin reference from the ambient pressure (PA) and inputs from the FMS. The difference between the reference pressure (PC REF) and the actual cabin pressure (PC ACT), named DELTA PC, produces a speed and direction command for the motor interface. The motor interface directly controls its associated motor of the outflow valve. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 84 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CABIN PRESSURE CONTROL SYSTEM COMPONENTS ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 85 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING COMPONENTS PRESSURIZATION CONTROL PANEL The PRESSURIZATION control panel is installed on the right hand side of the overhead panel in the cockpit. It has these switches: A rotary MODE selector switch A rotary spring-loaded LFE (Landing Field Elevation) switch A rotary spring-loaded CABIN ALT switch A guarded DUMP push-button switch The MODE selector switch has three position: AUTO for automatic operation LFE CTRL for manual selection of LFE MAN for manual operation When the MODE switch is set to AUTO, the CPCS operates fully automatically without any crew attention during flight. The CPCS takes the LFE value from the FMS. The OUTFLOW switch is spring-loaded to the STOP position. When it is turned to the UP position, the outflow valve is driven to the open position. When it is turned to the DOWN position, the outflow valve is driven to the closed position. The outflow valve is driven at a rate of 2 degrees per second. The LFE switch is spring-loaded to the STOP position. When it is turned to the UP position, the LFE is increased. When it is turned to the DOWN position, the LFE is decreased. The LFE increases by 50 ft every 0.5 s.After 2 s, the LFE increases by 500 ft every 0.5 s. The DUMP switch is used to depressurize the cabin in the event of emergency evacuation, smoke evacuation or to rapidly equalize differential pressure. The cabin is depressurized at a rate of 2000 SL ft/min. up to 12400 ft +/- 50 ft cabin altitude. Positive Differential Pressure Limitation When the MODE switch is set to LFE CTRL, the CPCS is still in automatic operation, but the LFE values are selected manually via the LFE switch. The LFE CTRL is used together with the LFE switch to select LFE. The LFE ranges from -2000 ft to 14000 ft. When the MODE switch is set to MAN, the CPCS operates in manual mode. The MAN switch is used together with the CABIN ALT switch to manually control the position of outflow valve. The CABIN ALT switch controls the position of the outflow valve in the manual mode of operation. It only functions when the MODE selector switch is set to MAN. It has these positions: UP DOWN STOP ISSUE 1, 24 Sep 2014 Whenever the differential pressure exceeds the nominal differential pressure by +4 hPa (+.06 PSID) the control logic will automatically open the outflow valve to limit differential pressure (available only in AUTO mode). An additional Independent control function will open the outflow valve if the nominal differential pressure +20 hPa (+.29 PSID) is reached. This function is available in both Auto and Manual modes. A pneumatically actuated safety valve is also used to limit differential positive pressure to +597 hPa (+8.66 PSID ). FOR TRAINING PURPOSES ONLY Page: 86 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING PRESSURIZATION CONTROL PANEL ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 87 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CPCS CONTROLLER The CPCS controller provides automatic cabin pressure control, failure monitoring and recording and communication with other aircraft systems. The CPCS controller has two separate, but identical, fully independent control channels. Each control channel includes: Two cabin pressure sensors Cabin pressure control circuit BITE (Built-in Test Equipment) control circuit Motor driver circuit ARINC (Aeronautical Radio Incorporated) 429 I/O Interface Discrete I/O interface Serial Interface for software down load and shop interrogation purposes EMI (ElectroMagnetic Interference) protection circuits on separate board Non-volatile fault and flight data storage The control channels communicate with each other via internal communication buses. Each control channel is supplied by two separate aircraft power supply sources for redundancy. In automatic mode, only one control channel controls the outflow valve at any time, the other is in hot stand-by. The CPCS controller switches active control from one control channel to the other after each flight or when an auto failure occurs. This gives the CPCS a dual redundant architecture. The manual mode of operation overrides and bypasses the CPCS. The crew controls the cabin pressure by manual control of the outflow valve. This gives the CPCS a triple redundant architecture. The CPCS provides positive pressure relief to avoid damage to the aircraft due to positive over pressure. When the differential pressure exceeds the maximum differential pressure of 597.08 hPa (8.66 psi), the CPCS software control logic opens the outflow valve. This function is only available in the automatic mode of operation. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 88 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CABIN PRESSURIZATION CONTROLLER ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 89 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING The CPCS controller provides automatic cabin pressure control. It also performs BITE power-up, continuous and initiated tests. The CPCS controller is installed in the forward avionics compartment. It has four built-in pressure sensor ports, two for each control channel. One sensor of the control channel is used for the control loop and indications, the other is used as a backup for safety functions and indications. Four electrical connectors, two on each end of the unit, provide interconnection to other aircraft systems. The independent control channels communicate via an internal CAN (Controller Area Network) bus and internal discrete signals. Each control channel is powered by two separate aircraft power supply sources for redundancy. In the operational state, if the control channel detects no faults and all BIT functions are enabled, the pressure control is activated. In the stand-by state, the control channel switches off drive power to the outflow valve and some system performance monitoring tests are disabled. If no faults are detected and manual mode is not selected, the pressure control loop and the position control loop are held initialized to actual values. This achieves a smooth transfer to the operational state in respect to cabin pressure rates. In the fail state, the control channel switches off drive power to the outflow valve because faults have been detected. All outputs to other aircraft systems are flagged invalid except ARINC information about the status of the system. Channel one is powered by the 28 VDC (Volt Direct Current) essential buses 1 and 2. Channel two is powered by the 28 VDC essential buses 1 and 3. The CPCS controller is part of a dual redundant system. It is active when the system operates in the automatic mode. Only one control channel operates the outflow valve at any given time. The other control channel is in hot standby. Pressure sensor signals are transmitted via ARINC 429 to the control circuits and are used for cabin pressure control logic. The control channel calculates a reference value for cabin pressure from external aircraft inputs and interna logic.The reference value is compared with the actual cabin pressure and when a difference exists, an error signal is output. This error signal is fed to one of the motors in the actuator to drive the outflow valve to the desired position. The initialization state performs these tasks: Power-up BIT (Built-in Test) Initialization of software Initialization of hardware Control channel determination for flight Resets all flight indications Initialization of pressure control loop Synchronisation to the other control channel Start normal control function ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 90 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CPCS CONTROLLER ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 91 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OUTFLOW VALVE The outflow valve controls the air flow out of the aircraft fuselage. It is installed on the forward fairing bulkhead. The outflow valve consists of a valve body and a rotary actuator. The valve body comprises a 8.5 in diameter butterfly valve, a two-piece butterfly valve flap, a splined shaft and an actuator housing. The valve body, valve flap and actuator housing are made of anodized aluminium alloy. The valve flap is bolted around the splined shaft and moves to the closed if loss of mechanical actuation occurs. The rotary actuator consists of two brush less DC (Direct Current) motors, a gear train and a dual channel potentiometer. Each DC motor is controlled and monitored by a separate channel of the CPCS controller. Only one DC motor drives the outflow valve at any time. Both DC motors use the same actuator mechanism. The gear train consists of two irreversible worm screws, a differential gear stage and two stages of spur gears. The worm screws are linked directly to the output shafts on the DC motors. The spiral angle of the worm screw prevents back driving of the motors. The dual potentiometer sends a position signal to each control channel of the CPCS controller. This provides position feedback of the outflow valve in automatic and manual modes of operation. The CPCS has a fail-safe software logic to close the outflow valve if the cabin pressure altitude reaches 14500 ft. This function overrides the normal automatic operation only, it does not effect the manual operation of the outflow valve. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 92 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OUTFLOW VALVE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 93 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING POSITIVE PRESSURE RELIEF VALVE The positive pressure relief valve is a pneumatically actuated gate valve, located on the rear pressure bulkhead, normally held in the closed position by a pre-loaded spring. Valve operation is independent of the Cabin Pressure Control System controller. The relief valve provides both positive and negative pressure relief. It contains a pilot valve that compares cabin pressure to ambient pressure. If the pressure difference exceeds 8.66 psid, the pilot valve will open and the differential pressure will act on the diaphragm to open the valve. A micro switch is mounted on the valve to provide input to the Modular Avionics Unit for status reporting. The static port connects the positive pressure relief valve to ambient pressure. The port is located at the rear fuselage section and has an integral heater powered by 28 VDC to eliminate ice blockage. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 94 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING POSITIVE PRESSURE RELIEF VALVE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 95 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING NEGATIVE PRESSURE RELIEF VALVE Under normal flight conditions, the valve is in the closed position. The valve is mechanically actuated using the self-balanced spring forces at the valve gate and the ambient-to-cabin differential pressure. If the ambient pressure exceeds the aircraft cabin pressure, the valve gate opens and limits the negative pressure. The springs set the cap to open at a differential pressure of -10 hPa (-0.15 psi). The valve is fully open at -35 hPa (-0.51 psi). The safety valve has also a negative relief function. If the ambient pressure acting on the underside of the gate valve exceeds the cabin pressure, the gate valve opens allowing air from ambient to flow into the cabin. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 96 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING NEGATIVE PRESSURE RELIEF ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 97 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OPERATION CABIN PRESSURE CONTROL MODES During ground and flight operation the CPCS determines the current flight mode depending on ARINC information. The system operates with the following flight modes: Ground (GN) Takeoff (TO) Climb (CI, CE) Cruise (CR) Descent (DI) Abort (AB) The mode logic uses the following information from the MAU (Modular Avionics Unit) to determine the current flight mode: Landing gear status and validity (generated by FADEC (Full- Authority Digital Engine-Control) Engine takeoff power status and validity (generated by FADEC) Ambient pressure (generated by ADC) Cruise Flight Level (CRFL) and validity (generated by FMS) The flight mode transitions for a normal flight are as follows: Ground Mode - The ground mode is active when the landing gear status shows that the landing gears are compressed and the engines takeoff power signals are not set. Ground to Taxi Mode - The taxi mode becomes active as soon as the doors signal indicates the doors are closed and both engines rotation (N2) are higher than 60%. This mode is only possible to be activated from the ground mode. Climb Mode to Abort - If the aircraft stops climbing and begins an immediate descent, the CPCS interprets this as a flight abortion. The abort is only possible if the cruise mode has not been entered and either the aircraft is below 10000 ft absolute or is less than 5000 ft above the takeoff field. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 98 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING GROUND AND TAKEOFF MODES ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 99 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CLIMB AND CRUISE MODES Climb external is used when a valid CRFL is received from the FMS. Climb internal is used if the CRFL is invalid or the FMS fails. Climb Mode to Abort - If the aircraft stops climbing and begins an immediate descent, the CPCS interprets this as a flight abort. The abort is only possible if the cruise mode has not been entered and either the aircraft is below 10000 ft absolute or is less than 5000 ft above takeoff field. Climb Mode to Cruise - In the climb external mode, the mode logic switches from climb to cruise when the aircraft reaches the planned CRFL. In the climb internal mode, the mode logic switches from climb to cruise when the aircraft stops climbing. Cruise Mode to Descent - The descent mode becomes active when the aircraft starts descending after the cruise. Descent to Ground - The ground mode is active when the landing gear status indicates that the aircraft is on the ground. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 100 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CLIMB AND CRUISE MODES ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 101 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DESCENT AND ABORT MODES The CPCS will transition to DESCENT mode by selecting the landing field altitude before the aircraft leaves the cruise flight level. The target pressure will be set to landing field altitude plus 0.12 psi to ensure landing with the CPCS in control. Cabin rate of change depends on cabin pressure, landing field pressure and ambient pressure within 200 and 750 fpm. If the aircraft stops climbing and begins immediate descent, the CPCS transits to ABORT mode. This transition is only possible from climb mode when the aircraft altitude is below 10000 ft absolute or 5000 above the takeoff field. In this mode, cabin pressure will be scheduled back to the takeoff altitude, with a 5000 fpm rate of change. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 102 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DESCENT AND ABORT MODES ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 103 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MANUAL MODE The manual mode of operation gives the flight crew manual control of the cabin pressure. When the MODE selector switch on the pressurization control panel is in the MAN position, it configures the CPCS for manual operation. Both automatic channels revert to the stand-by state. The manual operation is performed by one control channel which is selected automatically. The crew has direct manual control of the outflow valve via the CABIN ALT switch on the pressurization control panel. The CPCS detects any failure in the manual mode and provides fault messages to the EICAS and CMC (Central Maintenance Computer). The EICAS shows the message “PRESN MAN FAIL” if the manual function of both channels has failed. Failures detected during flight which do not require crew action are displayed on the CMCM (Central Maintenance Computer Module) after landing. Manual mode is differential pressure limited but is not cabin altitude limited. In manual mode there is no automatic cabin depressurization on ground (after landing). When in manual mode, the crew shall depressurize the cabin to a maximum differential pressure of 0.2 psid, before landing. After landing the crew shall open the OFV fully. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 104 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MANUAL MODE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 105 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ABNORMAL OPERATION These fault protection schemes are used to prevent the aircraft depressurization or overpressurization: Cabin altitude limit in automatic mode Differential pressure control Auto fault indication Manual fault indication Maintenance required indication Excessive cabin altitude warning Two pressure sensors measure the cabin pressure in each control channel. If the cabin altitude exceeds the limit of 14500 ft ±500 ft, logic circuits close the outflow valve automatically. This is done independently from the pressure control logic. If the CPCS BIT logic detects a failure within a CPCS component, a CMC message is generated for later maintenance action. This is for components that are not essentially required to finish the actual flight but require maintenance action. Both automatic control channels provide a high cabin altitude warning at 10000 ft cabin altitude independent of the selected mode. In automatic mode, if the aircraft operation requires a cabin landing field elevation above 10000 ft, the CPCS controller inhibits the 10000 ft warning up to a 14000 ft landing field elevation. The 10000 ft warning is always active for a cabin altitude of 14000 ft or higher. An additional circuit limits the cabin altitude to 12700 ft ±300 ft. This limitation is not available in manual mode. When the differential pressure exceeds the maximum differential pressure of 592.94 hPa (8.60 psi), the control logic opens the outflow valve to limit differential pressure. An additional independent control function opens the outflow valve if a nominal differential pressure of +24 hPa (0.34 psi) is reached. If the control channel logic detects a major failure of one of the auto control channels, an EICAS message is generated to alert the crew that the redundancy was lost. With the loss of the auto control channel redundancy, the maximum duration is limited as stated in the MEL (Minimum Equipment List). If both auto control channels are detected faulty, the EICAS indication changes color to alert the crew. The crew must select the manual mode of operation. If the BITE logic of the channels detect a major failure of both of the manual functions, an indication is displayed on the EICAS. The crew must descend the aircraft to 10000 ft because of loss of the CPCS function. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 106 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ABNORMAL OPERATION ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 107 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING INDICATIONS In case of a Cabin Pressure System fault, EICAS messages are displayed: If one controller channel fails, the EICAS advisory message PRESN AUTO FAULT will be displayed If both controller channels fail, the EICAS caution message PRESN AUTO FAIL will be shown When both channels are unable to operate in manual mode, the caution message PRESN MAN FAIL will be displayed If cabin altitude exceeds 9700 ft, a warning message HI CABIN ALT will illuminate, and an aural warning, CABIN, will sound. The EICAS Display also provides a continuous status of cabin altitude, cabin rate, differential pressure, and landing field elevation. Display color indicates current status of displayed value. Green - Normal range Amber - Advisory range Red – Warning ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 108 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING EICAS INDICATIONS ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 109 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING Each control channel of the CPCS controller has redundant ARINC transmitters to MAU 1 and MAU 2 to provide indications to the EICAS. This information is shown continuously on the main page of the EICAS display. The EICAS indications are: –ALT– Cabin altitude: Indicates the cabin altitude in feet. The color of the indication changes as the altitude changes as follows (Resolution: 100 ft): For airfield altitude < 9400 ft: Green for values £ 8100 ft Amber for values > 8100 ft and £9,700 ft. Red for values > 9700 ft. Amber dashes for invalid data. For airfield altitude ≥ 9400 ft: Green for values < airfield altitude +500 ft. Red for values ≥ airfield altitude +500 ft. Amber dashes for invalid data. –RATE– Cabin Pressure Rate: Indicates cabin pressure rate in feet per minute at sea level ( SLft/min). The color of the indication changes as the cabin pressure rate changes as follows (Resolution: 50 SLft/min): Amber for values above +2,500 SLft/min. Green for values -2,500 to +2,500 SLft/min. Amber for values below -2,500 SLft/min. Amber dashes for invalid data. –Delta P– Cabin differential pressure: Indicates cabin differential pressure in psi. The color of the indication changes as the D P changes as follows (Resolution: 0.1 psi): Green for values -0.2 to +8.4 psi. Amber for values -0.5 to -0.3 psi. Amber for values +8.4 to +9.1 psi. Red for values below -0.5 psi. Red for values above +9.1 psi. Amber dashes for invalid data. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 110 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING EICAS INDICATIONS (CONTINUED) ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 111 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING LFE– Landing Field Elevation TRAINING INFORMATION POINTS Indicates landing field elevation in ft. The color of the indication changes as the LFE value changes as follows (Resolution: 100 ft): Green for FMS values. Cyan for manual input with “CTRL” in front of value. Amber dashes for invalid data. Green dashes when manual mode is active. Warning: TO PREVENT ELECTRICAL SHOCK OR DAMAGE, DISCONNECT ALL SOURCES OF ELECTRICAL POWER BEFORE YOU INSTALL OR REMOVE THE PRESSURIZATION CONTROLLER. MAKE SURE THAT A PERSON APPROVED TO USE MODERN METHODS OF FIRST AID AND RESUSCITATION IS ALWAYS NEAR YOU. Caution: THE MODULE OR UNIT CONTAINS ELECTROSTATIC DISCHARGE SENSITIVE (ESDS) ITEMS. OBEY THE APPROVED INDUSTRY PRECAUTIONS WHEN YOU TOUCH, REMOVE, OR INSERT PARTS OR ASSEMBLIES. DAMAGE CAN OCCUR FROM ELECTROSTATIC DISCHARGE. The CPCS controller has BIT (Built-in Test) logic circuits to detect failures within each control channel or in CPCS functions. All detected faults are stored in NVM (Non-Volatile Memory) and are continuously transmitted to the EICAS and CMCM (Central Maintenance Computer Module) on the ARINC (Aeronautical Radio Incorporated) 429 output bus. The CPCS is provided with BITE that provides failure indications to the EICAS display and the CMC. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 112 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING EICAS INDICATIONS (CONTINUED) ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 113 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DIAGNOSTIC AND TEST The CPCS controller has BIT logic to detect failures within each control channel or in the CPCS functions. If the BIT logic detects a fault in the active control channel, the control channel goes into automatic fail. The CPCS switches automatically to the other control channel without any workload to the crew. A channel Fail message is displayed on the CMC display. All detected faults are stored in NVM (Non-Volatile Memory) and can be down loaded for maintenance purposes off-wing. All faults are continuously transmitted to EICAS and CMCM via the ARINC 429 output bus. The CPCS checks internal parameters and functionality. The internal fault detection logic detects and isolates single LRU (Line Replaceable Unit) and interconnection failures that cause loss of functionality or redundancy. The CPCS performs these tests: Power-up test Continuous hardware and software tests Continuous function tests The power-up test is done after a cold start, a reset or a power supply interrupt. During the power-up test internal devices initialize and check the hardware and software of the CPCS. When the test has passed, the main page is shown on the EICAS display. When the power-up test fail, the PRSN AUTO FAULT message is displayed on the EICAS. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 114 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING BUILT-IN TEST ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 115 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ATA 21-50 COOLING INTRODUCTION The air conditioning system utilizes two identical cooling packs that provide condition bleed air for cabin heating and cooling. The packs provide condition bleed air for cabin heating and cooling, and include the following components: Dual heat exchanger, Air cycle machine, Condenser-reheater, Water collector, Add heat bypass valve and temperature sensors. There are also two external components: The Pack bypass valve, and a Pack flow control valve which together control pack operation. During normal operation, each cooling pack provides half of the total fresh airflow; however, a single pack is capable of providing 67% of the total flow and ensuring safe aircraft ventilation and temperature control capability. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 116 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING AIR CONDITIONING SYSTEM ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 117 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DESCRIPTION The air conditioning system utilizes two identical air cooling packs, right and left, to condition bleed air for cabin heating and cooling. Each air cooling pack consists of a dual heat exchanger, air cycle machine, condenser/reheater, water collector, valves and temperature sensors. The primary function of the air cooling pack is to supply conditioned air to the cabin distribution system for environmental control. The air cooling pack also contains an internal condensing water collection system which removes moisture from the cooling pack air flow. Hot air from the engine bleed system is precooled in the dual heat exchanger using cold ram (outside) air to remove the heat. An air cycle machine within the pack contains two cooling turbines which generate cold air, through expansion, for cooling cabin. An equal quantity of filtered re circulated air is mixed with air from the air conditioning packs. The high quantity of supply air results in a complete cabin air exchange about every 2.5 to 3.5 minutes (based on aircraft configuration and altitude), or about 18 to 25 times an hour. The high air exchange rate is necessary to control temperature gradients, prevent stagnant cold areas, and maintain air quality. The cooling pack system conditions hot bleed air for cabin air conditioning. There are two identical cooling packs (right and left) per aircraft and they are located in the ECS (Environmental Control System) pack bay in the forward fairing of the aircraft. The cooling pack is an air cycle refrigeration system that uses air passing through and into the airplane as the refrigerant. The cooling pack system automatically controls the temperature and decreases the humidity of the cockpit and cabin air. The two cooling packs, which are installed in the forward part of the wing-to-fuselage fairing, provide dry, sterile, and dust free, conditioned air to the flight deck and passenger cabin at the proper temperature, flow rate, and pressure to satisfy pressurization and temperature control requirements. An equal quantity of filtered, re circulated air is mixed with air from the cooling packs. A flow control valve regulates flow of bleed air into the air conditioning packs. The refrigeration pack is out fitted with sensors and valves for temperature and operational control, and heat exchangers that use outside ram air for excess heat dissipation. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 118 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ECS PACK ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 119 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING FLOW CONTROL The flow of air to the air conditioning packs is measured using a differential pressure sensor which is mounted on a venturi duct. The differential pressure sensor sends an electronic signal to the AMS controller. The AMS controller uses the differential pressure, bleed manifold pressure, and pack inlet temperature to calculate the airflow that goes to the air conditioning pack. The AMS controller then supplies a torque motor current command to modulate the pack flow control valve to obtain the desired pack airflow rate. The pack flow control also is based on engine bleed availability. During normal operation each pack flow control valve is controlled to accepted half of the total flow reference. During dual engine bleed or single engine bleed and single pack operation, the total fresh air shall be reduced to 67% of the total flow reference. During single engine bleed and dual pack operation, the total fresh air flow shall be reduced to 75% of the total flow reference. Note: During single engine bleed operation the opposite side air conditioning pack will be turned off if a slat anti- ice operation is required. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 120 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING FLOW CONTROL ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 121 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING COMPONENTS PACK FLOW CONTROL VALVES VENTURI DELTA-P SENSORS There are two pack flow control valves, right and left, located upstream of the left and right air cooling packs. The differential pressure sensor is mounted on the flow sensing venturi duct directly upstream of the pack flow control valve. The sensor provides a 0 to 10 VDC (Volt Direct Current) electronic signal to the AMS controller, which is used to calculate the air flow that goes into the environmental control system. The sensor is hermetically sealed and consists of two input pressure ports, and internal pressure transducer, and an electrical connector. There are two differential pressure sensors per aircraft (one per cooling pack). The pack flow control valves are modulated by the AMS (Air Management System) controller to obtain the desired cabin ventilation rates. The pack flow control valve is a pneumatically actuated butterfly valve controlled by a torque motor. Modulation of the valve is electronically controlled by the AMS controller. The AMS controller applies a 0 to 50 mA torque motor current to position the valve as necessary to obtain the proper cabin ventilation rates. The valve incorporates a closed position switch which is used to provide position feedback to the AMS controller. A removable air filter is used to filter airborne contaminants from the supply air. A locking screw installed in the actuator housing can be used to lock the valve closed. FLOW SENSING VENTURIS The flow sensing venturi duct is a tapered steel duct that is used to calculate the air that goes into the air conditioning system. The taper in the venturi duct creates an orifice. The venturi duct contains pressure sensing ports on the upstream and downstream sides of the duct orifice. Airflow across this duct orifice is measured by a differential pressure sensor which is mounted on the venturi duct. This differential pressure is used by the AMS controller to calculate the air flow. There are two venturi ducts per aircraft (one per cooling pack). ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 122 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING FLOW CONTROL VALVE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 123 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DUAL HEAT EXCHANGERS The dual heat exchanger and fan inlet diffuser housing assembly is assembled in each of the ECS packs of the integrated air management system. In the pack, bleed air flows through the primary circuit of the dual heat exchanger to remove heat before entering the compressor section of the air cycle machine. The flow then passes through the secondary circuit of the heat exchanger before continuing on to the reheater. Both bleed circuits of the heat exchanger are cooled by ram air in series through the secondary first, then through the primary core sections. After exiting the primary core, the ram airflow enters the outer housing of the fan inlet diffuser housing where it is either pulled through the fan, or passes through the fan bypass check valve where it is vented to the ram overboard ducting. The dual heat exchanger is an aluminum design, which consists of sheet metal or cast headers and mount pads fusion-welded to a plate-fin core. The primary section is a single-pass, cross-flow configuration. The secondary section is a two-pass cross-counterflow configuration. The dual heat exchanger/fan inlet diffuser housing contains two access windows which can be used for inspection and or cleaning of the heat exchanger ram air circuit. The fan inlet diffuser housing is welded to the ram outlet header of the dual heat exchanger. FAN BYPASS CHECK VALVE The fan bypass check valve is a 12 in diameter hinged, petal-type check valve which has six petals that cover six orifice windows in a single valve seat. The valve allows airflow through the orifice windows in one direction. Flow in the opposite direction (reverse flow) is prevented by the petals closing on the aluminium check valve frame. The fan bypass check valve is installed in the cooling pack between the fan inlet diffuser housing and the ram air outlet duct, and allows ram air to bypass the air cycle machine fan whenever pressure in the ram air circuit exceeds the ACM fan outlet pressure. This fan bypass function is necessary to prevent ACM damage caused by excessive fan surge margins. There are two fan bypass check valves per aircraft (one per cooling pack). ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 124 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DUAL HEAT EXCHANGER ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 125 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING AIR CYCLE MACHINE The air cycle machine provides the source for pack cooling. The external structure consists of a fan and compressor housing, a first stage turbine housing, and a second stage turbine housing. Each housing is made of cast aluminium. The ACM internal structure has two turbine rotors which drive a compressor rotor and a cooling fan rotor. The four rotors and two shaft segments turn as one assembly locked together by a tie rod. The assembly rotates in a pair of hydrodynamic, foil-type journal bearings. Axial movement is limited by a pair of hydrodynamic thrust bearings. These hydrodynamic foil-type bearings use no oil and require no scheduled maintenance. The fan rotor is attached to one end of the assembly and is positioned adjacent to the fan shaft segment followed by the compressor rotor, first turbine rotor, turbine shaft segment, and second turbine rotor. The turbine shaft segment includes both a journal bearing surface and the thrust disk on which the two bearings act. A tie-rod goes through the centre of the shaft and rotor segments and holds the assembly together axially. The tie-rod is assembled with a high preload which permits all components of the assembly to operate as a one shaft system. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 126 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING AIR CYCLE MACHINE COMPONENTS ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 127 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CONDENSER/REHEATER WATER SPRAY NOZZLE The condenser/re-heater is an aluminum dual-heat exchanger consisting of headers and mounts welded to a core. Both core sections are single pass, crossflow, plate-and-fin designs. The condenser cold circuit is situated between the two turbine stages of the air cycle machine and is never subjected to sub-freezing air temperatures; therefore, it does not require complicated features for the prevention of ice buildup, which other systems using the conventional chilled recirculation cycle demand. The water spray nozzle is mounted in the ram air inlet ducting directly upstream of the dual heat exchanger. Water, which is collected in the water collector, is routed through drain line to the water spray nozzle. The water spray nozzle sprays the water on the ram inlet face of the secondary heat exchanger. This cools the air that goes into the secondary heat exchanger and improves heat exchanger performance. The condenser/reheater core consists of alternating hot and cold fin layers. A cast manifold is welded to the coreís hot inlet. The manifold provides most of the inter-pack flow passages between the heat exchangers, water collector, and ACM. The manifold bolts to a base on the dual heat exchanger end sheet and seals to the primary and secondary circuits using face seals. WATER COLLECTOR The water collector is a brazed and welded assembly. The collector body is constructed of two aluminium-brazed sub assemblies welded together at the outside diameter. Each section of the sub assembly is made of spun and hydro-formed sheet metal parts. The water collector removes water from the condenser/reheater heat exchanger and sends the dry air to the air cycle machine. A swirl vane at the water collector inlet sends the water to the duct walls. A clearance between the diffuser section and the air return diffuser section catches most of the water from the airflow. A drain boss located at the lowest section of the collector lets water drain by gravity and air pressure. An overflow drain boss located slightly above the lowest point lets water drain if the primary port is clogged. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 128 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CONDENSER ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 129 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING PACK BYPASS VALVE There are two pack bypass valves, a right and a left, used in the air cooling pack system. The pack bypass valve modulates to maintain a desired pack outlet temperature. The pack bypass valve is a pneumatically actuated butterfly valve controlled by a torque motor. Modulation of the valve is controlled electronically by the AMS controller. The AMS controller applies a 0 to 50 mA torque motor current to position the valve as necessary to obtain the proper cooling pack outlet temperatures. The valve contains a removable air filter which is used to filter airborne contaminants from the supply air. A locking screw installed in the actuator housing can be used to lock the valve closed. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 130 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING BYPASS VALVE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 131 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ADD HEAT, AND LOW LIMIT BYPASS VALVE ADD HEAT VALVE Bleed air passing by the pack inlet temperature sensor and through the primary heat exchanger enters the air cycle machine compressor. The add heat valve is a 1 in diameter pilot operated shutoff valve which is used to control temperatures at the condenser inlet and outlet locations within the air conditioning pack. The valve is closed by applying 15 VDC to pins A and B. There are two add heat valves per aircraft (one per cooling pack). Maintenance of the valve is on condition. Compressor inlet and outlet temperature is sensed by temperature sensors and forwarded to the AMS controller. The main flow from the compressor goes through the secondary heat exchanger and on to the condenser/reheater. Some hot air is tapped and directed to the Add Heat Valve to maintain turbine second stage inlet temperature. Air from the condenser/reheater is directed to the first stage turbine, where the temperature will drop. The Low Limit Bypass Valve is installed parallel to the first stage turbine. The valve provides additional warm air to maintain condenser inlet temperature. Air flows through the condenser and enters the second stage turbine for a further temperature reduction. Turbine outlet cold air is mixed with pack bypass air to achieve the requested duct temperature. LOW LIMIT VALVE The low temperature limit bypass valve is an electrically actuated valve, which is installed integral to the air cycle machine turbine housing. The linear actuator will be used to position a piston in a valve housing, which meters the amount of warm air bypass flow to control the temperature in the condenser inlet duct. The feedback for positioning is the downstream duct temperature. The actuator operates to position the valve in response to electrical signals from the AMS electronic controller. The control logic will be based on ìbump/ stop/checkî, where a signal is sent to the actuator to extend or retract in steps. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 132 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING LOW LIMIT BYPASS VALVE, ADD HEAT VALVE AND ECS PACK BYPASS VALVE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 133 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING TEMPERATURE SENSORS The air conditioning pack temperature control has five temperature sensors, which supply data to the AMS controller. The sensors are: Pack inlet temperature sensor, Compressor inlet temperature sensor, Compressor outlet temperature sensor, Condenser inlet temperature sensor and Pack outlet temperature sensor. All of these sensors are dual element sensors (except the pack inlet temperature sensor, which has a single element) in order to improve system reliability. The AMS controller monitors all sensor voltages in order to control pack operation or determine pack failure. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 134 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING TEMPERATURE SENSORS ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 135 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OPERATION Air is cooled in the primary section of the dual heat exchanger using ram air to remove the heat. The air is then compressed by the compressor portion of the dual turbine ACM. The heat generated by compression is removed by the secondary portion of the dual heat exchanger, using ram air. The air is then passed through the condenser/reheater where it is sub-cooled within the condenser using the cold exhaust air from the first stage turbine. This cooling process condenses water from the air to permit it to be collected by the water collector. The collected water is moved to the spray nozzle, which is located in the secondary ram inlet header of the dual heat exchanger. Pack outlet temperatures are continuously monitored by the AMS controller using electronic feedback from the pack outlet temperature sensor. The pack outlet temperature is controlled by adding hot pack inlet air to the pack outlet airflow. This is accomplished by modulation of the pack bypass valves. The AMS controller reads actual pack outlet temperatures and sends a torque motor current command to modulate the pack bypass valves to obtain the desired pack outlet temperatures. The water is sprayed on the ram air face of the core to increase the heat exchanger performance through evaporative cooling. After exiting the water collector, the air flows through the re-heater portion where it is preheated to increase first stage turbine performance. After expansion through the first stage turbine portion of the ACM, the air passes through the cold side condenser portion of the condenser/ reheater where it removes the heat for condensation. After exiting the cold side of the condenser, the air enters the second stage turbine of the ACM where it is expanded to provide the cold air source for cabin cooling. The condenser inlet temperature is continuously monitored by the AMS controller using electronic feedback from the condenser inlet temperature sensor. The condenser inlet temperature is controlled by adding warm compressor outlet air to the condenser inlet airflow. This is achieved by modulation of the low limit valve and/or the opening and closing of the add heat valve. The condenser inlet temperature is controlled to 34 ∞F/1.1∞C under most pack operating conditions to prevent water from freezing in the condenser. In certain low humidity conditions the condenser inlet may be controlled to 50 ∞F/ 10 ∞C. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 136 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING AIR CYCLE MACHINE OPERATION ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 137 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ECS OFF REQUEST The FADEC may send an ECS OFF signal to the AMS controller, requesting that no bleed air be extracted from the engine for the air- conditioning system. The FADEC sets this signal depending on the TDS input (REF ECS OFF), pressure altitude, flight phase and engine failure detection. If the ECS is bleeding air from the engine and the FADEC ECS OFF request is true and Altitude is below 15 000 ft, both ECS packs will be commanded OFF. The ECS cooling packs will be shut down at -30 ppm/ sec after receiving the ECS OFF signal from the FADEC. The APU can be used as a valid bleed air source when the ECS OFF signal is set to true and Anti-ice is not required. In response to the ECS OFF signal the AMS controller has the following requirements: If the FADEC transitions the ECS OFF signal from true to false, the both ECS cooling pack FCV’s will be automatically opened without any pilot action. The AMS will disregard the FADEC ECS OFF signal if aircraft altitude is above 15,000 ft. In general, the AMS controller will use the ECS OFF signal from the incontrol FADEC channel. If the AMS controller loses communication from one SPDA then AMS controller will use the other SPDA as a backup source of information for the ECS OFF and channel in control signals. The time from the ECS OFF signal being received in the AMS controller to ECS cooling pack FCV’s closing will be less than 5 seconds when commanded ON again by the AMS controller. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 138 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ECS OFF LOGIC ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 139 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING PACK RELATED MESSAGES TRAINING INFORMATION POINTS The Pack-related EICAS messages are: PACK FAIL CAUTION if any pack component develops a fault, PACK OFF advisory message if the pack is switched off, or PACK LEAK caution message when an overheat is detected in the pack high pressure bleed duct. To prevent electrical shock or damage, disconnect all electrical power including compressor inlet and discharge temperature sensors, condenser inlet temperature sensors, and pack inlet and outlet temperature sensors before installation or removal of the cooling pack. CMC messages will be provided to determine failed pack components if the PACK FAIL message is present. The pack will be disabled in the following conditions: bleed source not available, pack switch is OFF, left or right engine start with weight on wheels, duct leak or if the AMS built-in-test detects failure. Warning: DO NOT TOUCH THE COOLING PACK SYSTEM DUCTS OR COMPONENTS IMMEDIATELY AFTER THE SYSTEM IS TURNED OFF. THE HIGH AIR TEMPERATURE CAN CAUSE INJURY TO YOU. Caution: BE CAREFUL WHEN YOU HANDLE THE PACKS, VALVES, SENSING ELEMENTS, AND AIR CONDITIONING DUCTS. DO NOT LET OIL, GREASE OR RESIN GET ON THESE COMPONENTS. There must be no twists or bends on the bellows. In addition to that, the ducts and bellows must be aligned with the adjacent components. This is to avoid damage to the ducts installation and to the air conditioning packs during operation. There must be no twist or asymmetrical deformation of the rubber mounts. This is to avoid overloading of the air conditioning pack installation and prevent an eventual failure of the air cycle machine. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 140 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING PACK RELATED MESSAGES ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 141 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DIAGNOSTIC AND TEST ADD HEAT VALVE IBIT During the IBIT, preconditions are: WONW Airspeed below 50knots Channel in control and PACK ON Condenser temperature below 10deg C Test will drive the valve open, consequence: heat will be added to T1 turbine inlet. Test will check for temperature rise. CONDENSER IBIT During the IBIT , preconditions are: WONW Airspeed below 50knots Channel in control and PACK ON Source APU Manifold pressure above 12psi Test will drive flow control valve fully OPEN and bypass valve fully CLOSED. This will create full flow through the air cycle machine, checking condenser operation will maximum airflow. LOW LIMIT BY-PASS VALVE IBIT During the IBIT , preconditions are: WONW Airspeed below 50knots Channel in control and PACK OFF The test will drive the valve open and closed for 60 seconds ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 142 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING PACK TESTS ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 143 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ATA 21-60 TEMPERATURE CONTROL INTRODUCTION The temperature control system provides closed loop control for the flight deck and passenger cabin. The cabin two-zone configuration is an aircraftselectable option. The flight deck and passenger cabin temperatures are electronically controlled by the AMS controller between 19∞C and 30∞C. The AMS controller compares the actual temperature provided by the temperature sensors to the selected temperature. If a difference exists, the AMS controller will adjust the target duct temperature by modulating the pack bypass valve position until the selected temperature is achieved. In case of ambient sensor failure, the system defaults to the duct temperature sensor, and if the selector fails, the system defaults to a 75∞F/ 24∞C zone temperature. ZONE TEMPERATURE CONTROL Cabin Zone Temperature Sensor locations. Cabin Zone Temperature Sensor also uses ejector to draw ambient air across sensor element. Ambient air is drawn from space between overhead bins. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 144 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING AMS TEMPERATURE CONTROLLER ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 145 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DESCRIPTION COCKPIT ZONE CONTROL The temperature control system provides independent temperature control for the cockpit zone. During normal operation the cockpit zone receives airflow from the left air conditioning pack and the left recirculation fan. The cockpit zone temperature is electronically controlled by the AMS (Air Management System) controller. The AMS controller interfaces with a cockpit temperature selector (potentiometer) to determine the desired cockpit temperature. The AMS controller compares the selected cockpit temperature to the actual cockpit zone temperature. The difference between the selected temperature and the actual cockpit temperature is used to calculate a target cockpit zone duct temperature. The AMS controller will then modulate the left pack bypass valve to meet the target cockpit zone duct temperature. The cockpit temperature control system contains two identical electronic sensors which provide temperature feedback to the AMS controller. One sensor is located in the cockpit zone and the other sensor is located in the cockpit duct, downstream the mixing duct. The cockpit temperature is selected by the flight crew using the CKPT selector. During normal operation, the cockpit zone receives airflow from the left air conditioning pack and the left recirculation fan. Under normal operating conditions, the cockpit temperature is controlled by modulation of the left pack bypass valve. Hot pack bypass air is mixed with cold pack discharge air to obtain the desired zone temperature. Two temperature sensors each located in the cockpit zone and in the cockpit duct provide electronic signals to the AMS controller. Each temperature sensor contains two independent sensing elements which provide electronic signals to channel 1 and channel 2 of the AMS controller. This provides for redundancy so that failure of an individual sensing element will have no effect on cockpit temperature control. Using feedback from the temperature selector and the temperature sensors the AMS controller will then change the left air conditioning pack outlet temperature to achieve the desired cockpit zone temperature. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 146 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING COCKPIT ZONE CONTROL ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 147 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING PASSENGER CABIN SINGLE-ZONE CONFIGURATION The passenger cabin receives air from the left and right air conditioning packs, routed through the mixer duct, where it is blended with re circulated air from the fans. Air is then routed to the front and aft passenger cabin distribution ducts. In the single cabin zone configuration, the passenger cabin temperature is controlled by changing the right air conditioning pack outlet temperature. The single configuration includes two dual sensors, one ambient temperature sensor located in a Duct by the overhead bins, and the other cabin duct temperature sensor downstream of the mixer. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 148 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING SINGLE CABIN ZONE CONFIGURATION ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 149 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING TWO-ZONE CONFIGURATION The two cabin zone configuration uses a separate trim system for independent control of forward and aft cabin zones. Hot air is tapped from the right air conditioning pack for zone temperature control. The system includes: two trim modulating valves, two ejectors and three dual temperature sensors. The AMS controller compares the selected zone temperatures to actual zone temperatures. The difference between the selected temperature and the actual zone temperature is used to calculate a target duct temperature for both the forward and aft cabin zone ducts. The AMS controller will then modulate the right pack bypass valve, via the torque motor command, to meet the coldest cabin duct target temperature. The AMS controller compares the selected zone temperatures to actual zone temperatures. The difference between the selected temperature and the actual zone temperature is used to calculate a target duct temperature for both the forward and aft cabin zone ducts. The AMS controller will then modulate the right pack bypass valve, via the torque motor command, to meet the coldest cabin duct target temperature. The trim bypass valve for the coldest zone will be sent a signal to close. The AMS controller will then modulate the opposite zone trim modulating valve to meet the warmest cabin duct target temperature. The trim air system utilizes two trim air modulating valves, two hot air ejectors, and associated ducting to independently control the air temperature entering the forward and aft passenger cabin distribution ducts. This is accomplished by mixing hot air from the ejectors directly into the forward and aft distribution duct openings within the mixing duct. The amount of hot air flowing to the ejectors is controlled electronically by the AMS controller through modulation of two trim air modulating valves. The passenger cabin temperature is selected by the flight crew using the PAX CABIN selector. The forward and aft passenger cabin zone temperatures can be selected by the flight attendant using CABIN TEMPERATURE selectors located on the attendant control panels. The passenger cabin zone requiring the coldest air is controlled by modulation of the right pack bypass valve. The opposite zone (warmest zone) temperature is controlled by modulation of the trim air modulating valve related to that zone. Temperature sensors located in the forward and aft cabin zone and in the forward and aft cabin ducts provide actual temperature via electronic signals to the AMS controller. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 150 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING TWO CABIN ZONE CONFIGURATION ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 151 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING COMPONENTS TRIM MODULATING VALVES The zone trim valves regulate hot bleed flow to the trim ejectors, which are installed in the mixer duct. The valves are electronically controlled and pneumatically operated butterfly valves. The valves are fail-safe closed and can be manually locked in the closed position. The trim ejectors directionally inject hot bleed air into the forward and aft cabin outlet ducts. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 152 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING TRIM MODULATING VALVES ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 153 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING OPERATION During normal operation, the cockpit zone receives airflow from the left air conditioning pack and the left recirculation fan. Under normal operating conditions, the cockpit temperature is controlled by modulation of the left pack bypass valve. Hot pack bypass air is mixed with cold pack discharge air to obtain the desired zone temperature. Two temperature sensors each located in the cockpit zone and in the cockpit duct provide electronic signals to the AMS controller. Each temperature sensor contains two independent sensing elements which provide electronic signals to channel 1 and channel 2 of the AMS controller. This provides for redundancy so that failure of an individual sensing element will have no effect on cockpit temperature control. Using feedback from the temperature selector and the temperature sensors the AMS controller will then change the left air conditioning pack outlet temperature to achieve the desired cockpit zone temperature. The AMS controller compares the selected cockpit temperature to the actual cockpit zone temperature. The difference between the selected temperature and the actual cockpit temperature is used to calculate a target cockpit zone duct temperature. The AMS controller will then modulate the left pack bypass valve to meet the target cockpit zone duct temperature. Temperature sensors located in the forward and aft cabin zone and in the forward and aft cabin ducts provide actual temperature via electronic signals to the AMS controller. The AMS controller compares the selected zone temperatures to actual zone temperatures. The difference between the selected temperature and the actual zone temperature is used to calculate a target duct temperature for both the forward and aft cabin zone ducts. The AMS controller will then modulate the right pack bypass valve, via the torque motor command, to meet the coldest cabin duct target temperature. The trim bypass valve for the coldest zone will be sent a signal to close. The AMS controller will then modulate the opposite zone trim modulating valve to meet the warmest cabin duct target temperature. The trim air system utilizes two trim air modulating valves, two hot air ejectors, and associated ducting to independently control the air temperature entering the forward and aft passenger cabin distribution ducts. This is accomplished by mixing hot air from the ejectors directly into the forward and aft distribution duct openings within the mixing duct. The amount of hot air flowing to the ejectors is controlled electronically by the AMS controller through modulation of two trim air modulating valves. The passenger cabin temperature is selected by the flight crew using the PAX CABIN selector on the AIR COND / PNEUMATIC control panel. The forward and aft passenger cabin zone temperatures can be selected by the flight attendant using CABIN TEMPERATURE selectors located on the attendant control panels. The passenger cabin zone requiring the coldest air is controlled by modulation of the right pack bypass valve. The opposite zone (warmest zone) temperature is controlled by modulation of the trim air modulating valve related to that zone. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 154 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING AUTOMATIC TEMPERATURE CONTROL ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 155 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING DIAGNOSTIC AND TEST TEMP CONTROL AND TRIM CONTRL PARAMETERS This CMC page provides PACK health monitoring, by monitoring temperatures at different stages of the air cycle machine. Diagnostic page also shows the selected and actual flight deck and passenger cabin temperatures. Second diagnostic pages provide valve position for monitoring. For example 15 different status for AMS( bleed valve ) position. ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 156 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING CMC DIAGNOSTIC ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 157 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING ATA 21-00 MEL ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 158 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MEL - EXAMPLE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 159 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MEL - EXAMPLE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 160 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MEL - EXAMPLE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 161 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MEL - EXAMPLE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 162 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING MEL – EXAMPLE ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 163 Embraer ERJ-190 Series (GE CF34) B1.1. and B2 ATA 21 AIR CONDITIONING THIS PAGE IS INTENTIONALLY LEFT BLANK ISSUE 1, 24 Sep 2014 FOR TRAINING PURPOSES ONLY Page: 164