2 3 4 5 6 7 8 COMPUTERORIGINAL 1 A A B B CONTROL VOLTAGE. : 110/220 VDC MOTOR VOLTAGE. : 240 VAC C C HEATER VOLTAGE. : 240 VAC ITEM ABREVIATIONS :- DM:- DENSITY MONITOR OM:- OPERATING MECHANISM. D LOCAL REMOTE SWITCH IN REMOTE POSITION. CIRCUIT BREAKER IN " OFF " POSITION. AUXILIARY CIRCUIT " OFF " . DRAWN WITHOUT GAS PRESSURE. SPRING DISCHARGED. B AS PER CLIENT COMMENT. Revision Details E DIAGRAM BASED ON IEC 617. C AS PER CLIENT COMMENT. D NOTE :- WIRING TO BE DONE WITH CU.WIRE (GREY FOR DC CKT. BLACK FOR AC CKT. , GREEN + YELLOW FOR EARTHING. ) 1:- 2.5 SQ. MM. FOR CONTROL CKT. E 2:- 2.5 SQ. MM. FOR MOTOR CKT. 3:- 4.0 SQ. MM. FOR DOOR & PANEL EARTHING . F We reserve all rights in this document and in the information contained there in reproduction, use or disclousure to third porties without express outhority is strictly forbidden © ABB. 4:- ALL EMPTY MOUNTING HOLES TO BE BLOCKED WITH RUBBER GROMMAT. TERMINAL FOR CUSTOMER CONNECTION. - QUANTITY OF EACH COMPONENT IN BILL OF MATERIAL IS 1 NO. - S FOR :- SPARE TERMINAL. - TERMINAL ARRANGEMENT IS FOR INDICATING PURPOSE & MAY CHANGED DURING SUPPLY. Revision C 20110214 1 PO NO. : RRVPNL/SE/SSPC/XEn(S/G)/A1/ TN-2916/ABB/D.3975, DTD. 31.01.2011. 2 3 F SCHEMATIC DIAGRAM FOR 145kV SF6 CIRCUIT BREAKER TYPE LTB 145D1/B WITH FSA1 4 DRAWN. NS CHECKED. KD APPRD. BAC TOTAL SH ABB Limited 5 6 6 REF.DRG.NO.SKLTB20091209-3 7 1HYB903013-3 SH. NO. 1 8 2 K1+ -X1 33 1 -X1 10 -X1 7 -S12 -X1 50 10 44 K22 -K2 K14 34 20 16 -X1 -X1 3 -K2 -XO 32 K24 K14 22 K1+ 2 K14 -X1 17 33 PRE CLOSE TRIP CIRCUIT-I SUPERVISION. 11 -K1 14 -XO 12 -X1 -X1 13 PRE CLOSE TRIP CIRCUIT -II SUPERVISION. -X1 12 03 -X1 42 -K4 14 5 3 K 12 14 -K3 /3.F5 -X1 3 J4- 3 TRIP CKT.-I ANTIPUMPING PO NO. : RRVPNL/SE/SSPC/XEn(S/G)/A1/ TN-2916/ABB/D.3975, DTD. 31.01.2011. 2 3 SCHEMATIC DIAGRAM FOR 145kV SF6 CIRCUIT BREAKER TYPE LTB 145D1/B WITH FSA1 4 4 K3- K3- K3- -F12 SF6 SUPERVISION FOR CLOSE & TRIP CKT-I CHECKED. DRAWN. NS KD F TRIP CKT-II APPRD. BAC TOTAL SH REF.DRG.NO.SKLTB20091209-3 6 SH. NO. 1HYB903013-3 ABB Limited 5 2 A2 K3K2- E -Y3 -K6 A2 -F11 CLOSING CKT. K35 L8 A2 K2- -X1 1 A1 A1 INDICATION -K4 -K2 K2- 38 45 K2- K2- -X1 23 K2- 39 -X1 DC FAIL-II A1 K2- K2- A1 A2 K2- K2- -X1 DC FAIL-1 2 K2- A2 14 K35 12 -X1 43 INDICATION -Y2 -K1 2 K30 K25 -X1 1 -S1 K35 -K3 37-X1 -S1 L7 L5 K25 14 13 91 11 L6 36 K19 K17 -Y1 We reserve all rights in this document and in the information contained there in reproduction, use or disclousure to third porties without express outhority is strictly forbidden © ABB. -X1 5 2 K A1 25 -X1 15 92 11 04 K25 K25 82 K19 Revision Details 1 -VE POST CLOSE TRIP CIRCUIT-II SUPERVISION. D 44 -S1 K19 08 K19 1 C K3- 81 -S1 -S1 02 C 20110214 21 K34 -X1 Revision -X1 K36 K26 07 -S1 F 12 K24 K16 D 24 K2- 14 42 K34 POST CLOSE TRIP CIRCUIT-I SUPERVISION. 22 01 -X1 44 K35 24 4 32 33 K34 K15 K14 6 2 J2- 3 -K6 -K6 K24 -S3 -K1 -X1 B 11 41 31 -F2 K24 23 31 -XO 21 21 -F2 23 21 E K32 42 -XO 110/220 VDC DC SUPPLY-I C 51 -S12 31 5 A K31 9 -K2 8 11 K14 -X1 11 41 -S12 K12 12 PROTECTION TRIP CKT.-II K32 5 K22 14 41 K33 3 6 27 -X1 REMOTE TRIP CKT.-II PROTECTION TRIP CKT.-I REMOTE TRIP CKT.-I 4 K11 K11 K33 K32 -S13 4 K11 K11 K33 K33 2 K34 B 26 J3+ 1 -F12 K22 ISOLATOR INTERLOCK -X1 -S13 T N -S12 2 40 K33 -S12 -X1 C 2 1 REMOTE -X1 K3- K10 9 /3.D5 34 K21 -X1 22 K1+ 4 N -X1 K1+ K1+ 8 3 T REMOTE CLOSE K1+ K33 -X1 C LOCAL K1+ 110/220 VDC DC SUPPLY-II +VE K1+ 1 -F11 K1+ 7 K1+ 2 K24 1 6 K1+ J1+ 5 K22 1 4 K23 A -X1 3 K18 COMPUTERORIGINAL 1 6 7 2 8 2 -X1 4 6 -X1 H1 240V AC 7 H1 8 6 -X1 H2 -X1 31 7 8 -X1 29 18 A H1 H1 M1 -X1 5 H2 240V AC 5 M2 A -X1 3 H1 COMPUTERORIGINAL 1 H2 L10 47 -F2 H4 2 H4A L -X1 32 111 109 113 115 117 121 119 125 123 127 129 131 -X3 53 61 71 63 73 83 301 201 -S1 203 42 52 44 62 54 72 64 74 302 84 202 +OM -L1 204 -X3 102 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 1 2 3 SCHEMATIC DIAGRAM FOR 145kV SF6 CIRCUIT BREAKER TYPE LTB 145D1/B WITH FSA1 4 K48 X1 X1 +OM -L2 -X1 49 X2 D E LAMP RED X2 K2- K2- -X3 SPARE AUXILIARY SWITCH CONTACTS(8 NO+ 8 NC) PO NO. : RRVPNL/SE/SSPC/XEn(S/G)/A1/ TN-2916/ABB/D.3975, DTD. 31.01.2011. 19 K2- U82 U80 U78 U76 U74 U72 U64 U62 U54 U52 U44 U42 U34 U32 U24 U22 K2- 34 K2- 32 /2.F5 C 20110214 94 K49 LAMP GREEN Revision SF6 PRESSURE BLOCKING 93 11 -S1 24 -X1 48 12 22 C K1+ K1+ U81 U79 U77 U75 U73 U71 U63 U61 U53 U43 U41 U33 U31 U23 U21 U51 51 43 -S1 Revision Details We reserve all rights in this document and in the information contained there in reproduction, use or disclousure to third porties without express outhority is strictly forbidden © ABB. F 41 12 30 K1+ K1+ -S1 E 32 33 ALARM -X1 33 -XO SF6 GAS REPLENISHEMENT ALARM AT 0.62 Mpa (abs.) 107 31 22 6.0 bar(abs.) 0.6 MPa(abs) N /2.A5 23 23 31 TRIP-II BLOCK 0.6 Mpa (abs.) H2 1 D 21 6.0 bar(abs.) 0.6 MPa(abs) CLOSING/TRIP I BLOCK 0.6 Mpa ( abs.) H5 -X1 HEATER / ILLUMINATION / SOCKET (OUTLET) 105 21 6 H2A -PP -L L4 2 L2 INDICATION 103 12 13 SPRING CHARGING MOTOR 101 6.2 bar(abs.) 0.62 MPa(abs) /2.C7 11 C -X3 B 22 SPRING CHARGING INDICATION ~ M4 11 -R3 H2A F 24 1 AC FAIL M L3 8 M4 M5 -M1 -XO -K2 /2.C5 2 4 M5 A 2 21 -S3 H4A <0 22 -X1 -M 5 L9 -K5 -S3 2 1 -T1 3 -S3 7 H4 -K5 1 4 H2 M1A A2 -F5 2 H6A M3 A1 21 M1A M3 -F5 4 2 3 1 M1A M3 4 1 -F4 -F4 -F3 2 B 46 H5 -F3 -X1 L1 3 3 1 H2A 1 DRAWN. BREAKER ON/OFF INDICATION CHECKED. KD NS APPRD. BAC TOTAL SH REF.DRG.NO.SKLTB20091209-3 6 SH. NO. 1HYB903013-3 ABB Limited 5 F F2-SF6 GAS DENSITY MONITOR 6 7 3 8 F Revision C 20110214 1 2 3 PO NO. : RRVPNL/SE/SSPC/XEn(S/G)/A1/ TN-2916/ABB/D.3975, DTD. 31.01.2011. 4 SCHEMATIC DIAGRAM FOR 145kV SF6 CIRCUIT BREAKER TYPE LTB 145D1/B WITH FSA1 DRAWN. 5 NS CHECKED. X1 :- SUPPLY & CUSTOMER CONNECTION TERMINALS. X3 :-AUX. SPARE CONTACT TERMINALS. KD 6 APPRD. BAC ABB Limited 7 DC SUPPLY-I DC SUPPLY-II MOTOR SUPPLY HEATER SUPPLY +VE -VE L N L N X1 125 E I I E REF.DRG.NO.SKLTB20091209-3 1HYB903013-3 8 TERMINAL : CATM3 MAKE : ELMEX 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 X3 7 TERMINAL : CATM3 MAKE : ELMEX 1 2 3 4S 5 6 7 8 9 33 10 34 11 41 12 13 14 15 127 126 6 REMOTE CLOSE REMOTE TRIP CKT.-I REMOTE TRIP CKT.-II PRE CLOSE TRIP CKT.-I SUPERVISION POST CLOSE TRIP CKT.-I SUPERVISION POST CLOSE TRIP CKT.-II SUPERVISION PRE CLOSE TRIP CKT.-II SUPERVISION 16 17 18 19 20 21 22 23 128 129 130 131 132 5 F2-21 F2-23 F2-11 F2-12 F2-31 F2-33 D 24 25 26 27 29 133S 134S 135S 136S 137S 138S X3 4 SF6 DENSITY MONITER ISOLATOR INTERLOCK SF6 PRESSURE BLOCKING 30 31 32 36 37 38 139S 140S 141S 142S 143S 144S 145S 146S 147S 3 39 40 42 43 44 45 46 47 48 B B 49 50 X1 2 51 52S 53S 54S 55S 56S 57S 58S 59S 60S A COMPUTERORIGINAL A SPRING CHARGING INDICATION Revision Details E We reserve all rights in this document and in the information contained there in reproduction, use or disclousure to third porties without express outhority is strictly forbidden © ABB. 1 8 A B C SPARE CONTACTS AUXILIARY SWITCH C TERMINAL ARRANGEMENT IN OPERATING MECHANISM TOTAL SH SH. NO. 6 4 D E S :- FOR SPARE TERMINAL . F 2 COMPUTERORIGINAL 1 A B C F We reserve all rights in this document and in the information contained there in reproduction, use or disclousure to third porties without express outhority is strictly forbidden © ABB. E Revision Details D 3 4 5 6 7 8 (CONTROL VOLTAGE : 110 VDC, MOTOR VOLTAGE : 240 VAC, HEATHER VOLTAGE : 240 VAC) A 1 +DM-F2 SF6 GAS DENSITY MONITOR TRAFAG/SANGHAI ROYE ELECTRIC 10A,UP TO 250VDC 1HYB400202-1 2 +DM-XO(6) TERMINAL BLOCK IN DM --- --- --- --- 1HYB902293-14 3 +OM-EX1 EXTRA ELECTRIC PLATE --- 4 +OM-F3 2 POLE MCB-MOTOR ABB/SIEMENS 3A,110 V DC/110-250 V AC,TYPE-S272C-3 GHS2720001R0034 5 +OM-F4 2 POLE MCB-HEATER ABB/SIEMENS 6 A,110 VDC/110-250 V AC,TYPE-S272C-6 GHS2720001R0064 6 +OM-F5 2 POLE MCB-SUPPLY SOCKET ABB/SIEMENS 6 A,110 VDC/110-250 V AC,TYPE-S272C-6 GHS2720001R0064 7 +OM-F11 2 POLE MCB-DC SUPPLY-I ABB/SIEMENS 110 V DC,UPTO 250 V AC,16A,TYPES272C16 GHS2720001R0164 8 +OM-F12 2 POLE MCB-DC SUPPLY-II ABB/SIEMENS 110 V DC,UPTO 250 V AC,16A,TYPES272C16 GHS2720001R0164 9 +OM-K1 ANTI PUMPING RELAY ABB/SCHRACK/RELECO 3C/O,10A:110VDC,TYPE-CR-M(110DC3 +2SS+H1) 1SVR(405612R8000+405651R2000+405659R1100) 10 +OM-K2 GAS SUPERVISION RELAY I ABB/SCHRACK/RELECO 4C/O,6 A,110VDC,TYPE-CR-M(110DC4 +2SS+H1) 1SVR(405613R8000+405651R3000+405659R1100) 11 +OM-K3 DC SUPPLY-I FAILURE RELAY ABB/SCHRACK/RELECO 2C/O,12A:110VDC,TYPE-CR-M(110DC2 +2SS+H1) 1SVR(405611R8000+405651R1000+405659R1100) 12 +OM-K4 DC SUPPLY-II FAIL. RELAY ABB/SCHRACK/RELECO 2C/O,12A:110VDC,TYPE-CR-M(110DC2 +2SS+H1) 1SVR(405611R8000+405651R1000+405659R1100) 13 +OM-K5 AC FAILURE CONTACTOR 240V AC,TYPE-CS3-22E 1HYN700038P63 14 +OM-K6 GAS SUPERVISION RELAY II ABB/SCHRACK/RELECO 2C/O,12A:110VDC,TYPE-CR-M(110DC2 +2SS+H1) 1SVR(405611R8000+405651R1000+405659R1100) 15 +OM-L IILUMINATION LAMP BAJAJ/PHILIPS/CGL/GELECO 240V AC,5W --- 16 +OM-L1 SIGNAL LAMP LED GREEN TEKNIC/SIEMENS 110 V DC,TYPE-2PLBR3L110DC/3SB1402-2AZ2 1HYN400053P416/P316 17 +OM-L2 SIGNAL LAMP LED RED TEKNIC/ SIEMENS 110 V DC,TYPE-2PLBR4L110 DC/3SB1401-2AZ2 1HYN400053P417/P317 18 +OM-M DOOR LIMIT SWITCH KAYCEE/BOHMEN 5A,250VAC SWT-331491-P2 19 +OM-M1 SPING CHARGING MOTOR AGNI/SAHAT 735W,240VAC/DC,TYPE:UNIVERSAL EXIN300802 20 +OM-PP SOCKET(OUTLET) CGL (SCHNEIDER) 10 A,240 V AC,TYPE-AS10. SWT-331700-P326+SWT-331700-P327 21 +OM-R3 HEATER RVM/KIYOSH/RS COMPONENT 240 V AC,50 W MT-430162-P17 22 +OM-S1 AUXILIARY CONTACT ELMEX 220V-4A,TIME-20ms 1HYN300003R1 23 +OM-S3 MOTOR LIMIT SWITCH ELMEX 10A,250VDC 1HYN700023R1/R2 24 +OM-S12 LOCAL REMOTE SWITCH SALZER/KAYCEE 12A: VOLTAGE UPTO 250VDC EXIN400518P1 25 +OM-S13 CONTROL S/W TRIP CLOSE SALZER/KAYCEE 12A : UPTO 250V DC EXIN400517P1 26 +OM-T1 THERMOSTAT 0-60 DEGREE CENTIGRADE ---- 27 +OM-X1(58) TERMINAL BLOCK-CATM3 ELMEX/CONNECTWELL 32A,800V,4 SQ MM/0.5Nm ,TYPE-CAT M3 --- 28 +OM-X3(47) TERMINAL BLOCK-CATM3 ELMEX/CONNECTWELL 32A,800V,4 SQ MM/0.5Nm ,TYPE-CAT M3 --- 29 +OM-Y1 CLOSE COIL ABB 500W --- 30 +OM-Y2 TRIP-I COIL ABB 500W --- 31 +OM-Y3 TRIP-II COIL ABB 500W --- SPRECHER AND SCHUH/SIEMENS/ABB APT CONTROLS AND APPLIANCES PVT. LTD. OR EQUI. B C D E F Revision C 20110214 1 PO NO. : RRVPNL/SE/SSPC/XEn(S/G)/A1/ TN-2916/ABB/D.3975, DTD. 31.01.2011. 2 3 APPARATUS LISTS FOR 145kV SF6 CIRCUIT BREAKER TYPE LTB 145D1/B WITH FSA1 4 DRAWN. NS CHECKED. KD APPRD. BAC TOTAL SH REF.DRG.NO.1HYB903013-3 1HYB903013-3 ABB Limited 5 6 6 7 SH. NO. 5 8 2 COMPUTERORIGINAL 1 A B C F We reserve all rights in this document and in the information contained there in reproduction, use or disclousure to third porties without express outhority is strictly forbidden © ABB. E Revision Details D 3 4 5 6 7 8 (CONTROL VOLTAGE : 220 VDC, MOTOR VOLTAGE : 240 VAC, HEATHER VOLTAGE : 240 VAC) A 1 +DM-F2 SF6 GAS DENSITY MONITOR TRAFAG/SANGHAI ROYE ELECTRIC 10A,UP TO 250VDC 1HYB400202-1 2 +DM-XO(6) TERMINAL BLOCK IN DM --- --- --- --- 1HYB902293-14 3 +OM-EX1 EXTRA ELECTRIC PLATE --- 4 +OM-F3 2 POLE MCB-MOTOR ABB/SIEMENS 3A,110 V DC/110-250 V AC,TYPE-S272C-3 GHS2720001R0034 5 +OM-F4 2 POLE MCB-HEATER ABB/SIEMENS 6 A,110 VDC/110-250 V AC,TYPE-S272C-6 GHS2720001R0064 6 +OM-F5 2 POLE MCB-SUPPLY SOCKET ABB/SIEMENS 6 A,110 VDC/110-250 V AC,TYPE-S272C-6 GHS2720001R0064 7 +OM-F11 2 POLE MCB-DC SUPPLY-I ABB/SIEMENS 10A,250V DC,TYPE-S282UCK-10 GHS2820164R0427 8 +OM-F12 2 POLE MCB-DC SUPPLY-II ABB/SIEMENS 10A,250V DC,TYPE-S282UCK-10 GHS2820164R0427 9 +OM-K1 ANTI PUMPING RELAY ABB/SCHRACK/RELECO 3C/O,10A:220VDC,TYPE-CR-M(220DC3 +2SS+H1) 1SVR(405612R9000+405651R2000+405659R1100) 10 +OM-K2 GAS SUPERVISION RELAY I ABB/SCHRACK/RELECO 4C/O,6 A,220VDC,TYPE-CR-M(220DC4+2SS+H1) 1SVR(405613R9000+405651R3000+405659R1100) 11 +OM-K3 DC SUPPLY-I FAILURE RELAY ABB/SCHRACK/RELECO 2C/O,12A:220VDC,TYPE-CR-M(220DC2 +2SS+H1) 1SVR405611R9000+405651R1000+405659R1100 12 +OM-K4 DC SUPPLY-II FAIL. RELAY ABB/SCHRACK/RELECO 2C/O,12A:220VDC,TYPE-CR-M(220DC2 +2SS+H1) 1SVR405611R9000+405651R1000+405659R1100 13 +OM-K5 AC FAILURE CONTACTOR 240V AC,TYPE-CS3-22E 1HYN700038P63 14 +OM-K6 GAS SUPERVISION RELAY II ABB/SCHRACK/RELECO 2C/O,12A:220VDC,TYPE-CR-M(220DC2 +2SS+H1) 1SVR405611R9000+405651R1000+405659R1100 15 +OM-L IILUMINATION LAMP BAJAJ/PHILIPS/CGL/GELECO 240V AC,5W --- 16 +OM-L1 SIGNAL LAMP LED GREEN TEKNIC/SIEMENS 220 V DC,TYPE-2PLBR3L230DC/3SB1402-2LZ2 1HYN400053P402/P302 17 +OM-L2 SIGNAL LAMP LED RED TEKNIC/ SIEMENS 220 V DC,TYPE-2PLBR4L230 DC/3SB1401-2LZ2 1HYN400053P403/P303 18 +OM-M DOOR LIMIT SWITCH KAYCEE/BOHMEN 5A,250VAC SWT-331491-P2 19 +OM-M1 SPING CHARGING MOTOR AGNI/SAHAT 735W,240VAC/DC,TYPE:UNIVERSAL EXIN300802 20 +OM-PP SOCKET(OUTLET) CGL (SCHNEIDER) 10 A,240 V AC,TYPE-AS10. SWT-331700-P326+SWT-331700-P327 21 +OM-R3 HEATER RVM/KIYOSH/RS COMPONENT 240 V AC,50 W MT-430162-P17 22 +OM-S1 AUXILIARY CONTACT ELMEX 220V-4A,TIME-20ms 1HYN300003R1 23 +OM-S3 MOTOR LIMIT SWITCH ELMEX 10A,250VDC 1HYN700023R1/R2 24 +OM-S12 LOCAL REMOTE SWITCH SALZER/KAYCEE 12A: VOLTAGE UPTO 250VDC EXIN400518P1 25 +OM-S13 CONTROL S/W TRIP CLOSE SALZER/KAYCEE 12A : UPTO 250V DC EXIN400517P1 26 +OM-T1 THERMOSTAT 0-60 DEGREE CENTIGRADE ---- 27 +OM-X1(58) TERMINAL BLOCK-CATM3 ELMEX/CONNECTWELL 32A,800V,4 SQ MM/0.5Nm ,TYPE-CAT M3 --- 28 +OM-X3(47) TERMINAL BLOCK-CATM3 ELMEX/CONNECTWELL 32A,800V,4 SQ MM/0.5Nm ,TYPE-CAT M3 --- 29 +OM-Y1 CLOSE COIL ABB 500W --- 30 +OM-Y2 TRIP-I COIL ABB 500W --- 31 +OM-Y3 TRIP-II COIL ABB 500W --- SPRECHER AND SCHUH/SIEMENS/ABB APT CONTROLS AND APPLIANCES PVT. LTD. OR EQUI. B C D E F Revision C 20110214 1 PO NO. : RRVPNL/SE/SSPC/XEn(S/G)/A1/ TN-2916/ABB/D.3975, DTD. 31.01.2011. 2 3 APPARATUS LISTS FOR 145kV SF6 CIRCUIT BREAKER TYPE LTB 145D1/B WITH FSA1 4 DRAWN. NS CHECKED. KD APPRD. BAC TOTAL SH REF.DRG.NO.1HYB903013-3 1HYB903013-3 ABB Limited 5 6 6 7 SH. NO. 6 8