Tutorial Harmonic Analysis CYME 7.0 Power Engineering Software This tutorial provides a guideline on how to perform a harmonic analysis on a network file provided with this tutorial. Getting Started 1. Launch the program. 2. Open the file by clicking on the Icon of the Main toolbar and select the self contained study file provided with the Harmonic Analysis tutorial, Harmonic.sxst. Network Description This is a 13-bus system representative of a medium-sized network operating at 13.8 kV and fed from a utility supply at 69 kV. The system is composed of multiple transformers, cables, in-plant generator, variable frequency drive (VFD) generating harmonic currents and a power factor correction capacitor. © CYME International, October 2013 Variable Frequency Drive 1. Go to Equipment > Harmonic > Frequency Source. The variable frequency drive is represented by a multi-frequency current source rated at 3.2 MVA, connected on all three phases and has a Y-g configuration. 2. The harmonic spectrum generated by this drive, and as measured on site, are as per the details on the table to the right. CYME 7.0 Tutorial – Harmonic Analysis Page 2 Harmonic Analysis The objective of a Harmonic Analysis program is to analyze the effect of the harmonic currents and limit their effect on the network to within acceptable limits as specified in the IEEE 519-1992 standard. 1. Select Harmonic Analysis from the list of available analyses in the Simulation toolbar. You can also launch it from Analysis > Harmonic. 2. Click on the Run Simulation icon in the Simulation toolbar. 3. The Harmonic Analysis dialog box is comprised of four tabs as follows: Global Settings to select analysis type, line, cable, load models, overwrite individual harmonic settings of equipment with global settings and whether to include or not the skin effects of the synchronous machines in the analysis. Impedance Calculation at any bus or node and plot the impedance as a function of frequency to check for possible resonance conditions. Voltage and Current distortion analysis, distortion limits and report options setting. Capacitor Rating to check which capacitors in the system are experiencing overloads due to the presence of harmonic currents in the network. CYME 7.0 Tutorial – Harmonic Analysis Page 3 Voltage and Current Distortion Analysis 1. Select the Buses that are to be monitored and the results to be displayed on the one line diagram. Select bus PRI_69kV, B3, B8 (VFD Bus) and the SEC_13.8kV bus. 2. Click on the Distortion Limits button. 3. Select the IEEE 519-1992 standard defaults for Individual (IHD) and Total Harmonic Distortion (THD) for the voltage range specified. 4. Click on the Report Options button. 5. Set the Voltage Report Options as shown in the illustration to the right. Normal Condition Tags will be applied to buses within the Harmonic Distortion Limits specified and Abnormal Condition Tag is for buses that exceed the limit. 6. You can click on the button to run the Voltage Distortion Analysis or you can set the Frequency Scan parameters and run both analysis at the same time and plot the desired charts. Notes You can also select any branch to monitor the current distortions and display the results on the One Line Diagram of the network. For the purpose of this tutorial we will run a voltage distortion analysis simultaneously with a frequency scan analysis. CYME 7.0 Tutorial – Harmonic Analysis Page 4 Frequency Scan Analysis 1. Select the Bus that is to be included in the Impedance Calculation analysis: the SEC_13.8kV bus which is also the location of the 6MVAR Capacitor. 2. Set the range of the Frequency Scan “From” the lowest frequency which corresponds to our 60 Hz fundamental up “To” a frequency that includes the highest 37th harmonic frequency generated by the VFD drive. 3. Select steps of 5 Hz to generate a smooth plot of the impedance plots. 4. Select the Phase impedances for the plots. 5. Click on the Global Settings tab to set the parameters for the relevant network components such as. 6. Use the Series R-L Model for cables since they are relatively short. Model Loads as Parallel R-L. Ignore the Skin Effect of the synchronous machines. Click on the button to run both analysis Voltage Distortion and Frequency Scan. Note: The Program will first run a power flow to obtain the Fundamental Frequency Voltage and Current profile of the Network. This is a necessary step in order to obtain meaningful harmonic distortion results. CYME 7.0 Tutorial – Harmonic Analysis Page 5 Plotting and Interpretation of Results 1. Once the analysis is completed the CYMVIEW chart selector dialog box will be displayed on screen. 2. Plot the Impedance Scan and Voltage Waveform at Bus SEC_13.8kV. 3. The Impedance Plot indicates possible resonance condition around the 7th harmonic. 4. The voltage waveform has considerable distortion which suggests a Total Harmonic Distortion (THD) level that exceeds the maximum allowable at the bus which is set at 5%. 5. You can view the results of the Harmonic Analysis on the one line diagram that will now have result labels for the monitored buses as specified in the voltage distortion analysis. CYME 7.0 Tutorial – Harmonic Analysis Page 6 6. As can be noticed, the results indicate that the SEC_13.8kV bus has a THD of 5.37% which is beyond the acceptable limit. 7. To solve this problem, a filter that can tune out those harmonics to within acceptable limits can be installed. Single Tuned Filter at Capacitor Location 1. Go to Equipment > Harmonic > Single Tuned Filter and create a new equipment ID “STF”. 2. The objective is to tune the existing capacitor and therefore you need to enter its rating of 6 MVAR at 13.8 KV L-L. 3. Although the resonance is at the 7th harmonic installing a filter tuned to that frequency does not improve the situation since it will create a peak close to the 5th which has a higher harmonic current content. (Refer to VFD Drive Harmonic Content Table). 4. The tuned frequency of the filter will be set at the 5th harmonic and the configuration of the filter will be Y-g to match the configuration of the capacitor. 5. To compute the corresponding R, L and C values of the filter click on the button. 6. The dialog box that will be displayed will have all the information as entered in the General tab except for the filter quality factor. Select a high quality filter like 999; which effect is to neglect the resistance R of the filter. 7. Click on the button and the R, L and C fields of the General tab will be updated with the computed values. 8. Click on OK in the Single Tuned Filter dialog box to close it. CYME 7.0 Tutorial – Harmonic Analysis Page 7 9. From the Harmonic group of the Symbol bar tab of the Explorer bar, select the single tuned filter in the Harmonic Analysis symbol bar, drag and connect to the SEC_13.8kV bus. 10. Once the left hand mouse button is released the STF dialog will be displayed on screen. 11. Select the single tuned filter ID “STF” from the equipment database. 12. Make sure that you switch “OFF” the 6 MVAR-CAP. Voltage Distortion and Frequency Scan with the STF Installed 1. Run the Voltage Distortion and the Frequency Scan Analysis with the STF connected to the SEC_13.8kV bus. 2. Plot the Impedance Scan and Voltage Waveform at bus SEC_13.8kV. 3. The Impedance Plot Indicates that the installation of the filter tuned out the 5th harmonic at the bus and at the same time provided an attenuation of the impedance at the 7th harmonic. 4. The Voltage Waveform does not have any noticeable distortion level which suggests a Total Harmonic Distortion (THD) level that is within the Maximum allowable 5%. CYME 7.0 Tutorial – Harmonic Analysis Page 8 5. The results labels on the one line diagram confirm that the THD on the SEC_13.8kV bus is now at 0.84 %. Analysis Reports 1. If the Voltages and Distortion Report Options have been checked in the Voltage and Current tab of the Harmonic Analysis dialog box, then the reports will automatically be displayed on screen once the analysis is complete. 2. These reports include information such as: Individual Harmonic Distortion (IHD) in % for every harmonic frequency present in the system at each monitored bus. Total Harmonic Distortion (THD) in % at each monitored bus. KVT Product (KVT) for each bus, which expresses the inductive influence as the square root of the sum of squares of the weighted RMS values of all the sine-wave voltages (in KV), including the fundamental. The weighting factor Wh applied to voltage is called the “1960 TIF Weighting Value”. Refer to IEEE Standard 519. Telephone Influence Factor (TIF) which is a dimensionless quantity defined as the ratio of the square root of the sum of the squares of the weighted RMS values of all the sine-wave components including the fundamental to the un-weighted RMS value of the entire wave. using voltages in kV. 3. Sample Harmonic Analysis Report CYME 7.0 Tutorial – Harmonic Analysis Page 9