Uploaded by Blaire Daines

Phase 3 Relay Settings

advertisement
PHASE 3
General data and information
Relay Type
F-MPC30/UM45B
Source
DC 100/200V, AC 100V
Serial No.
29302339V5A
Location
Phase 3 Main VCB
CT Ratio
Manufacturer
Year Mfd.
750/5
FUJI Electric FA
2012
Settings
Code
Description
Setting
Code
Description
Setting
00
CT Primary
750
21
51G Curve
0001
02
Frequency
60
22
51G T
2.0
03
Single/Three Phase
3P
23
51G Output
111
10
INST C
2.0
24
50G C
0.4
11
INST Output
111
25
50G T
0.0
12
DT1 C
Loc
26
50G Output
111
13
DT1 T
0.00
27
CT (I ) Primary/residue
Loc
14
DT1 Output
000
28
OCGA A
Loc
15
OC C
80
29
OCGA T
10
16
OC Curve
0001
2A
OCGA Output
00
17
OC T
1.0
63
CB Open T
0.30
18
OC Output
111
65
TC Disconnect Monitor
0
19
OCA A
Loc
70
Input 1
Loc
1A
OCA T
10
80
Unit Alarm Select
1
1b
OCA Output
00
81
Ry Detection (common)
Loc
o
1c
DT2 C
Loc
82
Transmission 1
Loc
1d
DT2 T
0.0
83
Transmission 2
Loc
1E
DT2 Output
000
90
RS485 Address
Loc
20
51G C
0.20
91
RS485 Transmission
b192E
Download