POWERHOUSE MAIN SWITCHGEAR AND GENSET POSSIBLE INVERTER AREA C:\Users\MATEC - DESIGN\Desktop\Coca-Cola Cebu\09 26 2019\C COCA COLA (CEBU) No. of 380Wp Modules: 2160 pcs. DC Power Input: 820.8 kWp AC Power Output: 675 kVA DC/AC: 1.22 PV MODULE LAYOUT Notes: SCALE NTS 1. This design is not final and is issued for information only. 2. Roof layout is subject to change as per actual site condition. CONTRACTOR / CONSULTANT: MATEC PROPERTY PROFESSIONAL ELECTRICAL ENGINEER : OWNER'S ENGINEER : OWNER : Maschinen & Technik, Inc. Tech Center, Buencamino St.,Alabang Muntinlupa City 1770 Tel. Nos.: (+63 2) 850 6450 - 52 Fax No.: (+63 2) 850 3631 Email add.: Website: www.solar-philippines.com PROJECT TITLE : REV. No. DESCRIPTION DATE INITIAL SHEET NO.: 1 of 2 SHEET CONTENT: APPROVED BY: PRC No. : VALIDITY : PTR No. : DATE ISSUED : TIN No. : ISSUED AT : COCA COLA (CEBU) 820.8 kWp GRID-TIED PV SYSTEM PROJECT LOCATION : CEBU CITY RI ISSUED FOR INFORMATION 09-26-2019 JEV CHECKED BY: LLJ DRAWN BY: JEV DATE : 09-26-2019 PV MODULE LAYOUT DWG. No. : 2180 pcs x 380Wp Risen Solar Modules 10 x 20 Nos. 10 x 20 Nos. 10 x 20 Nos. 10 x 20 Nos. 10 x 20 Nos. 10 x 20 Nos. 10 x 20 Nos. 10 x 20 Nos. 10 x 20 Nos. 9 x 20 Nos. 9 x 20 Nos. TIGO TS4-R (FOR RAPID SHUTDOWN) TIGO ACCESS POINT 2-6mm² SOLAR CABLE + 1-5.5mm² THHN CPC DC FUSE BOX 15 A, 1000 VDC FUSE 2-6mm² SOLAR CABLE + 1-5.5mm² THHN CPC Inv. 1 Inv. 2 Inv. 3 Inv. 4 Inv. 5 Inv. 6 Inv. 7 Inv. 8 Inv. 9 SG60KU-M SG60KU-M SG60KU-M SG60KU-M SG60KU-M SG60KU-M SG60KU-M SG60KU-M SG60KU-M Inv. 10 SG60KU-M Inv. 11 60KVA SUNGROW INVERTERS SG60KU-M 4 - 30mm² THHN Cu + 1 - 14mm² THHN CPC 100AT 3Ø 100AT 3Ø 100AT 3Ø 100AT 3Ø 100AT 3Ø 100AT 3Ø 100AT 3Ø 100AT 3Ø 100AT 3Ø 100AT 3Ø 100AT 3Ø 23 kV SUPPLY FROM VECO 1200AT 3Ø PV-ACDB *With Pilot Lamps, TVSS, EFR NOTE: a. Shutting off of main ECB will automatically initiate Rapid Shutdown of the system. 3 SETS OF 4 - 250mm² THHN Cu + 1 - 50mm² THHN CPC 1200AT 3Ø TIGO CLOUD CONNECT ADVANCED ROUTER 3 SETS OF 4 - 250mm² THHN Cu + 1 - 50mm² THHN CPC MONITORING UNIT 750 kVA Dry-Type Transformer 480/277V (Sec. Wye-N) 240V (Pri. Wye) 60Hz 2500AT 3Ø 10A 2500AT 3Ø VCB 2 VCB 1 1.5 MVA 2 MVA 1600/5 CL 1 4000/5 CL 1 700 kVA 4000/5 CL 1 Metering CT POWER CENTER # 4 POWER CENTER # 1 POWER CENTER # 2 POWER CENTER # 3 LOAD LOAD LOAD 6 SETS OF 4 - 250mm² THHN Cu + 1 - 50mm² THHN CPC TAPPING POINT 3.5 mm² THHN Cu CABLES Notes: SINGLE LINE DIAGRAM 1. This design is not final and is issued for information only. 2. Tapping point in this design is on the secondary output of the largest size of transformer rated @ 440V. Final tapping point to be finalized. CONTRACTOR / CONSULTANT: PROFESSIONAL ELECTRICAL ENGINEER : SCALE NTS MATEC PROPERTY OWNER'S ENGINEER : OWNER : Maschinen & Technik, Inc. Tech Center, Buencamino St.,Alabang Muntinlupa City 1770 Tel. Nos.: (+63 2) 850 6450 - 52 Fax No.: (+63 2) 850 3631 Email add.: Website: www.solar-philippines.com PROJECT TITLE : REV. No. DESCRIPTION DATE INITIAL SHEET NO.: 2 of 2 SHEET CONTENT: APPROVED BY: PRC No. : VALIDITY : PTR No. : DATE ISSUED : TIN No. : ISSUED AT : COCA COLA (CEBU) 820.8 kWp GRID-TIED PV SYSTEM PROJECT LOCATION : CEBU CITY RI ISSUED FOR INFORMATION 09-26-2019 JEV CHECKED BY: LLJ DRAWN BY: JEV DATE : 09-26-2019 SINGLE LINE DIAGRAM DWG. No. :