See discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/309286358 Concepts for the Reduction of Low-Frequency Fields near High-Voltage Overhead Transmission Lines Thesis · August 2016 DOI: 10.13140/RG.2.2.28293.55525 CITATIONS READS 0 1,121 1 author: Sumit Kumar Otto-von-Guericke-Universität Magdeburg 1 PUBLICATION 0 CITATIONS SEE PROFILE All content following this page was uploaded by Sumit Kumar on 19 October 2016. The user has requested enhancement of the downloaded file. Otto-von-Guericke-University Magdeburg Faculty of Electrical Engineering and Information Technology Chair for Electromagnetic Compatibility Master Thesis Concepts for the Reduction of Low-Frequency Fields near High-Voltage Overhead Transmission Lines submitted: August 25, 2016 by: Sumit Kumar Mat.No. 204921 born on October 02, 1990 in Bhojpur, India Abstract Although there holds no certain mechanism about the occurence of hazards due to the impact of electromagnetic fields (EMFs) at low frequencies (50 Hz), the adverse effects on human health has been scientifically shown. The low frequency fields has an interference with electrical and electronic equipements in it’s close vicinity. There is a need for the reduction of the magnetic and electric fields of a high voltage line, when it passes through the dense populated area or whenever there is a chance of interference with nearby devices. Recently there is an amendment in 26th Federal Immission Control Ordinance, which has defined the limiting values not only for the fixed frequencies 16 2/3 Hz and 50 Hz, but also for the continuous frequency range from DC to 10 MHz. These limits have to be observed by all low-frequency appliances like high-voltage overhead transmission lines. Transmission line losses must be reduced so that the power system will be more efficient. The proposed work compares low reactance phasing where the conductors of the two circuits, from top to bottom, are arranged in reverse order (abc, c’b’a’) with superbundle phasing, where conductors of the two circuits are arranged in the same order from top to bottom (abc, a’b’c). For both configurations the influence of parameters like line imbalances, line impedances or conductor losses are analyzed and discussed in detail. For numerical configurations softwares like Matlab, the ElectroMagnetic Transients Program, OHTLC and ATPDraw are used. The developed worst-case and best-case configuration are compared in a scaled laboratory demonstration and the advantages of low reactance phasing over superbundle phasing has been explained in detail. i Declaration by the candidate I hereby declare that this thesis is my own work and effort and that it has not been submitted anywhere for any award. Where other sources of information have been used, they have been marked. The work has not been presented in the same or a similar form to any other testing authority and has not been made public. Magdeburg, August 25, 2016 ii Acknowledgment It takes a great pleasure for me to express my sincere gratitude towards Prof. Dr.- Ing. Ralf Vick for providing me the platform to enhance my technical skills in the field of High Voltage Alternating Current technology & Electromagnetic Compatibility. I would like to thanks Dr.-Ing. Mathias Magdowski for his invaluable suggestions, insightful technical information and guidance during the course of this research study. His dedication & sincerity in his field has been a great source of inspiration for me. I would like to thanks personally to Gudiya and Vicky for always motivating me to finish this work in due time. Last but not the least; I would like to thank my family and friends (Ankit, Sowmya, Rujul and Pavan), who have been of great support during my work on this thesis. iii Contents 1 Introduction 1.1 Effects of low frequency fields . . . . . . . . . . . . . . . . . . . . . . . . . 1.1.1 Effects on humans . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1.2 Effects on plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1.3 Effects on animals . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Exposure limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2.1 International commission on non-ionizing radiation protection or (ICNIRP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2.2 Institute of electrical and electronics engineers or (IEEE) . . . . . . 1.2.3 American conference of governmental industrial hygienists or (ACGIH) 1.3 Outline of Thesis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 10 10 10 10 11 2 Evolution of electric power transmission 2.1 Early transmission . . . . . . . . . . 2.2 Growth of the transmission system . 2.3 Today’s transmission system . . . . . 2.4 Importance of transmission systems . 2.4.1 Reliability . . . . . . . . . . . 2.4.2 Flexibility . . . . . . . . . . . 2.4.3 Economics . . . . . . . . . . . 2.4.4 Competition . . . . . . . . . . 15 15 15 17 18 18 18 19 19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 12 13 13 3 Softwares 20 3.1 EMTP-RV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3.2 Matlab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 4 Three phase system 23 4.1 Symmetrical components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 4.2 Modal transformation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 4.2.1 Frequency dependent transmission lines . . . . . . . . . . . . . . . . 26 5 Overhead transmission lines 28 5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 5.1.1 Calculations related to AC transmission . . . . . . . . . . . . . . . 28 1 Contents 5.2 5.3 5.4 High voltage cables . . . . . . . . . . . . 5.2.1 Pressure cables . . . . . . . . . . 5.2.2 Screened cables . . . . . . . . . . 5.2.3 Submarine cables . . . . . . . . . Overhead HVAC transmission lines . . . 5.3.1 Structures . . . . . . . . . . . . . 5.3.2 Insulators . . . . . . . . . . . . . 5.3.3 Conductor types . . . . . . . . . Overhead lines vs. buried cables . . . . . 5.4.1 Comparison of HVAC and HVDC 5.4.2 Voltage levels . . . . . . . . . . . 5.4.3 Magnetic fields . . . . . . . . . . 6 Results and discussion 6.1 Matlab results . . . . . 6.2 EMTP results . . . . . 6.2.1 Line impedance 6.3 Experimental results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 31 33 35 36 36 36 39 41 44 45 46 . . . . 50 50 55 60 64 7 Summary 68 Bibliography 69 2 Nomenclature a,A scalar, also complex valued ~ ~a,A vector, also complex valued α Attenuation constant β Phase constant λ Flux linkage q L/C Surge impedance a Radius of the conductor B Magnetic field density C0 Capacitance per unit length d Conductor spacing D1 , D2 , D3 Distance between conductors f Frequency G0 Conductance per unit length I Current enclosed by loop I 0, I 1, I 2 Sequence currents I a, I b, I c Unbalanced currents k0 Fixed constant kd Normalized air density factor ki Wire irregularity factor L Inductance L0 Inductance per unit length r Distance from the center o the wire 3 Nomenclature R0 Resistance per unit length SIL Surge impedance loading V 0 , V 1 , V 2 Sequence voltages V a , V b , V c Unbalanced voltages V0 Line voltage to neutral ZC Characteristic impedance Zs Series impedance 4 List of Acronyms EMF Electromagnetic field UV Ultraviolet ELF Extremely low frequency GUI Graphical user interface NCRP National Council of Radiation Protection and Measurements ACGIH American Conference of Governmental Industrial Hygienists OHTLC Overhead Transmission Line Constants IRPA/INIRC International Commission on Non-Ionizing Radiation Protection EMTP Electromagnetic Transient program GMD Geometric mean distance GMR Geometric mean radius 5 List of Figures 1.1 Electomagnetic spectrum [1] . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 Long-Legged Mary Ann type early DC dynamo. [2] . . . . . . . . . . . . . 16 3.1 3.2 Screenshot of EMTP-RV User Interface [3] . . . . . . . . . . . . . . . . . . 21 Graphical interface of the MATLAB workspace [4] . . . . . . . . . . . . . . 22 4.1 4.2 4.3 4.4 Positive sequence components . . . . . . . Negative sequence components . . . . . . . Zero sequence components . . . . . . . . . Three phase balanced/symmetrical system . . . . . . . . 24 24 24 25 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 5.10 5.11 5.12 Single core conductor channel cable [5] . . . . . . . . . . . . . . . . . . . Single-core sheath channel [5] . . . . . . . . . . . . . . . . . . . . . . . . Three-core filler-space channels [5] . . . . . . . . . . . . . . . . . . . . . . H-type cable [5] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S L type cable [5] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Comparison of submarine power cables [6] . . . . . . . . . . . . . . . . . Typical single-circuit 500 kV AC suspension tower (Dimensions in ft.) [7] Pin-type insulator [8] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Suspension Insulator [8] . . . . . . . . . . . . . . . . . . . . . . . . . . . Strain Insulator [8] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shackle Insulator [8] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . All Aluminum Conductor(AAC) cable and All Aluminum Alloy Conductor (AAAC) [9] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Aluminum Conductor Steel Reinforced (ACSR) cable [10] . . . . . . . . . Comparison of Overhead lines to Underground HTS cables [11] . . . . . . Comparison of HVAC and HVDC structures [12] . . . . . . . . . . . . . . General layout of the electricity network in Europe [13] . . . . . . . . . . Different phasing arrangements of double circuit transmission lines . . . . . . . . . . . . . . . 31 32 32 33 34 35 37 38 39 39 40 . . . . . . 41 41 42 44 45 49 5.13 5.14 5.15 5.16 5.17 6.1 6.2 6.3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Arrangment of conductors in double circuit transmission line . . . . . . . . 50 Magnetic fields for low rectance phasing and superbundle phasing for different voltage levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Magnetic fields comparison for superbundle phasing and low reactance phasing with compact conductors . . . . . . . . . . . . . . . . . . . . . . . 54 6 List of Figures 6.4 6.5 6.6 6.7 Line data used for overhead line parameter calculation in ATPDraw . . . . Simulation model of different phasing arrangements in ATP/EMTP . . . . Magnitude and phase angle of characteristic impedance of transmission lines Position of conductors and ground wires for double circuit transmission lines in OHTLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.8 Data configurations for double circuit transmission lines in OHTLC . . . . 6.9 Phasing arrangements for double circuit transmission line in OHTLC . . . 6.10 Devices used for experimental setup during the mesaurement of magnetic field 6.11 Double circuit lines constructed in the EMC laboratory at the chair of electromagnetic compatibility at the Otto-von-Guericke- Universität, Magdeburg 6.12 Magnetic fields comparison for measured values and values obtained from simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 55 57 59 60 61 62 65 66 67 List of Tables 1.1 1.2 1.3 Average magnetic fields of some appliances (µT) [14] . . . . . . . . . . . . 11 Exposure limits for electromagnetic fields [15] . . . . . . . . . . . . . . . . 13 Exposure limits for electric fields [15] . . . . . . . . . . . . . . . . . . . . . 14 2.1 2.2 New transmission line voltages during electrification of the United States [16] 16 Miles of High-Voltage Transmission Lines in the United States [16] . . . . . 17 5.1 5.2 5.3 Comparison of Overhead lines and Underground lines [17] . . . . . . . . . . 43 Different voltage levels for power system network [18] . . . . . . . . . . . . 46 Classification of voltage levels [19] . . . . . . . . . . . . . . . . . . . . . . . 46 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 Position of conductors in overhead lines for different configurations . . . Current and SIL loading for various voltage levels . . . . . . . . . . . . . Position of conductors in overhead lines for compact configurations . . . Comparison of maximum magnetic field for both arrangements . . . . . . Conductor arrangement and datas for line model drawn in ATPDraw . . Phase current for different configurations . . . . . . . . . . . . . . . . . . Maximum current unbalance for different voltage levels . . . . . . . . . . Symmetrical component current for different configurations . . . . . . . . Modal parameters for real transformation matrices at 50 Hz obtained from EMTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Positive sequence impedance (Per unit values) . . . . . . . . . . . . . . . Positive sequence impedance (Actual values) . . . . . . . . . . . . . . . . Zero sequence impedance (Per unit values) . . . . . . . . . . . . . . . . . Zero sequence impedance (Actual values) . . . . . . . . . . . . . . . . . . Positioning of conductors for line model drawn in OHTLC . . . . . . . . Measured magnetic field in the EMC laboratory at the chair of electromagnetic compatibility at the Otto-von-Guericke- Universität, Magdeburg . . 6.10 6.11 6.12 6.13 6.14 6.15 8 . . . . . . . . 51 51 52 53 55 56 56 56 . . . . . . 58 60 60 61 61 62 . 66 1 Introduction With the increase in science and technology, the systems tend to be more complex further. Peoples are more curious/concerned about the adverse effects of high voltage transmission lines (HVTL) on their healths. Due to the exposure of electromagnetic fields (EMF) occurred by HVTLs, certain risk for diseases like leukemia, breast cancer has been revealed recently. Electric and magnetic fields exists naturally and also occurs due to human activity. Occurence of EMFs due to human activity are formed by the use of electric and magnetic fields. With the increment in industrialization in the society, there tends to be a drastic change in the level of EMFs. Figure 1.1: Electomagnetic spectrum [1] Electric power system frequencies (50 Hz) are placed at the end of electromagnetic spectrum (see Fig. 1.1) and are sometimes assigned as extremely low frequencies (ELFs). 9 1 Introduction 1.1 Effects of low frequency fields Now a days electricity has been an essential part of our’s life. Whenever there is a flow of electricity, the existence of electric and magnetic fields are taken into account. There exists many sources from which humans are exposed to low frequency fields. Several questions were raised regarding the concern of extremely low frequency fields: • Effects of fields on humans, animals and plants? • What are the exposure limits? • Can fields be reduced? 1.1.1 Effects on humans Acute exposure at high levels (above 100 µT) may cause several biological effects that are illustrated by biophysical mechanisms. Low frequency fields have a great impact on human body. Low frequency magnetic fields generates electric fields and currents which tends to stimulate nerve and muscles in human body. Various studies have shown adverse health effects on humans when exposed to ELF magnetic field. “These includes cancers in adults, depression, suicide, cardiovascular disorders, reproductive dysfunction, developmental disorders, immunological modifications, neurobehavioural effects and neurodegenerative disease.” [20]. 1.1.2 Effects on plants Magnetic fields does have an considerable effect on the growth of plants. According to Belyavskaya’s research weak electromagnetic fields tends to cause the degradation of the growth of plants, reduction of cell division and intensified protein synthesis. Some researchers also claimed that impact of weak EMF shows an increase in the growth of plants, while others showed there is no change. The disagreement and conflicting results from the studies illustrates that the effects of magnetic fields on plants may be species-specific and/or reliant on the characteristics of field exposure such as intensity and duration. 1.1.3 Effects on animals Some species are more susceptible to low frequency fields: • Animals that are having electric sense organs. • Animals having weak defence mechanisms. 10 1 Introduction The feasible data provided a insufficient basis to determine the hazard of EMF to environmental species. However, besides some local insignificant effects, no critical consequences of EMF on environmental species were identified. 1.2 Exposure limits Since the 20th century, the people are getting exposed to electromagnetic fields, but there was rarely any report of adverse health effects due to exposure. But, with increase in the demand of electricity, advancment in new technologies, the level of exposure has also been increased upto a great extent. The main sources of exposures to EMFs are electrical appliances, the domestic circuits that are used to power them, the lines that carries electricity to our home (Tab. 1.1). The more time we spend in the vicinity of such appliances , more will be the exposure to EMFs. Table 1.1: Average magnetic fields of some appliances (µT) [14] Distance from source Appliances 15 cm 30 cm 1.2 m Iron 0.8 0.1 Dishwasher 2.0 1.0 – Electric stove element 3.0 0.8 – Straight-tube fluorescent light 4.0 0.6 – Electric mixer 10.0 1.0 – Microwave oven 20.0 1.0 0.2 Circular saw 20.0 4.0 – Hair dryer 30.0 0.1 – Vacuum cleaner 30.0 6.0 0.1 Electric can-opener 60.0 15.0 0.2 EMF exposure leads to various adverse health effects on humans, plants and animals. So, we have to set the limitations on electric and magnetic field exposure. The guidelines for limiting EMF exposure are established by professional organisations. Tab. 1.2 and Tab. 1.3 explains the exposure limits of electric and electromagnetic fields. These includes: • International Commission on Non-Ionizing Radiation Protection or (ICNIRP), • Institute of Electronical and Electronics Engineers or (IEEE) and • American Conference of Governmental Industrial Hygienists or (ACGIH). 1.2.1 International commission on non-ionizing radiation protection or (ICNIRP) The ICNIRP is a scientific association which provides protection against non-ionizing radiation and helps to determine the exposure limits for low frequency fields. It also 11 1 Introduction provides guidelines on the adverse consequences of non-ionizing radiation (NIR) to keep people and surroundings safe from NIR exposure. Non-ionizing radiation illustrates the section of the electromagnetic spectrum that covers electromagnetic radiation such as ultraviolet, light, infrared, and radiowaves. In everyday’s life we came across various sources of non-ionizing radiation such as home electrical appliances, sun and cellphones. “The aim of ICNIRP is screen and evaluate scientific knowledge and current findings toward providing protection guidance on non-ionizing radiation, i.e. radio, microwave and infrared. In the past, national authorities in more than 50 countries and multinational authorities such as the European Union have adopted the ICNIRP guidelines and translated them into their own regulatory framework on protection of the public and of workers from established adverse health effects caused by exposure to non-ionizing radiation.” [21] The ICNIRP comprises of: • a main commission which limits membership upto fourteen in order to provide assurance of efficiency and • four Standing Committees containing eight members each which covers various disciplines of epidemiology, biology, medicine, physics and optical radiation. “ICNIRP members includes scientists which are hired by universities or radiation protection agencies. Being an independent organisation, ICNIRP connects those communities, who works for the protection of environment and humans against non-ionizing radiation across the globe on a larger scale. Before publication, ICNIRP uploads its draft guidelines online so that public can review and proper suggestions as well as changes are made.” [22] 1.2.2 Institute of electrical and electronics engineers or (IEEE) The IEEE is the world’s most extensive organization which helps in the advancment of technology across the globe. IEEE comprises of various professional societies (e.g., Electromagnetic Compatibility Society, Power & Energy Society and Antennas and Propagation Society ). IEEE has established various guidelines for limiting the exposure of electromagnetic fields on humans, plants and animals. Standards Coordinating Committees (e.g., SCC-28, SCC-34) are established by the IEEE-SA Standards Board. They are responsible for the development of exposure standards associated with subjects that covers more than one society (e.g., radio frequency safety standards). International committee on electromagnetic safety Several exposure standards has been framed by the International Committee on Electromagnetic Safety (ICES) for the proper use (with in the limits) of electromagnetic energy 12 1 Introduction ranging from 0 Hz to 300 GHz. ICES is funded by the Institute of Electrical and Electronics Engineers (IEEE) and is governed by its guidelines. “The aim of ICES is to achieve general agreement among all the shareholders for the safe use of electromagnetic energy, thereby developing practical standards that are easily accepted and applied. ICES is driven by a Parent Committee and is further subdivided into 5 Subcommittees: • SC1 Techniques, Procedures, and Instrumentation; • SC2 Terminology, Units of Measurements, and Hazard Communication; • SC3 Safety Levels with Respect to Human Exposure, 0 - 3 kHz; • SC4 Safety Levels with Respect to Human Exposure, 3 kHz - 300 GHz; and • SC5 Safety Levels with Respect to Electro-Explosive Devices. ” [23] 1.2.3 American conference of governmental industrial hygienists or (ACGIH) The American Conference of Governmental Industrial Hygienists (ACGIH) is a professional organization consisting of industrial hygienists and experts of related professions, having headquarters in Cincinnati, Ohio. One of its aim is to ensure protection of workers by providing all the necessary information (scientific, objective) to occupational and environmental health professionals. Table 1.2: Exposure limits for electromagnetic fields [15] 1.000 nT Suggested for private individuals by the NCRP in 1996, but not yet authorized 10.000 nT Suggested for workers and their working area by the NCRP in 1996, but not yet authorized 100.000 nT Exposure limit in Germany and IRPA/INIRC recommendation for private individuals(everyday, fixed exposure). Maximum limit as recommended by the ACGIH for persons having pacemakers or other electronic implants in their body. 500.000 nT IRPA/INIRC recommendation for workers (everyday, continuous exposure) 1000.000 nT IRPA/INIRC exposure limit for private individuals (exposure limited for few hours everyday) 5000.000 nT IRPA/INIRC recommendation for workers (exposure limited for few hours everyday) 1.3 Outline of Thesis The background of low frequency fields (occurrence, range), their adverse effects on human health, exposure limits by different associations is briefly described in 1. The chapter wise objectives and the outline of the thesis is also described in this chapter. 13 1 Introduction Table 1.3: Exposure limits for electric fields [15] V 100 m Recommended in 1996 for “workers” and their work surroundings by the NCRP, but not yet authorized. V 1.000 m Maximum limit as proposed by ACGIH for persons having pacemakers or other electronic implants in their body. V 5.000 m Limitation of current in Germany and recommendation of IRPA/INIRC for “private individuals” V 10.000 m Exposure limit for “workers” as suggested by IRPA/INIRC V 20.000 m Exposure limit for “workers” as suggested by ACGIH V 25.000 m Exposure limit for “workers” for a period of utmost 2 hours, as suggested by IRPA/INIRC Chapter 2 describes the evolution of electric power system, the growth of transmission system and it’s importance. Chapter 3 describes the various softwares used for the numerical computation of results during the work. Chapter 4 describes the advantages of three phase system and desription of symmetrical components. Chapter 5 describes the overhead lines structures, types of insulators used, types of conductors, different types of overead lines, different types of voltage cables. 14 2 Evolution of electric power transmission We all are aware of the difficulties, which we have faced during the outage of power for few hours. Just imagine our life without power. We can’t imagine such situations in our life’s. But in the early days there was an existence of such life and in future also, the same scenario (power outage) is going to happen. In this section we are going to discuss the evolution of electric power transmission. 2.1 Early transmission “Before the invention of electricity, there exists several systems which were used for transmission of power across large distances. Amongst the systems, telodynamic (cable in motion), pneumatic (pressurized air), and hydraulic (pressurized fluid) transmission were in great demand during those days.” [24]. During early days, transmission of electric power over large distance had following barriers: • Separate generators are needed for separate lines • Generators had to installed near their loads Direct Current Beginings During the early period between 1870’s and 1880s, dc power systems (see Fig. 2.1) ruled over the entire world. Coal-fired steam engines and hydroelectric power plants were earlier developed plants in order to power AC and DC generation plants. Most of the industrialized cities were located besides/nearby waterfalls, hence it was very easy to convert to hydroelectric power by the means of traditional mill. High voltage systems are needed in order to transmit DC power over long distances. This need of transmission led to the discovery of HVDC systems. For transmission of power over long distances, the HVDC transmission is preferred over other modes, today it has been used possibly to replace major AC high-voltage modes. The main problem regarding transfer of power was transmission over long distance. AC power provided the solution to this problem. 2.2 Growth of the transmission system During the 19th century, the inventors started to make use of electricity for daily useful needs by placing small generators adjacent to the machines which requires electricity for 15 2 Evolution of electric power transmission Figure 2.1: Long-Legged Mary Ann type early DC dynamo. [2] their working. Systems which were developed later tends to distribute power using direct current. But this method suffers from a major drawback. During the distribution of power, the power plant’s location should be within a range of one mile from the place of the power generation (load). Later on, it has been realised that the power industry must transform the system into small power plants operating together so as to serve their respective neighbouring loads. [16] Table 2.1: New transmission line voltages during electrification of the United States [16] Date Typical Voltage 1896 11 000 1900 60 000 1912 150 000 1930 240 000 In 1890 a new system of power distribution has been developed by some researchers, most of them who were employees of Thomas Edison. The most eminent evolution in power system was the development of high-voltage lines (see Tab. 2.1) using alternating 16 2 Evolution of electric power transmission current (AC). Transmission of power over long distances turns out to be a major advantage of the AC systems. 2.3 Today’s transmission system With the increasing years, our society hs been inclined towards technologies and depends upon their network as well as on the power plants. Table 2.2 depicts the growth and feaures of today’s transmission system. The whole system has been structured into a complex network which comprises of several plants and lines connected together and operating at diverse voltage levels. Most of the developing countries laid more emphasis on the transmission system’s capacity to deliver the power in most reliable and efficient way, till the transmission owners come up with their plans for their own growth. Table 2.2: Miles of High-Voltage Transmission Lines in the United States [16] Voltage Miles of Transmission Line AC 230 kV 60 000 345 kV 150 000 500 kV 240 000 765 kV 2453 Total AC 154 503 DC 250-300 kV 930 400 kV 852 450 kV 192 500 kV 1333 Total DC 3307 TOTAL 157 810 AC/DC The objective of the current political discussion on transmission is to analyze how 17 2 Evolution of electric power transmission different technologies and new policies should be combined which can benefit weak areas of the network up to maximum. 2.4 Importance of transmission systems The power industry has been transformed up to a great extent and are defined by a number of factors which comprises of reliability, flexibility, economics, and competition. On a large scale, a strong transmission system has some distinct features: • It enhances the reliability of the electric power system • It tends to make a market (electricity customers) more flexible • It holds a big impact on power market economically. • It tends to enable competition among power plants thereby, by providing access of plants to market on a large scale. 2.4.1 Reliability The two basic components of electric system reliability, which are being explained by power system operators are: (a) Adequacy- the adeptness of the electric system to meet the demands of electrical requirements and energy of customers always, while expected and unexpected failures of power lines have to be taken into account. (b) Security- the capability of the system to sustain an abrupt disruption that tends to malfunction the whole system. Some power plants operate continuously; while others are operated only at peak hours when needed most. Some power plants, such as wind power plants or hydroelectric units, operate excellently, when there is an adequate amount of wind flow or the flow of water. Under some circumstances, such as environmental restrictions, there is a closure of hydroelectric plants. While all power plants are closed on a regular basis for maintenance and repair. Sometimes there is an unexpected failure of plants and lines which occur due to weather or natural havoc. 2.4.2 Flexibility Transmission allows to make proper use of natural reserves such as wind, coal or geothermal energy, even if the resource’s locations are distant from the electricity users. Wind plants should be installed at such locations where the occurrence of wind is strong and consistent. Coal plant locations should be chosen wisely. It should be located near mine’s area because the transportation of electricity is far cheaper when compared to transportation of coal. 18 2 Evolution of electric power transmission 2.4.3 Economics The original Edison system which was used to deliver power over a small area has been more useful for a limited purpose. The customers and the system are bound together by one company and one generator. There are many power plants which are operating under different load levels, some produce power cheaper than others across the country. From the economic side, more effective power plants should be installed and should be able to use transmission network so as to deliver power completely through the market. For serving customers at affordable price, low cost generation of power must be ensured by the robust transmission system. This helps many consumers to get electricity at low cost even if there is hike in natural gas price or during the occurrence of natural disasters. 2.4.4 Competition With the recent development (local to regional) in the power system, a lot of scope has gained contest in the current market. The new competitive generators nowadays are dependent on unbiased and lawful passage to the transmission system so as to distribute their commodities to any associated market. A new term “transmission constrained areas” has been introduced by analysts. They have only confined capacity to carry out power because the existence of the transmission system into the limited area is clogged or in the vicinity of its range. The installation of new transmission lines in the reserved area enables the power generators (within specified area) to lessen the market prices in order to have a healthy competition with low cost power. Apart from having several benefits, transmission is considered to be as an controversial issue. In order to deliver electricity to its consumers, the role of transmission is considered equally important as generation. It contributes almost 10% of a consumer’s total electric bill. Many questions have been raised during the modern development in transmission systems. • Need for transmission • Proper selection of places for transmission lines construction? 19 3 Softwares Different configurations of overhead transmission lines are discussed, in order to reduce low frequency fields around overhead lines. During our work we are going to use different softwares in order to achieve desirable results. These includes: • EMTP-RV • Matlab 3.1 EMTP-RV “EMTP-RV is a full-featured and technically advanced simulation and analysis professional software for power system transients. The package is an advanced computer program for the simulation of electromagnetic, electromechanical and control systems transients in multiphase electric power systems. EMTP-RV is used worldwide as a reference tool by the main actors of the power system industry (EDF, RTE, Hydro-Québec and many others). It is suitable for a wide variety of power system studies whether they relate to project, design and engineering, or to solving problems and unexplained failures.” [3] Fig. 3.1 shows the user interface of EMTP-RV. EMTP-RV is a specialized software for the simulation and analysis of transients in power systems. Here is an overview of the EMTP-RV software: • “Unique and comprehensive software, • Interoperable Software linkable to ETAP, • Large range of phenomenon, • Advanced model of electrical machines” [25] 20 3 Softwares Figure 3.1: Screenshot of EMTP-RV User Interface [3] 21 3 Softwares 3.2 Matlab “MATLAB (matrix laboratory) is a multi-paradigm numerical computing environment and fourth-generation programming language. A proprietary programming language developed by MathWorks, MATLAB allows matrix manipulations, plotting of functions and data, implementation of algorithms, creation of user interfaces (see Fig. 3.2), and interfacing with programs written in other languages, including C, C++, Java, Fortran and Python. Although MATLAB is intended primarily for numerical computing, an optional toolbox uses the MuPAD symbolic engine, allowing access to symbolic computing abilities. An additional package, Simulink, adds graphical multi-domain simulation and model-based design for dynamic and embedded systems.” [26] Figure 3.2: Graphical interface of the MATLAB workspace [4] 22 4 Three phase system Power can be tranmitted from generation side to the consumer’s side by the help of single phase or three phase circuits. Single phase circuit consists of only one phase and one neutral. So, the transmission of power is limited upto a certain value, when single phase circuit is used. Three phase circuit is defined as the multiphase system all the phases are used together to deliver power from the generation side to the distribution stations. Each one of the phase is having a phase difference of 120°. Since all the phases are involved in power generation, the power is continuous. Why three phase is preferred over single phase? The advantages of three phase systems are listed below: 1. To generate same power the size of 3 phase alternator is small when compared to single phase alternator. Due to the small size of alternator, less amount of space is required for installation. 2. The number of conductors in 3 -φ systems is less thereby making the system more economical. 3. Three phase induction motors have higher power factor and efficiency than that of a single phase induction motor. 4. The amount of copper and aluminium used for transmission is very low in 3 -φ systems. 4.1 Symmetrical components Charles Legeyt Fortescue [27] proposed a new technique called as symmetrical components so as to solve the set of unbalanced three phase quantities. Faults occuring in three phase systems are analyzed using this tool. Fortescue suggested that three phase system contains different independent components i.e positive, zero and negative for both current and voltage. Positive sequence (see Fig. 4.1) voltages are always present in the system since these are supplied by generators with in the system. The second set consistes of phasors which are balanced in nature having equal magnitude but phase diference of 120° occurs and the sequence rotates in anticlockwise, is termed as negative sequence (see Fig. 4.2). The third set contains phasors which are 23 4 Three phase system balanced in nature having equal magnitude and in phase with each other and there is no rotation of phases and hence termed as zero sequence (see Fig. 4.3). C 120° 120° A 120° B Figure 4.1: Positive sequence components B 120° 120° A 120° C Figure 4.2: Negative sequence components C B A Figure 4.3: Zero sequence components Unbalanced current and voltage (I a , I b , I c and V a , V b , V c ) can be obtained by the set of symmetrical components. 24 4 Three phase system The unbalanced currents can be represented as follows: Ia = I1 + I2 + I0 (4.1) I b = a2 I 1 + aI 2 + I 0 (4.2) I c = aI 1 + a2 I 2 + I 0 (4.3) The unbalanced voltages can be represented as follows: Va =V1+V2+V0 (4.4) V b = a2 V 1 + aV 2 + V 0 (4.5) V c = aV 1 + a2 V 2 + V 0 (4.6) VC IC IA IB VA VB VA VB VC 3V 1 a2 × V B VA a2 × V c VA Vc VB Figure 4.4: Three phase balanced/symmetrical system The sequence components (currents or voltages) for 3 phase unbalanced system can be 25 4 Three phase system obtained as follows: Zero sequence component: 1 I 0 = (I a + I b + I c ) 3 1 V 0 = (V a + V b + V c ) 3 (4.7) (4.8) Positive sequence component: 1 I 1 = (I a + aI b + a2 I c ) 3 1 V 1 = (V a + aV b + a2 V c ) 3 (4.9) (4.10) Negative sequence component: 1 I 2 = (I a + a2 I b + aI c ) 3 1 V 2 = (V a + a2 V b + aV c ) 3 (4.11) (4.12) Here a tends to rotate the vector anti-clockwise by 120° and a2 tends to shift the vector anti-clockwise by 240°. For a balanced system (see Fig. 4.4) only positive sequence (both voltage and current) occurs. 4.2 Modal transformation In order to solve the inacuuracies caused by previous models, proper selection of transmission line model is neccessary. The previus developed modal domain was of no use. Further it has been discovered that the phase domain models were calculated and then it’s associated modal domain should be computed for steady state solutions. 4.2.1 Frequency dependent transmission lines From the physical geometry of the conductors the impedance and admittance matrix are calculated easily with the help of EMTP. The line parameters are the functions of frequency, so we have to develop the set of equations in frequency domain first, by using fitting synthesis. The wave propagation is influenced by the following frequency dependent parameters: 26 4 Three phase system • Characteristic impedance (Z c ) Z C (ω) = v u 0 u R (ω) + jωL0 (ω) t (4.13) Z C (ω) = v u 0 u Z (ω) t (4.14) G0 (ω) + jωC 0 (ω) Y 0 (ω) • Propagation constant (γ) γ(ω) = q (R0 (ω) + jωL0 (ω))(G0 (ω) + jωC 0 (ω)) γ(ω) = α(ω) + jβ(ω) 27 (4.15) (4.16) 5 Overhead transmission lines Both AC and DC system shares analogous medium for transmission of power. Since the early days, power transmission over long distances was considered as a big issue. Power can be transmitted (over long distances) from generation to load side by the means of transmission lines, underground cables and submarine cables. 5.1 Introduction The economic growth of any country has a considerable dependency on electrical power. During the early days, only generation and distribution of electrical power were considered highly important, as there were several issues and challenges for the transmission of power over long distances. After the recent development of technologies, the electrical power transmission is considered as important as generation and distribution. The power transmission network is a lifelong capital investment with involves a huge investment. The proportion of this investment relating to transmission and distribution is about 50% of the total. Half of this, i.e. a quarter of the total amount, is invested for renewal and expansion of the public power supply cable network. While selecting the choice of the transmission technology to be used, we have to emphasize more on proper planning and surveying. Planning is important because every transmission project is directly dependent upon its geographical conditions, technical limitations and environmental concerns. During the transmission of electrical energy from the generation side to consumer the voltage and current levels have to be selected in the most effective way. Electrical energy is produced at relatively low voltage and high current at generating stations. The level of voltage has to be stepped up before transmission within generating premises to minimize the losses. The energy is transferred to the user through a series of complex electrical network with safety limitations, practicability and adaptability to the existing electrical network. There are different types of conduit segments referred to as bush-bars, distribution lines, cables or transmission lines. 5.1.1 Calculations related to AC transmission Corona loss “Due to a corona loss in power system, the efficiency of EHV (extra high voltage lines) has been significantly reduced. Corona loss occurs when there is an ionization of air molecules 28 5 Overhead transmission lines near the transmission line conductors. These coronas do not spark across lines, but rather carry current (hence the loss) in the air along the wire. Corona discharge power losses are also highly dependent on the weather and temperature” [28]. The corona loss was given by, " k0 a d P = (f + 25) V0 − g0 ki akd ln kd d a r !#2 X10−5 kW km (5.1) Where k0 is the fixed constant, kd is the normalized air density factor, f is the frequency, a is the radius of the conductor, d is the conductor spacing, V0 is the line voltage to neutral and ki is the wire irregularity factor. Resistive (Skin) loss During AC transmission, there is a flow of non uniform current through out the conductors i.e the current density will be more on the surface of the conductor and when we goes deep inside the conductor the current density will decrease. This phenomenon is termed as skin effect. In the case of DC system the flow of current is uniform throug out the conductor’s cross sectional area. There are several factors which affects the skin effect. These includes the shape of the conductor, frequency, type of material and diameter of the conductors. At higher frequencies the effective resistance of conductor increases and the cross section of the conductor is reduced. This phenomena occurs due to skin effect. With the increase in frequency, there is a decrease in skin effect i.e, at higher frequencies the skin effect is much lower. A less amount of current is present in the interior of a large conductor. This makes the use of tubular conductors in order to reduce the cost. Line Inductance For transmission line, line inductance is termed as the ratio of flux linkages (Wb-turns) to the current flowing through the line. L= λ I (5.2) The inductance is directly proportional to the spacing between the phases and inversly proportional to the radius of the conductors in transmission lines. Phases of the overhead lines are separated at a larger distance in order to ensure proper insulation. So, a higher voltage line will have more inductance when compared to the low voltage line. The inductance of overhead lines is given by, L = 2 × 10-7 GM D H/m GM R 29 (5.3) 5 Overhead transmission lines Where the Geometric Mean Distance (GMD) is defined by GM D = q 3 D1 D2 D3 (5.4) Where D1 ,D2 and D3 are the distances between 3 conductors. The Geometric Mean Radius is supplied by the manufacturer. 5.2 High voltage cables Whenever there is a need for power transmission via underground, high voltage cables are needed. These types of cables are either buried inside the ground or are placed in ducts. In order to transmit power, conductors are properly insulated which in turn makes the cables more costlier than overhead lines. Being single cored in nature, high voltage cables have their additional insulation and sheaths for mechanical protection. For underground transmission the classification of cables is performed in two ways. These are: 1. insulating material types 2. level of voltage used Cables are categorized into: • Low-tension (L.T.) cables — upto 1000 V • High-tension (H.T.) cables — upto 11.000 V • Super-tension (S.T.) cables — from 22 kV to 33 kV • Extra high-tension (E.H.T.) cables — from 33 kV to 66 kV • Extra super voltage cables — above 132 kV In the modern day transmission system underground cables are used for transmission of 3-phase power over short and long distances. For 3-phase transmission the following cables are used. (a) Belted cables — upto 11 kV (b) Screened cables — from 22 kV to 66 kV (c) Pressure cables — beyond 132 kV. 30 5 Overhead transmission lines 5.2.1 Pressure cables The presence of voids in solid type cables increases the chances of breakdown of insulation, which in turn makes the use of cables unreliable for voltages above 66 kV. Pressure cables are used when the operating voltages exceed 66 kV. Voids are easily removed bt the application of an extreme amount of pressure on compound. The pressure cables are classified into following types: • Oil-filled cables • Gas pressure cables Oil-filled cables In such types, ducts are provided with in the core or nearby in order to ensure proper circulation under pressure. To supply oil continuously to the channel, external reservoirs are installed at appropriate distances along the path of the cable. Eradication of voids makes the oil-filled cables suitable for use ranging from 66 kV up to 230 kV. Oil-filled cables are of three types: (i) single-core conductor channel (ii) single-core sheath channel (iii) three-core filler-space channels • Single-core conductor channel Figure 5.1: Single core conductor channel cable [5] Fig. 5.1 shows a typical single core conductor channel cable. It consists of a hollow conductor which behaves as an oil channel. External reservoir helps to supply the oil under pressure to the channel. The different layers of paper insulation have been compressed by oil under pressure and is forced 31 5 Overhead transmission lines to eliminate the voids that may have formed between the layers. Increase in cable temperature causes the oil to expand and the extra oil that is going to flow out will be stored in the reservoir. When there is fall in the temperature, the stored oil tends to flow back in the reservoir. • Single-core sheath channel Figure 5.2: Single-core sheath channel [5] The installation is very easy because of the location of channels at earth potential (see Fig. 5.2). • Three-core filler-space channels Figure 5.3: Three-core filler-space channels [5] In the 3-core oil-filler cable, the filler spaces are used to store the oil ducts. Fig. 5.3 describes the layout of three-core filler space channel cable. The oil-filled cables have three principal advantages. (i) No voids formation and ionisation (ii) Increase of temperature range and dielectric strength (iii) The cause of leakage and defects are easily tracked. High initial cost and complex layout structure are the major drawbacks of these types of cables. 32 5 Overhead transmission lines 5.2.2 Screened cables These type of cables have an operating voltage ranging from 22 kV to 33 kV. In some exceptional cases, they can be used upto 66 kV. There are two types of screened cables which are listed and explained below: • H type cables • S.L. type cables Hochstadter or H type Cable Figure 5.4: H-type cable [5] Fig. 5.4 shows the general layout of H type cable. Each one of the conductor is properly insulated by a perforated paper and is surrounded by a metallic screen which is in contact with each of the attached conducter’s screen. The arrangement of the cores is done in such a way that power dissipation will be minimised. All screens are grounded in order to make the potential value zero at the sheaths. The screens are so thin that there is rarely any current induced in them. Thermal expansion leads to the separation of the cores, but the core separation cannot introduces stress in the dielectric thereby reducing the losses. For such cables, the cores are not provided with an additional lead covering. If they are placed in ground for transmission of power, then they must be safeguarded with additional coverings. Heat is dissipated to the outer surroundings by the use of metallised screens. Their usage is limited up to 66 kV. S.L. type cable S.L. cable refers to separate lead screened cables. The general layout of S.L cable is shown in Fig. 5.5. In such type of cables the core is properly insulated and provided with an additional layer of lead. Screens are used to reduce the possibility of stress occurrence between core and sheath. An additional sheath per core makes these cables to bend according to their requirements, while this property was absent in H type cables. H-type cables and S.L. type cables shares same electrical and thermal advantages. The lack of 33 5 Overhead transmission lines Figure 5.5: S L type cable [5] oil in the filler reduces the occurrence of hazards which may occur due to oil drainage, thereby making these cables suited for hilly tracks. Due to simplification of terminating equipment, the S.L. type construction is beneficial for short runs. 34 5 Overhead transmission lines 5.2.3 Submarine cables In 1811 first submarine power cable was installed in Germany that was insulated with natural rubber. Submarine power cables are used to connect power grids across bays, estuaries, rivers, straits, etc. Fig. 5.6 shows a comparison of different types of submarine cables. (a) 115 kV single conductor submarine power cable - 1962 (b) Modern submarine power cable Figure 5.6: Comparison of submarine power cables [6] 35 5 Overhead transmission lines 5.3 Overhead HVAC transmission lines HVAC transmission circuit is 3 phase system consisting of exposed conductors which are supported by a chain of transmission structures. The number of conductors are limited in the range of one to four for each phase. Insulators are used to isulate the phases from the ground. Transmission structures makes the use of “single circuit” or “double circuit” which contains three phase and six phase respectively. The overhead lines are described in a better way by following: 5.3.1 Structures Transmission structures are used to support overhead lines. For the construction of structures, several materials are used based on the classification: • For low voltage tranmsission lines, wooden structures are used, but their use is limited for high voltage lines. • For high voltage lines tubular steel and lattice structures are used because of their durability, ease of maintenance and installation. The transmission structures are designed based on the purpose and their functionality in the transmission lines. Here is the overview of transmission structures: (i) Tangent or Suspension Type Structures (ii) Strain Angle Type Structures (iii) Dead-end Type Structures Suspension type structures (see Fig. 5.7) are most commonly used structures and their usage is limited upto straight part of the lines. As the conductors are placed in a straight line, their handling capacity is limited from 0 to 2°. When there is a change in the direction of line conductors, angle type structures are used. Due to change in the direction, extra force will be implemented on the lines. In order to withstand such forces angle type structures are used. When there is a large change in the angle of transmission line conductors, dead end structures are used. When compared to other types of structures, dead end structures are most stronger, larger in terms of loading capacity. Climatic factors such as wind, ice and snow plays a key role while designing and implementing the structures in transmission line. 5.3.2 Insulators In order to ensure proper functioning of transmission lines i.e, to avoid any leakage of current, overhead conductors should be provided with proper insulation. Proper insulation 36 5 Overhead transmission lines Figure 5.7: Typical single-circuit 500 kV AC suspension tower (Dimensions in ft.) [7] can be ensured by the use of insulators, which tends to prevent leakage current passing from conductor to earth. Porcelain is the most used material for insulators but several composition materials like glass and steatite are also used. Insulator’s selection plays a key role in proper functioning of overhead lines. The properties which every insulator material should have are listed below: (a) Insulators should have immense mechanical strength so as to endure conductor load, wind load etc. (b) They should have a higher electrical resistance so as to to avoid the possibility of the leakage current passing to the earth. (c) They should have a higher relative permittivity. (d) They should be free from impurities. 37 5 Overhead transmission lines Pin type insulators Pin insulator (see Fig. 5.8)was the first developed overhead insulator, but still they are in demand for transmission and distribution up to 33 kV system. For 11 kV system one part type insulator is used. As the name suggests, one part type insulator contains only one piece of glass or porcelain. This type of insulator is mounted on the pole structures with the help of bolts. They are used for straight transmission lines. Above 33 kV systems, the insulators become too heavy thereby making the system more complex and costly. Figure 5.8: Pin-type insulator [8] Suspension type insulators Above 33 kV pin type insulators are not used due to it’s oversize and overweight. It is very difficult to handle and replace bigger size insulators. In order to overcome these problems, suspension insulator (see Fig. 5.9) was developed. Discs are connected in series. Each disc is associated with a low voltage. Working voltage has a direct dependency upon the number of discs in series. These type of insulators are more economical and they replace pin insulators thereby reducing the area and cost of the system. They consists of interconnected discs, with each disk designed to support a particular voltage. If one disc is damaged amongs the sets, the whole string will not be useless, infact it can be replaced by a good one. Strain insulators The transmission lines are subjected to a large tension when there is a dead end or curve in the line. Strain insulators are used in order to reduce the excessive tension. For low voltage levels (below 11 kV) shackle insulators are used, but for higher voltage lines a group of suspension type insulators are used together as strain insulator. They are used to manage the mechanical stress by reducing the pressure from a conductor at the corner of a 38 5 Overhead transmission lines Figure 5.9: Suspension Insulator [8] transmission line. A strain insulator (Fig. 5.10) should posses higher mechanical strength and proper insulation. Figure 5.10: Strain Insulator [8] Shackle insulators For low voltage distribution networks, shackle insulators (Fig. 5.11) are used. With the increased use of underground cables for distribution, the use of such types of insulators has been decreased rapidly. These insulators can be used horizontally or vertically. They can be fixed to the pole with the help of bolts. 5.3.3 Conductor types The transmission line is considered as the backbone of the power system. The conductor materials play a key role in estimating the cost and span of transmission lines. Copper is most suited for the choice of the material for conductor due to its high conductivity and immense tensile strength. The higher cost incurred turns out to be the drawback of 39 5 Overhead transmission lines Figure 5.11: Shackle Insulator [8] copper’s use. The material used for power transmission has a dependency on following factors: 1. Required electrical properties 2. Required mechanical strength 3. Local conditions 4. Cost of material There isn’t any predefined guideline for the design of transmission and distribution lines. The conductors electrical and mechanical properties has a great impact on the cost incurred during the design of power lines. In order to serve the stated purpose, following are the conductors used: 1. AAC - All Aluminum Conductor 2. AAAC - All Aluminum Alloy Conductor 3. ACSR - Aluminum Conductor Steel Reinforced • AAC AAC (Fig. 5.12a) doesn’t fits for applications like transmission lines and rural distribution where long spans are utilized, due to its relatively poor strength-toweight ratio. However, it is extensively used in urban and coastal regions due to its excellent conductivity and corrosion resistance. • AAAC They used for distribution near ocean areas where there is a maximum chance of corrosion while using other conductors. The advantages of AAAC (Fig. 5.12b) conductors are listed below: 40 5 Overhead transmission lines (a) AAC (b) AAAC Figure 5.12: All Aluminum Conductor(AAC) cable and All Aluminum Alloy Conductor (AAAC) [9] - Low loss of power when compared to ASCR conductor - Very good corrosion resistance - Higher resistance to abrasion • ACSR Having higher strength to weight ratio and being economical, ACSR conductors are preferred over others for transmission lines having long spans. As the name suggests itself, ACSR (Fig. 5.13) conductors are combination of aluminium and steel. They merge the light weight and good conductivity of aluminium with high tensile strength along with the ruggedness of steel. Figure 5.13: Aluminum Conductor Steel Reinforced (ACSR) cable [10] 5.4 Overhead lines vs. buried cables In order to transmit electric power from generation point to consumer side, we can use either overhead lines or underground cables. Each of these methods has certain pros and cons. Fig. 5.14 and Tab. 5.1 shows a comparison between overhead lines and underground cables. 41 5 Overhead transmission lines Figure 5.14: Comparison of Overhead lines to Underground HTS cables [11] 42 5 Overhead transmission lines Table 5.1: Comparison of Overhead lines and Underground lines [17] Overhead lines Underground lines 1. Conducter size is small 2. Conductor size is quite large 2. Less insulation needed because 2. Very high insulation is required be- overhead lines are open to surroundings cause the underground system is located and essential insulation is provided by inside the ground thereby making the air. area quite compact. 3. Dissipation of heat is easy as 3. Heat dissipation is difficult due to overhead lines are exposed to non exposure of underground lines to atmosphere. the atmosphere. 4. The absence of insulation coating 4. Higher cost is incurred as the system over conductors makes the system very needs more number of insulation layers. cheap. 5. Detection of faults is very easy. 5. Faults cannot be detected easily because of the complex nature of the system. 6. System maintenance work is very 6. Maintenance turns out to be uneasy. easy. 7. Power is transmitted over long 7. Used for shorter distance. distance. 8. Safety of public is at stake. 8. More safety is assured. 43 5 Overhead transmission lines 5.4.1 Comparison of HVAC and HVDC systems Investment cost The transmission of electric power through DC systems needs lesser number of conductors when compared to AC systems. The use of lesser conductors (Fig. 5.15) makes HVDC transmission lines cheaper than an HVAC line. Over a certain distance, termed as break-even distance, HVDC lines are cheaper than HVAC. For overhead lines, the break-even distance is around 600 km. Figure 5.15: Comparison of HVAC and HVDC structures [12] Losses In DC systems, there is no skin effect and also the corona losses are very low when compared to AC systems. This makes favourable for the use of HVDC systems over HVAC systems. Asynchronous connection There exists diferent standardization for AC power grids. In some countries 50 Hz is taken, whereas in some countries 60 Hz is used. It is highly impossible to connect two different power grids operating at different frequencies. But a HVDC link makes it possible , thereby use of HVDC over long distance is preferrable. 44 5 Overhead transmission lines 5.4.2 Voltage levels Whenever there is a flow of current through network, loss in power takes place. As the power loss is directly proportional to the square of the current, transmission line operates at high voltage and low current. More the power will be transmitted, more will be the voltage. So, there is a need for standardisation of voltage levels across the globe. Figure 5.16: General layout of the electricity network in Europe [13] Power system comprises of generating stations, transmission systems and distribution systems. To deliver a vast amount of power from generating stations to distribution centres, transmission systems are used. The transmission voltages (Tab. 5.2) are dependent on following factors: • the distance upto which power is to be delivered • the amount of power to be transmitted • stability of the system Distribution stations are used to deliver power to the consumers. Fig. 5.16 shows a general layout of the electricity network in Europe. Tab. 5.3 shows the different voltage levels and their associated risks. 45 5 Overhead transmission lines Table 5.2: Different voltage levels for power system network [18] Power system network Voltage levels Generating stations 6.6 kV, 11 kV, 21 kV, 31 kV Transmission systems 110 kV, 220 kV, 132 kV, 400 kV Distribution systems 11 kV, kV, 3.3 kV, 230 V Table 5.3: Classification of voltage levels [19] IEC voltage range AC DC Defining risk High voltage (supply system) > 1000 VRMS > 1500 V electrical arcing Low voltage (supply system) 50 – 1000 VRMS 120 - 1500 V electrical shock Extra-low voltage (supply system) < 50 VRMS <120 V low risk 5.4.3 Magnetic fields Whenever there is a use of electricity, electric current is involved and where there is a flow of electric current, magnetic fields comes into existence. They are generated by electric current. Magnetic fields around overhead lines tends to induce current in the human body, which leads to the concern of health issues when exposed directly to magnetic fields. So, it is recommended to determine the exact amount of the fields in vicinity of home, working place and surroundings. When there is a flow of electron inside the conductor, magnetic fields are produced. The magnitude of a magnetic field is directly dependent on the current flowing inside the loop or wire, not on the voltage across them. Magnetic fields are measured in either Gauss (G) or Tesla (T). Methods to reduce magnetic fields around overhead lines Although it has not been mentioned anywhere across the globe that direct or indirect exposure to magnetic fields causes any types of diseases like cancer, leukemia etc, one should avoid direct or indirect exposure to magnetic fields. The exposure limits has been set up by various organizations like ICNIRP, IEEE and WHO. Magnetic fields around overhead lines can be reduced by following methods: • Height of the towers: With the increase in the height of the tower (structure), magnetic fields can be significantly reduced. But this approach has a certain drawback. When the height of the towers will be increased , the space allotted for designing tower will also increase and the capital cost in setting up the structure will also shoot up to a great extent. 46 5 Overhead transmission lines • Compact conductors: For this method the bundles are optimized by a certain factor, but this in turn causes other instabilities. • Swapped Phases: By interchanging the top and bottom phases of the transmission lines, magnetic fields can be reduced. According to Ampere’s law, the integral of B around any closed path is equal to µ times the current enclosed in the area. I B · dl = µ0 I (5.5) Where, the line integral is over any arbitrary loop , I is the current enclosed by that loop and r is the distance from the center of the wire The magnetic field generated by a single wire is obtained by following equation. ~ = µ0 I a~ϕ B 2πr (5.6) |B| = (Bx 2 + By 2 ) 2 1 Bx = By = n X µ0 I j y j 2 2 j=1 2π(xj + y j ) n X µ 0 I j xj 2 2 j=1 2π(xj + y j ) |B| = q (Bx 2 + By 2 ) (5.7) (5.8) (5.9) (5.10) The magnetic fields along x-axis and y-axis are calculated using (5.8) and (5.9) respectively. The resultant magnetic fields along the axes are calculated using (5.10). Surge Impedence Loading The SIL can be calculated by the formula: |V |2 SIL = q L/C 47 (5.11) 5 Overhead transmission lines |V | |I L | = √ q 3 L/C (5.12) q Where, L/C is the surge impedance in Ω, |V | is the line voltage in kV, |I L | is the line current in A and SIL is the surge impedance loading in MW. Surge impedance values lies in the range of 400 to 600Ω for overhead lines. Short transmission lines (<50 miles) are used to transmit load upto 1.2 to 1.5 times SIL. Characteristic impedance of overhead lines The characteristic impedance of a two conductor line is given by the formula: d Z = 120 ln r ! (5.13) Where, d is the separation of conductors and r is the radius of conductors. √ The resistance increases relatively with increase in frequency by a factor of f , where f is frequency. On other hand, with the increase in f , the inductance tends to decrease. 1. For a low frequency (f f c ), where f c is the critical frequency Z = R + jωL, R = Rdc = µ0 ρ ,L = S 8π (5.14) 2. For a high frequency (f f c ) √ √ ω µ0 ρ R 1 Z = (1 + j)R, R = √ ∝√ ∝ ωL = ω ω 2 2πrf s Z0 = √ Z ω 1 ∝ =√ Y ω f With the increase in frequency, the characteristic impedance tends to decrease. 48 (5.15) (5.16) 5 Overhead transmission lines (a) Superbundle phasing (b) Low reactance phasing Figure 5.17: Different phasing arrangements of double circuit transmission lines Fig. 5.17 shows the different phasing arrangements of double circuit transmission lines. In Fig. 5.17a the conductors are arranged in same order from top to bottom i.e, (ABC, A’B’C’). In Fig. 5.17b the top and bottom conductors positions are swapped and the order of the conducters will be in the form of (ABC, C’B’A’). The swapping of conductors turns out to be advantageous over previous phasing arrangements. When compared to superbundle phasing low reactance phasing has following advantages: • Low resistive loss • Low magnetic field • Low shield wire losses 49 6 Results and discussion 6.1 Matlab results Figure 6.1: Arrangment of conductors in double circuit transmission line Fig. 6.1 shows the arrangement of conductors in double circuit transmission lines. The position of the conductors are given as input in the Matlab program. We can calculate the current and surge impedance loading for different voltage levels using Eq. (5.11) and (5.12). From Tab. 6.2 we can see that with an increase in voltage, SIL also increases which inturn leads to the increase in current value. As magnetic field is directly dependent on current, we can say that more the current value more will be the magnetic field. Fig. 6.2 shows the magnetic fields comparison for both phasing arrangements. The magnetic fields comparison (compact conductors) for both phasing arrangements is illustrated in Fig. 6.3. From the above graphs it can be shown that swapping of phase conductors 50 6 Results and discussion Table 6.1: Position of conductors in overhead lines for different configurations Superbundle phasing Low reactance phasing dimensions (in m) dimensions (in m) h1 14 14 h2 26.7 26.7 h3 34 34 a11 -2.88 -7.08 a12 -2.38 -6.58 a21 2.38 6.58 a22 2.88 7.08 b11 -10.0 -10.0 b12 -9.50 -9.50 b21 9.50 9.50 b22 10.0 10.0 c11 -7.08 -2.88 c12 -6.58 -2.38 c21 6.58 2.38 c22 7.08 2.88 Conductors notation Table 6.2: Current and SIL loading for various voltage levels Voltage levels kV SIL loading (MW) Current (A) 154 88.93 334 275 283.59 596 380 541.5 822 500 937.5 1082 leads to a reduction of magnetic field around transmission lines. Tab. 6.1 and Tab. 6.3 shows the positioning of conductors and compact conductors of overhead lines for different configurations respectively. 51 6 Results and discussion Table 6.3: Position of conductors in overhead lines for compact configurations Superbundle phasing Low reactance phasing (compact) dimensions (in m) (compact) dimensions (in m) h1 14 14 h2 24.3 24.3 h3 29.2 29.2 a11 -2.40 -5.76 a12 -1.90 -5.26 a21 1.90 5.26 a22 2.40 5.76 b11 -8.1 -10.0 b12 -7.6 -9.50 b21 7.6 9.50 b22 8.1 10.0 c11 -5.76 -2.40 c12 -5.26 -1.90 c21 5.26 1.90 c22 5.76 2.40 Conductors notation 52 ·10−5 5 Low reactance phasing 4.5 4 Superbundle phasing 3.5 3 2.5 2 1.5 1 0.5 0 −100−80 −60 −40 −20 0 20 40 60 80 100 4 Magnetic flux (T) Magnetic flux (T) 6 Results and discussion ·10−5 Low reactance phasing Superbundle phasing 3.5 3 2.5 2 1.5 1 0.5 0 −100−80 −60 −40 −20 0 Distance (m) Distance (m) (a) 500 kV (b) 380 kV 2 1.6 Low reactance phasing Superbundle phasing Magnetic flux (T) Magnetic flux (T) ·10−5 2.5 1.5 1 0.5 0 −100−80 −60 −40 −20 0 20 40 60 80 100 ·10−5 Low reactance phasing Superbundle phasing 1.4 1.2 1 0.8 0.6 0.4 0.2 20 40 60 80 100 0 −100−80 −60 −40 −20 0 Distance (m) 20 40 60 80 100 Distance (m) (c) 275 kV (d) 154 kV Figure 6.2: Magnetic fields for low rectance phasing and superbundle phasing for different voltage levels Table 6.4: Comparison of maximum magnetic field for both arrangements Phase arrangements Voltage level (kV) Maximum magnetic field (T) Superbundle phasing 154 1 × 10−5 275 1.8 × 10−5 380 2.5 × 10−5 500 3.25 × 10−5 154 0.75 × 10−5 275 1.3 × 10−5 380 1.7 × 10−5 Low reactance phasing 500 2.2 × 10−5 The maximum magnetic field for low reactance phasing and superbundle phasing is shown in Fig. 6.4. 53 ·10−5 4.5 LR phasing 4 Superbundle phasing 3.5 3 2.5 2 1.5 1 0.5 0 −100−80 −60 −40 −20 0 20 40 60 80 100 ·10−5 Magnetic flux (T) Magnetic flux (T) 6 Results and discussion 3 LR phasing Superbundle phasing 2.5 2 1.5 1 0.5 0 −100−80 −60 −40 −20 0 Distance (m) Distance (m) (a) 500 kV 2 (b) 380 kV ·10−5 ·10−5 1.4 LR phasing Superbundle phasing Magnetic flux (T) Magnetic flux (T) 2.5 20 40 60 80 100 1.5 1 0.5 0 −100−80 −60 −40 −20 0 20 40 60 80 100 Distance (m) 1.2 LR phasing Superbundle phasing 1 0.8 0.6 0.4 0.2 0 −100−80 −60 −40 −20 0 20 40 60 80 100 Distance (m) (c) 275 kV (d) 154 kV Figure 6.3: Magnetic fields comparison for superbundle phasing and low reactance phasing with compact conductors 54 6 Results and discussion 6.2 EMTP results Figure 6.4: Line data used for overhead line parameter calculation in ATPDraw Table 6.5: Conductor arrangement and datas for line model drawn in ATPDraw Phase no. Rin (cm) Rout (cm) DC Resistance (Ω/km) Horizontal (m) Vtower (m) 1 0.37 1.4795 0.0597 -4.12 30.24 2 0.37 1.4795 0.0597 -4.47 24.12 3 0.37 1.4795 0.0597 -5.75 18 4 0.37 1.4795 0.0597 4.12 30.24 5 0.37 1.4795 0.0597 4.47 24.12 6 0.37 1.4795 0.0597 5.75 18 7 1e − 6 0.815 0.22227 -6.75 36.36 8 1e − 6 0.815 0.22227 6.75 36.36 Fig. 6.4 and Tab. 6.5 illustrates the phase, radius of conductors and position of conductors as well as the line model used in ATPDraw. The maximum difference between the currents occuring in different phases is given in 55 6 Results and discussion Table 6.6: Phase current for different configurations Phase a Phase b Phase c Voltage Phasing arrangements I (kA) Angle (degree) I (kA) Angle (degree) I (kA) Angle (degree) 500 kV Superbundle phasing 25.86 -78.73 29.88 157.76 25.07 29.69 Low reactance phasing 27.82 -81.43 30.08 156.63 27.7 34.72 Superbundle phasing 15.21 -75.4 17.06 158.8 15.40 30.10 Low reactance phasing 16.64 -81.33 17.11 158.35 16.53 33.75 Superbundle phasing 8.91 -77.56 9.6 158.8 8.74 30.11 Low reactance phasing 9.71 -80.6 9.80 157.98 9.48 32.33 275 kV 154 kV Table 6.7: Maximum current unbalance for different voltage levels 500 kV 275 kV 154 kV Difference (kA) Ratio (%) Difference (kA) Ratio (%) Difference (kA) Ratio (%) Superbundle phasing 4.38 17.85 1.85 11.64 0.86 9.46 Low reactance phasing 2.38 8.34 0.58 3.46 0.32 3.3 Table 6.8: Symmetrical component current for different configurations Positive Seq. Voltage 500 kV 275 kV 154 kV Zero Seq. Negative Seq. I1 (kA) Angle (degree) I0 (kA) Angle (degree) I2 (kA) Angle (degree) Superbundle phasing 26.83 -83.62 0.607 -63.6 2.98 38.48 Low reactance phasing 28.51 -83.37 0.24 -15.88 3.94 34.98 Superbundle phasing 15.79 -82.16 0.49 -33.40 1.74 43.93 Low reactance phasing 16.73 -83.06 0.33 -70 0.611 53.74 Superbundle phasing 9.04 -82.81 0.33 -57.84 0.82 42.66 Low reactance phasing 9.64 -83.41 0.32 -58.55 0.41 43.63 56 6 Results and discussion (a) Superbundle phasing. (b) Low reactance phasing. Figure 6.5: Simulation model of different phasing arrangements in ATP/EMTP Tab. 6.7. The difference has been computed by substracting the smallest current from the largest current of each of the phases in the Tab. 6.6. The ratio has been calculated by the ratio of the difference in current to the average current of each of the three phases. From the Tab. 6.6, it has been clearly shown that the superbundle phasing causes the largest unbalance of the phase currents and low reactance phasing causes less unbalance when compared to superbundle phasing. The symmetrical components of phase currents is listed in Tab. 6.8. Fig. 6.5 shows the simulation model of both phasing arrangements (Superbundle and Low reactance phasing) in ATP/EMTP. 57 6 Results and discussion Table 6.9: Modal parameters for real transformation matrices at 50 Hz obtained from EMTP R’(Ω/km) ) L’( mH km G’(Ω/km) µF ) C’( km Zc (Ω) Phase(°) 0.0407 2.940 2.5 × 10−10 9.46 × 10−3 582 -11.8 0.0171 0.83 2.1 × 10−10 1.46 × 10−2 260 -16.5 0.0159 0.632 2.04 × 10−10 1.76 × 10−2 214 -19.3 Modal transformation 0.0267 + j0.0483 0.0098 + j0.0266 0.0095 + j0.0241 Z s = 0.0098 + j0.0266 0.0254 + j0.0477 0.0089 + j0.0273 0.0095 + j0.0241 0.0089 + j0.0273 0.0248 + j0.0496 (6.1) The series impedance matrix (phase domain) is calculated by EMTP and is given by Eq. (6.1). The matrix comprises of self impedance and mutual impedance values. After modal transformation we got the values of overhead line parameters (Tab. 6.9. Fig. 6.6 shows the variation of magnitude and phase of Zc with respect to frequency. 58 6 Results and discussion Impedance (Ω) 750 Zc vs. Frequency 700 650 600 550 500 450 0 5 10 15 20 25 30 35 40 45 50 Frequency (Hz) (a) Magnitude of Zc −4 Zc vs. Phase −6 Phase (°) −8 −10 −12 −14 −16 −18 −20 0 5 10 15 20 25 30 35 40 45 50 Frequency (Hz) (b) Phase of Zc Figure 6.6: Magnitude and phase angle of characteristic impedance of transmission lines 59 6 Results and discussion 6.2.1 Line impedance (a) Superbundle phasing (Circuit1) (b) Superbundle phasing (Circuit2) Figure 6.7: Position of conductors and ground wires for double circuit transmission lines in OHTLC Table 6.10: Positive sequence impedance (Per unit values) Voltage levels (kV) Phasing arrangements %R %X % R+jX %Z 500 kV Low reactance phasing 0.0434 0.4976 0.0434+j0.4976 0.4995 Superbundle phasing 0.0432 0.5003 0.0432+j0.5003 0.5022 Table 6.11: Positive sequence impedance (Actual values) Voltage levels (kV) Phasing arrangements R(Ω) X R+jX(Ω) Z(Ω) 500 kV Low reactance phasing 1.0838 12.44 1.0838+j12.44 12.4871 Superbundle phasing 1.0793 12.5086 1.0793+j12.5086 12.5551 The Overhead Transmission Line Constants Program has been used to calculate the line impedances of the overhead lines. Fig. 6.7 and Fig. 6.8 shows the position of phase conductors, ground wires , type of ground wires and the distance over which the line 60 6 Results and discussion (a) Low reactance phasing (Circuit1) (b) Low reactance phasing (Circuit2) Figure 6.8: Data configurations for double circuit transmission lines in OHTLC Table 6.12: Zero sequence impedance (Per unit values) Voltage levels (kV) Phasing arrangements %R %X % R+jX %Z 500 kV Low reactance phasing 0.6626 2.0970 0.6626+j2.0970 2.1992 Superbundle phasing 0.6615 2.0987 0.6615+j2.0987 2.2005 Table 6.13: Zero sequence impedance (Actual values) Voltage levels (kV) Phasing arrangements R (Ω) X R+jX (Ω) Z (Ω) 500 kV Low reactance phasing 16.5656 52.42 16.5656+j52.42 54.98 Superbundle phasing 16.5381 52.46 16.5381+j52.46 55.123 61 6 Results and discussion Figure 6.9: Phasing arrangements for double circuit transmission line in OHTLC Table 6.14: Positioning of conductors for line model drawn in OHTLC Phase no. Horizontal distance (m) Vtower distance (m) 1 6.5 15 2 9.5 20 3 5.5 30 4 -6.5 15 5 -9.5 20 6 -5.5 30 7 4.5 35 8 -4.5 35 62 6 Results and discussion impedance is calculated. The output positive sequence and zero sequence transmission line impedances are calculated for both phasing arrangements (superbundle and low reactance phasing) and both the results have been compared. Fig. 6.9 and Tab. 6.14 shows the position of conductors that has been used as input data for calculation of impedances in OHTLC. Tab. 6.10, Tab. 6.12, Tab. 6.11 and Tab. 6.13 shows the calculated values of impedances for superbundle and low reactance phasing. It has been evident that low reactance phasing yields lower value of impedances when compared to superbundle phasing. 63 6 Results and discussion 6.3 Experimental results In order to evaluate and compare magnetic fields for both phasing arrangements, a physical model has been setup in the laboratory at the chair of electromagnetic compatibility at the Otto-von-Guericke-Universität Magdeburg). The following devices has been used for the computation of results: • Field probes • Gigaport HD+ box • Power supply • Oscilloscope For physical setup we have used two wooden board (rectangular) having equal size. In order to fix both boards, a wooden pole structure has been used. A program has been written in Matlab which controls the output channels of the HD+ box. For different positions and different heights, the magnetic fields are computed and compared or both phasing arrangements. Fig. 6.10 shows the different types of devices that are being used during the measurement of magnetic field around overhead lines. Tab. 6.15 shows the measured values of magnetic fields for low reactance phasing and superbundle phasing. Double circuit lines (Fig. 6.11) have been constructed with the help of copper enamulated wire in the EMC laboratory at the chair of electromagnetic compatibility at the Otto-vonGuericke-Universität, Magdeburg. Tab. 6.15 shows the measured magnetic field of both phasing arrangements for different positions. Fig. 6.12a shows the measured magnetic field and Fig. 6.12b shows the simulation results of the magnetic field. It has been clearly shown that measured values are much lower when compared to the simulation values because of the large difference in current. At centre (distance=0 cm or 0 m, the field is maximum/stronger because of it’s closeness to the source, when we move far away from the source , the magnetic field tends to be lower/weaker. The simulation is performed at 500 kV and 1000 A, while the measured values are taken at 0.90 V and 0.43 A. Since magnetic field is directly proportional to current and it decreases with the distance from the source, the measured values are lower than simulation values. It has been clearly shown that the magnetic field is relatively low for low reactance phasing when compared to superbundle phasing. The magnetic field tends to decrease with the increase in distance from the source. When the phases of the overehead lines are interchanged i.e from superbundle phasing to low reactance phasing there is an approximately decrease in magnetic field by a factor of 15 - 18% for measured values, while there is a decrease in the magnetic field by a factor of 20 - 30% for simulated values. 64 6 Results and discussion (a) Power supply (b) Gigaport HD+ box (c) Oscilloscope (d) Magnetic field probe Figure 6.10: Devices used for experimental setup during the mesaurement of magnetic field 65 6 Results and discussion Table 6.15: Measured magnetic field in the EMC laboratory at the chair of electromagnetic compatibility at the Otto-von-Guericke- Universität, Magdeburg Phasing arrangements Distance from the centre Magnetic field Superbundle phasing 0 cm 0.622 µT 15 cm 0.215 µT 30 cm 36.1 nT 45 cm 15.3 nT 57 cm 10.6 nT 76 cm 6.8 nT 0 cm 0.542 µT 15 cm 0.159 µT 30 cm 34.2 nT 45 cm 13.2 nT 57 cm 9.3 nT 76 cm 4.9 nT Low reactance phasing Figure 6.11: Double circuit lines constructed in the EMC laboratory at the chair of electromagnetic compatibility at the Otto-von-Guericke- Universität, Magdeburg 66 6 Results and discussion ·10−7 7 Superbundle phasing Low reactance phasing 5 4 3 Magnetic flux (T) Magnetic field (T) 6 2 1 0 0 10 20 30 40 50 Distance (cm) 60 70 80 ·10−5 5 Low reactance phasing 4.5 4 Superbundle phasing 3.5 3 2.5 2 1.5 1 0.5 0 −100−80 −60 −40 −20 0 20 40 60 80 100 Distance (m) (a) Measured values at 0.91 V (b) Simulation results at 500 kV Figure 6.12: Magnetic fields comparison for measured values and values obtained from simulation 67 7 Summary Humans are exposed to electromagnetic fields directly or indirectly i.e by the means of natural sources like thunderstorms or by the means of manmade (transmission lines and electrical apparatus). Continuous exposure to these fields leads to various types of diseases like cancer, leukemia etc. The low frequency fields has an interference with electrical and electronic equipement in it’s close vicinity. So, we have to reduce the elctromagnetic fields around the environment, when it passes through dense populated areas. This work has presented electromagnetic field reduction techniques i.e by the use of different phasing arrangements magnetic fields have been reduced upto a certain level. We have calculated the magnetic fields for the following arrangements: • Superbundle phasing • Low reactance phasing A Matlab program has been written for the calculation of magnetic fields for both arrangements. In order to calculate the magnetic fields we have given the number of conductors, position of conductors and the heights of the conductors as input. From the results it has been shown that low reactance phasing produces a lower magnetic field when compared to superbundle phasing. The conductors are compacted by a factor of 15% and again the both phasing arrangements for compact conductors are studied and the results produce a lower magnetic field while compared to the original position of conductors. But compaction of conductors leads to structural instabilities and other problems. For both phasing arrangements the line impedances have been calculated with the help of OHTLC program and the results indicates a lower impedance value for low reactance phasing than superbundle phasing. The phase currents have been calculated with the help of EMTP and the results clearly indicates a lower current imbalance for low reactance phasing as compared to superbundle phasing. For both phasing arrangements a physical setup has been implemented in the EMC laboratory at the chair of electromagnetic compatibility at the Otto-von-Guericke-Universität, Magdeburg. The lines have been constructed and with the help of field probes, the magnetic fields has been computed and compared. The measured values clearly depict that there will be a lower magnetic field when there is change of phasing from superbundle to low reactance. 68 Bibliography [1] Wikipedia. Electromagnetic spectrum. Electromagnetic_spectrum. https://en.wikipedia.org/wiki/ [2] EdisonTechcentre. The history of alternating current: The history of electrification. http://www.edisontechcenter.org/HistElectPowTrans.html. [3] EMTP-RV, The reference for power systems transients. Emtp-rv : Software for power systems transients. http://emtp-software.com/software_for_power_systems_ transients. [4] David Houcque. INTRODUCTION TO MATLAB FOR ENGINEERING STUDENTS. Northwestern University, August 2005. [5] J. Rohan Lucas. High Voltage Engineering, chapter 5. High voltage cables, pages 64–82. University Of Moratuwa, Sri Lanka, 2001. [6] International Cable Protection Committee Ltd. About submarine power cables. http://www.docfoc.com/ title-international-cable-protection-committee-ltd-about-submarine-power-cables-i [7] Robert D. Castro. Overview of the transmission line design process. Electric Power Systems Research, 35:109–118, 1995. [8] Electrical4u. Types of electrical insulator | overhead insulator. http://www. electrical4u.com/types-of-electrical-insulator-overhead-insulator/. [9] ZMS Cable. Bare conductor aac/aaac/acsr. ACSR-conductor.html. http://www.zmscable.com/ [10] THE UNIVERSITY OF SYDNEY. Line and cables. http://sydney.edu.au/ engineering/electrical/courses/power/plant/lines.xml. [11] Geun-Joon Lee. Superconductivity application in power system. 2011. [12] ELECTRICAL ENGINEERING PORTAL. Analysing the costs of high voltage direct current (hvdc) transmission. http://electrical-engineering-portal.com/ analysing-the-costs-of-high-voltage-direct-current-hvdc-transmission. 69 Bibliography [13] Wikipedia. Electric power distribution. Electric_power_distribution. https://en.wikipedia.org/wiki/ [14] Hydro Quebec. The power system and health electric and magnetic fields. http: //www.hydroquebec.com/fields/pdf/pop_23_01.pdf. [15] AARONIA AG. International exposure limits. http://www.aaronia.com/basics/ limits/international-exposure-limits/. [16] Richard P. Sedano Matthew H. Brown. Electricity Transmission: A Primer. National Council on Electricity Policy, 2004. [17] Electrical Edition. A comparison of overhead line system,underground cable system. http://www.electricaledition.com/2016/01/ comparison-of-overhead-lines-underground-cables.html. [18] Quora. Why electricity is being transmitted in multiple of 11? https://www.quora. com/Why-electricity-is-being-transmitted-in-multiple-of-11. [19] Wikipedia. High voltage. https://en.wikipedia.org/wiki/High_voltage. [20] Electromagnetic fields and public health, June 2007. http://www.who.int/peh-emf/ publications/facts/fs322/en/. [21] PediaView.com- Open Source Encyclopedia. International commission on nonionizing radiation protection. https://pediaview.com/openpedia/International_ Commission_on_Non-Ionizing_Radiation_Protection. [22] Wikipedia. International commission on non-ionizing radiation protection. https://en.wikipedia.org/wiki/International_Commission_on_ Non-Ionizing_Radiation_Protection. [23] Michael R. Murphy and Ronald C. Petersen. IEEE ICES Safety Standards for Electromagnetic Energy. IEEE ICES, Directed Energy Bioeffects Division, Air Force Research Laboratory, Brooks City-Base, TX, USA; )IEEE ICES, Piscataway, NJ, USA, 2006. [24] Wikipedia. History of electric power transmission. https://en.wikipedia.org/ wiki/History_of_electric_power_transmission. [25] EMTP-RV, The reference for power systems transients. Emtp-rv : Overview. http: //emtp-software.com/Overview. [26] Wikipedia. Matlab. https://en.wikipedia.org/wiki/MATLAB. 70 Bibliography [27] Gegrid solutions. Protection basics: Introduction to symmetrical components. https: //www.gegridsolutions.com/smartgrid/Dec07/7-symmetrical.pdf. [28] Curt Harting. Ac transmission line losses. Coursework for physics 240, Stanford University, Fall 2010. 71 View publication stats