Question bank (Part 1) Power System (3) Problem 1 For the circuit shown in figure 1, find the following; 1. The bus admittance matrix assuming no mutual coupling between any of the branches 2. Using the admittance matrix modification procedure and assuming nomutual coupling between branches, modify the admittance bus obtained in 1 to reflect removal of two branches 1-3 and 2-5 from the circuit Fig. 1 Problem 2 For the linear graph shown in figure 2 for the circuit shown in figure 1, find the following disregarding all mutual coupling between branches; 1. The branch-to-node incidence matrix A for the circuit with node 0 as reference. 2. Find the circuit admittance matrix using the network incidence matrix Problem 3 For the circuit shown in figure 1, considering that only two branches 1-3 and 2-3 are mutually coupled with mutual impedance is π0.15 per unit, find the following; 1. Branch admittance matrix. 2. Branch-to-node incidence matrix A wit node 0 reference. Then find the circuit admittance matrix using the network incidence matrix Problem 4 For the circuit shown in figure 1, solve; 1. The nodal equation to find the voltages at the four buses of Prob. 2. 2. The nodal equation to find the voltages at the four buses of Prob. 3. 2 Using both gaussian elimination and Kron reduction methods. Problem 5 - Determine the bus admittance matrix (πππ’π ) for the following power three phase system (note that some of the values have already been determined for you). Assume a three-phase 100 MVA per unit base. - Assume that a 75 Mvar shunt capacitance (three phase assuming one per unit bus voltage) is added at bus 4. Calculate the new value of Y44. Bus input data Problem 6 - Form the impedance matrix for the circuit shown in Fig. after removing node 5 by converting the voltage source to a current source, Determine the voltages with respect to reference node at each of four other nodes when π = 1.2∠0° and the load currents are πΌπΏ1 = −π0.1, πΌπΏ2 = −π0.1, πΌπΏ3 = −π0.2, and πΌπΏ4 = −π0.2, all in per unit. - Then draw the Thevenin equivalent circuit at bus 4 and use it to determine the current drawn by a capacitor of reactance 5.4 per unit connected between bus 4 and reference. - Calculate the voltage changes at each of the buses due to the capacitor. 3 - Calculate the total reactive power loss in the system. Problem 7 - Modify the impedance matrix of the Prob. 1 to include a capacitor of reactance 5.4 per unit connected from bus 4 to reference. - Calculate the new bus voltages using the modified impedance bus. Problem 8 For the reactance network of the Fig. find; - The impedance matrix by direct formulation - The voltage at each bus - The current drawn by a capacitor having a reactance of 5.0 per unit connected from bus 3 to neutral. - The change in voltage at each bus when the capacitor is connected at bus 3. - The voltage at each bus after connecting the capacitor. The magnitude and angle of each of the generated voltages may be assumed to remain constant. 4 Problem 9 Find the impedance bus for the three-bus circuit of the Fig. by the impedance matrix building algorithm. Problem 10 Consider the simplified electric power system shown in Figure for which the power flow solution can be obtained without resorting to iterative techniques. a. Compute the elements of the bus admittance matrix πππ’π . b. Calculate the phase angle πΏ2 by using the real power equation at bus 2 (voltage-controlled bus). c. Determine |π3 | and πΏ3 by using both the real and reactive power equations at bus 3 (load bus). d. Find the real power generated at bus 1 (swing bus). e. Evaluate the total real power losses in the system. Problem 11 - Assume a 0.8 + π0.4 per unit load at bus 2 is being supplied by a generator at bus 1 through a transmission line with series impedance of 0.05 + π0.1 per unit. Assuming bus 1 is the swing bus with a fixed per unit voltage of 1.0∠0, use the Gauss-Seidel method to calculate the voltage at bus 2 after three iterations. 5 - Repeat the above problem with the swing bus voltage changed to 1.0 ∠30° per unit. Problem 12 - For the three-bus system whose πππ’π is given below, calculate the second iteration value of π3 using the Gauss-Seidel method. Assume bus 1 as the slack (with π1 = 1.0∠0), and buses 2 and 3 are load buses with a per unit load of π2 = 1 + π0.5 and π3 = 1.5 + π0.75. Use voltage guesses of 1.0∠0 at both buses 2 and 3. The bus admittance matrix for a three-bus system is - Repeat the first problem except assume the bus 1 (slack bus) voltage of π1 = 1.05∠0. Problem 13 The bus admittance matrix for the power system shown in Figure is given by With the complex powers on load buses 2, 3, and 4 as shown in Figure, determine the value for π2 that is produced by the first and second iterations of the Gauss–Seidel procedure. Choose the initial guess π2 (0) = π3 (0) = π4 (0) = 1.0 ∠0 per unit. 6 Problem 14 The bus admittance matrix of a three-bus power system is given by with π1 = 1.0 ∠0 per unit; π2 = 1.0 per unit; π2 = 60 MW; π3 = −80 MW; π3 = −60 MVAR (lagging) as a part of the power-flow solution of the system. Find π2 and π3 within a tolerance of 0.01 per unit. Start with πΏ2 = 0, π3 = 1.0 per unit, and πΏ3 = 0. By using - Gauss-Seidel iteration method - Newton-Raphson method use a maximum power flow mismatch of 0.1 MVA. - Fast decoupled method - DC load flow Problem 15 A generator bus (with a 1.0 per unit voltage) supplies a 150 MW, 50 Mvar load through a lossless transmission line with per unit (100 MVA base) impedance of π0.1 and no line charging. Starting with an initial voltage guess 7 of 1.0 ∠0, iterate until converged using the Newton–Raphson power flow method and fast decoupled method. For convergence criteria use a maximum power flow mismatch of 0.1 MVA. Problem 16 For a three bus power system assume bus 1 is the swing with a per unit voltage of 1.0 ∠0, bus 2 is a PQ bus with a per unit load of 2.0 + π0.5, and bus 3 is a PV bus with 1.0 per unit generation and a 1.0 voltage setpoint. The per unit line impedances are j0.1 between buses 1 and 2, π0.4 between buses 1 and 3, and π0.2 between buses 2 and 3. Using a flat start, use the Newton– Raphson approach and fast decoupled method to determine the first iteration phasor voltages at buses 2 and 3. Problem 17 Figure shows the one-line diagram of a simple power system. Generators are connected at buses 1 and 4 while loads are indicated at all four buses. Base values for the transmission system, are 100 MVA, 230 kV. The π values or load are calculated from the corresponding π values assuming a power factor or 0.85. The net scheduled values, ππ and ππ are negative at the load buses 2 and 3. Generated ππΊπ is not specified where voltage magnitude is constant. In the voltage column the values for the load buses are flat start estimates. The slack bus voltage magnitude |π1 | and angle πΏ1 , and magnitude |π4 | at bus 4, are to be kept constant at the values listed. 1. Calculate the value of π2 for the first iteration using Gauss-Seidel method. 2. Calculate the value of π2 for the first iteration using Gauss-Seidel method with considering acceleration factor equal to 1.6. 3. Calculate the voltage at bus 4 with the originally estimated voltages at buses 2 and 3 replaced by the accelerated values indicated in (2). 4. Calculate the active and reactive power at the slack bus. 8 Problem 18 The small power system of Ex. 17, power flow study of the system is to be made by the Newton-Raphson method using the polar form of the equations for P and Q. 1. Determine the number of rows and columns in the jacobian. (0) 2. Calculate the initial mismatch βπ3 jacobian elements. 9 and the initial values of the 3. Calculate the state variables required in the power flow solution using Newton Raphson method. 4. Calculate the active and reactive power at the slack bus. 5. Calculate the state variables required in the power flow solution using Fast decoupled method. Problem 19 Two transformers are connected in parallel to supply an impedance to neutral per phase of 0.8 + π 0.6 per unit at a voltage of π2 = 1 .0∠0° per unit. Transformer Ta has a voltage ratio equal to the ratio of the base voltages on the two sides of the transformer. This transformer has an impedance of π0.1 per unit on the appropriate base. The second transformer Tb also has an impedance of π0.1 per unit on the same base but has a step-up toward the load of 1.05 times that of Ta (secondary windings on 1.05 tap). Figure 4.10 shows the equivalent circuit with transformer Tb represented by its impedance and the insertion of a voltage βπ. 1. Find the complex power transmitted to the load through each transformer using πππ’π model for each of two parallel transformers. 2. Repeat (1) except that Tb includes both a transformer having the same turns ratio as Ta and a regulating transformer with a phase shift of 3° (t = 1 .0∠3° ). The impedance of the two components of Tb is j0.1 per unit on the base of Ta. Problem 20 For each bus k, determine which of the variables ππ , πΏπ , ππ , and ππ are input data and which are unknowns. 10 Table. Bus input data Table. Line input data Table. Transformer input data 11 Table. Input data and unknowns 1. Compute the elements of the πππ’π . 2. Determine the DC power-flow solution for the five-bus system. 12