BUS BAR PROTECTION BY EMD WHAT IS BUS BAR AND MODELS • An electrical bus bar is defined as a conductor or a group of conductor used for collecting electrical energy from the incoming feeders and distributes them to the outgoing feeders • Types of Bubar Arrangements: 1.Single Bus bar Arrangement 2.Single Bus-Bar Arrangement With Bus Sectionalized 3.Main and Transfer Bus Arrangement 4.Double Bus Double Breaker Arrangement 5.Sectionalized Double Bus Bar Arrangement. 6.One and a Half Breaker Arrangement 7.Ring Main Arrangement 8.Mesh Arrangement SINGLE BUS BAR ARRANGEMENT ADVANTAGES DISADVANTAGES 1. Simple in Design In case of bus fault or bus 2. Easy Maintenance bar isolator fault or 3. Less Expenditure maintenance , Total 4. Good Appearance Substation is out of service. SINGLE BUS WITH CB SECTIONALISER SYSTEM ADVANTAGES DISADVANTAGES 1. One complete section can 1. In case of any fault in be taken out for maintenance bus bar /bus connected without disturbing the isolator maintenance continuity of other section. all connected feeders 2. Even if a fault occurs on of that section will be one section of the bus, that out of service . faulty section along will 2. Bay CT/CB be isolated while the other maintenance can be section continues to be in carried out results service feeder will be out of service SINGLE BUS & TRANSFER BUS SYSTEM ADVANTAGES DISADVANTAGES With this arrangement, all the feeders are normally on the main bus. If at any time, a line breaker maintenance is required, that particular feeder, can be transferred on to the transfer bus. The feeder protection thus gets transferred to trip bus couple breaker. 1. On fault occurrence or maintenance, entire bus becomes de-energised. 2. Only one line at a time can be transferred on the transfer bus DOUBLE MAIN BUS & TRANSFER BUS SYSTEM Salient features:- • This has got flexibility of transferring any line to any of the main buses. • For maintenance or any fault occurrence, only one bus becomes dead while • other bus continues to be in service. • Any line breaker can be taken out for maintenance by transferring it to • transfer bus, transferring its protection to transfer bus coupler breaker. ONE AND HALF CIRCUIT BREAKER SYSTEM Salient features:1. No changeover of line from one bus to the other is required. 2. For breaker maintenance of any line, the load gets transferred to the other bus. 3. For maintenance or an occurrence of a bus fault, all the interconnections will be on healthy bus. 4. Even if both buses become dead, lines can still be in service through the tiebreaker. This has got many such advantages to maintain the system stability. WHY BUS BAR PROTECTION REQUIRED ? Slow fault clearance. Busbar faults at F1 and F2 are cleared by remote time delayed Protection on circuits feeding the faults: Time Delayed Over current or Time Delayed Distance Protection Fast clearance by breakers at the busbars instantly Where busbars are sectionalised,Protection can limit the amount of system disruption for a busbar fault BUS BAR PROTECTION TYPES Two types of Busbar protection are implemented and used • Frame Leakage Protection • Differential protection or Circulating Current Protection • High impedance BBP • Low Impedance BBP • Centralised Busbar Protection • Decentralised busbar Protection (Digital Busbar Protection) FRAME LEAKAGE PROTECTION OF BUSBAR • In this, the bus bar supporting frame will be earthen through a current transformer. When the fault in busbar, the fault current flow through supporting frame’s earthing arrangement. The Current transformer in the earthen frame reads the fault current and if this fault current higher than the pickup current, then the relay operates. • Disadvantages: Careful construction of the system is of utmost importance in this case, as the switchgear must be insulated from ground, usually by standing it on concrete and the foundation bolts must not touch the steel reinforcement. THEORY BEHIND BBP • Busbar Protection is the Differential scheme in which current entering and leaving the bus should be equal • During Normal Load Conditions , The sum of these currents is equal to Zero. When fault occurs in protected zone , the differential current will flow through the relay and causes opening of connected breakers on the particular bus. HIGH IMPEDANCE BBP High impedance is nothing but a where the impedance value of the circuit is high which means when the circuit operates in high voltage with low current is called high impedance circuit. 1. The parallel CT must have same CT ratio 2. The CTs must be connected in same polarity Burden of the all parallel CTs should be same. In order to avoid the voltage, drop across the CT 3. CT accuracy should be same 4. CT cannot be shared with other circuit’s equipments LOW IMPEDANCE BBP Low impedance circuits are exactly opposite to the high impedance circuits, which means the circuit operates low voltage with high current such a circuit is called Low impedance circuit. The low-impedance bus differential relays can share the CTs with other relays, meters, transducers, etc • Centralised Busbar protection : In this solution, all copper wires from current transformers and status of disconnections, as well as the tripping circuits to the circuit breakers, are connected to a central panel, where the busbar protection IED is installed. • Decentralized busbar protection : In this case bay units are installed in the individual bay protection panels to provide the interfaces from the primary equipment to the busbar protection system. The bay units will be installed in the switchyard, close to the primary equipment.