Uploaded by er036905

7220 defult setting

advertisement
DEEP SEA ELECTRONICS
7220 INST ALL AT IO N INSTRUCTIONS
TYPICAL WIRING DIAGRAM
053-027
ISSUE 4
ACCESSING THE FRONT PANEL CONFIGURATION EDITOR
•
Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset
•
•
Press the Stop/Reset
and Info
buttons simultaneously.
If a module security PIN has been set, the PIN number request is then
shown :
(up) or
button.
•
Press
, the first ‘#’ changes to ‘0’. Press
correct value.
(down) to adjust it to the
•
Press
(right) when the first digit is correctly entered. The digit you have just entered will now
show ‘#’ for security.
•
Repeat this process for the other digits of the PIN number. You can press
move back to adjust one of the previous digits.
•
When
is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is
not correct, you must re-enter the PIN.
•
If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed :
(left) if you need to
EDITING A PARAMETER
•
•
•
•
To edit the parameter, press
to enter edit mode. The parameter begins to flash to indicate that
you are editing the value.
Press the up or down buttons to change the parameter to the required value.
•
Press
•
To exit the editor at any time, press and hold the
•
Deep Sea Electronics Plc.
Deep Sea Electronics inc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
LO CALL (from UK BT landlines) :
Telephone 0845 260 8933
Email: support@deepseaplc.com
Web: www.deepseaplc.com
Phone: +1 (815) 316-8706
Fax: +1 (815) 316- 8708
TOLL FREE (USA only) : Tel: 1 866 636 9703
Email: dsesales@deepseausa.com
Web: www.deepseausa.com
Deep Sea Electronics Plc.
(Far East)
Tel:+66 2 670 6228
Fax: +66 2 678 3028
Email: support@deepseaplc.com
Web: www.deepseaplc.com
Enter the editor as described above.
Press the left or right buttons to cycle to the section you wish to view/change.
Press the up or down buttons to select the parameter you wish to view/change within the currently
selected section.
to save the value. The parameter ceases flashing to indicate that it has been saved.
button.
NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure
security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to
ensure security.
NOTE: More comprehensive module configuration is possible using the 7xxx series PC configuration
software. Please contact us for further details
ADJUSTABLE PARAMETERS (Configuration editor)
Front Panel Configuration Editor
Section Parameter as shown on display
DISPLAY
EDITOR
ENGINE
Contrast
Language
LCD Page Timer
Auto Scroll Delay
Current Date and time
Alt Config
Oil Pressure Low Shutdown
Oil Pressure Low Pre Alarm
Coolant Temperature Low Warning
Coolant Temperature High Pre Alarm
Coolant Temperature High Shutdown
Start Delay Timer
Pre Heat Timer
Crank Duration Timer
Crank Rest Timer
Safety On Delay
Smoke Limiting
Smoke Limiting Off
Warm Up Timer
Cool Down Timer
Engine Under Speed Shutdown
Engine Under Speed Shutdown
Engine Under Speed Warning
Engine Under Speed Warning
Engine Over Speed Warning
Engine Over Speed Warning
Engine Over Speed Shutdown
Engine Speed Overshoot Delay
Engine Speed Overshoot
Fail To Stop Delay
Battery Under Voltage Warning
Battery Under voltage Warning Delay
Battery Under Voltage
Battery Over Voltage Warning
Battery Over Voltage Warning Delay
Battery Over Voltage Warning
Charge Alternator Failure Warning
Charge Alternator Failure Warning
Charge Alternator Warning Delay
Charge Alternator Failure Shutdown
Charge Alternator Failure Shutdown
Charge Alternator Shutdown Delay
Droop control
Droop control
GENERATOR Generator Under Voltage Shutdown
Generator Under Voltage Pre Alarm
Generator Voltage Nominal
Generator Over Voltage Pre Alarm
Generator Over Voltage Shutdown
Generator Under Frequency Shutdown
Generator Under Frequency Pre Alarm
Generator Frequency Nominal
Generator Over Frequency Pre Alarm
Generator Over Frequency Shutdown
Full Load Rating
Kw Overload Trip
Delayed Over Current
Delayed Over Current
AC System
CT Primary
CT Secondary
Generator Transient Delay
Front Panel Configuration Editor
Factory Settings
Section Parameter as shown on display
53%
English
5m
2s
hh:mm
Default Config
1.03bar
1.17bar
70ºC
90ºC
95ºC
5s
0s
10s
10s
10s
0s
0s
0s
1m
Inactive
1200RPM
Inactive
1350RPM
Inactive
1650RPM
1710RPM
2s
0s
30s
Active
1m
10V
Active
1m
30V
Active
6V
5s
Active
4.0V
5s
Inactive
4%
(Compatible engine ECUs only)
184V
196V
230V
265V
276V
40Hz
42Hz
50.0Hz
55Hz
57Hz
500A
100%
Active
100%
3 Phase, 4 Wire
600A
5A
0s
MAINS
TIMERS
Factory Settings
Mains Under Voltage Trip
Mains Over Voltage Trip
Mains Under Frequency Trip
Mains Over Frequency Trip
Mains Transient Delay
Return Delay
Mains Transfer Time
LCD Page Timer
Auto Scroll Delay
Start Delay Timer
Pre Heat Timer
Crank Duration Timer
Crank Rest Timer
Safety On Delay
Smoke Limiting
Smoke Limiting Off
Warm Up Timer
Cool Down Timer
Speed Overshoot Delay
Fail To Stop Delay
Battery voltage Low Warning Delay
Battery Voltage High Warning Delay
Return Delay
Generator Transient Delay
Mains Transient Delay
Mains Transfer Time
184V
276V
45Hz
55Hz
2s
30s
0.7s
5m
3s
5s
0s
10s
10s
10s
0s
0s
0s
1m
2s
30s
1m
1m
30s
0s
2s
0.7s
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
•
The ‘running’ editor can be entered while the engine is running. All protections remain active if the
engine is running while the running editor is entered.
•
Press and hold the
button to enter the running editor.
EDITING A PARAMETER
•
Enter the editor as described above.
•
Press the left or right buttons to cycle to the section you wish to view/change.
•
Press the up or down buttons to select the parameter you wish to view/change within the currently
selected section.
•
To edit the parameter, press
to enter edit mode. The parameter begins to flash to indicate that
you are editing the value.
Press the up or down buttons to change the parameter to the required value.
•
Press
•
To exit the editor at any time, press and hold the
•
to save the value. The parameter ceases flashing to indicate that it has been saved.
button.
ADJUSTABLE PARAMETERS (Running editor)
Running Editor
Section Parameter as shown on display
Factory Settings
DISPLAY
53%
English
0.0Hz
ENGINE
Contrast
Language
Manual Frequency Trim (Electronic engines only)
DIMENSIONS
240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”)
PANEL CUTOUT:
220mm x 160mm (8.7” x 6.3”)