Uploaded by a_calisura

Section 7 Fault Analysis

advertisement
SECTION 7: FAULT ANALYSIS
ESE 470 – Energy Distribution Systems
2
K. Webb
Introduction
ESE 470
Power System Faults
3

Faults in three-phase power systems are short circuits



Line-to-ground
Line-to-line
Result in the flow of excessive current

Damage to equipment



Heat – burning/melting
Structural damage due to large magnetic forces
Bolted short circuits

True short circuits – i.e., zero impedance

In general, fault impedance may be non-zero

Faults may be opens as well

K. Webb
We’ll focus on short circuits
ESE 470
Types of Faults
4

Type of faults from most to least common:
 Single
line-to-ground faults
 Line-to-line faults
 Double line-to-ground faults
 Balanced three-phase (symmetrical) faults

We’ll look first at the least common type of fault –
the symmetrical fault – due to its simplicity
K. Webb
ESE 470
5
K. Webb
Symmetrical Faults
ESE 470
Symmetrical Faults
6

Faults occur nearly instantaneously


Step change from steady-state behavior


Lightening, tree fall, arcing over insulation, etc.
Like throwing a switch to create the fault at 𝑡𝑡 = 0
Equivalent circuit model:
R: generator resistance
 L: generator inductance
𝑣𝑣 𝑡𝑡 = 2𝑉𝑉 sin 𝜔𝜔𝜔𝜔 + 𝛼𝛼
 𝑖𝑖 𝑡𝑡 = 0 for 𝑡𝑡 < 0
 Source phase, 𝛼𝛼, determines voltage at 𝑡𝑡 = 0

𝐺𝐺

K. Webb
Short circuit can occur at any point in a 60 Hz cycle
ESE 470
Symmetrical Faults
7


The governing differential equation for 𝑡𝑡 > 0 is
𝑑𝑑𝑑𝑑
𝑅𝑅
2𝑉𝑉𝐺𝐺
sin 𝜔𝜔𝜔𝜔 + 𝛼𝛼
+ 𝑖𝑖 𝑡𝑡
=
𝐿𝐿
𝑑𝑑𝑑𝑑
𝐿𝐿
The solution gives the fault current
𝑅𝑅
2𝑉𝑉𝐺𝐺
−𝑡𝑡
𝑖𝑖 𝑡𝑡 =
sin 𝜔𝜔𝜔𝜔 + 𝛼𝛼 − 𝜃𝜃 − sin 𝛼𝛼 − 𝜃𝜃 𝑒𝑒 𝐿𝐿
𝑍𝑍

where 𝑍𝑍 = 𝑅𝑅2 + 𝜔𝜔𝜔𝜔
2
and 𝜃𝜃 = tan−1
𝜔𝜔𝜔𝜔
𝑅𝑅
This total fault current is referred to as the asymmetrical fault current


K. Webb
It has a steady-state component
2𝑉𝑉𝐺𝐺
sin 𝜔𝜔𝜔𝜔 + 𝛼𝛼 − 𝜃𝜃
𝑖𝑖𝑎𝑎𝑎𝑎 𝑡𝑡 =
𝑍𝑍
And a transient component
𝑖𝑖𝑑𝑑𝑑𝑑
𝑅𝑅
2𝑉𝑉𝐺𝐺
−𝑡𝑡
sin 𝛼𝛼 − 𝜃𝜃 𝑒𝑒 𝐿𝐿
𝑡𝑡 = −
𝑍𝑍
ESE 470
Symmetrical Faults
8

Magnitude of the transient fault current, 𝑖𝑖𝑑𝑑𝑑𝑑 , depends on 𝛼𝛼


𝑖𝑖𝑑𝑑𝑑𝑑 0 = 0 for
𝑖𝑖𝑑𝑑𝑑𝑑 0 = 2𝐼𝐼𝑎𝑎𝑎𝑎 for


𝛼𝛼 = 𝜃𝜃
𝛼𝛼 = 𝜃𝜃 − 90°
𝐼𝐼𝑎𝑎𝑎𝑎 = 𝑉𝑉𝐺𝐺 /𝑍𝑍 is the rms value of the steady-state fault current
Worst-case fault current occurs for 𝛼𝛼 = 𝜃𝜃 − 90°
K. Webb
𝑅𝑅
2𝑉𝑉𝐺𝐺
𝜋𝜋
−𝑡𝑡
𝑖𝑖 𝑡𝑡 =
sin 𝜔𝜔𝜔𝜔 −
+ 𝑒𝑒 𝐿𝐿
𝑍𝑍
2
ESE 470
Symmetrical Faults
9

Important points here:
fault current has both steady-state and transient
components – asymmetrical
 Total
 Magnitude
of the asymmetry (transient component)
depends on the phase of the generator voltage at the
time of the fault
K. Webb
ESE 470
Generator Reactance
10


The reactance of the generator was assumed
constant in the previous example
Physical characteristics of real generators result in a
time-varying reactance following a fault
 Time-dependence
′′
 𝑋𝑋𝑑𝑑 :
′
 𝑋𝑋𝑑𝑑 :
modeled with three reactance values
subtransient reactance
transient reactance
 𝑋𝑋𝑑𝑑 : synchronous reactance
 Reactance
K. Webb
increases with time, such that
𝑋𝑋𝑑𝑑′′ < 𝑋𝑋𝑑𝑑′ < 𝑋𝑋𝑑𝑑
ESE 470
Sub-Transient Fault Current
11

Transition rates between reactance values are dictated by two time
constants:




𝜏𝜏𝑑𝑑′′ : short-circuit subtransient time constant
𝜏𝜏𝑑𝑑′ : short-circuit transient time constant
𝜋𝜋
Neglecting generator resistance and assuming 𝜃𝜃 = − , the synchronous
2
portion of the fault current is
𝑖𝑖𝑎𝑎𝑎𝑎 𝑡𝑡 = 2𝑉𝑉𝐺𝐺
𝑡𝑡
𝑡𝑡
− ′′
− ′
1
1
1
1
1
𝜋𝜋
𝜏𝜏
𝜏𝜏
𝑑𝑑
𝑑𝑑
−
𝑒𝑒
+ ′−
𝑒𝑒
+
sin 𝜔𝜔𝜔𝜔 + 𝛼𝛼 −
𝑋𝑋𝑑𝑑′′ 𝑋𝑋𝑑𝑑′
𝑋𝑋𝑑𝑑 𝑋𝑋𝑑𝑑
𝑋𝑋𝑑𝑑
2
At the instant of the fault, 𝑡𝑡 = 0, the rms synchronous fault current is


K. Webb
𝑰𝑰′′
𝐹𝐹
𝑽𝑽𝐺𝐺
= ′′
𝑋𝑋𝑑𝑑
This is the rms subtransient fault current, 𝑰𝑰′′
𝐹𝐹
This will be our primary metric for assessing fault current
ESE 470
12
K. Webb
Symmetrical Three-Phase Short
Circuits
ESE 470
13
Symmetrical 3-𝜙𝜙 Short Circuits


Next, we’ll calculate the subtransient fault current
resulting from a balanced three-phase fault
We’ll make the following simplifying assumptions:

Transformers modeled with leakage reactance only
Neglect winding resistance and shunt admittances
 Neglect Δ-𝑌𝑌 phase shifts

Transmission lines modeled with series reactance only
 Synchronous machines modeled as constant voltage sources
in series with subtransient reactances


Generators and motors
Induction motors are neglected or modeled as synchronous
motors
 Non-rotating loads are neglected

K. Webb
ESE 470
14
Symmetrical 3-𝜙𝜙 Short Circuits



We’ll apply superposition to determine three-phase
subtransient fault current
Consider the following power system:
Assume there is a balanced three-phase short of bus 1
to ground at 𝑡𝑡 = 0
K. Webb
ESE 470
15
Symmetrical 3-𝜙𝜙 Short Circuits


The instant of the fault can be modeled by the switch
closing in the following line-to-neutral schematic
The short circuit (closed switch) can be represented by two
back-to-back voltage sources, each equal to 𝑽𝑽𝐹𝐹
K. Webb
ESE 470
16
Symmetrical 3-𝜙𝜙 Short Circuits

Applying superposition, we can represent this circuit as the
sum of two separate circuits:
Circuit 1
K. Webb
Circuit 2
ESE 470
17
Symmetrical 3-𝜙𝜙 Short Circuits

Assume that the value of the fault-location source,
𝑽𝑽𝐹𝐹 , is the pre-fault voltage at that location
 Circuit
 The
𝑰𝑰′′
𝐹𝐹1 = 0
𝑽𝑽𝐹𝐹 source can therefore be removed from circuit 1
Circuit 1
K. Webb
1, then, represents the pre-fault circuit, so
Circuit 2
ESE 470
18
Symmetrical 3-𝜙𝜙 Short Circuits



The current in circuit 1, 𝑰𝑰𝐿𝐿 , is the pre-fault line current
Superposition gives the fault current
′′
′′
′′
𝑰𝑰′′
𝐹𝐹 = 𝑰𝑰𝐹𝐹𝐹 + 𝑰𝑰𝐹𝐹𝐹 = 𝑰𝑰𝐹𝐹𝐹
The generator fault current is
′′
′′
𝑰𝑰′′
=
𝑰𝑰
+
𝑰𝑰
𝐺𝐺
𝐺𝐺𝐺
𝐺𝐺𝐺

′′
𝑰𝑰′′
=
𝑰𝑰
+
𝑰𝑰
𝐿𝐿
𝐺𝐺
𝐺𝐺𝐺
The motor fault current is
′′
′′
𝑰𝑰′′
=
𝑰𝑰
+
𝑰𝑰
𝑀𝑀𝑀
𝑀𝑀𝑀
𝑴𝑴
K. Webb
′′
𝑰𝑰′′
=
−𝑰𝑰
+
𝑰𝑰
𝐿𝐿
𝑀𝑀
𝑀𝑀𝑀
ESE 470
19
Symmetrical 3-𝜙𝜙 Fault – Example

For the simple power system above:





Generator is supplying rated power
Generator voltage is 5% above rated voltage
Generator power factor is 0.95 lagging
A bolted three-phase fault occurs at bus 1
Determine:



K. Webb
Subtransient fault current
Subtransient generator current
Subtransient motor current
ESE 470
20
Symmetrical 3-𝜙𝜙 Fault – Example

First convert to per-unit




Use 𝑆𝑆𝑏𝑏 = 100 𝑀𝑀𝑀𝑀𝑀𝑀
Base voltage in the transmission line zone is
𝑉𝑉𝑏𝑏,𝑡𝑡𝑡𝑡 = 138 𝑘𝑘𝑘𝑘
Base impedance in the transmission line zone is
𝑍𝑍𝑏𝑏,𝑡𝑡𝑡𝑡
2
𝑉𝑉𝑏𝑏,𝑡𝑡𝑡𝑡
138 𝑘𝑘𝑘𝑘 2
=
=
= 190.4 Ω
𝑆𝑆𝑏𝑏
100 𝑀𝑀𝑀𝑀𝑀𝑀
The per-unit transmission line reactance is
𝑋𝑋𝑡𝑡𝑡𝑡 =
K. Webb
20 Ω
= 0.105 𝑝𝑝. 𝑢𝑢.
190.4 Ω
ESE 470
21
Symmetrical 3-𝜙𝜙 Fault – Example

The two per-unit circuits are

These can be simplified by combining impedances
K. Webb
ESE 470
22
Symmetrical 3-𝜙𝜙 Fault – Example



Using circuit 2, we can calculate the subtransient fault current
𝑰𝑰′′
𝐹𝐹
1.05∠0°
= 9.079∠ − 90° 𝑝𝑝. 𝑢𝑢.
=
𝑗𝑗𝑗.116
To convert to kA, first determine the current base in the generator
zone
𝐼𝐼𝑏𝑏,𝐺𝐺 =
𝑆𝑆𝑏𝑏
3𝑉𝑉𝑏𝑏,𝐺𝐺
=
100 𝑀𝑀𝑀𝑀𝑀𝑀
3 ⋅ 13.8 𝑘𝑘𝑘𝑘
The subtransient fault current is
= 4.18 𝑘𝑘𝑘𝑘
𝑰𝑰′′
𝐹𝐹 = 9.079∠ − 90° ⋅ 4.18 𝑘𝑘𝑘𝑘
𝑰𝑰′′
𝐹𝐹 = 37.98∠ − 90° 𝑘𝑘𝑘𝑘
K. Webb
ESE 470
23
Symmetrical 3-𝜙𝜙 Fault – Example

The pre-fault line current can be calculated from
the pre-fault generator voltage and power
𝑰𝑰𝐿𝐿 =
 Or,
𝑆𝑆𝐺𝐺
3𝑽𝑽′′
𝐺𝐺
=
100 𝑀𝑀𝑀𝑀𝑀𝑀
3 ⋅ 1.05 ⋅ 13.8 𝑘𝑘𝑘𝑘
𝑰𝑰𝐿𝐿 = 3.98∠ − 18.19° 𝑘𝑘𝑘𝑘
∠ − cos −1 0.95
in per-unit:
 This
3.98∠ − 18.19° 𝑘𝑘𝑘𝑘
= 0.952∠ − 18.19° 𝑝𝑝. 𝑢𝑢.
𝑰𝑰𝐿𝐿 =
4.18 kA
will be used to find the generator and motor fault
currents
K. Webb
ESE 470
24
Symmetrical 3-𝜙𝜙 Fault – Example


The generator’s contribution to the fault current is found by applying
current division
𝑰𝑰′′
𝐺𝐺𝐺
=
𝑰𝑰′′
𝐹𝐹
0.505
= 7.0∠ − 90° 𝑝𝑝. 𝑢𝑢.
0.505 + 0.15
Adding the pre-fault line current, we have the subtransient generator fault
current
′′
𝑰𝑰′′
𝐺𝐺 = 𝑰𝑰𝐿𝐿 + 𝑰𝑰𝐺𝐺𝐺
𝑰𝑰′′
𝐺𝐺 = 0.952∠ − 18.19° + 7.0∠ − 90°

Converting to kA
𝑰𝑰′′
𝐺𝐺 = 7.35∠ − 82.9° 𝑝𝑝. 𝑢𝑢.
𝑰𝑰′′
𝐺𝐺 = 7.35∠ − 82.9° ⋅ 4.18 𝑘𝑘𝑘𝑘
K. Webb
𝑰𝑰′′
𝐺𝐺 = 30.74∠ − 82.9° 𝑘𝑘𝑘𝑘
ESE 470
25
Symmetrical 3-𝜙𝜙 Fault – Example


Similarly, for the motor
𝑰𝑰′′
𝑀𝑀𝑀
=
𝑰𝑰′′
𝐹𝐹
0.15
= 2.08∠ − 90° 𝑝𝑝. 𝑢𝑢.
0.505 + 0.15
Subtracting the pre-fault line current gives the subtransient motor
fault current
′′
𝑰𝑰′′
𝑀𝑀 = −𝑰𝑰𝐿𝐿 + 𝑰𝑰𝑀𝑀𝑀
𝑰𝑰′′
𝑀𝑀 = −0.952∠ − 18.19° + 2.08∠ − 90°

𝑰𝑰′′
𝑀𝑀 = 2.0∠ − 116.9°
Converting to 𝑘𝑘𝑘𝑘
𝑰𝑰′′
𝑀𝑀 = 2.0∠ − 116.9° ⋅ 4.18 𝑘𝑘𝑘𝑘
K. Webb
𝑰𝑰′′
𝑀𝑀 = 8.36∠ − 116.9° 𝑘𝑘𝑘𝑘
ESE 470
26
K. Webb
Symmetrical Components
ESE 470
Symmetrical Components
27


In the previous section, we saw how to calculate
subtransient fault current for balanced three-phase
faults
Unsymmetrical faults are much more common
 Analysis

is more complicated
We’ll now learn a tool that will simplify the analysis
of unsymmetrical faults
 The
K. Webb
method of symmetrical components
ESE 470
Symmetrical Components
28

The method of symmetrical components:
Represent an asymmetrical set of 𝑁𝑁 phasors as a sum of 𝑁𝑁
sets of symmetrical component phasors
 These 𝑁𝑁 sets of phasors are called sequence components


Analogous to:
Decomposition of electrical signals into differential and
common-mode components
 Decomposition of forces into orthogonal components


For a three-phase system (𝑁𝑁 = 3), sequence
components are:
Zero sequence components
 Positive sequence components
 Negative sequence components

K. Webb
ESE 470
Sequence Components
29

Zero sequence components



Positive sequence components



Three phasors with equal magnitude and
equal phase
𝑽𝑽𝑎𝑎𝑎 , 𝑽𝑽𝑏𝑏𝑏 , 𝑽𝑽𝑐𝑐𝑐
Three phasors with equal magnitude and
± 120°, positive-sequence phase
𝑽𝑽𝑎𝑎1 , 𝑽𝑽𝑏𝑏1 , 𝑽𝑽𝑐𝑐1
Negative sequence components


K. Webb
Three phasors with equal magnitude and
± 120°, negative-sequence phase
𝑽𝑽𝑎𝑎2 , 𝑽𝑽𝑏𝑏2 , 𝑽𝑽𝑐𝑐2
ESE 470
Sequence Components
30

Note that the absolute phase and the magnitudes
of the sequence components is not specified
 Magnitude
and phase define a unique set of sequence
components

Any set of phasors – balanced or unbalanced – can
be represented as a sum of sequence components
K. Webb
𝑽𝑽𝑎𝑎
𝑽𝑽𝑎𝑎0
𝑽𝑽𝑎𝑎1
𝑽𝑽𝑎𝑎2
𝑽𝑽𝑏𝑏 = 𝑽𝑽𝑏𝑏0 + 𝑽𝑽𝑏𝑏1 + 𝑽𝑽𝑏𝑏2
𝑽𝑽𝑐𝑐
𝑽𝑽𝑐𝑐0
𝑽𝑽𝑐𝑐1
𝑽𝑽𝑐𝑐2
(1)
ESE 470
Sequence Components
31

The phasors of each sequence component have a fixed phase
relationship






If we know one, we know the other two
Assume we know phase 𝑎𝑎 – use that as the reference
For the zero sequence components, we have
𝑽𝑽0 = 𝑽𝑽𝑎𝑎𝑎 = 𝑽𝑽𝑏𝑏𝑏 = 𝑽𝑽𝑐𝑐𝑐
(2)
𝑽𝑽1 = 𝑽𝑽𝑎𝑎𝑎 = 1∠120° ⋅ 𝑽𝑽𝑏𝑏𝑏 = 1∠240° ⋅ 𝑽𝑽𝑐𝑐𝑐
(3)
𝑽𝑽2 = 𝑽𝑽𝑎𝑎𝑎 = 1∠240° ⋅ 𝑽𝑽𝑏𝑏𝑏 = 1∠120° ⋅ 𝑽𝑽𝑐𝑐𝑐
(4)
For the positive sequence components,
And, for the negative sequence components,
Note that we’re using phase 𝑎𝑎 as our reference, so
K. Webb
𝑽𝑽0 = 𝑽𝑽𝑎𝑎𝑎 , 𝑽𝑽1 = 𝑽𝑽𝑎𝑎𝑎 , 𝑽𝑽2 = 𝑽𝑽𝑎𝑎𝑎
ESE 470
Sequence Components
32

Next, we define a complex number, 𝑎𝑎, that has unit
magnitude and phase of 120°



𝑎𝑎 = 1∠120°
(5)
Multiplication by 𝑎𝑎 results in a rotation (a phase shift) of 120°
Multiplication by 𝑎𝑎2 yields a rotation of 240° = −120°
Using (5) to rewrite (3) and (4)
𝑽𝑽1 = 𝑽𝑽𝑎𝑎𝑎 = 𝑎𝑎𝑽𝑽𝑏𝑏𝑏 = 𝑎𝑎2 𝑽𝑽𝑐𝑐𝑐
𝑽𝑽2 = 𝑽𝑽𝑎𝑎𝑎 = 𝑎𝑎2 𝑽𝑽𝑏𝑏𝑏 = 𝑎𝑎𝑽𝑽𝑐𝑐𝑐
K. Webb
(6)
(7)
ESE 470
Sequence Components
33

Using (2), (6), and (7), we can rewrite (1) in a simplified
form
1
𝑎𝑎
𝑎𝑎2
𝑽𝑽0
𝑽𝑽1
𝑽𝑽2
(8)
The vector on the left is the vector of phase voltages, 𝑽𝑽𝑝𝑝
 The vector on the right is the vector of (phase 𝑎𝑎) sequence
components, 𝑽𝑽𝑠𝑠
 We’ll call the 3 × 3 transformation matrix 𝑨𝑨


𝑽𝑽𝑎𝑎
1 1
𝑽𝑽𝑏𝑏 = 1 𝑎𝑎2
𝑽𝑽𝑐𝑐
1 𝑎𝑎
We can rewrite (8) as
K. Webb
𝑽𝑽𝑝𝑝 = 𝑨𝑨𝑽𝑽𝑠𝑠
(9)
ESE 470
Sequence Components
34

We can express the sequence voltages as a function
of the phase voltages by inverting the
transformation matrix
where
So
K. Webb
𝑽𝑽𝑠𝑠 = 𝑨𝑨−1 𝑽𝑽𝑝𝑝
𝑨𝑨−1
=
1
3
1 1
1 𝑎𝑎
1 𝑎𝑎2
𝑽𝑽0
1 1
1
𝑽𝑽1 = 1 𝑎𝑎
3
𝑽𝑽2
1 𝑎𝑎2
(10)
1
𝑎𝑎2
𝑎𝑎
1
𝑎𝑎2
𝑎𝑎
(11)
𝑽𝑽𝑎𝑎
𝑽𝑽𝑏𝑏
𝑽𝑽𝑐𝑐
(12)
ESE 470
Sequence Components
35



The same relationships hold for three-phase
currents
The phase currents are
𝑰𝑰𝑎𝑎
𝑰𝑰𝑝𝑝 = 𝑰𝑰𝑏𝑏
𝑰𝑰𝑐𝑐
And, the sequence currents are
K. Webb
𝑰𝑰0
𝑰𝑰𝑠𝑠 = 𝑰𝑰1
𝑰𝑰2
ESE 470
Sequence Components
36

The transformation matrix, 𝑨𝑨, relates the phase
currents to the sequence currents
𝑰𝑰𝑝𝑝 = 𝑨𝑨𝑰𝑰𝑠𝑠

And vice versa
𝑰𝑰𝑎𝑎
1 1
𝑰𝑰𝑏𝑏 = 1 𝑎𝑎2
𝑰𝑰𝑐𝑐
1 𝑎𝑎
𝑰𝑰𝑠𝑠 = 𝑨𝑨−1 𝑰𝑰𝑝𝑝
K. Webb
𝑰𝑰0
1 1
1
𝑰𝑰1 = 1 𝑎𝑎
3
𝑰𝑰2
1 𝑎𝑎2
1
𝑎𝑎
𝑎𝑎2
1
𝑎𝑎2
𝑎𝑎
𝑰𝑰0
𝑰𝑰1
𝑰𝑰2
𝑰𝑰𝑎𝑎
𝑰𝑰𝑏𝑏
𝑰𝑰𝑐𝑐
(13)
(14)
ESE 470
Sequence Components – Balanced System
37


Before applying sequence components to unbalanced systems, let’s first
look at the sequence components for a balanced, positive-sequence,
three-phase system
For a balanced system, we have
𝑽𝑽𝑏𝑏 = 𝑽𝑽𝑎𝑎 ⋅ 1∠ − 120° = 𝑎𝑎2 𝑽𝑽𝑎𝑎

𝑽𝑽𝑐𝑐 = 𝑽𝑽𝑎𝑎 ⋅ 1∠120° = 𝑎𝑎𝑽𝑽𝑎𝑎
The sequence voltages are given by (12)


The zero sequence voltage is
1
1
𝑽𝑽0 = 𝑽𝑽𝑎𝑎 + 𝑽𝑽𝑏𝑏 + 𝑽𝑽𝑐𝑐 = 𝑽𝑽𝑎𝑎 + 𝑎𝑎 2 𝑽𝑽𝑎𝑎 + 𝑎𝑎𝑽𝑽𝑎𝑎
3
3
1
𝑽𝑽0 = 𝑽𝑽𝑎𝑎 1 + 𝑎𝑎 2 + 𝑎𝑎
3
Applying the identity 1 + 𝑎𝑎2 + 𝑎𝑎 = 0, we have
K. Webb
𝑽𝑽0 = 0
ESE 470
Sequence Components – Balanced System
38

The positive sequence component is given by

K. Webb
1
𝑽𝑽1 = 𝑽𝑽𝑎𝑎 + 𝑎𝑎𝑽𝑽𝑏𝑏 + 𝑎𝑎2 𝑽𝑽𝑐𝑐
3
1
𝑽𝑽1 = 𝑽𝑽𝑎𝑎 + 𝑎𝑎 ⋅ 𝑎𝑎2 𝑽𝑽𝑎𝑎 + 𝑎𝑎2 ⋅ 𝑎𝑎𝑽𝑽𝑎𝑎
3
1
𝑽𝑽1 = 𝑽𝑽𝑎𝑎 + 𝑎𝑎3 𝑽𝑽𝑎𝑎 + 𝑎𝑎3 𝑽𝑽𝑎𝑎
3
Since 𝑎𝑎3 = 1∠0°, we have
1
𝑽𝑽1 = 3𝑽𝑽𝑎𝑎
3
𝑽𝑽1 = 𝑽𝑽𝑎𝑎
ESE 470
Sequence Components – Balanced System
39


The negative sequence component is given by
1
𝑽𝑽2 = 𝑽𝑽𝑎𝑎 + 𝑎𝑎2 𝑽𝑽𝑏𝑏 + 𝑎𝑎𝑽𝑽𝑐𝑐
3
1
𝑽𝑽2 = 𝑽𝑽𝑎𝑎 + 𝑎𝑎2 ⋅ 𝑎𝑎2 𝑽𝑽𝑎𝑎 + 𝑎𝑎 ⋅ 𝑎𝑎𝑽𝑽𝑎𝑎
3
1
𝑽𝑽2 = 𝑽𝑽𝑎𝑎 + 𝑎𝑎4 𝑽𝑽𝑎𝑎 + 𝑎𝑎2 𝑽𝑽𝑎𝑎
3
Again, using the identity 1 + 𝑎𝑎2 + 𝑎𝑎 = 0, along with
the fact that 𝑎𝑎4 = 𝑎𝑎, we have
K. Webb
𝑽𝑽2 = 0
ESE 470
Sequence Components – Balanced System
40



So, for a positive-sequence, balanced, three-phase
system, the sequence voltages are
𝑽𝑽0 = 0, 𝑽𝑽1 = 𝑽𝑽𝑎𝑎 , 𝑽𝑽2 = 0
Similarly, the sequence currents are
𝑰𝑰0 = 0, 𝑰𝑰1 = 𝑰𝑰𝑎𝑎 , 𝑰𝑰2 = 0
This is as we would expect
 No
zero- or negative-sequence components for a
positive-sequence balanced system
 Zero- and negative-sequence components are only
used to account for imbalance
K. Webb
ESE 470
Sequence Components
41

We have just introduced the concept of symmetric
components
 Allows
for decomposition of, possibly unbalanced,
three-phase phasors into sequence components

We’ll now apply this concept to power system
networks to develop sequence networks
 Decoupled
networks for each of the sequence
components
 Sequence networks become coupled only at the point
of imbalance
 Simplifies the analysis of unbalanced systems
K. Webb
ESE 470
42
K. Webb
Sequence Networks
ESE 470
Sequence Networks
43

Power system components each have their own set of sequence networks






Sequence networks for overall systems are interconnections of the
individual sequence network
Sequence networks become coupled in a particular way at the fault
location depending on type of fault




Non-rotating loads
Transmission lines
Rotating machines – generators and motors
Transformers
Line-to-line
Single line-to-ground
Double line-to-ground
Fault current can be determined through simple analysis of the coupled
sequence networks
K. Webb
ESE 470
Sequence Networks – Non-Rotating Loads
44


Consider a balanced Y-load with the neutral
grounded through some non-zero impedance
Applying KVL gives the phase-𝑎𝑎-to-ground
voltage
𝑽𝑽𝑎𝑎𝑎𝑎 = 𝑍𝑍𝑦𝑦 𝑰𝑰𝑎𝑎 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑛𝑛


For phase 𝑏𝑏:
𝑽𝑽𝑎𝑎𝑎𝑎 = 𝑍𝑍𝑦𝑦 𝑰𝑰𝑎𝑎 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑎𝑎 + 𝑰𝑰𝑏𝑏 + 𝑰𝑰𝑐𝑐
𝑽𝑽𝑎𝑎𝑎𝑎 = 𝑍𝑍𝑦𝑦 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑎𝑎 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑏𝑏 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑐𝑐
(15)
𝑽𝑽𝑏𝑏𝑔𝑔 = 𝑍𝑍𝑦𝑦 𝑰𝑰𝑏𝑏 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑛𝑛 = 𝑍𝑍𝑦𝑦 𝑰𝑰𝑏𝑏 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑎𝑎 + 𝑰𝑰𝑏𝑏 + 𝑰𝑰𝑐𝑐
𝑽𝑽𝑏𝑏𝑔𝑔 = 𝑍𝑍𝑛𝑛 𝑰𝑰𝑎𝑎 + 𝑍𝑍𝑦𝑦 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑏𝑏 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑐𝑐
(16)
Similarly, for phase 𝑐𝑐:
K. Webb
𝑽𝑽𝑎𝑎𝑎𝑎 = 𝑍𝑍𝑛𝑛 𝑰𝑰𝑎𝑎 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑏𝑏 + 𝑍𝑍𝑦𝑦 + 𝑍𝑍𝑛𝑛 𝑰𝑰𝑐𝑐
(17)
ESE 470
Sequence Networks – Non-Rotating Loads
45

Putting (15) – (17) in matrix form
or
𝑽𝑽𝑎𝑎𝑔𝑔
𝑽𝑽𝑏𝑏𝑏𝑏 =
𝑽𝑽𝑐𝑐𝑐𝑐
𝑍𝑍𝑦𝑦 + 𝑍𝑍𝑛𝑛
𝑽𝑽𝑝𝑝 = 𝒁𝒁𝑝𝑝 𝑰𝑰𝑝𝑝


𝑍𝑍𝑛𝑛
𝑍𝑍𝑛𝑛
𝑍𝑍𝑛𝑛
𝑍𝑍𝑦𝑦 + 𝑍𝑍𝑛𝑛
𝑍𝑍𝑛𝑛
𝑍𝑍𝑛𝑛
𝑍𝑍𝑛𝑛
𝑍𝑍𝑦𝑦 + 𝑍𝑍𝑛𝑛
𝑰𝑰𝑎𝑎
𝑰𝑰𝑏𝑏
𝑰𝑰𝑐𝑐
(18)
where 𝑽𝑽𝑝𝑝 and 𝑰𝑰𝑝𝑝 are the phase voltages and currents, respectively, and 𝒁𝒁𝑝𝑝 is the
phase impedance matrix
We can use (9) and (13) to rewrite (18) as
Solving for 𝑽𝑽𝑠𝑠
or
K. Webb
𝑨𝑨𝑽𝑽𝑠𝑠 = 𝒁𝒁𝑝𝑝 𝑨𝑨𝑰𝑰𝑠𝑠
𝑽𝑽𝑠𝑠 = 𝑨𝑨−1 𝒁𝒁𝑝𝑝 𝑨𝑨𝑰𝑰𝑠𝑠
𝑽𝑽𝑠𝑠 = 𝒁𝒁𝑠𝑠 𝑰𝑰𝑠𝑠
(19)
ESE 470
Sequence Networks – Non-Rotating Loads
46
𝑽𝑽𝑠𝑠 = 𝒁𝒁𝑠𝑠 𝑰𝑰𝑠𝑠
(19)
where 𝑍𝑍𝑠𝑠 is the sequence impedance matrix
𝒁𝒁𝑠𝑠 = 𝑨𝑨−1 𝒁𝒁𝑝𝑝 𝑨𝑨 =

𝑍𝑍𝑦𝑦 + 3𝑍𝑍𝑛𝑛
0
0
0
𝑍𝑍𝑦𝑦
0
0
0
𝑍𝑍𝑦𝑦
(20)
Equation (19) then becomes a set of three uncoupled
equations
𝑽𝑽0 = 𝑍𝑍𝑦𝑦 + 3𝑍𝑍𝑛𝑛 𝑰𝑰0 = 𝑍𝑍0 𝑰𝑰0
𝑽𝑽1 = 𝑍𝑍𝑦𝑦 𝑰𝑰1 = 𝑍𝑍1 𝑰𝑰1
K. Webb
𝑽𝑽2 = 𝑍𝑍𝑦𝑦 𝑰𝑰2 = 𝑍𝑍2 𝑰𝑰2
(21)
(22)
(23)
ESE 470
Sequence Networks – Non-Rotating Loads
47

Equations (21) – (23) describe the uncoupled
sequence networks
 Zero-sequence
network:
 Positive-sequence
network:
K. Webb
 Negative-sequence
network:
ESE 470
Sequence Networks – Non-Rotating Loads
48

We can develop similar sequence networks for a balanced Δconnected load




K. Webb
𝑍𝑍𝑦𝑦 = 𝑍𝑍Δ /3
There is no neutral point for the Δ-network, so 𝑍𝑍𝑛𝑛 = ∞ - an open circuit
Zero-sequence
network:
Positive-sequence
network:

Negative-sequence
network:
ESE 470
Sequence Networks – 3-𝜙𝜙 Lines
49


Balanced, three-phase lines can be modeled as
The voltage drops across the lines are given by the
following system of equations
K. Webb
𝑽𝑽𝑎𝑎𝑎𝑎′
𝑍𝑍𝑎𝑎𝑎𝑎
𝑽𝑽𝑏𝑏𝑏𝑏′ = 𝑍𝑍𝑏𝑏𝑏𝑏
𝑍𝑍𝑐𝑐𝑐𝑐
𝑽𝑽𝑐𝑐𝑐𝑐 ′
𝑍𝑍𝑎𝑎𝑎𝑎
𝑍𝑍𝑏𝑏𝑏𝑏
𝑍𝑍𝑐𝑐𝑐𝑐
𝑍𝑍𝑎𝑎𝑎𝑎
𝑍𝑍𝑏𝑏𝑏𝑏
𝑍𝑍𝑐𝑐𝑐𝑐
𝑽𝑽𝑎𝑎𝑛𝑛 − 𝑽𝑽𝑎𝑎′𝑛𝑛
𝑰𝑰𝑎𝑎
𝑰𝑰𝑏𝑏 = 𝑽𝑽𝑏𝑏𝑏𝑏 − 𝑽𝑽𝑏𝑏′𝑛𝑛
𝑰𝑰𝑐𝑐
𝑽𝑽𝑐𝑐𝑐𝑐 − 𝑽𝑽𝑐𝑐 ′𝑛𝑛
(24)
ESE 470
Sequence Networks – 3-𝜙𝜙 Lines
50


Writing (24) in compact form
𝑽𝑽𝑝𝑝 − 𝑽𝑽𝑝𝑝′ = 𝒁𝒁𝑝𝑝 𝑰𝑰𝑝𝑝
(25)
𝒁𝒁𝑝𝑝 is the phase impedance matrix
Self impedances along the diagonal
 Mutual impedances elsewhere
 Symmetric
 Diagonal, if we neglect mutual impedances

K. Webb
ESE 470
Sequence Networks – 3-𝜙𝜙 Lines
51

We can rewrite (25) in terms of sequence components
𝑨𝑨𝑽𝑽𝑠𝑠 − 𝑨𝑨𝑽𝑽𝑠𝑠′ = 𝒁𝒁𝑝𝑝 𝑨𝑨𝑰𝑰𝑠𝑠
𝑽𝑽𝑠𝑠 − 𝑽𝑽𝑠𝑠′ = 𝑨𝑨−1 𝒁𝒁𝑝𝑝 𝑨𝑨𝑰𝑰𝑠𝑠
𝑽𝑽𝑠𝑠 − 𝑽𝑽𝑠𝑠′ = 𝒁𝒁𝑠𝑠 𝑰𝑰𝑠𝑠
(26)
where 𝒁𝒁𝑠𝑠 is the sequence impedance matrix

𝒁𝒁𝑠𝑠 = 𝑨𝑨−1 𝒁𝒁𝑝𝑝 𝑨𝑨
(27)
𝒁𝒁𝑠𝑠 is diagonal so long as the system impedances are
balanced, i.e.
Self impedances are equal: 𝑍𝑍𝑎𝑎𝑎𝑎 = 𝑍𝑍𝑏𝑏𝑏𝑏 = 𝑍𝑍𝑐𝑐𝑐𝑐
 Mutual impedances are equal: 𝑍𝑍𝑎𝑎𝑎𝑎 = 𝑍𝑍𝑎𝑎𝑎𝑎 = 𝑍𝑍𝑏𝑏𝑏𝑏

K. Webb
ESE 470
Sequence Networks – 3-𝜙𝜙 Lines
52


For balanced lines, 𝒁𝒁𝑠𝑠 is diagonal
𝑍𝑍𝑎𝑎𝑎𝑎 + 2𝑍𝑍𝑎𝑎𝑏𝑏
0
𝒁𝒁𝑠𝑠 =
0
0
𝑍𝑍𝑎𝑎𝑎𝑎 − 𝑍𝑍𝑎𝑎𝑎𝑎
0
0
𝑍𝑍0
0
= 0
0
𝑍𝑍𝑎𝑎𝑎𝑎 − 𝑍𝑍𝑎𝑎𝑎𝑎
0
𝑍𝑍1
0
0
0
𝑍𝑍2
Because 𝑍𝑍𝑠𝑠 is diagonal, (26) represents three
uncoupled equations
𝑽𝑽0 − 𝑽𝑽0′ = 𝑍𝑍0 𝑰𝑰0
(28)
𝑽𝑽2 − 𝑽𝑽2′ = 𝑍𝑍2 𝑰𝑰2
(30)
𝑽𝑽1 − 𝑽𝑽1′ = 𝑍𝑍1 𝑰𝑰1
K. Webb
(29)
ESE 470
Sequence Networks – 3-𝜙𝜙 Lines
53

Equations (28) – (30) describe the voltage drop across three
uncoupled sequence networks


K. Webb
Zero-sequence
network:
Positive-sequence
network:

Negative-sequence
network:
ESE 470
Sequence Networks – Rotating Machines
54


Consider the following model
for a synchronous generator
Similar to the Y-connected load


Generator includes voltage
sources on each phase
Voltage sources are positive
sequence

K. Webb
Sources will appear only in the
positive-sequence network
ESE 470
Sequence Networks – Synchronous Generator
55

Sequence networks for Y-connected synchronous
generator


K. Webb
Zero-sequence
network:
Positive-sequence
network:

Negative-sequence
network:
ESE 470
Sequence Networks – Motors
56

Synchronous motors
 Sequence networks
identical to those for synchronous
generators
 Reference current directions are reversed

Induction motors
 Similar
sequence networks to synchronous motors,
except source in the positive sequence network set to
zero
K. Webb
ESE 470
Sequence Networks - Y-Y Transformers
57

Per-unit sequence networks for transformers



Simplify by neglecting transformer shunt admittances
Consider a Y-Y transformer
Similar to the Y-connected load, the voltage drops
across the neutral impedances are 3𝐼𝐼0 𝑍𝑍𝑁𝑁 and 3𝐼𝐼0 𝑍𝑍𝑛𝑛
3𝑍𝑍𝑁𝑁 and 3𝑍𝑍𝑛𝑛 each appear in the zero-sequence network
 Can be combined in the per-unit circuit as long as shunt
impedances are neglected

K. Webb
ESE 470
Sequence Networks – Y-Y Transformers
58

Impedance accounting for leakage flux and winding resistance for
each winding can be referred to the primary


Add together into a single impedance, 𝑍𝑍𝑠𝑠 , in the per-unit model
Y-Y transformer sequence networks


K. Webb
Zero-sequence
network:
Positive-sequence
network:

Negative-sequence
network:
ESE 470
Sequence Networks – Y-ΔTransformers
59

Y-Δ transformers differ in a couple of ways

Must account for phase shift from primary to secondary
For positive-sequence network, Y-side voltage and current lead Δside voltage and current
 For negative-sequence network, Y-side voltage and current lag Δside voltage and current


No neutral connection on the Δ side

K. Webb
Zero-sequence current cannot enter or leave the Δ winding
ESE 470
Sequence Networks – Y-ΔTransformers
60

Sequence networks for Y-ΔTransformers


K. Webb
Zero-sequence
network:
Positive-sequence
network:

Negative-sequence
network:
ESE 470
61
Sequence Networks – Δ-ΔTransformers

Δ-Δ transformers
 Like
Y-Y transformers, no phase shift
 No neutral connections
 Zero-sequence current
winding
K. Webb
cannot flow into or out of either
ESE 470
62
Sequence Networks – Δ-ΔTransformers

Sequence networks for Δ-ΔTransformers


K. Webb
Zero-sequence
network:
Positive-sequence
network:

Negative-sequence
network:
ESE 470
Power in Sequence Networks
63



We can relate the power delivered to a system’s
sequence networks to the three-phase power delivered
to that system
We know that the complex power delivered to a threephase system is the sum of the power at each phase
𝑆𝑆𝑝𝑝 = 𝑽𝑽𝑎𝑎𝑎𝑎 𝑰𝑰𝑎𝑎∗ + 𝑽𝑽𝑏𝑏𝑏𝑏 𝑰𝑰𝑏𝑏∗ + 𝑽𝑽𝑐𝑐𝑐𝑐 𝑰𝑰𝑐𝑐∗
In matrix form, this looks like
𝑆𝑆𝑝𝑝 = 𝑽𝑽𝑎𝑎𝑛𝑛
K. Webb
𝑆𝑆𝑝𝑝 = 𝑽𝑽𝑇𝑇𝑝𝑝 𝑰𝑰𝑝𝑝∗
𝑽𝑽𝑏𝑏𝑏𝑏
𝑽𝑽𝑐𝑐𝑐𝑐
𝑰𝑰𝑎𝑎∗
𝑰𝑰∗𝑏𝑏
𝑰𝑰𝑐𝑐∗
(28)
ESE 470
Power in Sequence Networks
64

Recall the following relationships
𝑽𝑽𝑝𝑝 = 𝑨𝑨𝑽𝑽𝑠𝑠

𝑰𝑰𝑝𝑝 = 𝑨𝑨𝑰𝑰𝑠𝑠
(13)
Using (9) and (13) in (28), we have
𝑺𝑺𝑝𝑝 = 𝑨𝑨𝑽𝑽𝑠𝑠

(9)
𝑇𝑇
𝑨𝑨𝑰𝑰𝑠𝑠
𝑺𝑺𝑝𝑝 = 𝑽𝑽𝑇𝑇𝑠𝑠 𝑨𝑨𝑇𝑇 𝑨𝑨∗ 𝑰𝑰∗𝑠𝑠
∗
(29)
Computing the product in the middle of the right-hand side of (29),
we find
3 0 0
= 0 3 0 = 3𝑰𝑰3
0 0 3
where 𝑰𝑰3 is the 3×3 identity matrix
𝑨𝑨𝑇𝑇 𝑨𝑨∗
K. Webb
ESE 470
Power in Sequence Networks
65

Equation (29) then becomes
𝑺𝑺𝑝𝑝 = 𝑽𝑽𝑇𝑇𝑠𝑠 3𝑰𝑰3 𝑰𝑰∗𝑠𝑠
𝑺𝑺𝑝𝑝 = 3𝑽𝑽𝑇𝑇𝑠𝑠 𝑰𝑰∗𝑠𝑠
𝑺𝑺𝑝𝑝 = 3 𝑽𝑽0

𝑽𝑽1
𝑽𝑽2
𝑰𝑰∗0
𝑰𝑰1∗
𝑰𝑰∗2
𝑺𝑺𝑝𝑝 = 3 𝑽𝑽0 𝑰𝑰∗0 + 𝑽𝑽1 𝑰𝑰1∗ + 𝑽𝑽2 𝑰𝑰∗2
The total power delivered to a three-phase network is three
times the sum of the power delivered to the three sequence
networks

K. Webb
The three sequence networks represent only one of the three
phases – recall, we chose to consider only phase 𝑎𝑎
ESE 470
66
K. Webb
Unsymmetrical Faults
ESE 470
Unsymmetrical Faults
67

The majority of faults that occur in three-phase power
systems are unsymmetrical
Not balanced
 Fault current and voltage differ for each phase



The method of symmetrical components and sequence
networks provide us with a tool to analyze these
unsymmetrical faults
We’ll examine three types of unsymmetrical faults
Single line-to-ground (SLG) faults
 Line-to-line (LL) faults
 Double line-to-ground (DLG) faults

K. Webb
ESE 470
Unsymmetrical Fault Analysis - Procedure
68

Basic procedure for fault analysis:
1. Generate sequence networks for the system
2. Interconnect sequence networks appropriately at the
fault location
3. Perform circuit analysis on the interconnected
sequence networks
K. Webb
ESE 470
Unsymmetrical Fault Analysis
69

To simplify our analysis, we’ll make the following
assumptions
1. System is balanced before the instant of the fault
2. Neglect pre-fault load current
 All pre-fault machine terminal voltages and bus voltages are equal
to 𝑉𝑉𝐹𝐹
3. Transmission lines are modeled as series reactances only
4. Transformers are modeled with leakage reactances only
5. Non-rotating loads are neglected
6. Induction motors are either neglected or modeled as
synchronous motors
K. Webb
ESE 470
Unsymmetrical Fault Analysis
70

Each sequence network includes all interconnected powersystem components


Analysis will be simplified if we represent each sequence
network as its Thévenin equivalent


Generators, motors, lines, and transformers
From the perspective of the fault location
For example, consider the following power system:
K. Webb
ESE 470
Unsymmetrical Fault Analysis – Sequence Networks
71

The sequence networks for the system are generated by
interconnecting the sequence networks for each of the components
The zero-sequence network:

The positive-sequence network:


K. Webb
Assuming the generator is operating at the rated voltage at the time of
the fault
ESE 470
Unsymmetrical Fault Analysis – Sequence Networks
72

The negative sequence network:

Now, let’s assume there is some sort of fault at bus 1


Determine the Thévenin equivalent for each sequence network from the
perspective of bus 1
Simplifying the zero-sequence network to its Thévenin equivalent
K. Webb
ESE 470
Unsymmetrical Fault Analysis – Sequence Networks
73



The positive-sequence network simplifies to the following
circuit with the following Thévenin equivalent
Similarly, for the negative-sequence network, we have
Next, we’ll see how to interconnect these networks to
analyze different types of faults
K. Webb
ESE 470
Unsymmetrical Fault Analysis – SLG Fault
74


The following represents a
generic three-phase network
with terminals at the fault
location:
If we have a single-line-toground fault, where phase 𝑎𝑎 is
shorted through 𝑍𝑍𝑓𝑓 to ground,
the model becomes:
K. Webb
ESE 470
Unsymmetrical Fault Analysis – SLG Fault
75

The phase-domain fault conditions:
𝑰𝑰𝑎𝑎 =


𝑽𝑽𝑎𝑎𝑎𝑎
(1)
𝑍𝑍𝑓𝑓
𝑰𝑰𝑏𝑏 = 𝑰𝑰𝑐𝑐 = 0
(2)
Transforming these phase-domain
currents to the sequence domain
𝑰𝑰0
1 1
1
𝑰𝑰1 = 1 𝑎𝑎
3
𝑰𝑰2
1 𝑎𝑎2
1
𝑎𝑎2
𝑎𝑎
𝑽𝑽𝑎𝑎𝑔𝑔 /𝑍𝑍𝑓𝑓
𝑽𝑽𝑎𝑎𝑔𝑔 /𝑍𝑍𝑓𝑓
1
= 𝑽𝑽𝑎𝑎𝑔𝑔 /𝑍𝑍𝑓𝑓
0
3
𝑽𝑽𝑎𝑎𝑔𝑔 /𝑍𝑍𝑓𝑓
0
(3)
This gives one of our sequence-domain fault conditions
K. Webb
𝑰𝑰0 = 𝑰𝑰1 = 𝑰𝑰2
(4)
ESE 470
Unsymmetrical Fault Analysis – SLG Fault
76

We know that
and


𝑰𝑰𝑎𝑎 =
𝑽𝑽𝑎𝑎𝑎𝑎
𝑍𝑍𝑓𝑓
= 𝑰𝑰0 + 𝑰𝑰1 + 𝑰𝑰2
𝑽𝑽𝑎𝑎𝑎𝑎 = 𝑽𝑽0 + 𝑽𝑽1 + 𝑽𝑽2
(5)
(6)
Using (5) and (6) in (1), we get
𝑰𝑰0 + 𝑰𝑰1 + 𝑰𝑰2 =
1
𝑍𝑍𝑓𝑓
𝑽𝑽0 + 𝑽𝑽1 + 𝑽𝑽2
Using (4), this gives our second sequence-domain fault
condition
𝑰𝑰0 = 𝑰𝑰1 = 𝑰𝑰2 =
K. Webb
1
3𝑍𝑍𝑓𝑓
𝑽𝑽0 + 𝑽𝑽1 + 𝑽𝑽2
(7)
ESE 470
Unsymmetrical Fault Analysis – SLG Fault
77


The sequence-domain fault conditions
are satisfied by connecting the
sequence networks in series along
with three times the fault impedance
We want to find the phase domain
fault current, 𝑰𝑰𝐹𝐹
𝑰𝑰𝐹𝐹 = 𝑰𝑰𝑎𝑎 = 𝑰𝑰0 + 𝑰𝑰1 + 𝑰𝑰2 = 3𝑰𝑰1
𝑰𝑰1 =
K. Webb
𝑰𝑰𝐹𝐹 =
𝑽𝑽𝐹𝐹
𝑍𝑍0 +𝑍𝑍1 +𝑍𝑍2 +3𝑍𝑍𝐹𝐹
3𝑽𝑽𝐹𝐹
𝑍𝑍0 +𝑍𝑍1 +𝑍𝑍2 +3𝑍𝑍𝐹𝐹
(8)
ESE 470
SLG Fault - Example
78


Returning to our example power system
The interconnected
sequence networks for a
bolted fault at bus 1:
K. Webb
ESE 470
SLG Fault - Example
79

The fault current is
𝑰𝑰𝐹𝐹 =


𝑰𝑰𝐹𝐹 =
3𝑽𝑽𝐹𝐹
𝑍𝑍0 +𝑍𝑍1 +𝑍𝑍2 +3𝑍𝑍𝐹𝐹
3.0∠30°
𝑗𝑗𝑗.487
= 6.16∠ − 60° 𝑝𝑝. 𝑢𝑢.
𝑆𝑆𝑏𝑏
𝑉𝑉𝑏𝑏𝑏
150 𝑀𝑀𝑀𝑀𝑀𝑀
3 230 𝑘𝑘𝑘𝑘
The current base at bus 1 is
𝑰𝑰𝑏𝑏 =
=
So the fault current in kA is
= 376.5 𝐴𝐴
𝑰𝑰𝐹𝐹 = 2.32∠ − 60° 376.5 𝐴𝐴
K. Webb
𝑰𝑰𝐹𝐹 = 2.32∠ − 60° 𝑘𝑘𝑘𝑘
ESE 470
Unsymmetrical Fault Analysis – LL Fault
80


Now consider a line-to-line fault between
phase 𝑏𝑏 and phase 𝑐𝑐 through impedance 𝑍𝑍𝐹𝐹
Phase-domain fault conditions:
𝑰𝑰𝑎𝑎 = 0


(9)
𝑰𝑰𝑏𝑏 = −𝑰𝑰𝑐𝑐 =
𝑽𝑽𝑏𝑏𝑏𝑏 −𝑽𝑽𝑐𝑐𝑐𝑐
(10)
𝑍𝑍𝐹𝐹
Transforming to the sequence domain
𝑰𝑰0
1
1
𝑰𝑰1 = 1
3
𝑰𝑰2
1
1
𝑎𝑎
𝑎𝑎2
1
𝑎𝑎2
𝑎𝑎
0
0
1
𝑎𝑎 − 𝑎𝑎2 𝑰𝑰𝑏𝑏
𝑰𝑰𝑏𝑏 =
3
−𝑰𝑰𝑏𝑏
𝑎𝑎2 − 𝑎𝑎2 𝑰𝑰𝑏𝑏
(11)
So, the first two sequence-domain fault conditions are
𝑰𝑰0 = 0
K. Webb
𝑰𝑰2 = −𝑰𝑰1
(12)
(13)
ESE 470
Unsymmetrical Fault Analysis – LL Fault
81

To derive the remaining sequence-domain fault
condition, rearrange (10) and transform to the
sequence domain
𝑽𝑽𝑏𝑏𝑏𝑏 − 𝑽𝑽𝑐𝑐𝑐𝑐 = 𝑰𝑰𝑏𝑏 𝑍𝑍𝐹𝐹
𝑽𝑽0 + 𝑎𝑎2 𝑽𝑽1 + 𝑎𝑎𝑽𝑽2 − 𝑽𝑽0 + 𝑎𝑎𝑽𝑽1 + 𝑎𝑎2 𝑽𝑽2
= 𝑰𝑰0 + 𝑎𝑎2 𝑰𝑰1 + 𝑎𝑎𝑰𝑰2 𝑍𝑍𝐹𝐹
𝑎𝑎2 𝑽𝑽1 + 𝑎𝑎𝑽𝑽2 − 𝑎𝑎𝑽𝑽1 − 𝑎𝑎2 𝑽𝑽2 = 𝑎𝑎2 − 𝑎𝑎 𝑰𝑰1 𝑍𝑍𝐹𝐹

𝑎𝑎2 − 𝑎𝑎 𝑽𝑽1 − 𝑎𝑎2 − 𝑎𝑎 𝑽𝑽2 = 𝑎𝑎2 − 𝑎𝑎 𝑰𝑰1 𝑍𝑍𝐹𝐹
The last sequence-domain fault condition is
K. Webb
𝑽𝑽1 − 𝑽𝑽2 = 𝑰𝑰1 𝑍𝑍𝐹𝐹
(14)
ESE 470
Unsymmetrical Fault Analysis – LL Fault
82

Sequence-domain fault conditions
𝑰𝑰0 = 0
𝑰𝑰2 = −𝑰𝑰1

𝑽𝑽1 − 𝑽𝑽2 = 𝑰𝑰1 𝑍𝑍𝐹𝐹
(12)
(13)
(14)
These can be satisfied by:


K. Webb
Leaving the zero-sequence network open
Connecting the terminals of the positive- and negative-sequence
networks together through 𝑍𝑍𝐹𝐹
ESE 470
Unsymmetrical Fault Analysis – LL Fault
83

The fault current is the phase 𝑏𝑏 current, which is given by
𝑰𝑰𝐹𝐹 = 𝑰𝑰𝑏𝑏 = 𝑰𝑰0 + 𝑎𝑎2 𝑰𝑰1 + 𝑎𝑎𝑰𝑰2
𝑰𝑰𝐹𝐹 = 𝑎𝑎2 𝑰𝑰1 − 𝑎𝑎𝑰𝑰1
𝑰𝑰𝐹𝐹 = −𝑗𝑗 3 𝑰𝑰1 =
K. Webb
𝑰𝑰𝐹𝐹 =
3 𝑽𝑽𝐹𝐹 ∠−90°
𝑍𝑍1 +𝑍𝑍2 +𝑍𝑍𝐹𝐹
−𝑗𝑗 3 𝑽𝑽𝐹𝐹
𝑍𝑍1 +𝑍𝑍2 +𝑍𝑍𝐹𝐹
(15)
ESE 470
LL Fault - Example
84


Now consider the same system with a bolted line-to-line
fault at bus 1
The sequence network:
K. Webb
ESE 470
LL Fault - Example
85

𝑰𝑰1 =
1∠30°
𝑗𝑗𝑗.363
= 2.75∠ − 60°
The subtransient fault current is given by (15) as
𝑰𝑰𝐹𝐹 = 3 2.75∠ − 60° ∠ − 90°

𝑰𝑰𝐹𝐹 = 4.76∠ − 150° 𝑝𝑝. 𝑢𝑢.
Using the previously-determined current base, we can
convert the fault current to kA
𝑰𝑰𝐹𝐹 = 𝐼𝐼𝑏𝑏𝑏 ⋅ 4.76∠ − 150°
𝑰𝑰𝐹𝐹 = 4.76∠ − 150° 376.5𝐴𝐴
K. Webb
𝑰𝑰𝐹𝐹 = 1.79∠ − 150° 𝑘𝑘𝑘𝑘
ESE 470
Unsymmetrical Fault Analysis – DLG Fault
86

Now consider a double line-to-ground fault


Assume phases 𝑏𝑏 and 𝑐𝑐 are shorted to
ground through 𝑍𝑍𝐹𝐹
Phase-domain fault conditions:
𝑰𝑰𝑎𝑎 = 0

𝑰𝑰𝑏𝑏 + 𝑰𝑰𝑐𝑐 =
𝑽𝑽𝑏𝑏𝑏𝑏
𝑍𝑍𝐹𝐹
=
𝑽𝑽𝑐𝑐𝑔𝑔
𝑍𝑍𝐹𝐹
(16)
(17)
It can be shown that (16) and (17) transform to the following
sequence-domain fault conditions (analysis skipped here)
𝑰𝑰0 + 𝑰𝑰1 + 𝑰𝑰2 = 0
𝑽𝑽1 = 𝑽𝑽2
K. Webb
𝑰𝑰0 =
1
3𝑍𝑍𝐹𝐹
𝑽𝑽0 − 𝑽𝑽1
(18)
(19)
(20)
ESE 470
Unsymmetrical Fault Analysis – DLG Fault
87

Sequence-domain fault conditions
𝑰𝑰0 + 𝑰𝑰1 + 𝑰𝑰2 = 0
𝑽𝑽1 = 𝑽𝑽2

𝑰𝑰0 =
1
3𝑍𝑍𝐹𝐹
𝑽𝑽0 − 𝑽𝑽1
(18)
(19)
(20)
To satisfy these fault conditions


K. Webb
Connect the positive- and negative-sequence networks together directly
Connect the zero- and positive-sequence networks together through 𝑍𝑍𝐹𝐹
ESE 470
Unsymmetrical Fault Analysis – DLG Fault
88

The fault current is the sum of the phase 𝑏𝑏 and phase 𝑐𝑐
currents, as given by (17)

In the sequence domain the fault current is
𝑰𝑰𝐹𝐹 = 𝑰𝑰𝑏𝑏 + 𝑰𝑰𝑐𝑐 = 3𝑰𝑰0

𝑰𝑰𝐹𝐹 = 3𝑰𝑰0
(21)
𝐼𝐼0 can be determined by a simple analysis (e.g. nodal) of the
interconnected sequence networks
K. Webb
ESE 470
DLG Fault - Example
89



Now determine the subtransient fault current for a bolted
double line-to-ground fault at bus 1
The sequence network:
Here, because 𝑍𝑍𝐹𝐹 = 0, 𝑽𝑽0 = 𝑽𝑽1 = 𝑽𝑽2
K. Webb
ESE 470
DLG Fault - Example
90


To find 𝑰𝑰𝐹𝐹 , we must determine 𝑰𝑰0
We can first find 𝑉𝑉0 by applying voltage division
𝑍𝑍2 ||𝑍𝑍0
𝑽𝑽0 = 𝑽𝑽𝐹𝐹
𝑍𝑍1 + 𝑍𝑍2 ||𝑍𝑍0
𝑗𝑗𝑗.194||𝑗𝑗𝑗.124
𝑽𝑽0 = 1.0∠30°
𝑗𝑗𝑗.169 + 𝑗𝑗𝑗.194||𝑗𝑗𝑗.124
K. Webb
𝑽𝑽0 = 0.309∠30°
ESE 470
DLG Fault - Example
91



Next, calculate 𝑰𝑰0
−𝑽𝑽0 −0.309∠30°
𝑰𝑰0 =
=
= 2.49∠120° 𝑝𝑝. 𝑢𝑢.
𝑍𝑍0
𝑗𝑗𝑗.124
The per-unit fault current is
𝑰𝑰𝐹𝐹 = 3𝑰𝑰0 = 7.48∠120° 𝑝𝑝. 𝑢𝑢.
Using the current base to convert to kA, gives the
subtransient DLG fault current
𝑰𝑰𝐹𝐹 = 7.48∠120° 376.5 𝐴𝐴
K. Webb
𝑰𝑰𝐹𝐹 = 2.82∠120° 𝑘𝑘𝑘𝑘
ESE 470
Download