HOT WORK PERMIT STOP! Avoid hot work when possible! Consider using an alternative cold work method. This Hot Work Permit is required for any temporary operation involving open flames or producing heat and/or sparks conducted outside a Hot Work Designated Area. This includes, but is not limited to: brazing, cutting, grinding, soldering, torch-applied roofing and welding. Part 1 Instructions for Permit Authorizer Y NA 1. Specify the precautions to take. 2.Fill out and keep Part 1 during the hot work process. 3.Issue Part 2 to the person doing the job. 4.Keep Part 2 on file for future reference, including signed confirmation that the post-work fire watch and monitoring have been completed. 5. Sign off the final check on Part 2. The fire pump is in operation and switched to automatic. Control valves to water supply for sprinkler system are open. Extinguishers are in service/operable. Hot work equipment is in good working condition. Requirements within 35 ft. (10 m) of hot work n n Shield combustible construction using listed (e.g., FM Approved) welding pads, blankets and curtains. n n Remove or shield nonremovable combustibles using listed (e.g., FM Approved) welding pads, blankets and curtains. n nIsolate potential sources of flammable gas, ignitable liquid or combustible dust/lint (e.g., shut down equipment). n n Remove ignitable liquid, combustible dust/lint and combustible residues. n n Shut down ventilation and conveying systems. n nRemove combustibles and consider a second fire watch on opposite side of floor, wall, ceiling or roof when openings exist or thermally conductive materials pass through. n n Is work on a combustible building assembly (e.g., Torch-Applied Roofing)? If yes, provide ADDITIONAL REQUIRED PRECAUTIONS below. HOT WORK BY Employee Contractor DATE nn nn n n Required Precautions JOB NUMBER LOCATION OF WORK (BUILDING/FLOOR/OBJECT) WORK TO BE PERFORMED NAME OF PERSON PERFORMING HOT WORK Hot work on/in closed equipment, ductwork or piping n n Isolate equipment from service. NAME OF PERSON PERFORMING FIRE WATCH n n Remove ignitable liquid and purge flammable gas/vapor. n n Prior to work, and/or during work, monitor for flammable gas/vapor. LEL reading(s): I verify the above location has been examined, the Required Precautions n n Remove combustible dust/lint or other combustible materials. have been taken, and permission is authorized for this work. n nIs work on/in equipment with nonremovable combustible linings or PERMIT AUTHORIZER (PRINT AND SIGN) parts? If yes, provide ADDITIONAL REQUIRED PRECAUTIONS below. Fire watch/fire monitoring the hot work area THIS PERMIT EXPIRES ON (LIMIT AUTHORIZATION TO ONE SHIFT): DATE: TIME: Note: Emergency notification on back of form. Note: Emergency notification on back of form. Additional FM Global for Resources: Use as appropriate your facility. AM/PM Property Loss Prevention Data Sheet 10-3, Hot Work Management Hot Work Permit App via fmglobal.com/apps Hot Work Permit form (F2630) via fmglobalcatalog.com Online training at training.fmglobal.com FM Approved equipment via fmapprovals.com F2630 © 2018 FM Global. (01/2018) All rights reserved. Times listed are sufficient for majority. Use Table at back of permit for guidance for combustible concealed cavities, roof work or favorable factors. n Perform a continuous fire watch during hot work. n Perform a continuous fire watch post-work for n 1 hour or Other ___ hours. n n Perform fire monitoring for n 3 hours or Other ___ hours. ADDITIONAL REQUIRED PRECAUTIONS: WARNING HOT WORK IN PROGRESS! Watch for fire! Part 2 Instructions erson performing hot work: Record time started and display permit at P hot work area. After hot work is completed, record time and leave permit displayed for fire watch. Fire watch: Watch area during hot work and after work completion. Prior to leaving area, perform final inspection, sign, leave permit displayed and notify Fire Monitor or Permit Authorizer. F ire Monitor: Monitor area after post-work fire watch completion. Perform final inspection, sign and return to Permit Authorizer. HOT WORK BY Employee Contractor DATE JOB NUMBER LOCATION OF WORK (BUILDING/FLOOR/OBJECT) WORK TO BE PERFORMED NAME OF PERSON PERFORMING HOT WORK Y NA nn nn n n Required Precautions The fire pump is in operation and switched to automatic. Control valves to water supply for sprinkler system are open. Extinguishers are in service/operable. Hot work equipment is in good working condition. Requirements within 35 ft. (10 m) of hot work n n Shield combustible construction using listed (e.g., FM Approved) welding pads, blankets and curtains. n n Remove or shield nonremovable combustibles using listed (e.g., FM Approved) welding pads, blankets and curtains. n nIsolate potential sources of flammable gas, ignitable liquid or combustible dust/lint (e.g., shut down equipment). n n Remove ignitable liquid, combustible dust/lint and combustible residues. n n Shut down ventilation and conveying systems. n nRemove combustibles and consider a second fire watch on opposite side of floor, wall, ceiling or roof when openings exist or thermally conductive materials pass through. n n Is work on a combustible building assembly (e.g., Torch-Applied Roofing)? If yes, provide ADDITIONAL REQUIRED PRECAUTIONS below. Hot work on/in closed equipment, ductwork or piping n n Isolate equipment from service. NAME OF PERSON PERFORMING FIRE WATCH n n Remove ignitable liquid and purge flammable gas/vapor. n n Prior to work, and/or during work, monitor for flammable gas/vapor. LEL reading(s): I verify the above location has been examined, the Required Precautions n n Remove combustible dust/lint or other combustible materials. have been taken, and permission is authorized for this work. n nIs work on/in equipment with nonremovable combustible linings or PERMIT AUTHORIZER (PRINT AND SIGN) parts? If yes, provide ADDITIONAL REQUIRED PRECAUTIONS below. Fire watch/fire monitoring the hot work area THIS PERMIT EXPIRES ON (LIMIT AUTHORIZATION TO ONE SHIFT): DATE: TIME: AM/PM Hot Work Date: Start Time: Finish Time: am/pm am/pm Post-Work Fire Watch Finish Time: am/pm Finish Time: am/pm Name Fire Monitor n Person n Other ADDITIONAL REQUIRED PRECAUTIONS: Name/Other Final Check Times listed are sufficient for majority. Use Table at back of permit for guidance for combustible concealed cavities, roof work or favorable factors. n Perform a continuous fire watch during hot work. n Perform a continuous fire watch post-work for n 1 hour or Other ___ hours. n n Perform fire monitoring for n 3 hours or Other ___ hours. Time: Name F2630 © 2018 FM Global. (Rev. 01/2018) All rights reserved. am/pm WARNING HOT WORK IN PROGRESS! Watch for fire! In case of emergency, call the contacts listed below before attempting to extinguish the fire. Contact Number Construction and Occupancy Factors for Post-Work Fire Watch and Monitoring Periods Occupancy Factors Construction Factors Noncombustible construction, or FM Approved Class 1 or Class A building materials Combustible construction without concealed cavities Combustible construction with unprotected concealed cavities Watch Monitor Watch Monitor Watch Monitor Noncombustible with any combustibles contained within closed equipment (e.g., ignitable liquid within piping) 30 minutes 0 hours 1 hour 3 hours 1 hour 5 hours Office, retail or manufacturing with limited combustible loading 1 hour 1 hour 1 hour 3 hours 1 hour 5 hours Manufacturing with moderate to significant combustible loading except as noted below 1 hour 2 hours 1 hour 3 hours 1 hour 5 hours Warehousing 1 hour 2 hours 1 hour 3 hours 1 hour 5 hours Exceptions: Occupancies with processing or having bulk storage of combustible materials capable of supporting slowgrowing fires (e.g., paper, pulp, textile fibers, wood, bark, grain, coal or charcoal) 1 hour 3 hours 1 hour 3 hours 1 hour 5 hours When performing torch-applied roofing, apply additional precautions and conduct a minimum 2 hours fire watch and 2 hours fire monitoring. If an infrared camera is utilized, reduce to a 1 hour fire watch and 1 hour fire monitoring. hen performing hot work on/in equipment containing nonremovable combustible linings or parts, apply additional precautions and conduct a W minimum 1 hour fire watch and 3 hours fire monitoring within the equipment, and in the surrounding areas per Table above.