ECE 476 Power System Analysis Lecture 19: Short Circuit Analysis Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu Announcements • Please read Chapters 7 and 8 • HW 7 is due today • HW 8 is 7.6, 7.14, 7.20, 7.29, 8.3; it will be covered by an in-class quiz on due on Thursday Nov 3 (hence you will not need to turn it in) • Exam 2 is during class on Tuesday November 15 • Final exam is on Monday December 12, 1:30-4:30pm 1 Fault Analysis • The cause of electric power system faults is insulation breakdown • This breakdown can be due to a variety of different factors – – – – lightning wires blowing together in the wind animals or plants coming in contact with the wires salt spray or pollution on insulators 2 Fault Types • There are two main types of faults – – symmetric faults: system remains balanced; these faults are relatively rare, but are the easiest to analyze so we’ll consider them first. unsymmetric faults: system is no longer balanced; very common, but more difficult to analyze • The most common type of fault on a three phase system by far is the single line-to-ground (SLG), followed by the line-to-line faults (LL), double line-to-ground (DLG) faults, and balanced three phase faults 3 Lightning Strike Event Sequence 1. Lighting hits line, setting up an ionized path to ground 30 million lightning strikes per year in US! a single typical stroke might have 25,000 amps, with a rise time of 10 s, dissipated in 200 s. multiple strokes can occur in a single flash, causing the lightning to appear to flicker, with the total event lasting up to a second. 2. Conduction path is maintained by ionized air after lightning stroke energy has dissipated, resulting in high fault currents (often > 25,000 amps!) 4 Lightning Strike Sequence, cont’d 1. Within one to two cycles (16 ms) relays at both ends of line detect high currents, signaling circuit breakers to open the line – nearby locations see decreased voltages 2. Circuit breakers open to de-energize line in an additional one to two cycles – – breaking tens of thousands of amps of fault current is no small feat! with line removed voltages usually return to near normal 3. Circuit breakers may reclose after several seconds, trying to restore faulted line to service 5 Worldwide Lightning Strike Density Units are Lightning Flashes per square km per year; Florida is top location in the US; very few on the West Coast, or HI, AK. This is an important consideration when talking about electric reliability! Source: http://science.nasa.gov/science-news/science-at-nasa/2001/ast05dec_1/ 6 Fault Analysis • Fault currents cause equipment damage due to both thermal and mechanical processes • Goal of fault analysis is to determine the magnitudes of the currents present during the fault – – need to determine the maximum current to insure devices can survive the fault need to determine the maximum current the circuit breakers (CBs) need to interrupt to correctly size the CBs 7 RL Circuit Analysis • To understand fault analysis we need to review the behavior of an RL circuit v(t ) 2 V cos( t ) Before the switch is closed obviously i(t) = 0. When the switch is closed at t=0 the current will have two components: 1) a steady-state value 2) a transient value 8 RL Circuit Analysis, cont’d 1. Steady-state current component (from standard phasor analysis) iac (t ) where Z I ac 2 V cos(t ) Z R 2 ( L)2 R 2 X 2 V Z 9 RL Circuit Analysis, cont’d 2. Exponentially decaying dc current component i dc (t ) C1e t T where T is the time constant, T L R The value of C1 is determined from the initial conditions: t 2V i (0) 0 i ac (t ) i dc (t ) cos(t Z ) C1e T Z 2V C1 cos( Z ) which depends on Z 10 Time varying current 11 RL Circuit Analysis, cont’d Hence i(t) is a sinusoidal superimposed on a decaying dc current. The magnitude of i dc (0) depends on when the switch is closed. For fault analysis we're just 2V concerned with the worst case: C1 Z i (t ) i ac (t ) i dc (t ) i (t ) 2V 2V t T cos(t ) e Z Z t 2V (cos(t ) e T ) Z 12 RMS for Fault Current t 2V The function i(t) (cos(t ) e T ) is not periodic, Z so we can't formally define an RMS value. However, as an approximation define I RMS (t ) 2 2 iac (t ) idc (t ) 2 I ac 2t 2 T 2 I ac e This function has a maximum value of 3 I ac Therefore the dc component is included simply by multiplying the ac fault currents by 3 13 Generator Modeling During Faults • During a fault the only devices that can contribute fault current are those with energy storage • Thus the models of generators (and other rotating machines) are very important since they contribute the bulk of the fault current. • Generators can be approximated as a constant voltage behind a time-varying reactance ' Ea 14 Generator Modeling, cont’d The time varying reactance is typically approximated using three different values, each valid for a different time period: X"d direct-axis subtransient reactance X 'd direct-axis transient reactance Xd direct-axis synchronous reactance 15 Generator Modeling, cont’d For a balanced three-phase fault on the generator terminal the ac fault current is (see page 386) iac (t ) 1 1 1 ' e X Xd Xd ' d 2Ea t " 1 1 Td e X " X ' d d t Td' sin(t ) where Td" direct-axis subtransient time constant ( 0.035sec) Td' direct-axis transient time constant ( 1sec) 16 Generator Modeling, cont'd The phasor current is then I ac 1 1 1 ' e X Xd Xd ' d Ea t " 1 1 Td e X " X ' d d t Td' The maximum DC offset is 2 Ea' I DC (t ) e " Xd t TA where TA is the armature time constant ( 0.2 seconds) 17 Generator Short Circuit Currents 18 Generator Short Circuit Currents 19 Generator Short Circuit Example • A 500 MVA, 20 kV, 3 is operated with an internal voltage of 1.05 pu. Assume a solid 3 fault occurs on the generator's terminal and that the circuit breaker operates after three cycles. Determine the fault current. Assume X d" 0.15, " Td X d' 0.24, 0.035 seconds, ' Td X d 1.1 (all per unit) 2.0 seconds TA 0.2 seconds 20 Generator S.C. Example, cont'd Substituting in the values 1 t 2.0 1 1 1.1 0.24 1.1 e I ac (t ) 1.05 t 1 1 e 0.035 0.15 0.24 I ac (0) 1.05 7 p.u. 0.15 I base 500 106 14,433 A I ac (0) 101,000 A 3 3 20 10 I DC (0) 101 kA 2 e t 0.2 143 k A I RMS (0) 175 kA 21 Generator S.C. Example, cont'd Evaluating at t = 0.05 seconds for breaker opening 1 0.05 2.0 1 1 1.1 0.24 1.1 e I ac (0.05) 1.05 0.05 1 1 e 0.035 0.15 0.24 I ac (0.05) 70.8 kA I DC (0.05) 143 e 0.05 0.2 kA 111 k A I RMS (0.05) 70.82 1112 132 kA 22 Network Fault Analysis Simplifications • To simplify analysis of fault currents in networks we'll make several simplifications: – – – – – Transmission lines are represented by their series reactance Transformers are represented by their leakage reactances Synchronous machines are modeled as a constant voltage behind direct-axis subtransient reactance Induction motors are ignored or treated as synchronous machines Other (nonspinning) loads are ignored 23 Network Fault Example For the following network assume a fault on the terminal of the generator; all data is per unit except for the transmission line reactance generator has 1.05 terminal voltage & supplies 100 MVA with 0.95 lag pf Convert to per unit: X line 19.5 0.1 per unit 2 138 100 24 Network Fault Example, cont'd Faulted network per unit diagram To determine the fault current we need to first estimate the internal voltages for the generator and motor For the generator VT 1.05, SG 1.018.2 * I Gen 1.018.2 0.952 18.2 1.05 ' Ea 1.1037.1 25 Network Fault Example, cont'd The motor's terminal voltage is then 1.050 - (0.9044 - j 0.2973) j 0.3 1.00 15.8 The motor's internal voltage is 1.00 15.8 (0.9044 - j 0.2973) j 0.2 1.008 26.6 We can then solve as a linear circuit: 1.1037.1 1.008 26.6 If j 0.15 j 0.5 7.353 82.9 2.016 116.6 j9.09 26 Fault Analysis Solution Techniques • Circuit models used during the fault allow the network to be represented as a linear circuit • There are two main methods for solving for fault currents: – – Direct method: Use prefault conditions to solve for the internal machine voltages; then apply fault and solve directly Superposition: Fault is represented by two opposing voltage sources; solve system by superposition • first voltage just represents the prefault operating point • second system only has a single voltage source 27 Superposition Approach Faulted Condition Fault is represented by two equal and Exact Equivalent to Faulted Condition opposite voltage sources, each with a magnitude equal to the pre-fault voltage 28 Superposition Approach, cont’d Since this is now a linear network, the faulted voltages and currents are just the sum of the pre-fault conditions [the (1) component] and the conditions with just a single voltage source at the fault location [the (2) component] Pre-fault (1) component equal to the pre-fault power flow solution Obviously the pre-fault “fault current” is zero! 29 Superposition Approach, cont’d Fault (1) component due to a single voltage source at the fault location, with a magnitude equal to the negative of the pre-fault voltage at the fault location. I g I (1) I g(2) g Im I m(1) I m(2) (2) (2) I f I (1) I 0 I f f f 30 Two Bus Superposition Solution Before the fault we had E f 1.050, I (1) 0.952 18.2 and I m(1) 0.952 18.2 g Solving for the (2) network we get I g(2) I m(2) I (2) f Ef 1.050 j7 j0.15 j0.15 E f 1.050 j 2.1 j0.5 j0.5 j 7 j 2.1 j 9.1 This matches what we calculated earlier I g 0.952 18.2 j 7 7.35 82.9 31 Extension to Larger Systems The superposition approach can be easily extended to larger systems. Using the Ybus we have Ybus V I For the second (2) system there is only one voltage source so I is all zeros except at the fault location 0 I I f 0 However to use this approach we need to first determine If 32 Determination of Fault Current Define the bus impedance matrix Z bus as Z bus Z11 Then Z n1 1 Ybus V Z busI (2) V 1 (2) Z1n 0 V 2 I f Z nn 0 V (2) n 1 (2) Vn For a fault a bus i we get -If Zii V f Vi(1) 33 Determination of Fault Current Hence Vi(1) If Z ii Where Zii driving point impedance Zij (i j ) transfer point imepdance Voltages during the fault are also found by superposition Vi Vi(1) Vi(2) Vi(1) are prefault values 34 Three Gen System Fault Example For simplicity assume the system is unloaded before the fault with E g1 Eg 2 Eg 3 1.050 Hence all the prefault currents are zero. 35 Three Gen Example, cont’d Ybus 0 15 10 j 10 20 5 5 9 0 1 Zbus 0 15 10 j 10 20 5 5 9 0 0.1088 0.0632 0.0351 j 0.0632 0.0947 0.0526 0.0351 0.0526 0.1409 36 Three Gen Example, cont’d 1.05 For a fault at bus 1 we get I1 j 9.6 I f j 0.1088 V (2) 0.1088 0.0632 0.0351 j 9.6 j 0.0632 0.0947 0.0526 0 0.0351 0.0526 0.1409 0 1.050 0.600 0.3370 37 Three Gen Example, cont’d 1.050 1.050 00 V 1.050 0.6060 0.4440 1.050 0.3370 0.7130 38 PowerWorld Example 7.5: Bus 2 Fault One Five Four Three 7 pu 11 pu slack 0.724 pu 0.000 deg 0.579 pu 0.000 deg 0.687 pu 0.000 deg 0.798 pu 0.000 deg 0.000 pu 0.000 deg Two 39