Experiment – No. 1 Calculation of Energy performance Index (EPI) of a building Aim: To calculate the Energy Performance Index (EPI) of a building and compare with energy standard building Apparatus required: • • • Energy meter - 1 No. Typical load set up of a consumer Measuring tape Theory: Energy performance index (EPI) is used around the world to evaluate and monitor residential and commercial building energy performance during design, construction, renovation, and operation. The two most common indices are Asset Ratings and Operational Ratings. Asset Ratings are based on modeled energy use with uniform conditions of climate, schedules, plug loads, occupancy, and energy management. Operational Ratings are based on measured energy use, often normalized for relevant variables like climate and level of energy service. The main aim of this experiment is to find out EPI (Kwh/m2/Year) of a typical load of a consumer and to find out the various ways of decreasing the EPI value without decreasing the comfort levels of a consumer. EPI Vs Star rating values of a building: EPI (kwh/m2 /year) Star Label 190-165 1 Star 165-140 2 Star 140-115 3 Star 115-90 4 Star Below 90 5 Star Energy Management & Auditing Lab, Department of EE, School of Engineering & Technology, GIET University 1 Procedure: To identify the significance of the Energy Performance Index (EPI) value of the building two cases can be analyzed with a building fitted with normal loads & non-compliance green building materials versus a building fitted with energy efficient appliances and green building materials. Case I: Normal Building: 1. Take the readings of power consumption of normal building for 1/2-hour duration. 2. Calculate the reading for 12 hours and another 12 hours with 0.6 multiplying factor as shown in table I. 3. Calculate the above final value for 365 days as shown in Table I. 4. Now measure the room area in m2 with measuring tape. 5. Calculate the EPI value of normal building as shown in Table I. Table I: Power consumption for 1/2 Hr. (1) Kwh Reading of Reading of (1) X 12 hrs. (1) X 12 hrs. X 0.6 (2) (3) Kwh Kwh (2) + (3) X 365 Room area in m2 EPI (4) ÷ (5) (4) Kwh (5) Sq.m (6) Kwh/Sq.m/year Case II: Energy efficient Building: 1. Take the readings of power consumption of normal building for 1/2-hour duration. 2. Calculate the reading for 12 hours and another 12 hours with 0.6 multiplying factor as shown in table II. 3. Calculate the above final value for 365 days as shown in Table II. 4. Now measure the room area in m2 with measuring tape. 5. Calculate the EPI value of normal building as shown in Table II. Table II: Power consumption for 1/2 Hr. (1) Kwh Reading of Reading of (1) X 12 hrs. (1) X 12 hrs. X 0.6 (2) (3) Kwh Kwh (2) + (3) X 365 Room area in m2 EPI (4) ÷ (5) (4) Kwh (5) Sq.m (6) Kwh/Sq.m/year Calculations & Analysis: Analyze the results from Table I and Table II EPI of the normal building: EPI of the Energy efficiency of the building: Energy Management & Auditing Lab, Department of EE, School of Engineering & Technology, GIET University 2 Analysis: Analyze both the cases as per the observations from the experiment Tabulate the improvements/procedures to make the building to a 5-star rated building without compromising the comfort levels of the consumer. Result: Energy Management & Auditing Lab, Department of EE, School of Engineering & Technology, GIET University 3 Experiment No. 2 Identifying various parameters and calculation of HT consumer Electricity bill Aim: To identify the various parameters in HT tariff such as KWH, KVA, KVARH, MD and calculation of HT consumer electricity bill. Information required: HT consumer electricity bill From above HT consumer bill, the following parameters to be observed: - HT consumer: Voltage of High Tension is 11 KV Energy meter is attached to HT side: To minimize the CT rating and not to tamper the meter from consumers. - Contract demand: 547.78 KVA. [ as indicated in bill ] o Contract demand register (kW or kVA). This is the maximum power value, usually the average of 15 minutes, reached during the billing period (this average time may vary depending on the country). Once the value is higher than the contracted power, the customer will pay a penalty on the electricity bill. Energy Management & Auditing Lab, Department of EE, School of Engineering & Technology, GIET University 4 o Kwh reading: The kilowatt-hour (kWh, also kW⋅h or kW h) is a unit of energy equal to 3600 kilojoules (3.6 megajoules). The kilowatt-hour is commonly used as a billing unit for energy delivered to consumers by electric utilities. - Time of Day (or TOD) tariff is a tariff structure in which different rates are applicable for use of electricity at different time of the day. It means the cost of using 1 unit of electricity will be different in mornings, noon, evening and nights. Here, to encourage the consumer to use the electricity at mid night hours, each unit will be charged at 0.20 paise and it will be deducted from main tariff. Calculation procedure of HT consumer Tariff (bill) [ with the above bill]: S.N. Parameters 1 Colony load Reading 0 2 2a) Net Kwh to bill Kwh to bill 149600 149600 2c) TOD tariff 41580 3 Total Kwh 2a) – 2c) Demand Charge (kVA) Unit rate 4.40 / kwh Final bill 0 5.35 x kwh (149600)= 800360 0.20 x kwh (41580) = 8316 Time of day tariff 792044 547.78 250 / kVA should be 109500 but, here 568 x 250 142000 4 Power factor 0.9380 5 Overall drawl charges 20.0 250 / kVA 5000 6 Meter rent - 1000 1000 7 Customer charge 250 250 8 9 Net Total Electricity duty @8% On kwh consumption 940294 63363.52 14 19 20 Total Electricity bill Rebate amount 1003657.52 1003658 9402.94 21 Final Electricity bill 994255.00 792044 0 (8+9) Remarks As there is no colony load and hence it is zero 800360 minus 8316 exceeded to 568 It is above 0.9 and hence no penalty 547.78 rounded to 548 568 – 548 = 20 kVA (extra consumption ) As meter provided by Southco utility and hence meter rent to be paid For 11 KV supply, maintenance charge It depends on electricity regulatory decision on every month due to power purchase with extra rate Rounded If last month bill paid before due date, then a rebate of 10 % offered on previous month total electricity bill [19 – 20 ] Conclusion: Observed the HT consumer’s electricity bill and calculated the tariff of a particular month Energy Management & Auditing Lab, Department of EE, School of Engineering & Technology, GIET University 5 Experiment No. 3 Measuring the power factor of 3 – phase induction motor and procedure for power factor correction Aim: To measure the power factor of 3-Phase induction motor and to improve the power factor to the standard power factor value of 0.95 Apparatus required: Wattmeter – 1 No. Voltmeter – 1 No. Ammeter – 1 No. Power factor meter – 1 No. Clamp meter – 1 No. Capacitor – 1 No. Connecting wires Theory: Procedure: Energy Management & Auditing Lab, Department of EE, School of Engineering & Technology, GIET University 6 Experiment No. 4 Preparing an Energy audit report of domestic load Aim: To prepare an audit report for a domestic load Procedure for an Audit energy report: ▪ Form an Environment Committee and select audit team’s representative of administration, students, parents, teaching and support staff. ▪ Assign goals, tasks and responsibilities. ▪ Write goals (and outcomes) of the audit E.g. Increase awareness, change attitudes, link with the curriculum, reduce waste, etc. ▪ Consider resources for the audit – Establish a fund to provide for the audit, decide on related activities, competitions and events for the college calendar e.g. Environment Youth Forum, World Environment Day. ▪ Publicize concept of the environment audit energy, materials and water. ▪ Each member to obtain all relevant bills and consumption data and outline scope of audit. ▪ Locate all meters and record waste statistics to establish audit baseline. ▪ Evaluate the best ways of presenting data. ▪ Teams collaborate to a database of relevant information. Surveys: Before auditing the energy profile, the scope for better saving patterns has to be identified. • The following points are suggested under this sector for energy conservation: • Using Compact Fluorescent lamps • Using Fluorescent tube light. • Using electronic ballasts. • Switch off an extra light load. • Using light colour paints. Energy Management & Auditing Lab, Department of EE, School of Engineering & Technology, GIET University 7 • Replacement of old regulators. • Location for fixing of lamp. • Switching off the loads when not required. • Computer monitors stand-by modes. • Usage of branded appliances. Calculations: The below tables are showing the wattage comparison, life period and cost of CFL’s and incandescent bulbs in shown below. COMPARISION OF WATTAGES ORDINARY LAMPS CFL LAMP 60W 13W 75W 18W 100W 25W The following illustrates a cost benefits comparison of ordinary bulb with the CFL’s COMPARISION OF COSTS Factors of comparison Lamp life Required No. Of lamps Cost of lamps/lamp Cost of Elec. Rs.4.50 Per KWh + cost of lamp Ordinary Bulb (100W) 1000hrs CFL range (11w) 8000hrs ELECTRONIC BALLASTS: Cost benefits comparisons between electronic and conventional chokes (for a period of one year with 10 hours of operating time per day) Item Description Power Energy Consumption KWh= 4.50 Conventional Choke (duplicate) 58W Conventional Choke (ISI marked) 45W electronic Choke 25w Energy Management & Auditing Lab, Department of EE, School of Engineering & Technology, GIET University 8 ELECTRONIC FAN REGULATOR: Type of Fans Cheap quality fans ISI Standard fans Conventional Regulator Electronic Regulator 75W 70W 65W 60W Result & Analysis: compare the analysis and prepare a report for one year with one-year payback analysis. Energy Management & Auditing Lab, Department of EE, School of Engineering & Technology, GIET University 9 Energy Management & Auditing Lab, Department of EE, School of Engineering & Technology, GIET University 10