1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING ELECTRICAL SYMBOL LEGEND (NOT ALL SYMBOLS APPLY TO THIS PROJECT) 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com UPDATED: 03/03/2014 VAV-9 X EXAMPLES: A. SES1 (SERVICE ENTRANCE SECTION #1) B. 1H1A (SERVED FROM SES#1, 480/277 NORMAL, LEVEL 1, FIRST BOARD) C. 1EQH1A (SERVED FROM MAIN EMER SWBD #1, 480/277 EQUIP POWER, LEVEL 1, FIRST BOARD) RACEWAY & CONDUCTORS HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND INDIVIDUAL TWO OR THREE POLE CIRCUIT BREAKERS. CONDUCTOR IDENTIFICATION SYMBOL INDICATES NUMBER OF CONDUCTORS IN HOMERUN. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH WILL BE PROVIDED IN HOMERUN UON. NEUTRAL MAY BE USED WHERE INDICATED ON PLAN. ALL HOMERUNS WILL INCLUDE GROUND CONDUCTOR. LA-7 LA-13 DENOTES MOUNTING HEIGHT AFF KITCHEN EQUIPMENT REFERENCE A 6 E4 E4 6 A E3 E4 E3 E4 SECTION/ELEVATION LETTER OR DETAIL NUMBER J CODE SIZE JUNCTION BOX P CODE SIZE PULLBOX (OR AS SIZED ON PLAN) 40' VARIES SEE PLANS VARIES SEE PLANS 30/3R LIGHTNING PROTECTION AIR TERMINAL ROOF VARIES THERMOSTAT WALL +44" UON ENCLOSED CIRCUIT BREAKER. AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE UON 30/1 NON-FUSED DISCONNECT SWITCH. AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE UON 30/3R FUSED DISCONNECT SWITCH. AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE UON 0/1 MOTOR STARTER. STARTER SIZE INDICATED BY NUMBER/NEMA ENCLOSURE RATING, SINGLE SPEED UON 1/30/3R COMBINATION FUSIBLE DISCONNECT SWITCH AND MOTOR STARTER. NEMA STARTER SIZE/AMPERAGE/NEMA ENCLOSURE RATING, 3 POLE UON 5 MOTOR. NUMBER INDICATES HORSEPOWER RATING FOR 1HP AND LARGER F MOTOR. "F" INDICATES FRACTIONAL HORSEPOWER OS WALL MOUNTED OCCUPANCY SENSOR; TYPE AS INDICATED ON PLANS OS CEILING MOUNTED OCCUPANCY SENSOR; TYPE AS INDICATED ON PLANS DL DAY-LIGHTING SENSOR; TYPE AS INDICATED ON PLANS RC ROOM CONTROLLER; TYPE AS INDICATED ON PLANS SYMBOL VARIES X IONIZATION SMOKE DETECTOR I VARIES MOTOR CONTROL CENTER. DASHED LINES INDICATE CLEARANCES. DRY TYPE TRANSFORMER (LESS THAN 15kVA), WITH NO EQUIPMENT TAG. SIZE, TYPE AND LOCATION NOTED ON PLANS. AUTOMATIC TRANSFER SWITCH. DASHED LINES INDICATE CLEARANCES. ATS-1 X X GROUND BAR DEMOLITION DESCRIPTION NOTES DASHED SYMBOL INDICATES EXISTING DEVICE OR EQUIPMENT TO BE REMOVED DRAWOUT CIRCUIT BREAKER 300 400 REMOVE EXISTING RACEWAY IN ALL ACCESSIBLE AREAS. CAPPED AND ABANDONED IF IN UNACCESSIBLE AREA R SOLID SYMBOL, LIGHTER IN COLOR INDICATES EXISTING DEVICE OR EQUIPMENT TO REMAIN 80' EX EXISTING CONDUIT TO BE REUSED REFER TO DEMOLITION PLANS FOR ADDITIONAL INFORMATION X UNDER FLOOR SMOKE DETECTOR U FIRE/SMOKE DAMPER AS DETAILED VARIES UNDER FLOOR SEE PLANS AT DUCT SEE PLANS PRESSURE SWITCH PS +44" UON WALL TAMPER SWITCH FS FLOW SWITCH PIV POST INDICATOR VALVE 208Y/120V T1A 75kVA K-4 480V PM PRIMARY SITE METER ENCLOSURE ME METER ENCLOSURE. EITHER ON BUILDING OR ON UTILITY EQUIPMENT CT CT ENCLOSURE. EITHER ON BUILDING OR ON UTILITY EQUIPMENT MAGNETIC DOOR HOLDER R CONTROL RELAY MONITOR MODULE CEILING SURFACE EW PRO M EX I F E S S I ONA L New Mexico State University SEE PLANS VARIES Jett Hall and Jett Annex Renovations and Additions SPECIAL SYSTEMS SYMBOL DESCRIPTION 4 PORT FLOOR BOX WITH A/V. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS. FLOOR 2 PORT VOICE\DATA OUTLET WALL AC 2 PORT VOICE\DATA OUTLET ABOVE COUNTER TOP WALL W TELEPHONE OUTLET WALL MOUNTED MEDIUM VOLTAGE DRAWOUT CIRCUIT BREAKER WALL +84" UON WALL +108 UON WALL SEE PLANS A/V JUNCTION BOX. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS. A/V J- BOXES STACKED VERTICALLY. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS. WALL SEE PLANS C S COMBINATION CLOCK/SPEAKER. MOUNTED ABOVE AND CENTER TO WRITING/TACK BOARD WALL SEE PLANS DSVD DIGITAL SIGNAGE VIDEO DISPLAY WALL SEE PLANS VP VIDEO PROJECTOR REFER TO PLANS S PA CEILING SPEAKER: LOCAL SOUND SYSTEM IC CEILING SPEAKER: INTERCOM SYSTEM INTERCOM CALL SWITCH INTERCOM MASTER STATION S COMMUNICATION HORN COMMUNICATION BELL S WALL SPEAKER TRANSFORMER. TRANSFORMER NAME, TRANSFORMER kVA RATING, PRIMARY VOLTAGE AND WIRING CONFIGURATION, SECONDARY VOLTAGE, K RATING (IF APPLICABLE) LD J Jx Jx J 300A FUSE. "300A" DENOTES AMPERAGE RATING Jx J S Jx J DURESS ALARM PUSHBUTTON LOCK DOWN PUSHBUTTON KW KILOWATT METER Jx J SEE PLANS CEILING MOUNTED A/V JUNCTION BOX. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS. SECURITY SYMBOL DESCRIPTION CR CARD READER. KP KEY PAD M ELECTRONIC METER K1 KIRK KEY INTERLOCK No.1 R1 RELAY No.1 AS AMMETER SWITCH INTERIOR SECURITY CAMERA AMMETER INTERIOR SECURITY CAMERA 180° VOLTMETER SWITCH INTERIOR SECURITY CAMERA 360° V ABOVE CEILING EXTERIOR SECURITY CAMERA MOUNTING LOC. HT. WALL, UON +44" UON VARIES SEE PLANS VARIES SEE PLANS Mark VOLTMETER G GLASS BREAK DETECTOR WINDOW SEE PLANS MD MOTION DETECTOR CEILING SEE PLANS DS DOOR SWITCH DELTA CONNECTED WYE CONNECTED 5 UPS ES ELECTRIC STRIKE UPS M MAGNETIC LOCK Description September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VFD CONNECTION MOTOR CONNECTION Date Date A GENERATOR VFD B WIRELESS ACCESS POINT SURGE ARRESTOR SURGE PROTECTIVE DEVICE FLUSH J-HOOK ROUTING PATH 2 PORT CEILING MOUNTED VOICE/DATA OUTLET TRANSFER SWITCH. SEE PLANS FOR TYPE OF SWITCH SPD CEILING Construction Documents CABLE TRAY FOR COMMUNICATIONS WAP VS +18" UON +44" UON +44" UON TRIP SETTING FRAME SIZE 300A C VARIES SEE PLANS WALL IC SHUNT TRIP OPERATOR A MOUNTING LOC. HT. 4 PORT FLOOR BOX WITH POWER AND DATA GROUND CONNECTION ENGINE GENERATOR TELEVISION PEDESTAL A TE O PROJECT ADDRESSABLE/SUPERVISED RELAY R TRIP SETTING FRAME SIZE DISCONNECT SWITCH. "300A" DENOTES AMPERAGE RATING ST HAND HOLE - POWER OR COMMUNICATION AS INDICATED ON PLANS TVP ST VARIES PIPE M GROUND FAULT PROTECTION MANHOLE - POWER OR COMMUNICATION AS INDICATED ON PLANS TELECOMMUNICATION PEDESTAL F. H E C K REMOTE ALARM INDICATING LIGHT CURRENT TRANFORMER, NUMBER "3000/5" DENOTES RATIO. G CONNECTION CABINET (UTILITY METER MOUNT) TP HN NO. 12498 D TS MM UNDERGROUND UTILITY AND OR SYSTEM DISTRIBUTION. PAD MOUNTED SWITCH EG CEILING OR WALL BR J S HH SURFACE D BEAM TRANSMITTER DA N/A OVERHEAD UTILITY AND OR SYSTEM DISTRIBUTION. UTILITY OR FACILITY TRANSFORMER MH CEILING RATE OF RISE ONLY B DESCRIPTION UT CC G FIXED TEMERATURE; TEMPERATURE AS NOTED ON PLANS OR SPECIFICATIONS BEAM RECEIVER CIRCUIT BREAKER; TRIP SETTING/FRAME SIZE OR NO. OF POLES. SETTINGS AND PROTECTION AS NOTED ON PLANS 300 400 N = NEW EX = EXISTING VARIABLE FREQUENCY DRIVE UPS-A F ICM P = ELECTRICAL PRIMARY S = ELECTRICAL SECONDARY T = TELECOMMUNICATION TV = TELEVISION E = EMERGENCY POWER ATSC = AUTOMATIC TRANSFER SWITCH CONTROL DRY TYPE TRANSFORMER (15kVA OR ABOVE), WITH EQUIPMENT TAG (TAG INSIDE OR OUTSIDE, DEPENDING ON SIZE). IN MOST CASES, ACTUAL SIZE SHOWN ON PLANS (ELECTRICAL ROOMS). UNINTERRUPTABLE POWER SUPPLY. DASHED LINES INDICATE CLEARANCES. R/F COMBINATION RATE OF RISE / FIXED TEMPERATURE BT 3PH = THREE PHASE 1PH = SINGLE PHASE MCC VFD MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 P DESCRIPTION 300 400 DISTRIBUTION POLE FOR OVERHEAD ELECTRICAL OR COMMUNICATIONS AS INDICATED ON PLAN. X STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 PHOTOELECTRIC SMOKE DETECTOR VARIES FLUSH MOUNTED PANELBOARD. DASHED LINES INDICATE CLEARANCES. X +80" UON WALL BELL (GONG) B ONE-LINE DIAGRAM 3000/5 SYMBOL T CHIME NOTIFICATION Jxx N/A FIRE ALARM RACEWAY CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 PHOTOCELL T CB SMALL CASE LETTER DENOTES SWITCHING CONTROL 2= DOUBLE POLE TOGGLE SWITCH 3= THREE-WAY TOGGLE SWITCH 4= FOUR-WAY TOGGLE SWITCH P= PILOT LIGHT TOGGLE SWITCH M = MOMENTARY CONTACT SWITCH K= KEY OPERATED SWITCH WP = WEATHERPROOF TOGGLE SWITCH T= MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD PROTECTION D = DIMMER SWITCH VARIES SEE PLANS UTILITIES NORTH 1" = 40'-0" WALL MOUNTED CODE SIZE J-BOX +44" a= VARIES SEE PLANS X J PC DATA RACEWAY VOICE/DATA COMBINATION RACEWAY DRAWING NUMBER WHERE TAKEN 0 10' 20' SPECIAL PURPOSE RECEPTACLE. NEMA CONFIGURATION AND AMPERAGE AS NOTED ON PLANS DISTRIBUTION BOARD. DASHED LINES INDICATE CLEARANCES. T1A C R EXTERIOR DB L1A SPEAKER NOTIFICATION DUCT DETECTOR PUSHBUTTON (EMERGENCY POWER OFF - EPO) GROUNDING CONDUCTOR CABLE TRAY - POWER AND TELECOMMUNICATIONS TELECOMMUNICATIONS RACEWAY SURFACE MOUNTED PANELBOARD. DASHED LINES INDICATE CLEARANCES. S EMERGENCY BATTERY PACK LUMINAIRE (BUG-EYE/FROG-EYE) +18", UON WALL LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 STROBE LIGHT ONLY POTENTIAL TRANSFORMER. H1A HORN NOTIFICATION COMBINATION SPEAKER AND CHIME NOTIFICATION SPEAKER/HORN WITH STROBE LIGHT MAIN SWITCHBOARD. DASHED LINES INDICATE CLEARANCES. MSB SYMBOL NORTH ARROW OR MATCH ARCHITECT'S DOUBLE FACE EXIT LUMINAIRE. SHADED SIDE INDICATES FACE SIDE. PROVIDE DIRECTIONAL ARROW(S) AS INDICATED ON PLANS WALL DESCRIPTION DRAWING NUMBER WHERE DETAILED A CEILING WALL, UON F EXIT LUMINAIRE. SHADED SIDE INDICATES FACE SIDE. PROVIDE DIRECTIONAL ARROW(S) AS INDICATED ON PLANS DEVICE INDICATOR LETTER. "X" EQUALS DESIGNATION BELOW (TYPICAL FOR MOST SWITCH TYPES): EQUIPMENT SECTION/ELEVATION LETTER OR DETAIL NUMBER DRAWING NUMBER WHERE DETAILED WALL DOUBLE HEAD, POLE MOUNTED LUMINAIRE BUSWAY MEDICAL EQUIPMENT REFERENCE GENERAL DRAWING SYMBOLS FLUSH EMERGENCY DOUBLE DUPLEX (QUADPLEX) RECEPTACLE MECHANICAL EQUIPMENT REFERENCE +44" CEILING X CONDUIT TURNS SYMBOL SURFACE STRIP LUMINAIRE CEILING DOUBLE DUPLEX (QUADPLEX) RECEPTACLE WALL TRACK MOUNTED LUMINAIRES SIMPLEX RECEPTACLE DUPLEX RECEPTACLE CEILING DOWN LIGHT LUMINAIRE; CEILING MOUNTED WALL MOUNTED LUMINAIRES PULL STATION - FIREMAN'S TELEPHONE OUTLET LINEAR DIRECT/INDIRECT LUMINAIRE. CABLE OR STEM MOUNTED VARIES COMBINATION POWER/COMMUNICATION IN CEILING OUTLET. CONFIGURATION AS INDICATED ON PLANS COMBINATION POWER/COMMUNICATION POLE. CONFIGURATION AS NOTED ON PLANS CONDUIT STUBBED AND CAPPED T D V/D FA FLOOR CEILING MOUNTED EMERGENCY DOUBLE DUPLEX (QUADPLEX) RECEPTACLE MULTI-OULET ASSEMBLY (SURFACE MOUNTED RACEWAY) EXPOSED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT ON WALLS OR CEILINGS B G SURFACE MOUNTED LUMINAIRE. LUMINAIRE TYPE AS INDICATED ON PLANS EMERGENCY DUPLEX RECEPTACLE X UNDERGROUND RACEWAY BETWEEN DEVICES AND OR EQUIPMENT UP a F RECESSED MOUNTED LUMINAIRE. SMALL CASE "a" DENOTES SWITCHING, NUMBER "3" DENOTES BRANCH CIRCUITING. SYMBOL "A" DENOTES LUMINAIRE TYPE X CONCEALED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT IN WALLS OR IN CEILING SPACE DOWN CEILING MOUNTED EMERGENCY DUPLEX RECEPTACLE A FIRE ALARM ANNUNCIATOR PANEL SINGLE HEAD, POLE MOUNTED LUMINAIRE HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND INDIVIDUAL SINGLE POLE CIRCUIT BREAKER (S). SYMBOL REPRESENTS A MULTI-BRANCH CIRCUIT. NUMBER OF CONDUCTORS IN HOMERUN WILL INCLUDE A SEPERATE NEUTRAL FOR EACH CIRCUIT PHASE CONDUCTOR. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH WILL BE PROVIDED IN HOMERUN UON. ALL HOMERUNS WILL INCLUDE GROUND CONDUCTOR. LA-5,7,9 X CEILING MOUNTED DOUBLE DUPLEX (QUADPLEX) RECEPTACLE X HOMERUN FROM EQUIPMENT LOCATION. THE CIRCUIT NUMBER ADJACENT TO HOMERUN INDICATES PANEL SOURCE AND INDIVIDUAL SINGLE POLE CIRCUIT BREAKER (S). CONDUCTOR IDENTIFICATION SYMBOL INDICATES NUMBER OF CONDUCTORS IN HOMERUN. MINIMUM #12 CONDUCTORS AND 3/4" RACEWAY PATH WILL BE PROVIDED IN HOMERUN UON. ALL HOMERUNS WILL INCLUDE GROUND CONDUCTOR. LA-1,3 CEILING MOUNTED DUPLEX RECEPTACLE X = SWITCH LEG LA-1 X X CONDUCTOR IDENTIFICATION SYMBOLS. REFER TO PLANS FOR COMBINATION USE. CONDUCTOR IDENTIFICATION MOSTLY USED IN HOMERUN LOCATION, BUT CAN ALSO BE USED IN BRANCH CIRCUITING WHERE APPLIED. GROUND CONDUCTORS WILL BE INSTALLED IN ALL RACEWAYS WHETHER SHOWN OR NOT. = NEUTRAL COMBINATION DUPLEX RECEPTACLE AND COMMUNICATIONS FLOORBOX. DEVICE CONFIGURATION AS INDICATED ON PLANS. X DESCRIPTION = HOT/PHASE X X BRANCH CIRCUITS FROM OVERCURRENT PROTECTION (20A) TO FURTHEST DEVICE SHALL NOT EXCEED 75 FEET FOR #12AWG COPPER AND 150 FEET FOR #10AWG COPPER; MEASURED ALONG CONDUCTORS ROUTING PATH. BRANCH CIRCUITS EXCEEDING 150 FEET WILL BE SIZED SO THAT VOLTAGE DROP DOES NOT EXCEED 5%. = GROUND IN FLOOR EMERGENCY DOUBLE DUPLEX (QUADPLEX) RECEPTACLE. CONFIGURATION AS INDICATED ON PLANS X BRANCH CIRCUIT GENERAL INFORMATION: SYMBOL X MOUNTING LOC. HT. FAA WALL EE R = HIGH VOLTAGE PANELBOARD (480Y/277V) = LOW VOLTAGE PANELBOARD (208Y/120V) IN FLOOR DUPLEX RECEPTACLE. CONFIGURATION AS INDICATED ON PLANS IN FLOOR DOUBLE DUPLEX (QUADPLEX) RECEPTACLE. CONFIGURATION AS INDICATED ON PLANS IN FLOOR EMERGENCY DUPLEX RECEPTACLE. CONFIGURATION AS INDICATED ON PLANS 3 VARIES FATC FIRE ALARM TERMINAL CABINET (EQUIPMENT NAMING CONVENTION PER PLANS) CONSULTANTS GI N X DESCRIPTION HATCHING INDICATES EMERGENCY LIGHTING. HATCH WILL BE MODIFIED FOR EACH LUMINAIRE TYPE. EMERGENCY LUMINAIRE DESIGNATED WITH "E" IN TYPE DESIGNATION. FACP E EN X SES = SERVICE ENTRANCE SECTION NUMBER OR MAIN EMERG SWBD NUMBER SCALE BAR OR MATCH ARCHITECT'S 9/15/2015 7:20:46 PM SYMBOL BLANK FOR NORMAL POWER E = EMERGENCY EL = EMERGENCY-LIFE SAFETY-BRANCH EC = EMERGENCY-CRITICAL-BRANCH EQ = EMERGENCY-EQUIPMENT-BRANCH DEFINITION KEYED NOTE REFERENCE D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt T = TRANSFORMER DB = DISTRIBUTION BOARD MSB = MAIN SWITCH BOARD MCC= MOTOR CONTROL CENTER I = ISOLATED PANELBOARD ATS = AUTOMATIC TRANSFER SWITCH PDU = POWER DISTRIBUTION UNIT UPS = UNINTERRUPTABLE POWER SUPPLY B = BUSWAY MOUNTING LOC. HT. DESCRIPTION FIRE ALARM CONTROL PANEL MOUNTING LOC. HT. F SYMBOL 1, 2, 3, . . = FLOOR LEVEL (SB=SUB-BASEMENT, B=BASEMENT, M=MEZZANINE, P=PENTHOUSE) SYMBOL DESCRIPTION IV REFERENCE TAGS BLANK FOR NORMAL POWER G = GFCI RATED IG = ISOLATED GROUND T = TAMPERPROOF WG = WEATHERPROOF AND GFCI WP = WEATHERPROOF (IN-USE COVER) CL = CLOCK TV = TELEVISION A, B, C, = SEQUENCE OF PANELS OF THIS TYPE SYMBOL RE NEUT NFPA NIC NL NM NO O/H P PA PC PH PMCS R RC RSC SEC SPD SW TEMP TTB TV TVSS TYP. UC U/G UGE UL UON UPS V VFD W WG WP XFER XFMR (TRANSF) 1, 2, 3, . . = SUBFED PANEL H L REFER TO LUMINAIRE SCHEDULE FOR ALL LUMINAIRE TYPES WHETHER WALL MOUNTED OR CEILING MOUNTED. DEVICE INDICATOR LETTER. "X" EQUALS DESIGNATION BELOW (TYPICAL FOR MOST RECEPTACLE TYPES): N B MAX MCC MIN MH MM MTS MVA N N/A NC NEC NEMA AMPS, AMPERE, AMPERAGE ABOVE COUNTER ALTERNATING CURRENT AMERICANS WITH DISABILITIES ACT ABOVE FINISHED FLOOR ABOVE FINISHED GRADE AVAILABLE INTERRUPTING CURRENT ALUMINUM AMERICAN NATIONAL STANDARDS INSTITUTE AUTOMATIC TRANSFER SWITCH CONTROL AUTOMATIC TRANSFER SWITCH AUDIO/VISUAL AMERICAN WIRE GAUGE CONDUIT CIRCUIT BREAKER CLOSED CIRCUIT TELEVISION CIRCUIT CLOCK CURRENT LIMITING FUSE CONDUIT ONLY COPPER DIMMING DIRECT CURRENT DAY-LIGHTING DIAMETER EMERGENCY EMERGENCY, CRITICAL ENGINE GENERATOR EMERGENCY, LIFE SAFETY EMERGENCY, EQUIPMENT EXISTING FUTURE FIRE ALARM FIRE ALARM ANNUNCIATOR FIRE ALARM CONTROL PANEL FIRE ALARM TERMINAL CABINET FEEDER FACILITY MANAGEMENT SYSTEM GENERATOR GROUND FAULT INTERRUPTER GROUND FAULT CIRCUIT INTERRUPTER GROUND FAULT EQUIPMENT PROTECTION GROUND FAULT PROTECTION GROUND. HAND-OFF-AUTOMATIC. HORSEPOWER INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS ISOLATED GROUND THOUSAND CIRCULAR MILS KILOVOLT KILOVOLT AMPS KILOVOLT AMPS REACTIVE KILOWATT KILOWATT HOUR. LONG TIME, SHORT TIME, INSTANTANEOUS, AND GROUND FAULT PROTECTION MAXIMUM MOTOR CONTROL CENTER MINIMUM MANHOLE MIXED MEDIA MANUAL TRANSFER SWITCH MEGAVOLT AMPS NEW NOT APPLICABLE NORMALLY CLOSED NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NEUTRAL NATIONAL FIRE PROTECTION ASSOCIATION NOT IN CONTRACT NORMAL NEW MEXICO NORMALLY OPEN OVERHEAD POLE PUBLIC ADDRESS PHOTOCELL PHASE POWER MONITORING AND CONTROL SYSTEM REMOVED/REMOVAL ROOM CONTROLLER RIGID STEEL CONDUIT SECURITY SURGE PROTECTIVE DEVICE SWITCH TEMPORARY TELEPHONE TERMINAL BOARD TELEVISION TRANSIENT VOLTAGE SURGE SUPPRESSER TYPICAL UNDER COUNTER UNDERGROUND UNDERGROUND ELECTRIC UNDERWRITERS' LABORATORIES UNLESS OTHERWISE NOTED UNINTERRUPTABLE POWER SUPPLY VOLTS, VOLTAGE VARIABLE FREQUENCY DRIVE WALL MOUNTED WEATHERPROOF AND GFCI WEATHERPROOF TRANSFER TRANSFORMER FIRE ALARM R EG I S T E A AC A/C ADA AFF AFG AIC AL ANSI ATSC ATS A/V AWG C CB CCTV CKT CL CLF CO CU D DC DL DIA E EC EG EL EQ EX FUT FA FAA FACP FATC FDR FMS GEN GFI G OR GFCI GFEP GFP GND HOA HP IEEE LIGHTING CO DEFINITION ABBREV. IG KCMIL KV KVA KVAR KW KWH LSIG C DEVICES EQUIPMENT NAMING CONVENTION JO D ABBREVIATIONS REFER TO LIGHTING SCHEDULE E VAN H. GILBERT ARCHITECT PC SEE PLANS DOOR SHEET TITLE ELECTRICAL LEGEND E-001 1 2 3 4 5 6 SHEET 144 OF 187 5 6 022 EXISTING EMS CONSOLE TO BE REMOVED ME/AE COMPUTER LAB 020 018 021 013 MEN 009 EXISTING 12 PANELBOARD "DP" 015 016 EXISTING 18 CONTACTOR 14 17 UP DN MECHANICAL M010 14 14 11 12 DN DEMOLITION BASEMENT FLOOR PLAN D1 ELECTRICAL Scale: 1/16" = 1'-0" 24 23 DN 14 EXISTING PANELBOARD "P1" EXISTING 12 PANELBOARD "MC2" EXISTING PANELBOARD "MC1" 12 12 EXISTING PANELBOARD "NP1" 6 D ME/AE OFFICE 112 ME/AE OFFICE 113 CHME CHME OFFICE OFFICE 151 152 ME/AE DIRECTORS OFFICE SUITE CHME CHME OFFICE OFFICE 153 154 CHME OFFICE 155 CHME OFFICE 156 CHME OFFICE 157 CHME OFFICE 158 CHME OFFICE 159 STORAGE 159A 11 CLASSROOM 103 10 EXIST. PANELBOARD 12 "MC3" 18 10 23 12 DN 5 23 12 EXIST. PANELBOARD "C1" 12 EXIST. A1 EXIST. PLA CHME OFFICE 183D 2 ASME/ PI TAU SIGMA OFFICE 512 VEST. H102A ME/AE DEMO: REMOVE ADA PUSH BUTTMO AND WIRE EXISTING LAB 510A EXIST. A2 20 23 12 FUEL CELL LAB 168 169 SUPPORT 169B VESTIBULE 173 LAB 9. EXISTING DISCONNECT AND ASSOCIATED TANSFORMER CONNECTED TO EXISTING CO-GENERATION SYSTEM ON NMSU CONTROLING CONTINOUS LIGHTING ON JETT HALL ANEX BUILDING TO BE ABANDON IN PLACE. CO-GENERATION SYSTEM WILL EVENTUALLY BE REMOVED FROM NMSU (NOT PART OF SCOPE OF WORK). 10. EXISTING SUBSTATION WITH INTEGRATED FUSE, TRANSFORMER AND PANELBOARD TO BE REMOVED IN ITS ENTIRETY AS SHOWN. 11. EXISTING TELEPHONE TERMINAL BOARD AND ASSOCIATED 3" CONDUIT TO BE REMOVED IN ITS ENTIRETY AS SHOWN. 12. EXISTING PANELBOARD/SWITCHBOARD AND ASSOCIATED WIRE TO BE REMOVED IN ITS ENTIRETY. 13. EXISTING DISCONNECT TO BE REMOVED IN ITS ENTIRETY AS SHOWN. 14. EXISTING MOTOR/PUMP UNIT TO BE REMOVED IN ITS ENTIRETY AS SHOWN. D LAB 176D LAB 172 EXISTING CONCRETE PAD TO BE REMOVED IN ITS ENTIRETY AS SHOWN. 16. EXISTING METER TO BE REMOVED IN ITS ENTIRETY AS SHOWN. 17. EXISTING PAD MOUNTED TRANSFORMER WITH INTEGRAL HIGH VOLTAGE FUSES AND LOAD BREAK SWITCH LOCATED IN BASEMENT LEVEL TO BE REMOVED IN ITS ENTIRETY AS SHOWN. PLUS SECONDARY MAIN CIRCUIT BREAKER AND ASSOCIATED NEMA ENCLOSURE MOUNTED ON SIDE OF TRANSFORMER. 18. EXISTING CONTACTOR TO BE REMOVED IN ITS ENTIRETY AS SHOWN. 19. EXISTING ELECTRICAL/COMMUNICATION LINES FROM ANNEX BUILDING TO MAIN BUILDING TO BE REMOVED IN ITS ENTIRETY. 20. ALL ELECTRICAL WOEK ON MA/ME ROBOTICS LAB SHALL BE MINIMIZE AS MUCH AS POSSIBLE. REFERENCE SHEET EP-103C FOR NEW WORK ON THIS AREA. 21. EXISTING 2" CONDUIT FIBER PATHWAY TO REMAIN. CONTRACTOR SHALL AVOID DAMAGE TO FIBER LINE AT ALL COST. 22. EXISTING DISCONNECT FOR ELECTRICAL ROOM FAN AND ASSOCIATED CONDUCTORS AND PATHWAY TO BE REMOVED IN ITS ENTIRETY. 23. EXISTING ELECTRICAL EQUIPMENT TO BE SALVAGED TO OWNER. ELECTRICAL EQUIPMENT TO BE REMOVED BY CONTRACTOR AND TO BE TAKEN TO TORTUGA SUBSTATION. COORDINATE WITH NMSU. 24. EXISTING EXTERIOR LUMINAIRE TO BE REMOVED IN ITS ENTIRETY AS SHOWN. 25. EXISTING BUILT-IN FURNITURE TO REMAIN. POWER AT DESKS TO BE DISCONNECTED AND RECONNECTED AS INDICATED ON "EP" SHEET SERIES. 26. REFER TO SHEET AD-101 FOR EXISTING EQUIPMENT THAT WILL REMAIN DURING CONSTRUCTION. CONTRACTOR WILL DISCONNECT ANY EXISTING BRANCH CIRCUIT FROM EQUIPMENT. RECONNECT AS INDICATED ON "EP" SHEET SERIES. 170 1 OFFICE 176H 2 VESTIBULE 176 HN F. H E C K ST A TE O NO. 12498 D EW PRO M EX I F E S S I ONA L PROJECT New Mexico State University Jett Hall and Jett Annex Renovations and Additions C REDUCED GRAVITY & BIOMECHANICS 20 176C Construction Documents 1 2 LAB 176A 13 21 ME/ AE CAPSTONE PROJECTS 506A 12 EXIST. PANELBOARD "BN1" EXIST. PANELBOARD "B1" ME/ AE HYDRALLICS LAB 001 EXISTING PULL BOX TO BE REMOVED IN ITS ENTIRETY. 12 12 23 23 B CHME UNDERGRADUATE LAB 171 4"x4" 4"ø EXIST. 3#2 & 1#2 GND 5 KV RATED IN 2-1/2" CONDUIT TO BE REMOVED IN ITS ENTIRETY. GA OFFICE 507 16 23 GRADUATE STUDENT OFFICE 508 MATERIALS SCIENCE LAB EXISTING 4"X4" CONDUIT TRANSITIONING TO 4"Ø FEEDING ECI & ECII TO REMAIN. REFER TO NEW WORK FOR SPLICE CONNECTION. LAB 002 26 12 EXIST. PANELBOARD 5 12 EXISTING PULL BOX TO BE REMOVED IN ITS ENTIRETY. ME.AE DESIGN BUILD FLY LAB 21 13 25 509 14 EXIST. T5-555 EXIST. 3#2 & 1#2 GND 5 KV RATED IN 2-1/2" CONDUIT TO BE REMOVED IN ITS ENTIRETY. 001A DN J 7 EXIST. 12 PANELBOARD "171" P5-210 LAB 8 171E P5-220 P5-230 3 DN EXIST. 15KVA TRANSFORMER TO BE REMOVED IN ITS ENTIRETY EXIST. VAULT SWITCH 9 P5-225 P5-215 EXIST. TRANSFORMER 9 EXIST. S5-180 4 J EXISTING DISCONNECT 9 METERING COMPARTMENT 1 LOAD BREAK SWITCH Date 1 Mark Revision 1 Date Description Date JETT HALL TUNNEL A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © 4"Ø CONDUIT TO BUILDING ECI & ECII TO REMAIN JETT HALL VAULT Project North 9/15/2015 7:21:25 PM EXIST. 23 PANELBOARD "AN1" UNDERGRADUATE CORRIDOR COMPUTER H103 LAB ME/AE WELDING 172A 6 ME/AE OFFICE 004 ME/AE STORAGE 005 EXIST. MDF ROOM TO REMAIN ME/ AE MATERIALS LAB 506B VEST 507A 8. MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 003 EXIST. PANELBOARD "C2" STORAGE 510B ME/ AE EXISTING LAB 510 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 24 SPACECRAFT GUIDANCE, NAV. & CONTROLS LAB 505 MEN 511 B 15 EXIST. 3#2 & 1#2 GND 5 KV RATED IN 2-1/2" CONDUIT TO BE REMOVED IN ITS ENTIRETY. ME/AE WELDING SHOP 21 ME/ AE COMPUTER (GRADUATE) LAB 504 EXISTING P5-210 SWITCH TO REMAIN. P5-210 SHALL BE USED AS SPLICE CONNECTION POINT. REFER TO NEW WORK AND ONE LINE DIAGRAM FOR ADDITIONAL INFORMATION. STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 4"x4" 1 SHIRES LIBRARY 161 4"ø ME/ AE OFFICE 513 EXIST. 3#2 & 1#2 GND 5 KV RATED IN 2-1/2" CONDUIT TO BE REMOVED IN ITS ENTIRETY. 12 EXIST. PANELBOARD "CN1" ME/ AE OFFICE 514 7. 17 DN EXIST. FUSE CHME OFFICE 181 26 MECHATRONICS LAB 503 21 EXISTING EXHAUST FAN IN WELDING ROOM TO REMAIN. DISCONNECT EXISTING CONTROL AND CIRCUIT AND RECONNECT TO NEW CIRCUIT INDICATED IN SHEET EP-103C 15. EXIST. PANELBOARD "A1" 12 ME/ AE OFFICE 516 ME/ AE OFFICE 515 6. CHME OFFICE 183F 12 T5-570 5 12 CHME OFFICE 183E DN 15 12 EXIST. SPN 13 CHME OFFICE 183C EXIST. 1600 A SWITCHBOARD 24 MECHANICAL 14 M100x T5-560 ME/ AE STUDENT STUDY AREA 502 ME/ AE OFFICE 517 CHME OFFICE 183B 15 EXIST. CONTACTOR CHME OFFICE 183G MEN 185 WOMEN 119 T5-565 ME/ AE OFFICE 518 C EXIST. TELEPHONE OFFICE TERMINAL 102 19 EXIST. NP2 & T5-550 CHME OFFICE 183 CHME OFFICE 183A EXIST. PULLBOX EXIST. P2 & T5-545 10 21 JANITOR 121 EXIST. PANELBOARD "B" 24 M M ME/ AE OFFICE 519 EXISTING TRANSFORMER TO BE REMOVED IN ITS ENTIRETY AND SALVAGED TO OWNER. REFER TO ONE LINE DIAGRAM FOR ADDITIONAL INFORMATION. F 12 ME/AE SEMINAR 105 14 5. RE 22 STORAGE 529 MECHANICAL 501 EXISTING 400 A SWITCH LABELED "S5-180" TO REMAIN. REFER TO NEW WORK FOR RECONNECTION INFORMATION AND TO ONE LINE DIAGRAM FOR ADDITIONAL INFORMATION. CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 N 21 VESTIBULE DN107 4. LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 IV KITCHEN 102A EXIST. TELEPHONE 11 TERMINAL BOARD DATA 106A EXISTING VAULT SWITCHES P5-220, P5-230, P5-226, P-215, METERING COMPARTMENT & LOAD BREAK SWITCH TO BE REMOVED IN ITS ENTIRETY AS SHOWN. PLUS ASSOCIATED CONDUIT AND WIRE TO EXISTING TRANSFORMERS SHALL BE REMOVED AS WELL. REFER TO ONE LINE DIAGRAM FOR ADDITIONAL INFORMATION. CONSULTANTS R EG I S T E OFFICE 107C 3. E 117 CORRIDOR H101 ME/AE GRADUATE STUDENT OFFICE SUPPORT 106 107D 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com JO ME/AE OFFICE 111 ME/AE OFFICE 110 MAIL 116 ME/AE OFFICE 115 ALL EXISTING LUMINAIRES TO BE REMOVED, PLUS ASSOCIATED LIGHTING CONTROL, CONDUCTORS AND RACEWAYS PATHS. 14 EXIST. TELEPHONE TERMINAL BOARD ALL EXISTING BRANCH CIRUIT AND RACEWAY PATHS TO BE REMOVED. EXISTING RECEPTACLES, COMMUNICATION OUTLETS AND GENERAL ELECTRICAL DEVICES WILL BE REMOVED. ALL MECHANICAL SYSTEMS TO BE REMOVED AND REPLACED. REMOVE ALL ELECTRICAL CONNECTIONS BACK TO PANEL SOURCE. REFER TO NEW WORK. 2. 14 11 SEMINAR 109 REFER TO SHEET SERIES "AD-101" FOR ARCHITECTURAL DEMOLITION AND ITS EFFECTS ON ELECTRICAL REMOVAL. CONTRACTOR WILL REMOVE ALL ELECTRICAL SYSTEMS FROM DEMOLISHED LOCATIONS. REMOVE ALL ELECTRICAL BACK TO SYSTEM SOURCE EQUIPMENT. 1 12 23 EXISTING PANELBOARD "P" 014 ME/AE OFFICE 114 B. 1. EXISTING 12 PANELBOARD "A" AEROSPACE STRUCTURAL DYNAMICS LAB ME/AE GRAD OFFICE AIAA STUDENT PROJECT WORKSHOP 12 ALL EXISTING ELECTRICAL DISTRIBUTION EQUIPMENT TO BE REMOVED IN ITS ENTIRETY AND REPLACED. REFERENCE KEYNOTES ME/AE LAB 012 ME/AE SOLID MECHANICS LAB A. EXISTING FIRE ALARM 12 CABINET E ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES ME/AE COMPUTER SUPPORT CENTER ME/AE THERMAL SCIENCES LAB Van H. Gilbert Architect PC EE R 4 GI N 1 3 EN ME/AE COMPUTER LAB 2 CO 1 SHEET TITLE EXISTING CONDUIT TO S5-170 IN KNOX VAULT ECI &ECII SWITCH DEMOLITION FIRST FLOOR PLAN A1 ELECTRICAL Scale: 1/16" = 1'-0" 1 ED-101 8' 16' EXISTING CONDUIT TO NEW BAY#3 IN COLLEGE SUBSTATION EXIST. VAULT SWITCH POWER - Level 1 (Annotated) - TUNNEL VAULT 1 DEMO Scale: 1/4" = 1'-0" EXIST. S5-180 0' VAN H. GILBERT ARCHITECT PC EXISTING CONDUIT TO S5-210 LOCATED IN THOMAS BROWN VAULT 32' ELECTRICAL FIRST FLOOR DEMOLITION PLAN ED-101 1 2 3 4 5 6 SHEET 145 OF 187 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES A. ALL EXISTING ELECTRICAL DISTRIBUTION EQUIPMENT TO BE REMOVED IN ITS ENTIRETY AND REPLACED. B. REFER TO SHEET SERIES "AD-102" FOR ARCHITECTURAL DEMOLITION AND ITS EFFECTS ON ELECTRICAL REMOVAL. CONTRACTOR WILL REMOVE ALL ELECTRICAL SYSTEMS FROM DEMOLISHED LOCATIONS. REMOVE ALL ELECTRICAL BACK TO SYSTEM SOURCE EQUIPMENT. 2 CLASSROOM 209 8 8 CLASSROOM 210 CLASSROOM 212 CHME OFFICE 251 CLASSROOM 211 3 OFFICE 206A CLASSROOM 205 CLASSROOM 204 8 8 4 EXIST. PANELBOARD "C1" 4 EXIST. PANELBOARD "C2" CHME OFFICE 254 CHME OFFICE 255 CHME OFFICE 256 3 CHME OFFICE 257 CHME OFFICE 258 CHME OFFICE 259 CHME OFFICE 278 OFFICE 286 KITCHEN 263A 6 EXIST. CONTACTOR WOMEN 285 ME/ AE DESIGN LAB 601 STORAGE 283B SUPPORT 276B SUPPORT 276A 4 ENERGETICS & QUANTUM TRANSPORT LAB ME/ AE OFFICE 629 276 ME/ AE OFFICE 628 BIOMASS THERMOCHEMICAL PROCESSING 264 7 EXIST. PANELBOARD "A2" 9 7 EXIST. PANELBOARD "AN2" EXISTING MOTOR/PUMP UNIT TO BE REMOVED IN ITS ENTIRETY AS SHOWN. 6. EXISTING CONTACTOR TO BE REMOVED IN ITS ENTIRETY AS SHOWN. 7. EXISTING ELECTRICAL EQUIPMENT TO BE SALVAGED TO OWNER. ELECTRICAL EQUIPMENT TO BE REMOVED BY CONTRACTOR AND TO BE T AKEN TO TORTUGA SUBSTATION. COORDINATE WITH NMSU. 8. REFER TO SHEET AD-102 FOR EXISTING EQUIPMENT THAT WILL REMAIN DURING CONSTRUCTION. CONTRACTOR WILL DISCONNECT ANY EXISTING BRANCH CIRCUIT FROM EQUIPMENT. RECONNECT AS INDICATED ON "EP" SHEET SERIES. 9. EXISTING EQUIPMENT AND DEVICES IN ROOM WILL REMAIN AS PRESENTLY INSTALLED. EXISTING BRANCH CIRCUITS WILL BE DISCONNECTED FROM EXISTING PANEL SOURCE AND RECONNECTED INTO NEW PANEL AS INDICATED ON "EP" SHEET SERIES. 10. EXISTING BUILT-IN FURNITURE TO REMAIN. POWER AT DESKS TO BE DISCONNECTED AND RECONNECTED AS INDICATED ON "EP" SHEET SERIES. STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 LAB 265A 4 EXIST. PANELBOARD "C3" D SPECTROPHOTOMETER/ LASER LABORATORY 265 RENEWABLE ENERGY 274 INSTRUMENTATION LAB 602 NANOMATERIALS LAB 266A ME/ AE GRAD STUDENT OFFICE 603 10 ELECTRO CHEMICAL ANALYSIS 267 LAB 272B 1 4 EW PRO M EX I F E S S I ONA L PROJECT New Mexico State University SUPPORT 272C MULTIMEDIA INSTRUCTIONAL LAB 604 608 Jett Hall and Jett Annex Renovations and Additions LAB 269 7 EXIST. 4 PANELBOARD "BN2" 4 EXIST. PANELBOARD "C4" 7 RENEWABLE ENRGY LAB 607 A TE O LAB 268A FLOW CYTOMETRY 272A C ST EXIST. PANELBOARD "CN2" WOMEN 609 HEAT TRANSFER & SURFACE ENGINEERING LAB F. H E C K NO. 12498 D 1 HN F ME/ AE OFFICE 610 5. CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 IV 2 EXISTING PANELBOARD/SWITCHBOARD AND ASSOCIATED WIRE TO BE REMOVED IN ITS ENTIRETY AND SALVAGED TO OWNER. RE 1 4. N ME/ AE OFFICE 611 EXISTING 2" CONDUIT FIBER PATHWAY TO REMAIN. CONTRACTOR SHALL AVOID DAMAGE TO FIBER LINE AT ALL COST. LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 R EG I S T E ME/ AE OFFICE 612 3. CONSULTANTS EE R ME/ AE OFFICE 613 ALL EXISTING LUMINAIRES TO BE REMOVED, PLUS ASSOCIATED LIGHTING CONTROL, CONDUCTORS AND RACEWAYS PATHS. E GI N ME/ AE OFFICE 614 ALL EXISTING BRANCH CIRUIT AND RACEWAY PATHS TO BE REMOVED. EXISTING RECEPTACLES, COMMUNICATION OUTLETSAND GENERAL ELECTRICAL DEVICES WILL BE REMOVED. ALL MECHANICALSYSTEMS TO BE REPLACED. REMOVE ALL ELECTRICAL CONNECTIONS BACK TO PANEL SOURCE. ALL EXISTING LUMINAIRES TO BE REMOVED IN ITS ENTIRETY. REFER TO NEW WORK. 2. 4 ME/ AE OFFICE 615 D 1. SHIRES READING ROOM 263 STORAGE 206C DN REFERENCE KEYNOTES OFFICE 260 AICHE & OXE STUDENT OFFICE 282 CLASSROOM 283 EXIST. PANELBOARD "C" 4 CHME OFFICE 253 JANITOR 284 MEN 201 JANITOR 201A CLASSROOM 203 CHME OFFICE 252 EN E CLASSROOM 208 JO CLASSROOM 207 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com CO 1 THIN FILMS LAB 270 4 EXIST. PANELBOARD "B2" ME/ AE GRADUATE STUDENT OFFICE 606 C 9 CHE SHARED RESEARCH LAB 271 10 Construction Documents Project North DEMOLITION SECOND FLOOR PLAN B2 ELECTRICAL Scale: 1/16" = 1'-0" 0' 8' 16' 32' B B 1 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 5 5 Project North DEMOLITION PENTHOUSE FLOOR PLAN A2 ELECTRICAL Scale: 1/16" = 1'-0" 0' 8' 16' 32' Mark Date Description Date A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 9/15/2015 7:21:29 PM SHEET TITLE ELECTRICAL SECOND FLOOR DEMOLITION PLAN ED-102 1 2 3 4 5 6 SHEET 146 OF 187 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES A. D. E E. CONTRACTORS WILL FAMILIARIZE THEMSELVES WITH THE PROJECT PRIOR TO THE BID OPENING, TO ALLOW THEM TO SUBMIT A COMPLETE BID WITHIN THE SCOPE OF THE DRAWINGS AND SPECIFICATIONS. ANY QUESTIONS ARISING DURING THE BID PERIOD, IN REGARD TO THE CONTRACTOR’S FUNCTIONS, THE SCOPE OF THE WORK OR ANY OTHER ISSUE RELATED TO THIS PROJECT WILL BE BROUGHT UP DURING THE BID PERIOD WITH THE ARCHITECT FOR CLARIFICATION PRIOR TO AWARD OF CONTRACT. REFER TO SHEET E-601 FOR ELECTRICAL EQUIPMENT, CONDUIT SIZE AND ADDITIONAL INFORMATION ON ELECTRICAL DISTRIBUTION SYSTEM. E CONSULTANTS REFER TO SHEET SERIES "ET" FOR MDF AND IDF ROOMS, EQUIPMENT LAYOUTS AND EQUIPMENT SIZES. F. ALL UNDERGROUND CONDUITS LOCATED UNDER ROADWAYS AND PARKING LOTS SHALL BE CONCRETE ENCASED PATHWAYS TRAFFIC RATED. G. ALL HANDHOLES AND MANHOLES LOCATED IN ROADWAYS AND PARKING LOTS SHALL BE TRAFFIC RATED TIER 22. H. EXISTING UTILITIES EQUIPMENT AND RACEWAY OATHS SHOWN IN THESE DOCUMENTS IS FOR INFORMATION PUROSES. CONTRACTOR WILL CONTACT APPROPRIATE NMSU UTILITY DEPARTMENTS TO VERIFY EXACT INFORMATION FOR MODIFICATION OF UTILITIES PRIOR TO COMMENCEMNT OF ANY WORK. I. ALL "FLI" LUMINAIRES TO BE ROUTED THROUGH CONTACTOR LOCATED IN ELECTRICAL ROOMS. REFER TO SHEET E-604 FOR ADDITIONAL INFORMATION. 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 REFERENCE KEYNOTES 1. NEW SPARE CONDUCTOR BACK TO TUNNEL SPACE FOR FUTURE USE. REFER TO SITE PLAN FOR ADDITIONAL INFORMATION. 2. PROVIDE NEW 25 KV RATED CABLE FOR FUTURE CONNECTION TO 25 KV SERVICE. 3. EXIST. "P5-210" TO BE USED AS SPLICE CONNECTION POINT FROM JETT HALL NEW SERVICE LINE TO EXISTING LINE SERVING ENGR. COMPLEX I & II BACK THROUGHT TUNNEL. REFER TO ENLARGED PLAN AND ONE LINE DIAGRAM FOR ADDITIONAL INFORMATION. 4. PROVIDE NEW TRANSFORMER, PAD AND METER ENCLOSURE PROVIDED BY CONTRACTOR. TRANSFORMER TO BE DUAL RATED (5KV & 25KV). 5. ELECTRICAL ROOMS. REFER TO "EP" SHEET SERIES FOR ELECTRICAL ROOM EQUIPMENT AND LAYOUT. 6. NEW SWITCHGEAR. PROVIDE NEW CONCRETE PAS. 7. VAULT IN TUNNEL. REFER TO SHEET E-601 FOR ADDITIONAL INFORMATION. 8. PROVIDE NEW BOLLARD FOR PROTECTION OF NEW SERVICE TRANSFORMER. D MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 D X X X X X X X X X X X X X X X X X X X X X X X X X X X X 10 X D PRO M EX I F E S S I ONA L PROJECT X New Mexico State University X X A TE O F RE X X X RE-ROUTE CIRCUIT THROUGH CONTACTOR LOCATED IN ELECTRICAL ROOM E-167. REFER TO SHEET E-604 FOR ADDITIONAL INFORMATION. EW N X X 10. ST NO. 12498 R EG I S T E X X COORDINATE FIBER CONDUIT DEPTH WITH NEW RACEWAY AND CONDUCTORS. CONTRACTOR SHALL AVOID DAMAGE TO FIBER LINE. F. H E C K IV JO X X X JETT HALL NORTH 9. HN EE R X GI N X EN X CO X X X X X X X X X Jett Hall and Jett Annex Renovations and Additions X X X X X 5 X 5 C X X X C 10 X MSB X X FLI X X X 8 X Construction Documents X X 4 T1 X X 8 5 X X X X X FLI X 5 10 X X X X X X 9 B X JETT HALL ANNEX B JETT HALL EAST X JETT HALL WEST X X X X PMH SWITCH FLI X 6 10 X X X X X X X X X X X X X X X 2 3 X X X X X X X X X X X X X X X X EXISTING TUNNEL D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt X X Mark Description Date 7 A A 1 September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC SHEET TITLE EXISTING TUNNEL 9/15/2015 7:22:40 PM Date ELECTRICAL SITE PLAN SITE PLAN A1 ELECTRICAL Scale: 1" = 20'-0" 1 ES-101 2 3 4 5 6 SHEET 147 OF 187 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES A. B. C. D. E. F. E G. H. I. J. E-603 ARlD ARlD THERMAL SCIENCE LAB 016 ARlD ARlD ARlD ARlD OS OS 3 3 ARlD ARlDE MAE COMPUTER LAB 006 C4 E-603 ARlD ARlD ARlD ARlD ARlD MAE COMPUTER SUPPORT 010 ARlDE SUPPORT 012 ARlDE ARlD ARlD ARlD C4 E-603 ARlD MAE COMPUTER LAB 004 C4 E-603 ARlD ARlD ARlD OS OS OS 3 3 3 ARlD ARlD ARlDE ARlD ARlD ARlD 2 4 RC 4 MECHANICAL M002 ARlD BVlE 2 2 RC RC RC Al2 Al2E 1 Al2 1 4 ARlD ARlD A1SlE1 RC ARlDE ARlDE 1 1 OS ARlD ARlD 5 ARlD ARlD OS 1 ARlD ARlD C4 C4 E-603 E-603 OFFICE 011 C4 E-603 C4 C4 E-603 E-603 NON-LINEAR DYNAMICS & ENERGY HARVESTING 005 H1A SOLID MECHANICS LAB 015 3 8 OS ARlD Bl WOMEN R001 A1Fl C4 9 A1Fl E-603 8 DATA T005 10 CHASE 001B D 0' 4' 8' F. H E C K ST A TE O EW PRO M EX I F E S S I ONA L PROJECT COORDINATE WITH MECHANICAL EQUIPMENT MANUFACTURER PRIOR TO COMMENCEMENT OF ANY WORK New Mexico State University Project North PLAN - BASEMENT B1 LIGHTING Scale: 1/8" = 1'-0" HN NO. 12498 RE 1 1 D N ELEVATOR EQUIPMENT M017B Al2E 7 5 Bl AEROSPACE STRUCTURAL DYNAMICS LAB 009 7 C6lE A1FlE 3 ARlD Bl JANITOR J003 ARlDE A1Sl 4 6 Bl 2 OS ARlD 5 OS 3 ARlD OS 5 6 2 3 ARlD Al2 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 F FLIGHT RESEARCH LAB 013 ARlD Al2E RC 2 ARlDE 3 ARlD Al2 4 1 A1Sl 4 LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1A" LOCATED IN MECHANICAL ROOM 141. REFER TO DETAIL A4 ON SHEET E-402 FOR INVERTER SIZE AND DETAIL A1 ON SHEET E-605 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. LIGHTING ROOM CONTROLLER(S) FOR LIGHTING CONTROL SYSTEM. REFER TO SHEET E-603 FOR ADDITIONAL INFORMATION ON ROOM CONTROLLER CEILING-MOUNTED OCCUPANCY SENSOR, WATT STOPPER DT-355 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-603 FOR WIRING DIAGRAMS & ADDITIONAL INFORMATION ON SENSOR TYPE. ONE SWITCH; SWITCH TYPE AS INDICATED WILL CONTROL THE LUMINAIRES IN ROOM. REFERENCE DETAIL C4 OF SHEET E-603 FOR WIRING DIAGRAM ONE SWITCH; SWITCH TYPE AS INDICATED, WILL CONTROL THE LUMINAIRES IN THIS ROOM WALL-MOUNTED OCCUPANCY SENSOR, WATT STOPPER PW-100 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-603 FOR WIRING DIAGRAM AND ADDITIONAL INFORMATION ON SENSOR TYPE. LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1B" LOCATED IN NEW ELECTRICAL ROOM. REFERENCE DETAIL B2 ON SHEET E-604 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. ALL LUMINAIRES IN DASHED AREA WILL BE CONNECTED TO CIRCUIT INDICATED UNLESS OTHERWISE NOTED. CONTROL IS INDICATED OR NOTED ONE SWITCH; A KEYED MOMENTARY OVERRIDE SWITCH. THIS SWITCH WILL CONTROL CORRIDOR LIGHTING. IT WILL ALSO PROVIDE OVERRIDE OF LIGHTING BETWEEN 11PM AND 5AM. IF LIGHTING IS TURNED ON DURING THE NIGHT, THE LIGHTING WILL AUTOMATICALLY TURN OFF AFTER 30 MINUTES. LIGHTING WILL SIGNAL WITH A BLINK OF THE LIGHTS (5) MINUTES BEFORE SHUT DOWN. LABEL SWITCH 'CORRIDOR CONTROL'. REFERENCE DETAIL SHEET E-604 FOR WIRING DIAGRAM STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 IV ARlD 1 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 R EG I S T E VESTIBULE H017 Al2E RC 2 3 4 BVlE 4 OS Al2 RC 2 ARlDE 1 Al2E 4 RC 1 Al2 1 ARlD OS 3 ARlD RC 2 Al2E 5 Al2 4 4 3 5 1 1 Al2E 4 9 4 4 9 STORAGE S017A 2 CORRIDOR H002 1 5 Bl 1 2 Al2E 1 1 BVlE ARlDE 1 5 LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 REFERENCE KEYNOTES OS STORAGE Bl S018A D 1 CONSULTANTS 1 1 1 E BVlE ARlD ARlD 1 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com JO C4 ALL EXIT SIGNS ARE TYPE "E" (SINGLE FACE) OR "E2" (DOUBLE FACE) UNLESS OTHERWISE NOTED. ALL EXIT SIGNS WILL BE CONNECTED TO CIRCUIT SERVING THE ROOM THEY ARE LOCATED IN AND FROM NO OTHER CIRCUIT. PROVIDE UNSWITCHED CIRCUIT TO ALL EMERGENCY LIGHTING FIXTURES. FOR ELECTRICAL LUMINAIRE SCHEDULE, SEE SHEET E-701. REFER TO SHEET SERIES "EP" FOR ELECTRICAL ROOMS AND ELECTRICAL EQUIPMENT LAYOUT. FOR LUMINAIRE CONTROL CONNECTIONS AND LIGHTING SEQUENCE OF OPERATION, REFER TO SHEET E-603 AND E-604 FOR LUMINAIRES MOUNTING, REFER TO DETAIL C5 ON SHEET E-501 REFER TO SHEET SERIES "A" FOR ADDITIONAL CEILING GRID MOUNTING SUPPORT INFORMATION ALL LUMINAIRES WILL BE SECURELY SUPPORTED SEPARATLEY FROM CEILING GRID TO CEILING STRUCTURE.. FOR EXTERIOR LIGHTING ELEVATIONS, SEE ARCHITECTURAL SHEETS ALL EXTERIOR BUILDING LUMINAIRES, POLE MOUNTED SITE LUMINAIRES, HALLWAY AND STAIRWAY LUMINAIRES WILL BE ROUNTED THOUGH A TIME CLOCK LOCATED IN THE MAIN ELECTRICAL ROOM. REFER TO DETAIL A5 ON SHEET E-604 FOR ADDITIONAL INFORMATION. ALL CORRIDOR AND STAIRWAY/LOBBY LUMINAIRES WILL BE ROUNTED THOUGH A RELAY PANEL LOCATED IN ELECTRICAL ROOMS. REFER TO DIAGRAM A3 ON SHEET E-604 FOR ADDITIONAL INFORMATION. ALL LUMINAIRES TYPES ENDING WITH AN "E" DESIGNATION WILL BE CONNECTED TO A BATTERY INVERTER. REFER TO FLOOR PLAN FOR BATTERY INVERTER LOCATION. EE R 4 GI N 3 EN 2 CO 1 Jett Hall and Jett Annex Renovations and Additions 16' C C Construction Documents B B ELECTRICAL ROOM E001 9/15/2015 7:21:29 PM D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt BVlE BVlE UP BVlE 7 BVlE BVlE WG VESTIBULE H001 7 7 BVlE 7 10 SF-1 MECH. UNIT KEY PLAN MECHANICAL ROOM M003 BVlE 7 BVlE 7 7 BVlE 10 7 BVlE 5 BVlE BVlE BVlE 7 7 7 Mark Date Description Date A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © Project North PLAN - BASEMENT MECHANICAL A5 LIGHTING Scale: 1/8" = 1'-0" 0' VAN H. GILBERT ARCHITECT PC SHEET TITLE LIGHTING PLAN BASEMENT 4' 8' 16' EL-103A 1 2 3 4 5 6 SHEET 148 OF 187 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES A. B. C. D. E. E F. A2 / EL-103B FLl MAE OFFICE 114 ARlD ARlD MAE OFFICE C4 108 E-603 ARlD MAE OFFICE 106 C4 E-603 2 OS 2 OS ARlD ARlD ARlD ARlD ARlDE 7 7 ARlD ARlD ARlD ARlDE ARlDE ARlDE 7 1 1 ARlDE RC ARlD 1 4 4 4 4 4 4 7 BVlE Al2E Al2 7 Al2E Al2 ARlD ARlD ARlDE Al2 MAE DIRECTORS OFFICE SUITE 104 ARlD 3 9 LOBBY H100 7 Al2E 2 7 4 7 ARlDE RC ARlD 4 7 1 ARlD OS 1 ARlDE RC 2 7 1 RC RC 2 7 4 7 Al2E Al2 7 Al2E Al2 7 Al2E Al2 SUPPORT 117D RC RC 4 RC 4 1 ARlD OS 7 Al2 ARlD ARlDE 3 STORAGE S117A STORAGE S117B 2 7 OS ARlDE ARlD ARlD ARlDE 2 2 OS ARlD ARlD OS ARlD 2 ARlD 8 MAE OFFICE 105 ARlD C6lE BlE BREAK ROOM 105A 10 BACK OF ROOM FRONT OF ROOM ARlD C6lE 6 8 A1FlE 8 8 OS 8 7 3 8 A1FlE 10 8 2 OS ARlD C4 E-603 C4 E-603 ARlD COMPUTATIONAL FLOW PHYSICS LAB - I C4 111 E-603 Bl 7 ARlD 8 MAE SEMINAR 113 MAE GRADUATE STUDENT OFFICE 115 ARlD ARlD VESTIBULE H117 ARlD 4 UNISEX R101 A1 / EL-103C ARlD ARlD A4 CLASSROOM 109 Bl ARlD C4 E-603 9 Bl A1Fl A1Fl WOMEN R151 E-603 A1 / EL-103C 10 11 ONE SWITCH; SWITCH TYPE AS INDICATED, WILL CONTROL THE LUMINAIRES IN THIS ROOM ONE SWITCH; SWITCH TYPE AS INDICATED WILL CONTROL THE LUMINAIRES IN ROOM. REFERENCE DETAIL C4 OF SHEET E-603 FOR WIRING DIAGRAM THREE BUTTON, SINGLE OUTLET SWITCH TO BE PROGRAMMED TO CONTROL LUMINAIRES IN ROOM IN ACCORDANCE TO DETAIL A4 OF SHEET E-603 WALL-MOUNTED OCCUPANCY SENSOR, WATT STOPPER LMDW-102 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-604 FOR WIRING DIAGRAM AND ADDITIONAL INFORMATION ON SENSOR TYPE. D LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1A" LOCATED IN MECHANICAL ROOM 141. REFER TO DETAIL A4 ON SHEET E-402 FOR INVERTER SIZE AND DETAIL A1 ON SHEET E-605 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1B" LOCATED IN NEW ELECTRICAL ROOM. REFERENCE DETAIL B2 ON SHEET E-604 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. ONE SWITCH; A KEYED MOMENTARY OVERRIDE SWITCH. THIS SWITCH WILL CONTROL CORRIDOR LIGHTING. IT WILL ALSO PROVIDE OVERRIDE OF LIGHTING BETWEEN 11PM AND 5AM. IF LIGHTING IS TURNED ON DURING THE NIGHT, THE LIGHTING WILL AUTOMATICALLY TURN OFF AFTER 30 MINUTES. LIGHTING WILL SIGNAL WITH A BLINK OF THE LIGHTS (5) MINUTES BEFORE SHUT DOWN. LABEL SWITCH 'CORRIDOR CONTROL'. REFERENCE DETAIL SHEET E-604 FOR WIRING DIAGRAM D FLOOR LIGHTING PLAN - NORTHWEST C2 FIRST Scale: 1/8" = 1'-0" F. H E C K ST A TE O EW PRO M EX I F E S S I ONA L PROJECT New Mexico State University WALL-MOUNTED OCCUPANCY SENSOR, WATT STOPPER PW-100 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-603 FOR WIRING DIAGRAM AND ADDITIONAL INFORMATION ON SENSOR TYPE. ALL LUMINAIRES IN DASHED AREA WILL BE CONNECTED TO CIRCUIT INDICATED UNLESS OTHERWISE NOTED. CONTROL IS INDICATED OR NOTED Jett Hall and Jett Annex Renovations and Additions Project North C HN NO. 12498 RE 10 7 ARlD 1 2 7 OS 5 LIGHTING ROOM CONTROLLER(S) FOR LIGHTING CONTROL SYSTEM. REFER TO SHEET E-603 FOR ADDITIONAL INFORMATION ON ROOM CONTROLLER CEILING-MOUNTED OCCUPANCY SENSOR, WATT STOPPER DT-355 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-603 FOR WIRING DIAGRAMS & ADDITIONAL INFORMATION ON SENSOR TYPE. N 3 ARlDE 5 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 F OS 4 ARlDE ARlDE STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 IV ARlDE CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 R EG I S T E ARlD ARlDE 3 4 1 1 RC 3 8 OS ARlD OS OFFICE 117C 5 Al2E 9 10 4 ARlD LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 REFERENCE KEYNOTES ARlD 7 9 D OS 10 RC 7 ARlDE 4 OS 1 CONSULTANTS 2 OS ARlD E 7 ARlD OS 2 OS ARlD 2 OS C4 E-603 OS ARlD K. 4 2 ARlD 2 ARlD MAE OFFICE 104B C4 E-603 I. 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com JO CONFERENCE ROOM C4 E-603 116 ARlD C4 E-603 MAE OFFICE C4 110 E-603 ARlD H. J. MAIL 104A MAE OFFICE C4 112 E-603 ARlD G. ALL EXIT SIGNS ARE TYPE "E" (SINGLE FACE) OR "E2" (DOUBLE FACE) UNLESS OTHERWISE NOTED. ALL EXIT SIGNS WILL BE CONNECTED TO CIRCUIT SERVING THE ROOM THEY ARE LOCATED IN AND FROM NO OTHER CIRCUIT. PROVIDE UNSWITCHED CIRCUIT TO ALL EMERGENCY LIGHTING FIXTURES. FOR ELECTRICAL LUMINAIRE SCHEDULE, SEE SHEET E-701. REFER TO SHEET SERIES "EP" FOR ELECTRICAL ROOMS AND ELECTRICAL EQUIPMENT LAYOUT. FOR LUMINAIRE CONTROL CONNECTIONS AND LIGHTING SEQUENCE OF OPERATION, REFER TO SHEET E-603 AND E-604 FOR LUMINAIRES MOUNTING, REFER TO DETAIL C5 ON SHEET E501 REFER TO SHEET SERIES "A" FOR ADDITIONAL CEILING GRID MOUNTING SUPPORT INFORMATION ALL LUMINAIRES WILL BE SECURELY SUPPORTED SEPARATLEY FROM CEILING GRID TO CEILING STRUCTURE.. FOR EXTERIOR LIGHTING ELEVATIONS, SEE ARCHITECTURAL SHEETS ALL EXTERIOR BUILDING LUMINAIRES, POLE MOUNTED SITE LUMINAIRES, HALLWAY AND STAIRWAY LUMINAIRES WILL BE ROUNTED THOUGH A TIME CLOCK LOCATED IN THE MAIN ELECTRICAL ROOM. REFER TO DETAIL A5 ON SHEET E-604 FOR ADDITIONAL INFORMATION. ALL CORRIDOR AND STAIRWAY/LOBBY LUMINAIRES WILL BE ROUNTED THOUGH A RELAY PANEL LOCATED IN ELECTRICAL ROOMS. REFER TO DIAGRAM A3 ON SHEET E-604 FOR ADDITIONAL INFORMATION. ALL LUMINAIRES TYPES ENDING WITH AN "E" DESIGNATION WILL BE CONNECTED TO A BATTERY INVERTER. REFER TO FLOOR PLAN FOR BATTERY INVERTER LOCATION. ALL "FLI" LUMINAIRES TO BE ROUTED THROUGH CONTACTOR LOCATED IN ELECTRICAL ROOMS. REFER TO SHEET E-604 FOR ADDITIONAL INFORMATION. EE R 4 GI N 3 EN 2 CO 1 C 0' 4' 8' 16' Construction Documents CHME OFFICE 150 B C4 E-603 CHME OFFICE 152 C4 E-603 ARlD CHME OFFICE 154 C4 E-603 ARlD CHME OFFICE 156 C4 E-603 ARlD CHME OFFICE 158 C4 E-603 ARlD CHME OFFICE 160 C4 E-603 ARlD CHME OFFICE 162 C4 E-603 ARlD CHME OFFICE 164 C4 E-603 ARlD CHME OFFICE 168 CHME OFFICE 166 C4 E-603 ARlD ARlD ARlD OS 2 OS ARlDE 2 2 OS ARlDE ARlDE 9/15/2015 7:21:35 PM ARlDE 1 1 RC ARlDE RC 1 STOR 157 Al2E 8 Al2 Al2E 3 8 CHME OFFICE 159A ARlDE ARlD ARlD 8 RC RC 4 CORRIDOR H161 Al2E ARlDE 2 Bl 8 Al2 4 ARlD MEN R153 C6lE 8 C4 E-603 A1Fl ARlDE OS 4 2 8 4 8 ARlD ARlD 8 A1Fl C4 E-603 CHME OFFICE 159C E-603 8 64 4 RC RC ARlDE ARlDE 8 Al2E FLl 8 ARlDE ARlDE 8 8 C4 C4 E-603 ARlDE 8 C6l 1 OS CHME OFFICE 159F Al2 RC DATA ROOM T165 11 Mark 9 FLl 8 Al2E VESTIBULE H174 C6l A C6lE 0' 4 Project Number 14400 Drawn By Author Checked By Checker VAN H. GILBERT ARCHITECT PC LIGHTING FIRST FLOOR PLAN - NW & NE Project North 3 September 11, 2015 SHEET TITLE A4 / EL-103C FLOOR LIGHTING PLAN - NORTHEAST A2 FIRST Scale: 1/8" = 1'-0" Description Copyright © 8 ARlD A4 / EL-103C Date Date C6lE C6lE 8 CHME OFFICE C4 CHME OFFICE E-603 159D 159E H1B C6lE ENTRY H172 ARlDE ARlD C6l 3 E-603 ARlDE 8 CHME OFFICE 159B 8 C4 CHME OFFICE 159G RC 1 1 C6l C6l 1 Bl A1FlE 4 KEY PLAN 4 1 ARlD 8 4 8 ARlD CHME GRADUATE STUDENT COMPUTER CLUSTER OS 2 OS 159 ARlD ARlD 8 RC ARlDE BVlE Al2E Al2 1 4 C4 E-603 ARlD RC 1 CHME OFFICE 163 8 ARlD C6lE 8 RC 1 JANITOR J155 Al2E 8 4 3 3 Al2 2 ARlD OS ARlDE 4 Al2 CORRIDOR H161 Bl 9 4 4 4 Al2E 1 2 8 8 RC 2 OS ARlDE 8 RC 2 OS ARlDE 8 1 2 OS ARlDE 8 4 4 4 Al2 A 2 OS ARlD 9 1 4 ARlDE RC OS D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt RC 2 OS 8 8 8 2 OS B C4 E-603 4' 5 8' 16' EL-103B 6 SHEET 149 OF 187 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES A. ALL EXIT SIGNS ARE TYPE "E" UNLESS OTHERWISE NOTED. ALL EXIT SIGNS WILL BE CONNECTED TO CIRCUIT SERVING THE ROOM THEY ARE LOCATED IN AND FROM NO OTHER CIRCUIT. PROVIDE UNSWITCHED CIRCUIT TO ALL EMERGENCY LIGHTING FIXTURES. FOR ELECTRICAL LUMINAIRE SCHEDULE, SEE SHEET E-701. REFER TO SHEET SERIES "EP" FOR ELECTRICAL ROOMS AND ELECTRICAL EQUIPMENT LAYOUT. FOR LUMINAIRE CONTROL CONNECTIONS AND LIGHTING SEQUENCE OF OPERATION, REFER TO SHEET E-603 AND E-604 FOR LUMINAIRES MOUNTING, REFER TO SHEET E-501 REFER TO SHEET SERIES "A" FOR ADDITIONAL CEILING GRID MOUNTING SUPPORT INFORMATION ALL LUMINAIRES WILL BE SECURELY SUPPORTED SEPARATLEY FROM CEILING GRID TO CEILING STRUCTURE. ALL CORRIDOR AND STAIRWAY/LOBBY LUMINAIRES WILL BE ROUNTED THOUGH A RELAY PANEL LOCATED IN ELECTRICAL ROOMS. REFER TO DIAGRAM A3 ON SHEET E-604 FOR ADDITIONAL INFORMATION. ALL LUMINAIRES TYPES ENDING WITH AN "E" DESIGNATION WILL BE CONNECTED TO A BATTERY INVERTER. REFER TO FLOOR PLAN FOR BATTERY INVERTER LOCATION. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED WITH FIRE STOPPING, IE. 3M BRAND CALK, PUTTY, STRIP AND SHEET FORMS, DOW CORNERING 3-6548 SILICONE RTV FOAM. ALL "FLI" LUMINAIRES TO BE ROUTED THROUGH CONTACTOR LOCATED IN ELECTRICAL ROOMS. REFER TO SHEET E-604 FOR ADDITIONAL INFORMATION. B. C. D. E. F. E G. H. I. J. LOBBY H121 9 BVlE 5 BVlE BVlE C6lE 5 2 4 MAE OFFICE 124 ARlD ARlDE RC Al2 OS 4 C4 C4 E-603 D 9 3 E-603 3 ARlD 3 2 RC ARlD C6l RC 9 FLl 11 4 RC BVlE BVlE BVlE BVlE FLl2 3 E-603 ARlD 2 C4 E-603 ARlDE 9 ARlD MAE OFFICE 134 4 Al2 9 ARlD BVlE RC 3 11 BVlE BVlE ARlD 14 BVlE 2 BVlE BVlE FLl2 Al2E OS ARlD 10 4 ARlDE OS A2 7 E-603 3 4 9 E-603 MAE OFFICE 138 ARlD ARlD 4 RC A1SlE C6l 3 A1FlE C6lE A1Sl A1Sl BVlE C4 E-603 A1Sl UNISEX C6lE R142 FLl C4 2 E-603 5 A1SlE RC OS MAE OFFICE 196A ARlD BVlE A1Sl E-603 E-603 OS FLl ARlDE A1Sl 4 BVlE 11 RC 2 OS BVlE RC RC BVlE 4 4 2 ICW ARlDE RC 9 H1C 3 ARlD BVlE ARlD 10 ARlD MAE CAPSTONE PROJECTS - II 148 ARlD ARlD BVlE 2 10 Construction Documents REDUCED GRAVITY LAB 191C ARlDE OS MAE ROBOTICS LAB 191B ARlD 3 C4 OS E-603 ARlD 9 1 RC ARlDE 11 OS VESTIBULE H149 2 A1Sl BVlE BVlE 11 BVlE A1Sl BVlE 11 9 A1Sl 4 BVlE 10 10 A1SlE BVlE 10 A1SlE A1SlE A1Sl RC C4 E-603 2 BVlE BVlE BVlE C4 E-603 RC A1Sl C4 E-603 A1FlE BVlE 4 BVlE ARlD OS BVlE A1Fl FLl BVlE BVlE A1Sl 3 OS Mark BVlE Date Description Date A1Sl BVlE A1Fl A1Sl A A2 / CFP-103C A3 / CFP-103A 5 A1Sl BVlE MAE OFFICE 194A 11 C4 E-603 4 4 A1Fl GRADUATE STUDENT OFFICE 149B ARlD ARlD A1Sl A1Sl 11 11 3 OS 3 2 RC A1Sl KEY PLAN OS 9 A1Sl B FLl 3 4 3 A1Sl CHME UNDERGRADUATE LAB 193 3 RC 4 COMPUTATIONAL FLOW PHYSICS LAB - II 149A ARlD ARlD A1Sl 10 BVlE OS E-603 C6lE FLl BVlE C4 ARlDE ARlD C4 4'CFH E-603 11 4 ARlDE BVlE OS A2 / CFP-103C September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC A3 / CFP-103A FLl SHEET TITLE FLl Project North Project North 0' 4' 8' 16' 2 0' 3 LIGHTING FIRST FLOOR PLAN - ANNEX, EAST & WEST WING Project North FLOOR LIGHTING PLAN - EAST WING A4 FIRST Scale: 1/8" = 1'-0" FLOOR LIGHTING PLAN - ANNEX A2 FIRST Scale: 1/8" = 1'-0" FLOOR LIGHTING PLAN - WEST WING A1 FIRST Scale: 1/8" = 1'-0" 1 ARlDE 4 11 FLl 9 4 12 3 BVlE BVlE A1Sl A1Sl RC Al2E ARlD ARlD 10 E-603 9 2 6'CFH BVlE A1Sl A1Sl A1SlE OS 2 4 C4 E-603 MAE MATERIALS LAB 147 2 FLl A1Sl ARlD 4 ARlD A1SlE FLl Al2 Jett Hall and Jett Annex Renovations and Additions OS 10 10 ARlDE BVlE BVlE AERO FLUIDS LAB 194 A1Sl 3 New Mexico State University REFERENCE SHEET SERIES 'EP' FOR ELECTRICAL EQUIPMENT LAY-OUT ALL LUMINAIRES IN DASHED AREA WILL BE CONNECTED TO CIRCUIT INDICATED UNLESS OTHERWISE NOTED. CONTROL IS INDICATED OR NOTED ONE SWITCH; SWITCH TYPE AS INDICATED WILL CONTROL ALL'FLI2' LUMINAIRES. FLl A1Sl 4 MAE LAB 146 PROJECT 14 9 BVlE COMPOSITES LAB 144 C4 E-603 9 A1SlE BVlE BVlE L A1Sl MAE CAPSTONE PROJECTS - I 145 2 Al2E F E S S I ONA 3 A1Sl RC BVlE I RC ARlD 2 BVlE 15 A1Sl 3 4 3 BVlE ARlD 4 OS 4 C4 BVlE A1Sl MAE LAB 191 2 10 11 A1Sl PRO M EX 3 OS RC BVlE BVlE C4 4 BVlE 3 OS 13 14 EW 9 A1Sl 9 A1Sl A TE O ARlDE C4 E-603 BVlE 11 A1Sl BVlE BVlE A1SlE 15 10 C4 E-603 BVlE Al2 RC ARlDE MAE OFFICE 191A A1Sl FLl2 6 C6lE A1Sl 10 ARlD C4 RC 11 BVlE BVlE FLl2 10 4 RC ST NO. 12498 D FLl RC 5 FLl 5'CFH 2 A1Sl A1Sl 11 MAE COMPUTER (GRADUATE) LAB 137 C6lE A1Fl 2 11 Al2E 9 4 F. H E C K C 11 A1Sl 9 RC 12 C4 E-603 8 5 A1Fl 11 10 10 H1B 3 C4 E-603 FLl2 9 10 ARlD 4 C4 E-603 E-603 ARlD HN 4 OS Bl ARlD 2 RC BlE Bl FLl2 2 OS MDF 137A Al2 ARlDE WOMEN R140 STORAGE S196B 4 OS B Bl 5 C4 4 3 9 RC MAE OFFICE 136 OS ARlD 2 11 BVlE 4 Bl RC 10 A1SlE FLl FLl2 ARlDE BREAKROOM 179 ARlD 1 10 ARlDE D LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1A" LOCATED IN MECHANICAL ROOM 141. REFER TO DETAIL A4 ON SHEET E-402 FOR INVERTER SIZE AND DETAIL A1 ON SHEET E-605 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1B" LOCATED IN NEW ELECTRICAL ROOM. REFERENCE DETAIL B2 ON SHEET E-604 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1C" LOCATED IN ELECTRICAL ROOM 131. REFER TO DETAIL A1 ON SHEET E-402 FOR INVERTER SIZE AND DETAIL A1 ON SHEET E-605 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. ONE SWITCH; A KEYED MOMENTARY OVERRIDE SWITCH. THIS SWITCH WILL CONTROL CORRIDOR LIGHTING. IT WILL ALSO PROVIDE OVERRIDE OF LIGHTING BETWEEN 11PM AND 5AM. IF LIGHTING IS TURNED ON DURING THE NIGHT, THE LIGHTING WILL AUTOMATICALLY TURN OFF AFTER 30 MINUTES. LIGHTING WILL SIGNAL WITH A BLINK OF THE LIGHTS (5) MINUTES BEFORE SHUT DOWN. LABEL SWITCH 'CORRIDOR CONTROL'. REFERENCE DETAIL SHEET E-604 FOR WIRING DIAGRAM OS 2 11 BVlE 8 9 E-603 2 9 A1Sl1 CHME MINATURE CHEMICAL PILOT PLANT 184 ARlD 3 11 BVlE 3 RC 1 ARlD STORAGE S180 C4 A1Sl1 BVlE ARlD 4 Bl MAE WELDING A1SlE 182 C4 RC ARlDE A1Sl1 10 3 BVlE A1Sl1 Bl FLl 3 2 C4 E-603 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt ARlD MECHATRONICS LAB 133 4 9/15/2015 7:21:42 PM 2 BVlE 3 A1SlE OS OS A FLl ARlD OS ARlD 4 A1Sl1 OS BVlE 6 4 4 4 3 9 11 5 7 STUDENT PROJECTS CENTER 196 BVlE ARlD Unoccupied Unoccupied ARlD CHME COMPUTER LAB 177 OS BVlE ARlD FLl2 RC C4 E-603 C ARlD 2 10 ARlD BVlE Al2E OS MAE OFFICE 132 ARlD FLl A1Sl1 CORRIDOR H102 RC ARlDE 4 4 RE 4 3 ARlD C6l 10 C4 OS ARlDE 5 11 BVlE BVlE FLl2 ARlD MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 F ARlD LIGHTING ROOM CONTROLLER(S) FOR LIGHTING CONTROL SYSTEM. REFER TO SHEET E-603 FOR ADDITIONAL INFORMATION ON ROOM CONTROLLER CEILING-MOUNTED OCCUPANCY SENSOR, WATT STOPPER DT-355 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-603 FOR WIRING DIAGRAMS & ADDITIONAL INFORMATION ON SENSOR TYPE. ONE SWITCH; SWITCH TYPE AS INDICATED WILL CONTROL THE LUMINAIRES IN ROOM. REFERENCE DETAIL C4 OF SHEET E-603 FOR WIRING DIAGRAM ONE SWITCH; SWITCH TYPE AS INDICATED, WILL CONTROL THE LUMINAIRES IN THIS ROOM THREE BUTTON, SINGLE OUTLET SWITCH TO BE PROGRAMMED TO CONTROL LUMINAIRES IN ROOM IN ACCORDANCE TO DETAIL A4 OF SHEET E-603 CEILING-MOUNTED OCCUPANCY SENSOR, LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-604 FOR WIRING DIAGRAM AND ADDITIONAL INFORMATION ON SENSOR TYPE. STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 IV ARlDE 11 BVlE 2 OS BVlE 3 OS ARlD C6l RC C4 E-603 Al2 9 E-603 11 WALL-MOUNTED OCCUPANCY SENSOR, WATT STOPPER PW-100 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-603 FOR WIRING DIAGRAM AND ADDITIONAL INFORMATION ON SENSOR TYPE. N 3 ARlD 2 10 BVlE 11 11 1 R EG I S T E ARlDE H1A FLl2 3 ARlD 10 9 MAE OFFICE 130 ARlD ARlD FLl 14 C6lE ARlD 3 BVlE 2 C6l C4 ARlD 5 FLl2 ARlD ARlD C4 E-603 OS 4 ARlD E-603 10 MECHANICAL ROOM M198 BVlE BVlE CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 REFERENCE KEYNOTES C4 2 C6lE C6l C6lE BVlE FLl RC BVlE A1SlE 9 OS ARlD ARlD FLl 2 MAE OFFICE 128 ARlD 10 C6lW FLl OS Al2E ARlDE C4 E-603 C6lW ARlD 3 4 OS MAE OFFICE 126 9 C6lE 13 11 C6l 9 ARlD ARlDE 4 FLl C6lW 15 ELECTRICAL ROOM E127 MAE STUDENT LOUNGE 125 BVlE 10 9 Al2E C6lW LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 4 FLl BVlE 12 FLl C6lW 9 MECHANICAL M123 5 C6lE 12 9 9 BVlE 9 C6lW OS 9 C6l BVlE VESTIBULE H122 C6lE 5'CFH 1 Al2 OS FLl C6lW 13 OS Al2 CONSULTANTS A2 / EL-103B E-603 A2 / EL-103B C2 / EL-103B STORAGE S120 E JO C2 / EL-103B A2 / EL-103B C2 / EL-103B 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com EE R 4 GI N 3 EN 2 CO 1 4' 8' 0' 16' 4 5 4' 8' EL-103C 16' 6 SHEET 150 OF 187 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES A. B. C. D. E. F. E G. A2 / EL-103D H. I. J. ALL EXIT SIGNS ARE TYPE "E" UNLESS OTHERWISE NOTED. ALL EXIT SIGNS WILL BE CONNECTED TO CIRCUIT SERVING THE ROOM THEY ARE LOCATED IN AND FROM NO OTHER CIRCUIT. PROVIDE UNSWITCHED CIRCUIT TO ALL EMERGENCY LIGHTING FIXTURES. FOR ELECTRICAL LUMINAIRE SCHEDULE, SEE SHEET E-701. REFER TO SHEET SERIES "EP" FOR ELECTRICAL ROOMS AND ELECTRICAL EQUIPMENT LAYOUT. FOR LUMINAIRE CONTROL CONNECTIONS AND LIGHTING SEQUENCE OF OPERATION, REFER TO SHEET E-603 AND E-604 FOR LUMINAIRES MOUNTING, REFER TO SHEET E-501 REFER TO SHEET SERIES "A" FOR ADDITIONAL CEILING GRID MOUNTING SUPPORT INFORMATION ALL LUMINAIRES WILL BE SECURELY SUPPORTED SEPARATLEY FROM CEILING GRID TO CEILING STRUCTURE. ALL CORRIDOR AND STAIRWAY/LOBBY LUMINAIRES WILL BE ROUNTED THOUGH A RELAY PANEL LOCATED IN ELECTRICAL ROOMS. REFER TO DIAGRAM A3 ON SHEET E-604 FOR ADDITIONAL INFORMATION. ALL LUMINAIRES TYPES ENDING WITH AN "E" DESIGNATION WILL BE CONNECTED TO A BATTERY INVERTER. REFER TO FLOOR PLAN FOR BATTERY INVERTER LOCATION. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED WITH FIRE STOPPING, IE. 3M BRAND CALK, PUTTY, STRIP AND SHEET FORMS, DOW CORNERING 3-6548 SILICONE RTV FOAM. ALL "FLI" LUMINAIRES TO BE ROUTED THROUGH CONTACTOR LOCATED IN ELECTRICAL ROOMS. REFER TO SHEET E-604 FOR ADDITIONAL INFORMATION. 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 REFERENCE KEYNOTES FRONT OF ROOM BACK OF ROOM ARlD ARlD ARlD ARlD FRONT OF ROOM BACK OF ROOM ARlD ARlD ARlD ARlD C4 E-603 1 1 OS 1 7 H2A 7 OS 1 OS 7 1 OS 7 7 ARlD ARlDE ARlD ARlDE 3 RC 2 2 ARlDE ARlD CWl ARlD ARlDE ARlDE CWl CWl CWl CWl 3 7 ARlD ARlDE 3 3 RC 2 3 RC CWl CWl CWl 4 RC 6 RC Al2E Al2 Al2E Al2 Al2 Al2E Al2 7 Al2E Al2 7 Al2E Al2 ARlDE 2 Al2E 8 ARlD A4 E-603 RC ARlDE OS ARlD 7 ARlDE ARlD CLASSROOM 215 1 1 7 ARlDE OS E-603 BACK OF ROOM ARlD 1 A4 6 7 ARlDE ARlD 1 OS FRONT OF ROOM BACK OF ROOM FRONT OF ROOM ARlD 2 ARlD ARlD DATA T203 BVlE Bl STORAGE S207A A4 E-603 BACK OF ROOM Bl 9 WOMEN R201 7 1 OS 8 7 ARlDE OS FRONT OF ROOM C6lE 10 11 1 7 A1FlE OS BVlE 7 5 ARlD ARlD ARlD ARlD ARlD ARlD ARlD ARlD ARlD ARlD ARlD ARlD ARlD STORAGE S217B Bl 6 A1Fl 12 A1FlE 13 A1 / EL-103E A1 / EL-103E 14 D FLOOR LIGHTING PLAN - NORTHWEST C2 SECOND Scale: 1/8" = 1'-0" F. H E C K ST A TE O EW PRO M EX I F E S S I ONA L PROJECT ALL LUMINAIRES IN DASHED AREA WILL BE CONNECTED TO CIRCUIT INDICATED UNLESS OTHERWISE NOTED. CONTROL IS INDICATED OR NOTED ONE SWITCH; A KEYED MOMENTARY OVERRIDE SWITCH. THIS SWITCH WILL CONTROL LIGHTING IN THIS AREA. IT WILL ALSO PROVIDE OVERRIDE OF LIGHTING BETWEEN 11PM AND 5AM. LABEL SWITCH 'CORRIDOR CONTROL'. EXISTING LED LUMINAIRE TO BE REUSED. New Mexico State University Jett Hall and Jett Annex Renovations and Additions Project North C HN NO. 12498 RE 3 7 CLASSROOM 207 2 RC JANITOR 201A LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1A" LOCATED IN MECHANICAL ROOM 141. REFER TO DETAIL A4 ON SHEET E-402 FOR INVERTER SIZE AND DETAIL A1 ON SHEET E-605 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1B" LOCATED IN NEW ELECTRICAL ROOM. REFERENCE DETAIL B2 ON SHEET E-604 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. TWO BUTTON, SINGLE OUTLET SWITCH TO BE PROGRAMMED TO CONTROL LUMINAIRES IN ROOM IN ACCORDANCE TO DETAIL C2 OF SHEET E-603 REFERENCE SHEET SERIES 'EP' FOR ELECTRICAL EQUIPMENT LAY-OUT ONE SWITCH; A KEYED MOMENTARY OVERRIDE SWITCH. THIS SWITCH WILL CONTROL CORRIDOR LIGHTING. IT WILL ALSO PROVIDE OVERRIDE OF LIGHTING BETWEEN 11PM AND 5AM. IF LIGHTING IS TURNED ON DURING THE NIGHT, THE LIGHTING WILL AUTOMATICALLY TURN OFF AFTER 30 MINUTES. LIGHTING WILL SIGNAL WITH A BLINK OF THE LIGHTS (5) MINUTES BEFORE SHUT DOWN. LABEL SWITCH 'CORRIDOR CONTROL'. REFERENCE DETAIL SHEET E-604 FOR WIRING DIAGRAM N 7 Al2 Al2 5 D F ARlDE 4 Al2E MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 R EG I S T E 7 3 2 CLASSROOM 213 3 RC 7 1 E-603 Al2 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 IV Al2E 2 2 7 7 OS OS C4 7 11 6 7 MAE OFFICE 217A ARlD 7 Al2E CWl CWl CWl 4 7 5 RC OS 3 11 CWl 3 4 7 4 CWl CWl CWl CWl CWl CWl 7 2 OS 1 ARlD CWl CWl CWl CWl CWl 1 OS CWl CWl CWl ARlD 7 CWl CWl CWl CWl CORRIDOR H201 VESTIBULE H217 BlE ARlD ARlD 2 BlE D ARlD ARlD ARlD ARlDE ARlD MAE OFFICE 204 OS 12 OS CLASSROOM 210 CLASSROOM 206 ARlD ARlD CLASSROOM 216 C4 E-603 CLASSROOM 208 CEILING-MOUNTED OCCUPANCY SENSOR, WATT STOPPER DT-355 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-603 FOR WIRING DIAGRAMS & ADDITIONAL INFORMATION ON SENSOR TYPE. THREE BUTTON, SINGLE OUTLET SWITCH TO BE PROGRAMMED TO CONTROL LUMINAIRES IN ROOM IN ACCORDANCE TO DETAIL A4 OF SHEET E-603 LIGHTING ROOM CONTROLLER(S) FOR LIGHTING CONTROL SYSTEM. REFER TO SHEET E-603 FOR ADDITIONAL INFORMATION ON ROOM CONTROLLER ONE SWITCH; SWITCH TYPE AS INDICATED WILL CONTROL THE LUMINAIRES IN ROOM. REFERENCE DETAIL C4 OF SHEET E-603 FOR WIRING DIAGRAM ONE SWITCH; SWITCH TYPE AS INDICATED, WILL CONTROL THE LUMINAIRES IN THIS ROOM WALL-MOUNTED OCCUPANCY SENSOR, WATT STOPPER PW-100 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-603 FOR WIRING DIAGRAM AND ADDITIONAL INFORMATION ON SENSOR TYPE. JO ARlD A4 E-603 OS A4 E-603 1 13 C4 E-603 EE R 4 GI N 3 EN 2 CO 1 C 0' 4' 8' 16' C2 / EL-103D Construction Documents B CHME OFFICE 250 CHME OFFICE 252 C4 C4 E-603 E-603 ARlD MEETING/WAITING ROOM 264 CHME OFFICE 258 CHME OFFICE 260 C4 C4 C4 C4 C4 C4 E-603 E-603 E-603 E-603 E-603 E-603 ARlD 1 OS CHME OFFICE 262 CHME OFFICE 256 ARlD 1 OS CHME OFFICE 254 OS ARlD 1 ARlD 1 OS OS ARlD 1 ARlD 1 OS OS H2B CHME OFFICE C4 268 E-603 ARlD 1 12 OS E-603 ARlD ARlD 1 ARlD ARlD COPY ROOM 4 268A OS 1 1 OS B C4 8 8 ARlDE 8 RC ARlDE RC 4 ARlDE 4 3 8 Al2 3 Al2 Bl 5 4 RC 5 OS 1 A1Fl 8 4 14 Al2 CORRIDOR H203 14 Al2 14 E-603 1 OS FRONT OF ROOM 8 14 14 14 14 KEY PLAN Al2 11 8 Al2 8 Al2E CHME CONFERENCE ROOM 274 Al2E ARlD RC E-603 ARlD 8 4 3 ARlDE ARlD ARlD Mark 1 OS 14 14 ARlD 4 14 14 Al2 4 RC 3 C4 E-603 A C6lE C6lE 1 2 3 0' 4 Project Number 14400 Drawn By Author Checked By Checker VAN H. GILBERT ARCHITECT PC SHEET TITLE LIGHTING SECOND FLOOR PLAN - NW & NE Project North FLOOR LIGHTING PLAN - NORTHEAST A2 SECOND Scale: 1/8" = 1'-0" September 11, 2015 C6l 8 A4 / EL-103E A4 / EL-103E Description Copyright © 8 A1FlE Date Date OS ARlD ARlD CHME OFFICE 265 BACK OF ROOM 14 Al2E 4 C4 14 RC Al2E CHME OFFICE 263 ARlD A4 3 8 8 Al2E 2 CLASSROOM 259 ARlDE 4 3 E-603 9/15/2015 7:21:47 PM ARlD ARlDE RC 8 14 14 14 14 C4 3 8 14 1 A1Fl 4 RC ARlDE RC 4 4 8 3 14 MEN R253 CHME OFFICE 251 ARlD 3 14 RC JANITOR J255 Bl C6lE ARlDE STORAGE S257 4 8 8 OS Al2 ARlDE Al2E H2B - 4 2 8 RC ARlDE RC 4 4 8 8 Al2E 11 A ARlDE 8 Al2E Al2E 8 RC ARlDE RC 4 8 J D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 8 8 8 4' 5 8' 16' EL-103D 6 SHEET 151 OF 187 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES A. 6 ELECTRICAL ROOM E301 6 BVlE 7 6 6 BVlE 10 6 BVlE BVlE BVlE 6 BVlE B. C. 12 D. 6 H2A E. F. PENTHOUSE M301 E G. Project North H. PLAN - PENTHOUSE D3 LIGHTING Scale: 1/8" = 1'-0" C2 / EL-103D 0' C2 / EL-103D 1 3 ARlD RC 6 A1Sl BVlE C4 E-603 6 2 VESTIBULE H221 OS A1Sl COMBUSTION LAB 225 C4 4' 8' 16' A2 / EL-103D A2 / EL-103D 5 12 FLl A1SlE 6 A1Sl Al2E 3 BVlE ARlDE E-603 A1Sl ARlDE OS 2 3 RC 6 2 3 A1SlE C4 D MAE OFFICE 226 2 RC 2 ARlD A1SlE ARlD ARlD A1Sl1 DS ARlD CHME RESEARCH LAB 289 2 A1Sl A1Sl1 2 ARlDE ARlD A1Sl 5 Al2E MAE OFFICE 236 RC 6 2 ARlD RC ARlDE 1 6 1 OS Al2 ARlD A1SlE 1 3 MEN R240 2 C4 E-603 3 A1SlE A1Sl1 A1Sl A1Sl A1Sl1 ARlD ARlD DS 2 Al2E C6lE LASER ROOM 286 2 OS SECTION 10 OS BACK OF ROOM 8 RC A1Sl1 FRONT OF ROOM A1Sl A1Sl1 A1Sl1 A1Sl ARlDE ARlD ARlD 2 A1Sl1 C4 3 2 RC A1SlE OS SECTION 11 A1SlE OS ARlD A1SlE ARlD 5 2 6 Al2 ARlD ARlD 2 2 DS 4 RC ARlD 6 A1Sl1 6 6 A1SlE 2 RC A1Sl A1Sl1 A1Sl 2 ARlD MULTIMEDIA INSTRUCTIONAL LAB 245 Al2 ARlD ARlD HEAT TRANSFER & SURFACE ENGINEERING C4 LAB E-603 244 ARlD 2 OS FLl A1SlE 2 ARlD ARlD BACK OF ROOM ARlD RC 5 3 2 FRONT OF ROOM C4 E-603 9 OS A1Sl KEY PLAN 2 A1Sl1 A1Sl 3 ARlD LAB MANAGER OFFICE 295 6 2 MAE GRADUATE STUDENT OFFICE 249 3 RC RC 4 1 BVlE ARlD 6 ARlDE OS 13 6 H2B - 3 5 ARlDE A1SlE 11 2 ARlD ARlD BVlE ARlD J 2 3 RC Mark BVlE C4 E-603 ENERGETIC MATERIAL LAB 292 2 ARlD Date Description Date C4 E-603 ARlD C4 E-603 ARlD 5 3 ARlD OS ARlD RC OS ARlD E-603 A1Sl1 A1SlE A1Sl 4 RC C4 A1SlE OS SECTION 14 6 ARlD EQUIPMENT ROOM 290 Al2E ARlDE OS RENEWABLE ENERGY & 2 THERMAL SYSTEMS LAB 248 A1Sl DS A1Sl1 ARlD ARlD C4 E-603 5 1 OS SECTION 13 OS ARlD B OS E-603 ARlD ARlD A1Sl1 MICROSCOPE ROOM 2 288 A4 8 ARlD ARlD 5 3 ARlD Al2E ARlDE D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 1 OS SECTION 12 ARlDE ARlD A1Sl1 3 A1Sl A1Sl 5 OS E-603 4 B1 E-603 5'CFH ARlD Construction Documents OS FLl ARlD 6 A C 14 6 ARlD L Jett Hall and Jett Annex Renovations and Additions 5 7 OS A1Fl B F E S S I ONA OS A1SlE 14 2 ARlD I BSL-2 ROOM 284 A1Sl1 RC E-603 PRO M EX C4 E-603 A1Sl1 5 OS SECTION 9 RC 6 6 OS A1SlE 1 C4 EW OS A1Sl1 A1Sl A TE O ARlD E-603 A1FlE A1Sl ARlDE 2 C4 3 2 OS SECTION 8 A1Sl1 2 MAE OFFICE 238 ARlD DS FLl 6 ARlDE RC 1 MAE GRADUATE STUDENT OFFICE 237 ARlD ARlD 3 OS EIGHT BUTTON, SINGLE OUTLET SWITCH TO BE PROGRAMMED TO CONTROL LUMINAIRES IN ROOM IN ACCORDANCE TO DETAIL B1 OF SHEET E-603 GLASSWARE / AUTOCLAVE 282 2 5 ST New Mexico State University A1SlE A1Sl F. H E C K PROJECT A1Sl1 ARlD 6 3 A1SlE HN NO. 12498 D RC 3 OS SECTION 7 1 RC E-603 14 A1Sl1 4 2 A1SlE 3 2 OS A1Sl E-603 2 C4 12 13 D 5 4 ARlDE 6 A1Sl B1 C4 C A1Sl E-603 A1Sl1 FLl A1Sl1 ARlD C4 5 OS ARlD ANALYTICAL / INSTRUMENTATION 280 A1Sl1 Al2 OS 9 10 OS 11 OS SECTION 6 1 6 MAE OFFICE 234 RC A1Sl1 2 ARlD CORRIDOR H202 ARlDE E-603 2 1 6 3 OS 3 A1Sl1 A1Sl MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 F ARlD 3 E-603 A1Sl 8 ONE SWITCH; SWITCH TYPE AS INDICATED WILL CONTROL THE LUMINAIRES IN ROOM. REFERENCE DETAIL C4 OF SHEET E-603 FOR WIRING DIAGRAM CEILING-MOUNTED OCCUPANCY SENSOR, WATT STOPPER DT-355 OR APPROVED EQUAL. LOCATE PER MANUFACTURER'S RECOMMENDATIONS. SHOWN HERE FOR BID PURPOSES. REFER TO SHEET E-603 FOR WIRING DIAGRAMS & ADDITIONAL INFORMATION ON SENSOR TYPE. LIGHTING ROOM CONTROLLER(S) FOR LIGHTING CONTROL SYSTEM. REFER TO SHEET E-603 FOR ADDITIONAL INFORMATION ON ROOM CONTROLLER TWO BUTTON, SINGLE OUTLET SWITCH TO BE PROGRAMMED TO CONTROL LUMINAIRES IN ROOM IN ACCORDANCE TO DETAIL C2 OF SHEET E-603 LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1B" LOCATED IN NEW ELECTRICAL ROOM. REFERENCE DETAIL B2 ON SHEET E-604 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. LUMINAIRE WILL BE CONNECTED TO LIGHTING BATTERY INVERTER "B1A" LOCATED IN MECHANICAL ROOM 141. REFER TO DETAIL A4 ON SHEET E-402 FOR INVERTER SIZE AND DETAIL A1 ON SHEET E-605 FOR TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM. ONE SWITCH; SWITCH TYPE AS INDICATED, WILL CONTROL THE LUMINAIRES IN THIS ROOM THREE BUTTON, SINGLE OUTLET SWITCH TO BE PROGRAMMED TO CONTROL LUMINAIRES IN ROOM IN ACCORDANCE TO DETAIL A4 OF SHEET E-603 EXISTING LED LUMINAIRE TO BE REUSED. ALL LUMINAIRES IN DASHED AREA WILL BE CONNECTED TO CIRCUIT INDICATED UNLESS OTHERWISE NOTED. CONTROL IS INDICATED OR NOTED ONE SWITCH; SWITCH TYPE AS INDICATED. WILL CONTROL THE LUMINAIRES IN HALLWAY. REFERENCE DETAIL B4 OF SHEET E-603 FOR WIRING DIAGRAM REFERENCE SHEET SERIES 'EP' FOR ELECTRICAL EQUIPMENT LAY-OUT ONE SWITCH; A KEYED MOMENTARY OVERRIDE SWITCH. THIS SWITCH WILL CONTROL CORRIDOR LIGHTING. IT WILL ALSO PROVIDE OVERRIDE OF LIGHTING BETWEEN 11PM AND 5AM. IF LIGHTING IS TURNED ON DURING THE NIGHT, THE LIGHTING WILL AUTOMATICALLY TURN OFF AFTER 30 MINUTES. LIGHTING WILL SIGNAL WITH A BLINK OF THE LIGHTS (5) MINUTES BEFORE SHUT DOWN. LABEL SWITCH 'CORRIDOR CONTROL'. REFERENCE DETAIL SHEET E-604 FOR WIRING DIAGRAM RE Al2E RC C4 C4 E-603 A1SlE EXPERIMENTAL OS METHODS LAB 2 233 1 2 6 5 2 OS SECTION 4 E-603 ARlD 7 OS SECTION 5 A1SlE ARlDE OS 10 2 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 N 1 1 E-603 ARlD H2A ARlD 4 OS H2B A1Sl1 5 C4 ARlD ARlD MAE OFFICE 232 ARlD 10 2 A1SlE 14 5 DS A1Sl1 C4 MAE OFFICE 230 6 FLl ARlDE 6 4 6 A1Sl CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 IV 2 ARlDE A1Sl RC Al2 OS ARlD A1Sl A1SlE LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 R EG I S T E MAE OFFICE 228 3 RC A1Sl1 5 OS SECTION 3 A1Sl 1 3 A1Sl1 3 OS 6 3 C4 E-603 A1Sl1 A1Sl OS A1SlE RC 6 A1Sl 2 ARlDE OS ARlD A1Sl1 FLl A1Sl 4 Al2E E-603 A1Sl A1Sl1 HAZARDOUS MATERIAL LAB 278 OS SECTION 2 5 FLl 2 2 A1Sl1 6 RC 1 OS RC CONSULTANTS REFERENCE KEYNOTES 1 FLl A1Sl E A1Sl1 3 2 Al2 ARlD OS 2 SECTION 1 OS 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com 5 RC 4 7 C4 MAE OFFICE 224 A1SlE A1Sl 5 OS 13 C4 E-603 A1SlE BVlE ELECTRICAL ROOM E301 E-603 7 A1Sl ARlD MAE OFFICE 222 J. REF.: DETAIL D3 ON SHEET EL-103E 5'CFH ARlDE I. ALL EXIT SIGNS ARE TYPE "E" UNLESS OTHERWISE NOTED. ALL EXIT SIGNS WILL BE CONNECTED TO CIRCUIT SERVING THE ROOM THEY ARE LOCATED IN AND FROM NO OTHER CIRCUIT. PROVIDE UNSWITCHED CIRCUIT TO ALL EMERGENCY LIGHTING FIXTURES. FOR ELECTRICAL LUMINAIRE SCHEDULE, SEE SHEET E-701. REFER TO SHEET SERIES "EP" FOR ELECTRICAL ROOMS AND ELECTRICAL EQUIPMENT LAYOUT. FOR LUMINAIRE CONTROL CONNECTIONS AND LIGHTING SEQUENCE OF OPERATION, REFER TO SHEET E-603 AND E-604 FOR LUMINAIRES MOUNTING, REFER TO SHEET E-501 REFER TO SHEET SERIES "A" FOR ADDITIONAL CEILING GRID MOUNTING SUPPORT INFORMATION ALL LUMINAIRES WILL BE SECURELY SUPPORTED SEPARATLEY FROM CEILING GRID TO CEILING STRUCTURE. ALL CORRIDOR AND STAIRWAY/LOBBY LUMINAIRES WILL BE ROUNTED THOUGH A RELAY PANEL LOCATED IN ELECTRICAL ROOMS. REFER TO DIAGRAM A3 ON SHEET E-604 FOR ADDITIONAL INFORMATION. ALL LUMINAIRES TYPES ENDING WITH AN "E" DESIGNATION WILL BE CONNECTED TO A BATTERY INVERTER. REFER TO FLOOR PLAN FOR BATTERY INVERTER LOCATION. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE SEALED WITH FIRE STOPPING, IE. 3M BRAND CALK, PUTTY, STRIP AND SHEET FORMS, DOW CORNERING 3-6548 SILICONE RTV FOAM. ALL "FLI" LUMINAIRES TO BE ROUTED THROUGH CONTACTOR LOCATED IN ELECTRICAL ROOMS. REFER TO SHEET E-604 FOR ADDITIONAL INFORMATION. JO 7 BVlE EE R 4 GI N 3 EN 2 CO 1 A BVlE ARlD September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © 4'CFH ARlD ARlD VAN H. GILBERT ARCHITECT PC ARlD 9/15/2015 7:21:53 PM SHEET TITLE FLOOR LIGHTING PLAN - EAST WING A4 SECOND Scale: 1/8" = 1'-0" FLOOR LIGHTING PLAN - WEST WING A1 SECOND Scale: 1/8" = 1'-0" 0' 1 LIGHTING SECOND FLOOR PLAN - E & W WING, & PENTHOUSE Project North Project North 4' 8' 2 0' 16' 3 4 5 4' 8' EL-103E 16' 6 SHEET 152 OF 187 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES H. I. J. E K. CIRCUITS FOR GENERAL POWER WITHIN DASHED AREA ARE FED FROM PANEL 'LBAA' UNLESS NOTED OTHERWISE. 1 T 22 2 J G 4 G 7 G 7 4 G 8 G 14 G 2 G TYP. L1A11 - 8 3 5 2 8 J 8 J J SUPPORT 012 7 5 G 8 L1A11 STORAGE S018A 6 L1A- 1 10 5 D 10 14 6 3 STORAGE S017A 7 2 L1A12 L1A12 - 2,7 L1A13 - 5 L1A12 - 10,12,14 TYP. G 4 7 L1A13 - 2 15 TAC22 ELEVATOR UNIT TYP. LBAA - 16,18,20 14 J 5 8 13 3 L1A12 - 1 1 9 11 T M1A- 5 J 5 11 6 3 2 G L1A13 - 3 14 MECHANICAL M002 2 L1A8 - 6 8 SCV3-005 19 LBAA - 12 12 19 LBAA - 11,19 11 13 9 L1A14 - 2 8 12 14 4 4 21 J J TYP. 4 5 L1A - 2 15 L1A15 LBAA - 4 2 4 3 NON-LINEAR DYNAMICS & ENERGY HARVESTING 005 SCV3-006 L1A-1 4 4 J 7 G 16 8 8 15 9 1 4 G L1A15 - 1 L1A15 - 11 14 J 6 9 J 12 8 1 2 13 17 2 DATA T005 J WOMEN R001 LBAA - 10 TYP. 13 2 11 G 11 10 11 LBAA - 1 15 L1A-1 L1A14 - 5 2 5 4 15 JANITOR J003 15 LBAA - 17 L1A15 - 8 L1A15 - 4,6 SCV3-008 2 L1A15 - 9 LBAA - 7 7 7 L1A15 - 13 L1A15 - 2 12 7 J 14 J 7 LBAA - 14 OFFICE 007 L1A-1 L1A14 - 4 L1A14 - 7 14 6 23 ACU-1 6 J 4 POWER RECEPTACLE TO BE INSTALLED INSIDE PLUMBING CHASE. MOUNT MULTI-OUTLET ASSEMBLY 6" ABOVE COUNTER TOP BACK SPLASH, TABLE TOP OR SINK. OPEN SPACE TO RUN ELECTRICAL RACEWAYS FROM UNDERGROUND UP TO ELECTRICAL ROOM ON FIRST FLOOR AND PENHOUSE LEVEL. UNDERGROUND BANK OF CONDUITS FROM MSB. REFER TO SITE PLAN FOR CONTINUATION OF FEEDERS. REUSE EXISTING CABINET TO RUN NEW WIRE WHEN POSSIBLE. PROVIDE NEW POWER OUTLETS IN SAME LOCATION. POSSIBLE ROUTING OF CONDUIT FROM ELECTRICAL ROOM-E127 TO BASEMENT PLENUM SPACE THROUGH NEW CHASE. CONTRACTOR TO COORDINATE FINAL ROUTING OF CONDUIT. FOR EACH UNIT, REFER TO SHEET SERIES M-700 AND P-7OO FOR MECHANICAL EQUIP CHARACTERISTICS. REFER TO SHEET E-708 FOR ELECTRICAL CONNECTIONS AND ADDITIONAL INFORMATION. CONTRACTOR TO PROVIDE POWER FROM VFD TO MECHANICAL EQUIPMENT. TERMINATE PER MANUFACTURERS DIRECTIONS. SPLIT SYSTEM UNIT. REFER TI SHEET E-709 FOR ADDITIONAL ELECTRICAL INFORMATION. PROVIDE A THERMAL SWITCH DISCONNECT ADJACENT TO UNIT. RACEWAY AND CONDUCTORS WILL BE EXTENDED TO ASSOCIATED ROOF UNIT FOR THIS SPLIT SYSTEM. REFER TO SHEET SERIES 'M' FOR ADDITIONAL INFORMATION 10 14 L1A15 - 14 9 8 OFFICE L1A- 1 011 1 2 3 L1A8 - 4 3 14 7 J 2 G 1 12 CHASE 001B 5 13 Project North PLAN - BASEMENT C1 POWER Scale: 1/8" = 1'-0" NEMA CONFIGURATION RECEPTACLE TO MATCH NEMA CONFIGURATION OF EQUIPMENT PLUG. PROVIDE 4#6 & 1#10 GROUND IN 3/4" CONDUIT OR IN 5400 MULTI-OULET ASSEMBLY. PROVIDE CONDUCTORS AND RACEWAY FROM PANEL SOURCE UP TO NEW 6" SQUARE JUNCTION BOX MOUNTED IN CEILING SPACE AND DOWN THROUGH WIREMOLD. REFERENCE DETAIL. FLUSH MOUNTED POWER OUTLETS IN MULTI-OUTLET ASSEMBLY. REFER TO DETAIL 8 ON SHEET E-501 FOR ADDITIONAL INFORMATION. NEMA CONFIGURATION RECEPTACLE TO MATCH NEMA CONFIGURATION OF EQUIPMENT PLUG. PROVIDE 4#10 & 1#10 GROUND IN 3/4" CONDUIT OR IN 5400 MULTI-OULET ASSEMBLY. LOW-VOLTAGE POWER SUPPLY CONNECTION TO AUTOMATIC SENSOR-OPERATED LAVATORY FAUCETS AND FLUSH VALVES. PROVIDE CONCEALED RACEWAYS, BACK BOXES, TRANSFORMER AND HARDWIRED CONNECTIONS TO ALL SENSORS/FAUCETS AS REQUIRED. CRITICAL COORDINATION OF ROUGH-IN REQUIRED PRIOR TO COMMENCING WORK. WIRE ALL COMPONENTS COMPLETE FOR OPERATION. 14 15 0' 4' 8' 16' 16 17 C A2 / EP-103C A2 / EP-103C 18 19 20 22 23 24 3 HN F. H E C K ST A TE O NO. 12498 D EW PRO M EX I F E S S I ONA L PROJECT New Mexico State University Jett Hall and Jett Annex Renovations and Additions C SINGLE POINT CONNECTION FOR FUTURE HEAT TAPE. NEW LOCATION FOR EXISTING 2KVA TRANSFORMER. EXTEND NEW CIRCUIT TO NEW SERVICE DISCONNECT. CONDUCTORS AND RACEWAY FROM EXISTING DISCONNECT TO UNIT TO REMAIN AS PRESENTLY INSTALLED. PROVIDE NEW JUNCTION BOX FOR SUMP PUMP. REFERENCE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. NEMA CONFIGURATION RECEPTACLE TO MATCH NEMA CONFIGURATION OF EQUIPMENT PLUG. REFERECE SHEET E-801 FOR ADDITION INFORMATION ON ELECTRICAL CONNECTIONS FOR LAB EQUIPMENT. CONTRACTOR TO FIELD VERIFY BEFORE COMMENCING ANY WORK. SPLIT SYSTEM UNIT. PROVIDE A THERMAL SWITCH SERVICE DISCONNECT ADJACENT TO UNIT FOR THIS SPLIT SYSTEM. EXTEND POWER CIRCUIT TO CONDENSING UNIT ON ROOF. CONTRACTOR TO PROVIDE POWER FROM VFD TO EQUIPMENT MOTOR. TERMINATE PER MANUFACTURES DIRECTION. 21 B D LIGHTING BATTERY INVERTER FOR EMERGENCY LIGHTING FOR FIRST (EAST) AND FIRST FLOOR (NORTH-EAST) AREA. LIGHTING BATTERY INVERTER SYSTEM EQUIPMENT WILL BE FOR EGRESS EMERGENCY LIGHTING. EQUIPMENT WILL BE STACKED TO MINIMIZE WALL SPACE. INVERTER WILL OPERATE IN THE EVENT OF AN EMERGENCY. BATTERY INVERTER FOR FIRST FLOOR (EAST) WILL BE RATED FOR 1500 VA. BATTERY INVERTER FOR FIRST FLOOR (NORTH-EAST) WILL BE RATED FOR 2000VA. REFER TO TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM ON SHEET E-604. L1A15 - 12 14 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 RACEWAY AND CONDUCTORS TO PENETRATE WALL INTO WIREMOLD. PROVIDE NEW SERVICE DISCONNECT IN SAME LOCATION WHERE OLD DISCONNECT WAS LOCATED. NEMA CONFIGURATION AND SIZE SHOULD MATCH EXISTING DISCONNECT ELECTRICAL CHARACTERISTICS.REFERECE SHEET E-801 FOR ADDITION INFORMATION ON ELECTRICAL CONNECTIONS FOR LAB EQUIPMENT. CONTRACTOR TO FIELD VERIFY BEFORE COMMENCING ANY WORK. L1A14 - 3 14 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 F L1A12 - 11 8 L1A12 - 8 L1A12 -9 L1A12 - 5 SOLID MECHANICS LAB 5 L1A12 - 13 015 20 10 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 REFERENCE KEYNOTES 8 LBAA - 21 AEROSPACE STRUCTURAL DYNAMICS LAB 009 SCV3-004 SHOULD CONTRACTOR AT ANY TIME NOTICE THAT THE ACTUAL FIELD CONDITIONS DO NOT CORRESPOND TO THE INFORMATION GIVEN ON THE DRAWINGS, THEN IT WILL BE THEIR RESPONSIBILITY TO NOTIFY THE ENGINEER FOR CLARIFICATION, PRIOR TO COMMENCING SUCH WORK. RE 11 3 SCV3-003 G. 14 4 TYP. THE CONTRACTOR SHALL INSTALL TIE HANDLES OR MULTI-POLE BREAKERS FOR ALL CIRCUITS SHARING A NEUTRAL CONDUCTOR. N ELEVATOR EQUIPMENT M017B TYP. FLIGHT RESEARCH LAB 013 L1A- 1 L1A13 - 4,6,8 6 FCU-3 14 J 6 15 F. PROVIDE BLANK COVER PLATE FOR ALL EXISTING OUTLETS NOT BEING REUSED, UNLESS THEY ARE COVERED BY WIREMOLD. LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 R EG I S T E 9 T 7 L1A8 L1A9 - 9 CORRIDOR H002 LBAA - 9,13 11 15 L1A- 1 SCV3-002 MAE COMPUTER LAB 004 L1A8 - 6 J L1A9 - 6 L1A14 L1A13 - 7,9,11 L1A12 - 6 1 CONTRACTOR SHALL INSTALL PULL AND JUNCTION BOXES WHEREVER REQUIRED BY N.E.C. OR JOB CONDITIONS. ALL NEW WIRING SHALL BE TAGGED AT ALL PULL BOXES, JUNCTION BOXES, EQUIPMENT BOXES AND CABINETS WITH APPROVED PLASTIC TAGS. ACTION CRAFT, BRADY OR APPROVED EQUAL. 5 14 5 VESTIBULE H017 M1A- 5 E. E TYP. 6 L1A9 - 1 THE CONDUIT RUNS, AS SHOWN ON PLANS, INDICATE APPROXIMATE ROUTING. EXACT CONSULTANTS LOCATION OF CONDUIT RUNS SHALL BE AS FIELD CONDITIONS DICTATE. IV 3 L1A10 - 3 19 9 19 L1A12 - 4 5 13 1 11 L1A13 - 1 5 15 7 D. L1A8 - 1 L1A8 - 5 J 3 3 LBAA 6 L1A13 L1A9 - 3 4 2 L1A10 - 2 10 20 6 2 17 L1A15 - 3 11 L1A12 - 3 10 T 5 1 1 9 TYP. 14 J 19 3 14 5 4 9 15 LOCATION OF EQUIPMENT AND OTHER DEVICES SHOWN ON THE PLANS ARE APPROXIMATE AND SHALL BE FIELD VERIFIED. 2 15 FCU-2 L1A9 5 J 13 22 14 L1A15 - 7 J SCV3-007 2 L1A9 - 11 J 2 L1A9 - 5 8 L1A9 - 8 L1A10 - 5 L1A15 - 19 L1A9 - 4 MAE COMPUTER LAB 006 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com C. J 7 L1A9 - 2 L1A9 - 7 2 11 5 L1A15 - 10 L1A10 - 1 1 14 19 L1A15 - 510 7 T 2 3 FCU-1 M1A - 5 2 SCV3-001 1 3 8 7 2 1 MAE COMPUTER SUPPORT 010 3 7 11 2 5 TYP. 5 L1A- 1 1 TYP. 8 2 3 1 15 15 15 G L1A11 - 1 5 3 L1A10 5 L1A11 - 16,18,20 10 8 G 5 7 3 2 L1A11 - 5 L1A11 - 8 3 L1A11 - 3,6 2 G L1A11 - 12 L1A11 - 15 L1A11 - 9,11 G 12 IT WILL BE THE CONTRACTOR’S OBLIGATION TO INCLUDE, IN THEIR BID, THE COSTS FOR INSTALLING JUNCTION BOXES, PROVIDING MISCELLANEOUS COVERS, WORK WITH OTHER DISCIPLINES WHERE THE CONTRACT INVOLVES ELECTRICAL POWER OR CONTROL CONNECTIONS, SWITCHES, ETC. ALL OF THIS WORK SHALL BE PART OF THIS CONTRACT. L1A8 - 2 J L1A11 - 2 THERMAL SCIENCE LAB 016 6 G 2 15 G 12 L1A11 - 7 15 G G 14 B. EE R T J L1A11 - 10 FINAL ROUTING LOCATION OF NEW UNDERGROUND CABLE TO BE FIELD VERIFY BY CONTRACTOR PRIOR TO COMMENCING ANY WORK 14 14 14 L1A11 - 4 AFTER THE CONTRACTOR HAS RECEIVED APPROVED SHOP DRAWINGS FOR THE ELECTRICAL DISTRIBUTION EQUIPMENT, THEY SHALL SUBMIT SCALED LAYOUTS OF ALL ELECTRICAL EQUIPMENT TO THE ENGINEER FOR APPROVAL TO ENSURE THAT ALL CLEARANCE REQUIREMENTS ARE MET. THIS SUBMITTAL SHALL BE PROVIDED WITH SUFFICIENT TIME SO AS NOT TO INTERFERE WITH THE TIMELY EXECUTION OF THE ROUGH-IN WORK THAT WILL BE REQUIRED. GFCI RECEPTACLES WILL BE INSTALLED AT ALL LOCATIONS AS REQUIRED BY THE LATEST VERSION OF NEC, STATE AND LOCAL CODES. SOME LOCATIONS WILL BE WITHIN 6'-0" OF SINKS, EXTERIOR DOORS AND WET LOCATIONS. ALL EXTERIOR RECEPTACLES LOCATIONS WILL BE GFCI RATED AND WEATHERPROOF. GI N 14 CONTRACTOR SHALL MAKE AS-BUILT DRAWINGS DOCUMENTING ANY AND ALL WIRING AND EQUIPMENT CONDITIONS AND CHANGES WHILE COMPLETING THIS CONTRACT. PROVIDE UPDATED TYPEWRITTEN DIRECTORIES FOR ALL PANELS AND LABEL ALL PANELS WITH PLASTIC LAMINATED NAMEPLATES. A. JO 22 L1A11 - 13 L. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH ALL TRADES FOR THE EXACT LOCATION OF EQUIPMENT AND APPURTENANCES THAT REQUIRE ELECTRICAL CONNECTIONS AND PROVIDE ALIGNMENT OF DEVICES. EN 2 CO 1 Construction Documents B E-301 EXISTING 4"Ø CONDUIT TO BUILDING ECI & ECII. ELECTRICAL ROOM E001 4 3 M1BM - 20,22,24 1 P5-210 (J-BOX) 9/15/2015 7:22:01 PM D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 1 4 . T1E T1C VFD-2 8 VFD-3 8 23 ACU-4 M1BM - 13,15,17 M1BM - 19,21,23 L1BM 4 J J E-301 J 12 B1B J 21 EXIST. TRANSFORMER L1BM - 7 ELECT 266E EXIST. S5-180 EXISTING DISCONNECT EXISTING CONDUIT TO S5-170 IN KNOX VAULT 1 2 7 23 1 L1BM- 1 L1BM- 9,11 L1BM- 8,10 M1BM - 14,16,18 VFD-5 8 VFD-6 8 KEY PLAN M1BM - 2,4,6 SF-1 MECHANICAL ROOM M003 PCP-2 7 VESTIBULE H001 M1BM - 7,9,11 1 EP-103A T CIRCUITS FOR GENERAL POWER WITHIN DASHED AREA ARE FED FROM PANEL 'L1BM' UNLESS NOTED OTHERWISE 4"Ø CONDUIT TO BUILDING ECI & ECII TO REMAIN ACU-3 8 VFD-4 HDB1B 4 A 8 UP TO LDB1B M1BM 3 VFD-1 M1BM - 8,10,12 3 7 7 M1BM - 31,33,35 T 24 EXISTING CONDUIT TO NEW BAY#3 IN COLLEGE SUBSTATION 1 M1BM - 37,39,41 VFD-16 3 L1BM - 6 VFD-19 VFD-18 VFD-17 A 24 PLAN - TUNNEL A3 POWER Scale: 1/8" = 1'-0" Project North PLAN - BASEMENT MECHANICAL A5 POWER Scale: 1/8" = 1'-0" 0' 4' 8' 0' 16' Description September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © Project North - Level 1 (Annotated) - Callout 2 1 POWER Scale: 1/4" = 1'-0" Revision 1 Date Date 18 J Date 1 Mark M1BM - 38,40,42 HRP-2 L1BM - 2 GFP-1 VFD-15 EXISTING CONDUIT TO S5-210 LOCATED IN THOMAS BROWN VAULT M1BM - 25,27,29 M1BM - 32,34,36 M1BM - 26,28,30 VAN H. GILBERT ARCHITECT PC SHEET TITLE POWER PLAN BASEMENT 4' 8' 16' EP-103A 1 2 3 4 5 6 SHEET 153 OF 187 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES DN 9 MOUNT ON EXISTING RAIL E DN J A2 / EP-103B L1A - 5 10 14 30 30 15 14 38 15 30 MAE OFFICE 108 42 LOCATION OF EQUIPMENT AND OTHER DEVICES SHOWN ON THE PLANS ARE APPROXIMATE AND SHALL BE FIELD VERIFIED. D. THE CONDUIT RUNS, AS SHOWN ON PLANS, INDICATE APPROXIMATE ROUTING. EXACT LOCATION OF CONDUIT RUNS SHALL BE AS FIELD CONDITIONS DICTATE. E. CONTRACTOR SHALL INSTALL PULL AND JUNCTION BOXES WHEREVER REQUIRED BY N.E.C. OR JOB CONDITIONS. ALL NEW WIRING SHALL BE TAGGED AT ALL PULL BOXES, JUNCTION BOXES, EQUIPMENT BOXES AND CABINETS WITH APPROVED PLASTIC TAGS. ACTION CRAFT, BRADY OR APPROVED EQUAL. F. THE CONTRACTOR SHALL INSTALL TIE HANDLES OR MULTI-POLE BREAKERS FOR ALL CIRCUITS SHARING A NEUTRAL CONDUCTOR. G. SHOULD CONTRACTOR AT ANY TIME NOTICE THAT THE ACTUAL FIELD CONDITIONS DO NOT CORRESPOND TO THE INFORMATION GIVEN ON THE DRAWINGS, THEN IT WILL BE THEIR RESPONSIBILITY TO NOTIFY THE ENGINEER FOR CLARIFICATION, PRIOR TO COMMENCING SUCH WORK. H. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH ALL TRADES FOR THE EXACT LOCATION OF EQUIPMENT AND APPURTENANCES THAT REQUIRE ELECTRICAL CONNECTIONS AND PROVIDE ALIGNMENT OF DEVICES. 41 MAIL 104A ? 43 ? 3 TU1-117 42 J. 3 T T M1A- 3 T M1A- 3 14 MAE DIRECTORS OFFICE SUITE 104 49 49 3 TU1-116 I. 49 MAE OFFICE 106 42 35 ? C. TU1-118 41 M1A- 3 T MAE DIRECTORS OFFICE SUITE 104 3 49 39 3 D M1A - 3 10 L. PROVIDE BLANK COVER PLATE FOR ALL EXISTING OUTLETS NOT BEING REUSED, UNLESS THEY ARE COVERED BY WIREMOLD. 21 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 D TU1-122 7 T 7 21 21 L1A - 6 11 29 13 27 29 9 TU1-109 STORAGE S117B 8 G 10 13 STORAGE S117A 13 9 4 13 29 MAE SEMINAR 113 3 COMPUTATIONAL FLOW PHYSICS LAB - I 111 16 TO FIRST FLOOR PLENUM SPACE 23 MAE GRADUATE STUDENT OFFICE 115 9 L1A - 31 15 9 27 1 44 2 34 16 J MAE OFFICE 105 15 TYP. 27 37 36 37 5 L1A - 3 6 WOMEN R151 34 7 8 J 16 33 36 4 18 18 44 37 9 44 34 34 37 16 37 BREAK ROOM 105A 34 3 44 3 CLASSROOM 109 36 5 33 TU1-120 23 6 9 TYP. 29 DNJ 36 33 J J A1 / EP-103C T 27 9 VESTIBULE H117 13 12 M1A- 3 T 33 A1 / EP-103C 9 1 10 11 Project North FIRST FLOOR PLAN - NORTHWEST C2 POWER Scale: 1/8" = 1'-0" 12 13 0' 4' 8' 14 16' 15 16 MOUNT RECEPTACLE ON WOOD RAIL BELOW COUNTER TOP. LOW-VOLTAGE POWER SUPPLY CONNECTION TO AUTOMATIC SENSOR-OPERATED LAVATORY FAUCETS AND FLUSH VALVES. PROVIDE CONCEALED RACEWAYS, BACK BOXES, TRANSFORMER AND HARDWIRED CONNECTIONS TO ALL SENSORS/FAUCETS AS REQUIRED. CRITICAL COORDINATION OF ROUGH-IN REQUIRED PRIOR TO COMMENCING WORK. WIRE ALL COMPONENTS COMPLETE FOR OPERATION. 17 SURGE PROTECTED RECEPTACLES. (1)20A 120V QUADPLEX, (1)30A 120V TWIST LOCK, AND (1)30A 208V TWIST LOCK. COORDINATE MOUNTING LOCATIONS WITH NMSU PRIOR TO COMMENCEMENT OF WORK. MOUNT DEVICE AT 48 FOR VENDING MACHINE, PROVIDE DEDICATED CIRCUIT. REUSE CONDUIT IF APPLICABLE. COMBINATION 120V RECEPTACLE AND USB PORT. HUBBEL #USB20W. DEVICE FOR FIRE SMOKE DAMPER. COORDINATE WITH MECHANICAL PRIOR TO COMMENCEMENT OF ANY WORK. SPLIT SYSTEM UNIT. PROVIDE A THERMAL SWITCH SERVICE DISCONNECT ADJACENT TO UNIT FOR THIS SPLIT SYSTEM. EXTEND POWER CIRCUIT TO CONDENSING UNIT ON ROOF. IRRIGATION CONTROLLER. PROVIDE POWER INDICATED AND COORDINATE WITH ARCHITECTURAL DRAWINGS EXACT LOCATION. 18 C2 / EP-103B 19 20 21 22 F. H E C K ST A TE O NO. 12498 RE 7 T 21 27 TU1-113 T M1A- 3 11 T M1A- 3 TU1-119 HN EW N 3 29 3 3 TU1-111 T M1A- 3 TU1-115 M1A- 3 23 POWER RECEPTACLE TO BE INSTALLED INSIDE PLUMBING CHASE. MOUNT DEVICE AT 48” FOR REFRIGERATOR, PROVIDE DEDICATED CIRCUIT. FOR EACH UNIT, REFER TO SHEET SERIES M-700 AND P-7OO FOR MECHANICAL EQUIP CHARACTERISTICS. REFER TO SHEET E-708 FOR ELECTRICAL CONNECTIONS AND ADDITIONAL INFORMATION. NEW RACEWAY PATH FROM WEST AREA TO NORTHWEST AREA FOR COMMUNICATIONS AND FIRE ALARM. NEW RACEWAY PATH FROM ELECTRICAL ROOM TO BASEMENT LEVEL. REFER TO ONE LINE DIAGRAM FOR ADDITIONA INFORMATION. POSSIBLE ROUTING OF CONDUIT FROM ELECTRICAL ROOM-E127 TO BASEMENT PLENUM SPACE THROUGH NEW CHASE. CONTRACTOR TO COORDINATE FINAL ROUTING OF CONDUIT. RACEWAY AND CONDUCTORS TO PENETRATE WALL INTO WIREMOLD. PROVIDE A GFCI RATED RECEPTACLE IN THE PIT OF THE ELEVATOR NEAR ENTRANCE TO PIT. MOUNT DEVICE 6 in BELOW FIRST FLOOR LEVEL OR AS DIRECTED BY ELECATOR INSTALLER. PROVIDE A METAL END USE COVER. EXTEND CIRCUIT TO LUMINAIRE IN PIT. PROVIDE JUNCTION BOXES FOR PUSH BUTTONS FOR HANDICAP SYSTEM AND FOR CONNECTIONS TO DOOR HARDWARE. PROVIDE 3/4" CONDUIT BETWEEN EACH JUNCTION BOX AND PERMANENT CONDUCTION PER DOOR HARDWARE INSTALLATION INSTRUCTIONS. EXTEND CIRCUIT TO DOOR POWER SUPPLY FOR ACCESS CONTROL SYSTEM. RECEPTACLE FOR FLAT PANEL TELEVISION. MOUNT ADJACENT TO DATA/AV OUTLETS; COORDINATE FINAL MOUNTING HEIGHT AND DETAILS WITH ET SYSTEM INSTALLER. REFER TO AV DRAWINGS FOR MORE INFORMATION. FLOORBOX. PROVIDE A 3/4" CONDUIT BETWEEN EACH DEVICE AND FOR HOMERUN. CIRCUIT INDICATED WILL SERVE ALL DEVICES IN FLOORBOX. COORDINATE WITH ARCHITECT AND FURNITURE INSTALLER. POWER FOR DOOR ACCESS CONTROL SYSTEM. TERMINATE AT J-BOX ABOVE CEILING. SPLIT SYSTEM UNIT. REFER TI SHEET E-709 FOR ADDITIONAL ELECTRICAL INFORMATION. PROVIDE A THERMAL SWITCH DISCONNECT ADJACENT TO UNIT. RACEWAY AND CONDUCTORS WILL BE EXTENDED TO ASSOCIATED ROOF UNIT FOR THIS SPLIT SYSTEM. REFER TO SHEET SERIES 'M' FOR ADDITIONAL INFORMATION F SUPPORT 117D 37 27 1 2 UNISEX R101 44 IV 9 36 3 1 21 R EG I S T E OFFICE 117C 29 16 11 REFERENCE KEYNOTES 7 D PRO EE R 7 C CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 M EX I F E S S I ONA GI N J LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 EN 9 CONSULTANTS AFTER THE CONTRACTOR HAS RECEIVED APPROVED SHOP DRAWINGS FOR THE ELECTRICAL DISTRIBUTION EQUIPMENT, THEY SHALL SUBMIT SCALED LAYOUTS OF ALL ELECTRICAL EQUIPMENT TO THE ENGINEER FOR APPROVAL TO ENSURE THAT ALL CLEARANCE REQUIREMENTS ARE MET. THIS SUBMITTAL SHALL BE PROVIDED WITH SUFFICIENT TIME SO AS NOT TO INTERFERE WITH THE TIMELY EXECUTION OF THE ROUGH-IN WORK THAT WILL BE REQUIRED. FINAL ROUTING LOCATION OF NEW UNDERGROUND CABLE TO BE FIELD VERIFY BY CONTRACTOR PRIOR TO COMMENCING ANY WORK J E CONTRACTOR SHALL MAKE AS-BUILT DRAWINGS DOCUMENTING ANY AND ALL WIRING AND EQUIPMENT CONDITIONS AND CHANGES WHILE COMPLETING THIS CONTRACT. PROVIDE UPDATED TYPEWRITTEN DIRECTORIES FOR ALL PANELS AND LABEL ALL PANELS WITH PLASTIC LAMINATED NAMEPLATES. K. TU1-121 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com JO 14 35 IT WILL BE THE CONTRACTOR’S OBLIGATION TO INCLUDE, IN THEIR BID, THE COSTS FOR INSTALLING JUNCTION BOXES, PROVIDING MISCELLANEOUS COVERS, WORK WITH OTHER DISCIPLINES WHERE THE CONTRACT INVOLVES ELECTRICAL POWER OR CONTROL CONNECTIONS, SWITCHES, ETC. ALL OF THIS WORK SHALL BE PART OF THIS CONTRACT. 39 39 MAE OFFICE 104B 43 T M1A- 3 TU1-114 M1A- 3 41 3 TU1-112 ? T TYP. 43 MAE OFFICE 110 B. 21 49 42 43 MAE OFFICE 112 32 42 15 38 28 3 T 41 28 TU1-110 32 M1A- 3 39 38 28 32 MAE OFFICE 114 3 CONFERENCE ROOM 116 32 35 35 30 14 GFCI RECEPTACLES WILL BE INSTALLED AT ALL LOCATIONS AS REQUIRED BY THE LATEST VERSION OF NEC, STATE AND LOCAL CODES. SOME LOCATIONS WILL BE WITHIN 6'-0" OF SINKS, EXTERIOR DOORS AND WET LOCATIONS. ALL EXTERIOR RECEPTACLES LOCATIONS WILL BE GFCI RATED AND WEATHERPROOF. 39 CIRCUITS FOR GENERAL POWER WITHIN DASHED AREA ARE FED FROM PANEL 'L1A' UNLESS NOTED OTHERWISE. 32 A. CO 1 L PROJECT New Mexico State University Jett Hall and Jett Annex Renovations and Additions C Construction Documents CIRCUITS FOR GENERAL POWER WITHIN DASHED AREA ARE FED FROM PANEL 'L1B' UNLESS NOTED OTHERWISE B 55 55 12 12 12 CHME OFFICE 150 50 54 51 51 CHME OFFICE 152 51 46 54 47 47 46 50 53 CHME OFFICE 160 50 53 CHME OFFICE 158 CHME OFFICE 156 CHME OFFICE 154 53 39 43 39 CHME OFFICE 164 43 43 CHME OFFICE 162 24 6 M1B-1 T 6 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 32 55 22 54 6 M1B-1 54 46 T 32 32 22 27 42 CHME OFFICE 166 47 T 27 47 26 26 26 4 42 CHME OFFICE 168 31 27 4 39 31 4 31 13 13 3 7 TU2-112 J 3 TU2-115 TU2-113 3 TU2-106 3 M1B-1 CORRIDOR H161 3 3 TU2-111 9 M1B - 2 STOR 157 36 L1B - 20 36 18 7 13 T M1B-2 CHME OFFICE 159A 33 36 JANITOR J155 36 TU2-110 M1B-2 38 T 28 3 TYP. CHME GRADUATE STUDENT COMPUTER CLUSTER 159 40 TU2-108 38 15 3 49 3 9 M1B-2 M1B-2 T 38 TU2-109 30 T CHME OFFICE 159G 59 35 A L1A - 7 J 16 J 38 L1B - 65 33 J CHME OFFICE 159E 38 33 10 48 28 35 49 7 M1B-2 T 9 24 30 19 14 59 J 44 45 33 TU2-103 3 L1A - 17,19 L1B - 15 L1A - 8 DATA ROOM T165 18 59 3 J 13 Mark T 9 L1B - 7 M1B - 1 13 35 44 48 TO FIRST FLOOR PLENUM SPACE 44 48 30 CHME OFFICE 159F 40 40 DN 20 J 20 J 22 J J L1B - 37 J A L1B - 57 13 2 3 0' 4 14400 Drawn By Author Checked By Checker VAN H. GILBERT ARCHITECT PC POWER FIRST FLOOR PLAN - NORTHWEST & NORTHEAST Project North 1 Project Number 13 A4 / EP-103C FIRST FLOOR PLAN - NORTHEAST A2 POWER Scale: 1/8" = 1'-0" September 11, 2015 SHEET TITLE J A4 / EP-103C Description Copyright © 20 J Date Date ENTRY H172 17 L1B - 5 9 TU2-104 T 9 CHME OFFICE 159B J CHME OFFICE CHME OFFICE 159C 159D 13 KEY PLAN 59 9 28 45 CHME OFFICE 163 59 T L1A - 12 MEN R153 3 3 TU2-107 13 13 45 49 TU2-105 T 7 T J TU2-114 45 9/15/2015 7:22:08 PM M1B-1 46 T 22 B 4 39 42 M1B-1 55 42 4' 5 8' 16' EP-103B 6 SHEET 154 OF 187 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES H. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH ALL TRADES FOR THE EXACT LOCATION OF EQUIPMENT AND APPURTENANCES THAT REQUIRE ELECTRICAL CONNECTIONS AND PROVIDE ALIGNMENT OF DEVICES. I. CONTRACTOR SHALL MAKE AS-BUILT DRAWINGS DOCUMENTING ANY AND ALL WIRING AND EQUIPMENT CONDITIONS AND CHANGES WHILE COMPLETING THIS CONTRACT. PROVIDE UPDATED TYPEWRITTEN DIRECTORIES FOR ALL PANELS AND LABEL ALL PANELS WITH PLASTIC LAMINATED NAMEPLATES. AFTER THE CONTRACTOR HAS RECEIVED APPROVED SHOP DRAWINGS FOR THE ELECTRICAL DISTRIBUTION EQUIPMENT, THEY SHALL SUBMIT SCALED LAYOUTS OF ALL ELECTRICAL EQUIPMENT TO THE ENGINEER FOR APPROVAL TO ENSURE THAT ALL CLEARANCE REQUIREMENTS ARE MET. THIS SUBMITTAL SHALL BE PROVIDED WITH SUFFICIENT TIME SO AS NOT TO INTERFERE WITH THE TIMELY EXECUTION OF THE ROUGH-IN WORK THAT WILL BE REQUIRED. FINAL ROUTING LOCATION OF NEW UNDERGROUND CABLE TO BE FIELD VERIFY BY CONTRACTOR PRIOR TO COMMENCING ANY WORK. K. 3 6 E-301 5 E-301 TYP. 30 L1C1 - 21 6 19 19 TU1-107 30 4 M1A - 1 16 T 30 4 9 18 MAE OFFICE 130 7 L1C1- 33 4 35 26 10 9 L1AA- 1 T 16 26 CORRIDOR H102 14 J 27 10 29 27 25 6 18 24 M1A-16 T TU1-105 5 29 10 MAE COMPUTER (GRADUATE) LAB 137 14 C 25 14 4 M1A-16 6 15 22 6 6 T SCV3-107 33 4 32 L1A1 - 5 5 24 G L1A - 26 WOMEN R140 8 J TYP. J T L1A3 - 9 6 J SCV3-106 L1AA- 1 J G 24 J 6 7 1 20/1 9 COMPOSITES LAB 3 2 TYP. L1A7 - 12 2 L1A7 - 4 13 13 25 5 J J J J L1A7 - 13 4 L1A7 - 11 L1A7 - 5 5 1 8 12 6 J 9 9 1 21 J G G 2 G SCV3-104 L1A5 - 2 9 TYP. L1A4 - 7 23 G TYP. VESTIBULE H149 28 20 35 G 5 17 M1A-16 T CIRCUITS FOR WITHIN DASHED AREA ARE FED FROM PANEL 'L1C2' UNLESS NOTED OTHERWISE L1B5 - 1,30 G 2 J 13 G 6 5 TU1-101 L1A6 - 6 3 6 L1A6 - 3 T M1A-16 L1AA - 3 L1C2 - 12 J 27 15 J 15 J J J 30 29 29 30 5 6 8 L1B4 - 11 16 6 15 6 25 26 27 28 38 17 38 29 L1B5 - 13 15 38 23 L1B5 - 5 30 35 9 31 L1B5 - 8,10 35 L1B5 - 35,38 34 32 L1B5 - 34 20 5 L1B5 - 31,33 21 5 J 33 J 31 18 30 CHME UNDERGRADUATE LAB 193 L1C2 - 24 L1B5 - 42,44,46 33 23 L1B5 - 9,11 35 22 30 22 L1B5 - 27 31 L1C2 - 30 15 28 MAE OFFICE 194A 33 <unnamed> 33 27 32 33 36 27 31 L1C2 - 46,48,50 20 L1B5 - 3 REUSE MAIN CONTROL PANEL 20 23 L1B5 - 4,6 30/1 9 16 39 25 34 31 25 L1C2 - 52,54,56 PUSH BUTTON ACTUATOR FOR MOTORIZED DOOR OPERATOR(S). COORDINATE ROUGH-IN AND WIRING REQUIREMENTS WITH DOOR INSTALLER. WIRE ALL DEVICES COMPLETE FOR OPERATION. REFER TO DETAIL A4 ON SHEET E-501. COMBINATION 120V RECEPTACLE AND USB PORT. HUBBEL #USB20W. FIELD COORDINATE PANELBOARD LOCATION WITH FIBER OPTIC LINES. SURGE PROTECTED RECEPTACLES. (1)20A 120V QUADPLEX, (1)30A 120V TWIST LOCK, AND (1)30A 208V TWIST LOCK. COORDINATE MOUNTING LOCATIONS WITH NMSU PRIOR TO COMMENCEMENT OF WORK. REROUTE ALL CIRCUITS CONNECTED TO EXISTING PANELBOARD 171 AND CONNECT TO NEW PANELBOARD L1B5. NEMA CONFIGURATION RECEPTACLE TO MATCH NEMA CONFIGURATION OF EQUIPMENT PLUG. REFERECE SHEET E-801 FOR ADDITION INFORMATION ON ELECTRICAL CONNECTIONS FOR LAB EQUIPMENT. CONTRACTOR TO FIELD VERIFY BEFORE COMMENCING ANY WORK. NEMA CONFIGURATION RECEPTACLE TO MATCH NEMA CONFIGURATION OF EQUIPMENT PLUG. PROVIDE 4#6 & 1#10 GROUND IN 3/4" CONDUIT OR IN 5400 MULTI-OULET ASSEMBLY. PROVIDE NEW CONTROL PANEL FOR EXISTING LABORATORY EQUIPMENT. PROVIDE NEW SERVICE DISCONNECT IN SAME LOCATION WHERE OLD DISCONNECT WAS LOCATED. NEMA CONFIGURATION AND SIZE SHOULD MATCH EXISTING DISCONNECT ELECTRICAL CHARACTERISTICS. CONTRACTOR TO FIELD VERIFY BEFORE COMMENCING ANY WORK. PROVIDE NEW 480V VFD RATED FOR 25 HP. COORDINATE WITH MANUFACTURERS REQUIREMENTS PRIOR TO COMMENCEMENT OF ANY WORK. PROVIDE JUNCTION BOX WITH DEDICATED CIRCUIT FOR DRINKING FOUNTAIN. COORDINATE WITH MANUFACTURERS REQUIREMENTS PRIOR TO COMMENCEMENT OF ANY WORK. CONTRACTOR TO PROVIDE POWER FROM VFD TO MECHANICAL EQUIPMENT. TERMINATE PER MANUFACTURERS DIRECTIONS. REUSE EXISTING .5 KVA, SINGLE PHASE BOOST TRANSFORMER. TRANSFORMER TO BE MOUNTED TO WALL. COORDINATE WITH MANUFACTURERS REQUIREMENTS PRIOR TO COMMENCEMENT OF ANY WORK. PROGRAMMABLE TIME CLOCK WITH ROOF MOUNTED PHOTOCELL FOR CONTROL OF EXTERIOR BUILDING LUMINAIRES. PROVIDE A FOUR POLE CONTACTOR. REFER TO SHEET E-604 FOR ADDITIONAL INFORMATION. PROGRAMMABLE TIME CLOCK FOR CONTROL OF HALLWAY AND STAIR LUMINAIRES. PROVIDE A FOUR POLE CONTACTOR. REFER TO SHEET E-604 FOR SEQUENCES OF OPERATION AND ADDITIONAL INFORMATION. DEVICE FOR FIRE SMOKE DAMPER. COORDINATE WITH MECHANICAL PRIOR TO COMMENCEMENT OF ANY WORK. SPLIT SYSTEM UNIT. PROVIDE A THERMAL SWITCH SERVICE DISCONNECT ADJACENT TO UNIT FOR THIS SPLIT SYSTEM. EXTEND POWER CIRCUIT TO CONDENSING UNIT ON ROOF. L1B4 - 23,25,27 30 37 L1B5 - 20 24 7 9 37 23 36 39 J A3 / EP-103A 25 J 39 25 40 J L1B5 - 18 37 L1B5 - 12,22 40 G 19 T 29 J 39 2 L1B5 - 40 J L1B5 - 16,28 L1B5 - 55,57,59 28 L1B5 - 54,56,58 L1B5 - 25,39 30 38 23 40 23 L1B5 - 43,45,47 L1C2 - 53,55,57 J 40 36 L1B5 - 36 TYP. 37 L1B5 - 26 26 26 41 L1B5 - 23 G J 39 22 J 12 22 23 HN F. H E C K ST A TE O NO. 12498 D EW PRO M EX I F E S S I ONA L PROJECT New Mexico State University Jett Hall and Jett Annex Renovations and Additions C Construction Documents FLOORBOX. PROVIDE A 3/4" CONDUIT BETWEEN EACH DEVICE AND FOR HOMERUN. CIRCUIT INDICATED WILL SERVE ALL DEVICES IN FLOORBOX. COORDINATE WITH ARCHITECT AND FURNITURE INSTALLER. NEMA CONFIGURATION RECEPTACLE TO MATCH NEMA CONFIGURATION OF EQUIPMENT PLUG. PROVIDE 4#10 & 1#10 GROUND IN 3/4" CONDUIT OR IN 5400 MULTI-OULET ASSEMBLY. LOW-VOLTAGE POWER SUPPLY CONNECTION TO AUTOMATIC SENSOR-OPERATED LAVATORY FAUCETS AND FLUSH VALVES. PROVIDE CONCEALED RACEWAYS, BACK BOXES, TRANSFORMER AND HARDWIRED CONNECTIONS TO ALL SENSORS/FAUCETS AS REQUIRED. CRITICAL COORDINATION OF ROUGH-IN REQUIRED PRIOR TO COMMENCING WORK. WIRE ALL COMPONENTS COMPLETE FOR OPERATION. L1B4 - 1 L1B4 - 10 L1B5 22 B KEY PLAN 1 Date 1 Mark Revision 1 Date Description Date A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC SHEET TITLE 2 UP 9/15/2015 7:22:17 PM 30 16 J 17 14 22 27 J A3 / EP-103A Project North Project North FIRST FLOOR PLAN - WEST WING A1 POWER Scale: 1/8" = 1'-0" 0' 1 8 D EXTEND NEW CIRCUIT TO NEW SERVICE DISCONNECT. CONDUCTORS AND RACEWAY FROM EXISTING DISCONNECT TO UNIT TO REMAIN AS PRESENTLY INSTALLED. MOUNT RECEPTACLE ON WOOD RAIL BELOW COUNTER TOP. LIGHTING BATTERY INVERTER FOR EMERGENCY LIGHTING FOR ANNEX AREA. LIGHTING BATTERY INVERTER SYSTEM EQUIPMENT WILL BE FOR EGRESS EMERGENCY LIGHTING. INVERTER WILL OPERATE IN THE EVENT OF AN EMERGENCY. BATTERY INVERTER WILL BE RATED FOR 1500 VA. REFER TO TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM ON SHEET E-604. 20 21 9 L1AA - 9 15 30 12 24 TYP. 20 J 7 L1C2 - 27 33 L1AA - 8 L1AA - 2 17 4 L1B5 - 7 24 17 J 5 L1A6 - 1 2 MAE CAPSTONE PROJECTS - II L1A6 - 9 148 J 9 1 9 1 L1B4 - 4 L1B4 - 14,17 L1B5 - 37 L1B5 - 32 11 AERO FLUIDS LAB 194 31 GRADUATE STUDENT OFFICE 149B 19 18 15 30 3 30 14 7 J L1A6 - 2 1 L1B4 - 2 4 L1B4 - 22,24,26 J 20 17 L1B3 - 3 J L1B5 - 32 6 G 18 8 L1B5 - 2 16 SCV2-107B L1B5 - 14 L1B5 - 15,17,19 TYP. L1B- 1 T L1B5 - 49,51,53 L1B1 T 23 SCV2-107A L1B5 - 21 7 L1B5 - 24 12 L1C2 - 9 30 J 9 6 RECEPTACLE FOR FLAT PANEL TELEVISION. MOUNT ADJACENT TO DATA/AV OUTLETS; COORDINATE FINAL MOUNTING HEIGHT AND DETAILS WITH ET SYSTEM INSTALLER. REFER TO AV DRAWINGS FOR MORE INFORMATION. PROVIDE NEW SERVICE DISCONNECT IN SAME LOCATION WHERE OLD DISCONNECT WAS LOCATED. NEMA CONFIGURATION AND SIZE SHOULD MATCH EXISTING DISCONNECT ELECTRICAL CHARACTERISTICS.REFERECE SHEET E-801 FOR ADDITION INFORMATION ON ELECTRICAL CONNECTIONS FOR LAB EQUIPMENT. CONTRACTOR TO FIELD VERIFY BEFORE COMMENCING ANY WORK. J 3 L1C2 - 47,49,51 7 6 4 G TYP. G L1A6 L1A6 - 5 14 20 3 4 L1B4 - 15 L1B4 - 16 L1B- 1 T L1B4 - 28,30,32 2 29 34 J TYP. 13 L1C2 - 58,60,62 L1C2 - 37 3 17 8 30 9 18 13 L1B3 - 2 REDUCED GRAVITY LAB 191C MAE ROBOTICS LAB 191B 1 23 TYP. 1 24 FLOW 20 24 COMPUTATIONAL PHYSICS LAB - II TU1-102 149A 23 L1C2 - 4 L1B3 - 9,11,13 6 12 L1C2 - 6,8 L1C2 - 59,61,63 2 4 L1B- 1 J 5 L1B4 - 9 13 26 L1C2 - 5 16 10 21 5 L1B- 1 SCV2-105 L1B4 - 13 L1C2 - 3 L1A5 - 1 L1A5 - 4 MAE MATERIALS LAB 147 L1A5 - 6 4 30 36 15 9 J J L1B4 12 7 L1C2 - 41,43,45 L1C2 - 40,42,44 13 L1B4 - 19 L1B4 - 12 L1C2 - 38 34 2 L1B3 - 7 MAE LAB 191 L1C2 - 7 23 14 SCV2-106 J M1C - 13,15,17 7 7 ? G SK4 5 19 J 19 26 L1B3 - 1 SCV2-103 14 1 13 SCV2-104 L1B4 - 7 L1B4 - 5 18 21 7 14 L1A5 - 5 L1A5 5 M1C - 8,10,12 29 L1B3 - 5 SCV2-102 L1B4 - 21 21 TYP. 3 3 ACU-9 G M1A - 14,16,18 3 7 12 13 2 L1B3 - 14 21 9 20 MAE OFFICE 191A L1C2 - 26 29 4 1 9 L1AA- 1 L1A5 - 3 T 2 1 G T 13 L1A6 - 7 L1AA- 1 SCV3-101 4 L1A6 - 4 7 2 8 L1A7 - 8 10 17 L1AA1 T J L1A7 - 9 SCV3-102 MAE LAB L1A7 - 10 146 11 11 16 J J 4 J L1A6 - 8 7 2 5 7 7 L1A4 - 9 L1A4 - 2 L1A4 - 5 9 L1A4 - 4 TYP. 5 4 32 J 13 J J L1C2 - 16 3 L1A4 - 8 11 20 29 29 L1B- 1 J 5 L1B4 - 3 AHU-5 L1A4 - 3 L1A4 - 6 T L1A4 5 2 G 12 1 G L1A7 - 1 3 2 SCV3-105 144 36 J 23 J 28 13 7 18 3 L1C2 - 29 32 TYP. 14 T L1B- 1 1 20 11 23 L1AA- 1 L1A7 30/1 23 L1A7 - 6 B 34 L1C2 LDB1C 33 3 J J J 2 L1C2 - 32 11 9 5 13 L1B4 - 18 L1C2 - 2 34 35 ELECTRICAL T E194B 33 L1AA- 32 1 3 MAE CAPSTONE PROJECTS - I 145 T L1AA- 1 36 J 11 8 5 9 J 21 10 BREAKROOM 179 23 G 3 14 11 9 L1B3 - 4 L1B4 - 20 41 MAE OFFICE 196A 41 41 CHME MINATURE CHEMICAL PILOT PLANT 184 L1B3 35 41 36 3 3 J 4 5 SCV3-103 7 L1A7 - 7 5 35 8 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 EXISTING EXHAUST FAN TO BE RECONNECTED TO CIRCUIT INDICATED. CONTROL OF EXISTING FAN AND SWITCH WILL REMAIN AND RECONNECTED. FLUSH MOUNTED POWER OUTLETS IN MULTI-OUTLET ASSEMBLY. REFER TO DETAIL 8 ON SHEET E-501 FOR ADDITIONAL INFORMATION. MULTI-OUTLET ASSEMBLY TO BE MOUNTED BELOW COUNTERTOP. REFER TO DETAIL 8 ON SHEET E-501 FOR ADDITIONAL INFORMATION. POWER RECEPTACLE FOR CEILING MOUNTED VIDEO PROJECTOR MOUNTED IN PROJECTOR DROP CEILING PLATE. JUNCTION BOX FOR ELECTRIC PROJECTOR SCREEN. REFER TO SHEET SERIES 'T' FOR ADDITIONAL INFORMATION. PROVIDE CONDUCTORS AND RACEWAY FROM PANEL SOURCE UP TO NEW 6" SQUARE JUNCTION BOX MOUNTED IN CEILING SPACE AND DOWN THROUGH WIREMOLD. REFERENCE DETAIL. EXTEND 480V CIRCUIT TO NEW 100A DISCONNECT. CONDUCTORS AND RACEWAY FROM EXISTING CIRCUIT BREAKER TO UNIT TO REMAIN AS PRESENTLY INSTALLED. EXTEND NEW CIRCUIT TO NEW NEC-SIZED JUNCTION BOX. RECONNECT TO EXISTING CONDUCTOR/RACEWAY IN FURNITURE ASSEMBLY. JUNCTION BOX WILL BE MOUNTED ABOVE FUME HOOD. CONTRACTOR TO PROVIDE POWER TO FUME HOOD WHICH INCLUDES LIGHTING AND RECEPTACLES. IN ADDITION, PROVIDE POWER TO HOOD CONTROLLER PROVIDED BY MECHANICAL. COORDINATE WITH MANUFACTURER'S REQUIREMENTS AND SHEET SERIES 'M' PRIOR TO COMMENCEMENT OF WORK. J 58,60,62 5 30 35 36 J H1C M1C M1C - 7,9,11 L1A3 - 4 L1A3 - 5 TYP. L1A3 6 B1C 38 L1A3 - 1 L1C1 - 29 TYP. L1B - 17 G 41 23 12 CIRCUITS FOR WITHIN DASHED AREA ARE FED FROM PANEL 'L1C1' UNLESS NOTED OTHERWISE 6 7 41 23 23 29 9 8 23 2 30 56 TYP. 41 2 4 L1C1 - 2 52 SCV2-101 L1B2 - 6,8,10 L1B3 - 6,8,10 J 41 STORAGE S180 L1B2 MAE WELDING 12 182 L1B- 1 T 8 5 26 25 7 22 L1B2 - 5,7 22 21 100/1 9 15 21 21 20 L1C1 - 13 36 L1A3 - 3 L1A3 - 10 J 23 L1C1 - 67,69,71 9 3 AUTONOMOUS SYSTEMS LAB 141 10 24 24 STORAGE S196B 2 L1A3 - 2 11 15 56 Unoccupied Unoccupied 4 18 STUDENT PROJECTS CENTER 196 L1C1 - 68,70,72 34 L1A3 - 8 12 UNISEX R142 9 4 J 6 L1A3 - 2 9 6 1 L1C2- 1 L1C2- 1 13 7 9 23 25 T1F 13 9 L1AA 2 17 L1C2- 1 28 7 4 F L1C1 - 41 9 34 L1C1 - 32 19 L1C1 - 56,58,60 4 13 J 8 TU1-104 31 13 13 30 MOUNT MULTI-OUTLET ASSEMBLY 6" ABOVE COUNTER TOP BACK SPLASH, TABLE TOP OR SINK. MOUNT DEVICE AT 48” FOR REFRIGERATOR, PROVIDE DEDICATED CIRCUIT. POWER FOR DOOR ACCESS CONTROL SYSTEM. TERMINATE AT J-BOX ABOVE CEILING. FOR EACH UNIT, REFER TO SHEET SERIES M-700 AND P-7OO FOR MECHANICAL EQUIP CHARACTERISTICS. REFER TO SHEET E-708 FOR ELECTRICAL CONNECTIONS AND ADDITIONAL INFORMATION. RACEWAY AND CONDUCTORS TO PENETRATE WALL INTO WIREMOLD. SPLIT SYSTEM UNIT. REFER TI SHEET E-709 FOR ADDITIONAL ELECTRICAL INFORMATION. PROVIDE A THERMAL SWITCH DISCONNECT ADJACENT TO UNIT. RACEWAY AND CONDUCTORS WILL BE EXTENDED TO ASSOCIATED ROOF UNIT FOR THIS SPLIT SYSTEM. REFER TO SHEET SERIES 'M' FOR ADDITIONAL INFORMATION 21 4 T L1B2 - 1 14 2 26 11 2 30 30 L1A1 - 6 J 16 L1C1 - 50,52,54 L1C1 - 12 18 T L1A2 - 11 5 30 30 L1A1 - 4 1 J 4 6 5 6 22 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 5 24 M1A-16 T 15 A 2 TU2-102 3 18 ALTERATIONS ON ME/AE ROBOTICS LAB-191C SHALL BE KEPT AS MINIMUM AS POSSIBLE. WIRE FROM RECEPTACLES SHALL BE INTERCEPTED ON PLENUM SPACE AND ROUTED TO NEW PANEL SOURCE WHEN POSSIBLE. RECEPTACLES ON THIS AREA SHALL BE RE-USE. WIREMOLD SHALL NOT BE INSTALLED IN THIS AREA. 3 52 12 J 34 L1C1 - 16 21 L1C1 - 44,46,48 L1A2 - 9 L1A2 - 4 MDF 7 ACU-10 137A 27 L1A2 - 6 L1A2 - 1 L1A2 - 7 L1A2 L1A2 - 5 L1AA- 32 L1A2 - 13 L1A2 - 2 L1A2 - 8,10 2 TYP. 15 1 L1A2 - 3 9 L1AA- 1 MAE OFFICE 138 34 L1A1 - 3 L1A1 - 2 3 2 T TU1-103 MAE OFFICE 136 25 22 4 J 3 22 L1A1 - 1 TYP. 3 3 2 18 L1C1 - 23,25 L1C1 - 49,51,53 L1C1 - 61,63,65 6 9 10 L1C1 - 62,64,66 15 2 6 L1AA - 12 J 5 L1C1 - 10 L1C1 - 55,57,59 L1A1 - 10 12 MAE OFFICE 134 18 24 26 14 11 12 30 J 7 L1A1 - 8 L1A1 - 9 18 19 30 8 TYP. MECHATRONICS LAB 133 11 MAE OFFICE 132 29 27 8 7 L1A1 - 7 9 L1A1 - 11 11 13 J L1A1 10 L1C1 - 31 AHU-4 L1C1 - 43,45,47 27 14 7 9 TU1-106 5 4 L1C1 - 15,17 L1C1 - 18,20 28 14 TYP. J L1B1 - 3 M1B - 3 CIRCUITS FOR WITHIN DASHED AREA ARE FED FROM PANEL 'L1B' UNLESS NOTED OTHERWISE 22 34 L1B1 - 10 L1C1 - 1 30 M1A-16 T 13 3 TYP. SCV3-108 21 12 1 56 RE 26 11 L1C1 - 6 L1C1 - 3 L1C1 - 22 L1B1 - 12 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 N 27 TYP. TU1-108 10 M1C1 - 4,6,8 52 L1B1 - 2 7 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 F 26 30 9 5 35 9 8 SHOULD CONTRACTOR AT ANY TIME NOTICE THAT THE ACTUAL FIELD CONDITIONS DO NOT CORRESPOND TO THE INFORMATION GIVEN ON THE DRAWINGS, THEN IT WILL BE THEIR RESPONSIBILITY TO NOTIFY THE ENGINEER FOR CLARIFICATION, PRIOR TO COMMENCING SUCH WORK. R EG I S T E 30 19 L1C1- 33 7 G. LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 IV 28 6 19 30 THE CONTRACTOR SHALL INSTALL TIE HANDLES OR MULTI-POLE BREAKERS FOR ALL CIRCUITS SHARING A NEUTRAL CONDUCTOR. CHME COMPUTER LAB L1B1 - 8 ON FIRST FLOOR PLENUM SPACE 18 TYP. J J L1B1 - 9 11 F. CONSULTANTS 34 22 26 L1B1 - 14 L1B1 - 18 30 L1C1 CONTRACTOR SHALL INSTALL PULL AND JUNCTION BOXES WHEREVER REQUIRED BY N.E.C. OR JOB CONDITIONS. ALL NEW WIRING SHALL BE TAGGED AT ALL PULL BOXES, JUNCTION BOXES, EQUIPMENT BOXESAND CABINETS WITH APPROVED PLASTIC TAGS. ACTION CRAFT, BRADY OR APPROVED EQUAL. E REFERENCE KEYNOTES 56 4 L1C1 - 8 20 MSB L1C1 - 7 20 E. T M1B- 3 J L1B1 - 1 J L1C1 - 5 30 30 MAE STUDENT LOUNGE 125 7 T L1C1 - 42 L1C1 - 36 L1C1 - 37 7 7 MAE OFFICE 128 L1B1 - 6 177 7 E-301 MECHANICAL ROOM M198 DN J 31 31 MAE OFFICE 126 31 TO FIRST FLOOR PLENUM SPACE 9 5 21 J MAE OFFICE 124 13 THE CONDUIT RUNS, AS SHOWN ON PLANS, INDICATE APPROXIMATE ROUTING. EXACT LOCATION OF CONDUIT RUNS SHALL BE AS FIELD CONDITIONS DICTATE. 26 TYP. 52 J 22 L1B1 - 11 39 ELECTRICAL ROOM E167 J 21 13 D. 25 TU2-101 L1B1 - 13 E-301 19 M1A-16 16 T1D 4 LOCATION OF EQUIPMENT AND OTHER DEVICES SHOWN ON THE PLANS ARE APPROXIMATE AND SHALL BE FIELD VERIFIED. 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com 34 L1B1 - 5 L1B1 - 17 LDB1B H1B 38 5 28 L1B1 - 15 L1B- 16 MECHANICAL M123 25 L1B1 7 L1B J DN 11 M1B C. A2 / EP-103B J ELECTRICAL ROOM E127 6 28 41 J VESTIBULE H122 D 5 J L1B - 61,63 UP 31 ACU-5 J STORAGE S120 4 23 E-301 A2 / EP-103B J C2 / EP-103B J C2 / EP-103B IT WILL BE THE CONTRACTOR’S OBLIGATION TO INCLUDE, IN THEIR BID, THE COSTS FOR INSTALLING JUNCTION BOXES, PROVIDING MISCELLANEOUS COVERS, WORK WITH OTHER DISCIPLINES WHERE THE CONTRACT INVOLVES ELECTRICAL POWER OR CONTROL CONNECTIONS, SWITCHES, ETC. ALL OF THIS WORK SHALL BE PART OF THIS CONTRACT. SQUARE NOTES REPRESENT APPROXIMATE EQUIPMENT LAY-OUT. REFERENCE SHEET E-801 FOR ADDITIONAL INFORMATION FOR THAT EQUIPMENT. CONTRACTOR TO COORDINATE FINAL EQUIPMENT LOCATION. L. CIRCUITS FOR GENERAL POWER WITHIN DASHED AREA ARE FED FROM PANEL 'L1AA' UNLESS NOTED OTHERWISE. B. EE R E GFCI RECEPTACLES WILL BE INSTALLED AT ALL LOCATIONS AS REQUIRED BY THE LATEST VERSION OD NEC, STATE AND LOCAL CODES. SOME LOCATIONS WILL BE WITHIN 6'-0" OF SINKS, EXTERIOR DOORS AND WET LOCATIONS. ALL EXTERIOR RECEPTACLES LOCATIONS WILL BE GFCI RATED AND WEATHERPROOF. JO J. A. GI N 3 EN 2 CO 1 8' 16' 2 0' 3 33 60/1 33 30 DN 4' 8' 0' 16' 4 POWER FIRST FLOOR PLAN - ANNEX, EAST & WEST WING 33 30/3R Project North FIRST FLOOR PLAN - EAST WING A4 POWER Scale: 1/8" = 1'-0" FIRST FLOOR PLAN - ANNEX A2 POWER Scale: 1/8" = 1'-0" 4' 60/1 L1B5 - 48,50,52 5 4' 8' EP-103C 16' 6 SHEET 155 OF 187 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES A. GFCI RECEPTACLES WILL BE INSTALLED AT ALL LOCATIONS AS REQUIRED BY THE LATEST VERSION OD NEC, STATE AND LOCAL CODES. SOME LOCATIONS WILL BE WITHIN 6'-0" OF SINKS, EXTERIOR DOORS AND WET LOCATIONS. ALL EXTERIOR RECEPTACLES LOCATIONS WILL BE GFCI RATED AND WEATHERPROOF. B. IT WILL BE THE CONTRACTOR’S OBLIGATION TO INCLUDE, IN THEIR BID, THE COSTS FOR INSTALLING JUNCTION BOXES, PROVIDING MISCELLANEOUS COVERS, WORK WITH OTHER DISCIPLINES WHERE THE CONTRACT INVOLVES ELECTRICAL POWER OR CONTROL CONNECTIONS, SWITCHES, ETC. ALL OF THIS WORK SHALL BE PART OF THIS CONTRACT. C. LOCATION OF EQUIPMENT AND OTHER DEVICES SHOWN ON THE PLANS ARE APPROXIMATE AND SHALL BE FIELD VERIFIED. D. THE CONDUIT RUNS, AS SHOWN ON PLANS, INDICATE APPROXIMATE ROUTING. EXACT LOCATION OF CONDUIT RUNS SHALL BE AS FIELD CONDITIONS DICTATE. E. CONTRACTOR SHALL INSTALL PULL AND JUNCTION BOXES WHEREVER REQUIRED BY N.E.C. OR JOB CONDITIONS. ALL NEW WIRING SHALL BE TAGGED AT ALL PULL BOXES, JUNCTION BOXES, EQUIPMENT BOXESAND CABINETS WITH APPROVED PLASTIC TAGS. ACTION CRAFT, BRADY OR APPROVED EQUAL. F. THE CONTRACTOR SHALL INSTALL TIE HANDLES OR MULTI-POLE BREAKERS FOR ALL CIRCUITS SHARING A NEUTRAL CONDUCTOR. G. SHOULD CONTRACTOR AT ANY TIME NOTICE THAT THE ACTUAL FIELD CONDITIONS DO NOT CORRESPOND TO THE INFORMATION GIVEN ON THE DRAWINGS, THEN IT WILL BE THEIR RESPONSIBILITY TO NOTIFY THE ENGINEER FOR CLARIFICATION, PRIOR TO COMMENCING SUCH WORK. H. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH ALL TRADES FOR THE EXACT LOCATION OF EQUIPMENT AND APPURTENANCES THAT REQUIRE ELECTRICAL CONNECTIONS AND PROVIDE ALIGNMENT OF DEVICES. E CIRCUITS FOR GENERAL POWER WITHIN DASHED AREA ARE FED FROM PANEL 'L2A' UNLESS NOTED OTHERWISE 23 16 16 21 19 21 19 24 24 19 23 23 CLASSROOM 208 CLASSROOM 210 23 M2A- 27 M2A- 27 CLASSROOM 206 TU1-215 21 7 M2A- 27 M2A- 27 TU1-211 7 M2A- 27 21 7 TU1-217 TU1-213 7 23 7 TU1-218 21 19 REFERENCE KEYNOTES D TU1-219 3 1 3 7 M2A- 27 ACU-13 24 18 2 2 M2A- 27 8 8 DATA T203 2 5 18 14 18 2 8 J 4 1 14 9 9 A1 / EP-103E 7 8 4 TO SECOND FLOOR PLENUM SPACE STORAGE S217B 4 STORAGE S207A 9 WOMEN R201 7 7 4 D G A TE O EW PRO M EX I F E S S I ONA L New Mexico State University 8 A1 / EP-103E SECOND FLOOR PLAN - NORTHWEST C2 POWER Scale: 1/8" = 1'-0" ST PROJECT Jett Hall and Jett Annex Renovations and Additions Project North C F. H E C K NO. 12498 RE 18 J 6 PROVIDE NEW RECEPTACLES IN MULTI OULET RACEWAY FOR CONNECTIONS OF EXISTING LAB EQUIPMENT AS SHOWN. DEVICE FOR FIRE SMOKE DAMPER. COORDINATE WITH MECHANICAL PRIOR TO COMMENCEMENT OF ANY WORK. FOR EACH UNIT, REFER TO SHEET SERIES M-700 AND P-7OO FOR MECHANICAL EQUIP CHARACTERISTICS. REFER TO SHEET E-708 FOR ELECTRICAL CONNECTIONS AND ADDITIONAL INFORMATION. SPLIT SYSTEM UNIT. PROVIDE A THERMAL SWITCH SERVICE DISCONNECT ADJACENT TO UNIT FOR THIS SPLIT SYSTEM. EXTEND POWER CIRCUIT TO CONDENSING UNIT ON ROOF. HN N 4 L2A - 5 7 14 9 7 8 JANITOR 201A CLASSROOM 213 2 18 4 CLASSROOM 207 G R EG I S T E M2A- 27 M2A- 27 7 TU1-216 M2A- 27 TU1-210 7 6 2 3 4 F 7 TU1-214 TU1-212 CLASSROOM 215 4 7 8 7 9 7 18 VESTIBULE H217 14 14 14 8 MOUNT MULTI-OUTLET ASSEMBLY 6" ABOVE COUNTER TOP BACK SPLASH, TABLE TOP OR SINK. POWER RECEPTACLE TO BE INSTALLED INSIDE PLUMBING CHASE. RACEWAY AND CONDUCTORS TO PENETRATE WALL INTO WIREMOLD. LOW-VOLTAGE POWER SUPPLY CONNECTION TO AUTOMATIC SENSOR-OPERATED LAVATORY FAUCETS AND FLUSH VALVES. PROVIDE CONCEALED RACEWAYS, BACK BOXES, TRANSFORMER AND HARDWIRED CONNECTIONS TO ALL SENSORS/FAUCETS AS REQUIRED. CRITICAL COORDINATION OF ROUGH-IN REQUIRED PRIOR TO COMMENCING WORK. WIRE ALL COMPONENTS COMPLETE FOR OPERATION. IV MAE OFFICE 217A 24 9 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 FINAL ROUTING LOCATION OF NEW UNDERGROUND CABLE TO BE FIELD VERIFY BY CONTRACTOR PRIOR TO COMMENCING ANY WORK K. 7 24 3 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 21 24 16 D CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 AFTER THE CONTRACTOR HAS RECEIVED APPROVED SHOP DRAWINGS FOR THE ELECTRICAL DISTRIBUTION EQUIPMENT, THEY SHALL SUBMIT SCALED LAYOUTS OF ALL ELECTRICAL EQUIPMENT TO THE ENGINEER FOR APPROVAL TO ENSURE THAT ALL CLEARANCE REQUIREMENTS ARE MET. THIS SUBMITTAL SHALL BE PROVIDED WITH SUFFICIENT TIME SO AS NOT TO INTERFERE WITH THE TIMELY EXECUTION OF THE ROUGH-IN WORK THAT WILL BE REQUIRED. J. CLASSROOM 216 16 MAE OFFICE 204 19 LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CONTRACTOR SHALL MAKE AS-BUILT DRAWINGS DOCUMENTING ANY AND ALL WIRING AND EQUIPMENT CONDITIONS AND CHANGES WHILE COMPLETING THIS CONTRACT. PROVIDE UPDATED TYPEWRITTEN DIRECTORIES FOR ALL PANELS AND LABEL ALL PANELS WITH PLASTIC LAMINATED NAMEPLATES. I. 19 CONSULTANTS EE R 16 23 E JO 16 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com GI N 3 EN 2 CO 1 C 0' 4' 8' 16' C2 / EP-103D Construction Documents CIRCUITS FOR GENERAL POWER WITHIN DASHED AREA ARE FED FROM PANEL 'L2B' UNLESS NOTED OTHERWISE B 2 2 1 3 CHME OFFICE 252 1 1 CHME OFFICE 250 2 4 3 3 CHME OFFICE 254 7 2 4 T 22 18 22 M2B- 1 18 7 TU2-202 4 T 6 22 21 TU2-207 M2B- 1 6 T 19 19 9 9 7 CHME OFFICE 262 21 9 MEETING/WAITING ROOM 21 264 10 7 9 CHME OFFICE 268 TU2-204 M2B- 1 T T ? 8 20 B 10 7 TU2-205 M2B- 1 10 3 3 3 CORRIDOR H203 KEY PLAN 3 17 7 15 STORAGE S257 TU2-210 16 34 14 34 7 13 TU2-206A CHME OFFICE 13 263 14 M2B- 1 M2B- 1 T TU2-203 13 7 TU2-206B JANITOR J255 MEN R253 16 15 7 T T M2B- 1 16 J CHME OFFICE 251 L2B - 35 11 M2B- 1 T 12 4 3 20 11 15 16 TO SECOND FLOOR PLENUM SPACE 1 G 15 16 14 15 1 6 A 17 Project Number 14400 Drawn By Author Checked By Checker VAN H. GILBERT ARCHITECT PC J POWER SECOND FLOOR PLAN - NW & NE A4 / EP-103E SECOND FLOOR PLAN - NORTHEAST A2 POWER Scale: 1/8" = 1'-0" 3 September 11, 2015 SHEET TITLE Project North 2 Description Copyright © 17 A4 / EP-103E 1 Revision 1 Date Date 6 13 Date 1 Mark 12 J 14 12 34 L2B - 38 J 7 CHME CONFERENCE ROOM 274 J J TU2-201 11 12 CHME OFFICE 265 11 14 CLASSROOM 259 15 A 10 17 16 M2B- 1 T M2B- 1 T 8 6 8 CHME OFFICE 260 7 19 17 7 5 7 CHME OFFICE 258 7 18 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 4 5 CHME OFFICE 256 TU2-208 M2B- 1 9/15/2015 7:22:24 PM 6 TU2-209 23 23 5 0' 4 4' 5 8' 16' EP-103D 6 SHEET 156 OF 187 3 VFD-24 VFD-23 M2A - 3,5,7 VFD-25 L2A - 25,27 M2A - 9,11,13 M2A - 14,16,18 L2A - 28,30 VFD-22 M2A - 8,10,12 M2A - 15,17,19 VFD-26 M2A - 21,23,25 M2A - 26,28,30 EF-3 EF-4 PCP-1 VFD-21 3 3 E HDB2A Project North PLAN - PENTHOUSE D3 POWER Scale: 1/8" = 1'-0" 7 18 30,1 L2A1 - 13 J J 8 VESTIBULE H221 8 9 MAE OFFICE 222 9 14 T 4 7 M2A- 1 5 8 L2A1 - 2 4 26 22 26 MAE OFFICE 226 D 26 22 TYP. 5 18 12 L2A2 - 6 15 TU1-207 22 4 L2AA 5 9 7 10 SCV2-203 11 L2AA- 2 L2A2 - 1 14 CIRCUITS FOR GENERAL POWER WITHIN DASHED AREA ARE FED FROM PANEL 'L2AA' UNLESS NOTED OTHERWISE SCV2-204 5 L2AA - 14 1 10 10 2 L2A3 - 9 L2A3 - 8 16 SCV2-205 L2AA- 2 L2AA- 2 17 11 1 L2A3 15 L2AA- 2 BSL-2 ROOM 284 L2AA - 7 15 13 L2AA - 10 11 12 SCV2-210E TU1-203 10 L2AA- 2 GLASSWARE / AUTOCLAVE 282 12 T TU1-203 3 L2AA - 12 4 6 9 2 18 4 TU1-204 17 6 TYP. 6 8 5 J 13 4 5 ANALYTICAL / INSTRUMENTATION 1 280 LE-102A CHME RESEARCH LAB 289 J J 1 M2A- 1 T 16 J MAE GRADUATE STUDENT OFFICE 237 5 2 SCV2-210D L2A2 - 12 17 5 J 6 13 TYP. 7 12 30,1 5 16 MAE OFFICE 238 1 L2AA- 2 12 17 4 9 EXPERIMENTAL METHODS LAB 233 L2A2 - 16,18,20 2 TU1-205 6 REFERENCE KEYNOTES 6 L2AA- 2 J LASER ROOM 286 SCV2-210F L2A3 - 10 18 J J 19 12 TU1-202 M2A- 1 8 7 9 T 20 J 5'CFH J G G 5 9 18 L2A5 - 8,10,12 30,1 L2A5 - 9 J L2AA- 2 18 L2A5 3 21 SCV3-202 11 L2A5 - 7 9 B 1 LE-102B 18 T L2AA- 1 L2A5 - 6 12 L2A5 - 11,13,15 7 HEAT TRANSFER & SURFACE ENGINEERING LAB 17 244 11 MULTIMEDIA INSTRUCTIONAL LAB 245 SCV2-206 SCV2-210G 1 MICROSCOPE ROOM 288 13 TYP. 13 TYP. L2A5 - 3 G G G G A L2A4 - 1 9/15/2015 7:22:30 PM L2A3 - 6 18 G 2 6 G G J 8 9 L New Mexico State University Jett Hall and Jett Annex Renovations and Additions C Construction Documents B 12 KEY PLAN TYP. L2B2 - 10,12 4 3 4 18 4 ENERGETIC MATERIAL LAB 292 18 13 TYP. MAE GRADUATE STUDENT OFFICE 249 TU1-201 M2A- 1 T J 3 18 Mark LAB MANAGER OFFICE 295 18 L2B2 - 6,8 L2AA - 9 L2AA - 13 13 17 L2AA - 11 12 A 14 J 18 Date Description Date L2B2 - 9,11 September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © 16 VAN H. GILBERT ARCHITECT PC SHEET TITLE 15 11 SECOND FLOOR PLAN - EAST WING A4 POWER Scale: 1/8" = 1'-0" SECOND FLOOR PLAN - WEST WING A1 POWER Scale: 1/8" = 1'-0" 0' POWER SECOND FLOOR PLAN - E & W WING, & PENTHOUSE Project North Project North 1 F E S S I ONA L2B2 - 2 13 3 12 L2A3 - 7 L2A3 - 5 J 12 4 J L2A5 - 5 L2A4 - 9,11 L2AA- 1 T 8 SCV3-201 LDB2A - 5 8 L2A4 - 7 G 5 3 5 L2A4 - 8 L2A4 - 5 5 G 7 10 13 L2A4 - 4 G 4 TYP. 2 L2A4 - 6 G 6 4 L2A4 - 3 2 RENEWABLE ENERGY & THERMAL SYSTEMS LAB J 248 L2A4 - 2 7 3 I PROJECT 16 L2A4 10 J 4'CFH G PRO M EX J G 6 EW 11 L2AA- 2 J J J 8 17 J 4 12 9 3 L2B2 10 J 12 12 2 SCV2-209 1 4 J L2AA- 2 1 J 3 L2A5 - 1 L2A5 - 2 L2A5 - 4 A TE O L2B2 - 3 4 4 EQUIPMENT ROOM 290 SCV2-210H 1 1 ST NO. 12498 D EXISTING LAB 292 HAS BEEN RECENTLY RENOVATED. INTERCEPT ALL BRANCH CIRCUITS WITH CODE-SIZE JUNCTION BOX IN THIS AREA. EXTEND BRANCH CIRCUITS TO NEW PANELBOARD L2B2. PROVIDE NEW RECEPTACLES IN MULTI OULET RACEWAY FOR CONNECTIONS OF EXISTING LAB EQUIPMENT AS SHOWN. PROVIDE NEW SERVICE DISCONNECT IN SAME LOCATION WHERE OLD DISCONNECT WAS LOCATED. NEMA CONFIGURATION AND SIZE SHOULD MATCH EXISTING DISCONNECT ELECTRICAL CHARACTERISTICS. CONTRACTOR TO FIELD VERIFY BEFORE COMMENCING ANY WORK. PROGRAMMABLE TIME CLOCK FOR CONTROL OF HALLWAY AND STAIR LUMINAIRES. PROVIDE A FOUR POLE CONTACTOR. REFER TO SHEET E-604 FOR SEQUENCES OF OPERATION AND ADDITIONAL INFORMATION. LIGHTING BATTERY INVERTER FOR EMERGENCY LIGHTING FOR SECOND FLOOR (EAST) AND SECOND FLOOR (NORTH-EAST) AREA. LIGHTING BATTERY INVERTER SYSTEM EQUIPMENT WILL BE FOR EGRESS EMERGENCY LIGHTING. INVERTER WILL OPERATE IN THE EVENT OF AN EMERGENCY. BATTERY INVERTER FOR SECOND FLOOR (EAST) WILL BE RATED FOR 2000 VA. BATTERY INVERTER FOR SECOND FLOOR (NORTH-EAST) WILL BE RATED FOR 2000VA. REFER TO TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM ON SHEET E-604. DEVICE FOR FIRE SMOKE DAMPER. COORDINATE WITH MECHANICAL PRIOR TO COMMENCEMENT OF ANY WORK. SPLIT SYSTEM UNIT. PROVIDE A THERMAL SWITCH SERVICE DISCONNECT ADJACENT TO UNIT FOR THIS SPLIT SYSTEM. EXTEND POWER CIRCUIT TO CONDENSING UNIT ON ROOF. F. H E C K L2AA- 2 2 J D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt J REUSE EXISTING CABINET TO RUN NEW WIRE WHEN POSSIBLE. PROVIDE NEW POWER OUTLETS IN SAME LOCATION. MOUNT MULTI-OUTLET ASSEMBLY 6" ABOVE COUNTER TOP BACK SPLASH, TABLE TOP OR SINK. EXTEND NEW CIRCUIT TO NEW NEC-SIZED JUNCTION BOX. RECONNECT TO EXISTING CONDUCTOR/RACEWAY IN FURNITURE ASSEMBLY. POWER RECEPTACLE FOR CEILING MOUNTED VIDEO PROJECTOR MOUNTED IN PROJECTOR DROP CEILING PLATE. PROVIDE CONDUCTORS AND RACEWAY FROM PANEL SOURCE UP TO NEW 6" SQUARE JUNCTION BOX MOUNTED IN CEILING SPACE AND DOWN THROUGH WIREMOLD. REFERENCE DETAIL. FLUSH MOUNTED POWER OUTLETS IN MULTI-OUTLET ASSEMBLY. REFER TO DETAIL 8 ON SHEET E-501 FOR ADDITIONAL INFORMATION. EXISTING LAB - 278 HAS BEEN RECENTLY RENOVATED. INTERCEPT ALL BRANCH CIRCUITS WITH CODE-SIZE JUNCTION BOX IN THIS AREA. EXTEND BRANCH CIRCUITS TO NEW PANELBOARD L2B1. LOW-VOLTAGE POWER SUPPLY CONNECTION TO AUTOMATIC SENSOR-OPERATED LAVATORY FAUCETS AND FLUSH VALVES. PROVIDE CONCEALED RACEWAYS, BACK BOXES, TRANSFORMER AND HARDWIRED CONNECTIONS TO ALL SENSORS/FAUCETS AS REQUIRED. CRITICAL COORDINATION OF ROUGH-IN REQUIRED PRIOR TO COMMENCING WORK. WIRE ALL COMPONENTS COMPLETE FOR OPERATION. HN SCV2-207 5 L2A5 - 7 22 L2AA- 2 CONDUIT FEEDERS TO BE RUN ON NEW FURR DOWN SPACE. REFERENCE TO PANEL SCHEDULE FOR ADDITIONAL INFORMATION. ROUTING OF FEEDERS AND BRANCH CIRCUITS THROUGH OPEN PLENUM SPACE TO BE COORDINATED WITH MECHANICAL. COORDINATE ENTRANCE THROUGH BUILDING TO AVOID INTEREFERENCE WITH STRUCTURE AND ROUTE CONDUITS ON PLENUM SPACE. FOR EACH UNIT, REFER TO SHEET SERIES M-700 AND P-7OO FOR MECHANICAL EQUIP CHARACTERISTICS. REFER TO SHEET E-708 FOR ELECTRICAL CONNECTIONS AND ADDITIONAL INFORMATION. RACEWAY AND CONDUCTORS TO PENETRATE WALL INTO WIREMOLD. OPEN SPACE TO RUN ELECTRICAL RACEWAYS FROM UNDERGROUND UP TO ELECTRICAL ROOM ON FIRST FLOOR AND PENHOUSE LEVEL. NEMA CONFIGURATION RECEPTACLE TO MATCH NEMA CONFIGURATION OF EQUIPMENT PLUG. PROVIDE 4#10 & 1#10 GROUND IN 3/4" CONDUIT OR IN 5400 MULTI-OULET ASSEMBLY. JUNCTION BOX WILL BE MOUNTED ABOVE FUME HOOD. CONTRACTOR TO PROVIDE POWER TO FUME HOOD WHICH INCLUDES LIGHTING AND RECEPTACLES. IN ADDITION, PROVIDE POWER TO HOOD CONTROLLER PROVIDED BY MECHANICAL. COORDINATE WITH MANUFACTURER'S REQUIREMENTS AND SHEET SERIES 'M' PRIOR TO COMMENCEMENT OF WORK. 2 3 5 7 D L2B1 - 7,9 1 6 J 12 T M2A- 1 MAE OFFICE 236 20 9 7 10 L2A2 - 5 17 16 FINAL ROUTING LOCATION OF NEW UNDERGROUND CABLE TO BE FIELD VERIFY BY CONTRACTOR PRIOR TO COMMENCING ANY WORK 8 L2B1 - 11,13 7 6 J L2A2 - 7 17 20 HAZARDOUS MATERIAL LAB 278 3 9 L2A2 - 4 12 23 20 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 AFTER THE CONTRACTOR HAS RECEIVED APPROVED SHOP DRAWINGS FOR THE ELECTRICAL DISTRIBUTION EQUIPMENT, THEY SHALL SUBMIT SCALED LAYOUTS OF ALL ELECTRICAL EQUIPMENT TO THE ENGINEER FOR APPROVAL TO ENSURE THAT ALL CLEARANCE REQUIREMENTS ARE MET. THIS SUBMITTAL SHALL BE PROVIDED WITH SUFFICIENT TIME SO AS NOT TO INTERFERE WITH THE TIMELY EXECUTION OF THE ROUGH-IN WORK THAT WILL BE REQUIRED. K. 7 5 MAE OFFICE 234 C 14 6 L2A2 - 10 15 21 1 9 5 21 23 20 14 5 TYP. 21 3 L2A2 - 3 L2A2 - 14 TU1-206 13 23 22 19 SCV2-202 L2A2 - 17 J MAE OFFICE 232 8 2 L2AA- 2 SCV2-210B J 15 T M2A- 1 21 ACU-11 SCV2-210C TYP. L2A2 - 22,24,26 J T2C SCV2-201 F 15 L2AA- 2 2 18 24 L2B- 28 CONTRACTOR SHALL MAKE AS-BUILT DRAWINGS DOCUMENTING ANY AND ALL WIRING AND EQUIPMENT CONDITIONS AND CHANGES WHILE COMPLETING THIS CONTRACT. PROVIDE UPDATED TYPEWRITTEN DIRECTORIES FOR ALL PANELS AND LABEL ALL PANELS WITH PLASTIC LAMINATED NAMEPLATES. J. J IV 15 T2D DISCONNECT IN CEILING SPACE 10 L2A2 - 15 10 6 L2B1 - 12,14 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH ALL TRADES FOR THE EXACT LOCATION OF EQUIPMENT AND APPURTENANCES THAT REQUIRE ELECTRICAL CONNECTIONS AND PROVIDE ALIGNMENT OF DEVICES. I. 6 5 7 L2AA- 2 13 4 L2A2 - 9 MAE OFFICE 230 6 2 17 12 8 2 L2A2 - 11,13 4 SCV2-210A 17 RE 25 L2B - 24,26 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 SHOULD CONTRACTOR AT ANY TIME NOTICE THAT THE ACTUAL FIELD CONDITIONS DO NOT CORRESPOND TO THE INFORMATION GIVEN ON THE DRAWINGS, THEN IT WILL BE THEIR RESPONSIBILITY TO NOTIFY THE ENGINEER FOR CLARIFICATION, PRIOR TO COMMENCING SUCH WORK. 8 4 L2B1 - 3 J 30,1 T L2AA- 1 CORRIDOR SCV3-203 H202 T L2AA- 1 14 3 25 6 8 3 L2AA- 2 H2B HDB2B LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 THE CONTRACTOR SHALL INSTALL TIE HANDLES OR MULTI-POLE BREAKERS FOR ALL CIRCUITS SHARING A NEUTRAL CONDUCTOR. H. 5 L2B LDB2B J J CONSULTANTS N 24 J 2 L2A2 - 2 L2A2 - 8 L2A2 - 19,21,23 SCV3-204 L2A2 9 3 25 3 M2B L2A1 - 14 J L2A1 - 3 11 F. CONTRACTOR SHALL INSTALL PULL AND JUNCTION BOXES WHEREVER REQUIRED BY N.E.C. OR JOB CONDITIONS. ALL NEW WIRING SHALL BE TAGGED AT ALL PULL BOXES, JUNCTION BOXES, EQUIPMENT BOXESAND CABINETS WITH APPROVED PLASTIC TAGS. ACTION CRAFT, BRADY OR APPROVED EQUAL. E R EG I S T E M2A- 1 T MAE OFFICE 228 24 14 G G 7 14 L2A1 - 19 L2A1 19 G G G G G 2 3 13 25 COMBUSTION LAB 225 4 4 12 8 14 3 THE CONDUIT RUNS, AS SHOWN ON PLANS, INDICATE APPROXIMATE ROUTING. EXACT LOCATION OF CONDUIT RUNS SHALL BE AS FIELD CONDITIONS DICTATE. A2 / EP-103D ACU-12 L2B - 25,27 J 12 L2A1 - 8 3 22 L2A1 - 9 L2A1 - 1 J MAE OFFICE 224 19 E-301 A2 / EP-103D E-301 L2A1 - 11 19 26 M2A- 1 T TU1-208 8 L2A1 - 7 TYP. 3 12 8 13 16' ELECTRICAL ROOM E267 G G G 7 3 8' E. 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com G. L2B1 REF.: DETAIL L2A D3 ON SHEET EP-103E G 8 TU1-209 9 4 L2A1 - 4,6 4' LOCATION OF EQUIPMENT AND OTHER DEVICES SHOWN ON THE PLANS ARE APPROXIMATE AND SHALL BE FIELD VERIFIED. J 5'CFH 6 DN 0' C2 / EP-103D TO SECOND FLOOR PLENUM SPACE 3 J C2 / EP-103D D. ELECTRICAL ROOM E301 L2A- 11 PENTHOUSE M301 AHU-1 C. IT WILL BE THE CONTRACTOR’S OBLIGATION TO INCLUDE, IN THEIR BID,THE COSTS FOR INSTALLING JUNCTION BOXES, PROVIDING MISCELLANEOUS COVERS, WORK WITH OTHER DISCIPLINES WHERE THE CONTRACT INVOLVES ELECTRICAL POWER OR CONTROL CONNECTIONS, SWITCHES, ETC. ALL OF THIS WORK SHALL BE PART OF THIS CONTRACT. 22 L2A- 11 T2A H2A 3 VFD-20 3 ACU-15 19 B. GFCI RECEPTACLES WILL BE INSTALLED AT ALL LOCATIONS AS REQUIRED BY THE LATEST VERSION OD NEC, STATE AND LOCAL CODES. SOME LOCATIONS WILL BE WITHIN 6'-0" OF SINKS, EXTERIOR DOORS AND WET LOCATIONS. ALL EXTERIOR RECEPTACLES LOCATIONS WILL BE GFCI RATED AND WEATHERPROOF. A. T2B ACU-14 ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES 5 L2A Van H. Gilbert Architect PC EE R M2A M2A - 20,22,24 TO SECOND FLOOR PLENUM SPACE J LDB2A 6 GI N J VFD-27 5 EN 11 M2A - 2,4,6 4 CO 2 JO 1 4' 8' 2 0' 16' 3 4 5 4' 8' EP-103E 16' 6 SHEET 157 OF 187 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES A. REFER TO MECHANICAL EQUIPMENT SCHEDULE ON SHEET SERIES "M" FOR ADDITIONAL INFORMATION ON EQUIPMENT. REFERENCE KEYNOTES 1 E 2 3 4 5 6 EXTEND RACEWAY AND CONDUCTORS TO VFD THAT IS ASSOCIATED WITH THIS UNIT. REFER TO SHEET EP-103E FOR CONTINUATION. REFER TO SHEET E-709 FOR ADDITIONAL INFORMATION. FOR EACH UNIT, REFER TO SHEET SERIES M-700 AND P-7OO FOR MECHANICAL EQUIP CHARACTERISTICS. REFER TO SHEET E-708 FOR ELECTRICAL CONNECTIONS AND ADDITIONAL INFORMATION. EXTEND RACEWAY AND CONDUCTORS TO VFD THAT IS ASSOCIATED WITH THIS UNIT. REFER TO SHEET EP-103A FOR CONTINUATION. REFER TO SHEET E-709 FOR ADDITIONAL INFORMATION. EXTEND RACEWAY AND CONDUCTORS TO INDOOR UNIT ASSOCIATED WITH THIS UNIT. COORDINATE WITH MANUFACTURERS REQUIREMENTS BEFORE COMMENCEMENT OF ANY WORK. MOUNT DEVICE 18" ABOVE ROOF. PROVIDE PEDESTAL MOUNTED WATERPROOF GFCI RECEPTACLE 18" ABOVE ROOF. SEAL ALL PENETRATIONS THROUGH ROOF. REFERENCE DETAIL 7 ON SHEET E-501. CONTRACTOR TO COORDINATE EXACT LOCATION. 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 6 WG 6 L2A- 3 WG L2B- 36 6 2 L2A - 29,31 CU-2 4 GEF-1 L2A - 10,12 3 2 2 EF-4 CU-15 1 CU-7 2 4 2 4 2 PRO 4 M EX I F E S S I ONA L CU-8 EF-5 CU-11 WG PROJECT L2B- 36 6 New Mexico State University CU-12 Jett Hall and Jett Annex Renovations and Additions 5 L2B- 36 3 C C 2 EF-7 L2A- 20 EW CU-5 CU-8 5 A TE O NO. 12498 D CU-4 CU-7 EF-6 2 CU-3 4 CU-15 1 2 2 ST F EF-3 EF-2 RE L2A- 20 2 6 2 F. H E C K N WG L2A- 20 WG CU-14 EF-1 R EG I S T E 6 2 HN IV CU-14 3 EE R 2 4 L2B - 29,31 L2B - 37 GI N S 4 D 2 CU-6 L1A - 51,53 L2A- 20 WG EN CU-13 CO CU-1 JO 2 D 2 LEF-1 3 L2AA - 28,30 LEF-2 4 2 MSB - 6 CU-10 2 4 1 L2A- 20 2 GEF-2 S WG 2 CU-9 M1C - 2,4,6 5 L1C2- 19 L2A- 20 5 Construction Documents WG 6 L2A - 1 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt B B KEY PLAN - Roof (Annotated) Overall 1 POWER Scale: 1/16" = 1'-0" Mark Date Description Date A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 9/15/2015 7:22:35 PM SHEET TITLE ELECTRICAL ROOF PLAN EP-123 1 2 3 4 5 6 SHEET 158 OF 187 1 2 3 4 5 6 A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS. FIRE ALARM SYSTEM DEVICES ARE SHOWN IN GENERAL LOCATIONS. EXACT LOCATIONS SHALL BE DETERMINED BY THE FIRE ALARM SYSTEM ENGINEER/INSTALLER AND COORDINATED WITH OTHER TRADES, AND INSTALLED IN COMPLIANCE WITH NFPA 72 REQUIREMENTS. FIRE ALARM NOTIFICATION APPLIANCES SHALL BE WALL MOUNTED. ALL NEW WIRELESS ACCESS (WAP) DEVICES SHOWN ON THIS PLAN WILL BE PROVIDED AND INSTALLED BY NMSU. CONTRACTOR WILL INSTALL, NMSU PROVIDED CABLES, AND RACEWAY PATHS BACK TO SOURCE. SOURCE LOCATION TO BE DETERMINED BY NMSU. IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC PRESENTATION OF THE MINIMUM FIRE ALARM SYSTEM REQUIREMENTS.DEVICES INDICATED ON THESE DOCUMENTS ARE IN NOW WAY IMPLIED TO BE COMPREHENSICE OF THE FINAL DESIGN. IT IS THE RESPOSABILITY OF THE FIRE ALARM CONTRACTOR TO PROVIDE A COMPLETE FIRE ALARM SYSTEM BASED UPON THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSABILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OD THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSMTEMS IMPACTING THE FIRE ALARM SYSTEM. LENGHT OF CABLES TO BE COORDINATED WITH NMSU SO THAT AT EACH OUTLET THERE WILL BE 18" OF SLACK AND IN THE MDF/IDF ROOMS 30'-0" OF SLACK FOR NMSU USE. B. C. D. E. E F. K. 2 2 2 2 2 2 L1A10 2 MAE COMPUTER LAB 006 WAP R/F 2 2 R/F 2 R/F WAP R/F 2 2 MAE COMPUTER LAB 004 SUPPORT 012 R/F WAP MECHANICAL M002 R/F 2 2 2 N. P 2 2 THERMAL SCIENCE LAB 016 L. M. 2 2 2 2 2 2 R MAE COMPUTER SUPPORT 010 L1A11 P L1A9 DH L1A8 O. DH 1 STORAGE S018A P P ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES ALL NETWORK CABLING IS OWNER FURNISHED CONTRACTOR INSTALLED (OFCI) AND NMSU IS RESPONSIBLE FOR TERMINATIONS AND TESTING OF ALL NETWORK CABLING. 2 Van H. Gilbert Architect PC 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 CORRIDOR H002 S 1 DH S WAP S S WAP S 2 2 S WAP 2 18" X 4" FACT P STORAGE S017A L1A15 OFFICE 011 1. NON-LINEAR DYNAMICS & ENERGY HARVESTING 005 R/F P 2 1 2 2 2 2 2 2 2 2 D CHASE 001B J 2 RE DH 2 F. H E C K ST EW N 2 R/F P HN A TE O NO. 12498 R EG I S T E 2 WOMEN R001 P R/F WAP R/F NEW DOOR HOLDER TO BE RELEASED UPN FIRE ALARM SIGNAL. DATA T005 2 R/F REFERENCE KEYEDNOTES 2 F R/F AEROSPACE STRUCTURAL DYNAMICS LAB 009 R/F IV R/F ELEVATOR EQUIPMENT M017B 2 FLIGHT RESEARCH LAB 013 SOLID MECHANICS LAB 015 P 2 2 2 L1A14 LBAA PRO EE R VESTIBULE H017 2 M EX I F E S S I ONA GI N 1 L1A13 L1A12 D JANITOR J003 EN 2 2 2 JO DH CO F D L 2 PROJECT New Mexico State University Project North SYSTEMS PLAN - BASEMENT C1 SPECIAL Scale: 1/8" = 1'-0" 0' 4' 8' Jett Hall and Jett Annex Renovations and Additions 16' C C Construction Documents B B ELECTRICAL ROOM E001 T1E T1C 9/15/2015 7:22:41 PM D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt M1BM R/F R/F P L1BM HDB1B P KEY PLAN B1B VESTIBULE H001 P MECHANICAL ROOM M003 F R/F P Mark Date Description Date J A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © Project North SYSTEMS PLAN - BASEMENT MECHANICAL A5 SPECIAL Scale: 1/8" = 1'-0" 0' 4' 8' VAN H. GILBERT ARCHITECT PC SHEET TITLE SPECIAL SYSTEMS PLAN - BASEMENT 16' ET-103A 1 2 3 4 5 6 SHEET 159 OF 187 1 2 3 4 5 6 A. B. C. D. E. DN E DN DS DS DS DS CR F. F K. L. M. MAE OFFICE 104B MAE OFFICE 112 MAE OFFICE 110 MAE OFFICE 108 TS FS N. MAE OFFICE 114 ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES ALL NETWORK CABLING IS OWNER FURNISHED CONTRACTOR INSTALLED (OFCI) AND NMSU IS RESPONSIBLE FOR TERMINATIONS AND TESTING OF ALL NETWORK CABLING. CONFERENCE ROOM 116 Van H. Gilbert Architect PC MAIL 104A P FAA MAE OFFICE 106 S O. WAP 2 MAE DIRECTORS WAP OFFICE SUITE 104 PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS. FIRE ALARM SYSTEM DEVICES ARE SHOWN IN GENERAL LOCATIONS. EXACT LOCATIONS SHALL BE DETERMINED BY THE FIRE ALARM SYSTEM ENGINEER/INSTALLER AND COORDINATED WITH OTHER TRADES, AND INSTALLED IN COMPLIANCE WITH NFPA 72 REQUIREMENTS. FIRE ALARM NOTIFICATION APPLIANCES SHALL BE WALL MOUNTED. ALL NEW WIRELESS ACCESS (WAP) DEVICES SHOWN ON THIS PLAN WILL BE PROVIDED AND INSTALLED BY NMSU. CONTRACTOR WILL INSTALL, NMSU PROVIDED CABLES, AND RACEWAY PATHS BACK TO SOURCE. SOURCE LOCATION TO BE DETERMINED BY NMSU. IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC PRESENTATION OF THE MINIMUM FIRE ALARM SYSTEM REQUIREMENTS.DEVICES INDICATED ON THESE DOCUMENTS ARE IN NOW WAY IMPLIED TO BE COMPREHENSICE OF THE FINAL DESIGN. IT IS THE RESPOSABILITY OF THE FIRE ALARM CONTRACTOR TO PROVIDE A COMPLETE FIRE ALARM SYSTEM BASED UPON THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSABILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OD THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSMTEMS IMPACTING THE FIRE ALARM SYSTEM. LENGHT OF CABLES TO BE COORDINATED WITH NMSU SO THAT AT EACH OUTLET THERE WILL BE 18" OF SLACK AND IN THE MDF/IDF ROOMS 30'-0" OF SLACK FOR NMSU USE. 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 2 WAP 2 F D DS D 18" X 4" DS S P S WAP S S 2 S S WAP S MAE SEMINAR 113 P STORAGE S117A DNJ D WOMEN R151 CLASSROOM 109 NEW FIRE ALARM PATH MAE OFFICE 105 NEW FIRE ALARM PATH NEW FIRE ALARM PATH S A1 / ET-103C NEW FIRE ALARM PATH SYSTEMS FIRST FLOOR PLAN - NORTHWEST C2 SPECIAL Scale: 1/8" = 1'-0" PRO EE R I F E S S I ONA GI N M EX L New Mexico State University Jett Hall and Jett Annex Renovations and Additions Project North C EW PROJECT J A1 / ET-103C NO. 12498 RE VESTIBULE P H117 2 COMPUTATIONAL FLOW PHYSICS LAB - I 111 A TE O EN WAP 2 ST N WAP P STORAGE S117B JO BREAK ROOM 105A F. H E C K F MAE GRADUATE STUDENT OFFICE 115 HN IV SUPPORT 117D R EG I S T E OFFICE 117C UNISEX R101 CO CR 2 C 0' 4' 8' 16' C2 / ET-103B Construction Documents B B CHME OFFICE 152 CHME OFFICE 154 CHME OFFICE 156 CHME OFFICE 158 CHME OFFICE 160 CHME OFFICE 164 WAP 2 WAP CORRIDOR H161 2 WAP KEY PLAN 2 P STOR P 157 CHME OFFICE 163 CHME OFFICE 159A JANITOR J155 R/F CHME OFFICE 159G WAP 2 CHME GRADUATE STUDENT COMPUTER CLUSTER 159 VESTIBULE H174 DATA ROOM T165 MEN R153 P P J CHME OFFICE 159F J DS F CHME OFFICE 159C J DS J CHME OFFICE 159B CHME OFFICE 159D CHME OFFICE 159E DS ENTRY H172 P Mark CR TO FACT A P P FSD FSD WAP 2 DN P Project Number 14400 Drawn By Author Checked By Checker VAN H. GILBERT ARCHITECT PC SHEET TITLE FSD SPECIAL SYSTEMS FIRST FLOOR PLAN - NW & NE A4 / ET-103C SYSTEMS FIRST FLOOR PLAN - NORTHEAST A2 SPECIAL Scale: 1/8" = 1'-0" 3 September 11, 2015 Copyright © Project North 2 Description P A4 / ET-103C 1 Date Date F FACT A DS 18" X 4" CR 9/15/2015 7:22:43 PM CHME OFFICE 168 CHME OFFICE 166 18" X 4" D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt CHME OFFICE 150 CHME OFFICE 162 0' 4 4' 5 8' 16' ET-103B 6 SHEET 160 OF 187 2 3 4 5 6 ALL NETWORK CABLING IS OWNER FURNISHED CONTRACTOR INSTALLED (OFCI) AND NMSU IS RESPONSIBLE FOR TERMINATIONS AND TESTING OF ALL NETWORK CABLING. A. B. C. E F. K. C2 / ET-103B A2 / ET-103B J R/F CHME COMPUTER LAB 177 R/F H1B P WAP P T1D VESTIBULE H122 2 S EXISTING 2" FIBER TO REMAIN DN MECHANICAL ROOM M198 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 D DS WAP L1C1 MAE OFFICE 126 WAP 2 2 P CR 2 F BREAKROOM 179 2 A TE O F RE WAP ST EW N STUDENT PROJECTS CENTER 196 F. H E C K NO. 12498 D R/F MAE WELDING 182 HN IV P 18" X 4" MAE OFFICE 130 P R/F R EG I S T E P R/F STORAGE S180 L1B2 DS S Unoccupied Unoccupied JO WAP MAE OFFICE 128 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 F M1C1 MAE STUDENT LOUNGE 125 2 LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 P R/F F WAP CONSULTANTS CR R/F 2 ELECTRICAL ROOM E167 F MAE OFFICE 124 D O. WAP E PRO EE R UP P 2 LDB1B P S N. WAP L1B 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com M EX I F E S S I ONA GI N F M1B MECHANICAL M123 L. M. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS. FIRE ALARM SYSTEM DEVICES ARE SHOWN IN GENERAL LOCATIONS. EXACT LOCATIONS SHALL BE DETERMINED BY THE FIRE ALARM SYSTEM ENGINEER/INSTALLER AND COORDINATED WITH OTHER TRADES, AND INSTALLED IN COMPLIANCE WITH NFPA 72 REQUIREMENTS. FIRE ALARM NOTIFICATION APPLIANCES SHALL BE WALL MOUNTED. ALL NEW WIRELESS ACCESS (WAP) DEVICES SHOWN ON THIS PLAN WILL BE PROVIDED AND INSTALLED BY NMSU. CONTRACTOR WILL INSTALL, NMSU PROVIDED CABLES, AND RACEWAY PATHS BACK TO SOURCE. SOURCE LOCATION TO BE DETERMINED BY NMSU. IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC PRESENTATION OF THE MINIMUM FIRE ALARM SYSTEM REQUIREMENTS.DEVICES INDICATED ON THESE DOCUMENTS ARE IN NOW WAY IMPLIED TO BE COMPREHENSICE OF THE FINAL DESIGN. IT IS THE RESPOSABILITY OF THE FIRE ALARM CONTRACTOR TO PROVIDE A COMPLETE FIRE ALARM SYSTEM BASED UPON THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSABILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OD THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSMTEMS IMPACTING THE FIRE ALARM SYSTEM. LENGHT OF CABLES TO BE COORDINATED WITH NMSU SO THAT AT EACH OUTLET THERE WILL BE 18" OF SLACK AND IN THE MDF/IDF ROOMS 30'-0" OF SLACK FOR NMSU USE. EN STORAGE P S120 LOBBY H121 A2 / ET-103B FSD ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES D. E. C2 / ET-103B Van H. Gilbert Architect PC CO 1 L PROJECT L1A1 CORRIDOR H102 MAE OFFICE 132 MECHATRONICS LAB 133 NEW FIRE ALARM PATH R/F S New Mexico State University WAP F 2 P R/F P R/F MAE OFFICE 134 R/F CHME MINATURE CHEMICAL PILOT PLANT 184 2 F CR WAP R/F F SK4 L1B3 C Jett Hall and Jett Annex Renovations and Additions R/F C DS WAP MAE COMPUTER (GRADUATE) LAB R/F 137 2 1 8 " X4 " R/F MAE OFFICE 136 MDF 137A STORAGE S196B R/F P 18" X 4" S DS L2B11 P ELECTRICALR/F L1AA P R/F WAP J 2 REDUCED GRAVITY LAB 191C L1B4 E194B LDB1C Construction Documents WAP CR M1C WOMEN R140 R/F F B1C H1C R/F MAE OFFICE 138 MAE LAB 191 MAE OFFICE 191A 18" X 4" FACT R/F R/F MAE OFFICE 196A P P R/F MAE ROBOTICS LAB 191B J F 2 J WAP R/F R/F 2 AUTONOMOUS SYSTEMS LAB 141 P UNISEX R142 L1A3 S F WAP L1B5 WAP DS 2 R/F COMPOSITES LAB 144 B 2 MAE CAPSTONE PROJECTS - I R/F 145 AERO FLUIDS LAB 194 CR L1A7 P R/F P R/F R/F CR L1A4 DS 2 R/F MAE MATERIALS LAB 147 S R/F MAE LAB 146 L1A5 6'CFH VESTIBULE H149 2 P DS EXISTING 2" FIBER TO REMAIN WAP COMPUTATIONAL FLOW PHYSICS LAB - II 149A L1A6 R/F GRADUATE STUDENT OFFICE WAP 149B R/F WAP 2 P R/F NEW FIRE ALARM PATH R/F MAE CAPSTONE PROJECTS - II 148 F MAE OFFICE 194A Mark LAB 193A 2 WAP R/F 2 TS FS TS FS F P Description A J September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC CR F R/F FACP J Date Date P DS A KEY PLAN CR CS1 F DS ICW D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt CHME UNDERGRADUATE LAB 193 F WAP F R/F DS B SHEET TITLE SPECIAL SYSTEMS FIRST FLOOR PLAN ANNEX, E & W WING 9/15/2015 7:22:47 PM DN UP SYSTEMS FIRST FLOOR PLAN - WEST WING A1 SPECIAL Scale: 1/8" = 1'-0" SYSTEMS FIRST FLOOR PLAN - EAST WING A4 SPECIAL Scale: 1/8" = 1'-0" SYSTEMS FIRST FLOOR PLAN - ANNEX A2 SPECIAL Scale: 1/8" = 1'-0" ET-103C 1 2 3 4 5 6 SHEET 161 OF 187 1 2 3 4 5 6 A. B. C. D. E. 5 E 6 4 3 1 F. 24 25 7 15 14 29 16 18 30 17 20 19 31 22 32 21 23 K. 8 27 10 9 26 11 13 12 28 L. M. P N. P MAE OFFICE 204 WAP CLASSROOM 216 2 WAP WAP 2 CLASSROOM 210 P WAP 2 O. 2 CLASSROOM 206 CLASSROOM 208 ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES ALL NETWORK CABLING IS OWNER FURNISHED CONTRACTOR INSTALLED (OFCI) AND NMSU IS RESPONSIBLE FOR TERMINATIONS AND TESTING OF ALL NETWORK CABLING. 2 Van H. Gilbert Architect PC PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS. FIRE ALARM SYSTEM DEVICES ARE SHOWN IN GENERAL LOCATIONS. EXACT LOCATIONS SHALL BE DETERMINED BY THE FIRE ALARM SYSTEM ENGINEER/INSTALLER AND COORDINATED WITH OTHER TRADES, AND INSTALLED IN COMPLIANCE WITH NFPA 72 REQUIREMENTS. FIRE ALARM NOTIFICATION APPLIANCES SHALL BE WALL MOUNTED. ALL NEW WIRELESS ACCESS (WAP) DEVICES SHOWN ON THIS PLAN WILL BE PROVIDED AND INSTALLED BY NMSU. CONTRACTOR WILL INSTALL, NMSU PROVIDED CABLES, AND RACEWAY PATHS BACK TO SOURCE. SOURCE LOCATION TO BE DETERMINED BY NMSU. IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC PRESENTATION OF THE MINIMUM FIRE ALARM SYSTEM REQUIREMENTS.DEVICES INDICATED ON THESE DOCUMENTS ARE IN NOW WAY IMPLIED TO BE COMPREHENSICE OF THE FINAL DESIGN. IT IS THE RESPOSABILITY OF THE FIRE ALARM CONTRACTOR TO PROVIDE A COMPLETE FIRE ALARM SYSTEM BASED UPON THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSABILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OD THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSMTEMS IMPACTING THE FIRE ALARM SYSTEM. LENGHT OF CABLES TO BE COORDINATED WITH NMSU SO THAT AT EACH OUTLET THERE WILL BE 18" OF SLACK AND IN THE MDF/IDF ROOMS 30'-0" OF SLACK FOR NMSU USE. 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 F D D 18" X 4" WAP S S 2 FACT F WAP 2 P R/F D WAP 2 2 A TE O NO. 12498 RE WAP CLASSROOM 207 ST EW N VESTIBULE H217 CLASSROOM 213 R EG I S T E CLASSROOM 215 F. H E C K F DATA T203 MAE OFFICE 217A HN IV R/F JANITOR 201A PRO EE R S M EX I F E S S I ONA GI N S EN CORRIDOR H201 CO S JO 2 1 8 " X4 " WAP S P L P P P STORAGE S207A STORAGE S217B P A1 / ET-103E WOMEN R201 PROJECT New Mexico State University A1 / ET-103E Jett Hall and Jett Annex Renovations and Additions Project North SYSTEMS SECOND FLOOR PLAN - NORTHWEST C2 SPECIAL Scale: 1/8" = 1'-0" C C 0' 4' 8' 16' C2 / ET-103D Construction Documents B B MEETING/WAITING ROOM 264 9/15/2015 7:22:51 PM D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt CHME OFFICE 250 CHME OFFICE 252 CHME OFFICE 254 S S WAP F CHME OFFICE 256 CHME OFFICE 258 CHME OFFICE 260 CORRIDOR H203 CHME OFFICE 268 COPY ROOM 268A CHME OFFICE 262 S S WAP KEY PLAN 2 2 P STORAGE S257 CHME OFFICE 263 P JANITOR J255 MEN R253 J CHME CONFERENCE ROOM 274 R/F J CHME OFFICE 251 A WOMEN R201 F CLASSROOM 259 CHME OFFICE 265 Mark S WAP 1 Date TO FACT J A J P P P FSD FSD FSD Drawn By Author Checked By Checker VAN H. GILBERT ARCHITECT PC SPECIAL SYSTEMS SECOND FLOOR PLAN NW & NE A4 / ET-103E SYSTEMS SECOND FLOOR PLAN - NORTHEAST A2 SPECIAL Scale: 1/8" = 1'-0" 3 14400 SHEET TITLE Project North 2 Project Number FSD P A4 / ET-103E 1 September 11, 2015 Copyright © P FSD Description 2 P J Date 0' 4 4' 5 8' 16' ET-103D 6 SHEET 162 OF 187 1 2 3 4 5 LDB2A L2A T2B P H2A PENTHOUSE M301 R/F T2A HDB2A A. B. C. D. E. ELECTRICAL ROOM E301 E F. Project North SYSTEMS PLAN - PENTHOUSE D3 SPECIAL Scale: 1/8" = 1'-0" C2 / ET-103D 0' C2 / ET-103D 4' 8' K. 16' L. M. A2 / ET-103D A2 / ET-103D F DN REF.: DETAIL D3 ON SHEET ET-103E 5'CFH P N. ELECTRICAL ROOM E267 S MAE OFFICE 222 P WAP 2 P R/F VESTIBULE H221 R/F R/F F P WAP R/F 2 COMBUSTION LAB 225 MAE OFFICE 224 O. HAZARDOUS MATERIAL LAB 278 S R/F Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES ALL NETWORK CABLING IS OWNER FURNISHED CONTRACTOR INSTALLED (OFCI) AND NMSU IS RESPONSIBLE FOR TERMINATIONS AND TESTING OF ALL NETWORK CABLING. F M2A 6 PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS. FIRE ALARM SYSTEM DEVICES ARE SHOWN IN GENERAL LOCATIONS. EXACT LOCATIONS SHALL BE DETERMINED BY THE FIRE ALARM SYSTEM ENGINEER/INSTALLER AND COORDINATED WITH OTHER TRADES, AND INSTALLED IN COMPLIANCE WITH NFPA 72 REQUIREMENTS. FIRE ALARM NOTIFICATION APPLIANCES SHALL BE WALL MOUNTED. ALL NEW WIRELESS ACCESS (WAP) DEVICES SHOWN ON THIS PLAN WILL BE PROVIDED AND INSTALLED BY NMSU. CONTRACTOR WILL INSTALL, NMSU PROVIDED CABLES, AND RACEWAY PATHS BACK TO SOURCE. SOURCE LOCATION TO BE DETERMINED BY NMSU. IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC PRESENTATION OF THE MINIMUM FIRE ALARM SYSTEM REQUIREMENTS.DEVICES INDICATED ON THESE DOCUMENTS ARE IN NOW WAY IMPLIED TO BE COMPREHENSICE OF THE FINAL DESIGN. IT IS THE RESPOSABILITY OF THE FIRE ALARM CONTRACTOR TO PROVIDE A COMPLETE FIRE ALARM SYSTEM BASED UPON THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSABILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OD THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSMTEMS IMPACTING THE FIRE ALARM SYSTEM. LENGHT OF CABLES TO BE COORDINATED WITH NMSU SO THAT AT EACH OUTLET THERE WILL BE 18" OF SLACK AND IN THE MDF/IDF ROOMS 30'-0" OF SLACK FOR NMSU USE. 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 R/F D D MAE OFFICE 226 WAP L2A1 RE D MAE OFFICE 230 R/F EXPERIMENTAL METHODS LAB 233 EE R F E S S I ONA L PROJECT 1 LE-102A 2 MAE OFFICE 232 New Mexico State University R/F R/F R/F Jett Hall and Jett Annex Renovations and Additions R/F MAE OFFICE 234 R/F 18" X 4" C MAE GRADUATE STUDENT OFFICE 237 WAP I WAP 2 MAE OFFICE 236 PRO M EX R/F CHME RESEARCH LAB 289 WAP S EW N CORRIDOR H202 R/F NO. 12498 GI N L2A2 A TE O EN S ST F ANALYTICAL / INSTRUMENTATION 280 F. H E C K CO R/F HN IV R/F R EG I S T E MAE OFFICE 228 JO 2 R/F C GLASSWARE / AUTOCLAVE 282 R/F BSL-2 ROOM 284 R/F R/F 2 1 L2AA MAE OFFICE 238 LE-102B S R/F Construction Documents J J J WAP 2 MEN R240 R/F LASER ROOM 286 L2A3 R/F R/F R/F 5'CFH CHME RESEARCH LAB 289 B L2A5 HEAT TRANSFER & SURFACE ENGINEERING LAB 244 S MICROSCOPE ROOM 288 R/F WAP R/F B R/F 2 R/F MULTIMEDIA INSTRUCTIONAL LAB 245 WAP EQUIPMENT ROOM 290 R/F WAP S WAP KEY PLAN 2 2 J J R/F J D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 2 L2A4 ENERGETIC MATERIAL LAB 292 LAB MANAGER OFFICE 295 R/F RENEWABLE ENERGY & THERMAL SYSTEMS LAB 248 Mark WAP Description Date 2 R/F MAE GRADUATE STUDENT OFFICE 249 A Date A P P September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 4'CFH 9/15/2015 7:23:01 PM SHEET TITLE SYSTEMS SECOND FLOOR PLAN - EAST WING A4 SPECIAL Scale: 1/8" = 1'-0" SYSTEMS SECOND FLOOR PLAN - WEST WING A1 SPECIAL Scale: 1/8" = 1'-0" 0' 1 4' 8' 2 SPECIAL SYSTEMS 2ND FLOOR PLAN - E & W WING, & PENTHOUSE Project North Project North 0' 16' 3 4 5 4' 8' ET-103E 16' 6 SHEET 163 OF 187 1 2 3 4 5 6 1 E-301 ELECTRICAL ROOM E301 A. GFCI RECEPTACLES WILL BE INSTALLED AT ALL LOCATIONS AS REQUIRED BY THE LATEST VERSION OF NEC, STATE AND LOCAL CODES. SOME LOCATIONS WILL BE WITHIN 6'-0" OF SINKS, EXTERIOR DOORS AND WET LOCATIONS. ALL EXTERIOR RECEPTACLES LOCATIONS WILL BE GFCI RATED AND WEATHERPROOF. B. IT WILL BE THE CONTRACTOR’S OBLIGATION TO INCLUDE, IN THEIR BID, THE COSTS FOR INSTALLING JUNCTION BOXES, PROVIDING MISCELLANEOUS COVERS, WORK WITH OTHER DISCIPLINES WHERE THE CONTRACT INVOLVES ELECTRICAL POWER OR CONTROL CONNECTIONS, SWITCHES, ETC. ALL OF THIS WORK SHALL BE PART OF THIS CONTRACT. 1 E-301 ELECTRICAL ROOM E301 E C. LOCATION OF EQUIPMENT AND OTHER DEVICES SHOWN ON THE PLANS ARE APPROXIMATE AND SHALL BE FIELD VERIFIED. D. THE CONDUIT RUNS, AS SHOWN ON PLANS, INDICATE APPROXIMATE ROUTING. EXACT LOCATION OF CONDUIT RUNS SHALL BE AS FIELD CONDITIONS DICTATE. E. CONTRACTOR SHALL INSTALL PULL AND JUNCTION BOXES WHEREVER REQUIRED BY N.E.C. OR JOB CONDITIONS. ALL NEW WIRING SHALL BE TAGGED AT ALL PULL BOXES, JUNCTION BOXES, EQUIPMENT BOXES AND CABINETS WITH APPROVED PLASTIC TAGS. ACTION CRAFT, BRADY OR APPROVED EQUAL. F. THE CONTRACTOR SHALL INSTALL TIE HANDLES OR MULTI-POLE BREAKERS FOR ALL CIRCUITS SHARING A NEUTRAL CONDUCTOR. G. SHOULD CONTRACTOR AT ANY TIME NOTICE THAT THE ACTUAL FIELD CONDITIONS DO NOT CORRESPOND TO THE INFORMATION GIVEN ON THE DRAWINGS, THEN IT WILL BE THEIR RESPONSIBILITY TO NOTIFY THE ENGINEER FOR CLARIFICATION, PRIOR TO COMMENCING SUCH WORK. H. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE WITH ALL TRADES FOR THE EXACT LOCATION OF EQUIPMENT AND APPURTENANCES THAT REQUIRE ELECTRICAL CONNECTIONS AND PROVIDE ALIGNMENT OF DEVICES. 7 PENTHOUSE M301 HDB2A LDB2A 12 8 L2A T2A L1A T2B T2B 3 LDB1A 2 L1A - 45,47 CLASSROOM 213 E-301 L1A - 52,54 J J 13 ELECTRICAL ROOM ELECTRICAL ROOM E127 1 T1A E127 ACU-7 L1A - 25 J T1B L1A B1A HDB1A ACU-8 6 H1A TIME CLOCK L1A- 4 5 MECHANICAL M123 CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 AFTER THE CONTRACTOR HAS RECEIVED APPROVED SHOP DRAWINGS FOR THE ELECTRICAL DISTRIBUTION EQUIPMENT, THEY SHALL SUBMIT SCALED LAYOUTS OF ALL ELECTRICAL EQUIPMENT TO THE ENGINEER FOR APPROVAL TO ENSURE THAT ALL CLEARANCE REQUIREMENTS ARE MET. THIS SUBMITTAL SHALL BE PROVIDED WITH SUFFICIENT TIME SO AS NOT TO INTERFERE WITH THE TIMELY EXECUTION OF THE ROUGH-IN WORK THAT WILL BE REQUIRED. J. 10 1 13 E CONTRACTOR SHALL MAKE AS-BUILT DRAWINGS DOCUMENTING ANY AND ALL WIRING AND EQUIPMENT CONDITIONS AND CHANGES WHILE COMPLETING THIS CONTRACT. PROVIDE UPDATED TYPEWRITTEN DIRECTORIES FOR ALL PANELS AND LABEL ALL PANELS WITH PLASTIC LAMINATED NAMEPLATES. I. J LDB1A 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com DN 4 HDB1A ELECTRICAL ROOM E127 L1A - 83 L1A - 4 COMBUSTION LAB 225 MAE SEMINAR 113 ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES E-301 2 Van H. Gilbert Architect PC K. FINAL ROUTING LOCATION OF NEW UNDERGROUND CABLE TO BE FIELD VERIFY BY CONTRACTOR PRIOR TO COMMENCING ANY WORK L. PROVIDE BLANK COVER PLATE FOR ALL EXISTING OUTLETS NOT BEING REUSED, UNLESS THEY ARE COVERED BY WIREMOLD. MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 11 D D 4 1 1 SECTION Scale: 1/4" = 1'-0" POWER FOR DOOR ACCESS CONTROL SYSTEM. TERMINATE AT J-BOX ABOVE CEILING. PROGRAMMABLE TIME CLOCK WITH ROOF MOUNTED PHOTOCELL FOR CONTROL OF EXTERIOR BUILDING LUMINAIRES. PROVIDE A FOUR POLE CONTACTOR. REFER TO SHEET E-604 FOR ADDITIONAL INFORMATION. 2-1/2 in CONDUITS FROM LDB1A TO LABORATORY PANELBOARDS ON FIRST FLOOR. PROVIDE PULL BOX BEFORE ENTERING THE BUILDING. COORDINATE ENTRANCE THROUGH BUILDING TO AVOID INTEREFERENCE WITH STRUCTURE AND ROUTE CONDUITS ON PLENUM SPACE. OPEN SPACE TO RUN ELECTRICAL RACEWAYS FROM UNDERGROUND UP TO ELECTRICAL ROOM ON FIRST FLOOR AND PENHOUSE LEVEL. UNDERGROUND BANK OF CONDUITS FROM MSB. REFER TO SITE PLAN FOR CONTINUATION OF FEEDERS. FMS CONTROL EQUIPMENT. PROVIDE JUNSTION BOX FOR CIRCUIT TERMINATION TO UNIT. PROVIDE JUNCTION WITH DEDICATED CIRCUIT FOR SUMP PUMP BELOW ELECTRICAL ROOM ON RAMP. JUNCTION BOX SHALL BE LOCATED AS CLOSE AS POSSIBLE TO SUMP PUMP. FIELD COORDINATE FINAL LOCATION. REFERENCE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. 5 2 2 SECTION Scale: 1/4" = 1'-0" 6 M1A - 8,10,12 AHU-3 1 C M1A - 13,15,17 7 8 2 MECHANICAL M123 VFD-13 J J 9 2 VFD-14 PCP-3 3 E-301 10 L1A - 55 11 M1A - 7,9,11 4 10 1 M1A - 2,4,6 HRP-3 12 10 E-301 GFP-2 ELECTRICAL ROOM E267 MECHANICAL M123 6 ENLARGED Scale: 1/4" = 1'-0" 32"x50" ELECTRICAL ROOM E267 CLASSROOM 259 HDB2B H2B L2B HDB2B 13 PRO EE R M EX I F E S S I ONA GI N CO EW EN D L PROJECT New Mexico State University Jett Hall and Jett Annex Renovations and Additions C PROGRAMMABLE TIME CLOCK FOR CONTROL OF HALLWAY AND STAIR LUMINAIRES. PROVIDE A FOUR POLE CONTACTOR. REFER TO SHEET E-604 FOR SEQUENCES OF OPERATION AND ADDITIONAL INFORMATION. LIGHTING BATTERY INVERTER FOR EMERGENCY LIGHTING FOR SECOND FLOOR (WEST) AND SECOND FLOOR (WORTH-WEST). LIGHTING BATTERY INVERTER SYSTEM EQUIPMENT WILL BE FOR EGRESS EMERGENCY LIGHTING. INVERTER WILL OPERATE IN THE EVENT OF AN EMERGENCY. BATTERY INVERTER FOR SECOND FLOOR (WEST) WILL BE RATED FOR 2000 VA. BATTERY INVERTER FOR SECOND FLOOR (NORTH-WEST) WILL BE RATED FOR 2000 VA. REFER TO TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM ON SHEET E-604. M1A A TE O F 3 RE 2 ST N FOR EACH UNIT, REFER TO SHEET SERIES M-700 AND P-7OO FOR MECHANICAL EQUIP CHARACTERISTICS. REFER TO SHEET E-708 FOR ELECTRICAL CONNECTIONS AND ADDITIONAL INFORMATION. CONTRACTOR TO PROVIDE POWER FROM VFD TO MECHANICAL EQUIPMENT. TERMINATE PER MANUFACTURERS DIRECTIONS. LIGHTING BATTERY INVERTER FOR EMERGENCY LIGHTING FOR FIRST FLOOR (WEST), FIRST FLOOR (NORTH-WEST) AND BASEMENT AREA. LIGHTING BATTERY INVERTER SYSTEM EQUIPMENT WILL BE FOR EGRESS EMERGENCY LIGHTING. INVERTERS WILL BE STACKED TO MINIMIZE WALL SPACE. INVERTER WILL OPERATE IN THE EVENT OF AN EMERGENCY. BATTERY INVERTER FOR FIRST FLOOR (WEST) WILL BE RATED FOR 2500 VA. BATTERY INVERTER FOR FIRST FLOOR (NORTH-WEST) WILL BE RATED FOR 2000 VA. BATTERY INVERTER FOR BASEMENT WILL BE RATED FOR 1500 VA. REFER TO TYPICAL EMERGENCY LIGHTING BATTERY INVERTER DIAGRAM ON SHEET E-604. F. H E C K NO. 12498 R EG I S T E 1 JO REFERENCE KEYNOTES HN IV ELECTRICAL E127 5 ENLARGED Scale: 1/4" = 1'-0" FLIGHT RESEARCH LAB 013 Construction Documents SPLIT SYSTEM UNIT. PROVIDE A THERMAL SWITCH SERVICE DISCONNECT ADJACENT TO UNIT FOR THIS SPLIT SYSTEM. EXTEND POWER CIRCUIT TO CONDENSING UNIT ON ROOF. CHME RESEARCH LAB 289 LDB2B T2C T2D T2D B B ELECTRICAL ROOM E167 ELECTRICAL ROOM E167 VAC. EXHAUST 2 VFD-10 VFD-9 2 LM1- 7 VP-1 LM1- 7 AC-1 CP-1 CHME COMPUTER LAB 177 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt DWH-1 J J J H1B M1B M1C1 - 22,24,26 LDB1B H1B T1D 1 CHWP-1 M1C1 - 2 LM1 - 11,13,15 LM1 - 1 T1D DI-1 LM1 - 5 LM1 - 10 UV-1 DI-1 ST-1 RO-1 M1C1 - 16,18,20 CHWP-2 LM1 - 12,14,16 LM1 - 4,6,8 ROP-1 LM1 - 2 (HWP-1 AND HWP-2) M1C1 - 21,23,25 J L1B J CA-1 1 HX SKID M1C1 - 15,17,19 CHME OFFICE 159C MECHANICAL ROOM M198 LM1 - 3 2 VFD-8 M1C1 - 10,12,14 M1C1 - 3,5,7 BT WS1 LM1- 7 LM1 - 9 A B1B B1B T1C M1C1 LM1 J LM1- 7 VFD-11 2 Mark MECHANICAL ROOM M198 7 ENLARGED Scale: 1/4" = 1'-0" HDB1B VESTIBULE H001 1 M1C1 - 9,11,13 9 HDB1B FCU-5 2 VFD-7 WS1 ELECTRICAL ROOM E001 ELECTRICAL ROOM E001 M1C1 - 1 1 J FIL. ILP-1 TMV-1 Date Description Date A MECHANICAL ROOM M003 September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © T1E VAN H. GILBERT ARCHITECT PC 9/15/2015 7:20:55 PM SHEET TITLE 3 3 SECTION Scale: 1/4" = 1'-0" ELECTRICAL SECTIONS AND ENLARGED PLANS 4 4 SECTION Scale: 1/4" = 1'-0" E-301 1 2 3 4 5 6 SHEET 164 OF 187 2 3 NO. 12 GAUGE WIRE HANGER TO BUILDING FRAMING OR STRUCTURAL MEMBERS. SUSPEND FROM OPPOSITE CORNERS OF FIXTURE 5 6 ARCHITECTURE • INTERIORS • PLANNING GALVANIZED MOUNTING PLATE: 18 GAUGE MINIMUM THICKNESS, STAGGERED GALVANIZED NUTS AND BOLTS, MAINTAIN A 36" DEEP X 30" WIDE CLEAR WORKING AREA IN FRONT OF SAFETY SWITCH FUSED SAFETY SWITCH, SHALL ISOLATE HIGH, LOW, AND PUMP BACK OF MECHANICAL UNIT LAY-IN LUMINAIRE FUSED 3-POLE SAFETY SWITCH WITH GROUNDING TERMINAL BAR EQUIPMENT SERVICE GFCI RECEPTACLE COPPER BUS BAR (REFER TO DIAGRAM AND KEYED NOTE ON SHEET E-602.) GFCI RECEPTACLE: INSTALL ON EACH UNIT UNLESS WITHIN 25' OF ANOTHER GFCI RECEPTACLE WEATHERPROOF E LIQUID-TIGHT FLEXIBLE STEEL CONDUIT (USED TO ABSORB ANY VIBRATION) CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 STAND-OFFS BOLT CONNECTION WITH COMPRESSION SPADE LUG FITTING (TYPICAL) LB-LINE BOX (OPTIONAL) NOTE A: ALUMI-FLASH FLASHING WITH PROPERLY SELECTED NEOPRENE CAP LAY-IN LUMINAIRE SUPPORT NO SCALE THIS OPTION SHOULD BE USED IF SAFETY SWITCH IS TO BE MOUNTED TO MECHANICAL UNIT. CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 TO SERVICE ENTRANCE GROUND 2700V INSULATORS STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 GROUNDING ELECTRODE BUS 3 MAIN Scale: NOT TO SCALE EQUIPMENT MOUNTING AND OPTIONAL SAFETY SWITCH LOCATION 2 ELECTRICAL Scale: NO SCALE LUMINAIRE SUPPORT 1 LAY-IN Scale: NOT TO SCALE E MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 #4 BARS 6" O.C. EACH WAY, PROVIDE 2" CLEARANCE ALL AROUND TROUGH AREA 1'-0" 1'-2" 1'-8" 6'-0" OR TO SURFACE CLEAR FOR CONDUIT 1'-10" 4'-4" GROUND ROD 5/8"x 8'-0" 1" CHAMFER 3'-6"x6'-6" HIGH MINIMUM NOTES: 4" 3"MIN. 3'-6" 480V SECONDARY SEE ONE-LINE FOR SIZE AND QUANTITY MEDIUM VOLTAGE FEEDER FLOOR B BRING CONDUITS UP FLUSH WITH PAD 1'-0" SECONDARY COMPARTMENT C CONCRETE PAD SHALL BE 3000 PSI CONCRETE, LEVEL WITH ±1/4" IN 5' AND TROWEL FINISHED TO PROVIDE A TRUE PLANE WITHIN 1/16" IN 5' AS DETERMINED BY A 5' STRAIGHT EDGE. D EXISTING GRADE AND BACKFILL UNDER CONCRETE PAD SHALL BE COMPACTED TO 95% IN ACCORDANCE WITH ASTM D1557. COORDINATE PAD REQUIREMENTS WITH EL PASO ELECTRIC. REBAR SECONDARY CONDUITS PRIMARY CONDUITS E MOUNTED TRANSFORMER 4 PAD Scale: NOT TO SCALE A TE O D EW PRO M EX I F E S S I ONA L PROJECT EXCLUSIVELY DEDICATED ELECTRICAL SPACE. NO PIPING OR DUCT SHALL BE ALLOWED WITHIN THESE AREAS SECTION A-A MEDIUM VOLTAGE FEEDER ST NO. 12498 RE PRIMARY COMPARTMENT F. H E C K N 6'-0" OR TO SURFACE CLEAR FOR CONDUIT A NO CONCRETE IN TROUGH AREA. CONCRETE PAD HN F RECESSED OF SURFACE MOUNTED ELECTRICAL PANEL 6'-4" IV PERMANENT IDENTIFICATION PLACARD D R EG I S T E PAD MOUNTED OIL-FILLED TRANSFORMER TO BE FACTORY PAINTED DESERT TAN TRANSFORMER NO.T3 WALL 42" MINIMUM IN COMPLIANCE WITH ARTICLE 110 IN THE NEC 10" DANGER - HIGH VOLTAGE SIGN CEILING 7" 1'-2" D A SECONDARY CONDUITS AREA JO 6'-0" A CLEAR FROM ALL PIPING CONTAINING WATER STRUCTURE EE R SEISMIC FIXTURE CLAMPS : REQUIRED AT ALL (4) LUMINAIRE CORNERS W/2#10 SELF-TAPPING SCREWS. AGI SEISMIC PRODUCTS OR EQUAL. AC 184 COMPLIANT 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com GI N CEILING SYSTEM HANGER WIRES (TYP.) Van H. Gilbert Architect PC EN CEILING SYSTEM HANGER WIRES (TYP.) 4 CO 1 ELECTRICAL SPACE. NO WATER PIPING SHALL BE ALLOWED WITHIN THESE AREAS New Mexico State University AT ELECTRICAL PANELS 6 CLEARANCE Scale: NOT TO SCALE PAD DETAIL 5 TRANSFORMER Scale: NOT TO SCALE Jett Hall and Jett Annex Renovations and Additions C C EMT CONDUIT TO AND WIRE TO PANEL SOURCE AS NOTED ON DRAWINGS SMOKE & HEAT DETECTOR CONNECTED TO FIRE ALARM SYSTEM 6" SQUARE J-BOX IN ACCESSIBLE CEILING SPACE 12" MAX A CAST METAL, 2-GANG, NEMA 3R JUNCTION BOX WITH THREADED HUBS PROVIDE AND INSTALL BLANK COVER EVERY 7'-0" FOR FUTURE DEVICES RIGID STEEL CONDUIT FOR SUPPORT PER N.E.C. ART. 314 RIGID STEEL 3/4" CONDUIT FOR WIRING PROVIDE AND INSTALL DUPLEX OUTLETS. SECTION "A-A" PROVIDE AND INSTALL SPECIALTY DEVICES. PROVIDE AND INSTALL QUADPLEX OUTLETS DISCONNECT CB, LOCKABLE "CAR LIGHTING, RECEPT, HVAC" BASEMENT WEST LBA-4 1ST FLOOR EAST L1B-28 I GFI F 3/4" CONDUIT 3. COORDINATE OUTLETS LOCATIONS WITH FURNITURE. D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt NOTE: REFER TO STRUCTURAL AND ARCHITECTURAL DRAWINGS FOR SECURELY ATTATCHING TO ROOF STRUCTURE AND FLASHING 4. REFERENCE "E" SERIES DRAWINGS FOR ADDITIONAL INFORMATION. ROOF MOUNTING DETAIL 7 RECEPTACLE Scale: NO SCALE 8 I SWITCH AND RECEPTACLE I SMOKE DETECTOR AT EACH LOBBY LBA-6 BASEMENT WEST L1B-30 1ST FLOOR EAST ELEVATOR CAB B A. NEC 620 (ELEVATORS) B. NFPA-72: (RECALL OPERATION), (ELEVATOR SHUTDOWN) C. ASME/ANSI (SAFETY CODE FOR ELEVATORS) D. NFPA-101 (HIGH RISE /STANDBY POWER) E. UBC 97 (RECALL OPERATION) WIREMOLD DETAIL Scale: NOT TO SCATE BASEMENT WEST 1ST FLOOR EAST CB REFER TO ELECTRICAL ONE-LINE DIAGRAM FOR CIRCUIT AND MAIN POWER EQUIPMENT INFORMATION. DISCONNECT/CB SHUNT TRIP TYPE, LOCKABLE 2. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE. ELEVATION LBA-10 L1B-34 REFERENCES: NOTES: 1. HEIGHTS SHOWN ARE TYPICAL TO CENTER OF BACKBOX / DEVICE UNLESS NOTED OTHERWISE. Construction Documents GFI F 18" (TYP.) UNLESS NOTED OTHERWISE ON DRAWINGS SLAB FLOOR 2-GANG JUNCTION BOX SMOKE & HEAT DETECTORS AT PIT J ELEVATOR CLOSET B LBA-8 L1B-32 GFI MULTI-OUTLET WIREWAY 5400 SERIES DUAL CHANNEL. COORDINATE HEIGHT WITH ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN. CB CAST METAL "WHILE-IN-USE" WATERPROOF COVER(S) & RECEPTACLE(S) BASEMENT WEST 1ST FLOOR EAST TELECOM OUTLET FOR CAR PHONE/COMM. CEILING A ELEVATOR MOTOR/CONTROLLER I F SMOKE & HEAT DETECTORS AT TOP OF SHAFT NOTES: A. TRACTION TYPE ELEVATORS/EQUIPMENT MAY HAVE DIFFERENT REQUIREMENTS. B. COORDINATE ELEVATOR MOTOR SIZE WITH OWNER OR ARCHITECT. NOTE: ELEVATOR PHASE I & II RECALL SEQUENCE OF OPERATION SHALL BE SO THE APPROPRIATE SMOKE SENSOR SHALL ACTIVATE FIREFIGHTERS SERVICE PHASE I RECALL OPERATION. THE ELEVATOR SHALL RETURN TO THE DESIGNATED FLOOR LEVEL AND REMAIN OPEN WITHOUT RESPONDING TO ANY OTHER HALLWAY OR CAR PUSH BUTTONS. 1 Date 1 Mark AS HEAT FROM THE FIRE ESCALATES, THE HEAT SENSOR CONTACTS TO SHUNT-TRIP DISCONNECT SHALL BE ACTIVATED. THIS AUTOMATICALLY DISCONNECTS THE MAIN POWER LINE SUPPLY TO ELEVATOR. AS THE FIRE INTENSIFIES; THE APPROPRIATE SPRINKLER HEADS SHALL RELEASE WATER TO EXTINGUISH THE FIRE WITH ELECTRICAL POWER REMOVED AT SOURCE. Revision 1 Date Description Date September 11, 2015 Project Number A A 210 DEGREES TYPICAL HEAT DETECTOR TRIP 286 DEGREES TYPICAL SPRINKLER-HEAD DISCHARGE 14400 Drawn By NAS Checked By JFH Copyright © VAN H. GILBERT ARCHITECT PC 9/15/2015 7:20:58 PM SHEET TITLE ELEVATOR DETAILS 9 TYPICAL Scale: 1/8" = 1'-0" ELECTRICAL DETAIL SHEET E-501 1 2 3 4 5 6 SHEET 165 OF 187 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING TELECOM ROOM # TELECOM ROOM ID# 221-TR1 PATCH PANEL PORT PATCH PANEL # EQPT. RACK ID TELECOM ROOM ID# 1.1.B.36 E 1-1/4" CONDUIT & CONNECTOR. SERVICING CLOSET 1.1.B.37 4-11/16" SQUARE, 2-5/8" DEEP JUNCTION BOX WITH KNOCKOUTS. STRUCTURE PORT LABEL 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com 4-11/16" SQUARE 1-DEVICE RAISED MUD RING. THREADED ROD E CONSULTANTS 1.1.B.38 LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 BLANK CABLE LENGTH 12" COIL IN BACK BOX CABLE TRAY - VOICE DATA CABLING ONLY 201-A CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 CATEGORY CABLES (QTY AS INDICATED ON PLANS) OUTLET ID OUTLET ID OUTLET ROOM # MODULAR JACK OR BLANK AS NEEDED UNISTRUT SUPPORTS TELECOMMUNICATIONS OUTLE 1 STANDARD Scale: NO SCALE FACEPLATE TRAY DETAIL 2 CABLE Scale: NO SCALE STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 OUTLET BOX DETAILS (TYPICAL) 3 TELECOM Scale: NO SCALE MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 13-5/8" B A J-HOOK SPACED EVERY 4'-0" BACK TO TR ROOM DESIGNATED BY NMSU 4-3/4" B A PROTECTIVE BUSHING AT END OF CONDUIT. WALL A B FLANGED COVER FOR CARPET FLOOR POWER 9 1/4" AV POWER POWER 120V POWER COMPARTMENT: CONNECT QTY(1) 3/4" EMT SIDE VIEW (SIDE MOUNT HOUSING ONLY) VOICE/DATA OUTLET REFER TO DETAIL E4 THIS SHEET FOR ADDITONAL INFORMATION POWER/DATA VOICE/DATA POWER VOICE/ DATA POWER VOICE/DATA COMPARTMENT: CONNECT QTY(1) 1-1/4" EMT VOICE/DATA RFB4-SS FLOOR BOX DETAIL (J11) 4 WIREMOLD Scale: NO SCALE BOX ROUNTING 5 TELECOMMUNICATION Scale: NO SCALE 6" MIN MULTI-GANG ASSEMBLY BOX FIRE ALARM NOTIFIER (STROBE/HORN/SPEAKER) C S CLOCK/ SPEAKER LIGHT SWITCH (OR OCCUPANCY SENSOR/SWITCH) EVOLUTION POKE THROUGH 8-AT FLOOR BOX DETAIL 6 WIREMOLD Scale: NO SCALE C Construction Documents EXIT "VARIES" COORDINATE B VOICE/DATA OUTLET SECURITY CARD READER 2" ABOVE BACKSPLASH (COORDINATE WITH ARCH) WALL PHONE JACK 12" AUDIO-VISUAL CONTROL KEYPAD PB IC CR WHITEBOARD / SMART BOARD 96" MAX INTERCOM SWITCH DOOR POWER/DATA WIREWAY (AS NEEDED; SEE PLANS) Jx 80" MIN D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt EQ. WALL MOUNTED PROJECTOR POWER OUTLET PUSHBUTTON (DOOR ACTUATOR) C L 80" MIN (BACKSPLASH) 4" 4" MAX MAX 46" L Jx 6" MIN B F E S S I ONA CEILING AUDIO-VISUAL INPUT JACK 6" MIN EQ. (6'-8" MAX) I AUDIO-VISUAL SCREW COVER PULL BOX EQ. EXIT PRO M EX Jett Hall and Jett Annex Renovations and Additions STRUCTURAL CEILING JX EW New Mexico State University BOTTOM FEED. CENTER-MOUNT HOUSING ASSEMBLY FOR TELECOM & A/V. ACCEPTS (1)1-1/4" CONDUIT. WIREMOLD CAT #1125CHA (TYPICAL OF 3) 16 3/4" A TE O PROJECT POWER NOTE: REFER TO SHEET E611 FOR ADDITIONAL DETAILS INCLUDING CONDUIT REQUIREMENTS. C SIDE VIEW (ALL BOTTOM HOUSINGS) D BOTTOM FEED. SIDE-MOUNT HOUSING ASSEMBLY FOR POWER. ACCEPTS (1)3/4" CONDUIT. WIREMOLD CAT # 575CHA (TYPICAL OF 2) ST NO. 12498 RE VOICE/ DATA F. H E C K N 2-7/16" 1" CONDUIT THROUGH WALL TO CEILING SPACE. ISOMETRIC VIEW R EG I S T E J6 POWER/DATA/A V HN F A TOP VIEW (COVER) IV B A: 1-1/4" K.O. B: 3/4" K.O. C: 1" K.O. D: 1/2" K.O. EE R C GI N B D STUBB CONDUIT 6" INTO CEILING SPACE. EN A CO D JO 10" 5-7/8" D COUNTER Jx FLOOR BOX 18" 18" FLOOR AUDIO-VISUAL INPUT JACK VOICE/DATA OUTLET NOTES: 1. HEIGHTS SHOWN ARE TYPICAL TO CENTER OF BACKBOX / DEVICE UNLESS NOTED OTHERWISE. 2. DEVICES ABOVE DOORS SHALL BE CENTERED BETWEEN TOP OF DOOR TRIM AND CEILING LINE. 3. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE. POWER OUTLET Mark COMPONENT MOUNTING HEIGHTS 7 ELECTRICAL Scale: NONE Date Description Date A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 9/15/2015 7:21:02 PM SHEET TITLE SPECIAL SYSTEMS DETAIL SHEET E-502 1 2 3 4 5 6 SHEET 166 OF 187 1 2 3 4 5 GENERAL NOTES REFERENCE E-602 FOR COPPER FEEDER SCHEDULE, VOLTAGE DROP, FAULT CURRENT AND SERVICE CALCULATION. 16. EXISTING 4"Ø CONDUIT AND CONDUCTORS TO BE REMAIN. REFERENCE FLOOR PLAN FOR ADDITIONAL INFORMATION. B. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO REPRESENT PHYSICAL ARRANGEMENTS, LOCATIONS, ROUTING OR CONNECTIONS. PHYSICAL LAYOUTS ARE TO BE PER FIELD CONDITIONS AND AS INDICATED ELSEWHERE IN THE ELECTRICAL PLANS. 17. REFERENCE SHEET SERIES "LE" FOR PANELBOARD INFORMATION. 18. ELEVATOR CONTROLLER 19. GROUND CONDUCTOR FOR THIS ELEVETARO FEEDER WILL BE RATED FOR 100% OF THE PHASE CONDUCTOR AND NOT AS CALLED FOR IN FEEDER TAG/SCHEDULE. EXIST JETT VAULT SWITCH: "S5-180" 3 C. 4 REFERENCE THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS REGARDING EQUIPMENT AND INSTALLATION. EXISTING 5KV SWITCH "S5-180" 9 D. CONTRACTOR WILL MEASURE AND TORQUE ALL PANEL FEEDERS, MEASURE RESISTANCE TO GROUND AT SERVICE GROUND AND PROVIDE WRITTEN DOCUMENTATION OF TEST RESULTS. E TO KNOX VAULT E. CONTRACTOR WILL LABEL ALL DISTRIBUTION EQUIPMENT PRIOR TO FINAL OBSERVATION WALKTHROUGH. F. REFER TO GROUNDING DIAGRAM ON SHEET E-605. 20. PROVIDE SPARE CIRCUIT BREAKER (S). SIZE AS INDICATED. 21. PROVIDE SPACE FOR ADDITIONAL CIRCUIT BREAKERS. SIZE AS INDICATED. 22. 10 EXISTING TRANSFORMERS AND FEEDER LINES TO BE REMOVED IN ITS ENTIRETY, PLUS ALL ASSOCIATED CONDUCTORS. 11 EXISTING T5-540 TRANSFORMER TO REMAIN. EXISTING FEEDER LINE TO BE REUSED. 12. EXISTING JETT HALL: "S5-180" SWITCH TO REMAIN. CONNECT NEW 25 KV RATED CABLE FROM NEW PMH SWITCH AS SHOWN. EXISTING SWITCH SHALL BE UPGRADED WHEN THE TIME COMES TO CHANGE TO THE 25 KV SERVICE. REFER TO FLOOR PLAN FOR ADDITIONAL LOCATION INFORMATION. SOLID STATE, ELECTRONIC TRIP CIRCUIT BREAKER WITH LONG-TIME, SHORT-TIME, INSTANTANEOUS AND GROUND FAULT FUNCTUINS. 100% RATED AND LOCKABLE. SHEET KEYNOTES ARCHITECTURE • INTERIORS • PLANNING 1 NEW CONDUIT LINE FROM NEW PMH SWITCH. 2 EXIST. "P5-210" TO BE USED AS SPLICE CONNECTION POINT FROM JETT HALL NEW SERVICE LINE TO EXISTING LINE SERVING ENGR. COMPLEX I & II BACK THROUGHT TUNNEL. 3 TRANSFORMER, PAD AND METER ENCLOSURE PROVIDED BY CONTRACTOR. TRANSFORMER TO BE DUAL RATED (5KV & 25KV). 4 METER AND METER ENCLOSURE TO BE MOUNTED TO SIDE OF TRANSFORMER. METER TO BE PROVIDED BY NMSU AND INSTALLED BY DIVISION 26. CONTRACTOR WILL COORDINATE WITH NMSU REPRESENATIVE AND NMSU SERVICE GUIDE FOR CORRECT INSTALLATION. 5 E CONSULTANTS SPD MOUNTED EXTERNALLY TO SWITCHBOARD/PANELBOARD. WHERE EQUIPMENT IS INSTALLED EXTERIOR TO THE BUILDING, THE EQUIPMENT WILL BE IN A NEMA 3R ENCLOSURE, LOCKABLE AND HINGED DOOR. SIZE OF ENCLOSURE WILL BE LARGE ENOUGH TO ACCOMMODATE MANUFATURER;S CLEARANCE REQUIREMENTS OF SPD DEVICE. 13. NEW SPARE CONDUCTOR BACK TO TUNNEL SPACE FOR FUTURE USE. REFER TO SITE PLAN FOR ADDITIONAL INFORMATION. 14. PROVIDE NEW 25 KV RATED CABLE FOR FUTURE CONNECTION TO 25 KV SERVICE. 6 MOLDED CASE, THERMAL-MAGNETIC CIRCUIT BREAKERS, 100% RATED AND LOCKABLE. 15. EXISTING P5-220, P5-230, P5-225, P5-215, METER COMPARTMENT AND LOAD BREAK SWITCH LOCATED IN JETT HALL VAULT TO BE DEMOLISH IN ITS ENTIRETY AS SHOWN. 7 INTEGRAL POWER MONITOR MOUNTED INTERNALLY TO SWITCHBOARD. REFER TO SPECIFICATIONS FOR METERING INSTRUMENTATION REQUIREMENTS. 17 17 17 17 17 17 17 PANEL "2LP1" PANEL "2LP2" PANEL "2LP3" PANEL "2LP4" PANEL "2LP5" PANEL "2LP6" PANEL "2LP7" 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 TO COLLEGE SUBSTATION (NES) TO THOMAS BROWN VAULT 85A 15 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MLO 225A MLO 225A MLO 225A 225A MLO 225A MLO 225A 5 16 5 SPD 480V/277 Y 480V/277 Y 480V/277 Y 480V/277 Y EXIST. T5-545 300 KVA EXIST. T5-550 300 KVA EXIST. T5-560 225 KVA EXIST. T5-565 225 KVA EXIST. T5-570 500 KVA 10 10 225A 3P 21 6 "LDB2A" 208Y/120V, 3PH, 4W 800A DIST. BOARD 21 DEVICES 10 MINIMUM 14KAIC BUS BRACING MINIMUM 14KA 6 800A 3P BUS BRACING 225 Y 14KAIC MINIMUM 14KA MINIMUM 225A 3P 20 225A 3P 21 21 D PANEL "L2A" RE (TYP.) PANEL "M2B" MLO 225A PANEL "H2B" E-605 350A 3P 225A 3P 400A 3P 225A 3P 225A 3P 21 6 6 DEVICES 35KAIC MINIMUM 35KA MINIMUM BUS BRACING 800A MLO 800A MLO 225 Y 225 Y 225A 3P 200A 3P 6 6 "HDB2A" 200 350A 3P 225A 3P 480Y/277V, 3PH, 4W 800A DIST. BOARD 21 350 225 Y 225A 3P 200A 3P 6 20 20 225 Y 200 6 DEVICES BUS BRACING 35KAIC MINIMUM 35KA MINIMUM "HDB2B" 20 6 400A 3P 225A 3P 20 21 21 SECOND LEVEL 14KA MINIMUM 60 Y PANEL "L1AA" 6 MLO 225A 800A 3P 60A 3P PANEL "LBAA" MLO 6 225A 3P 20 6 225 Y 225A 3P 225A 3P 20 21 225 Y 800A 3P 225A 3P 21 225A 3P 208Y/120V, 3PH, 4W 800A DIST. BOARD 800A 3P DEVICES 14KAIC MINIMUM 6 BUS BRACING "LDB1C" 14KA 225A 3P 20 6 MINIMUM 6 6 6 6 6 20 DEVICES BUS BRACING 14KAIC MINIMUM 14KA MINIMUM PANEL "L1B" 400A PANEL "H1B" 800 Y 800 Y 2 3 200A 60 Y 60A 3P 7 M 4 14 (2) 4"C, (2) 3#350 & (2)1#2 GND 25 KV FEEDER 800A 3P 6 400A 3P 6 20 225A 3P 6 20 225A 3P 21 225A 3P 6 6 21 800A 3P 6 350 350A 3P 6 800A 3P 6 800A MLO 800 Y 1 1 E-605 E-605 800 Y 400 225 Y 225 Y 225 Y 800 Y 200 200A 3P 6 DEVICES 21 21 400A 3P 20 225A 3P 60 Y 6 35KAIC MINIMUM 35KA MINIMUM 60A 3P GFP 6 20 21 225A 3P "HDB1A" "T1D" 112.5KVA 480-208Y/120V B "T1F" 300 KVA 480-208Y/120V 22 60 Y 400A 3P 225A 3P PANEL "M1B" (TYP.) 225 Y 225 Y 225 Y 400 225A 3P 21 GRADE/FIRST LEVEL 800 Y PANEL "L1BM" SPD "T1E" 75 KVA 480-208Y/120V 225 Y 1 E-605 (TYP.) Mark Date Description Date PANEL "M1BM" SPD A MLO ONE LINE DIAGRAM (NEW WORK) A1 ELECTRICAL Scale: 1/8" = 1'-0" 400A 225A A 225 225 Y 9/15/2015 7:21:02 PM Construction Documents 225A 3P E-605 MLO 225A MLO 225A 15 19 225 Y 480Y/277V, 3PH, 4W 800A DIST. BOARD BUS BRACING 2500 Y BACK TO 13 TUNNEL 800A 3P 1000A 3P ELEVATOR PANEL "H1C" 18 480Y/277V, 3PH, 4W 2500A MAIN SWITCHBOARD 225A 400A 3P 3P GFP 2500A MCB 200A 225A 3P 20 6 GROUND BUS M TO KNOX VAULT TO COLLEGE SUBSTATION (NES) TO THOMAS BROWN VAULT 400A 3P 6 4.16 KV 4 600A SPD 3 480/277Y POINT OF NEW CONNECTION MINIMUM "MSB" "T1" 2000 KVA 200A 42KA 225A 3P 225A 1 EXISTING 7.5 KV SWITCH "S5-180" BUS BRACING 5 42KAIC MINIMUM PANEL "M1C" MLO 4"C, 3#3/0 & 1#6 GND 25 KV FEEDER PRIMARY PMH SWITCH 25KV, 600A EXIST JETT VAULT SWITCH: "S5-180" 12 DEVICES PANEL "M1C1" 225A EXISTING "P5-210" (PULL BOX) 225A 2 "T1C" 225KVA 480-208Y/120V 1 PANEL "H1A" MLO 480Y/277V, 3PH, 4W 2500A MAIN SWITCHBOARD B 6 400 Y PANEL "M1A" 400A (TYP.) "T1B" 112.5KVA 480-208Y/120V MLO 5 KV ∆ D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 1 60A 3P 208Y/120V, 3PH, 4W 800A DIST. BOARD 400 Y E-605 60 Y "LDB1B" 480V/277 Y "T1A" 225KVA 480-208Y/120V MLO 225A MLO 225A MLO 225A MLO 225A MLO 225A MLO 400A 6 6 6 225 Y 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225 Y 225 Y 225 Y 225 Y 400A 3P 600A 3P 225A 3P 225A 225A 400A EXIST. T5-540 1000 KVA 400 Y 225A 11 800 Y 600 Y 225 Y PANEL "L1A" 400A ENGR. COMPLEX Ι & ΙΙ MLO 600A 225A MLO 225A MLO 225A MLO 225A MLO 225A MLO "LDB1A" SPD 60 Y 60A 3P 5 MLO MINIMUM 225 Y C PANEL "L1B5" 225A BUS BRACING 14KAIC SPD PANEL "L1B4" PANEL "L1B3" PANEL "L1B2" PANEL "L1B1" 400A 21 DEVICES 225A MLO 225A MLO 225A MLO 225A MLO 225A MLO 225A 208Y/120V, 3PH, 4W 800A DIST. BOARD SPD PANEL "L1C2" MLO 21 20 20 225A 3P 5 6 6 6 6 6 6 6 6 6 6 6 5 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225 Y 225 Y 225 Y 225 Y 225 Y 225 Y 225 Y 225 Y 225 Y 225 Y PANEL "L1C1" PANEL "LM1" 800 Y 225A 225A 3P 225A 3P 225A 3P MLO 225A MLO 225A 225A MLO 225A MLO 225A MLO 6 6 6 6 225A 3P 225A 3P 225A 3P 225A 3P 225 Y 225 Y 225 Y 225 Y PANEL "L1A15" PANEL "L1A14" PANEL "L1A13" PANEL "L1A12" PANEL "L1A11" PANEL "L1A10" PANEL "L1A9" PANEL "L1A8" PANEL "L1A7" PANEL "L1A6" PANEL "L1A5" PANEL "L1A4" PANEL "L1A3" PANEL "L1A2" L Jett Hall and Jett Annex Renovations and Additions 225A 3P C PANEL "L1A1" F E S S I ONA 225A 3P 60A 3P 6 480Y/277V, 3PH, 4W 800A DIST. BOARD I New Mexico State University 60 Y 225A 3P 6 PRO M EX 5 SPD 350 EW PROJECT MLO "T2D" 112.5KVA 480-208Y/120V 225A MLO 225A (TYP.) PANEL "M2A" D MLO E-605 "T2C" 225KVA 480-208Y/120V 1 PANEL "H2A" 225A 1 "T2B" 112.5KVA 480-208Y/120V A TE O NO. 12498 N 225KVA 480-208Y/120V ST EE R 400 Y 400 Y F. H E C K F 800 Y HN IV SPD R EG I S T E ONE LINE DIAGRAM (DEMOLITION) D1 ELECTRICAL Scale: 1/8" = 1'-0" 400A 800 Y PANEL "L2B" GI N JET HALL BUILDING ENGR. COMPLEX Ι & ΙΙ DEVICES 6 6 225A 3P 20 6 "LDB2B" 208Y/120V, 3PH, 4W 800A DIST. BOARD 800A 3P 6 6 6 6 6 6 6 6 6 225A 3P 60A 3P JO 10 225A 3P 6 6 6 6 20 20 5KVâ–² 60 Y 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P PANEL "L2AA" MLO 5KVâ–² 480V/277 Y 10 10 5KVâ–² 60A 3P 225 Y 400A 11 EXIST. T5-555 500 KVA 5KVâ–² 225A 3P 225 Y 225 Y 225 Y 225 Y 225 Y 225 Y 225 Y 225 Y 60 Y 225 A 480V/277 Y 480V/277 Y EXIST. T5-540 1000 KVA 5KVâ–² 225 Y 225A 3P MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 SPD 225 A 5KVâ–² 5KVâ–² 225A 3P 225A 3P 225A 3P 225A 3P 225A 3P 225 Y 225 Y 225 Y 225 Y D PANEL "L2B2" PANEL "L2B1" MLO 225A PANEL "L2A5" MLO 225A MLO 225A PANEL "L2A4" PANEL "L2A3" PANEL "L2A2" PANEL "L2A1" 225A PS-225 MLO PS-215 225A PS-230 MLO PS-220 MLO M PS-210 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 75A 225A 100A 15 MLO 85A 170A 15 225A 15 MLO 15 225A 15 MLO 2 EN 2 EXISTING 7.5 KV SWITCH "S5-180" TO REMAIN. ALL CONDUCTORS TO KNOX VAULT, THOMAS BROWN VAULT AND COLLEGE SUBSTATION TO REMAIN OPERATIONAL DURING CONSTRUCTION. ISOLATE AND COVER EXISTING JETT VAULT SWITCH "S5-180" TO AVOID DAMAGE TO EQUIPMENT. REFER TO NEW ELECTRICAL ONE LINE FOR RECONNECTION INFORMATION. Van H. Gilbert Architect PC CO 1 9 A 6 800A MLO 400A 3P 20 225A 3P 21 2 3 20 225A 3P 21 225A 3P 6 DEVICES 4 5 Project Number 14400 Drawn By Author Checked By Checker Copyright © 400 Y 400A 3P 350 200 350A 3P 6 200A 3P 6 480Y/277V, 3PH, 4W 800A DIST. BOARD BUS BRACING BASEMENT LEVEL 1 225A 3P September 11, 2015 35KAIC MINIMUM 35KA MINIMUM 6 225 Y 225A 3P VAN H. GILBERT ARCHITECT PC SHEET TITLE ELECTRICAL DIAGRAMS 6 "HDB1B" E-601 6 SHEET 167 OF 187 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING FEEDER SCHEDULE ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED. CONDUIT NOTES E CONSULTANTS THREE PHASE THREE WIRE & GROUND FEEDER ELECTRICAL EQUIPMENT CALCULATION NO SCALE D 3#12 12 3/4" 25 3#10 10 3/4" 30 3#10 10 3/4" 35 3#8 10 3/4" 40 3#8 10 3/4" 45 3#8 10 3/4" 50 3#8 10 3/4" 60 3#6 10 1" 70 3#4 8 1 1/4" 80 3#4 8 1 1/4" 90 3#2 8 1 1/4" 100 3#2 8 1 1/4" 125 3#1 6 1 1/2" 150 3#1/0 6 1 1/2" 175 3#2/0 6 2" 200 3#3/0 6 2" 225 3#4/0 4 2 1/2" 250 3-250 KCMIL 4 3" 300 3-350 KCMIL 4 3" 350 3-500 KCMIL 2 4" 400 3-600 KCMIL 2 4" (2) 2 1/2" 500 (2) 3-250 KCMIL (2) 2 (2) 3" 600 (2) 3-350 KCMIL (2) 1 (2) 3" 700 (2) 3-500 KCMIL (2) 1 (2) 4" 800 (2) 3-600 KCMIL (2) 1/0 (2) 4" 1000 (3) 3-400 KCMIL (3) 2/0 (3) 3" 1200 (3) 3-600 KCMIL (3) 3/0 (3) 4" 1600 (4) 3-600 KCMIL (4) 4/0 (4) 4" 2000 (5) 3-600 KCMIL (5)250 KCMIL (5) 4" 2500 (6) 3-600 KCMIL (6)350 KCMIL (6) 4" 3000 (8) 3-500 KCMIL (8)400 KCMIL (8) 4" 4000 (10) 3-600 KCMIL (10)500 KCMIL (10) 4" MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 D D4 NO SCALE ELECTRICAL SERVICE CALCULATION NO SCALE C D 20Y 4#12 12 3/4" 25Y 4#10 10 3/4" 30Y 4#10 10 3/4" 35Y 4#8 10 3/4" 40Y 4#8 10 3/4" 45Y 4#8 10 3/4" 50Y 4#8 10 3/4" 60Y 4#6 10 1" 70Y 4#4 8 1 1/4" 80Y 4#4 8 1 1/4" 90Y 4#2 8 1 1/4" 100Y 4#2 8 1 1/4" 125Y 4#1 6 1 1/2" 150Y 4#1/0 6 2" 175Y 4#2/0 6 2" 200Y 4#3/0 6 2" 225Y 4#4/0 4 2 1/2" 250Y 4-250 KCMIL 4 3" 300Y 4-350 KCMIL 4 3" 350Y 4-500 KCMIL 2 4" 400Y 4-600 KCMIL 2 4" 450Y (2) 4#4/0 (2) 2 (2) 2 1/2" 500Y (2) 4-250 KCMIL (2) 2 (2) 3" 600Y (2) 4-350 KCMIL (2) 1 (2) 3" 700Y (2) 4-500 KCMIL (2) 1 (2) 4" 800Y (2) 4-600 KCMIL (2) 1/0 (2) 4" 1000Y (3) 4-400 KCMIL (3) 2/0 (3) 3" 1200Y (3) 4-600 KCMIL (3) 3/0 (3) 4" 1600Y (4) 4-600 KCMIL (4) 4/0 (4) 4" 2000Y (5) 4-600 KCMIL (5) 250 KCMIL (5) 4" 2500Y (6) 4-600 KCMIL (6) 350 KCMIL (6) 4" 3000Y (8) 4-500 KCMIL (8) 400 KCMIL (8) 4" 4000Y (10) 4-600 KCMIL (10) 500 KCMIL (10) 4" 5000Y (12) 4-600 KCMIL (12) 700 KCMIL (12) 4" ST A TE O NO. 12498 RE C2 LIGHTING POWER DENSITY CALCULATION F. H E C K EW N THREE PHASE FOUR WIRE & GROUND FEEDER HN F (2) 2 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 IV (2) 3#4/0 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 R EG I S T E 450 LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 JO D2 20 PRO EE R GROUND M EX I F E S S I ONA GI N CONDUCTORS EN DESIGNATION E CO NOTE: 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com L PROJECT New Mexico State University Jett Hall and Jett Annex Renovations and Additions C Construction Documents EQUIPMENT BONDING JUMPER FOR SEPARATELY DERIVED SYSTEMS PER NEC 250.66 (PROVIDE CONDUCTOR GROUND BELOW INSTEAD OF FEEDER GROUND FOR THREE PHASE, 4-WIRE SYSTEMS INDICATED ABOVE) GROUND DESIGNATION B 20YS THRU 100YS 8 125YS THRU 150YS 6 175YS THRU 200YS 4 225YS THRU 300YS 2 350YS THRU 500YS 1/0 600YS THRU 700YS 2/0 800YS THRU 5000YS 3/0 B D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt THREE PHASE FOUR WIRE 200% NEUTRAL & GROUND FEEDER 100Y-E 3#2, 1#4/0 NEUTRAL 8 2" 150Y-E 3#2/0, 2#2/0 NEUT. 6 2" 4 2 1/2" (2) 2 (2) 2 1/2" (2) 2 (2) 2 1/2" (2) 2 (2) 3" (2) 1/0 (2) 4" 225Y-E 350Y-E 400Y-E 500Y-E 800Y-E 3-250 KCMIL, 2-250 KCMIL NEUT. (2) 3#3/0, (2) 2#3/0 NEUT. (2) 3#4/0, (2) 2#4/0 NEUT. (2) 3-350 KCMIL, (2) 2-350KCMIL NEUT. (2) 3-600 KCMIL, (2) 2-600KCMIL NEUT. FEEDER SCHEDULE A5 COPPER Scale: NO SCALE A1 Mark Date Description Date FAULT CURRENT CALCULATION NO SCALE A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 9/15/2015 7:21:06 PM SHEET TITLE ELECTRICAL CALCULATIONS A3 1 2 VOLTAGE DROP CALCULATION NO SCALE E-602 3 4 5 6 SHEET 168 OF 187 4 5 ARCHITECTURE • INTERIORS • PLANNING SECTION 2 LUMINAIRES GENERAL NOTES a = SECTION 1 c = SECTION 3 d = SECTION 4 e = SECTION 5 E f = SECTION 6 DIMMING ROOM CONTROLLER LMRC-212 DIMMING ROOM CONTROLLER LMRC-212 0-10V CONTROL LOOP (CLASS 2) 0-10V CONTROL LOOP (CLASS 2) ADDITIONAL CONTROLLER WILL BE CONNECTED FROM THE NEXT CONTROLLER. REFERENCE FLOOR PLAN FOR CONTROLLER AND SENSOR QUANTITY. PROVIDE CABLE AS NECESSARY. Hot 120/277 g = SECTION 7 h=HALLWAY LIGHTING CONTROL DESCRIPTION Scene (a) ZONE 8 Auto-ON/Auto-OFF Scene (b) ZONE 9 Auto-ON/Auto-OFF Scene (c) ZONE 10 Auto-ON/Auto-OFF Scene (d) ZONE 11 Auto-ON/Auto-OFF Scene (e) ZONE 12 Auto-ON/Auto-OFF Scene (f) ZONE 13 Auto-ON/Auto-OFF Scene (g) ZONE 14 Auto-ON/Auto-OFF Scene (h) Hallway Auto-ON/Auto-OFF 120/277 SECTION 2 B. DIAGRAMS ARE SHOWN FOR BIDDING PURPOSES. CONTRACTOR WILL PROVIDE ACCURATE AND COORDINATED DIAGRAMS FOR SHOP DRAWING SUBMITTALS. CONTRACTOR WILL PROVIDE ENGRAVED SWITCHES AND A PLACARD WITH CONTROL DESCRIPTION. PLACARD WILL BE PER ARCHITECTURAL REQUIREMENTS, PLACARD WILL BE NO LARGER THAN A SWITCH COVER PLATE. b = SECTION 9 c = SECTION 10 e = SECTION 12 LIGHTING SEQUENCE OF OPERATION A. h=HALLWAY a One Button Dimming Switch LMDM-101 "Hallway Override Control" (REFER TO "EL" SHEETS FOR QUANTITIES) CAT5e LMRJ-Watt Stopper Cable Lighting Loads Two Button DLM Wall Switch LMSW-102 (REFER TO "EL" SHEETS FOR QUANTITIES) Lighting Loads SECTION 1 a c e g Two Button DLM Wall Switch LMSW-102 (REFER TO "EL" SHEETS FOR QUANTITIES) b d f h b d f h a c e g Lighting Loads MOUNT ADJACENT TO SWITCH(ES) CAT5e LMRJ-Watt Stopper Cable LMDC-100 FOR UP TO 10'-0" CLG. LMPC-100 FOR ABOVE 10'-0" CLG. (REFER TO "EL" SHEETS FOR QUANTITIES) (TYPICAL) Lighting Loads SECTION 8 RJ45 (TYPICAL) RJ45 (TYPICAL) One Button Dimming Switch LMDM-101 "Hallway Override Control" (REFER TO "EL" SHEETS FOR QUANTITIES) RJ45 (TYPICAL) SECTION 9 SECTION 10 SECTION 11 RJ45 (TYPICAL) B. SECTION 6 SECTION 5 D SECTION 7 HALLWAY 1 HALLWAY 2 LMDC-100 FOR UP TO 10'-0" CLG. LMPC-100 FOR ABOVE 10'-0" CLG. (REFER TO "EL" SHEETS FOR QUANTITIES) (TYPICAL) LMLS-500 (REFER TO "EL" SHEETS FOR LOCATIONS USED) SEE INSTALLATION INSTRUCTIONS FOR TERMINATION TYPE. QUANTITY AS SHOWN ON PLAN. (TYP.) LMLS-500 (REFER TO "EL" SHEETS FOR LOCATIONS USED) HALLWAY 4 HALLWAY 3 SECTION 14 SECTION 13 SECTION 12 LMDC-100 FOR UP TO 10'-0" CLG. LMPC-100 FOR ABOVE 10'-0" CLG. (REFER TO "EL" SHEETS FOR QUANTITIES) (TYPICAL) REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION STOPPER "DLM" WIRING DIAGRAM B1 WATT Scale: NO SCALE Neutral Neutral 0-10V CONTROL LOOP (CLASS 2) 0-10V CONTROL LOOP (CLASS 2) D. Hot Hot E. 120/277 120/277 a a F. Occupancy Sensor Auto On/Auto Off C CAT5e LMRJ-Watt Stopper Cable LMDC-100 FOR UP TO 10'0" CLG. LMPC-100 FOR ABOVE 10'-0" CLG. (REFER TO "EL" SHEETS FOR QUANTITIES) One Button Dimming Switch LMDM-101 (REFER TO "EL" SHEETS FOR QUANTITIES) One Button Dimming Switch LMDM-101 (REFER TO "EL" SHEETS FOR QUANTITIES) SEE INSTALLATION INSTRUCTIONS FOR TERMINATION TYPE. QUANTITY AS SHOWN ON PLAN. RJ45 (TYPICAL) a One Button Dimming Switch LMDM-101 (REFER TO "EL" SHEETS FOR QUANTITIES) A1 A1 Lighting Loads a E-603 E-603 a D STOPPER "DLM" WIRING DIAGRAM C2 WATT Scale: NO SCALE C4 F. H E C K ST A TE O NO. 12498 D EW PRO M EX I F E S S I ONA L PROJECT New Mexico State University Jett Hall and Jett Annex Renovations and Additions C RJ45 (TYPICAL) ADDITIONAL SWITCHES WILL BE CONNECTED FROM THE NEXT SWITCH. PROVIDE CABLE AS NECESSARY FOR COMPLETE CONTROLLABILITY. Construction Documents REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION HN E-603 Lighting Loads RJ45 (TYPICAL) MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 A1 Lighting Loads SEE INSTALLATION INSTRUCTIONS FOR TERMINATION TYPE. QUANTITY AS SHOWN ON PLAN. G. CAT5e LMRJ-Watt Stopper Cable LMDC-100 FOR UP TO 10'0" CLG. LMPC-100 FOR ABOVE 10'-0" CLG. (REFER TO "EL" SHEETS FOR QUANTITIES) STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 RE DIMMING ROOM CONTROLLER LMRC-212 DIMMING ROOM CONTROLLER LMRC-212 RESTROOMS, LARGE AND SMALL: 1. LARGE: DUAL TECHNOLOGY (ULTRASONIC/INFRARED) SWITCHES TO CONTROL ENTIRE ROOM. 2. SMALL: THE WALL-MOUNTED SENSOR WILL CONTROL LUMINAIRES, AND IN SOME CASES, VIA A RELAY, THE EXHAUST FAN. UTILITY ROOMS (STORAGE, JANITORS AND THE LIKE): WALLMOUNTED OCCUPANCY SENSOR WILL CONTROL THE LUMINAIRE(S) IN THE ROOM. OFFICES, SMALL/LARGE: 1. SMALL: WALL-MOUNTED OCCUPANCY SENSOR WITH SWITCH WILL CONTROL THE LUMINAIRE(S) IN THE ROOM. 2. LARGE: DUAL TECHNOLOGY (ULTRASONIC/INFRARED) SWITCHES TO CONTROL ENTIRE ROOM. CORRIDORS, STAIRWELLS AND COMMON AREAS: 1. LOCAL CONTROL OF LUMINAIRES WILL BE VIA A KEYED MOMENTARY SWITCH. 2. OVERALL CONTROL WILL BE PROGRAMMED ON AT 5 AM AND OFF AT 11 PM. 3. OVERRIDE SWITCH TO OPERATE PROGRAMMED CONTROL BETWEEN 11 PM AND 5 AM. OVERRIDE WILL TURN LIGHT ON FOR 30 MINUTE INCREMENTS. EXTERIOR BUILDING LIGHTING: 1. ALL EXTERIOR BUILDING LIGHTING WILL BE PROGRAMMED TO COME ON AT 1/2 HOUR BEFORE DUSK AND OFF A 1/2 HOUR AFTER DAWN. 2. ALL WALKWAY LIGHTING, EXCEPT THOSE NOTED, WILL COME ON 1/2 HOUR BEFORE DUSK AND OFF AT 11 PM CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 N C. LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 R EG I S T E LIGHTING CONTROL DESCRIPTION Scene (a) All room luminaires - Manual-ON/Auto-OFF CONSULTANTS F ROOM LUMINAIRES CLASSROOMS (VARIOUS ROOMS WILL HAVE DIFFERING CONTROL LOADS. SEE DIAGRAMS AND ROOMS FOR ADDITIONAL INFORMATION. INFORMATION BELOW IS TYPICAL: 1. UNOCCUPIED MODE: WHEN ROOM IS UNOCCUPIED, ALL LIGHTING SHALL BE DISABLED AND DE-ENERGIZED BY OCCUPANCY SENSOR(S) IN ROOM. 2. OCCUPIED MODE: a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY SWITCHES IN ROOM. NO LUMINAIRES WILL AUTOMATICALLY ENERGIZE. b. DURING OCCUPANCY AT THREE BUTTON SWITCH: TOP BUTTON (a) WILL BE PROGRAMMED TO CONTROL ALL LED LUMINAIRES IN CLASSROOM AT 50% LUMEN OUTPUT. MIDDLE BUTTON (b) WILL BE PROGRAMMED TO CONTROL ALL LED LUMINAIRES IN CLASSROOM AT 100% LUMEN OUTPUT. BOTTOM BUTTON (c) WILL BE PROGRAMMED TO CONTROL LUMINAIRES IN FRONT OF CLASSROOM TO TURN OFF AND LUMINAIRES IN BACK OF CLASSROOM AT 50% LUMEN OUTPUT. c. WHEN PERSONNEL LEAVE THE ROOM AND OCCUPANCY SENSOR TIMES OUT, THE SYSTEM SHALL RESET TO THE UNOCCUPIED MODE. PROJECT LABS (VARIOUS ROOMS WILL HAVE DIFFERING CONTROL LOADS. SEE DIAGRAMS AND ROOMS FOR ADDITIONAL INFORMATION. INFORMATION BELOW IS TYPICAL: 1. UNOCCUPIED MODE: WHEN ROOM IS UNOCCUPIED, ALL LIGHTING SHALL BE DISABLED AND DE-ENERGIZED BY OCCUPANCY SENSOR(S) IN ROOM. 2. OCCUPIED MODE: a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY SWITCHES IN ROOM. NO LUMINAIRES WILL AUTOMATICALLY ENERGIZE. b. DURING OCCUPANCY AT FOUR BUTTON SWITCH: TOP BUTTON (a) WILL BE PROGRAMMED TO CONTROL ALL FRONT OF ROOM LED LUMINAIRES AT 50% LUMEN OUTPUT. SECOND BUTTON (b) WILL BE PROGRAMMED TO CONTROL ALL FRONT OF ROOM LED LUMINAIRES AT 100% LUMEN OUTPUT. THIRD BUTTON (c) WILL BE PROGRAMMED TO CONTROL ALL BACK OF ROOM LED LUMINAIRES AT 50% LUMEN OUTPUT. BOTTOM BUTTON (d) WILL BE PROGRAMMED TO CONTROL ALL BACK OF ROOM LED LUMINAIRES AT 100% LUMEN OUTPUT. c. WHEN PERSONNEL LEAVE THE ROOM AND OCCUPANCY SENSOR TIMES OUT, THE SYSTEM SHALL RESET TO THE UNOCCUPIED MODE. E IV ROOM LUMINAIRES LIGHTING CONTROL DESCRIPTION a. All room luminaires - Manual-ON/Auto-OFF 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com d = SECTION 11 LIGHTING CONTROL DESCRIPTION PLACARD LMDC-100 FOR UP TO 10'-0" CLG. LMPC-100 FOR ABOVE 10'-0" CLG. (REFER TO "EL" SHEETS FOR QUANTITIES) (TYPICAL) SECTION 3 a = SECTION 8 g = SECTION 14 LIGHTING CONTROL DESCRIPTION PLACARD SECTION 4 A. f = SECTION 13 Hot a MOUNT ADJACENT TO SWITCH(ES) Occupancy Sensor Auto On/Auto Off EE R Occupancy Sensor Auto On/Auto Off b = SECTION 2 Van H. Gilbert Architect PC GI N SECTION 1 LUMINAIRES LIGHTING CONTROL DESCRIPTION Scene (a) ZONE 1 Auto-ON/Auto-OFF Scene (b) ZONE 2 Auto-ON/Auto-OFF Scene (c) ZONE 3 Auto-ON/Auto-OFF Scene (d) ZONE 4 Auto-ON/Auto-OFF Scene (e) ZONE 5 Auto-ON/Auto-OFF Scene (f) ZONE 6 Auto-ON/Auto-OFF Scene (g) ZONE 7 Auto-ON/Auto-OFF Scene (h) Hallway Auto-ON/Auto-OFF 6 Neutral EN 3 Neutral CO 2 JO 1 WATT STOPPER "DLM" WIRING DIAGRAM NO SCALE Neutral B FRONT OF ROOM LUMINAIRES LIGHTING CONTROL DESCRIPTION Scene (a) (50% lumen output of all LED luminaires) Manual-ON/Auto-OFF Scene (b) (100% lumen output of all LED luminaires) Manual-ON/Auto-OFF Scene (c) (turn off front of room luminaires and 50% lumen output of back of room LED luminaires) Manual-ON/Auto-OFF BACK OF ROOM LUMINAIRES D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt DIMMING ROOM CONTROLLER LMRC-212 9/15/2015 7:21:09 PM B 0-10V CONTROL LOOP (CLASS 2) Hot 120/277 DIMMER SWITCH A A= 50% LIGHT LEVEL B B= 100% LIGHT LEVEL. TO CONTROL LED DIMMING LUMINAIRES IN ROOM a b Occupancy Sensor Auto On/Auto Off A/V = FRONT OFF/ BACK 50% LMDC-100 FOR UP TO 10'-0" CLG. LMPC-100 FOR ABOVE 10'-0" CLG. (REFER TO "EL" SHEETS FOR QUANTITIES) A/V Watt Stopper a = 50% LIGHT LEVEL CAT5e LMRJ-Watt Stopper Cable Three Button DLM Wall Switch LMSW-103 (REFER TO "EL" SHEETS FOR QUANTITIES) b = 100% LIGHT LEVEL c = A/V=FRONT OFF/BACK 50% Mark A SWITCH & PLACARD DETAIL A1 ENGRAVED Scale: NO SCALE SWITCH & PLACARD DETAIL A2 ENGRAVED Scale: NO SCALE SEE INSTALLATION INSTRUCTIONS FOR TERMINATION TYPE. QUANTITY AS SHOWN ON PLAN. a b A2 LIGHTING CONTROL DESCRIPTION PLACARD c E-603 MOUNT ADJACENT TO SWITCH(ES) A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © RJ45 (TYPICAL) VAN H. GILBERT ARCHITECT PC SHEET TITLE ADDITIONAL SWITCHES WILL BE CONNECTED FROM THE NEXT SWITCH. PROVIDE CABLE AS NECESSARY FOR COMPLETE CONTROLLABILITY. LIGHTING DIAGRAMS & SEQUENCE OF OPERATION REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION A4 Description Date Watt Stopper Lighting Loads Date WATT STOPPER "DLM" WIRING DIAGRAM NO SCALE E-603 1 2 3 4 5 6 SHEET 169 OF 187 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING GENERAL NOTES A. DIAGRAMS ARE SHOWN FOR BIDDING PURPOSES. CONTRACTOR WILL PROVIDE ACCURATE AND COORDINATED DIAGRAMS FOR SHOP DRAWING SUBMITTALS. E 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS CIRCUIT (HOT/NEUTRAL) FROM LIGHTING PANEL FOR MULTIPLE ROOMS AND H CONTROL IN EACH ROOM 3 6 X2 X1 7 4 CIRCUIT (HOT/NEUTRAL) FROM LIGHTING PANEL FOR MULTIPLE ROOMS AND H CONTROL IN EACH ROOM U.L. 924 EMERGENCY POWER CONTROLLER MODEL: EPC-D-F-VOLT C 2-WIRE CONTROL DEVICES 9 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 CUT OR CAP CONDUCTORS 10 3 6 X2 X1 7 4 1 2 N 8 NEUTRAL 5 VIOLET 10 5 1 2 N 9 GRAY 8 GRAY VIOLET CUT OR CAP CONDUCTORS EMERGENCY LOAD HOT EMERGENCY LOAD LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 U.L. 924 EMERGENCY POWER CONTROLLER MODEL: EPC-D-F-VOLT C MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 4-WIRE CONTROL DEVICE D D BLUE 120V BLUE 120V 277V 277V YELLOW RE D BLUE 120V CIRCUIT (HOT/NEUTRAL) FROM LIGHTING PANEL FOR MULTIPLE ROOMS AND CONTROL IN EACH ROOM YELLOW EMERGENCY LOAD WHITE RED BLUE CIRCUIT (HOT/NEUTRAL) FROM LIGHTING PANEL FOR MULTIPLE ROOMS AND CONTROL IN EACH ROOM BLUE RED CIRCUIT (HOT/NEUTRAL) FROM LIGHTING PANEL FOR MULTIPLE ROOMS AND CONTROL IN EACH ROOM YELLOW EMERGENCY LOAD WHITE BLUE RED CIRCUIT (HOT/NEUTRAL) FROM LIGHTING PANEL FOR MULTIPLE ROOMS AND CONTROL IN EACH ROOM YELLOW EMERGENCY LOAD WHITE RED 2 AMP / OR 4 WIRE CONTROL DIAGRAM ABOVE FOR THIS UNIT YELLOW EMERGENCY LOAD WHITE EE R GI N C INDIVIDUAL ROOM INVERTER NEUTRAL INVERTER HOT LIGHTING BATTERY INVERTER INVERTER WILL OPERATE IN THE EVENT OF AN EMERGENCY. INVERTER LOCATED IN THE ELECTRICAL ROOM. LIGHTING BATTERY INVERTER INVERTER NEUTRAL INVERTER HOT INVERTER WILL OPERATE IN THE EVENT OF AN EMERGENCY. INVERTER LOCATED IN THE ELECTRICAL ROOM. LIGHTING BATTERY INVERTER TO PANEL FOR CONSTANT POWER REFER TO PLANS FOR CIRCUIT AND OTHER INFORMATION SINGLE ROOM AND CONTROL ON ONE LIGHTING CIRCUIT AND ONE INVERTER B1 INDIVIDUAL ROOM INVERTER NEUTRAL INVERTER HOT TO PANEL FOR CONSTANT POWER REFER TO PLANS FOR CIRCUIT AND OTHER INFORMATION INVERTER WILL OPERATE IN THE EVENT OF AN EMERGENCY. INVERTER LOCATED IN THE ELECTRICAL ROOM. Construction Documents TO PANEL FOR CONSTANT POWER REFER TO PLANS FOR CIRCUIT AND OTHER INFORMATION MULTI ROOM AND CONTROL ON ONE LIGHTING CIRCUIT AND ONE INVERTER MULTI ROOM, CONTROL AND CIRCUITS ON ONE LIGHTING INVERTER EMERGENCY LIGHTING, CONTROL, AND BATTERY INVERTER DIAGRAM NO SCALE B D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt L Jett Hall and Jett Annex Renovations and Additions 277V 2 AMP / OR 4 WIRE CONTROL DIAGRAM ABOVE FOR THIS UNIT INDIVIDUAL ROOM B KEYED MOMENTARY OVERRIDE SWITCH(ES) IN HALLWAYS KEYED MOMENTARY OVERRIDE SWITCH(ES) IN HALLWAYS 277V TIMECLOCK KM TERMINAL BLOCK KEYED MOMENTARY OVERRIDE SWITCH(ES) IN HALLWAYS 277V TIMECLOCK WILL INCORPORATE AN H-O-A SWITCH FOR MANUAL AND AUTOMATIC CONTROL 2.0A FUSE C H1A-6 (1ST F. NW) H1A-2 (BASEMENT) H1A-11 (1ST F. WEST) SPARE 4 POLE CONTACTOR (HINGED COVERED PULLBOX) NEMA TYPE1 ENCLOSURE 277V LIGHTING CONTACTOR - ELECTRICAL ROOM E127 KM TIMECLOCK TERMINAL BLOCK KEYED MOMENTARY OVERRIDE SWITCH(ES) IN HALLWAYS 277V TIMECLOCK WILL INCORPORATE AN H-O-A SWITCH FOR MANUAL AND AUTOMATIC CONTROL TIMECLOCK KM TERMINAL BLOCK 2.0A FUSE TIMECLOCK WILL INCORPORATE AN H-O-A SWITCH FOR MANUAL AND AUTOMATIC CONTROL 2.0A FUSE C H1B-2 (1ST F. NE) SPARE SPARE SPARE C H2A-2 (2ND F. NW) H2A-9 (2ND F. WEST) SPARE SPARE 4 POLE CONTACTOR 4 POLE CONTACTOR (HINGED COVERED PULLBOX) NEMA TYPE1 ENCLOSURE 277V (HINGED COVERED PULLBOX) NEMA TYPE1 ENCLOSURE 277V LIGHTING CONTACTOR - ELECTRICAL ROOM E167 277V 277V 277V 277V LIGHTING CONTACTOR - ELECTRICAL ROOM E301 KM TIMECLOCK TERMINAL BLOCK TIMECLOCK WILL INCORPORATE AN H-O-A SWITCH FOR MANUAL AND AUTOMATIC CONTROL TIMECLOCK WILL INCORPORATE AN H-O-A SWITCH FOR MANUAL AND AUTOMATIC CONTROL TIMECLOCK PC PHOTOCELL ON ROOF FOR EXTERIOR LIGHTS TERMINAL BLOCK C H2B-5 (2ND F. NE) H2B-2 (2ND F. EAST) SPARE SPARE 4 POLE CONTACTOR (HINGED COVERED PULLBOX) NEMA TYPE1 ENCLOSURE 277V LIGHTING CONTACTOR - ELECTRICAL ROOM E267 TIMECLOCK PC TERMINAL BLOCK PHOTOCELL ON ROOF FOR EXTERIOR LIGHTS 2.0A FUSE 2.0A FUSE TYPICAL CONTROL SEQUENCE: (a) ON AT 5 AM. (b) OFF AT 11 PM. 9/15/2015 7:21:12 PM F E S S I ONA New Mexico State University C A I PROJECT 120V 277V 2 AMP / OR 4 WIRE CONTROL DIAGRAM ABOVE FOR THIS UNIT M EX YELLOW INDIVIDUAL ROOM 120V 277V 2 AMP / OR 4 WIRE CONTROL DIAGRAM ABOVE FOR THIS UNIT WHITE INDIVIDUAL ROOM 120V A TE O 277V 2 AMP / OR 4 WIRE CONTROL DIAGRAM ABOVE FOR THIS UNIT RED NOTE: APPROVED MANUFACTURER'S FOR BATTERY INVERTERS ARE EVENLITE, MYERS AND LVS. PRO BLUE 120V 277V EW N INDIVIDUAL ROOM ST NO. 12498 R EG I S T E INDIVIDUAL ROOM F. H E C K F WHITE HN IV EMERGENCY LOAD WHITE RED EN YELLOW 2 AMP / OR 4 WIRE CONTROL DIAGRAM ABOVE FOR THIS UNIT CO RED CIRCUIT (HOT/NEUTRAL) FROM LIGHTING PANEL FOR MULTIPLE ROOMS AND CONTROL IN EACH ROOM JO 2 AMP / OR 4 WIRE CONTROL DIAGRAM ABOVE FOR THIS UNIT C H1B-11 (WEST) SPARE SPARE SPARE TIMECLOCK WILL INCORPORATE AN H-O-A SWITCH FOR MANUAL AND AUTOMATIC CONTROL 2.0A FUSE C H1A-16 (EAST) SPARE SPARE SPARE TIMECLOCK PC TERMINAL BLOCK PHOTOCELL ON ROOF FOR EXTERIOR LIGHTS TIMECLOCK WILL INCORPORATE AN H-O-A SWITCH FOR MANUAL AND AUTOMATIC CONTROL C H1C-5 (ANNEX) SPARE SPARE SPARE 4 POLE CONTACTOR 4 POLE CONTACTOR (18"x18"x6" HINGED COVERED PULLBOX) NEMA TYPE1 ENCLOSURE 277V (18"x18"x6" HINGED COVERED PULLBOX) NEMA TYPE1 ENCLOSURE 277V (18"x18"x6" HINGED COVERED PULLBOX) NEMA TYPE1 ENCLOSURE 277V LIGHTING CONTACTOR - ELECTRICAL ROOM E167 A. 2.0A FUSE 4 POLE CONTACTOR LIGHTING CONTACTOR - ELECTRICAL ROOM E127 SEQUENCES OF OPERATIONS LIGHTING CONTACTOR - ELECTRICAL ROOM E194B B. CORRIDORS, STAIRWELLS AND COMMON AREAS: 1. LOCAL CONTROL OF LUMINAIRES WILL BE VIA A KEYED MOMENTARY SWITCH. 2. OVERALL CONTROL WILL BE PROGRAMMED ON AT 5 AM AND OFF AT 11 PM VIA ASTRONOMICAL CLOCK. 3. OVERRIDE SWITCH TO OPERATE PROGRAMMED CONTROL BETWEEN 11 PM AND 5 AM. OVERRIDE WILL TURN LIGHT ON FOR 30 MINUTE INCREMENTS. EXTERIOR BUILDING LIGHTING: 1. ALL EXTERIOR BUILDING LIGHTING WILL BE PROGRAMMED TO COME ON AT 1/2 HOUR BEFORE DUSK AND OFF A 1/2 HOUR AFTER DAWN VIA PHOTOCELL AND TIMECLOCK. 2. ALL WALKWAY LIGHTING, EXCEPT THOSE NOTED, WILL COME ON 1/2 HOUR BEFORE DUSK AND OFF AT 11 PM VIA ASTRONOMICAL CLOCK. 1 Date 1 Mark Revision 1 Date Description Date A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © CONTROL SEQUENCE: (a) ON AUTOMATICALLY SELECTED ASTRONOMIC SETTING. (b) OFF AT PRESET TIME; COORDINATE WITH OWNER'S REPRESENTATIVE. VAN H. GILBERT ARCHITECT PC SHEET TITLE LIGHTING DIAGRAMS & COMMON AREA LIGHTING DIAGRAM A1 HALLWAY Scale: NO SCALE BUILDING LIGHTING DIAGRAM A4 EXTERIOR Scale: NO SCALE E-604 1 2 3 4 5 6 SHEET 170 OF 187 1 2 3 4 5 6 Van H. Gilbert Architect PC OUTDOOR UNDERGROUND SYSTEM ARCHITECTURE • INTERIORS • PLANNING APPLY TO ELECTRICAL GROUNDING DIAGRAM ONLY GENERAL NOTES E #4#0 IN DUCTBANK <5'-0" METER & BACKFLOW PREVENTER(S) COLD WATER PIPE TO AIR TERMINALS 10 10 M BUILDING STRUCTURAL STEEL GROUND OUTDOOR TRANSFORMER NEUTRAL 10 #4/0 #4/0 2 #4/0 #4/0 SERVICE CONDUCTOR SIZE (AWG OR kCMIL) GROUNDING ELECTRODE CONDUCTOR (AWG) <= #2 8 1/0 OR 1/0 6 2/0 OR 3/0 4 OVER 3/0 THROUGH 350 2 OVER 350 THROUGH 600 1/0 OVER 600 THROUGH 1100 2/0 OVER 1100 3/0 3. NON K-RATED TRANSFORMER 4. 5. GROUND 7 1. SERVICE ENTRANCE EQUIPMENT NEUTRAL 10 4. 2'-4" MINIMUM 5. D #4/0 #4/0 WITH 600V INSULATION 6. PANELBOARD #6 7. CABLE TRAY 5 3'-0" 1 3 GROUND PIPE/CONDUIT TELECOMM ROOM 10 TRANSFORMER FOR SEPARATELY DERIVED SYSTEM (SIMILAR FOR ALL SEPARATELY DERIVED DRY-TYPE TRANSFORMERS) NEUTRAL 4 3 BUILDING STRUCTURAL STEEL ~ CW HW 3 10 GROUND 8 ~ GROUND SWITCHBOARD, DISTRIBUTION BOARD OR PANELBOARD NEUTRAL 10. 11. 12. 13. WATER HEATER (TYPICAL) D D F. H E C K ST A TE O EW PRO M EX I F E S S I ONA L PROJECT New Mexico State University Jett Hall and Jett Annex Renovations and Additions 1 3 8 C HN NO. 12498 RE 9. MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 N 11 REFER TO ONE-LINE DIAGRAM AND FEEDER SCHEDULE FOR GROUNDED CONDUCTOR SIZE. CONNECT GROUNDING ELECTRODE CONDUCTOR TO GROUND ROD. FOR EQUIPMENT GROUNDING CONDUCTOR SIZE REFER TO ONE-LINE DIAGRAM AND FEEDER SCHEDULE. PROVIDE GROUNDING ELECTRODE CONDUCTOR SIZE BASED ON THE CONDUCTOR SIZE OF THE SECONDARY OF THE TRANSFORMER. SIZE PER NEC 250.66 AND PER SCHEDULE ON THIS SHEET. PROVIDE A CONCRETE-ENCASED MAIN GROUNDING ELECTRODE IN THE BUILDING FOUNDATION AROUND THE ENTIRE PERIMETER OF THE BUILDING. LOCATE ELECTRODE IN THE BOTTOM ONE-THIRD OF THE FOUNDATION WITH AT LEAST 3 INCHES OF CONCRETE COVER. USE EITHER #4/0 BARE COPPER CABLE OR #6 OR LARGER STEEL REINFORCING BARS MADE ELECTRICALLY CONTINUOUS USING EXOTHERMICALLY WELDED #4/0 JUMPERS. BOND EACH PERIMETER STRUCTURAL STEEL COLUMN TO THE CONCRETE-ENCASED MAIN GROUNDING ELECTRODE. USE EXOTHERMIC WELDS. PROVIDE A 1/4" X 4" X 12" "MAIN GROUNDING ELECTRODE GROUND BAR" FOR SINGLE POINT GROUNDING. LOCATE AT AN ACCESSIBLE POINT NEAR THE SERVICE ENTRANCE EQUIPMENT. MAKE OTHER CONNECTIONS TO THE GROUND BAR USING TWO-HOLE COMPRESSION SPADE LUGS THAT MEET IEEE 837 REQUIREMENTS. LABEL EACH CONNECTION. USE THE "MAIN GROUNDING ELECTRODE GROUND BAR" INSTEAD OF BUILDING STRUCTURAL STEEL IF THE FIRST OVER CURRENT DEVICE FOR THE SEPARATELY DERIVED SYSTEM IS WITHIN SAME ROOM OF THE "MAIN GROUNDING ELECTRODE GROUND BAR". INSTALL A 1/4" X 4" COPPER "TELECOMMUNICATIONS GROUNDING BUSBAR" IN EACH TELECOMMUNICATIONS ROOM. CONNECT CABLES TO THE "TELECOMMUNICATIONS GROUNDING BUSBAR" USING COMPRESSION SPADE LUGS. LABEL CONDUCTORS PER ANSI-J-STD-607-A. LABEL EACH CONNECTION. SEE PLAN FOR BAR LENGTH AND LOCATIONS. BONDING JUMPER SIZED PER GROUNDING ELECTRODE CONDUCTOR SCHEDULE THIS SHEET. BOND HOT WATER PIPE TO COLD WATER PIPE AT EACH WATER HEATER WITH A #8 BARE COPPER CONDUCTOR. LIGHTNING PROTECTION COUNTERPOISE - #4/0 BARE COPPER. BOND EACH CORNER STRUCTURAL STEEL AND PERIMETER STRUCTURAL STEEL AT NO MORE THAN 50 FOOT SPACING TO THE LIGHTNING PROTECTION COUNTERPOISE. STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 R EG I S T E #6 COLD WATER PIPE CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 F 8. #4/0 LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 IV 3 9 CONSULTANTS REFERENCE KEYNOTES 1 MAIN GROUNDING ELECTRODE GROUND BAR E APPLY TO ELECTRICAL GROUNDING DIAGRAM ONLY 2. 3. GRADE 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com EE R NOTE: ALL CONDUCTORS ARE COPPER. JO MANHOLE GROUND LOOP AND ROD 2 2. GI N GROUNDING ELECTRODE CONDUCTOR SCHEDULE INSTALL GROUNDING CONNECTIONS TO BUILDING STRUCTURE AND WATER PIPES AT LOCATIONS THAT ARE VISIBLE AND ACCESSIBLE FOR INSPECTION, MAINTENANCE, AND TESTING. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC SERVICE ENTRANCE CONDUIT. BOND TO SERVICE ENTRANCE EQUIPMENT GROUND BUS USING GROUNDING ELECTRODE CONDUCTOR. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC FEEDER CONDUIT. BOND TO GROUND BUS USING CONDUCTOR THAT IS SIZED EQUAL TO EQUIPMENT GROUNDING CONDUCTOR. BOND ELECTRICAL EQUIPMENT ENCLOSURES TO GROUND BAR USING SAME SIZE CONDUCTOR AS FEEDER EQUIPMENT GROUND CONDUCTOR OR FACTORY PROVIDED GREEN SCREW. CLEAN COATED RE-BAR PRIOR TO PERFORMING ELECTRICAL CONNECTION. EN 1. MANHOLE CO AIR TERMINAL C GROUND NEUTRAL GROUNDING DIAGRAM 1 ELECTRICAL Scale: 1/8" = 1'-0" 7 2ND LEVEL NORTH WEST RET. 7 6 SUP. R 2ND LEVEL EAST 2 TS GENERAL NOTES 2 TS 1 FS A. 1 TYP. TYP. FATC5 5 F P FATC4 5 P B. F C. D. IDF T232 DATA T203 E. 12 12 B L2C-37 120VAC 7 10 RET. R D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt RET. 7 6 SUP. RET. FS TYP. 2 120VAC TS 1 FS TS 1 FS 1 TYP. TYP. FATC2 5 9 F P TS FAA 11 14 MDF 137A M M P F ME/MA HYDRAULICS 194 FATC3 5 P F 1. 2. TTB 8 DATA ROOM T165 3. 4. 5. DC 12 12 3 1ST LEVEL WEST 1ST FLOOR NORTHEAST L1A-89 120VAC LIC-44 120VAC 7 RET. 2"C L1B-53 120VAC 15 6. ANNEX 6 SUP. R TYP. 7. 8. 9. 2 120VAC A 12 4 TS FS 10. 11. 12. 13. 1 TYP. DATA T005 P FIRE ALARM DIAGRAM INDICATES GENERAL DIAGRAMMATIC CONNECTIONS ONLY. ALL CONNECTIONS AND INSTALLATION WILL BE PER FIRE ALARM SYSTEM MANUFACTURER'S SHOP DRAWINGS. DEVICE QUANTITIES ARE NOT INDICATED ON THIS DRAWING. REFER TO FLOOR PLANS FOR QUANTITIES AND LOCATIONS. REFER TO SPECIFICATION SECTION 283111 FOR FIRE ALARM SYSTEM REQUIREMENTS. FIRE ALARM WIRING AND CABLING SHALL BE IN CONFORMANCE WITH NEC AND TYPE SHALL BE AS RECOMMENDED BY FIRE ALARM SYSTEM MANUFACTURER. SEAL ALL PENETRATIONS THROUGH WALLS, FLOOR, CEILINGS AND ROOF PER ARCHITECTURAL SPECIFIED REQUIREMENTS. SEAL WILL MATCH THE FIRE RATING OF EACH PENETRATION LOCATION. IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC PRESENTATION OF THE MINIMUM FIRE ALARM SYSTEM REQUIREMENTS. DEVICES INDICATED ON THESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE COMPREHENSIVE OF THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO PROVIDE A COMPLETE FIRE ALARM SYSTEM BASED UPON THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OF THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMS IMPACTING THE FIRE ALARM SYSTEM. B REFERENCE KEYNOTES TYP. FACP 13 6 SUP. R TYP. 120VAC FATC1 5 9/15/2015 7:21:17 PM 2"C 2 2 TS 2"C R TYP. 120VAC F. 7 6 SUP. 10 L2C-37 120VAC 10 2"C Construction Documents APPLY TO FIRE ALARM DIAGRAM ONLY TYP. 120VAC FS 6 SUP. R TYP. 120VAC RET. F 14. ALARM RISER DIAGRAM1 2 FIRE Scale: NOT TO SCALE 15. MINIMUM 3/4" CONDUIT AND FIRE ALARM CABLING AS REQUIRED BY THE FIRE ALARM MANUFACTURER. INDEPENDENTLY SUPERVISE EACH FLOW AND TAMPER SWITCH WITH AN ADDRESSABLE MODULE. REFER TO FIRE PROTECTION/PLUMBING PLANS FOR LOCATION OF EACH LOCATION. DIGITAL COMMUNICATOR FOR CENTRAL STATION MONITORING. CONDUIT AND COMMUNICATIONS CABLING FOR CENTRAL STATION REPORTING. FIRE ALARM TERMINAL CABINETS (FATC) WILL BE FACTORY MANUFACTURED, UL LABELED PANELS. THE FATC WILL ENCLOSE ALL TERMINATIONS FOR DEVICES ON THE FLOOR OR AREA IT SERVES. INTELLIGENT CARDS AS REQUIRED OR INDEPENDENT OPERATION, POWER SUPPLIES AND STANDBY BATTERIES WILL BE PROVIDED AT EACH LOCATION. DUCT SMOKE DETECTOR, FURNISHED BY DIVISION 28. INSTALLED IN DUCT BY DIVISION 23. CONNECTED, WIRED AND TESTED BY DIVISION 28. REFERENCE MECHANICAL CONTROL DIAGRAMS FOR MECHANICAL INTERCONNECTIONS. PROVIDE DUCT DETECTORS IN NEW AND EXISTING UNITS WHERE 2000CFM AND ABOVE EXIST. INSTALL PER CODE. FIRE SMOKE DAMPER. ROUTE 120VAC VIA FIRE ALARM ADDRESSABLE RELAY. TELEPHONE TERMINAL BOARD. PROVIDE NEW ANNUNCIATOR PANEL IN ENTRY VESTIBULE. FIELD COORDINATE EXACT LOCATION. PROVIDE RACEWAY PATH OVERHEAD OR UNDERGROUND TO FATC. FIRE ALARM SYSTEM F.A.C.P. 9200 SERIES. PROVIDE SURGE PROTECTION FOR CIRCUIT TO FIRE ALARM PANEL. RELAY MODULES FOR SHUNT TRIP, AUTO RECALL, ALTERNATE RECALL, AND FIRE CAP. TAMPER SWITCH IN HOT BOX. TERMINATE AS REQUIRED FOR NOTIFICATION OF TAMPERING OF EQUIPMENT. PROVIDE SEPERATE DROP FOR ANALOG CONNECTION TO FIRE ALARM CONTROL PANEL, SHOULD NMSU WISH TO HAVE FACP COMMUNICATION IN THIS FASHION. 12 BASEMENT LEVEL Mark Description Date A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC SHEET TITLE ELECTRICAL GNDING DIAGRAM AND FIRE RISER DIAGRAM L2C-37 120VAC 1 Date E-605 2 3 4 5 6 SHEET 171 OF 187 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING Branch Panel: L1A 0 VA 50 VA 540 VA 360 VA 50 VA 360 VA 1260 VA 720 VA 180 VA 600 VA 180 VA 360 VA 360 VA 900 VA 360 VA 0 VA 540 VA 540 VA 9790 VA 1080 VA 9920 VA 540 VA 9920 VA 180 VA 360 VA 1080 VA 1080 VA 1080 VA 1080 VA 540 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 0 VA 1080 VA 1080 VA 1080 VA 1080 VA 1500 VA 8080 VA 1500 VA 6660 VA 1080 VA 6660 VA 1500 VA 1500 VA 1500 VA 1500 VA 100 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 26140 VA 218 A 31910 VA 272 A 180 VA 30680 VA 261 A TYPE A1Fl A1FlE A1Sl 277 0R 120 MULTI TAP (UNV.) RECESSED GYP. BOARD 277 0R 120 MULTI TAP (UNV.) C D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt B CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Circuit Description MTR SCV3 UNITS WEST NC GRADUATE STUDENT OFFICE... REC MAE OFFICE 124 REC Room 125, H121, H102 NC GRADUATE STUDENT OFFICE... REC VESTIBULE H122 REC MAE STUDENT LOUNGE 125 REC MAE OFFICE 136 REC Room 149B, 149A REC MAE OFFICE 124 REC Room H102, 125 REC Room H149, H102, H122 REC Room 136, 134 REC Room 132, 130, 134 REC Room 134, 132 REC Room 126, 124 Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Load Classification NC MTR REC Pole s Trip 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 ----------------------------------Total Load: Total Amps: A 700 VA B C 180 VA 180 VA 900 VA 360 VA 900 VA 360 VA 180 VA 360 VA 540 VA 540 VA 540 VA 540 VA 540 VA 720 VA 180 VA 180 VA 360 VA A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 84 540 VA 720 VA 720 VA 1080 VA 720 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 720 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 8080 VA 67 A Connected Load 720 VA 700 VA 19980 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 6660 VA 56 A Demand Factor 100.00% 100.00% 75.03% 0 VA 0 VA 6660 VA 56 A Estimated Demand 720 VA 700 VA 14990 VA Pole s 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ------------------ Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------------------ CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 NONE PRISMATIC A12.125 LED 3500K 4000 LUMEN 40W LED DRIVER RECESSED GYP. BOARD LED 3500K 4000 LUMEN 40W LED DRIVER SURFACE MOUNT OR STEM SUSPENEDED LED 3500K 3000 LUMEN LED 3500K 3000 LUMEN LED 3500K 3000 LUMEN LED DRIVER NONE LED DRIVER NONE LED DRIVER via BATTERY INVERTER 3000 LUMEN LED, LP835, 80CRI, 3500K 30W LED DRIVER via BATTERY INVERTER MANUFACTURER/MODEL LITHONIA #RTL4-40L-D41-LP835-NX-DGA14 CREE #CR14-40L-35K-S PHILIPS #1DL-G-41L-835-4-D-UNV METALUX #14EN-LD1-51-UNV-L835-CD1-U DF-14W-U PRISMATIC LITHONIA #RTL4-40L-D41-LP835-NX-DGA14 A12.125 CREE #CR14-40L-35K-S PHILIPS #1DL-G-41L-835-4-D-UNV METALUX #14EN-LD1-51-UNV-L835-CD1-U DF-14W-U PEARLESCENT KENALL #ES12-48-1-90L35K-DCC-1-DV-2H-PP POLYCARBONATE LUMINAIRELED#VPF8-4-25-3500-120-277-OP-WHT-JB NEWSTAR#VIC4W-L3-35-1-RW-UN-WH PEARLESCENT KENALL #ES12-96-1-90L35K-DCC-1-DV-2H-PP POLYCARBONATE LUMINAIRELED#VPF8-4-25-3500-120-277-OP-WHT NEWSTAR#VIC4W-L3-35-1-RW-UN-WH PEARLESCENT KENALL #ES12-96-1-90L35K-DCC-1-DV-2H-PP POLYCARBONATE LUMINAIRELED#VPF8-4-25-3500-120-277-OP-WHT-EMB72 2 NEWSTAR#VIC4W-L3-35-1-RW-UN-WH WHITE ACRYLIC CREE #CR22-31L-35K-10V PHILIPS #2STG-30-L835-2-D-UNV METALUX #22EN-LD1-30-UNV-L835-CD1-U LITHONIA #2FSL2-30L-LP835 METALUX # 24SR-LD1-29-C-UNV-L835-CD1 1,2,3 RECESSED T-BAR Al2E 2' x 2' X 4 3/8" RECESSED LED VOLUMETRIC LUMINAIRE, COLD ROLLED STEEL HOUSING, BAKED WHITE ENAMEL FINISH WITH MODULAR FIELD UPGRADEABLE LEDS AND DRIVERS. EMERGENCY THROUGH LIGHTING INVERTER. 277 0R 120 MULTI TAP (UNV.) RECESSED T-BAR 3000 LUMEN LED, LP835, 80CRI, 3500K 30W LED DRIVER via BATTERY INVERTER WHITE ACRYLIC CREE #CR22-31L-35K-10V PHILIPS #2STG-30-L835-2-D-UNV METALUX #22EN-LD1-30-UNV-L835-CD1-U LITHONIA #2FSL2-30L-LP835 METALUX # 24SR-LD1-29-C-UNV-L835-CD1 1,2,3 ARlD 2' X 4' X 4 3/8" RECESSED LED VOLUMETRIC LUMINAIRE, COLD ROLLED STEEL HOUSING, BAKED WHITE ENAMEL FINISH. LINEAL FACETED REFLECTOR. EXTRUDED LENS WITH OPTICAL FILM. 0-10V DIMMABLE WITH MODULAR FIELD UPGRADEABLE LEDS AND DRIVERS 277 0R 120 MULTI TAP (UNV.) RECESSED T-BAR LED 3500K 4800 LUMENS 48W LED DRIVER 0-10V DIMMING NONE WHITE ACRYLIC CREE #CR24-50L-35K-10V LITHONIA #2FSL4-48L-LP835 PHILIPS #2STG-50-L835-4-D-UNV METALUX #24EN-LD1-49-UNV-L835-CD1-U 1,2,3 ARlDE 2' x 4' X 4 3/8" RECESSED LED VOLUMETRIC LUMINAIRE, COLD ROLLED STEEL HOUSING, BAKED WHITE ENAMEL FINISH. LINEAL FACETED REFLECTOR. EXTRUDED LENS WITH OPTICAL FILM. 0-10V DIMMABLE WITH MODULAR FIELD UPGRADEABLE LEDS AND DRIVERS. EMERGENCY THROUGH LIGHTING INVERTER. 277 0R 120 MULTI TAP (UNV.) RECESSED T-BAR LED 3500K 4800 LUMENS 48W LED DRIVER 0-10V DIMMING via BATTERY INVERTER WHITE ACRYLIC CREE #CR24-50L-35K-10V LITHONIA #2FSL4-48L-LP835 PHILIPS #2STG-50-L835-4-D-UNV METALUX #24EN-LD1-49-UNV-L835-CD1-U 1,2,3 4' GENERAL PURPOSE LED LIGHT STRIP FIXTURE, DIE FORMED STEEL HOUSING, BAKED WHITE ENAMEL FINISH, WITH DIFFUSING LENS. 277 0R 120 MULTI TAP (UNV.) SURFACE CEILING OR BOTTOM LED OF JOISTS 3500K 3000 LUMENS LED DRIVER 1,2,3 4' GENERAL PURPOSE LED LIGHT STRIP FIXTURE, DIE FORMED STEEL HOUSING, BAKED WHITE ENAMEL FINISH, WITH DIFFUSING LENS. EMERGENCY THROUGH LIGHTING INVERTER. 277 0R 120 MULTI TAP (UNV.) WALL MOUNTED 8'-0"AFF OR LED SURFACE CEILING OR BOTTOM 3500K OF JOISTS 3000 LUMENS LED DRIVER LITHONIA #ZL2N-L48-3000LM-MDD-MVOLT-35K 80CRI-WH, COLUMBIA #LCL4-35-LW-EU, PHILIPS #LF-4-10-31-35-U-LAG, METALUX #SNLED-LD1-32-UNV-L835-CD1-U-WN/SNF-4FT-B LITHONIA #ZL2N-L48-3000LM-MDD-MVOLT-35K 80CRI-WH METALUX #SNLED-LD1-32-UNV-L835-CD1-U-WN/SNF-4FT-B COLUMBIA #LCS4-35-LW-EU PHILIPS #LF-4-10-31-35-U-LAG 4' EXTREME ENVIRONMENT LED HIGH ENERGY EFFICIENT LOW PROFILE ENCLOSED LUMINAIRE. INDOOR / OUTDOOR VANDAL RESISTANT WITH WIDE DISTRIBUTION. 277 0R 120 MULTI TAP (UNV.) WALL MOUNTED 8'-0"AFF OR LED SURFACE CEILING OR BOTTOM 3500K OF JOISTS IF 10'-0" AFF OR 4000 LUMENS LOWER. IF CEILING OR STRUCTURE IS HIGHER THAN 10'-0", ROD MOUNT SO BOTTOM OF FIXTURE IS AT 10'-0". LED DRIVER C6lE E1 EXIST.2 FLl 6" ROUND LED DOWN LIGHT WITH SEMI-SPECULAR CLEAR REFLECTOR, WHITE TRIM RING. UL LISTED FOR FEED THROUGH WIRING. 0-10V DIMMABLE. 277 0R 120 MULTI TAP (UNV.) RECESSED CEILING 6" ROUND LED DOWN LIGHT WITH SEM-SPECULAR CLEAR REFLECTOR, WHITE TRIM RING. UL LISTED FOR FEED THROUGH WIRING. 0-10V DIMMABLE. EMERGENCY THROUGH LIGHTING INVERTER. LED EXIT SIGN, EMERGENCY, DIE CAST ALUMINUM HOUSING WITH GREEN CHARACTERS, BLACK HOUSING AND BRUSHED ALUMINUM FACE (SINGLE FACE AND DIRECTIONAL ARROWS AS INDICATED ON LIGHTING PLANS). MEETS UL LISTINGS FOR THIS TYPE OF LUMINAIRE. WITH SELF-CONTAINED, SELF DIAGNOSING, NICKEL-CADIUM EMERGENCY BATTERY PACK. 277 0R 120 MULTI TAP (UNV.) RECESSED CEILING EXISTING LUMINAIRE 277 0R 120 MULTI TAP (UNV.) 277 0R 120 MULTI TAP (UNV.) 8"H x 6-5/8W x 4"D, SLIM, LOW PROFILE ONE PIECE DIE CAST HOUSING. EXTERNAL FINS TO EXTRACT HEAT FROM LUMINAIRE. SILOCONE SEALED OPTICAL CHAMBER WITH IMPACT RESISTANT TEMPERED GLASS LENS, FUL CUT OFF. WHITE HOUSING 277 0R 120 MULTI TAP (UNV.) NONE via TO BATTERY INVERTER via BATTERY INVERTER LED 3500K 1500 LUMENS LED DRIVER 0-10V DIMMING NONE LED 3500K 1500 LUMENS LED DRIVER 0-10V DIMMING via BATTERY INVERTER UNIVERSAL SURFACE WALL AT LED 8'-6"AFF OR CEILING POLE 16'-0" NONE LED 5100K 9000 LUMENS (177W) EXTERIOR WALLSURFACE. SEE 2300 LUMEN ARCHITECTURAL ELEVATIONS LED, LP835, FOR HEIGHTS 80CRI, 3500K LED DRIVER INTEGRAL ELECTRONIC LED DRIVER LED DRIVER NICKEL CADMIUM PER MFG. NONE via BATTERY INVERTER WHITE ACRYLIC WHITE ACRYLIC POLYCARBONATE LITHONIA #FEM4-LED-4L/35-IMAFL LENS FAIL-SAFE #HVL8-4-LD3-2LO-35-UNV-O-ED1C COLUMBIA #LXEM4-35LW-RFA-EU DAY-BRITE #DWPE43L835-4-UNV NONE GOTHAM #EVO-35/22-6AR-MVOLT LITON #LHALD625-151-B60-T35 PRESCOLITE #LF6LED7G4-6LFLED7G435KWHWT PORTFOLIO #LD6A20D010TE-ERM6A20835-6LM0LI-HB26 NONE GOTHAM #EVO-35/22-6AR-MVOLT LITON #LHALD625-151-B60-T35 PRESCOLITE #LF6LED7G4-6LFLED7G435KWHWT PORTFOLIO #LD6A20D010TE-ERM6A20835-6LM0LI-HB26 BRUSHED LITHONIA #LE-S-1-G-ELN-SD ALUMINUM FACE SURE-LITES #CX7-1-G-SD DUALLITE #SE-S-G-BNE-I MULE LIGHTING #MD B 1 G BA SD FLAT, CLEAR, HIGH IMPACT, TEMPERED GLASS IMPACT RESISTANT TEMPERED GLASS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 1,2,3 277 0R 120 MULTI TAP (UNV.) SURFACE MOUNT OR STEM SUSPENEDED E CONSULTANTS 2' x 2' X 4 3/8" RECESSED LED VOLUMETRIC LUMINAIRE, COLD ROLLED STEEL HOUSING, BAKED WHITE ENAMEL FINISH WITH MODULAR FIELD UPGRADEABLE LEDS AND DRIVERS SURFACE MOUNT OR STEM SUSPENEDED 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com NOTES Al2 C6l Circuit Description NC GRADUATE STUDENT OFFICE... REC Room 125, S120 REC MAE OFFICE 138 NC GRADUATE STUDENT OFFICE... REC MECHANICAL M123 REC MECHATRONICS LAB 133 REC MAE OFFICE 136 REC MAE OFFICE 130 REC MAE OFFICE 130 REC Room 149A, 149B REC Room 136, 138 REC Room 149A, H102, R140, R142 REC Room 132, 130, 128 REC Room 128, 124, 126 REC Room 130, 128 REC Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space LENS 8" x 4' SURFACE MOUNTED LED LIGHT FIXTURE. COLD ROLLED STEEL HOUSING AND PEARLESCENT POLYCARBONATE LENS. EMERGENCY THROUGH BATTERY INVERTER Branch Panel: L1AA Volts: Phases: Wires: Spaces: EM. BAT. PK. A1SlE BVlE CORRIDOR H102 L1A Surface Type 1 BALLAST TYPE 8" x 4' SURFACE MOUNTED LED LIGHT FIXTURE. COLD ROLLED STEEL HOUSING AND PEARLESCENT POLYCARBONATE LENS. BlE Location: Supply From: Mounting: Enclosure: LAMPS A1Sl1 Bl Notes: - Skirt: Top & bottom MOUNTING CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 1,2,3 1,2,3 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 1,2,3 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 D HN F. H E C K ST A TE O F 88730 VA 71375 VA 246 A 198 A 1' x 4' LED LIGHT FIXTURE, LOW PROFILE (MAXIMUM OF 3 11/16" DEEP) SPECIFICATION GRADE TROFFER, COLD ROLLED STEEL HOUSING, BAKED WHITE ENAMEL FINISH, FLAT STEEL DOOR FRAME 1' x 4' ARCHITECTURAL LED HIGH ENERGY EFFICIENT TROFFER LUMINAIRE. WIDE DISTRIBUTION, RECESSED, LOW PROFILE WITH STEP DIMMING CONTROL. EMERGENCY THROUGH LIGHTING INVERTER. 8" X 8' SURFACE MOUNTED LED LIGHT FIXTURE. COLD ROLLED STEEL HOUSING AND PEARLESCENT POLYCARBONATE LENS. VOLTS 277 0R 120 MULTI TAP (UNV.) 277 0R 120 MULTI TAP (UNV.) 277 0R 120 MULTI TAP (UNV.) Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: DESCRIPTION IV Estimated Demand 1310 VA 27425 VA 9800 VA 32840 VA CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 NO. 12498 RE Demand Factor 100.00% 125.00% 100.00% 58.98% Circuit Description REC MECHANICAL M002 ELECTRICAL ROOM E127 CON CON DATA ROOM T165 REC REC CORRIDOR H161 REC CONFERENCE ROOM 116 REC MAE SEMINAR 113 REC Room R151, 101B LBAA --CON Room R140, R142 REC Room 110, 112 REC Room 114, 116 REC Room 114, 116 REC Room 105A, 105 REC Room 109, 105 REC Room 110, 108 Spare REC Room 104B, 104A, 106 REC Room 105A, 105 L1AA --CU-8/ACU-8 -Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space EW N Connected Load 1310 VA 21940 VA 9800 VA 55680 VA 0 VA Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 225 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 225 A --30 A -20 A 20 A 20 A 20 A 20 A ---------- D PRO EE R C M EX I F E S S I ONA GI N 0 VA B ELECTRICAL LUMINAIRE SCHEDULE R EG I S T E Load Classification NC CON MTR REC A Pole s 1 1 1 1 1 1 1 1 1 3 --1 1 1 1 1 1 1 1 1 1 3 --2 -1 1 1 1 1 ---------- EN D Circuit Description MTR Room 015, 013, 011, 009, 005,... CON WOMEN R151 CON CON MEN R153 REC Room 117D, 113, 115 REC BREAK ROOM 105A REC Room S117B, 117C, S117A REC CONFERENCE ROOM 116 NC DATA ROOM T165 -REC Room H117, H100 REC MAE SEMINAR 113 CON REC Room 113, 111, 115 REC Room S117B, 117C, 117D,... CON VESTIBULE H117 REC Room 109, 105 REC Room 110, 112 REC Room 113, 111, 109 REC Room 104B, 104 REC Room 106, 104B REC Room 108, 106 CU-7/ACU-7 -REC Room 104, 104B, 104A CU-1/ACU-1 -MTR MECHANICAL M123 Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space CON Pole s Trip 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 2 --20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 30 A 2 --20 A 1 30 A 2 --20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 ------------------20 A 1 Total Load: Total Amps: A.I.C. Rating: 10000 Mains Type: Mains Rating: 400 A MCB Rating: 300 A 120/208 Wye 3 4 84 CO E CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Volts: Phases: Wires: Spaces: ELECTRICAL ROOM E127 T1B Surface Type 1 JO Location: Supply From: Mounting: Enclosure: LUMINAIRE SCHEDULE NOTES: 1. MANUFACTURERS CATALOG NUMBERS REPRESENT MANUFACTURER SERIES. SHOP DRAWING SUBMITTALS WILL INCLUDE ALL PART NUMBERS REPRESENTING ALL ITEMS OF THIS LUMINAIRE SCHEDULE. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ORDER LUMINAIRES TO INCLUDE ALL PARTS INDICATED ON SCHEDULE FOR EACH LUMINAIRE. SUBMITTAL WILL CALL OUT EACH PART CLEARLY. 2. LUMINAIRE REQUIRES MOUNTING COORDINATION WITH ARCHITECT PRIOR TO COMMENCEMENT OF ANY WORK. THIS LUMINAIRE MAY REQUIRE A HIGHER OR LOWER MOUTING FROM THAT PROVIDED ON THIS SCHEDULE OR NOTES ON PLAN DUE TO ARCHITECTURAL REQUIREMENTS OR CONSTRUCTION CONDITIONS. 3. ALL LUMINAIRES ON THIS LUMINAIRE SCHEDULED ARE APPROVED FOR BID ON THIS PROJECT. IF A LUMINAIRE IS SUBMITTED THAT IS NOT ON THIS SCHEDULE IT WILL BE REJECTED. L 1,3,4 PROJECT 1,2,3 New Mexico State University 1,2,3 Jett Hall and Jett Annex Renovations and Additions C 1,2,3 1,2,3 KIM #WP9 LE2 5K120 1,2,3 LUMARK #XTOR3A-N RAB #SLIM26NW DECO#VINCI-LED-30-35-UNV EVOY#DLC-LWP30-3500K 1,2,3 Construction Documents KEYPLAN B PANEL L1A ELECTRICAL LUMINAIRE SCHEDULE PANEL L1AA Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 21400 VA 16410 VA 59 A 46 A Notes: - Skirt: Top & Bottom Mark Date Description Date A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 9/15/2015 7:21:17 PM SHEET TITLE ELECTRICAL SCHEDULES E-701 1 2 3 4 5 6 SHEET 172 OF 187 Circuit Description REC MECHATRONICS LAB 133 REC MECHATRONICS LAB 133 REC MECHATRONICS LAB 133 REC MECHATRONICS LAB 133 REC MECHATRONICS LAB 133 REC MECHATRONICS LAB 133 Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Trip Poles 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 ----------------Total Load: Total Amps: Load Classification REC A 360 VA 360 VA Poles 1 360 VA 360 VA 1 360 VA 360 VA 1 360 VA 360 VA 1 360 VA 360 VA 1 360 VA 0 VA 1 0 VA 0 VA 1 0 VA 0 VA 1 0 VA 0 VA 1 0 VA 0 VA 1 0 VA 0 VA 1 0 VA 0 VA 1 0 VA 0 VA 1 0 VA 0 VA -0 VA 0 VA -0 VA 0 VA -0 VA 0 VA -0 VA 0 VA -0 VA 0 VA -0 VA 0 VA -0 VA 0 VA -1440 VA 1440 VA 1080 VA 12 A 12 A 9A Connected Load 3960 VA B C Demand Factor 100.00% Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A --------- Circuit Description REC MECHATRONICS LAB 133 REC MECHATRONICS LAB 133 REC MECHATRONICS LAB 133 REC MECHATRONICS LAB 133 REC MECHATRONICS LAB 133 Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Estimated Demand 3960 VA CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 3960 VA 3960 VA 11 A 11 A Branch Panel: L1A3 Volts: Phases: Wires: Spaces: MDF 137A LDB1A Surface Type 1 Circuit Description REC MDF 137A REC MAE COMPUTER (GRADUAT... REC MAE COMPUTER (GRADUAT... REC MDF 137A REC MDF 137A REC MDF 137A REC MDF 137A Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Trip Poles A 20 A 1 180 VA 360 VA 20 A 1 20 A 1 20 A 1 360 VA 360 VA 20 A 1 20 A 1 20 A 1 360 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 --0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 1620 VA Total Amps: 14 A Load Classification CON REC Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: D Location: Supply From: Mounting: Enclosure: A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 Connected Load 720 VA 4500 VA A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 B 720 VA C 720 VA 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1800 VA 15 A Demand Factor 125.00% 100.00% Poles 1 1 720 VA 720 VA 1 2 -360 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -1800 VA 15 A Estimated Demand 900 VA 4500 VA Trip 20 A 20 A 20 A 20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Location: Supply From: Mounting: Enclosure: Circuit Description CON MDF 137A REC MAE COMPUTER (GRADUAT... REC MAE COMPUTER (GRADUAT... CON MDF 137A -Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 360 VA C 360 VA Poles 1 1 Trip 20 A 20 A Circuit Description REC AUTONOMOUS SYSTEMS LA... REC AUTONOMOUS SYSTEMS LA... 1 1 1 1 1 1 1 1 1 -------- 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A -------- REC AUTONOMOUS SYSTEMS LA... REC AUTONOMOUS SYSTEMS LA... Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space -- -- Space -- -- Space 360 VA 360 VA 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1440 VA 13 A Demand Factor 100.00% 0 VA 0 VA 360 VA 3A Estimated Demand 3240 VA CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 3240 VA 3240 VA 9A 9A Notes: - Skirt: Top D Branch Panel: L1A6 Volts: Phases: Wires: Spaces: MAE MATERIALS LAB 147 LDB1A Surface Type 1 A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 Location: Supply From: Mounting: Enclosure: Volts: Phases: Wires: Spaces: MAE CAPSTONE PROJECT... LDB1A Surface Type 1 A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 HN F. H E C K ST A TE O F Location: Supply From: Mounting: Enclosure: 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com IV A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 Connected Load 3240 VA B NO. 12498 RE Volts: Phases: Wires: Spaces: Trip Poles A 20 A 1 360 VA 360 VA 20 A 1 20 A 1 20 A 1 360 VA 360 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 --0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 1440 VA Total Amps: 13 A 5220 VA 5400 VA 14 A 15 A Branch Panel: L1A5 MAE CAPSTONE PROJECT... LDB1A Surface Type 1 Circuit Description REC AUTONOMOUS SYSTEMS LA... REC AUTONOMOUS SYSTEMS LA... REC AUTONOMOUS SYSTEMS LA... REC AUTONOMOUS SYSTEMS LA... REC AUTONOMOUS SYSTEMS LA... Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 EW N Location: Supply From: Mounting: Enclosure: Volts: Phases: Wires: Spaces: R EG I S T E Branch Panel: L1A4 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 ARCHITECTURE • INTERIORS • PLANNING AUTONOMOUS SYSTEMS... LDB1A Surface Type 1 Load Classification REC Notes: - Skirt: Top Notes: - Skirt: Top Van H. Gilbert Architect PC D PRO EE R Volts: Phases: Wires: Spaces: MECHATRONICS LAB 133 LDB1A Surface Type 1 6 M EX I F E S S I ONA GI N E CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 5 Branch Panel: L1A2 Branch Panel: L1A1 Location: Supply From: Mounting: Enclosure: Notes: PROVIDE TOP SKIRT 4 EN 3 CO 2 JO 1 L PROJECT C CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description REC MAE CAPSTONE PROJECTS ... REC MAE CAPSTONE PROJECTS ... REC MAE CAPSTONE PROJECTS ... REC MAE CAPSTONE PROJECTS ... CON MAE CAPSTONE PROJECTS ... Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Trip Poles A B 20 A 1 180 VA 180 VA 20 A 1 360 VA 360 VA 20 A 1 20 A 1 360 VA 2880 VA 30 A 1 2880 VA 0 VA 20 A 1 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 20 A 1 0 VA 0 VA 20 A 1 0 VA 0 VA 20 A 1 --0 VA 0 VA --0 VA 0 VA ----0 VA 0 VA --0 VA 0 VA ----0 VA 0 VA --0 VA 0 VA --Total Load: 3600 VA 3600 VA Total Amps: 30 A 30 A Load Classification CON REC Connected Load 8640 VA 1800 VA Demand Factor 125.00% 100.00% C Poles 1 1 360 VA 2880 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -3240 VA 27 A Estimated Demand 10800 VA 1800 VA Trip 20 A 20 A 30 A 30 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Circuit Description CKT REC MAE CAPSTONE PROJECTS ... 2 REC MAE CAPSTONE PROJECTS ... 4 CON MAE CAPSTONE PROJECTS ... 6 CON MAE CAPSTONE PROJECTS ... 8 Spare 10 Spare 12 Spare 14 Spare 16 Spare 18 Spare 20 Spare 22 Spare 24 Space 26 Space 28 Space 30 Space 32 Space 34 Space 36 Space 38 Space 40 Space 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 9/15/2015 7:21:17 PM A Connected Load 2160 VA B C 360 VA 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 720 VA 6A Demand Factor 100.00% Poles 1 1 360 VA 360 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -720 VA 6A Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ----------- Circuit Description REC MAE MATERIALS LAB 147 REC MAE MATERIALS LAB 147 REC MAE MATERIALS LAB 147 Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Estimated Demand 2160 VA CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 10440 VA 12600 VA 29 A 35 A Location: Supply From: Mounting: Enclosure: Circuit Description REC COMPOSITES LAB 144 REC COMPOSITES LAB 144 REC COMPOSITES LAB 144 REC COMPOSITES LAB 144 REC MAE LAB 146 REC MAE LAB 146 REC MAE LAB 146 Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Load Classification REC CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description REC MAE CAPSTONE PROJECTS ... REC MAE CAPSTONE PROJECTS ... REC MAE CAPSTONE PROJECTS ... REC MAE CAPSTONE PROJECTS ... REC MAE CAPSTONE PROJECTS ... Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Load Classification CON REC 2160 VA 2160 VA 6A 6A Notes: - Skirt: Top Branch Panel: L1A7 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Trip Poles A 20 A 1 360 VA 360 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 ----0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 720 VA Total Amps: 6A Load Classification REC Notes: - Skirt: Top B Circuit Description REC MAE MATERIALS LAB 147 REC MAE MATERIALS LAB 147 REC MAE MATERIALS LAB 147 Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Trip Poles A 20 A 1 360 VA 360 VA 20 A 1 20 A 1 20 A 1 360 VA 600 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 --0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 1680 VA Total Amps: 14 A Connected Load 600 VA 2700 VA B C 180 VA 360 VA 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 900 VA 8A Demand Factor 125.00% 100.00% Poles 1 1 360 VA 360 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -720 VA 6A Estimated Demand 750 VA 2700 VA Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Circuit Description CKT REC MAE CAPSTONE PROJECTS ... 2 REC MAE CAPSTONE PROJECTS ... 4 REC MAE CAPSTONE PROJECTS ... 6 CON MAE CAPSTONE PROJECTS ... 8 Spare 10 Spare 12 Spare 14 Spare 16 Spare 18 Spare 20 Spare 22 Spare 24 Space 26 Space 28 Space 30 Space 32 Space 34 Space 36 Space 38 Space 40 Space 42 New Mexico State University Jett Hall and Jett Annex Renovations and Additions C Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Construction Documents 3300 VA 3450 VA 9A 10 A Notes: - Skirt: Top Branch Panel: L1A8 Volts: Phases: Wires: Spaces: COMPOSITES LAB 144 LDB1A Surface Type 1 Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ----- Poles A 1 360 VA 360 VA 1 1 1 360 VA 360 VA 1 1 1 540 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 -0 VA 0 VA ---0 VA 0 VA ----Total Load: 1980 VA Total Amps: 17 A Connected Load 4320 VA A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 B C 360 VA 0 VA 360 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 900 VA 8A Demand Factor 100.00% Poles 1 1 360 VA 360 VA 1 1 1 360 VA 360 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA -1440 VA 13 A Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ----- Circuit Description REC COMPOSITES LAB 144 REC COMPOSITES LAB 144 REC COMPOSITES LAB 144 REC MAE LAB 146 REC MAE LAB 146 REC COMPOSITES LAB 144 Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space -- Space -- Space Estimated Demand 4320 VA Location: Supply From: Mounting: Enclosure: Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Notes: - Skirt: Top CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Volts: Phases: Wires: Spaces: MAE COMPUTER LAB 004 LDB1A Surface Type 1 Circuit Description REC MAE COMPUTER LAB 004 REC MAE COMPUTER LAB 004 REC MAE COMPUTER LAB 004 Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Load Classification REC Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Poles A 1 360 VA 1080 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ----Total Load: 1440 VA Total Amps: 12 A Connected Load 4320 VA A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 B C 720 VA 720 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1440 VA 12 A Demand Factor 100.00% Poles 1 1 720 VA 720 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 -0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -1440 VA 12 A Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Circuit Description REC MAE COMPUTER LAB 004 REC MAE COMPUTER LAB 004 REC MAE COMPUTER LAB 004 Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space -- Space -- Space Estimated Demand 4320 VA CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 PANEL L1A1 PANEL L1A2 PANEL L1A3 PANEL L1A4 PANEL L1A5 PANEL L1A6 PANEL L1A7 PANEL L1A8 Mark Date Description Date A Panel Totals September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 4320 VA 4320 VA 12 A 12 A KEYPLAN B 4320 VA 4320 VA 12 A 12 A VAN H. GILBERT ARCHITECT PC SHEET TITLE ELECTRICAL SCHEDULES Notes: - Skirt: Top E-702 1 2 3 4 5 6 SHEET 173 OF 187 E CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Branch Panel: L1A10 Volts: Phases: Wires: Spaces: MAE COMPUTER LAB 006 LDB1A Surface Type 1 Circuit Description REC MAE COMPUTER LAB 006 REC MAE COMPUTER LAB 006 REC MAE COMPUTER LAB 006 REC MAE COMPUTER LAB 006 REC MAE COMPUTER LAB 006 REC MAE COMPUTER LAB 006 Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Trip Poles A 20 A 1 360 VA 540 VA 20 A 1 20 A 1 20 A 1 540 VA 360 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 1800 VA Total Amps: 15 A Load Classification REC Connected Load 5400 VA A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 B 720 VA C 720 VA 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1800 VA 15 A Demand Factor 100.00% Poles 1 1 720 VA 720 VA 1 1 1 360 VA 0 VA 1 1 1 0 VA 0 VA 1 1 -0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -1800 VA 15 A Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------------ Circuit Description REC MAE COMPUTER LAB 006 REC MAE COMPUTER LAB 006 REC MAE COMPUTER LAB 006 REC MAE COMPUTER LAB 006 Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Estimated Demand 5400 VA Panel Totals Volts: Phases: Wires: Spaces: MAE COMPUTER SUPPORT... LDB1A Surface Type 1 Circuit Description REC MAE COMPUTER SUPPORT 010 REC MAE COMPUTER SUPPORT 010 REC MAE COMPUTER SUPPORT 010 Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------------ Load Classification REC Poles A B 1 360 VA 360 VA 1 360 VA 1 1 0 VA 0 VA 1 0 VA 1 1 0 VA 0 VA 1 0 VA 1 -0 VA 0 VA -0 VA --0 VA 0 VA -0 VA --0 VA 0 VA -0 VA --0 VA 0 VA -0 VA 720 VA 6A Connected Load 1440 VA A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 C 0 VA 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 360 VA 3A Demand Factor 100.00% 0 VA 360 VA 3A Poles 1 1 1 1 1 1 1 1 1 ------------- Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------------- Location: Supply From: Mounting: Enclosure: Circuit Description REC MAE COMPUTER SUPPORT 010 Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Estimated Demand 1440 VA CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 5400 VA 5400 VA 15 A 15 A Notes: - Skirt: Top 1440 VA 1440 VA 4A 4A Connected Load 16746 VA 4320 VA B 360 VA C 360 VA 993 VA 180 VA 360 VA 4800 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 7053 VA 59 A Demand Factor 100.00% 100.00% Poles 1 1 720 VA 180 VA 1 1 1 993 VA 360 VA 1 1 3 0 VA 4800 VA --1 0 VA 0 VA 1 1 1 0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -7053 VA 59 A Estimated Demand 16746 VA 4320 VA Trip 20 A 20 A 20 A 20 A 30 A 20 A 20 A 50 A --20 A 20 A 20 A 20 A -------- Circuit Description REC THERMAL SCIENCE LAB 016 REC THERMAL SCIENCE LAB 016 REC THERMAL SCIENCE LAB 016 CON ME/AE THERMAL LAB 016 CON HYDRONIC PUMP - LAB 016 REC THERMAL SCIENCE LAB 016 REC THERMAL SCIENCE LAB 016 NC SPECIALTY REC- LAB 016 --Spare Spare Spare Spare Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 21066 VA 21066 VA 58 A 58 A D Volts: Phases: Wires: Spaces: FLIGHT RESEARCH LAB 013 LDB1A Surface Type 1 A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 Location: Supply From: Mounting: Enclosure: Volts: Phases: Wires: Spaces: AEROSPACE STRUCTURAL... LDB1A Surface Type 1 A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 F. H E C K ST A TE O F Branch Panel: L1A14 HN IV Location: Supply From: Mounting: Enclosure: 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com NO. 12498 RE A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 Trip Poles A 20 A 1 360 VA 360 VA 20 A 1 20 A 1 20 A 1 360 VA 540 VA 30 A 2 --20 A 1 180 VA 360 VA 20 A 1 20 A 1 20 A 1 0 VA 4800 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 ----0 VA 0 VA ------0 VA 0 VA ----Total Load: 6960 VA Total Amps: 58 A EW N Volts: Phases: Wires: Spaces: Circuit Description CON ME/AE THERMAL LAB 016 REC THERMAL SCIENCE LAB 016 REC THERMAL SCIENCE LAB 016 REC THERMAL SCIENCE LAB 016 CON COMPRESSOR - LAB 016 -CON HYDRONIC PUMP - LAB 016 REC THERMAL SCIENCE LAB 016 Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 Notes: - Skirt: Top Branch Panel: L1A13 SOLID MECHANICS LAB 015 LDB1A Surface Type 1 Volts: Phases: Wires: Spaces: R EG I S T E Location: Supply From: Mounting: Enclosure: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 ARCHITECTURE • INTERIORS • PLANNING THERMAL SCIENCE LAB 016 LDB1A Surface Type 1 Load Classification NC REC Notes: - Skirt: Top Branch Panel: L1A12 Van H. Gilbert Architect PC Branch Panel: L1A11 Total Load: Total Amps: Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: D Location: Supply From: Mounting: Enclosure: Notes: PROVIDE TOP SKIRT 6 D PRO EE R Location: Supply From: Mounting: Enclosure: 5 M EX I F E S S I ONA GI N Branch Panel: L1A9 4 EN 3 CO 2 JO 1 L PROJECT C CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description REC SOLID MECHANICS LAB 015 REC SOLID MECHANICS LAB 015 REC SOLID MECHANICS LAB 015 REC SOLID MECHANICS LAB 015 REC SOLID MECHANICS LAB 015 REC SOLID MECHANICS LAB 015 REC SOLID MECHANICS LAB 015 Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Trip Poles A 20 A 1 180 VA 360 VA 20 A 1 20 A 1 20 A 1 360 VA 360 VA 20 A 1 20 A 1 20 A 1 180 VA 2880 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 --0 VA 0 VA ------0 VA 0 VA ----Total Load: 4320 VA Total Amps: 36 A Load Classification NC REC Connected Load 8640 VA 3960 VA B 360 VA C 720 VA 360 VA 180 VA 2880 VA 180 VA Poles 1 1 720 VA 1 1 3 2880 VA --- Trip 20 A 20 A 20 A 20 A 30 A --- Circuit Description REC SOLID MECHANICS LAB 015 REC SOLID MECHANICS LAB 015 REC SOLID MECHANICS LAB 015 REC SOLID MECHANICS LAB 015 CON DISCONNECT - LAB 015 --- 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 4140 VA 35 A Demand Factor 100.00% 100.00% 0 VA 0 VA 4140 VA 35 A Estimated Demand 8640 VA 3960 VA 1 1 1 1 1 1 1 ----- 20 A 20 A 20 A 20 A 20 A 20 A 20 A ----- Spare Spare Spare Spare Spare Spare Spare Space Space Space Space -- -- Space -- -- Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 12600 VA 12600 VA 35 A 35 A D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 9/15/2015 7:21:17 PM A Connected Load 50400 VA 1080 VA Demand Factor 100.00% 100.00% Estimated Demand 50400 VA 1080 VA Trip 20 A 70 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Circuit Description REC FLIGHT RESEARCH LAB 013 NC AC MOTOR - LAB 013 --Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Location: Supply From: Mounting: Enclosure: Space Space Load Classification NC REC Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ----- Circuit Description REC REC Room 009 WATER HEATER - LAB 009 REC AEROSPACE STRUCTURAL... Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space 51480 VA 51480 VA 143 A 143 A Trip Poles A 20 A 1 0 VA 180 VA 20 A 1 30 A 1 20 A 1 180 VA 360 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 --0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 720 VA Total Amps: 6A Connected Load 1200 VA 1440 VA B 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA C 540 VA 1200 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 720 VA 6A Demand Factor 100.00% 100.00% 0 VA 0 VA 1200 VA 10 A Estimated Demand 1200 VA 1440 VA Poles 1 1 1 1 1 1 1 1 1 1 1 1 ---------- Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Circuit Description REC AEROSPACE STRUCTURAL... REC AEROSPACE STRUCTURAL... Spare REC AEROSPACE STRUCTURAL... Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 New Mexico State University Jett Hall and Jett Annex Renovations and Additions C Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Construction Documents 2640 VA 2640 VA 7A 7A Notes: - Skirt: Top Branch Panel: LBAA Volts: Phases: Wires: Spaces: NON-LINEAR DYNAMICS &... LDB1A Surface Type 1 Circuit Description REC NON-LINEAR DYNAMICS &... REC MAE COMPUTER SUPPORT... REC MAE COMPUTER SUPPORT... REC MAE COMPUTER SUPPORT... REC NON-LINEAR DYNAMICS &... REC NON-LINEAR DYNAMICS &... REC NON-LINEAR DYNAMICS &... Spare Spare REC MAE COMPUTER SUPPORT... Spare Spare Spare Spare Spare Space Space Space Space CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Load Classification NC REC Notes: - Skirt: Top Branch Panel: L1A15 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Trip Poles A B C Poles 20 A 1 180 VA 180 VA 1 20 A 1 360 VA 4800 VA 3 20 A 1 360 VA 4800 VA -200 A 3 12000 VA 4800 VA ---12000 VA 0 VA 1 --12000... 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -Total Load: 17160 VA 17160 VA 17160 VA Total Amps: 143 A 143 A 143 A Load Classification NC REC Notes: - Skirt: Top B Circuit Description REC FLIGHT RESEARCH LAB 013 REC FLIGHT RESEARCH LAB 013 REC FLIGHT RESEARCH LAB 013 NC AC MOTOR - LAB 015 --Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Poles 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 --------Total Load: Total Amps: A 180 VA 360 VA 540 VA B C 180 VA 360 VA 1500 VA 360 VA 360 VA 540 VA 360 VA 360 VA 0 VA 0 VA 0 VA Connected Load 3000 VA 4680 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 2520 VA 21 A A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 2580 VA 22 A Demand Factor 100.00% 100.00% Poles 1 2 360 VA 1500 VA -1 1 360 VA 360 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA -2580 VA 22 A Estimated Demand 3000 VA 4680 VA Trip 20 A 20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ----- Location: Supply From: Mounting: Enclosure: Circuit Description REC NON-LINEAR DYNAMICS &... NC SPECIALTY REC - LAB 007 -REC NON-LINEAR DYNAMICS &... REC MAE COMPUTER SUPPORT... REC NON-LINEAR DYNAMICS &... REC NON-LINEAR DYNAMICS &... Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space -- Space -- Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Volts: Phases: Wires: Spaces: CORRIDOR H002 L1A Surface Type 1 Circuit Description NC WOMEN R001 REC Room M017B, H017, H002 REC Room S017A, 012 REC REC OFFICE 011 REC OFFICE 011 REC OFFICE 011 REC Room J003, R001 REC Room T005, H017 REC OFFICE 011 NC CORRIDOR H002 Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A Poles A 1 50 VA 360 VA 1 1 1 720 VA 900 VA 1 1 1 360 VA 360 VA 1 1 1 540 VA 6500 VA 1 Total Load: Total Amps: Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Notes: - Skirt: Top 7680 VA 7680 VA 21 A 21 A Load Classification NC CON REC 9790 VA 82 A Connected Load 50 VA 19500 VA 10080 VA B 720 VA 360 VA 540 VA A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 C Poles 1 1440 VA 1 1080 VA 1080 VA 1 1 360 VA 1 360 VA 360 VA 1 1 6500 VA 3 540 VA 6500 VA --- Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 100 A --- Circuit Description REC CHASE 001B REC Room 009 REC Room S017A, H002, S018A REC Room 012, M002 REC DATA T005 REC OFFICE 011 REC DATA T005 CON ELEV EQUIP M017B --- 0 VA 9920 VA 83 A Demand Factor 100.00% 125.00% 99.60% CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 PANEL L1A9 PANEL L1A10 PANEL L1A11 PANEL L1A12 PANEL L1A13 PANEL L1A14 PANEL L1A15 PANEL LBAA Mark Date Description Date 9920 VA 83 A Estimated Demand 50 VA 24375 VA 10040 VA KEYPLAN B A Panel Totals September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 29630 VA 34465 VA 82 A 96 A VAN H. GILBERT ARCHITECT PC SHEET TITLE ELECTRICAL SCHEDULES Notes: - Skirt: Top & Bottom E-703 1 2 3 4 5 6 SHEET 174 OF 187 Circuit Description MTR Room 182, 184, 191, 191B, 193 REC BREAKROOM 179 CON CON REC Room T165, 163, 159G, 159F CON CHME STUDENT... REC Room 159, H161 REC DATA ROOM T165 REC CHME STUDENT... REC DATA ROOM T165 REC CHME STUDENT... REC BREAKROOM 179 REC CHME STUDENT... REC CHME OFFICE 162 REC CHME STUDENT... REC CHME OFFICE 162 REC CHME OFFICE 159E REC CHME OFFICE 159D CON CORRIDOR H161 REC Room 164, 166, 168 REC Room S180, 179 REC Room 162, 164 REC Room 159B, 159A, 159C REC Room 162, 164 REC Room 159B, 159A REC Room 154-1, 152-1 REC Room 158-1, 160 REC Room 152-1, 150 CON REC Room T165, 163, 159G CU-5/ACU-5 -CON CORRIDOR H161 Spare Spare Spare Spare Spare Space Space Space Space Pole s Trip 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 30 A 2 --20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 --------Total Load: Total Amps: 700 VA B C 180 VA 180 VA 1080 VA 360 VA 360 VA 540 VA 720 VA 1260 VA 180 VA 720 VA 1080 VA 1260 VA 180 VA 360 VA 360 VA 360 VA 360 VA 540 VA 540 VA 540 VA 540 VA 540 VA 540 VA 540 VA 180 VA 360 VA 540 VA 540 VA 360 VA 540 VA 540 VA 720 VA 900 VA 540 VA 720 VA 720 VA 900 VA 1080 VA 1080 VA 900 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1440 VA 1080 VA 1080 VA 1080 VA 1440 VA 360 VA 720 VA 1440 VA 720 VA 1500 VA 720 VA 1500 VA 0 VA 0 VA 25 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 16960 VA 143 A 16620 VA 141 A CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description NC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Trip Poles A 20 A 1 180 VA 360 VA 20 A 1 20 A 1 20 A 1 540 VA 180 VA 20 A 1 20 A 1 20 A 1 360 VA 360 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 --0 VA 0 VA ------0 VA 0 VA ----Total Load: 1980 VA Total Amps: 17 A Load Classification NC REC Connected Load 180 VA 5760 VA B 180 VA C 900 VA 180 VA 360 VA 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1980 VA 17 A Demand Factor 100.00% 100.00% Poles 1 1 360 VA 360 VA 1 1 1 360 VA 180 VA 1 1 1 360 VA 360 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA -1980 VA 17 A Estimated Demand 180 VA 5760 VA Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------- Location: Supply From: Mounting: Enclosure: Circuit Description REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 REC CHME COMPUTER LAB 177 Spare REC CHME COMPUTER LAB 177 Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description CON MAE WELDING 182 REC MAE WELDING 182 NC MAE WELDING 182 -Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Trip Poles A 20 A 1 180 VA 360 VA 20 A 1 20 A 2 --0 VA 1920 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 ----0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 2460 VA Total Amps: 21 A Load Classification NC CON REC 5940 VA 5940 VA 16 A 16 A Notes: - Skirt: Top Volts: Phases: Wires: Spaces: MAE WELDING 182 LDB1B Surface Type 1 Connected Load 6120 VA 180 VA 1080 VA A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 B 360 VA C 360 VA 0 VA 1920 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 2640 VA 22 A Demand Factor 100.00% 125.00% 100.00% Poles 1 1 360 VA 1920 VA 3 --0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -2280 VA 19 A Estimated Demand 6120 VA 225 VA 1080 VA Trip 20 A 20 A 30 A --20 A 20 A 20 A 20 A 20 A 20 A ----------- Circuit Description REC MAE WELDING 182 REC MAE WELDING 182 NC MAE WELDING 182 --Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 7380 VA 7425 VA 20 A 21 A Notes: - Skirt: Top D Panel Totals Branch Panel: L1B4 48545 VA 33745 VA 135 A 94 A Location: Supply From: Mounting: Enclosure: Branch Panel: L1B5 Volts: Phases: Wires: Spaces: MAE ROBOTICS LAB 191B LDB1B Surface Type 1 A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 84 Location: Supply From: LDB1B Mounting: Surface Enclosure: Type 1 Volts: Phases: Wires: Spaces: A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 126 F. H E C K ST A TE O NO. 12498 RE Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: HN F Estimated Demand 2545 VA 2250 VA 3700 VA 25250 VA Circuit Description REC BREAKROOM 179 REC CHME OFFICE 168 REC CHME OFFICE 150 CON CHME STUDENT... REC CHME OFFICE 159C REC Room 150, 152-1 REC BREAKROOM 179 CON ELECTRICAL ROOM E167 REC DATA ROOM T165 CON CORRIDOR H161 REC CHME OFFICE-1 156-1 REC Room H161, 168 REC CHME OFFICE-1 156-1 REC CHME OFFICE 159A REC CHME OFFICE 163 REC CHME OFFICE 150 REC Room 178, H103 REC Room J155, 157, R153 REC CHME GRADUATE STUDENT... REC Room 159F, 159G REC Room 166, 168 REC Room 159D, 159E, 159C REC Room 158-1, 160 REC Room 159C, 159E, 159D REC Room 156-1, 158-1 CON CHME STUDENT... REC Room 154-1, 156-1 CON CHME STUDENT... NC BREAKROOM 179 --Spare Spare Spare Spare Spare Spare Spare Space Space Space Space A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 100 A MCB Rating: 120/208 Wye 3 4 42 IV Demand Factor 100.00% 125.00% 100.00% 62.35% 0 VA 0 VA 14965 VA 125 A Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 30 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A ----- Volts: Phases: Wires: Spaces: CHME COMPUTER LAB 177 LDB1B Surface Type 1 ARCHITECTURE • INTERIORS • PLANNING EW N Connected Load 2545 VA 1800 VA 3700 VA 40500 VA 0 VA Pole s 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 --1 1 1 1 1 1 1 ----- Location: Supply From: Mounting: Enclosure: 10000 MCB 400 A 400 A Branch Panel: L1B2 R EG I S T E Load Classification NC CON MTR REC A A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: 120/208 Wye 3 4 84 Van H. Gilbert Architect PC D PRO EE R D Volts: Phases: Wires: Spaces: ELECTRICAL ROOM E167 T1D Surface Type 1 6 JO E CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 5 Branch Panel: L1B1 Branch Panel: L1B Location: Supply From: Mounting: Enclosure: 4 M EX I F E S S I ONA GI N 3 EN 2 CO 1 L Notes: Branch Panel: L1B3 Location: Supply From: Mounting: Enclosure: Notes: PROVIDE TOP SKIRT Volts: Phases: Wires: Spaces: CHME MINATURE CHEMIC... LDB1B Surface Type 1 A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 C CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description REC CHME MINATURE CHEMICAL PILO... REC CHME MINATURE CHEMICAL PILO... REC CHME MINATURE CHEMICAL PILO... REC CHME MINATURE CHEMICAL PILO... NC CHME MINATURE CHEMICAL PILOT... --REC MAE WELDING 182 Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Trip 20 A 20 A 20 A 20 A 20 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------ Pole s A B 1 360 VA 360... 1 360 VA 360 VA 1 1 360 VA 0 VA 3 360 VA 0 VA --0 VA 360... 1 360 VA 0 VA 1 1 0 VA 0 VA 1 0 VA 0 VA 1 1 0 VA 0 VA 1 0 VA 0 VA 1 -0 VA 0 VA -0 VA 0 VA --0 VA 0 VA -0 VA 0 VA Total Load: Total Amps: Load Classification NC REC 1440 VA 12 A Connected Load 720 VA 3420 VA B 1440 VA 12 A Demand Factor 100.00% 100.00% Pole s 1 1 540... 360 VA 3 --0 VA 360 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA -1260 VA 11 A C Estimated Demand 720 VA 3420 VA Trip 20 A 20 A 20 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------- Circuit Description REC CHME MINATURE CHEMICAL PILO... REC CHME MINATURE CHEMICAL PILO... NC CHME MINATURE CHEMICAL PILOT... --REC MAE WELDING 182 REC CHME MINATURE CHEMICAL PILO... Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt Notes: - Skirt: Top 4140 VA 4140 VA 11 A 11 A CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Circuit Description REC REDUCED GRAVITY LAB 191C REC MAE OFFICE 191A REC Room 191A, 191 REC MAE LAB 191 REC MAE ROBOTICS LAB 191B REC REDUCED GRAVITY LAB 191C REC MAE ROBOTICS LAB 191B REC MAE ROBOTICS LAB 191B REC MAE ROBOTICS LAB 191B REC MAE LAB 191 REC Room 191, 191A NC WALKING STATION LAB 191C --Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Load Classification NC REC Pole s Trip 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 30 A 3 ----20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 ------------------------------Total Load: Total Amps: A 180 VA B C 180 VA 540 VA 720 VA 720 VA 1080 VA 540 VA 900 VA 720 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 540 VA 540 VA 540 VA 2400 VA 2400 VA 2400 VA 2400 VA 2400 VA 2400 VA 4100 VA 0 VA 0 VA 4100 VA 4100 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 12320 VA 103 A Connected Load 26700 VA 10440 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 12500 VA 104 A Demand Factor 100.00% 97.89% 0 VA 0 VA 12320 VA 103 A Estimated Demand 26700 VA 10220 VA Pole s 1 1 1 1 1 1 1 1 1 1 3 --3 --1 1 1 1 1 1 1 1 1 1 1 ---------------- PROJECT Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 30 A --60 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------------- Circuit Description REC REDUCED GRAVITY LAB 191C NC COMPUTER STATION - LAB 191B REC REDUCED GRAVITY LAB 191C REC REDUCED GRAVITY LAB 191C REC REDUCED GRAVITY LAB 191C REC MAE ROBOTICS LAB 191B REC MAE ROBOTICS LAB 191B REC MAE ROBOTICS LAB 191B REC Room 191, 191A REC MAE OFFICE 191A NC STATION - LAB 191B --NC IR UNIT- LAB 191B --Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Notes: - Skirt: Top 37140 VA 36920 VA 103 A 102 A CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99 101 103 105 107 109 111 113 115 117 119 121 123 125 Circuit Description REC CHME UNDERGRADUATE LAB 193 NC CHME UNDERGRADUATE LAB 193 NC FLUIDEZCA - LAB 193 REC CHME UNDERGRADUATE LAB 193 NC CHME UNDERGRADUATE LAB 193 -NC VISCOSITY TABLE - LAB 193 NC CHME UNDERGRADUATE LAB 193 --NC INTERACTING TANK W/ PC - LAB 193 REC LAB 193A REC CHME UNDERGRADUATE LAB 193 REC CHME UNDERGRADUATE LAB 193 REC CHME UNDERGRADUATE LAB 193 REC CHME UNDERGRADUATE LAB 193 REC CHME UNDERGRADUATE LAB 193 REC CHME UNDERGRADUATE LAB 193 CHME UNDERGRADUATE LAB 193 CHME UNDERGRADUATE LAB 193 REC Room S196B, 196A NC LIFT MACHINCE - LAB 193 --NC SURPLACE COVER - LAB 193 --NC DISCONNECT - LAB 193 --Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Load Classification Receptacle NC CON REC Trip Poles 20 A 1 20 A 1 20 A 1 20 A 1 30 A 2 --20 A 1 30 A 3 ----20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 30 A 3 ----30 A 3 ----60 A 3 ----20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 ----------------------------------Total Load: Total Amps: A 0 VA B C 180 VA 180 VA 360 VA 540 VA 360 VA 720 VA 360 VA 360 VA 0 VA 360 VA 180 VA 180 VA 180 VA 360 VA 180 VA 0 VA 0 VA 180 VA 360 VA 180 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 540 VA 360 VA 540 VA 540 VA 1920 VA 1920 VA 1920 VA 1920 VA 1920 VA 1920 VA 2000 VA 2000 VA 2000 VA 2000 VA 2000 VA 2000 VA 4000 VA 4000 VA 4000 VA 4000 VA 4000 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20160 VA 168 A Connected Load 720 VA 39300 VA 12000 VA 8460 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 4000 VA 0 VA 20160 VA 168 A Demand Factor 100.00% 100.00% 125.00% 100.00% 0 VA 0 VA 20160 VA 168 A Poles 1 2 -2 -1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 --3 --3 --1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ------------------ Estimated Demand 720 VA 39300 VA 15000 VA 8460 VA Trip 20 A 30 A -30 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A --30 A --60 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------------------ Circuit Description NC ARMFIELD TABLE W/PC LAB 193 NC ARMFIELD HEAT TRANSFER - LAB... -NC CHME UNDERGRADUATE LAB 193 -REC LAB 193A NC FRIDGE - LAB 193 REC CHME UNDERGRADUATE LAB 193 NC PC OFFICE - LAB 193 REC CHME UNDERGRADUATE LAB 193 REC LAB 193A REC CHME UNDERGRADUATE LAB 193 REC CHME UNDERGRADUATE LAB 193 REC CHME UNDERGRADUATE LAB 193 REC CHME UNDERGRADUATE LAB 193 NC REFLUX CONTROL - E LAB 193 PROCESS CONTROL MODULE - LAB 193 CHME UNDERGRADUATE LAB 193 REC CHME UNDERGRADUATE LAB 193 REC LAB 193A CON CHME UNDERGRADUATE LAB 193 --NC DISCONNECT --NC DISCONNECT - LAB 193 --Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space New Mexico State University Jett Hall and Jett Annex Renovations and Additions C Construction Documents KEYPLAN B PANEL L1B PANEL L1B3 PANEL L1B1 PANEL L1B2 PANEL LB4 PANEL L1B5 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Notes: - Skirt: Top A CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 60480 VA 63480 VA 168 A 176 A Mark Date Description Date A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 9/15/2015 7:21:18 PM SHEET TITLE ELECTRICAL SCHEDULES E-704 1 2 3 4 5 6 SHEET 175 OF 187 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING E D A C 180 VA 600 VA 540 VA 180 VA 540 VA 600 VA 3333 VA 5000 VA 360 VA 360 VA 720 VA 6000 VA 180 VA 360 VA 1920 VA 540 VA 1920 VA 1920 VA 360 VA 1920 VA 540 VA 540 VA 2000 VA 180 VA 2000 VA 10080... 0 VA 20960... 360 VA 9360 VA 540 VA 540 VA 1200 VA 0 VA 360 VA 540 VA 540 VA 0 VA 0 VA 0 VA 540 VA 540 VA 720 VA 1200 VA 720 VA 1200 VA 720 VA 1200 VA 1900 VA 1920 VA 1900 VA 1920 VA 1900 VA 1920 VA 1920 VA 1920 VA 1920 VA 1920 VA 1920 VA 1920 VA 2000 VA 2400 VA 2000 VA 2400 VA 2000 VA 2400 VA 3400 VA 7200 VA 3400 VA 7200 VA 3400 VA 7200 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 50213 VA 419 A Connected Load 108813 VA 38600 VA 4680 VA 0 VA 0 VA 50160 VA 418 A 51720 VA 431 A Demand Factor 100.00% 100.00% 100.00% Poles 1 1 1 1 1 1 1 1 2 -1 1 3 --1 1 1 1 1 1 3 --3 --3 --3 --3 --1 1 1 1 1 1 1 1 1 1 1 1 ---------------- Estimated Demand 108813 VA 38600 VA 4680 VA Trip 20 A 20 A 20 A 125 A 20 A 100 A 20 A 20 A 20 A -20 A 20 A 225 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A --20 A --20 A --30 A --100 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------------- Circuit Description NC MILLER RADIATOR - 196 REC STUDENT PROJECTS CENTER 196 NC SHARP ASSEMBLY- 196 NC ROCKWELL DRILLER - 196 NC SWIVEL METAL CUTTER - 196 NC HASS TOOLBOX - 196 REC STUDENT PROJECTS CENTER 196 NC SPECIALTY RECEPTACLE - 196 NC INDUCTION HARDENER - 196 -NC BENCH/GRINDER STATION - 196 REC STUDENT PROJECTS CENTER 196 LM1 --NC MICROWAVE - 196 Spare NC WOOD CUTTER - 196 Spare Spare NC GRINDER STATION - 196 NC ROCKWELL DRILLER - 196 --NC BPR BENDING MACHINE - 196 --NC HOLE PUNCHER - 196 --NC ENCO DRILLER - 196 --NC SHEET STATION - 196 --Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 152093 VA 152093 VA 422 A 422 A Notes: - Skirt: Top Branch Panel: L2B1 Location: Supply From: Mounting: Enclosure: Volts: Phases: Wires: Spaces: CHME RESEARCH LAB 289 LDB2B Surface Type 1 A.I.C. Rating: 10000 Mains Type: Mains Rating: 100 A MCB Rating: 120/208 Wye 3 4 42 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt B CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description REC HAZARDOUS MATERIAL LAB... REC HAZARDOUS MATERIAL LAB... REC HAZARDOUS MATERIAL LAB... NC HAZARDOUS MATERIAL LAB... -NC HAZARDOUS MATERIAL LAB... -- Trip 20 A 20 A 20 A 30 A -20 A -- Poles A 1 180 VA 720 VA 1 1 2 1500 VA 360 VA -2 -0 VA 0 VA B 180 VA 1500 VA C 720 VA 360 VA 0 VA REC HAZARDOUS MATERIAL LAB... Spare Spare Spare Spare Spare Spare Space Space Space Space 20 A 20 A 20 A 20 A 20 A 20 A 20 A ----- 1 1 1 1 1 1 1 ----- Space -- -- Space --Total Load: Total Amps: 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 2760 VA 23 A 2760 VA 23 A Poles 1 1 540 VA 540 VA 1 1 1 720 VA 720 VA 2 -1 360 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA -2880 VA 24 A Trip 20 A 20 A 20 A 20 A 20 A 20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------- Circuit Description REC HAZARDOUS MATERIAL LAB... REC HAZARDOUS MATERIAL LAB... REC HAZARDOUS MATERIAL LAB... REC HAZARDOUS MATERIAL LAB... REC HAZARDOUS MATERIAL LAB... NC HAZARDOUS MATERIAL LAB... -Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Circuit Description NC AERO FLUIDS LAB 194 AERO FLUIDS LAB 194 REC AERO FLUIDS LAB 194 AERO FLUIDS LAB 194 REC STUDENT PROJECTS CENTE... CON AERO FLUIDS LAB 194 --REC REC STUDENT PROJECTS CENTE... REC Room E194B, 194 REC MAE OFFICE 194A REC AERO FLUIDS LAB 194 REC AERO FLUIDS LAB 194 REC AERO FLUIDS LAB 194 REC AERO FLUIDS LAB 194 REC STUDENT PROJECTS CENTE... NC AEROLAB SUPPY - LAB 194 REC MAE OFFICE 194A CON DISCONNECT - LAB 194 --NC DESIGN UNIT - LAB 194 --NC DC POWER SUPPLY - LAB 194 --NC AERO FLUIDS LAB 194 --Spare Spare Spare Spare Spare Spare Space Space Space Space Load Classification NC CON REC A 1800 VA 0 VA B 720 VA C 720 VA 720 VA 1800 VA 360 VA 1800 VA 720 VA 180 VA 180 VA 180 VA 180 VA 180 VA 0 VA 180 VA 0 VA 180 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 360 VA 540 VA 540 VA 540 VA 720 VA 720 VA 720 VA 1500 VA 1920 VA 1500 VA 1920 VA 1500 VA 1920 VA 1920 VA 1920 VA 1920 VA 1920 VA 1920 VA 1920 VA 1920 VA 3600 VA 1920 VA 3600 VA 1920 VA 3600 VA 6800 VA 7200 VA 6800 VA 7200 VA 6800 VA Trip 20 A 20 A 30 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A --20 A --20 A --100 A --- 1 1 1 1 1 1 ----- 20 A 20 A 20 A 20 A 20 A 20 A ----- 7200 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 34340 VA 287 A Connected Load 80520 VA 9540 VA 9360 VA 0 VA 0 VA 32360 VA 270 A Demand Factor 100.00% 125.00% 100.00% 0 VA 0 VA 32720 VA 273 A Estimated Demand 80520 VA 11925 VA 9360 VA Circuit Description CKT REC AERO FLUIDS LAB 194 2 AERO FLUIDS LAB 194 4 NC SPECIALTY RECEPTACLE - LAB... 6 -8 REC STUDENT PROJECTS CENTE... 10 REC AERO FLUIDS LAB 194 12 REC STUDENT PROJECTS CENTE... 14 REC AERO FLUIDS LAB 194 16 REC STUDENT PROJECTS CENTE... 18 REC STUDENT PROJECTS CENTE... 20 REC MAE OFFICE 194A 22 REC AERO FLUIDS LAB 194 24 REC AERO FLUIDS LAB 194 26 REC AERO FLUIDS LAB 194 28 REC AERO FLUIDS LAB 194 30 REC AERO FLUIDS LAB 194 32 REC Room S196B, 196A 34 REC Room S196B, 196A 36 AERO FLUIDS LAB 194 38 NC AERO FLUIDS LAB 194 40 -42 -44 NC AEROSMITH UNIT - LAB 194 46 -48 -50 NC OMEGA WATER SYSTEM - LAB... 52 -54 -56 NC EXCITER - LAB 194 58 -60 -62 64 Spare 66 Spare 68 Spare 70 Spare 72 Spare 74 Spare 76 Space 78 Space 80 Space 82 Space 84 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Load Classification MTR REC 99420 VA 101805 VA 276 A 283 A Notes: - Skirt: Top A 400 VA 1500 VA B 540 VA 50 VA C 1080 VA 720 VA 900 VA 180 VA 180 VA 1080 VA 180 VA 180 VA 180 VA 180 VA 540 VA 1080 VA 540 VA 1080 VA 540 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 0 VA 0 VA 1500 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1500 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 7170 VA 60 A Connected Load 4900 VA 16790 VA 0 VA 7260 VA 61 A Demand Factor 100.00% 79.78% E Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 30 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------------------ 0 VA 7260 VA 61 A Estimated Demand 4900 VA 13395 VA Circuit Description CKT SCV3 UNITS Room 289, 278, 280, 28... 2 REC Room 224, 222 4 REC Room 236, 238, R240 6 REC Room 222, 224 8 REC MAE GRADUATE STUDENT... 10 REC MAE GRADUATE STUDENT... 12 REC MAE GRADUATE STUDENT... 14 REC Room 238, 236 16 REC Room 245, 249 18 REC Room 236, 234 20 REC Room 226, 228 22 REC Room 228, 230 24 REC Room 226, 224 26 CU-10/ACU-10 28 -30 Spare 32 Spare 34 Spare 36 Spare 38 Spare 40 Spare 42 Spare 44 Spare 46 Spare 48 Space 50 Space 52 Space 54 Space 56 Space 58 Space 60 Space 62 Space 64 Space 66 Space 68 Space 70 Space 72 Space 74 Space 76 Space 78 Space 80 Space 82 84 CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 D Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 21690 VA 18295 VA 60 A 51 A Location: Supply From: Mounting: Enclosure: Volts: Phases: Wires: Spaces: Pole s 1 1 1 1 1 1 1 1 1 1 1 1 2 -2 -- Circuit Description REC Room 252, 250 REC Room 254, 252 REC Room 256, 258 REC Room 260, 258, 262 REC Room 264, 262, 268 REC Room 265, 274 REC Room 263, 259 REC Room 259, R253, 251, S257 REC Room H203, 274 REC CHME OFFICE 256 REC MEETING/WAITING ROOM 264 REC CHME OFFICE 252 CU-12/ACU-12 -CU-6/ACU-6 -- Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 30 A -30 A -- A 1080 VA 1080 VA CON Room R253 CON Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space 20 A 1 20 A 1 180 VA 150 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 10890 VA Total Amps: 92 A A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: 120/208 Wye 3 4 84 B C 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 900 VA 900 VA 1080 VA 1080 VA 1080 VA 1080 VA 1080 VA 900 VA 540 VA 540 VA 360 VA 540 VA 540 VA 360 VA 1500 VA 180 VA 1500 VA 0 VA 360 VA Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 30 A -20 A Circuit Description REC Room 252, 250 REC Room 256, 254 REC Room 260, 258 REC Room 264, 262, 260 REC Room 268, 268A, 264 REC Room 265, 274 REC Room 259, 263 REC Room 259, 251, H203 REC CHME OFFICE 250 REC CHME OFFICE 262 REC CHME OFFICE 258 CU-11/ACU-11 -REC ELECTRICAL ROOM E267 1 1 1 1 1 1 1 1 1 1 1 1 --------------- 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A --------------- REC Room H203, 259 REC NC Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space 1500 VA 1500 VA 540 VA Load Classification NC MTR REC Pole s 1 1 1 1 1 1 1 1 1 1 1 2 -1 Connected Load 225 VA 6360 VA 22140 VA 0 VA 0 VA 0 VA 75 VA 540 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 8280 VA 69 A Demand Factor 100.00% 100.00% 72.58% 0 VA 0 VA 9555 VA 81 A Estimated Demand 225 VA 6360 VA 16070 VA CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 ST A TE O EW PRO M EX I F E S S I ONA Jett Hall and Jett Annex Renovations and Additions Volts: Phases: Wires: Spaces: ENERGETIC MATERIAL LA... LDB2B Surface Type 1 Circuit Description REC ENERGETIC MATERIAL LAB... REC ENERGETIC MATERIAL LAB... REC ENERGETIC MATERIAL LAB... REC ENERGETIC MATERIAL LAB... NC ENERGETIC MATERIAL LAB 292 -- Trip 20 A 20 A 20 A 20 A 20 A -- Poles A 1 180 VA 360 VA 1 1 1 720 VA 0 VA 2 -- Total Load: Total Amps: Load Classification NC REC 1260 VA 11 A Connected Load 2160 VA 2520 VA B 360 VA C 360 VA 540 VA 720 VA 720 VA 0 VA 2160 VA 18 A Demand Factor 100.00% 100.00% C A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 100 A MCB Rating: 120/208 Wye 3 4 12 Poles 1 1 720 VA 2 -2 0 VA -- Trip 20 A 20 A 20 A -20 A -- Circuit Description REC ENERGETIC MATERIAL LAB... REC ENERGETIC MATERIAL LAB... NC ENERGETIC MATERIAL LAB 292 -NC ENERGETIC MATERIAL LAB 292 -- 1260 VA 11 A Estimated Demand 2160 VA 2520 VA CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Construction Documents KEYPLAN B Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 4680 VA 4680 VA 13 A 13 A PANEL L1C1 Notes: SKIRT: TOP PANEL L2B1 PANEL L1C2 PANEL L2AA PANEL L2B PANEL L2B2 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 28725 VA 22655 VA 80 A 63 A Mark Notes: Date Description Date Load Classification NC REC Connected Load 4440 VA 3960 VA A Demand Factor 100.00% 100.00% Estimated Demand 4440 VA 3960 VA Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: L New Mexico State University Location: Supply From: Mounting: Enclosure: 10000 MCB 400 A 400 A F. H E C K PROJECT Branch Panel: L2B2 ELECTRICAL ROOM E267 T2D Surface Type 1 HN NO. 12498 D Notes: - Skirt: Top & Bottom Branch Panel: L2B CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Circuit Description SCV3 UNITS Room 244, 248, 233 REC MAE OFFICE 226 REC MAE OFFICE 232 REC MEN R240 REC MAE GRADUATE STUDENT... REC MAE GRADUATE STUDENT... REC MAE GRADUATE STUDENT... REC MAE OFFICE 232 REC MAE OFFICE 238 REC MAE OFFICE 226 REC Room 232, 234 REC Room 234, 232 REC Room 230, 228 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Pole s 1 1 1 1 1 1 1 1 1 1 1 1 1 2 -1 1 1 1 1 1 1 1 1 ------------------ 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com F 0 VA Total Load: Total Amps: Load Classification NC MTR REC B Pole s Trip 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 ------------------------------------Total Load: Total Amps: A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 84 IV Poles 1 1 1 1 1 1 1 2 -1 1 2 -1 1 1 1 1 1 1 1 3 --3 --3 --3 --3 --1 1 1 1 1 1 1 1 1 1 1 1 --------------- Volts: Phases: Wires: Spaces: CORRIDOR H202 L2A Surface Type 1 RE Trip 20 A 20 A 20 A 35 A 20 A 20 A 20 A 20 A -20 A 20 A 30 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A --20 A --20 A --30 A --50 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A --------------- Pole s 1 1 2 -1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 --3 --3 --3 --- Location: Supply From: Mounting: Enclosure: N Circuit Description NC GRINDER MACHINE - 196 NC 6" CARBIDE GRINDER - 196 NC AIRCEL CONDENSER - WELDING... NC MILLING & DRILLING UNIT - 196 REC STUDENT PROJECTS CENTER 196 REC MAE OFFICE 196A NC STUDENT PROJECTS CENTER 196 NC GRINDER MACHINE - 196 -NC BENCH/GRINDER - 196 NC RACINE STATION - 196 NC STEEL STATION - 196 -Spare REC STUDENT PROJECTS CENTER 196 NC SPECIALTY RECEPACTLE - 196 NC REC STUDENT PROJECTS CENTER 196 NC ASSEMBLY- 196 Spare NC REFRIGERATOR - 196 NC STUDENT PROJECTS CENTER 196 --NC SPECIALTY REC- 196 --NC GRINDER MACHINE - 196 --NC DISCONNECT - 196 --NC SPECIALTY REC - 196 --Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Pole s Trip 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 3 ----20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 30 A 3 ----30 A 3 ----50 A 3 ----100 A 3 ----20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 --------Total Load: Total Amps: A.I.C. Rating: 14000 Mains Type: MLO Mains Rating: 400 A MCB Rating: 120/208 Wye 3 4 84 R EG I S T E C CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99 101 103 105 107 109 111 113 115 117 119 121 123 125 Volts: Phases: Wires: Spaces: AERO FLUIDS LAB 194 LDB1C Surface Type 1 EE R Location: Supply From: Mounting: Enclosure: GI N A.I.C. Rating: 14000 Mains Type: MLO Mains Rating: 600 A MCB Rating: 120/208 Wye 3 4 126 EN Volts: Phases: Wires: Spaces: STUDENT PROJECTS... LDB1C Surface Type 1 Branch Panel: L2AA CO Location: Supply From: Mounting: Enclosure: Branch Panel: L1C2 JO Branch Panel: L1C1 8400 VA 8400 VA 23 A 23 A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 9/15/2015 7:21:18 PM SHEET TITLE Notes: SKIRT:TOP & BOTTOM ELECTRICAL SCHEDULES E-705 1 2 3 4 5 6 SHEET 176 OF 187 2 3 GEF-2 REC ON ROOF NC WOMEN R201 REC Room 213, 207, T203 REC Room 213, 215 REC Room E301, M301 L2AA --REC Room 206, 208, 210 REC Room 204, 206, 208, 210 REC Room 210, 216 CU-14/ACU-14 -CU-2/ACU-2 -Spare Spare Space Space Space Load Classification NC MTR REC A B Poles 180 VA 540 VA 1 180 VA 1440 VA 1 360 VA 600 VA 1 1260 VA 1260 VA 1 1080 VA 1500 VA 2 720 VA 1500 VA -7170 VA 1080 VA 1 7260 VA 1080 VA 1 7260 VA 1080 VA 1 1080 VA 1080 VA 1 1080 VA 1080 VA 1080 VA 1 1500 VA 1500 VA 1500 VA 2 1500 VA 1500 VA -1500 VA 0 VA 1 0 VA 0 VA 1 0 VA 0 VA 1 0 VA 0 VA -0 VA 0 VA -0 VA 0 VA -16650 VA 16620 VA 16680 VA 139 A 139 A 139 A Connected Load 360 VA 17080 VA 32510 VA Demand Factor 100.00% 100.00% 65.38% C Estimated Demand 360 VA 17080 VA 21255 VA Trip 20 A 20 A 20 A 20 A 30 A -20 A 20 A 20 A 20 A 20 A 30 A -20 A 20 A 20 A ---- Circuit Description CKT REC MAE OFFICE 217A 2 REC Room 207, T203, S207A, 201B 4 REC CORRIDOR H201 6 REC Room T203, H201, R201, 201A... 8 CU-13/ACU-13 10 -12 REC Room 213, 207, 215 14 REC Room 210, 216 16 REC Room 215, 217A, H217, S217B 18 REC ON ROOF 20 22 REC Room 204, 206, H201 24 26 CU-15/ACU-15 28 -30 Spare 32 Spare 34 Spare 36 Space 38 Space 40 Space 42 49950 VA 38695 VA 139 A 107 A D 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 2900 VA 24 A Demand Factor 100.00% 100.00% Estimated Demand 4720 VA 4320 VA Circuit Description REC COMBUSTION LAB 225 NC COMBUSTION LAB 225 -REC COMBUSTION LAB 225 Spare Spare REC COMBUSTION LAB 225 Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 2160 VA 19 A Connected Load 1080 VA 4140 VA 1980 VA 18 A Demand Factor 100.00% 100.00% Load Classification NC REC 9040 VA 9040 VA 25 A 25 A Trip 20 A 20 A Volts: Phases: Wires: Spaces: 20 A 30 A -- Poles A 1 540 VA 500 VA 1 1 2 -- Total Load: Total Amps: Load Classification MTR REC 360 VA 180 VA 1440 VA 360 VA 540 VA 360 VA 1440 VA 2000 VA 720 VA 360 VA 2000 VA 360 VA 360 VA 2000 VA 360 VA 360 VA 2000 VA 2000 VA 2000 VA 2000 VA 2000 VA 2000 VA 2000 VA 0 VA 2000 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 9800 VA 82 A Connected Load 22720 VA 6660 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 9780 VA 82 A Demand Factor 100.00% 100.00% 0 VA 0 VA 9800 VA 82 A Estimated Demand 22720 VA 6660 VA Poles 1 1 1 1 1 1 1 3 --3 --1 1 1 1 ----- Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 30 A --30 A --20 A 20 A 20 A 20 A ----- Circuit Description CKT REC EXPERIMENTAL METHODS... 2 REC EXPERIMENTAL METHODS... 4 REC EXPERIMENTAL METHODS... 6 REC EXPERIMENTAL METHODS... 8 REC EXPERIMENTAL METHODS -... 10 REC EXPERIMENTAL METHODS... 12 REC EXPERIMENTAL METHODS... 14 NC EXPERIMENTAL METHODS -233 16 -18 -20 NC EXPERIMENTAL METHODS - 233 22 -24 -26 Spare 28 Spare 30 Spare 32 Spare 34 Space 36 Space 38 Space 40 Space 42 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 29380 VA 29380 VA 82 A 82 A Volts: Phases: Wires: Spaces: RENEWABLE ENERGY &... LDB2A Surface Type 1 A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 Location: Supply From: Mounting: Enclosure: HEAT TRANSFER &... LDB2A Surface Type 1 Volts: Phases: Wires: Spaces: A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 HN F. H E C K ST A TE O NO. 12498 D EW PRO M EX I F E S S I ONA L PROJECT Trip 20 A 20 A 20 A 20 A 20 A Circuit Description CKT REC Room 237, 245 2 REC MULTIMEDIA INSTRUCTIONAL LAB... 4 NC MULTIMEDIA INSTRUCTIONAL LAB... 6 NC MULTIMEDIA INSTRUCTIONAL LAB... 8 NC MULTIMEDIA INSTRUCTIONAL LAB... 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description REC RENEWABLE ENERGY - LAB... REC RENEWABLE ENERGY -LAB... REC RENEWABLE ENERGY -LAB... REC RENEWABLE ENERGY-LAB 248 NC RENEWABLE ENERGY- LAB 248 -Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Trip Poles A 20 A 1 180 VA 720 VA 20 A 1 20 A 1 20 A 1 720 VA 360 VA 20 A 2 --20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 --0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 1980 VA Total Amps: 17 A Load Classification NC REC Panel Totals A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: 120/208 Wye 3 4 42 B C 5220 VA 5220 VA 14 A 14 A Connected Load 1440 VA 4320 VA B C 360 VA 540 VA 720 VA 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1980 VA 17 A Demand Factor 100.00% 100.00% Poles 1 1 720 VA 360 VA 1 1 1 720 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -1800 VA 15 A Estimated Demand 1440 VA 4320 VA Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Circuit Description CKT REC RENEWABLE ENERGY-LAB 248 2 REC RENEWABLE ENERGY -LAB... 4 REC RENEWABLE ENERGY-LAB 248 6 REC RENEWABLE ENERGY - LAB... 8 REC RENEWABLE ENERGY-LAB 248 10 Spare 12 Spare 14 Spare 16 Spare 18 Spare 20 Spare 22 Spare 24 Space 26 Space 28 Space 30 Space 32 Space 34 Space 36 Space 38 Space 40 Space 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description REC HEAT TRANSFER- LAB 244 REC HEAT TRANSFER -LAB 244 REC HEAT TRANSFER- LAB 244 REC HEAT TRANSFER -LAB 244 REC HEAT TRANSFER- LAB 244 NC HEAT TRANSFER- LAB 244 --REC HEAT TRANSFER - LAB 244 Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Trip Poles A B C Poles 20 A 1 360 VA 360 VA 1 20 A 1 360 VA 360 VA 1 20 A 1 540 VA 720 VA 1 20 A 1 540 VA 2000 VA 3 20 A 1 540 VA 2000 VA -30 A 3 2000 VA 2000 VA ---2000 VA 0 VA 1 --2000 VA 0 VA 1 20 A 1 360 VA 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -Total Load: 5260 VA 5260 VA 5620 VA Total Amps: 44 A 44 A 47 A Load Classification NC REC 5760 VA 5760 VA 16 A 16 A Connected Load 12000 VA 4140 VA Demand Factor 100.00% 100.00% Estimated Demand 12000 VA 4140 VA Trip 20 A 20 A 20 A 30 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A -------- Circuit Description REC HEAT TRANSFER -LAB 244 REC HEAT TRANSFER- LAB 244 REC HEAT TRANSFER- LAB 244 NC HEAT TRANSFER - LAB 244 --Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 New Mexico State University Jett Hall and Jett Annex Renovations and Additions C Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Construction Documents 16140 VA 16140 VA 45 A 45 A Notes: - Skirt: Top 180 VA Location: Supply From: Mounting: Enclosure: 10000 MCB 225 A 400 A Poles 1 Trip 20 A Circuit Description GFP-1 MECHANICAL ROOM M003 1 2 -- 20 A 30 A -- CON MECHANICAL ROOM M003 CU-4/ACU-4 -- 360 VA 180 VA SUMP PUMP VESTIBULE H001 CU-3/ACU-3 -- C Branch Panel: LM1 ELECTRICAL ROOM E001 T1E Surface Type 1 Circuit Description REC Room E001, H001 REC MECHANICAL ROOM M003 180 VA B Branch Panel: L2A5 Notes: - Skirt: Top Location: Supply From: Mounting: Enclosure: A D 1080 VA 9A Estimated Demand 1080 VA 4140 VA Trip Poles 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 30 A 2 --20 A 1 20 A 1 30 A 3 ----20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 --------Total Load: Total Amps: F Pole Pole s s A B C 1 1080 VA 720... 1 1 900 VA 720 VA 1 1 180... 180 VA 1 1 180 VA 180... 1 1 180 VA 180 VA 1 1 720... Circuit Description REC EXPERIMENTAL METHODS-... REC EXPERIMENTAL METHODS... REC EXPERIMENTAL METHODS... REC EXPERIMENTAL METHODS... EXPERIMENTAL METHODS -233 NC EXPERIMENTAL METHODS -233 -REC EXPERIMENTAL METHODS... REC EXPERIMENTAL METHODS... NC EXPERIMENTAL METHODS - 233 --Spare Spare Spare Spare Spare Space Space Space Space IV Trip 20 A 20 A 20 A 20 A 20 A 20 A Branch Panel: L1BM B CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Notes: Location: Supply From: Mounting: Enclosure: A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 Notes: - Skirt: Top D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt 180 VA Trip 20 A 30 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- RE Circuit Description REC Room 245, H202 REC Room 245, 249 NC MULTIMEDIA INSTRUCTIONAL LAB... NC MULTIMEDIA INSTRUCTIONAL LAB... NC MULTIMEDIA INSTRUCTIONAL LAB... REC MULTIMEDIA INSTRUCTIONAL LAB... Load Classification NC REC 9/15/2015 7:21:18 PM 2000 VA Poles 1 2 900 VA 2000 VA -1 1 180 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -3080 VA 26 A A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 N Volts: Phases: Wires: Spaces: MULTIMEDIA... LDB2A Surface Type 1 Total Load: Total Amps: A 720 VA C Volts: Phases: Wires: Spaces: EXPERIMENTAL METHODS... LDB2A Surface Type 1 R EG I S T E Location: Supply From: Mounting: Enclosure: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Connected Load 4720 VA 4320 VA B Location: Supply From: Mounting: Enclosure: Branch Panel: L2A4 Branch Panel: L2A3 C Trip Poles A 20 A 1 0 VA 360 VA 20 A 1 20 A 1 20 A 1 540 VA 540 VA 20 A 1 20 A 1 20 A 1 720 VA 720 VA 20 A 1 20 A 1 20 A 1 180 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 --0 VA 0 VA ------0 VA 0 VA ----Total Load: 3060 VA Total Amps: 26 A A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 Notes: - Skirt: Top Notes: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description REC COMBUSTION LAB 225 REC COMBUSTION LAB 225 REC Room 237, H221, H202 REC COMBUSTION LAB 225 REC COMBUSTION LAB 225 REC COMBUSTION LAB 225 NC COMBUSTION LAB 225 Spare Spare REC COMBUSTION LAB 225 Spare Spare Spare Spare Spare Space Space Space Space Space Space Load Classification NC REC Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Volts: Phases: Wires: Spaces: COMBUSTION LAB 225 LDB2A Surface Type 1 ARCHITECTURE • INTERIORS • PLANNING EE R Trip Poles 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 225 A 3 ----20 A 1 20 A 1 20 A 1 30 A 2 --30 A 2 --20 A 1 20 A 1 ------Total Load: Total Amps: Location: Supply From: Mounting: Enclosure: 10000 MCB 400 A 400 A Branch Panel: L2A2 GI N Circuit Description A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: 120/208 Wye 3 4 42 Van H. Gilbert Architect PC EN Volts: Phases: Wires: Spaces: ELECTRICAL ROOM E301 112.5 kVA, 277 V/480 V, Thr... Surface Type 1 6 CO E CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 5 Branch Panel: L2A1 Branch Panel: L2A Location: Supply From: Mounting: Enclosure: 4 JO 1 1500 VA 1500 VA 1500 VA 1500 VA 2720 VA 24 A Connected Load 6860 VA 900 VA 3360 VA 29 A Demand Factor 100.00% 100.00% CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description Receptacle MECHANICAL ROOM... CON MECHANICAL ROOM M198 Receptacle MECHANICAL ROOM... Receptacle MECHANICAL ROOM... CON MECHANICAL ROOM M198 CON MECHANICAL ROOM M198 --- Trip 20 A 20 A 20 A 20 A 20 A 20 A --- Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Notes: 7760 VA 7760 VA 22 A 22 A Load Classification MTR REC A.I.C. Rating: 10000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 120/208 Wye 3 4 42 Poles A B C Poles 1 180 VA 180 VA 1 1 1600 VA 3000 VA 3 1 360 VA 3000 VA -1 720 VA 3000 VA -1 10000 VA 360 VA 1 3 3000 VA 3000 VA 3 -3000 VA 3000 VA --3000 VA 3000 VA -- Total Load: Total Amps: 1680 VA 14 A Estimated Demand 6860 VA 900 VA Volts: Phases: Wires: Spaces: MECHANICAL ROOM M198 L1C1 Surface Type 1 10080 VA 85 A Connected Load 38600 VA 1800 VA 20960 VA 176 A Demand Factor 100.00% 100.00% Trip 20 A 20 A --20 A 20 A --- Circuit Description Receptacle MECHANICAL ROOM... CON MECHANICAL ROOM M198 --Receptacle MECHANICAL ROOM... CON MECHANICAL ROOM M198 --- CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 PANEL L2A PANEL L2A1 PANEL L2A2 PANEL L2A3 PANEL L2A4 PANEL L2A5 PANEL L1BM PANEL LM1 Mark Date Description Date 9360 VA 78 A Estimated Demand 38600 VA 1800 VA KEYPLAN B A Panel Totals September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 40400 VA 40400 VA 112 A 112 A VAN H. GILBERT ARCHITECT PC SHEET TITLE ELECTRICAL SCHEDULES Notes: E-706 1 2 3 4 5 6 SHEET 177 OF 187 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING Branch Panel: M1B Trip Poles A B C Poles 20 A 1 480 VA 443 VA 3 20 A 1 960 VA 443 VA -30 A 1 2400 VA 443 VA -20 A 3 1330 VA 5817 VA 3 --1330 VA 5817 VA ---1330 VA 5817 VA -40 A 3 5817 VA 22160... 3 --5817 VA 22160 VA ---5817 VA 22160 VA -20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 20 A 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -Total Load: 36047 VA 36527 VA 37967 VA Total Amps: 130 A 132 A 137 A Load Classification CON MTR Demand Factor 125.00% 100.00% Estimated Demand 43628 VA 75639 VA Circuit Description HRP-3 -MECHANICAL M123 --AHU-3 - MECHANICAL M123 (2) --CON AUTOCLAVE - MATERIALS L... --Spare Spare Spare Spare Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description MTR TERMINAL UNITS NE MTR TERMINAL UNITS EAST Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Trip Poles A 20 A 1 360 VA 420 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 780 VA Total Amps: 3A Load Classification MTR Connected Load 900 VA A.I.C. Rating: 25000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 480/277 Wye 3 4 42 B 120 VA C 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 120 VA 1A Demand Factor 100.00% 0 VA Poles 1 1 1 1 1 1 1 --------------- Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A --------------- Location: Supply From: Mounting: Enclosure: Circuit Description MTR TEMRINAL UNITS NE Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Circuit Description Spare --AHU-4 - ELECTRICAL E194B --VFD - CON AERO FLUIDS LAB 194 --Spare --Space Space Space Space Space Space Space Space Space 0 VA 0A Estimated Demand 900 VA Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 110541 VA 119267 VA 133 A 143 A 900 VA 900 VA 1A 1A A.I.C. Rating: 25000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 480/277 Wye 3 4 42 Trip Poles A B C Poles 30 A 3 0 VA 1080 VA 3 --0 VA 1080 VA ---0 VA 1080 VA -20 A 3 1329 VA 1350 VA 3 --1329 VA 1350 VA ---1329 VA 1350 VA -100 A 3 6214 VA 0 VA 1 --6214 VA 0 VA 1 --6214 VA 0 VA 1 20 A 3 0 VA 0 VA 1 --0 VA 0 VA 1 --0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -Total Load: 9973 VA 9973 VA 9973 VA Total Amps: 36 A 36 A 36 A Load Classification NC MTR Notes: Notes: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Volts: Phases: Wires: Spaces: ELECTRICAL E194B MSB Surface Type 1 Connected Load 18642 VA 11277 VA Demand Factor 100.00% 100.00% Estimated Demand 18642 VA 11277 VA Trip 30 A --20 A --20 A 20 A 20 A 20 A 20 A 20 A ---------- Circuit Description CU-9 --AHU-5 - ME/ AE HYDRAULICS LAB... --Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 29919 VA 29919 VA 36 A 36 A Notes: D Load Classification MTR A 900 VA B 831 VA 831 VA 0 VA 831 VA 0 VA 831 VA 831 VA 831 VA 831 VA 831 VA C 0 VA 831 VA 831 VA 5817 VA 831 VA 5817 VA 831 VA 5817 VA 5817 VA 11080 VA 5817 VA 11080... 5817 VA 11080... 11080... 1000 VA 11080 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 38018 VA 138 A Connected Load 113254 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 11080... 0 VA 0 VA 38118 VA 138 A Demand Factor 100.00% 0 VA 0 VA 37118 VA 134 A Pole s 3 --3 --3 --3 --3 --1 1 1 1 ------------------------ Volts: Phases: Wires: Spaces: ELECTRICAL ROOM E267 HDB2B Surface Type 1 Location: Supply From: Mounting: Enclosure: A.I.C. Rating: 25000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 480/277 Wye 3 4 42 Volts: Phases: Wires: Spaces: ELECTRICAL ROOM E127 HDB1A Surface Type 1 A.I.C. Rating: 25000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 480/277 Wye 3 4 42 D Trip 20 A --20 A --20 A --40 A --70 A --20 A 20 A 20 A 20 A ------------------------ Circuit Description CKT PCP-1 - PENTHOUSE M301 2 -4 -6 VFD-22/EF-3 PENTHOUSE M300 8 -10 -12 VFD-25/EF-6 - PENTHOUSE M300 14 -16 -18 VFD-27/LEF-2 PENTHOUSE M300 20 -22 -24 VFD-21/AHU-1- PENTHOUSE M300 (2) 26 -28 -30 Spare 32 Spare 34 Spare 36 Spare 38 Space 40 Space 42 Space 44 Space 46 Space 48 Space 50 Space 52 Space 54 Space 56 Space 58 Space 60 Space 62 Space 64 Space 66 Space 68 Space 70 Space 72 Space 74 Space 76 Space 78 Space 80 Space 82 Space 84 Estimated Demand 113254 VA CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description MTR CORRIDOR H203 Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Trip Poles A 20 A 1 1100 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 ----0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 1100 VA Total Amps: 4A Load Classification MTR Connected Load 1100 VA B 0 VA C 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0A Demand Factor 100.00% 0 VA Poles 1 1 1 1 1 ----------------- Trip 20 A 20 A 20 A 20 A 20 A ----------------- Circuit Description Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description LTG ME/AE THERMAL LAB 016 LTG Room 017A, 015, 009, 011 Room 104A, 104 LTG Room R151, R101, 105A, 105 LTG Room H117, 117D, 117C, 117B LTG Room 138, 146, R140, H102-2,... LTG Room 137, 137A, 133, 141 Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space 0 VA 0A Estimated Demand 1100 VA Load Classification Lighting LTG Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Trip Poles A 20 A 1 1269 VA 417 VA 20 A 1 20 A 1 20 A 1 986 VA 314 VA 20 A 1 20 A 1 20 A 1 1051 VA 930 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 4968 VA Total Amps: 20 A 1100 VA 1100 VA 1A 1A Connected Load 2660 VA 10905 VA B C 1806 VA 1140 VA 172 VA 1413 VA 0 VA 1975 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 6507 VA 25 A Demand Factor 125.00% 125.00% Poles 1 1 48 VA 389 VA 1 1 1 535 VA 1009 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 -0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -1981 VA 7A Estimated Demand 3325 VA 13631 VA Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A --------- Circuit Description CKT LTG Room 004 2 LTG Room 114, 112, 110, 108, 116,... 4 Lighting - Dwelling Unit ME/AE... 6 Lighting - Dwelling Unit ME/AE... 8 LTG Room 128, 126, 124, 120, 122,... 10 LTG Room 149B, 149, 137, 147, 145... 12 LTG Room 125, M123 14 Exterior Lighting 16 Spare 18 Spare 20 Spare 22 Spare 24 Spare 26 Space 28 Space 30 Space 32 Space 34 Space 36 Space 38 Space 40 Space 42 D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt PRO M EX I F E S S I ONA L New Mexico State University Jett Hall and Jett Annex Renovations and Additions C Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Construction Documents 13565 VA 16956 VA 16 A 20 A Notes: Notes: Panel Totals Branch Panel: H1B Branch Panel: M1C1 113254 VA 113254 VA 136 A 136 A Location: Supply From: Mounting: Enclosure: Volts: Phases: Wires: Spaces: MECHANICAL ROOM M198 MSB Surface Type 1 A.I.C. Rating: Mains Type: Mains Rating: MCB Rating: 480/277 Wye 3 4 42 Location: Supply From: Mounting: Enclosure: 25000 MCB 225 A 225 A Volts: Phases: Wires: Spaces: ELECTRICAL ROOM E167 HDB1B Surface Type 1 A.I.C. Rating: 25000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 480/277 Wye 3 4 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description MTR MECHANICAL ROOM M198 CHWP-2 - MECHANICAL ROOM... --HWP-1 - MECHANICAL ROOM M198 --CON MECHANICAL ROOM M198 --CHWP-1 - MECHANICAL ROOM... --- Trip 20 A 20 A --20 A --20 A --20 A --- Poles 1 3 --3 --3 --3 --- Total Load: Total Amps: A 0 VA B C 0 VA 1330 VA 1330 VA 1330 VA 1330 VA 1330 VA 1330 VA 3047 VA 3047 VA 3047 VA 3047 VA 3047 VA 3047 VA 4000 VA 5817 VA 4000 VA 5817 VA 4000 VA 5817 VA 5817 VA 10000 VA 5817 VA 10000 VA 5817 VA 10000... 34388 VA 124 A 34388 VA 124 A Poles 1 3 --3 --3 --3 --- Trip 20 A 20 A --20 A --20 A --20 A --- Circuit Description MTR MECHANICAL ROOM M198 MTR AHU-4 - 196 --HWP-2 -MECHANICAL ROOM M198 --AHU-4 - MECHANICAL ROOM M198 --CON MECHANICAL ROOM M198 --- CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description CON MECHANICAL ROOM M003 LTG MECHANICAL ROOM M003 LTG Room 177, 182 LTG Room H172, H174, H161, J155,... LTG Room 184, 191, 191A, 191B,... Exterior Lighting Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space 34388 VA 124 A Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Poles A 1 180 VA 330 VA 1 1 1 549 VA 670 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ----Total Load: 1729 VA Total Amps: 6A B C Poles 1 180 VA 748 VA 1 507 VA 1256 VA 1 1 841 VA 1138 VA 1 1835 VA 0 VA 1 1 0 VA 0 VA 1 0 VA 0 VA 1 1 0 VA 0 VA -0 VA 0 VA --0 VA 0 VA -0 VA 0 VA --0 VA 0 VA -0 VA 0 VA --0 VA 0 VA -0 VA 0 VA -2907 VA 3598 VA 11 A 14 A Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Circuit Description CKT LTG Room 193A, 193 2 LTG Room 191C, 193 4 LTG Room 159G, 163, T165, 159F,... 6 LTG CHME STUDENT... 8 LTG Room 150, 152-1, 154-1, 156-1,... 10 Spare 12 Spare 14 Spare 16 Spare 18 Spare 20 Space 22 Space 24 Space 26 Space 28 Space 30 Space 32 Space 34 Space 36 Space 38 -- Space 40 -- Space 42 A Connected Load 99174 VA 3990 VA Demand Factor 125.00% 100.00% Estimated Demand 123968 VA 3990 VA Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 103164 VA 127958 VA 124 A 154 A Load Classification Lighting CON LTG Connected Load 1820 VA 180 VA 6297 VA Demand Factor 125.00% 125.00% 125.00% Estimated Demand 2275 VA 225 VA 7871 VA Panel Totals PANEL M1B PANEL M1C PANEL M2A PANEL M2B PANEL H1A PANEL M1C1 PANEL H1B Date Description Date September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Notes: Notes: PANEL M1A Mark A Load Classification CON MTR KEYPLAN B Notes: 9/15/2015 7:21:19 PM EW PROJECT Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: B Location: Supply From: Mounting: Enclosure: A TE O F Circuit Description TERMINAL UNITS - 2ND FLOOR... VDF-24/EF-5 -PENTHOUSE M301 --VFD-23/EF-4 - PENTHOUSE M300 --VFD-26/LEF-2 - PENTHOUSE M300 --VFD-20/AHU-1 - PENTHOUSE M300 --TERMINAL UNITS - 2ND FLOOR NW Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Pole s Trip 20 A 1 20 A 3 ----20 A 3 ----40 A 3 ----70 A 3 ----20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 ----------------------------------------------Total Load: Total Amps: A.I.C. Rating: 25000 Mains Type: MLO Mains Rating: 400 A MCB Rating: 480/277 Wye 3 4 84 ST NO. 12498 RE C CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Volts: Phases: Wires: Spaces: PENTHOUSE M301 HDB2A Surface Type 1 F. H E C K N Location: Supply From: Mounting: Enclosure: Branch Panel: H1A Branch Panel: M2B R EG I S T E Branch Panel: M2A HN IV JO D Connected Load 34902 VA 75639 VA Trip 20 A --40 A --100 A --20 A 20 A 20 A 20 A --------- Volts: Phases: Wires: Spaces: ELECTRICAL ROOM E167 HDB1B Surface Type 1 EE R Circuit Description MTR TERMINAL UNITS - WEST MTR TERMINAL UNITS - NW MTR FAN COIL UNITS - BASEMENT PCP-3 - MECHANICAL M123 --AHU-3 - MECHANICAL M123 (1) --Spare Spare Spare Spare Space Space Space Space Space Space Space Space Location: Supply From: Mounting: Enclosure: A.I.C. Rating: 25000 Mains Type: Mains Rating: 400 A MCB Rating: 400 A 480/277 Wye 3 4 42 GI N E CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Volts: Phases: Wires: Spaces: MECHANICAL M123 HDB1A Recessed Type 1 EN Location: Supply From: Mounting: Enclosure: Branch Panel: M1C CO Branch Panel: M1A 8297 VA 10371 VA 10 A 12 A VAN H. GILBERT ARCHITECT PC SHEET TITLE ELECTRICAL SCHEDULES E-707 1 2 3 4 5 6 SHEET 178 OF 187 1 2 3 4 5 Branch Panel: H1C Location: Supply From: Mounting: Enclosure: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 E Volts: Phases: Wires: Spaces: Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------------ Poles A 1 964 VA 0 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ----Total Load: 964 VA Total Amps: 3A Space Space Load Classification Lighting LTG Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING Branch Panel: H2A ELECTRICAL E194B MSB Surface Type 1 Circuit Description LTG STUDENT PROJECT CENTER LTG AERO FLUIDS LAB 194 Exterior Lighting Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space 6 Connected Load 1260 VA 2136 VA A.I.C. Rating: 25000 Mains Type: MLO Mains Rating: 100 A MCB Rating: 480/277 Wye 3 4 42 B 1079 VA C 0 VA 1350 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1079 VA 4A Demand Factor 125.00% 125.00% 0 VA 0 VA 1350 VA 5A Estimated Demand 1575 VA 2670 VA Poles 1 1 1 1 1 1 1 1 -------------- Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------------ Location: Supply From: Mounting: Enclosure: Circuit Description Spare Spare Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space -- Space -- Space CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Volts: Phases: Wires: Spaces: ELECTRICAL ROOM E301 HDB2A Surface Type 1 Circuit Description LTG Room 216, 210 LTG Room 215, 213, 217B LTG Room 222, H221, 224, 226, 228... LTG Room 233, 237, 245 LTG Room H202-1 Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Poles A 1 1665 VA 510 VA 1 1 1 1144 VA 865 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ----Total Load: 4185 VA Total Amps: 15 A Load Classification LTG Connected Load 7908 VA A.I.C. Rating: 25000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 480/277 Wye 3 4 42 B 1172 VA C 412 VA 476 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 2060 VA 8A Demand Factor 125.00% Poles 1 1 548 VA 1052 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 1 -0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -1600 VA 6A Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ---------- Circuit Description LTG Room 206, 204 LTG Room 207, T203, 207A, 201A,... LTG Room 245, 244, 249 LTG ME/AE LAB 233 Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space -- Space -- Space Estimated Demand 9885 VA Notes: 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 3396 VA 4245 VA 4A 5A CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 7908 VA 9885 VA 10 A 12 A Notes: D C 1249 VA 1498 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 2746 VA 10 A Demand Factor 0.00% 125.00% Poles 1 1 647 VA 1138 VA 1 1 1 0 VA 0 VA 1 1 1 0 VA 0 VA 1 --0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA ---0 VA 0 VA -1785 VA 6A Estimated Demand 0 VA 8468 VA Trip 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ------------- Circuit Description LTG NEW CHME RESEARCH LAB... CON CLASSROOM 259 LTG CHME OFFICE 250 Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: Notes: 6774 VA 8468 VA 8A 10 A CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Circuit Description T1G --HRP-2 MECHANICAL ROOM M003 --VFD-3/SF-1 MECHANICAL ROOM... --VFD-4/SF-1 MECHANICAL ROOM... --PCP-2 MECHANICAL ROOM M003 --VFD-16/EF-2 - MECHANICAL ROOM... --VFD-18/LEF-1 - MECHANICAL ROO... --Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Space Space Space Pole s Trip 225 A 3 ----25 A 3 ----40 A 3 ----40 A 3 ----20 A 3 ----20 A 3 ----50 A 3 ----20 A 1 20 A 1 20 A 1 40 A 1 40 A 1 40 A 1 ------------------------------Total Load: Total Amps: Load Classification MTR REC A 2720 VA 5817 VA C 3360 VA 5817 VA 1680 VA 5817 VA 3878 VA 5817 VA 3878 VA 5817 VA 3878 VA 5817 VA 5817 VA 5817 VA 5817 VA 5817 VA 5817 VA 5817 VA 5817 VA 5817 VA 5817 VA 5817 VA 5817 VA 5817 VA 831 VA 1329 VA 831 VA 1329 VA 831 VA 1329 VA 1329 VA 831 VA 1329 VA 831 VA 1329 VA 831 VA 831 VA 831 VA 831 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 831 VA 0 VA 0 VA 0 VA 831 VA 0 VA 0 VA 0 VA 831 VA 0 VA 0 VA 0 VA 0 VA 0 VA 47482 VA 172 A Connected Load 141146 VA 900 VA B B 0 VA 48122 VA 174 A Demand Factor 100.00% 100.00% 0 VA 0 VA 46442 VA 168 A Estimated Demand 141146 VA 900 VA Pole s 3 --3 --3 --3 --3 --3 --3 --1 1 1 1 1 1 1 --------------- ST A TE O F Connected Load 0 VA 6774 VA B PRO M EX I F E S S I ONA GI N EW EN D EE R NO. 12498 CO A.I.C. Rating: 25000 Mains Type: MLO Mains Rating: 400 A MCB Rating: 480/277 Wye 3 4 84 F. H E C K IV Load Classification CON LTG Trip Poles A 20 A 1 1673 VA 504 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 20 A 1 0 VA 0 VA 20 A 1 20 A 1 --0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ------0 VA 0 VA ----Total Load: 2176 VA Total Amps: 8A Volts: Phases: Wires: Spaces: ELECTRICAL ROOM E001 HDB1B Surface Type 1 RE C Circuit Description LTG NEW CHME RESEARCH LAB... LTG GLASSWARE / AUTOCLAVE... LTG Room 268, 268A, 250, 252, 254... Spare Spare Spare Spare Spare Spare Space Space Space Space Space Space Space Space Space Space Space Space Location: Supply From: Mounting: Enclosure: A.I.C. Rating: 25000 Mains Type: MLO Mains Rating: 225 A MCB Rating: 480/277 Wye 3 4 42 HN N CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Volts: Phases: Wires: Spaces: ELECTRICAL ROOM E267 HDB2B Surface Type 1 R EG I S T E Branch Panel: M1BM Branch Panel: H2B Location: Supply From: Mounting: Enclosure: JO D L PROJECT Trip 40 A --40 A --40 A --40 A --20 A --50 A --50 A --20 A 20 A 20 A 20 A 50 A 50 A 50 A --------------- Circuit Description CKT VFD-6/SF-1 MECHANICAL ROOM... 2 -4 -6 VFD-2/SF-1 MECHANICAL ROOM... 8 -10 -12 VFD-5/SF-1 MECHANICAL ROOM... 14 -16 -18 VFD1/SF-1 MECHANICAL ROOM... 20 -22 -24 VFD-15/EF-1 - MECHANICAL ROOM... 26 -28 -30 VFD-17/LEF-1 - MECHANICAL ROO... 32 -34 -36 VFD-19/LEF-1 - MECHANICAL ROO... 38 -40 -42 Spare 44 Spare 46 Spare 48 Spare 50 Spare 52 Spare 54 Spare 56 Space 58 Space 60 Space 62 Space 64 Space 66 Space 68 Space 70 Space 72 Space 74 Space 76 Space 78 Space 80 Space 82 Space 84 New Mexico State University Jett Hall and Jett Annex Renovations and Additions C Construction Documents Panel Totals Total Conn. Load: Total Est. Demand: Total Conn. Current: Total Est. Demand Current: 142046 VA 142046 VA 171 A 171 A B D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt Notes: Mark Date Description Date A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 9/15/2015 7:21:19 PM SHEET TITLE ELECTRICAL SCHEDULES E-708 1 2 3 4 5 6 SHEET 179 OF 187 1 2 3 4 5 6 Van H. Gilbert Architect PC ARCHITECTURE • INTERIORS • PLANNING E 2428 Baylor Dr SE Albuquerque, NM 87106 Tel 505-247-9955 Fax 505-247-1826 E-mail info@vhgarchitect.com Web Site www.vhgarchitect.com E CONSULTANTS LABORATORY CONSULTANT RFD - Research Facilities Design 3965 Fifth Ave. Suite 400 San Diego, CA 92103 Phone 619-297-0159 CIVIL ENGINEER Lilley Engineering, Inc. 5160 Calle Bellisima Las Cruces, NM 88011 Phone 575-521-0006 STRUCTURAL ENGINEER Stubbs Engineering, Inc. 277 E. Amador Ave. Suite 200 Las Cruces, NM 88001 Phone 575-993-5228 MECHANICAL/ELECTRICAL ENGINEER Bridgers & Paxton Consulting Engineers 4600-C Montgomery Blvd. NE Albuquerque, NM 87109 Phone 505-883-4111 D HN F. H E C K A TE O F ST IV JO D PRO EE R I F E S S I ONA GI N M EX EN RE D CO EW N R EG I S T E NO. 12498 L PROJECT New Mexico State University Jett Hall and Jett Annex Renovations and Additions C C Construction Documents D:\Revit 2015\Projects\7168 MEP-JETT HALL_OUrias.rvt B B Mark Date Description Date A A September 11, 2015 Project Number 14400 Drawn By Author Checked By Checker Copyright © VAN H. GILBERT ARCHITECT PC 9/15/2015 7:21:21 PM SHEET TITLE ELECTRICAL USER DEFINED E-801 1 2 3 4 5 6 SHEET 180 OF 187