1. Write a program to determine the efficiency and regulation of a 250 km, 3-phase, 50 Hz, transmission line delivering 20 MW at 0.8 lagging pf to a balanced load at 132 kV. The line resistance is 0.11 ohm/km, line inductance is 1.24 mH/km and capacitance is 0.0094 µF/km. Repeat the experiment by considering 0.8 leading p.f. and compare the results. 2. For the data given below obtain i) primitive admittance matrix ii) bus incidence matrix. Line num. Bus code Admittance in p.u. 1 1-4 1.4 2 1-2 1.6 3 2-3 2.4 4 3-4 2.0 5 2-4 1.8 3. The figure shows the single line diagram of a simple 3 bus power system with generator at bus-1. The magnitude at bus 1 is adjusted to 1.05pu. The scheduled loads at buses 2 and 3 are marked on the diagram. Line impedances are marked in p.u. The base value is 100MVA. The line charging susceptances are neglected. Determine the phasor values of the voltage at the load bus 2 and 3. (i) Find the slack bus real and reactive power. (ii) Verify the result using MATLAB. 4. A 60Hz synchronous generator having inertia constant H = 5 MJ/MVA and a direct axis transient reactance Xd1 = 0.3 per unit is connected to an infinite bus through a purely reactive circuit as shown in figure. Reactances are marked on the diagram on a common system base. The generator is delivering real power Pe = 0.8 per unit and Q = 0.074 per unit to the infinite bus at a voltage of V = 1 per unit. a. b. A temporary three-phase fault occurs at the sending end of the line at point F. When the fault is cleared, both lines are intact. Determine the critical clearing angle and the critical fault clearing time. Verify the result using MATLAB program. 5. The one line diagram of a simple power system is shown in figure. The neutral of each generator is grounded through a current limiting reactor of 0.25/3 per unit on a 100MVA base. The system data expressed in per unit on a common 100 MVA base is tabulated below. The generators are running on no load at their rated voltage and rated frequency with their emf in phase. Determine the fault current for balanced three phase fault at bus 3 through a fault impedance, Zf = j0.1 per unit. Verify the result using MATLAB program. Item Base MVA G1 G2 T1 T2 L12 L13 L23 100 100 100 100 100 100 100 Voltage Rating kV 20 20 20/220 20/220 220 220 220 X1 X2 X0 0.15 0.15 0.10 0.10 0.125 0.15 0.25 0.15 0.15 0.10 0.10 0.125 0.15 0.25 0.05 0.05 0.10 0.10 0.30 0.35 0.7125 6. An isolated power station has the following parameters Turbine time constant, T = 0.5sec Governor time constant, g = 0.2sec Generator inertia constant, H = 5sec Governor speed regulation = R per unit The load varies by 0.8 percent for a 1 percent change in frequency, i.e, D = 0.8 The governor speed regulation is set to R = 0.05 per unit. The turbine rated output is 250MW at nominal frequency of 60Hz. A sudden load change of 50 MW (ΔPL = 0.2 per unit) occurs. (i) Find the steady state frequency deviation in Hz. (ii) Use MATLAB to obtain the time domain performance specifications and the frequency deviation step response. 7. For the data given below obtain Z Bus using zbus building algorithm. Line num. Bus code Admittance in p.u. 1 2 3 4 5 8. 1-0 2-1 3-1 2-0 2-3 4 10 10 4 10 9. Consider the system given below and assume that there is a DLG fault at bus 2, involving phases b and c. Assume that Zf is j0.1 pu and Zg is j0.2 pu (where Zg is the neutral-toground impedance) both based on 50 VA. Consider the system shown below and the following data: Generator G1: 15 kV, 50 MVA, X1 = X2 = 0.10 pu and X0 = 0.05 pu based on its own rating Synchronous motor G2: 15 kV, 20 MVA, X1 = X2 = 0.20 pu and X0 = 0.07 pu based on its own rating Transformer T1: 15/115 kV, 30 MVA, X1 = X2 = X0 = 0.06 pu based on its own rating Transformer T2: 115/15 kV, 25 MVA, X1 = X2 = X0 = 0.07 pu based on its own rating Transmission line TL23: X1 = X2 = 0.03 pu and X0 = 0.10 pu based on its own rating Assume a DLG fault at bus 2, involving phases b and c, and determine the fault current in per units and amperes. Use 50 MVA as the megavolt-ampere base and assume that Zf is j0.1 pu and Zg is j0.2 pu (where Zg is the neutral-to-ground impedance) both based on 50 MVA. 10. The single line diagram of a sample 3-bus power system is shown below. Data for this system are given in Table 1 and Table 2. a) Determine the phasor values of the voltages at buses 2 and 3 using the Gauss-Seidel method. Perform only one iteration) b) Determine the line flows and line losses after first iteration. Neglect line charging admittance. Table 2. Line Impedances Table 1 Bus Data 11. (i) Determine Z bus matrix for the power system network shown in fig. (ii) The line between buses 1 and 3 with impedance Z13 = j0.56 is removed by the simultaneous opening of breakers at both ends of the line. Determine the new bus impedance matrix. 12. Determine the critical clearing angle and critical clearing time for the power system shown in Figure below for a three-phase fault at the point F. Generator having inertia constant H = 5 MJ/MVA is supplying 1.0 p.u. MW power under prefault condition. 16) Write a program to determine the efficiency and regulation of a 250 Km transmission line having resistance of 0.133 ohm/km/phase, inductance of 0.398mH/km/phase and shunt capacitance of 31.83μF/km/phase. The receiving end load is 50MW at 220kV with 0.8 lagging power factor.