Uploaded by khalid ali

PBC 6200 Alarm configuration Ericsson Rev3

advertisement
Pbc 6200
External Alarm Configuration procedure on RBS
6201
PBC 6200
External alarms configuration procedures
• 4 External alarms will be configured on RBS 6201
•
PBC 6200 AC Failure Alarm
•
PBC 6200 DC Failure Alarm
•
PBC 6200 Major Alarm
•
PBC 6200 Minor Alarm
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 2
PBC 6200
External alarm board at Power unit side
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 3
PBC 6200
External alarm cable installation & Pin Assignment at power unit
PIN 1
1
Not connected , Pin 1 is the most right Pin
2
Not connected
3
13
Not connected
14
DC Alarm COM
Not connected
15
DC ALARM
4
Not connected
16
Not connected
5
Not connected
17
Major COM
6
Not connected
18
Major
7
Not connected
19
Not connected
8
Not connected
20
Minor COM
9
Not connected
21
Minor
10
Not connected
11
AC Mains Failure COM
12
AC Mains Failure
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 4
PBC 6200
External alarm cable installation at SAU side
AC
Failure
AC Failure
COM
DC
Failure
DC Failure
COM
Major
Major
COM
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 5
Minor
Minor
COM
PBC 6200 configuration
Assigned Relays
SSC-02
Relay ID
Alarms assigned for
IB port
4
AC Failure Alarm
5
DC Failure Alarm”
6
Major Alarm
7
Minor Alarm
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 6
RBS configuration
SAU
port
2G port
ID
Comment
“Probable
cause”
Alarm
Level
9
8
Breaking
DP09
1
10
9
Breaking
DP10
1
11
10
Breaking
DP11
1
12
11
Breaking
DP12
1
Type
Short code meaning
Short Code
PBC 6200 AC Failure
DP09
PBC 6200 DC Failure
DP10
PBC 6200 Major
DP11
PBC 6200 Minor
DP12
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 7
VIP Note
We Will use Codes to
define any alarm on any
2G RBS according to
new standard scenarios
PBC 6200
Alarm ports configuration procedure
1.
From Config choose Alarm level and
change Main load from Minor to
Major
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 9
2. From Config choose Relay and LED
and clear configuration for Relay 1
to be none
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 10
2. From Config choose Relay and LED
and clear configuration for Relay 2
to be none
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 11
3. Select Relay 4 then choose (AC
Breaker & AC Alarm)
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 12
4. Select Relay 5 then choose ( Main
Load , Priority load and LV DC)
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 13
4. Select Relay 6 then choose ( Major)
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 14
4. Select Relay 7 then choose ( Minor)
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 15
5.
From setting change site name to be the site id
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 16
9. PBC 6200 management parameters (WEB
parameters)
Insert IP “3G IP+5”
Subnet mask “3G Subnet mask”
Gateway “3G IP”
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 17
10. IP ping test
› After changing the IP and connect the PBC 6200 Ethernet port to
LMTB (in RBS 6000) or ETH port (in RBS 3000)
› Try to ping the new IP through HyperTerminal
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 18
RBS 6201
Alarm ports configuration procedure
RBS 6201
Alarm ports configuration procedures
• Configure alarms “DP09 , DP10 , DP11 , DP12 “ as per new scenarios sheet sent
from VF and in the correct ports .
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 20
RBS 6201
Alarm ports configuration procedures
• To check those alarms and functions follow below steps
1.
2.
Switching off PBC 6200 AC Circuit breakers “all phases” will activate
•
DP09
•
DP11
Switching off PBC 6200 AC Circuit breakers “one phase or two phase only“ will activate
•
3.
4.
Switch off one of Load CBs “RRU or TN” “have P or M sensors” will activate
•
DP10
•
DP11
Remove one rectifier will activate
•
5.
DP11
DP12
Remove two rectifiers will activate
•
DP11
Ahmed Salah | Ericsson Internal | PBC 6200 & RBS 6201 configuration | 2014-07-20 | Page 21
Download