4
3
ELECTRICAL SYMBOL LEGEND
SYMBOL
F
SYMBOL
S3
THREE-WAY SWITCH
S4
FOUR-WAY SWITCH
SP
SINGLE POLE SWITCH
WITH PILOT LIGHT
S WP
SINGLE POLE SWITCH
WITH WEATHERPROOF COVER
S WPL
SK
DESCRIPTION
T
SINGLE POLE SWITCH
(SUBSCRIPT INDICATES ITEM CONTROLLED)
Sa
TRANSFORMER
30AR
NF
NON-FUSED DISCONNECT SWITCH, SIZE AS NOTED
NF DENOTES NON-FUSED
30AR
20AF
FUSED DISCONNECT
E
# OF POLES
30/3
0 3R
SINGLE POLE SWITCH
WITH WEATHERPROOF LOCKING COVER
COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED
3 POLE UNLESS OTHERWISE NOTED
ENCLOSURE NEMA 1 UNLESS NOTED
SINGLE POLE KEY SWITCH
SINGLE POLE SWITCH WITH SECURITY LOCKING KEY
S LV
LOW VOLTAGE SWITCH
SF
FAN SWITCH
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS,
SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS,
FLUSH MOUNTED
MANUAL MOTOR STARTER WITH OVERLOAD HEATERS
AND PILOT LIGHT
S
DIMMER SWITCH
(1500 WATTS UNLESS OTHERWISE INDICATED)
SURGE PROTECTION TYPE (TVSS)
DUPLEX RECEPTACLE
C
FLOOR OUTLET BOX AND DUPLEX RECEPTACLE
WITH APPROPRIATE FLANGE.
UP
DUPLEX RECEPTACLE WITH
EACH HALF ON SEPARATE CIRCUIT
(BREAKER SHALL BE TWO POLE WITH COMMON TRIP)
DN
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
EWC
WP
C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.
TS
SPRINKLER TAMPER
SWITCH CONNECTION
BRANCH CIRCUIT CONDUIT EXPOSED
FS
SPRINKLER WATERFLOW
SWITCH CONNECTION
2
SURGE SUPRESSOR
C3 = SERVICE ENTRANCE DEVICE
B3 = DISTRIBUTION BOARD DEVICE
A3 = PANELBOARD DEVICE
ST
SHUNT-TRIP BUTTON - FLUSH MOUNTED UNLESS
OTHERWISE NOTED NEMA 3R FOR EXTERIOR LOCATIONS
C
POWER CONNECTION TO EQUIPMENT
WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES, (CLASSIFIED AS
FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT AFFECTING THE FIRE
CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:
A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY
FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).
E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE
WALL RATING SHALL BE MAINTAINED.
F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100
SQUARE INCHES PER 100 SQUARE FEET.
G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL BE
SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.
H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.
I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH
BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.
5.
ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED.
6.
ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED UP.
7.
THE NUMBER OF ARROWHEADS ON THE HOMERUNS DENOTES THE NUMBER OF CIRCUITS.
8.
ALL PANELS IN THIS PROJECT SHALL BE PROVIDED WITH A TYPE WRITTEN DIRECTORY.
LIGHTING FIXTURE SCHEDULE
REQUIRED LAMPS
TYPE
DESCRIPTION
MANUFACTURER
MODEL
VOLTAGE
TYPE
LAMP
QUANTITY
A1
A1E
2x4 LED LAY-IN SECURTIY LIGHTING FIXTURE
2x4 LED LAY-IN SECURTIY LIGHTING FIXTURE WITH
EMERGENCY BATTERY BACK-UP DRIVER
2x4 LED LAY-IN LIGHTING FIXTURE WITH EMERGENCY
BATTERY BACK-UP DRIVER
2x2 LED LAY-IN SECURTIY LIGHTING FIXTURE
2x2 LED LAY-IN SECURTIY LIGHTING FIXTURE WITH
EMERGENCY BATTERY BACK-UP DRIVER
2x2 LED LAY-IN LIGHTING FIXTURE WITH EMERGENCY
BATTERY BACK-UP DRIVER
4' LONG LED UP/DOWN WALL MOUNTED SECURITY
LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP
DRIVER
4' LONG LED WALL MOUNTED VAPORTITE LIGHTING
FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER
4' LONG LED CHAIN HUNG VAPORTITE LIGHTING FIXTURE
FAIL-SAFE
FAIL-SAFE
FSR-SC-X-24-4-LD3-3-STD-40-UNV-80/97-ED1C
FSR-SC-X-24-4-LD3-3-STD-40-UNV-80/97-ED1C-EBP
277 V
277 V
7900 LUMEN LED
7900 LUMEN LED
WITH UNIT
WITH UNIT
122 VA
122 VA
METALUX
24EN-LD1-6700-UNV-EL14-L840-CD-1
277 V
6700 LUMEN LED
WITH UNIT
70 VA
FAIL-SAFE
FAIL-SAFE
FSR-SC-X-24-2-LD3-3-STD-40-UNV-80/97-ED1C
FSR-SC-X-24-2-LD3-3-STD-40-UNV-80/97-ED1C-EBP
277 V
277 V
5000 LUMEN LED
5000 LUMEN LED
WITH UNIT
WITH UNIT
77 VA
77 VA
METALUX
22EN-LD1-34-UNV-EL14-L840-CD-1
277 V
3400 LUMEN LED
WITH UNIT
35 VA
FAIL-SAFE
FMB-X-4-5000/2500-7-40-UNV-80/97-ED-EBP
277 V
5000 LUMEN DOWN/2500
LUMEN UP
WITH UNIT
105 VA
WALL MOUNT @+8'-0" A.F.F.
METALUX
VT-LD2-55-DR-W-EL400-UNV-L840-CD2-WL-VT2
277 V
5500 LUMEN LED
WITH UNIT
81 VA
WALL MOUNT IN ELEVATOR PIT
METALUX
277 V
5500 LUMEN LED
WITH UNIT
81 VA
MOUNT FIXTURE @ +8'-0" A.F.F.
277 V
5500 LUMEN LED
WITH UNIT
81 VA
MOUNT FIXTURE @ +8'-0" A.F.F. IN NON SECURE AREAS,
MOUNT FIXTURE @ +12'-0" A.F.F. IN SECURE AREAS
FAIL-SAFE
FAIL-SAFE
VT-LD2-55-DR-W-UNV-L840-CD2-WL-VT2-CHAIN/SETU
VT-LD2-55-DR-W-EL400-UNV-L840-CD2-WL-VT2-CHAI
N/SET-U
FMSLP-X-12-4-7500-7-40-UNV-80/97-ED
FMSLP-X-12-4-7500-7-40-UNV-80/97-ED-EBP
277 V
277 V
7500 LUMEN LED
7500 LUMEN LED
WITH UNIT
WITH UNIT
105 VA
105 VA
FAIL-SAFE
FHL-7L-50-3A-UNV-TL
277 V
7400 LUMEN LED
WITH UNIT
36 VA
FAIL-SAFE
FHL-7L-50-3A-UNV-TL-EBP
277 V
7400 LUMEN LED
WITH UNIT
94 VA
LUMARK
XTORA9A-WG-XTORMX
277 V
7200 LUMEN LED
WITH UNIT
86 VA
FAIL-SAFE
EXL-7-*-RW-*-*
277 V
LED
PROVIDED
WITH FIXTURE
FIRE ALARM CONTROL PANEL
A2E
FIRE ALARM TERMINAL CABINET
B1
B1E
B2E
FAAP
FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED
CE
FIRE ALARM SYSTEM CONDUIT AND WIRING
F
D1E
E
FIREMAN'S ELEVATOR WARNING LIGHT
D3
D3E
LIGHTNING PROTECTION SYSTEM
FIXTURE DESIGNATION
FLUORESCENT FIXTURE
a
CI
CLASS I MAIN CONDUCTOR CABLE
GE
CII
CLASS II MAIN CONDUCTOR CABLE
S1
LOWER CASE LETTER INDICATES
CONTROL CIRCUIT SWITCH LEG
X
TEE SPLICE
CIRCUIT NUMBER
BONDING PLATE
FLUORESCENT FIXTURE DIAGONAL SHADING DENOTES
TO LIGHT FIXTURE CONNECTED TO CRITICAL BRANCH.
PIPE CLAMP FOR PLUMBING VENT THRU ROOF.
FLUORESCENT FIXTURE
DIAGONAL SHADING DENOTES HALF OF LAMPS
CONNECTED TO CRITICAL BRANCH, OTHER HALF
TO NORMAL BRANCH. (3 LAMP FIXTURES SHALL
HAVE 2 LAMPS CONNECTED TO CRITICAL,
1 LAMP CONNECTED TO NORMAL).
FLUORESCENT FIXTURE
COMPLETELY SHADED DENOTES LIGHT
FIXTURE CONNECTED TO LIFE SAFETY BRANCH
CIRCUIT.
F
FE
G
AIR TERMINATION DEVICE
4' LONG LED CHAIN HUNG VAPORTITE LIGHTING FIXTURE
WITH EMERGENCY BATTERY BACK-UP DRIVER
1x4 LED SURFACE MOUNTED SECURITY FIXTURE
1x4 LED SURFACE MOUNTED SECURITY FIXTURE WITH
EMERGENCY BATTERY BACK-UP DRIVER
LED WET LOCATION HIGH BAY FIXTURE
LED WET LOCATION HIGH BAY FIXTURE WITH
EMERGENCY BATTERY BACK-UP DRIVER
BUILIDING MOUNTED LED WALLPACK FIXTURE WITH WIRE
GUARD
INSTITUTIONAL GRADE LED EXIT SIGN, CEILING
MOUNTED, RED LETTERS, WHITE BACKGROUND AND
SINGLE OR DOUBLE FACE
METALUX
LIGHTING FIXTURE SCHEDULE NOTES:
LOAD
COMMENTS
MOUNT FIXTURE @ +18'-0" A.F.F. OR FLUSH WITH
BOTTOM OF BEAM, WHICH EVER IS LOWER
MOUNT FIXTURE @ +18'-0" A.F.F. OR FLUSH WITH
BOTTOM OF BEAM, WHICH EVER IS LOWER
VERIFY FINISH WITH ARCHITECT, MOUNT FIXTURE AT
20'-0" TO TOP OF FIXTURE
VERIFY COLOR/FINISH WITH ARCHITECT. SINGLE FACE,
DOUBLE FACE, AND DIRECTIONAL INDICATOR OPTIONS
SHALL BE IN ACCORDANCE WITH FLOOR PLANS.
SEAL
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
1. SHADED FIXTURES IN PLAN VIEW ARE EMERGENCY LIGHTING FIXTURES PROVIDED WITH AN EMERGENCY BATTERY BACK-UP SOURCE.
2. VERIFY COLOR/FINISH OF ALL FIXTURES WITH THE ARCHITECT.
3. SINGLE FIXTURE LISTED IN SCHEDULE. ALL EQUIVALENT FIXTURES SHALL MEET OR EXCEED THE PERFORMANCE OF FIXTURES LISTED IN LIGHTING FIXTURE SCHEDULE.
GROUND TERMINAL
BONDING CONDUCTOR
GROUND BAR
DN
DOWN CONDUCTOR
COUNTERPOISE CONDUCTOR
G
FLUORESCENT FIXTURE
HALF SHADING DENOTES HALF OF LAMPS CONNECTED
TO LIFE SAFETY BRANCH, OTHER HALF TO NORMAL
BRANCH. (3 LAMP FIXTURES SHALL HAVE 2 LAMPS
CONNECTED TO LIFE SAFETY, 1 LAMP
CONNECTED TO NORMAL).
KEY PLAN
P
F
DN
PARAPET MOUNTED AIR TERMINAL
FLAT ROOF MOUNTED OR MECHANICAL
THRU-ROOF CONDUCTOR
SCALE
FLUORESCENT WALL MOUNTED FIXTURE WITH
WALL OUTLET BOX
NOT TO SCALE
HID, FLUORESCENT, OR INCANDESCENT FIXTURE
FLUORESCENT, OR INCANDESCENT WALL WASHER.
MAGNETIC MOTOR STARTER OR CONTACTOR
SIZE AS NOTED
EXIT LIGHT FIXTURE
DIRECTION ARROWS AS SHOWN
(SHADED QUADRANT INDICATES FACE(S) OF FIXTURE)
ELECTRIC DUCT HEATER
WALL MOUNTED EXIT LIGHT FIXTURE
MOTOR CONNECTION, NUMBER DENOTES HORSEPOWER
EXTERIOR LIGHT FIXTURE WITH ARMS AS SHOWN
ON DRAWINGS
EDH-X
B
CEILING HEAT DETECTOR 135° UNLESS OTHERWISE
INDICATED.
FLUORESCENT STRIP FIXTURE
DUPLEX RECEPTACLE
CONDUIT SEAL-OFF FITTINGS
5
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
CONNECTION TO CLOSURE/ HOLDER INCLUDES DETECTOR
LIGHTING
A
JUNCTION BOX
C3
H
FACP
CABLE TRAY
SS
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
CONNECTION TO CLOSURE/ HOLDER
CONDUIT TURNING DOWN
EXISTING AFFECTED BY THIS PROJECT
ISOLATED GROUND DUPLEX RECEPTACLE,
(ORANGE DEVICE)
PLUG-IN STRIP WITH RECEPTACLES, 18" O.C. UNLESS
OTHERWISE INDICATED
J
H
H
GFI RECEPTACLE MOUNTED ABOVE COUNTER
PHOTOCELL, MOUNTED ON ROOF FACING NORTH
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
CONDUIT TURNING UP
4.
COMBINATION AUDIBLE/VISUAL
NOTIFICATION DEVICE
C = CEILING-MOUNTED
CD = CANDELA RATING
BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB,
UNDERGROUND OR UNDER FLOOR.
NEW
LIGHTING CONTROL TIME CLOCK
F
FIREMAN'S PHONE JACK
FUTURE
SPECIAL PURPOSE RECEPTACLE, RATING AS NOTED
XXCD
P
GFI RECEPTACLE. WP DENOTES WEATHERPROOF COVER.
CLOCK RECEPTACLE
GND
COMBINATION AUDIBLE/VISUAL NOTIFICATION DEVICE
CHIME/FLASHING "FIRE" LIGHT
CD = CANDELA RATING
EXISTING TO REMAIN
SIMPLEX RECEPTACLE (EWC DENOTES
ELECTRIC WATER COOLER. COORDINATE WITH EWC
INSTALLER FOR MOUNTING HEIGHT)
NOTE:
TICK MARKS SHOWN ON ANY DEVICE REPRESENTS
RECEPTACLE CONNECTED TO THE EMERGENCY CIRCUIT
(RED DEVICE) TYPICAL FOR ANY DEVICE IN LEGEND
C
B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.
VISUAL SIGNALING UNIT, WALL MOUNTED
(NO AUDIO DEVICE)
EXISTING TO BE REMOVED
TWO DUPLEX RECEPTACLES WITH COMMON COVER
MOUNTED ABOVE COUNTER
C
REMOTE FIRE ALARM WITH TEST SWITCH
FLEXIBLE CONDUIT
TWO DUPLEX RECEPTACLES WITH COMMON COVER
IG
RT
FATC
DUPLEX RECEPTACLE WITH TOP HALF SWITCHED
D
DUCT SMOKE REMOTE ALARM INDICATING LAMP,
W/ TEST SWITCH, WALL MOUNTED 72" AFF
CONDUIT CONTINUED
DUPLEX SAFETY RECEPTACLE MOUNT
COVERPLATES WITH SPANNER HEAD SCREWS
THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL CEILING WITH
A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING,
DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL
APPURTENANCES IN ACCORDANCE WITH NEC 408.
R
F
CONDUIT STUB
B.
INPUT MONITORING MODULE
F
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110.
I
EQUIPMENT BRANCH CONDUIT
FLOOR OUTLET BOX WITH TWO DUPLEX RECEPTACLES
AND ONE COMBINATION W/ VOICE/DATA OUTLET
EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH
THEY ARE TO BE INSTALLED.
SUPERVISED CONTROL RELAY
LIFE SAFETY BRANCH CONDUIT
EQ
3.
R
CRITICAL BRANCH CONDUIT
L
RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE,
UNLESS OTHERWISE NOTED. ABOVE COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK
SPLASH TO CENTERLINE OF DEVICE.
R = RETURN
S = SUPPLY
GROUND OR GROUND ROD AS NOTED
PEDESTAL MOUNTED RECEPTACLE
2.
DUCT SMOKE DETECTOR
FIRE ALARM SPEAKER WITH STROBE
CD = CANDELA RATING
BRANCH CIRCUIT CONDUIT CONCEALED ABOVE
CEILING OR IN WALL. CONDUIT SHALL INCLUDE
PHASE, NEUTRAL AND GROUND CONDUCTORS
AS REQUIRED FOR CIRCUITS (UNLESS OTHERWISE NOTED).
LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF
DEVICE, UNLESS OTHERWISE NOTED.
E = ELEVATOR WITH RECALL CONTACTS
I = IONIZATION
F
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS,
FLUSH MOUNTED
TWIST LOCK RECEPTACLE
SP
CEILING SMOKE DETECTOR, PHOTO-ELECTRIC
TYPE UNLESS OTHERWISE NOTED
XXCD
DUPLEX RECEPTACLE
DESCRIPTION
Dewberry Architects Inc.
1.
MANUAL PULL STATION
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS,
SURFACE MOUNTED
MANUAL MOTOR STARTER WITH OVERLOAD HEATERS
S MP
T
F
NEMA STARTER SIZE
SL
D
SYMBOL
AR DENOTES AMP RATING OF SWITCH
AF DENOTES AMP FUSE SIZE
MCP
SIZE
CEILING MOUNTED OCCUPACY SENSOR
M
FIRE ALARM/DETECTION SYSTEM
AUTOMATIC TRANSFER SWITCH
WALL MOUNTED OCCUPANCY SENSOR
S
GENERAL NOTES:
BASIC MATERIALS CONT.
DESCRIPTION
1
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
BASIC MATERIALS
2
114400 North 49th Street
Clearwater, FL.
5
Pinellas County
6
VFD
VARIABLE FREQUENCY DRIVE
DDC
DIRECT DIGITAL CONTROL PANEL
TRACK WITH TRACK LIGHT FIXTURE (TRIANGLES
INDICATE QUANTITY OF LIGHT FIXTURES)
BATTERY PACK WITH TWIN HEADS
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
No.
Description
Date
REVISIONS
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
ELECTRICAL
SYMBOL LEGEND
A
PROJECT NO.
E-000
SHEET NO.
50057109
6
5
4
3
2
1
ELECTRICAL KEY NOTES
KEYNOTE TEXT
#
1
2
3
4
5
6
F
7
8
PROPOSED LOCATION FOR DUKE ENERGY PRIMARY SERVICE
CONDUCTORS
NEW PRIMARY SERVICE TO REFEED EXISTING DUKE ENERGY
TRANSFORMERS SERVING "A", "B", AND "C" BARRACKS
EXISTING DUKE ENERGY PAD-MOUNTED SWITCHGEAR TO
REMAIN.
EXISTING DUKE ENERGY TRANSFORMER TO REMAIN.
DEMOLISH EXISTING "FSG" SECONDARY SERVICE BACK TO
EXISTING TRANSFORMER.
DEMOLISH ALL ELECTRICAL ASSOCIATED WITH VISITOR CENTER,
FOOD SERVICE, AND LAUNDRY FACILITY. EXISTING EMERGENCY
GENERATOR SERVES "A" AND "B" BARRACKS.
REFEED EXISTING "A" AND "B" BARRACKS' EMERGENCY FEEDS
FROM NEW INFRASTRUCTURE BUILDING. VERIFY ALL EXISTING
REQUIREMENTS.
DEMOLISH EXISTING DUKE ENERGY PRIMARY FEEDER,
ASSOCIATED TRANSFORMERS BACK TO SOURCE.
Dewberry Architects Inc.
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
GENERAL NOTES:
E
EXISTING 480/277V, 3 PHASE, 4W,
150KVA, PAD-MOUNTED ELECTRICAL
UTILITY TRANSFORMER (MINI 1)
CR
OS
SB
AYO
U
VT
MH
2
VT
VT
2
MH
VT
T
T
4
("A" AND "B")
7
"B"
PROPOSED NEW DUKE
ENERGY PRIMARY
SERVICE
"M1"
4
7
(HEALTH)
T
MH
145TH AVE N
HEALTH CARE FACILITY
PB
T
"A"
SHERIFF ADMIN.
2
8
T
4
2' V ALLEY GU TTER
D
Pinellas County
EXISTING 208/120V, 3 PHASE, 4W,
75KVA, PAD-MOUNTED ELECTRICAL
UTILITY TRANSFORMER (UNLABELED
BLDG. ADJACENT TO HEALTH)
114400 North 49th Street
Clearwater, FL.
SAFE HARBOR
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
PROPOSED NEW DUKE
ENERGY PRIMARY
SERVICE
1. TRANSFORMER, SWITCHGEAR, AND PULL BOX LOCATIONS ARE
BASED UPON CIVIL DRAWINGS, ELECTRICAL UTILITY DRAWINGS,
AND SATELLITE IMAGERY. FIELD VERIFY EXACT LOCATIONS.
2. UNDERGROUND FEEDER ROUTING IS DIAGRAMMATIC AND BASED
UPON CIVIL DRAWINGS AND ELECTRICAL UTILITY DRAWINGS. REFER
TO CIVIL AND ELECTRICAL UTILITY DRAWINGS FOR FURTHER
INFORMATION.
3. TRANSFORMER DATA IS BASED UPON ELECTRICAL UTILITY
DRAWINGS AND AN EXISTING FACILITY ELECTRICAL ASSESSMENT
REPORT DATED JULY 19, 2006.
4. ALL WORK REQUIRED BY THE UTILITY COMPANY SHALL BE
PERFORMED BY THE UTILITY COMPANY AND ALL ASSOCIATED COSTS
SHALL BE INCLUDED BY THE DESIGN BUILDER.
5. DESIGN BUILDER TO SEQUENCE ALL DEMOLITION WITH OWNER TO
MINIMIZE SHUTDOWNS TO ALL EXISTING OPERATIONS TO REMAIN.
6. PROVIDE EMERGENCY POWER TO ALL NEW SECURITY WORK IN
EXISTING BUILDINGS. COORDINATEREQUIREMENTS WITH SECURITY
DRAWINGS.
PB
("C" AND "FSC")
"C"
"M2"
8
2
SEAL
5
T
6
PRELIMINARY DOCUMENTS
VT
NOT FOR CONSTRUCTION
VT
T
EXISTING 480/277V, 3 PHASE, 4W,
150KVA, PAD-MOUNTED ELECTRICAL
UTILITY TRANSFORMER (MINI 2)
T
T
1
C
PB
1
3
4
T
VT
142ND AVE N
OCPD OCPD OCPD
(CENTRAL)
PB
CENTRAL DIVISION
3
PB
PB
PB
POND
POND
EXISTING PRIMARY-SIDE,
MEDIUM VOLTAGE,
UNDERGROUND
FEEDERS. TYPICAL.
T
T
T
SOUTH DIVISION
4
T
4
(CJC)
("A" SOUTH)
49TH ST N
6
1
T
KEY PLAN
SCALE
PINELLAS COUNTY
CRIMINAL COURT
COMPLEX
1" = 100'-0"
"G"
POND
POND
VT
4
B
"F"
MAINTENANCE
"E"
"D"
"C"
(SA)
T
VT
No.
Description
Date
REVISIONS
T
SIR LB021
(FI R 1/2" LB1344 0.30' S., 0.50' W.)
VT
OHE
LAND LINE
JURISDICT IONAL WET
4
("F" SOUTH)
OHE
OHE
VT
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
ELECTRICAL SITE
PLAN
A
PROJECT NO.
1
ELECTRICAL SITE PLAN
E-001
Scale: 1" = 100'-0"
SHEET NO.
50057109
3
2
1
#
1
2
1
1.1
3
5
6.9
7
WP
COORDINATE LOCATION, MOUNTING HEIGHT, AND
REQUIREMENTS WITH FOOD SERVICE CONSULTANT AND
SHOP DRAWINGS PRIOR TO ROUGH-IN. SEAL ALL CONDUIT
PENETRATIONS AND MAKE CONNECTIONS IN
ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
4
PROVIDE DEDICATED BRANCH CIRCUIT IN 208/120V
PANELBOARD. COORDINATE VOLTAGE, CIRCUIT
BREAKER/CONDUCTOR AMPERE RATING, PHASE, AND
CONNECTION REQUIREMENTS WITH EQUIPMENT
SELECTIONS. ADJUST CONDUCTOR AND CONDUIT SIZES
FOR VOLTAGE DROP (AS REQUIRED).
5
PROVIDE DEDICATED BRANCH CIRCUIT IN 480/277V
PANELBOARD. COORDINATE VOLTAGE, CIRCUIT
BREAKER/CONDUCTOR AMPERE RATING, PHASE, AND
CONNECTION REQUIREMENTS WITH EQUIPMENT
SELECTIONS. ADJUST CONDUCTOR AND CONDUIT SIZES
FOR VOLTAGE DROP (AS REQUIRED).
6
PROVIDE DEDICATED BRANCH CIRCUIT IN 208/120V
PANELBOARD. ADJUST CONDUCTOR AND CONDUIT SIZES
FOR VOLTAGE DROP (AS REQUIRED).
J-BOX FOR SECURITY GATE OPERATOR. COORDINATE
LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH
ARCHITECT AND SECURITY GATE SHOP DRAWINGS PRIOR
TO INSTALLATION.
WP
A
A
J
A.1
A.1
7
4
BULK DRY
STORAGE
108
9
PROGRAM
MEETING ROOM
116
PROGRAM
MEETING ROOM
110
TV
WORKER
STAGING
122
WP
WALK-IN REF. FAN COIL
UNIT
5
7
TV
LOADING
DOCK
105
INMATE
TOILET
121
WP
COILING DOOR #2
5
3
9
4
E
SEARCH
123
STORAGE
6
10
J J
J
6
5
10
SECURITY
ELECTRONICS
101
5
VAV BOX
SALLYPORT
SERVICE DRIVE
103
DOCK
FAN COILSTORAGE
UNIT
102
5
5
BULK REFIG
2 STORAGE
109
JANITOR
142
STORAGE
112
OFFICE
115
VAV BOX
INMATE
TOILET
113
B
AV CLOSET
117
JANITOR
114
5
6
6
6
5
VAV BOX
STAFF
118
J
8
STAIR
A
SA1
COILING DOOR #1
5
CORRIDOR
141
4
FEC
FEC
C
ELEVATOR
A
EA
OFFICE/
CONTROL
137
1
WP
D
WATER
HEATER
124
CART
WASH
139
ELECTRICAL
140
4
1
5
4
WP
WP
C
VAV BOX
WP
ELEVATOR
B 1
E-141
EB
WP
5
WP
STAIR
B
SB1
ELEVATOR
C
6
EC
1
GENERAL NOTES:
WP
WP
5
WP
5
C
J
6
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
DISCONNECT SWITCH FOR DOCK LIFT. COORDINATE
LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH
ARCHITECT AND SECURITY GATE SHOP DRAWINGS PRIOR
TO INSTALLATION.
DISCONNECT SWITCH FOR DOCK LEVELER. COORDINATE
LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH
ARCHITECT AND SECURITY GATE SHOP DRAWINGS PRIOR
TO INSTALLATION.
1. PROVIDE ELECTRICAL CONNECTIONS FOR ALL EQUIPMENT
INDICATED ON ARCHITECTURAL, MECHANICAL, PLUMBING,
FIRE PROTECTION, OR OTHER EQUIPMENT PLANS AS
REQUIRED. CONNECTION INFORMATION TO BE
COORDINATED WITH FINAL CONSTRUCTION DOCUMENTS.
2. COORDINATE ALL LAUNDRY EQUIPMENT WITH LAUNDRY
SERVICE DRAWINGS.
3. ALL FINAL LAUNDRY EQUIPMENT CONNECTIONS WILL BE
PROVIDED AS REQUIRED BY FINAL LAUNDRY
CONSTRUCTION DOCUMENTS INCLUDING ALL ELECTRICAL
STUB-UP LOCATIONS, OVERCURRENT PROTECTION,
CONDUIT AND WIRE REQUIREMENTS.
4. REFER TO TECHNOLOGY DRAWINGS FOR ALL SECURITY
AND DATA INFRASTRUCTURE CONNECTION
REQUIREMENTS. ALL EQUIPMENT COORDINATION SHALL
BE IN ACCORDANCE WITH FINAL TECHNOLOGY
CONSTRUCTION DOCUMENTS.
INMATE
TOILET
119
5
Dewberry Architects Inc.
10 J-BOX FOR SECURITY ELECTRONICS. COORDINATE
LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH
OWNER AND SECURITY CONTRACTOR PRIOR TO
INSTALLATION.
VAV BOX
VAV BOX
WP
B
9
5
6
7
TV
DOCK
STAGING
107
8
PROGRAM
MEETING ROOM
111
4
DEDICATED RECEPTACLE FOR SUMP PUMP
J-BOX FOR WALK-IN REFRIGERATOR LIGHTING, DOOR
HEATER (IF PROVIDED), AND CONTROLS. COORDINATE
LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH
FOOD SERVICE CONSULTANT AND SHOP DRAWINGS
PRIOR TO ROUGH-IN. SEAL ALL CONDUIT PENETRATIONS
AND MAKE CONNECTIONS IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS.
3
F
WP
ELECTRICAL KEY NOTES
KEYNOTE TEXT
5
L104
L109B
L109A
6
5
L116
L108B
L101
WP
STAFF
TOILET
125
L108A
GARBAGE/
RECYCLE DOCK
106
114400 North 49th Street
Clearwater, FL.
4
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
5
Pinellas County
6
AIR
COMPRESSOR
126
4
WP
FAN COIL UNIT
UTILITY
WASH
136
TRASH COMPACTOR
5
L115
SEAL
4
CLEAN LAUNDRY
STORAGE
135
TRASH COMPACTOR
WP
4
CENTRAL
LAUNDRY
138
J
C
NOT FOR CONSTRUCTION
4
4
D
PRELIMINARY DOCUMENTS
L111A
L111B
7
D
KEY PLAN
4
L111C
BEDDING
STORAGE
134
WP
PARKING AREA
VAV BOX
4
DRYERS
127
L111D
5
4
WATER TANK
STORAGE
104
L111E
MAINTENANCE
SUPPLY
133
SCALE
4
L111F
VAV BOX
1/8" = 1'-0"
4
RISER
ROOM
132
5
UNIFORM
STORAGE
131
4
INMATE
TOILET
129
BREAK
ROOM
130
CHEMICAL
STORAGE
128
E.9
L111G
DRYER BOOSTER FAN
L114A
L114B
4
L111H
4
H
4
2448
2448
E.9
C
F
F
WP
B
1
1
1.1
FIRST FLOOR POWER PLAN
Scale: 1/8" = 1'-0"
3
5
6.9
7
No.
Description
Date
REVISIONS
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
FIRST FLOOR
POWER PLAN
A
PROJECT NO.
E-110
SHEET NO.
50057109
6
5
4
3
2
1
GENERAL NOTES:
1
1.1
3
5
6.9
1. REFER TO REFLECTED CEILING PLANS FOR EXACT LOCATIONS
OF FIXTURES.
2. ALL LIGHTING FIXTURES SHALL BE CONTROLLED VIA RELAY
CONTROL PANELS FROM THE MAIN BUILDING CONTROL/SECURITY
ROOM.
3. PROVIDE UNSWITCHED CONDUCTORS TO ALL EMERGENCY
LIGHTING POWER SUPPLIES IN DESIGNATED FIXTURES.
4. REFER TO SHEET E-000 FOR FIXTURE SCHEDULE.
7
Dewberry Architects Inc.
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
F
S1
S1
S1
A
S1
G
G
GE
X
G
FE
GE
A1E
G
GE
G
F
GE
G
G
BULK DRY
STORAGE
108
GE
FE
GE
G
A1E
A1
A1
G
GE
G
GE
A1
GE
G
F
GE
F
A1
G
A1E
A1
A1E
GE
G
SEARCH
B1 123
G
A1E
G
A1
A1E
A1
A1E
GE
G
G
GE
FE
S1
DOCK
STORAGE
102
JANITOR
114 B1
FE
FE
STORAGE
112
F
BULK REFIG
STORAGE
109
F
G
GE
G
GE
G
A1E
115
A2E
B1E
A1E
A1
A1E
GE
G
GE
G
GE
A1
D1E
C
S1
X
CE
A1E
G
GE
G
GE
G
A2E
A1E
A1
C
CART
WASH
139
FE
X
ELECTRICAL
140
D3E
D1E
ELEVATOR
B
EB
D1E
D1E
ELEVATOR
C
D1E
EC
G
GE
G
GE
G
GE
G
GE
G
GARBAGE/
RECYCLE DOCK
106
GE
F
F
UTILITY
WASH
136
FE
S1
C
CE
GE
X
FE
F
TRASH COMPACTOR
X
STAFF
TOILET
125
FE
GE
CE
B1
X
F
WATER
FE
HEATER
X
GE
X
X
FEC
STAIR
B
SB1
A1E
X
S1
A1E
X
D3E
OFFICE/
CONTROL
A2E 137 A2E
A1
A1
A1E
A1
D1E
A1E
F
A1
X
FEC
A1E
F
ELEVATOR
A
EA
A1E
CORRIDOR
141
A2E
A1E
A1
X
X
CE
A1E
B
INMATE
TOILET
119
F
STAFF
TOILET
118
B1E
A1
FE
FE
X
A1
FE
AV CLOSET
A2E
FE
X
CE
STAIR
A
SA1
A1E
FE
FE
A1
FE
STORAGE
A1E
FE
SALLYPORT
SERVICE DRIVE
103
B1
121
B1
G
A1
INMATE
FE
A1
A1
B
GE
S1
A1E
111
GE
D3E
A1E
X
G
DOCK
STAGING
107
X
A1E
A1E
G
E
A1
WORKER
STAGING
122
A1
A1E
FE
SECURITY
ELECTRONICS
101
A.1
A1
PROGRAM
MEETING ROOM
116
PROGRAM
MEETING ROOM
110
LOADING
DOCK
105
S1
D
A1E
A
A1E
G
GE
G
GE
G
GE
G
AIR
COMPRESSOR
126
GE
114400 North 49th Street
Clearwater, FL.
GE
S1
A1
A1
A1E
A1
GE
A1E
X
F
G
GE
A1E
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
GE
GE
A1
X
Pinellas County
A.1
S1
CE
F
SEAL
D3E
G
GE
G
GE
G
FE
GE
CLEAN
LAUNDRY
F
FE
STORAGE
135
F
S1
G
GE
G
GE
G
GE
PRELIMINARY DOCUMENTS
CENTRAL
LAUNDRY
138
NOT FOR CONSTRUCTION
D3
D
S1
C
D
KEY PLAN
GE
G
GE
G
GE
FE
F
F
FE
G
GE
G
GE
G
GE
G
BEDDING
STORAGE
134
PARKING AREA
D3E
DRYERS
127
D3
G
GE
G
GE
WATER TANK
STORAGE
104
FE
G
F
F
MAINTENANCE
SUPPLY
133
FE
GE
G
GE
G
GE
G
GE
SCALE
D3
GE
G
GE
G
1/8" = 1'-0"
D3E
RISER
ROOM
132
GE
FE
F
UNIFORM
STORAGE
131
F
FE
F
D3E
S1
INMATE
FE
TOILET
F
X
F
CHEMICAL
STORAGE
128
FE
G
G
G
D3E
E.9
H
E.9
FE
BREAK
ROOM
130
2448
S1
C
a
F
2448
F
S1
S1
S1
B
1
1.1
3
5
6.9
7
No.
Description
Date
REVISIONS
1
FIRST FLOOR LIGHTING PLAN
Scale: 1/8" = 1'-0"
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
FIRST FLOOR
LIGHTING PLAN
A
PROJECT NO.
E-111
SHEET NO.
50057109
6
5
4
3
2
1
#
1
1
1.1
3
5
6.9
7
F
MOUNT HEAT DETECTOR TO ELEVATOR PIT WALL AS
INDICATED. LOCATE WITHIN 2'-0" OF SIDEWALL FIRE
SPRINKLER PENDENT. COORDINATE LOCATION AND
REQUIREMENTS WITH DIVISION 21 CONTRACTOR AND
A.H.J. PRIOR TO INSTALLATION.
3
MOUNT SMOKE DETECTOR ABOVE ELEVATOR DOOR
AS INDICATED.
TAMPER SWITCH FOR CONTROL VALVE SERVING
ELEVATOR PIT SIDEWALL FIRE SPRINKLER PENDENT
COORDINATE LOCATION WITH A.H.J. PRIOR TO
INSTALLATION.
5
A
F
A.1
A.1
WP
PROGRAM
MEETING ROOM
116
PROGRAM
MEETING ROOM
110
Dewberry Architects Inc.
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
GENERAL NOTES:
1. ALL NOTIFICATION DEVICES SHALL HAVE A LUMINOUS
INTENSITY OF 75 CANDELA UNLESS OTHERWISE NOTED.
WORKER
STAGING
122
F
BULK DRY
STORAGE
108
COORDINATE LOCATION WITH DIVISION 21
CONTRACTOR PRIOR TO INSTALLATION. PROVIDE
ADDRESSABLE INPUT MONITORING MODULE(S)
LOCATED WITHIN A CONDITIONED, ACCESSIBLE
SPACE OR IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
2
4
A
ELECTRICAL KEY NOTES
KEYNOTE TEXT
LOADING
DOCK
105
F
INMATE
TOILET
121
PROGRAM
MEETING ROOM
111
DOCK
STAGING
107
F
F
AV CLOSET
117
WP
F
F
STAFF
TOILET
118
F
F
F
STAIR
A
SA1
1
WP
CORRIDOR
141
4
1
FEC
TS
F
5
INMATE
TOILET
113
F
FS TS
WP
JANITOR
142
BULK REFIG
STORAGE
109
INMATE
TOILET
119
F
1
F
DOCK
STORAGE
102
SALLYPORT
SERVICE DRIVE
103
F
SECURITY
ELECTRONICS
101
OFFICE
115
STORAGE
112
Pinellas County
JANITOR
114
B
F
F
4
TS
1
E
4
FEC
TS
C
WATER
HEATER
124
F
ELEVATOR
A
EA
H
3
CART
WASH
139
OFFICE/
CONTROL
137
WP
F
WP
ELECTRICAL
140
H
2
ELEVATOR
B
EB
H
2
STAIR
B
SB1
ELEVATOR
C
EC
C
E
F
C
F
F
WP
F
STAFF
TOILET
125
F
AIR
COMPRESSOR
126
GARBAGE/
RECYCLE DOCK
106
UTILITY
WASH
136
TRASH COMPACTOR
114400 North 49th Street
Clearwater, FL.
WP
B
D
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
STORAGE
120
F
WP/110cd
E
SEARCH
123
SEAL
F WP
CLEAN LAUNDRY
STORAGE
135
PRELIMINARY DOCUMENTS
WP
F
110cd
110cd
D
F
F
D
NOT FOR CONSTRUCTION
CENTRAL
LAUNDRY
138
C
KEY PLAN
BEDDING
STORAGE
134
WP
F
PARKING AREA
WATER TANK
STORAGE
104
DRYERS
127
MAINTENANCE
SUPPLY
133
SCALE
1/8" = 1'-0"
RISER
ROOM
132
1
INMATE
TOILET
129
BREAK
ROOM
130
FS
TS
CHEMICAL
STORAGE
128
H
E.9
UNIFORM
STORAGE
131
2448
2448
E.9
C
F
F
F
B
1
1.1
3
5
6.9
7
No.
Description
Date
REVISIONS
1
FIRST FLOOR FIRE ALARM & MISC. SYSTEMS PLAN
DRAWN BY
JMB
Scale: 1/8" = 1'-0"
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
A
FIRST FLOOR
FIRE ALARM &
MISC. SYSTEMS
PLAN
PROJECT NO.
E-112
SHEET NO.
50057109
6
5
4
3
2
1
ELECTRICAL KEY NOTES
KEYNOTE TEXT
#
1
1
1.1
3
5
2
7
6.9
PROVIDE DEDICATED BRANCH CIRCUIT IN 208/120V PANELBOARD.
COORDINATE VOLTAGE, CIRCUIT BREAKER/CONDUCTOR AMPERE
RATING, PHASE, AND CONNECTION REQUIREMENTS WITH
EQUIPMENT SELECTIONS. ADJUST CONDUCTOR AND CONDUIT
SIZES FOR VOLTAGE DROP (AS REQUIRED).
Dewberry Architects Inc.
PROVIDE DEDICATED BRANCH CIRCUIT IN 480/277V PANELBOARD.
COORDINATE VOLTAGE, CIRCUIT BREAKER/CONDUCTOR AMPERE
RATING, PHASE, AND CONNECTION REQUIREMENTS WITH
EQUIPMENT SELECTIONS. ADJUST CONDUCTOR AND CONDUIT
SIZES FOR VOLTAGE DROP (AS REQUIRED).
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
GENERAL NOTES:
F
A
H
C
H
A
C
A.1
A.1
CHEMICAL STORAGE
(SECURE)
216
DRY FOOD
STORAGE
204
SECURED
STORAGE
209
2
BREAK
ROOM
211
WARE WASH
AREA
215
WP
WP
K209
1. PROVIDE ELECTRICAL CONNECTIONS FOR ALL EQUIPMENT
INDICATED ON ARCHITECTURAL, MECHANICAL, PLUMBING,
OR OTHER EQUIPMENT PLANS AS REQUIRED.
CONNECTION INFORMATION TO BE COORDINATED WITH
FINAL CONSTRUCTION DOCUMENTS.
2. COORDINATE ALL KITCHEN EQUIPMENT WITH LAUNDRY
SERVICE DRAWINGS.
3. ALL FINAL KITCHEN EQUIPMENT CONNECTIONS WILL BE
PROVIDED AS REQUIRED BY KITCHEN CONSTRUCTION
DOCUMENTS INCLUDING ALL ELECTRICAL STUB-UP
LOCATIONS, OVERCURRENT PROTECTION, CONDUIT AND
WIRE REQUIREMENTS.
4. REFER TO TECHNOLOGY DRAWINGS FOR ALL SECURITY
AND DATA INFRASTRUCTURE CONNECTION
REQUIREMENTS. ALL EQUIPMENT COORDINATION SHALL
BE IN ACCORDANCE WITH FINAL TECHNOLOGY
CONSTRUCTION DOCUMENTS.
5. PROVIDE SHUNT-TRIP BREAKERS FOR ALL EQUIPMENT
LOCATED UNDER GREASE HOODS.
K208.1
CORRIDOR
212
1
1
1
1
1
1
1
1
STORAGE/
FUTURE LINK
217
1
1
1
H
H
K329F
FAN COIL UNIT
UNIFORM
205
WP
K329G
FOOD SERVICE
MGMT OFFICE
214
K329M
K329H
K329J
K329I
STAIR
A
SA2
FEC
J
DAIRY
COLDROOM
247
1
K101.2
K316B
1
C1
1
K102.4B
12"X12"
1075 CFM
.27" S.P.
G G
G
9"X8"
538 CFM
.07" S.P.
C
C
C
#321.2L
G
G
G G
12"X12"
937 CFM
.27" S.P.
12"X12"
937 CFM
.27" S.P.
H
CORRIDOR
229
STAFF
TOILET
226
TV
1
DAILY DRY
STORAGE
236
A/V
CLOSET
224
K306
1
K307
E.9
C
K311B
C
K102.10B
H
1
1
2
1
1
1
REF
K305
FINISH VEG
PREP
237
1
1
1
MIC MIC
1
FINISH MEAT
PREP
238
1
1
E.9
H
F
K309D
FAN COIL UNIT
K308
K311A
CONNECTOR TO
CENTRAL TOWER
CN
B
1
1
1.1
SECOND FLOOR POWER PLAN
Scale: 1/8" = 1'-0"
3
1/8" = 1'-0"
REFER TO PARTIAL
PLAN ON SHEET E-140.
REF
H
H
1
SCALE
1
1
C
-10 FREEZER
239
1
F
MULTI-PURPOSE
223
1
1
C
K102.11B
-20 FREEZER
240
KEY PLAN
STAFF
TOILET
227
K302
K102.9B
K102.10A
D
1
1
1
K309C
1
1
12"X12"
937 CFM
.27" S.P.
FAUCET, TANGENT DRAW-OFF
ARE OPTIONAL
K321.2
K101.9
K102.11A
JAN
228
NOT FOR CONSTRUCTION
1
D
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
12"X10"
1353 CFM
.43" S.STEAM
P.
SAFET Y VA LVE
1/ 2" N PT
SATE
12"X10"CO N DEN
RETU RN
1352 CFM
.43" S.P.
FIRE CABINET
K102.9A
PRELIMINARY DOCUMENTS
K417
K322C
D
K101.8
1
K420
J
1
K415
1
J
1
1
K419
D
1
SEAL
1
1
K402
K322B
TV
K416
K309A
C
1
K321.1
1
1
1
K322A
1
STEAM
CO N TRO L
VALVE
1/ 2" N PT
CO N DEN SATE
RETU RN
11"X8"
1012 CFM
.29" S.P.
11"X8"
1011 CFM
.29" S.P.
G
12"X10"
809 CFM
.20" S.P.
G
K321.3
1
#321.1R
241
J
K327A
C
THAW/PULL
K102.7A
K102.7B
1
SAFET Y VA LVE
12"X10"
809 CFM
.20" S.P.
C D
K101.7
J
BULK
COLDROOM
242
G G
K102.8B
G
K319
1
G
1
C
#321.2R
SAFET Y VA LVE
1/ 2" N PT
SAFET Y VA LVE
1/ 2" N PT
SAFET Y VA LVE
K318A
K102.8A
1
1/ 2" N PT
CO N DEN SATE
RETU RN STEAM
CO N TRO L
VALVE
#321.1L
1
1
K403
1
1
STEAM
CO N TRO L
VALVE
CO N DEN SATE
12"
X9"
RETU RN
1216 CFM
.37" S.P.
K318B
1
1
K404
1
K326J
K323B
12"X10"
1379 CFM
.42" S.P.
12"X12"
937 CFM
.27" S.P.
1
1
R
K101.6
FINISHED BULK
COLDROOM
243
1
1
K326I
K327B
K326H
SERVING
231
K414
R
SATE
12"X9"CO N DEN
RETU RN
1217 CFM
STEAM
.37" S.P.
CO N TRO L
J
K315
1
1
K309B
K326F
1
FOOD PREP
SERVICE AREA
230
G
STEAM
CO N TRO L
VALVE
K326G
K413
1
D
1
J
FIRE CABINET
1
1
1
1
CORRIDOR
222
R
K101.5
K102.6B
K326E
K326D
STAFF DINING
MULTI-PURPOSE
232
1
1
R
K102.6A
1
1
1
D
1
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
J
K323A
K407
K326B
1
K326C
K412B
12"X11"
1648 CFM
.47" S.P.
1
1
K409
G
K326A
K101.3
BULK MEAT
COLDROOM
242
K102.5B
HOT FOOD
1
PRODUCTION
235
K412A
K216.2B
12"X12"
937 CFM
.27" S.P.
1
K102.5A
1
K329A
J
1CORRIDOR
251
FINISH PRODUCE
COLDROOM
1
1
245
H C
1
K329B
D1
1
#321.6R
1
E1
E2
G
D1
C
K411
K216.2A
#321.6L
1
E1
E2
G
K101.4
1
12"X10"
1456 CFM
.39" S.P.
K102.4A
K101.1
1
D2
C1
J
1
K316A
D2
BULK PRODUCE
COLDROOM
248
ELEC
233
STAIR
B
SB2
ELEVATOR
C
EC
ELEVATOR
B 2
EBE-141
D
1
C
ICE/BEV.
234
ELEVATOR
A
EA
VALVE
1
TRASH
HOLDING
246
1
D
K329K
1
K102.3B
D
JAN
249
STORAGE
218
CORRIDOR
221
CO N DEN SATE
TRAP AN D ST RAI N ER
K102.3A
B
K329L
CORRIDOR
250
FEC
D
CART STORAGE
AND WASHING
219
C
2
STAFF
TOILET
206
TRAY
MAKE-UP
220
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
INMATE
TOILET
207
B
K329E
OFFICE
213
Pinellas County
EQUIPMENT
STORAGE
203
JAN/EQUIP
SUPPLIES
202
K329D
C
KITCHEN/LAUNDRY
STORAGE
201
E
K329C
C
INMATE
TOILET
208
114400 North 49th Street
Clearwater, FL.
CORRIDOR
210
1
5
6.9
7
No.
Description
Date
REVISIONS
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
SECOND FLOOR
POWER PLAN
A
PROJECT NO.
E-120
SHEET NO.
50057109
6
5
4
3
2
1
GENERAL NOTES:
1
1.1
3
5
6.9
1. REFER TO REFLECTED CEILING PLANS FOR EXACT LOCATIONS
OF FIXTURES.
2. ALL LIGHTING FIXTURES SHALL BE CONTROLLED VIA RELAY
CONTROL PANELS FROM THE MAIN BUILDING CONTROL/SECURITY
ROOM.
3. PROVIDE UNSWITCHED CONDUCTORS TO ALL EMERGENCY
LIGHTING POWER SUPPLIES IN DESIGNATED FIXTURES.
4. REFER TO SHEET E-000 FOR FIXTURE SCHEDULE.
7
Dewberry Architects Inc.
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
F
A.1
F
FE
F
FE
FE
DRY FOOD
STORAGE
204
FE
F
FE
F
FE
FE
F
C
A
C
FE
F
FE
FE
FE
F
F
A.1
CHEMICAL STORAGE
(SECURE)
216
F
SECURED
STORAGE
209
F
FE
H
F
H
A
F
BREAK
ROOM
211
FE
F
F
FE
F
FE
FE
WARE WASH
AREA
215
F
FE
F
X
FE
FE
B1E
F
F
B
EQUIPMENT
STORAGE
203
FE
A1E
A2E
A2E
UNIFORM
205
F
F
FE
STAFF
TOILET
206
FE
F
A1
B2E
F
A2E
FE
F
FE
FTRAY
MAKE-UP
220
FE
F
FE
FE
B
FOOD SERVICE
MGMT OFFICE
214
A2E
A2E
F
FE
B2E
FE
B2E
F
FE
F
CART STORAGE
AND WASHING
219
FE
STORAGE
218
F
FE
B2E
X
STAIR
A
SA2
FE
A1E
A1
A1E
A1
A1E
A1
A1E
A1
A1E
A1
A1E
A1
A1
X
X
A1
CORRIDOR
221
A1E
A1E
X
FEC
X
GE
DAIRY
COLDROOM
247
F
FE
F
FE
F
ICE/BEV.
234
ELEVATOR
A
EA
ELEVATOR
B
EB
ELEC
233
D3E
D
JAN
249
CE
D3E
FE
TRASH
HOLDING
246
X
X
FEC
X
X
FE
A1E
ELEVATOR
C
EC
STAIR
B
SB2
X
B1
D
D
F
C
FE
FE
F
A1E
FE
F
A1
A2E
FE
INMATE
TOILET
207
F
FE
C
E
JAN/EQUIP
SUPPLIES
202
FE
B1
STORAGE/
FUTURE LINK
217
X
C
KITCHEN/LAUNDRY
STORAGE
201
FE
CORRIDOR
212
CORRIDOR
B1
210
INMATE
TOILET
208
F
X
C
D2
F
CE
BULK PRODUCE
COLDROOM
248
E1
E2
G
D2
C1
FE
C1
F
FE
F
FE
X
E1
E2
G
A1
A1E
D1
A1
F
G
G
FOOD PREP
SERVICE AREA
230
A1E
12"X12"
937 CFM
.27" S.P.
FE
F
A1E
C
C
NOT FOR CONSTRUCTION
A1
B1E
D
D
12"X12"
937 CFM
.27" S.P.
STEAM
CO N TRO L
VALVE
H
12"X10"
1353 CFM
.43" S.STEAM
P.
A1E
A1
X
FE
B1
KEY PLAN
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
H C
FE
F
A1E
FE
A1
A1
FE
12"X12"
937 CFM
.27" S.P.
G
FAUCET, TANGENT DRAW-OFF
ARE OPTIONAL
F
FIRE CABINET
D
D
F
A1
FE
FE
X
B1
223
A1
CORRIDOR
229
STAFF
FE
F
A1E
A1
A1E
A1E
FE
SCALE
H
F
A1E
C
FE
A1E
A1E
X
228
SAFET Y VA LVE
1/ 2" N PT
SATE
12"X10"CO N DEN
RETU RN
1352 CFM
.43" S.P.
11"X8"
1011 CFM
.29" S.P.
A1
C
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
F
CO N DEN SATE
TRAP AN D ST RAI N ER
1/ 2" N PT
CO N DEN SATE
RETU RN
11"X8"
1012 CFM
.29" S.P.
G
12"X10"
809 CFM
.20" S.P.
FE
#321.1R
F
A1E
PRELIMINARY DOCUMENTS
C
THAW/PULL
241
G G
BULK
COLDROOM
242
SEAL
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
1/ 2" N PT
CO N DEN SATE
12"
X9"
RETU RN
1216 CFM
.37" S.P.
SAFET Y VA LVE
1/ 2" N PT
CO N DEN SATE
RETU RN STEAM
CO N TRO L
VALVE
FE
SAFET Y VA LVE
12"X10"
809 CFM
.20" S.P.
C D
G
G
C
A1E
STEAM
CO N TRO L
VALVE
12"X10"
1379 CFM
.42" S.P.
12"X12"
937 CFM
.27" S.P.
#321.1L
F
D
A1
G
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
VALVE
1/ 2" N PT
SAFET Y VA LVE
A1
R
FE
A1E
A1
D
G
FINISHED BULK
COLDROOM
243
A1
SERVING
231
9"X8"
538 CFM
.07" S.P.
FE
12"X10"
1456 CFM
.39" S.P.
F
CORRIDOR
222
A1E
G G
12"X12"
937 CFM
.27" S.P.
#321.2R
FE
R
SATE
12"X9"CO N DEN
RETU RN
1217 CFM
STEAM
.37" S.P.
CO N TRO L
SAFET Y VA LVE
F
A1
12"X12"
1075 CFM
.27" S.P.
G G
STEAM
CO N TRO L
VALVE
FIRE CABINET
FE
STAFF DINING
MULTI-PURPOSE
A1E
CE
R
F
A1
D
BULK MEAT
COLDROOM
242
C
A1
A1
#321.6L
GE
A1E
#321.6R
FE
G
FE
G
F
12"X11"
1648 CFM
.47" S.P.
CORRIDOR
251
FE
FINISH PRODUCE
COLDROOM
245
A1E
HOT FOOD
PRODUCTION
F
235
A1
X
G
D1
A1E
114400 North 49th Street
Clearwater, FL.
F
FE
FE
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
FE
F
Pinellas County
F
H
FE
H
F
H
C
A1E
F
FE
F
DAILY DRY
STORAGE
236
D3E
F
A/V
CLOSET
224
D3E
E.9
A1
A1E
A1
REF
F
FINISH VEG
PREP
237
A1
B1
A1E
A1
B1E
E.9
X
C
H
1/8" = 1'-0"
REFER TO PARTIAL
PLAN ON SHEET E-140.
A1E
REF
F
FINISH MEAT
PREP
FE
238
MIC MIC
-10 FREEZER
239
C
-20 FREEZER
240
H
C
F
F
CONNECTOR TO
CENTRAL TOWER
CN
B
1
1
1.1
SECOND FLOOR LIGHTNG PLAN
Scale: 1/8" = 1'-0"
3
5
6.9
7
No.
Description
Date
REVISIONS
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
SECOND FLOOR
LIGHTNG PLAN
A
PROJECT NO.
E-121
SHEET NO.
50057109
6
5
4
3
2
1
#
1
1.1
3
5
6.9
7
1
ADDRESSABLE INPUT MONITORING MODULE FOR MONITORING
OF KITCHEN HOOD FIRE SUPPRESSION SYSTEM. COORDINATE
LOCATION AND REQUIREMENTS WITH FOOD SERVICE
CONSULTANT AND KITCHEN HOOD SHOP DRAWINGS.
2
TAMPER SWITCH FOR CONTROL VALVE SERVING ELEVATOR
HOISTWAY FIRE SPRINKLER PENDENT
COORDINATE LOCATION WITH DIVISION 21 CONTRACTOR PRIOR
TO INSTALLATION. PROVIDE ADDRESSABLE INPUT MONITORING
MODULE(S) LOCATED WITHIN A CONDITIONED, ACCESSIBLE
SPACE OR IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
3
F
ELECTRICAL KEY NOTES
KEYNOTE TEXT
Dewberry Architects Inc.
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
GENERAL NOTES:
1. ALL NOTIFICATION DEVICES SHALL HAVE A LUMINOUS
INTENSITY OF 75 CANDELA UNLESS OTHERWISE NOTED.
A
C
C
H
A
H
A.1
A.1
CHEMICAL STORAGE
(SECURE)
216
SECURED
STORAGE
209
F
DRY FOOD
STORAGE
204
WARE WASH
AREA
215
F
BREAK
ROOM
211
F
F
STORAGE/
FUTURE LINK
217
CORRIDOR
212
H
F
C/ F
75cd
F
F
CORRIDOR
250
2
CORRIDOR
221
3
E
E
FEC
TRASH
HOLDING
246
ELEVATOR
A
EA
F
ICE/BEV.
234
C/
95cd
ELEVATOR
HB
EB
ELEC
233
D
F
FEC
STAIR
B
SB2
ELEVATOR
C
EC
D
C
D2
D2
C1
C1
E
E1
E2
E1
E2
G
D1
G
D1
CORRIDOR
222
STEAM
CO N TRO L
VALVE
F
12"X12"
1075 CFM
.27" S.P.
G
G
G G
12"X12"
937 CFM
.27" S.P.
9"X8"
538 CFM
.07" S.P.
12"X10"
1456 CFM
.39" S.P.
G
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
VALVE
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
STEAM
CO N TRO L
VALVE
C/
95cd
12"X12"
937 CFM
.27" S.P.
PRELIMINARY DOCUMENTS
C
C
CO N DEN SATE
TRAP AN D ST RAI N ER
SAFET Y VA LVE
D
H
D
JAN
228
12"X12"
937 CFM
.27" S.P.
#321.2L
C
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
NOT FOR CONSTRUCTION
STEAM
CO N TRO L
VALVE
SAFET Y VA LVE
1/ 2" N PT
CO N DEN SATE
RETU RN
11"X8"
1012 CFM
.29" S.P.
G
12"X10"
1353 CFM
.43" S.P.
STEAM
12"X10"
809 CFM
.20" S.P.
F
1/ 2" N PT
CO N DEN SATE
RETU RN STEAM
CO N TRO L
VALVE
#321.1L
SAFET Y VA LVE
1/ 2" N PT
CO N DEN SATE
12"
X9"
RETU RN
1216 CFM
.37" S.P.
12"X12"
937 CFM
.27" S.P.
12"X10"
1379 CFM
.42" S.P.
SAFET Y VA LVE
1/ 2" N PT
SATE
12"X9"CO N DEN
RETU RN
1217 CFM
STEAM
.37" S.P.
CO N TRO L
SAFET Y VA LVE
#321.2R
FIRE CABINET
R
F
D
C D
G
D
SEAL
R
FINISHED BULK
COLDROOM
243
C/
95cd
R R
F
SERVING
231
D
BULK MEAT
COLDROOM
242
FOOD PREP
SERVICE AREA
230
#321.6L
12"X11"
1648 CFM
.47" S.P.
G G
G
G
FINISH PRODUCE
COLDROOM
245
CORRIDOR
251
STAFF DINING
MULTI-PURPOSE
232
HOT FOOD
PRODUCTION
235
#321.6R
BULK PRODUCE
COLDROOM
248
KEY PLAN
STEAM CO N DEN SATE
TRAP AN D ST RAI N ER
12"X12"
937 CFM
.27" S.P.
D
C
D
FIRE CABINET
I
STAFF
TOILET
227
MULTI-PURPOSE
223
F
FAUCET, TANGENT DRAW-OFF
ARE OPTIONAL
H C
1/ 2" N PT
G
12"X10"
809 CFM
.20" S.P.
G
#321.1R
SATE
12"X10"CO N DEN
RETU RN
1352 CFM
.43" S.P.
THAW/PULL
241
G G
BULK
COLDROOM
242
11"X8"
1011 CFM
.29" S.P.
C
C
C
F
D
DAIRY
COLDROOM
247
E
TS
F
JAN
249
STORAGE
218
114400 North 49th Street
Clearwater, FL.
H
CART STORAGE
AND WASHING
219
F
STAIR
A
SA2
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
STAFF
TOILET
206
F
FS TS
C
3
B
FOOD SERVICE
MGMT OFFICE
214
UNIFORM
205
Pinellas County
B
F
INMATE
TOILET
207
TRAY
MAKE-UP
220
OFFICE
F
C / 213
75cd
F
EQUIPMENT
STORAGE
203
C
JAN/EQUIP
SUPPLIES
202
C
KITCHEN/LAUNDRY
STORAGE
201
E
F
INMATE
TOILET
208
CORRIDOR
210
1
F
CORRIDOR
229
SCALE
F
H
STAFF
TOILET
226
F
FINISH CVEG
PREP
237
DAILY DRY
STORAGE
236
A/V
CLOSET
224
REF
FINISH MEAT
PREP
238
1/8" = 1'-0"
REFER TO PARTIAL
PLAN ON SHEET E-140.
REF
C
MIC MIC
H
C
F
-10 FREEZER
239
C
-20 FREEZER
240
E.9
E.9
C
H
F
H
C
F
F
F
CONNECTOR TO
CENTRAL TOWER
CN
B
1
1
1.1
SECOND FLOOR FIRE ALARM & MISC. SYSTEMS PLAN
Scale: 1/8" = 1'-0"
3
5
6.9
7
No.
Description
Date
REVISIONS
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
A
SECOND FLOOR
FIRE ALARM &
MISC. SYSTEMS
PLAN
PROJECT NO.
E-122
SHEET NO.
50057109
4
3
2
1
#
1
2
1
1.1
3
5
6.9
3
7
CWP-2 ABS
CHWP-2 ABS
CWP-1 ABS
CHWP-1 ABS
SYSTEM PUMP
FUTURE SYSTEM PUMP
A
A
A.1
A.1
1
PROVIDE DEDICATED BRANCH CIRCUIT IN 480/277V
PANELBOARD. COORDINATE VOLTAGE, CIRCUIT
BREAKER/CONDUCTOR AMPERE RATING, PHASE, AND
CONNECTION REQUIREMENTS WITH EQUIPMENT
SELECTIONS. ADJUST CONDUCTOR AND CONDUIT
SIZES FOR VOLTAGE DROP (AS REQUIRED).
5
FIRE ALARM NOTIFICATION APPLIANCE CIRCUIT POWER
SUPPLY UNIT WITH BATTERY BACKUP
FREE-STANDING RECEPTACLE
PROVIDE DEDICATED BRANCH CIRCUIT IN 208/120V
PANELBOARD. COORDINATE VOLTAGE, CIRCUIT
BREAKER/CONDUCTOR AMPERE RATING, PHASE, AND
CONNECTION REQUIREMENTS WITH EQUIPMENT
SELECTIONS. ADJUST CONDUCTOR AND CONDUIT
SIZES FOR VOLTAGE DROP (AS REQUIRED).
FUTURE ELECTRIC CHILLER
CHWPFUTURE
ABS
ELECTRIC CHILLER
4
4
4
4
CWP-2
ABS
ELECTRIC CHILLER
CHWP-2
ABS
CWP-1
ABS
CONTROL
CONFERENCE RM
313
4
4
CHWP-1
ABS
SYS PUMP
FUTURE SYS PUMP
2
2
ELECTRIC CHILLER
2
2 CONTROL
ROOM
2
302
2
8
1
2
7
2
OFFICE
301
8
2
4
4
ABSORPTION CHILLER
1
2
RECIRC. PUMP
2
2
2
4
B
FUTURE ABSORPTION
CHILLER
2
2
1
STAIR
A
SA3
8
2
FUTURE ABSORPTION CHILLER
E
STAFF
TOILET
305
2 2
VESTIBULE
304
2
REF
3
CHW AHU
J
B
3
J
3
J
J
3
2
2
303
2
2
FAN COIL UNIT
CWP-FUTURE
WP
4
FUTURE CWP
4
CHILLER ROOM AHU
CHWP-FUTURE
ELEVATOR
LOBBY
307
4
FUTURE CHWP
CWP-3
CHWP-3
CWP-2
CHWP-2
CWP-1
CHWP-1
FAN COIL UNIT
4
FAN COIL UNIT
CWP-3
CHWP-3
CWP-2
CHWP-2
CWP-1
FEC
CHWP-1
ELEVATOR
A
EA
ELEVATOR
CONTROL
310
GENERATOR
4CONTROL
E-141309
FAN COIL UNIT
STAIR
B
SB3
4
4
4
I.T.
ROOM
306
ELEVATOR
C
EC
DEDICATED RECEPTACLE FOR SECURITY DISPLAY.
COORDINATE LOCATION, MOUNTING HEIGHT, AND
REQUIREMENTS WITH SECURITY CONTRACTOR PRIOR
TO INSTALLATION.
1. PROVIDE ELECTRICAL CONNECTIONS FOR ALL EQUIPMENT
INDICATED ON ARCHITECTURAL, MECHANICAL, PLUMBING,
OR OTHER EQUIPMENT PLANS AS REQUIRED. CONNECTION
INFORMATION TO BE COORDINATED WITH FINAL
CONSTRUCTION DOCUMENTS.
2
FAN COIL UNIT
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
GENERAL NOTES:
8
1
REF
ELECTRIC CHILLER
4
8
2
STEAM RECOVERY WATER
HEATER
FUTURE ELECTRIC
CHILLER
6
7
Dewberry Architects Inc.
Pinellas County
CWPFUTURE
ABS
8
COORDINATE FINAL LOCATION WITH
ARCHITECT/OWNER PRIOR TO ROUGH-IN.
PROVIDE DEDICATED BRANCH CIRCUIT IN 208/120V
PANELBOARD. ADJUST CONDUCTOR AND CONDUIT
SIZES FOR VOLTAGE DROP (AS REQUIRED).
J-BOX FOR SECURITY ELECTRONICS. COORDINATE
LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS
WITH OWNER AND SECURITY CONTRACTOR PRIOR TO
INSTALLATION.
4
F
FUTURE CONDENSER
REFRIGERANT PURGE
WATER PUMP FAN
FUTURE CHWP ABSORPTION
ABSORPTION
ELECTRICAL KEY NOTES
KEYNOTE TEXT
5
E-141
COILING DOOR #3
4
D
4
C
4
4
ELECTRICAL
ROOM
312
4
4
C
3
E-141
WP
4
114400 North 49th Street
Clearwater, FL.
5
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
6
KITCHEN SUPPLY FAN
WP
GENERATOR RADIATOR #1
LAUNDRY AHU
4
SEAL
4
4
GENERATOR #1
KITCHEN EXHAUST FAN
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
D
EXTERIOR
ROOF
ER1
C
WP
GENERATOR
ROOM
311
EXTERIOR
ROOF
ER2
D
6
KEY PLAN
FUTURE GENERATOR
RADIATOR #2
4
K102
4
KITCHEN AHU
FUTURE GENERATOR #2
SCALE
4
WP
KITCHEN EQUIPMENT
CONDENSING UNIT
E.9
1/8" = 1'-0"
E.9
WP
F
F
B
1
1
1.1
THIRD FLOOR POWER PLAN
Scale: 1/8" = 1'-0"
3
5
6.9
7
No.
Description
Date
REVISIONS
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
THIRD FLOOR
POWER PLAN
A
PROJECT NO.
E-130
SHEET NO.
50057109
6
5
4
3
2
1
GENERAL NOTES:
1
1.1
3
5
6.9
1. REFER TO REFLECTED CEILING PLANS FOR EXACT LOCATIONS
OF FIXTURES.
2. ALL LIGHTING FIXTURES SHALL BE CONTROLLED VIA RELAY
CONTROL PANELS FROM THE MAIN BUILDING CONTROL/SECURITY
ROOM.
3. PROVIDE UNSWITCHED CONDUCTORS TO ALL EMERGENCY
LIGHTING POWER SUPPLIES IN DESIGNATED FIXTURES.
4. REFER TO SHEET E-000 FOR FIXTURE SCHEDULE.
7
Dewberry Architects Inc.
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
F
A
A
GE
A.1
G
GE
G
G
GE
GE
G
GE
GE
G
A2E
A2E
A2E
A2E
A.1
CONTROL
CONFERENCE RM
A2E
G
GE
G
GE
GE
G
G
GE
G
GE
A2E
A2E
A2E
A2E
A2E
A2E
A2E
A2E
CONTROL
ROOM
302
A2E
G
A2E
REF
A2E OFFICE A2E
301
G
G
GE
GE
G
GE
G
GE
E
REF
B
G
FE
STAIR
GE
G
GE
GE
G
G
GE
G
GE
G
GE
G
X
X
STAFF
TOILET
FE
CHILLER
ROOM
308
SA3
B
FE
F
SECURITY
ELECTRONICS
303
VESTIBULE
FE
S1
X
FE
GE
G
GE
G
G
GE
GE
G
GE
G
GE
G
GE
FE
X
FE
ELEVATOR
LOBBY
307
X
FE
F
STAIR
B
SB3
D3E
G
GE
G
GE
D3E
G
GE
C
G
GE
ELECTRICAL
G
GE
ELEVATOR
ELEVATOR
A
EA
D3E
D
FEC
D3E
GE
310
GE
D3E
GENERATOR
CONTROL
309
GE
GE
GE
G
GE
D3E
G
D3E
ELEVATOR
C
EC
GE
D3E
D3E
FE
I.T.
ROOM
306
FE
D3E
GE
C
312
CE
GE
G
GE
G
X
S1
GE
114400 North 49th Street
Clearwater, FL.
GE
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
G
Pinellas County
GE
CE
S1
G
GE
G
GE
G
SEAL
GE
G
GE
G
GE
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
D
C
S1
EXTERIOR
ROOF
ER1
GENERATOR
ROOM
311
S1
S1
G
GE
G
GE
G
GE
G
GE
G
GE
EXTERIOR
ROOF
ER2
D
S1
KEY PLAN
SCALE
1/8" = 1'-0"
G
E.9
GE
G
GE
G
S1
E.9
S1
F
F
B
1
1
1.1
THIRD FLOOR LIGHTING PLAN
Scale: 1/8" = 1'-0"
3
5
6.9
7
No.
Description
Date
REVISIONS
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
THIRD FLOOR
LIGHTING PLAN
A
PROJECT NO.
E-131
SHEET NO.
50057109
6
5
4
3
2
1
#
1
2
1
1.1
3
5
6.9
7
RELAYS FOR PRIMARY LEVEL ELEVATOR RECALL,
ALTERNATE LEVEL ELEVATOR RECALL, SHUNT-TRIP
ACTUATION, ELEVATOR WARNING LIGHT
ILLUMINATION, AND SHUNT-TRIP CONTROL CIRCUIT
VOLTAGE MONITORING.
4
COORDINATE LOCATION WITH OWNER AND A.H.J.
PRIOR TO INSTALLATION.
FIRE ALARM NOTIFICATION APPLIANCE CIRCUIT
POWER SUPPLY UNIT WITH BATTERY BACKUP
5
A
110cd
A.1
F
F
F
110cd
F
A.1
CONTROL
CONFERENCE RM
313
TAMPER SWITCH FOR CONTROL VALVE SERVING
ELEVATOR HOISTWAY FIRE SPRINKLER PENDENT
COORDINATE LOCATION WITH DIVISION 21
CONTRACTOR PRIOR TO INSTALLATION. PROVIDE
ADDRESSABLE INPUT MONITORING MODULE(S)
LOCATED WITHIN A CONDITIONED, ACCESSIBLE
SPACE OR IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
3
F
A
ELECTRICAL KEY NOTES
KEYNOTE TEXT
Dewberry Architects Inc.
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
GENERAL NOTES:
1. ALL NOTIFICATION DEVICES SHALL HAVE A LUMINOUS
INTENSITY OF 75 CANDELA UNLESS OTHERWISE NOTED.
CONTROL
ROOM
302
REF
F
OFFICE
301
F
F
F
F
B
4
FACP
110cd
REF
F
STAFF
TOILET
305
F
CHILLER
ROOM
308
SECURITY
ELECTRONICS
303
VESTIBULE
304
F
STAIR
A
SA3
B
F
Pinellas County
5
F
2
ELEVATOR
LOBBY
307
FS TS
2
1
QUANTITY: 5
E
2
1
STAIR
B
SB3
E
TS
TS
R
R
F
3
3
GENERATOR
CONTROL
309
I.T.
ROOM
306
ELEVATOR
C
H
EC
F
ELEVATOR
CONTROL
310
H
ELEVATOR
AH
EA
FEC
ELECTRICAL
ROOM
312
C
F
C/
80cd
F
F
D
R
E
3
C/
80cd
QUANTITY: 5
C
110cd
QUANTITY: 5
114400 North 49th Street
Clearwater, FL.
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
F
E
S
SEAL
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
WP
F
WP
GENERATOR
ROOM
311
EXTERIOR
ROOF
ER1
C
D
F
D
EXTERIOR
ROOF
ER2
KEY PLAN
S
SCALE
1/8" = 1'-0"
E.9
F
F
E.9
110cd
F
B
1
1
1.1
THIRD FLOOR FIRE ALARM & MISC. SYSTEMS PLAN
Scale: 1/8" = 1'-0"
3
5
6.9
7
No.
Description
Date
REVISIONS
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
A
THIRD FLOOR
FIRE ALARM &
MISC. SYSTEMS
PLAN
PROJECT NO.
E-132
SHEET NO.
50057109
5
4
3
2
1
#
1
1.1
3
5
6.9
7
1
2
ELECTRICAL KEY NOTES
KEYNOTE TEXT
FREE-STANDING RECEPTACLE
PROVIDE DEDICATED BRANCH CIRCUIT IN
480/277V PANELBOARD. COORDINATE
VOLTAGE, CIRCUIT BREAKER/CONDUCTOR
AMPERE RATING, PHASE, AND
CONNECTION REQUIREMENTS WITH
EQUIPMENT SELECTIONS. ADJUST
CONDUCTOR AND CONDUIT SIZES FOR
VOLTAGE DROP (AS REQUIRED).
Dewberry Architects Inc.
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
A
A.1
A.1
(2) SINGLE-CELL COOLING TOWERS
(ABSORPTION CHILLERS)
(1) FUTURE
2-CELL COOLING TOWER
(ELECTRIC CHILLER)
B
E
S1
FE
FUTURE 2-CELL
COOLING TOWER
(ELECTRIC CHILLER)
2-CELL COOLING TOWER
(ELECTRIC CHILLER)
S1
B
S1
S1
STAIR
A
SA4
S1
FUTURE COOLING TOWER
- ABSORPTION
COOLING TOWER ELECTRIC
FE
1
1
COOLING TOWER ELECTRIC
1
1
FE
1
110cd
WP
WP
WP
FE
WP
2
WP
WP WP
FUTURE COOLING TOWER
- ELECTRIC
2
COOLING TOWER ABSORPTION
FE
2
F
WP WP
110cd
FE
S1
S1
S1
S1
S1
FE
C
D
C
1. A COMPLETE LIGHTNING PROTECTION SYSTEM
SHALL BE FURNISHED IN ACCORDANCE WITH
NFPA 780. SYSTEM TO BE INSTALLED ACCORDING
TO MANUFACTURER'S NRECOMMENDATIONS AND
OBTAIN A UL LETTER OF CIRTIFICATION.
2. THE CONTRACTOR SHALL PROVIDE A COMPLETE
ROOF COMPATIABLE LIGHTNING PROTECTION
SYSTEM AS APPROVED BY ARCHITECT AND/OR
ENGINEER. THE SYSTEM SHALL BE INSTALLED BY
A LIGHTNING PROTECTION CONTRACTOR
ACTIVELY ENGAGED IN THE INSTALLATION OF UL
MASTER LABEL SYSTEMS. THE CONTRACTOR
SHALL HAVE A MINIMUM OF 5 YEARS EXPERIENCE
IN LIGHTNING PROTECTION INSTALLATIONS.
3. INSTALL CONDUCTORS AND COMPLEMENTARY
PARTS SO COMPLETED WORK IS UNOBTRUSIVE
AND DOES NOT DISTRACT FROM APPEARANCE.
4. INTERCONNECT CONDUCTORS TO PROVIDE AT
LEAST TWO ELECTRIC PATHS TO GROUND. AVOID
AN UPWARD DIRECTION FOR LATERAL
CONDUCTORS INTERCONNECTING AIR
TERMINALS. TURN RADIUS OF AT LEAST 8 INCHES
AT AN INCLUDED ANGLE NOT MOREN ACUTE
THEN RIGHT ANGLE. SPACE DOWN CONDUCTORS
AROUND BUILDINGS PERIPHERY AS SHOWN IN
PLAN VIEW.5. REFER TO DETAIL SHEET FOR
LIGHTNING PROTECTION DETAILS.
5. DOWNCONDUCTOR MAY UTILIZE VERTICAL
BUILDING STEEL CLOUMNS WHERE ACCESSIABLE.
OTHERWISE, PROVIDE DOWNCONDUCTOR RUNS
IN PVC AT CONCRETE COLUMNS.
6. BOND FULL SIZE CONDUCTOR TO ALL METAL
OBJECTS ON ROOF. BOND ROOF DRAINS AS
REQUIRED, LADDER HATCHS, ETC.
7. JOB CONDITIONS MIGHT NECESSITATE A SLIGHT
VARIATION IN INSTALLATION.
8. UPON COMPLETION OF THE JOB, THE
CONTRACTOR SHALL FURNISH THE OWNER WITH
A UL LETTER OF CERTIFICATION.
9. PROVIDE LIGHTNING PROTECTION AT
GENERATOR LOCATION AND TIE INTO SYSTEM AS
REQUIRED.
10. REFER TO DETAIL SHEET FOR CONNECTION
DETAILS TO ALL MECHANICAL EQUIPMENT WITH
UNDERLINED TAGS SHOWN ON PLAN VIEW.
11. LIGHTNING PROTECTION SYSTEM SHALL BE
COPPER.
Pinellas County
A
F
F
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
LIGHTNING PROTECTION GENERAL NOTES:
STAIR
B
SB4
FE
114400 North 49th Street
Clearwater, FL.
6
2
2
SEAL
GENERATOR SUPPLY FAN
GENERATOR EXHAUST
FAN
D
D
C
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
KEY PLAN
SCALE
FUTURE SUPPLY FAN
FUTURE EXHAUST FAN
1/8" = 1'-0"
E.9
E.9
F
F
B
1
1
ROOF ELECTRICAL PLAN
Scale: 1/8" = 1'-0"
1.1
3
5
6.9
7
No.
Description
Date
REVISIONS
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
ROOF
ELECTRICAL PLAN
A
PROJECT NO.
E-140
SHEET NO.
50057109
6
5
4
3
2
1
#
ELECTRICAL KEY NOTES
KEYNOTE TEXT
1 SUSPEND TRANSFORMER FROM STRUCTURE.
2 PROVIDE DEDICATED BRANCH CIRCUIT IN 208/120V PANELBOARD.
COORDINATE VOLTAGE, CIRCUIT BREAKER/CONDUCTOR AMPERE
RATING, PHASE, AND CONNECTION REQUIREMENTS WITH EQUIPMENT
SELECTIONS. ADJUST CONDUCTOR AND CONDUIT SIZES FOR VOLTAGE
DROP (AS REQUIRED).
3
FAN COIL UNIT
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
3 PROVIDE DEDICATED BRANCH CIRCUIT IN 480/277V PANELBOARD.
COORDINATE VOLTAGE, CIRCUIT BREAKER/CONDUCTOR AMPERE
RATING, PHASE, AND CONNECTION REQUIREMENTS WITH EQUIPMENT
SELECTIONS. ADJUST CONDUCTOR AND CONDUIT SIZES FOR VOLTAGE
DROP (AS REQUIRED).
LDP
F
Dewberry Architects Inc.
L1N
ELECTRICAL
H1N
140
TL1N
2
2
2
1
FAN COIL UNIT
ENLARGED PLAN - ELEC. 140
I.T.
ROOM
306
Scale: 1/4" = 1'-0"
2
2
2
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
2
E
2
KDP
FAN COIL UNIT
L2N
3
L2KB
1
ELEC
233
1
1
TL2KB
H2NK
5
H2N
ENLARGED PLAN - I.T. ROOM 306
Scale: 1/4" = 1'-0"
Pinellas County
TL2N
TL2KA
L2KA
2
ENLARGED PLAN - ELEC. 233
Scale: 1/4" = 1'-0"
F
A1E
X
D
E.9
A1
F
A1E
CN
114400 North 49th Street
Clearwater, FL.
2
A1
DEDICATED ELECTRICAL CHASE BELOW FOR SERVICE FEEDERS.
SERVICE #1: 4,000A - TEN (10) 4" CONDUITS
SERVICE #2: 4,000A - TEN (10) 4" CONDUITS
SERVICE #3: 3,000A - EIGHT (8) 4" CONDUITS
H3NA
A1E
6.9
7
TL3NA
MDP-B
A1
SEAL
MDP-A
A1E
PRELIMINARY DOCUMENTS
L3NA
F
A1
NOT FOR CONSTRUCTION
PP-MECH
C
A1E
KEY PLAN
X
3
ENLARGED PLAN - ELECTRICAL ROOM 312
Scale: 1/4" = 1'-0"
6
PARTIAL ELECTRICAL PLAN - BRIDGE TO CENTRAL
Scale: 1/8" = 1'-0"
SCALE
As indicated
ELEV. CAB
ELEV.
MOTOR/CONTROLLER
FAN COIL UNIT
ELEV. CAB
B
310
3
ELEV.
MOTOR/CONTROLLER
ELEV.
MOTOR/CONTROLLER
No.
Description
Date
ELEV. CAB
REVISIONS
4
ENLARGED PLAN - ELEVATOR CONTROL ROOM 310
Scale: 1/4" = 1'-0"
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
A
ENLARGED
ELECTRICAL
PLANS
PROJECT NO.
E-141
SHEET NO.
50057109
6
5
4
3
2
1
ELECTRICAL KEY NOTES
KEYNOTE TEXT
#
1
2
3
4
5
F
6
7
8
THREE HOUR CHASE FOR SERVICE ENTRANCE CONDUIT ROUTING. REFER TO ARCHITECTURAL
DRAWINGS FOR DETAILS.
DESIGN/BUILDER TO ROUTE ALL CONDUITS FOR ELECTRICAL SERVICES FOR PHASE 1 AND
FUTURE PHASES IN ELECTRICAL CHASE. STUB-UP AND CAP ALL FUTURE CONDUIT ON
EXTERIOR OF BUILDING.
REVERSE REVENUE METERING EQUIPMENT FOR CO-GENERATION SYSTEM. METERING
REQUIREMENTS PER DUKE ENERGY INTERCONNECTION STANDARDS.
DESIGN/BUILDER TO COORDINATE FINAL CONNECTION REQUIREMENTS TO ALL MECHANICAL
EQUIPMENT WITH FINAL EQUIPMENT SELECTIONS.
2.1 MW, 480/277V, 3 PH., 4 WIRE COGENERATION UNIT. BASIS OF DESIGN IS A GE/JENBACHER,
NATURAL GAS, RECIPROCATING ENGINE.
KITCHEN DISTRIBUTION PANEL AND ALL KITCHEN BRANCH CIRCUIT PANELS TO BE BASED ON
ALL FINAL LOAD INFORMATION IN FINAL DESIGN/BUILD DOCUMENTS.
LAUNDRY DISTRIBUTION PANEL AND ALL LAUNDRY BRANCH CIRCUIT PANELS TO BE BASED ON
ALL FINAL LOAD INFORMATION IN FINAL DESIGN/BUILD DOCUMENTS.
GENERATOR/UTILITY PARALLELING SWITCHGEAR. PROVIDE ALL REQUIRED RELAYING,
INSTRUMENTATION, AND CONTROL PER DUKE ENERGY INTERCONNECTION REQUIREMENTS.
REFER TO NARRATIVES AND SPECIFICATIONS FOR DETAILS.
Dewberry Architects Inc.
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
GENERAL NOTES:
Pinellas County
E
ELECTRIC CHILLER 2
ELECTRIC CHILLER 1
ELECTRIC CHILLER 3 (FUTURE)
4
8
FUTURE
HOUSING
PP-MECH
(GEN.)
(UTILITY)
1200A-3P
SPACE
CONTROLS
AND
INSTRUMENTATION
1200A-3P
SPACE
2500A-3P
1200A-3P
SPARE
FUTURE
HOUSING
FUTURE (4000A FRAME)
FUTURE
HOUSING
FUTURE
HOUSING
800A-3P
SPACE
800A-3P
SPACE
800A-3P
SPARE
4
FUTURE (4000A FRAME)
FUTURE
HOUSING
4000A-3P
800A-3P
SPARE
2000A-3P
800A-3P
800A-3P
SPACE
CONTROLS
AND
INSTRUMENTATION
2500A-3P
(GEN.)
4000A-3P
(UTILITY)
SPD
SPD
4000A-3P
MDP-A
3000A-3P
2500A-3P
1200A-3P
SPACE
1200A-3P
SPACE
MDP-B
(TIE)
D
H3NA
5
5
SECTION 1 SECTION 2
400A
SPD
4000A
SPD
H3NA
L3NA
L3NA
SECTION 1 SECTION 2
SPD
400A
225A
225A
4000A
114400 North 49th Street
Clearwater, FL.
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
ALL SIZES INDICATED ON THIS DRAWING SHALL BE VERIFIED BY DESIGN BUILDER AND
ADJUSTED AS REQUIRED BASED ON FINAL LOAD CALCULATIONS.
ALL FINAL LOAD CALCULATIONS SHALL INCLUDE ALL FUTURE WORK AS PART OF MASTER
PLAN ELEMENTS.
ALL UTILITY WORK TO BE PER DUKE ENERGY REQUIREMENTS.
REFER TO DESIGN CRITERIA NARRATIVES FOR ADDITIONAL DETAILS.
REFER TO MECHANICAL AND ELECTRICAL SPECIFICATIONS AND NARRATIVES FOR COGENERATION DESCRIPTION AND DETAILS.
TL3NA
75KVA XFMR
2000A
LEVEL 3
FUTURE
1
TO BUILDING STEEL
AND COLD WATER
PIPING
TO BUILDING STEEL
AND COLD WATER
PIPING
SEAL
TO BUILDING STEEL
AND COLD WATER
PIPING
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
KDP
C
2
L2KA
L2KA
L2KA
L2KB
SECTION 3 SECTION 2 SECTION 1
6
400A
400A
KEY PLAN
L2KB
L2KB
SECTION 1 SECTION 2 SECTION 3
SPD
400A
400A
400A
400A
H2NK
SECTION 1
400A
H2N
SPD
SECTION 1
L2N
L2N
SECTION 1 SECTION 2
SPD
400A
225A
225A
800A
TL2KA
TL2KB
TL2N
112.5KVA XFMR
112.5KVA XFMR
75KVA XFMR
LEVEL 2
L1N
L1N
3
UTILITY XFMR 'C'
M
3
FUTURE UTILITY XFMR 'B'
M
400A
UTILITY XFMR 'A'
NOT TO SCALE
LDP
H1N
SECTION 2 SECTION 1
SCALE
SECTION 1
400A
400A
SPD
7
SPD
M
TL1N
600A
112.5KVA XFMR
LEVEL 1
B
GROUNDING
ELECTRODE
SYSTEM
1
Electrical Riser Diagram
No.
Description
Date
REVISIONS
Scale: N.T.S.
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
ELECTRICAL
RISER DIAGRAM
A
PROJECT NO.
E-200
SHEET NO.
50057109
6
5
4
3
2
1
Dewberry Architects Inc.
CENTERED BETWEEN
DOOR & CEILING
(COORDINATE WITH
ARCHITECT)
1/16" THICK WHITE PLASTIC WITH
COLORED FACE PER SPECIFCIATIONS
F
CLOCK OUTLET
EXIT
h
TELEVISI
ON
OUTLET
PANELBOARD
CENTERED OVER DOOR
(WHERE APPLICABLE)
AHU-X
F
h
90"
FIRE HORN (OR CHIME) & LIGHT
80" AFF FROM BOTTOM OF
DEVICE
480V, 3∅
FED FROM "NDH1-4"
REMOTE TEST
VOLUME CONTROL
1/4" HIGH LETTERING FOR
REMAINING TEXT
120/208V, 3∅, 4W
FED FROM PANEL "XXXX"
VIA T-XXX
ADHESIVE BACKING WHEN INSTALLED
IN CONDITIONED SPACES
TYPICAL 120/208V PANELBOARD
80"
FA PULL
STATION
DUPLEX RECEPTACLE
h
h
TELE. OUTLET
EQUIPMENT VOLTAGE
h
6" AFC
EQUIPMENT NAME
54"
SWITCH
48"
78" MAX.
TO TOP DEVICE
PANEL "XXXX"
1/16" THICK WHITE PLASTIC
WITH COLORED FACE PER
SPECIFCIATIONS
1/4" HIGH LETTERING
FOR REMAINING TEXT
1\2" HIGH LETTERING FOR
PANELBOARD NAME
AHU-X
COMPUTER
OUTLET
1
480V, 3∅
FED FROM "NDH1-4"
TELE. OUTLET
36"
AFF
18"
AFF
E
PANEL "XXX"
PANELBOARD VOLTAGE
FASTEN WITH BRASS SCREWS WHEN
LOCATED IN NON-CONDITIONED OR
EXTERIOR SPACES
h
PANELBOARD NAME
277/480V, 3∅, 4W
FED FROM PANEL "XXXX"
PANELBOARD SOURCE
EQUIPMENT SOURCE
(PANEL & CIRCUIT)
TYPICAL 277/480V PANELBOARD
TYPICAL EQUIPMENT
42" A.F.F. W/ 36" COUNTER,
39" A.F.F. W/ 30" COUNTER,
48" A.F.F. WITHOUT COUNTER
OR AS NOTED ON PLANS
FINISHED FLOOR
DUPLEX RECEPTACLE
SPECIAL POWER OUTLET
ELECTRICAL MOUNTING HEIGHTS DETAIL
1
NOT TO SCALE
EQUIPMENT NAMEPLATE DETAIL
2
NOT TO SCALE
PANELBOARD NAMEPLATE DETAIL
3
NOT TO SCALE
MOUNTING BRACKET (TYP.)
10"
JOISTS
#6-32 (TYP.)
CADWELD
B544A018
OR EQUAL
1-1/8"
PRIMARY EQUIPMENT
GROUNDING CONDUCTOR
(PER NEC 250-122)
3/4" CONDUIT (TYP.
FOR ALL DEVICES)
D
F
F
FS
TS
TYPICAL INDICATING
DEVICES
DELTA
GROUND BAR
F
TYPICAL INDICATING
DEVICES
TYPICAL CONTROL
RELAYS
H
F
H
F
F
F
F
R
R
FS
TS
DEDICATED TELEPHONE
CONNECTION
FOR THIRD PARTY NOTIFICATION
DIALER
TYPICAL INITIATING
DEVICES
-
+
FIRE ALARM
ANNUNCIATOR
PANEL (FAAP)
SECONDARY PHASE
CONDUCTORS
NEUTRAL
COMMUNICATIONS CABLING TO
EXISTING FACP IN CENTRAL
C
120V POWER
HE
(SI AVY
BY ZED DUTY
ST
CH
RU
AN
CT
NE
UR
L IR
LE
A
L
ON
N
EN
JO GTH
GIN
IST
T
E
ER
SA OM
)
S R ATC
EQ
H
UIR
ED
BONDING JUMPER
(PER NEC 250.28,102)
PERMANENT FIRE
ALARM
ZONE LEGEND
-
#6 GROUNDING CONDUCTOR TO
NEAREST METAL WATER PIPE.
GROUNDING ELECTRODE,
VIA GROUND BAR
(PER NEC 250.30)
TYPICAL SPRINKLER
TAMPER AND FLOW
SWITCHES
FIRE ALARM
CONTROL PANEL
+
WYE
SECONDARY EQUIPMENT
GROUNDING CONDUCTOR
(PER NEC 250.122)
FIRE ALARM RISER DIAGRAM
4
NOT TO SCALE
STEP DOWN TRANSFORMER GROUNDING
NOT TO SCALE
r" NEOPRENE
ISOLATION
PAD
FRONT VIEW
GROUND BUS BAR
GROUND CONDUCTORS
QUANTITY AS
REQUIRED.
SEAL
STANDOFF BRACKET
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
NOTES:
COMMUNICATIONS CABLING TO
EXISTING FACP IN "A" SOUTH
1st FLOOR
#6 TO COMMUNICATIONS RACK
#4/0 GROUNDING CONDUCTOR TO NEXT GROUND
BAR OR TO MAIN SERVICE GOUND.
THREADED ROD (SIZE TO
BE DETERMINED BY
STRUCTURAL ENGINEER)
GROUNDING ELECTRODE
CONDUCTOR
(PER NEC 250.66)
TYPICAL INDICATING
DEVICES
FACP
ADDRESSABLE
FIRE ALARM
SYSTEM WITH
NETWORK
INTERFACE
CARD(S) AND
BATTERY
BACKUP AS
A3
REQUIRED
SPD
TR
AN
SF
OR
ME
R
BONDING JUMPER TO FRAME
(PER NEC 250.28,102)
3/4" CONDUIT (TYP.
FOR ALL DEVICES)
TYPICAL INITIATING
DEVICES
9/32"
(TYP.)
JOIST HANGER CLIP
(TYPICAL OF 2)
DRY-TYPE TRANSFORMER
TYPICAL SPRINKLER
TAMPER AND FLOW
SWITCHES
UPPER FLOORS AND ROOF
4"
TYPICAL INITIATING
DEVICES
1"
F
C
INSULATOR
GROUND LUGS
1"
H
3/4"
PRIMARY PHASE
CONDUCTORS
Pinellas County
1
114400 North 49th Street
Clearwater, FL.
WALL MOUNTED LIGHT FIXTURES
AS NOTED ON PLANS
1\2" HIGH LETTERING FOR
PANELBOARD NAME
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
h
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
5
1.
MAXIMUM TRANSFORMER SIZE TO BE HUNG SHALL BE 75KVA.
2.
COORDINATE ALL SUPPORT DETAILS AND SIZES WITH STRUCTURAL
ENGINEER.
3.
TRANSFORMER SHALL BE POSITIONED TO ALLOW 48"
CLEARENCE IN FRONT OF TRANSFORMER.
TRANSFORMER HANGER DETAIL
NOT TO SCALE
CUT ROD FLUSH
TO
CHANNEL IRON
CADWELD
B544A018
OR EQUAL
DOUBLE NUT WITH
LOCK WASHERS
6
KEY PLAN
INSULATOR
ISOMETRIC ELEVATION
GROUND BAR DETAIL
NOT TO SCALE
7
SCALE
TWIST ALL LEADS TOGETHER
(AS MANY TURNS AS
PRACTICAL) AND TIE WRAP
TYPICAL TVSS DEVICE
LOCATIONS (CAT C3
OR AS
INDICATED ON
DRAWINGS)
BREAKER FEEDING
SURGE
SUPPRESSOR
(TYP)
NOT TO SCALE
TWIST ALL LEADS
TOGETHER
(AS MANY TURNS AS
PRACTICAL) AND TIE
WRAP
OPTIONAL TVSS
DEVICE
LOCATIONS (CAT
B3
OR C1 AS
INDICATED
ON DRAWINGS)
B
No.
NEUTRAL BUS
CONNECTION
BREAKER FEEDING
SURGE SUPPRESSOR
Date
REVISIONS
NEUTRAL BUS
CONNECTION
PANELBOARD
Description
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
SERVICE ENTRANCE OR DISTRIBUTION PANEL
03/19/2014
TITLE
ELECTRICAL
DETAILS
NOTE: MOUNT TVSS DEVICE IN A LOCATION TO MAINTAIN ALL
LEADS AS SHORT AS POSSIBLE. (18" MAX.)
A
TVSS EXTERIOR MOUNT INSTALLATION DETAIL
NOT TO SCALE
8
PROJECT NO.
E-201
SHEET NO.
50057109
6
5
4
3
2
1
Dewberry Architects Inc.
PLAIN LOCKING LID
FINISHED GRADE
PARAPET
CABLE TO CABLE HEAVY
DUTY TYPE CADWELD
"TA" SERIES
F
COPPERWELD
GROUND ROD
5/8" X 20'-0"
VERTICALLY
DRIVEN.
HIGHER ROOFTOP
5 1/4" DIA VALVE BOX
COPPERWELD GROUND
ROD
5/8" X 20'-0" VERTICALLY
DRIVEN.
CABLE TO GROUND
ROD
HEAVY DUTY TYPE
CADWELD "GT"
SERIES.
10" MIN. ABOVE
HIGHEST SURFACE
MAIN CONDUCTOR (COPPER)
24"
(1) 1"C.
CONCEALED
WITHIN WALL
GROUND WIRE
#115000CM
COPPER
CABLE
APPROVED
EXOTHERMIC
CONNECTION
2'-0" MAX. TO
OUTSIDE
EDGE OF ROOF
SET SCREW TYPE FITING
CADWELD BONDED
CONNECTIONS
TO BE USED FOR ALL
CONCEALED
INACCESIBLE
CONNECTIONS
2" MIN.
MAIN
CONDUCTOR
(COPPER)
CL ROD
ROD CL
AIR TERMINAL
CADWELD BONDED
CONNECTION
TO BUILDING STEEL
CABLE TO GROUND ROD
HEAVY
DUTY TYPE CADWELD
"GT" SERIES.
#115000CM COPPER CABLE
PREMANUFACTURED THRUROOF
PENETRATION
MAIN CONDUCTOR (COPPER)
401 SW Water St.
Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax
FLAT SURFACE BASE
ATTACHED
TO TOP SURFACE
PREMANUFACTURED THRUROOF PENETRATION
MAINTAIN
20'-0"
BETWEEN
RODS
3" MIN.
SET SCREW TYPE FITTING
COMPACTED GRAVEL
CADWELD BONDED
CONNECTIONS
TO BUILDING STEEL
LIGHTNING CONDUCTOR
LOWER ROOFTOP
GROUND ROD CONNECTION DETAIL
NOT TO SCALE
GROUND ROD
1
GROUND ROD INSPECTION WELL DETAIL
2
NOT TO SCALE
HIGHER TO LOWER ROOF CONDUCTOR DETAIL
3
NOT TO SCALE
ROOF MOUNTED AIR TERMINAL DETAIL
4
NOT TO SCALE
CLASS 1 COPPER LIGHTNING
CONDUCTOR (32 x 17 AWG)
ALUMINUM POINT (1/2"x12")
CLASS 1 COPPER
LIGHTNING
CONDUCTOR (32 x 17
AWG)
CONNECTOR
D
STAINLESS STEEL NUT
ALUMINUM ROOF CABLE
LOOP WITH
STAINLESS
STEEL SHEET
METAL
SCREW
STAINLESS STEEL WASHER
LEAD SEALING WASHER
1\2" DIA.
BRASS
THREADED
RISER
BAR
BOOT FLASHING FURNISHED AND
INSTALLED BY ROOFING
CONTRACTOR
SOLID ALUMINUM AIR
TERMINAL
SPACE ALONG
PARAPET 20'
O.C. MAX
METAL MOUNT
POINT BASE
WITH STAINLESS
STEEL
SHEET METAL
SCREW
THRU-ROOF CONNECTOR WITH BRONZE
MOUNTING PLATE SECURED TO ROOF
DECK EXTENDING UP THROUGH
INSULATION AND ROOFING MATERAILS
ROOF
LEAD SEALING WASHER AND
STAINLESS STEEL WASHER
STAINLESS STEEL NUT
BIMETALLIC CABLE SPLICE
UNIVERSAL CABLE
ANCHOR
SPACED 3'-0" O.C.
MAX
SEAL
OFFSET WALL POINT
BASE
BOLT & LEAD
ANCHOR
W/ SEALANT
AROUND BASE
CLASS 1 COPPER
LIGHTNING
CONDUCTOR (32 x 17
AWG)
VERTICAL CONNECTOR
10" MIN
2'-0" MAX
ALUMINUM CABLE RUN TO
ROOF CIRCUIT
WITH PARALLEL CABLE SPLICE
1\2" DIA. BRASS THREADED RISER BAR
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
CLASS 1 COPPER LIGHTNING
CONDUCTOR (32 x 17 AWG)
C
THRU-ROOF CABLE CONNECTOR DETAIL
NOT TO SCALE
Pinellas County
E
114400 North 49th Street
Clearwater, FL.
1. LOCATE GROUND RODS A MINIMUM OF 2'-0" FROM BUILDING FOUNDATION.
2. TOP OF GROUND ROD SHALL BE A MINIMUM OF 1'-0" BELOW FINISHED GRADE
Pinellas County Jail Phase I
Infrastructure Criteria Package - Drawings
SLOT BOX FOR CABLE
KEY PLAN
5
THRU-WALL CABLE PENETRATION DETAIL
NOT TO SCALE
6
TYPICAL AIR TERMINAL ON EXHAUST EQUIPMENT DETAIL
NOT TO SCALE
7
TYPICAL AIR TERMINAL ON PARAPET DETAIL
NOT TO SCALE
8
SCALE
NOT TO SCALE
B
No.
Description
Date
REVISIONS
DRAWN BY
JMB
APPROVED BY
GAC
CHECKED BY
GAC
DATE
03/19/2014
TITLE
ELECTRICAL
DETAILS
A
PROJECT NO.
E-202
SHEET NO.
50057109