DRAWING SYMBOLS E A R NORTH ARROW DETAIL DETAIL IDENTIFICATION 0.00' 0.00' Structural Engineer Contact: Rich Boyer Ridge Engineering 15475 NW Pumkin Ridge Rd. North Plains, OR 97133 Ph. 503.702.9169 M PARTITION TYPES (SEE SHEET A1.0) WINDOW TYPE (SEE SHEET A2.0) S ARCHITECTURAL DRAWINGS INDEX B Sheet Number F EXISTING GRADE 2 REVISION A1.0 A1.1 A1.2 A1.3 A1.4 A2.0 A3.0 A4.0 A4.1 A5.0 A5.1 N PROPERTY LINE FENCE C XX COLUMN GRID G O XX T 1ST FLOOR APARTMENT PLANS 2ND FLOOR APARTMENT PLANS ROOF PLAN UNIT PLAN - ACCESSIBLE UNIT PLAN - ADAPTABLE EXTERIOR ELEVATIONS BUILDING SECTIONS WALL SECTIONS & DETAILS WINDOW FLASHING DETAILS DUCTING AND VENTILATION PLAN RADON MITIGATION PLAN E1.1 LIMITED ELECTRICAL PLAN BREAKLINE SYMBOLS STRUCTURAL DRAWINGS INDEX WORK, CONTROL 0'-0" 1ST FLR. OR DATUM POINT H GYPSUM BOARD Sheet Number Sheet Name S0.0 S1.0 S2.0 S3.0 S4.0 S5.0 S5.1 STRUCTURAL NOTES FOUNDATION PLAN 2ND FLOOR FRAMING PLAN ROOF FRAMING PLAN STRUCTURAL ELEVATIONS & SHEAR WALL SCHEDULE STRUCTURAL DETAILS STRUCTURAL DETAILS P U CONCRETE EARTH GRAVEL V PLASTER & LATH D I CMU OR BRICK PLYWOOD BIDDER DESIGN ELECTRICAL CRITERIA W RIGID INSULATION J Q WOOD MEMBER 1. ELECTRICAL DESIGN CONTRACTOR WILL COORDINATE POWER, SIGNAL AND LIGHTING DESIGN AND PROVIDE CALCULATIONS IN CONFORMANCE WITH STATE ELECTRICAL CODE, ENERGY CODE AND BUILDING CODE. K 2. ELECTRICAL DESIGN CONTRACTOR WILL REVIEW THE PROGRAM DRAWING AND WILL MEET WITH THE TENANT TO FINALIZE THE EXACT POWER LOCATIONS AND REQUIREMENTS FOR EQUIPMENT. DESIGN WILL PROVIDE FOR CODE REQUIRED AND MAINTENANCE RECEPTACLES. DESIGN WILL INCLUDE FIRE ALARM SYSTEM IF REQUIRED, COORDINATED AND EXTENDED FROM BUILDING FIRE ALARM SYSTEM. OUTLETS, PHONE AND DATA JACKS SHOWN ON ARCHITECTURAL PLANS (IF ANY) ARE MINIMUM REQUIRED AND MAY NOT INCLUDE ADDITIONAL OUTLETS REQUIRED BY CODE OR FOR MANTENANCE. WOOD BLOCKING FINISHED WOOD ACOUSTICAL TILE TOTAL SQUARE FOOTAGES STEEL 3. ELECTRICAL DESIGN CONTRACTOR WILL COORDINATE HIS WORK WITH THE ARCHITECT AND WITH THE HVAC AND FIRE SPRINKLER DESIGN/BUILD 4. ELECTRICAL DESIGN CONTRACTOR WILL MEET WITH THE TENANT TO DETERMINE AND/OR CONFIRM THE LOCATION OF ALL DATA AND COMMUNICATION CONNECTIONS REQUIRED AND INCLUDE CONDUIT, BOX AND PULL STRING IN THE REQUIRED LOCATIONS UNDER THE T.I. CONTRACT. CODE SUMMARY ALUMINUM 7,260 SF = LIVING UNITS 536 SF = PATIOS AND DECKS 1,830 SF = EXTERIOR BREEZEWAYS ________________________________ SECTION I - GOVERNING CODES 2009 IBC W/ WA. AMENDMENTS AND CITY OF VANCOUVER AMMENDMENTS DEFERRED SUBMITTALS: 1 Sheet Name C1.0 COVER SHEET C1.1 CODE ANALYSIS / SITE PLAN A0.1 BUILDING PLANS/OCCUPANCY AND EXITING ANALYSIS GRADE ELEVATION NEW OR FINISH GRADE BATT INSULATION 9,189 SF TOTAL Ph. 360.699.5317 fax. 360.694.7818 SECTION II - GENERAL BUILDING DATA 1. NUMBER OF STORIES: 2 2. FIRE SPRINKLERS YES 903.3.1.2 NFPA 13R 3. CONSTRUCTION TYPE: V-B OCCUPANCY GROUP: R-2 WOOD ROOF TRUSSES FIRE SPRINKLER HVAC ELECTRICAL PLUMBING SEE SHEET A0.1 FOR OCCUPANT LOAD AND EXITING 5. CONFIRM LIGHTING SWITCHING REQUIREMENTS WITH OWNER 6. CONSTRUCTION AND AS-BUILT DRAWINGS TO BE PROVIDED ON ELECTRONIC MEDIA, AUTOCAD RELEASE 14 OR LATER, TO THE ARCHITECT FOR THE OWNER'S RECORDS. ELECTRICAL DESIGN/BUILD CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY ALL DEVICES, INCLUDING BUT NOT LIMITED TO: STROBES, ANNUNCIATERS AND EGRESS LIGHTING, REQUIRED BY ALL APPLICABLE CODES. POWER AND LIGHTING DRAWINGS INCLUDED IN THIS DOCUMENT ARE FOR DESIGN PURPOSES ONLY. ANY DEVICE REQUIRED BY CODE OR BY BUILDING OFFICIAL AND NOT INCLUDED IN ELECTRICAL DESIGN/BUILDERS BASE BID SHALL BE INSTALLED AT THE ELECTRICAL DESIGN CONTRACTOR'S EXPENSE. 1 7. ENERGY INFORMATION FOUND ON SHEET A0.1 PER RCW 64.55 FLASHING DETAILS ARE PROVIDED ON SHEET A4.0, SPECIAL INSPECTIONS AS REQUIRED ARE THE G.C.'S RESPONSIBILITY. WATER TESTING OF THE WINDOW FLASHING AND WATER BARRIER BY THE G.C. IS REQUIRED UNLESS A STANDARD PRE-TESTED ASSEMBLY IS USED. G.C. TO PROVIDE A SUBMITTAL OF THE DETAILS THEY ARE TO USE. TYPE "A" AND "B" UNITS EACH UNIT SHALL BE PROVIDED WITH ONE OR MORE SHUT-OFF VALVES TO TERMINATE TYPE A UNITS REQUIRED: (72) 2 BEDROOM UNITS X 5% = (4) 2 BEDROOM UNITS REQUIRED. TYPE A UNITS REQUIRED: BUILDING A-1 HAS (2) TYPE A UNITS. BUILDINGS B-1 AND B-4 HAVE (2) TYPE A UNITS IN EACH BUILDING. TYPE B UNITS ARE REQUIRED IN THE BALANCE OF THE BOTTOM FLOORS OF ALL UNITS. THERE ARE (18) TYPE B UNITS IN THE "A" BUILDINGS AND (20) TYPE B UNITS IN THE "B" BUILDINGS. AFFECTING THE DWELLING UNITS. ALL SHUT-OFF VALVES NEED TO BE ACCESSIBLE TO THE DWELLING UNIT OCCUPANT AT ALL TIMES AND WITHOUT THE REMOVAL OF ANY PERMANENT CONSTRUCTION. This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. 1 DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting 6/22/2012 DRAWN BY CHECKED BY KK,ED DH 2. IT IS THE DESIGN/ BUILD CONTRACTOR'S RESPONSIBILITY TO CONFORM TO ALL APPLICABLE BUILDING CODES AND TO PROVIDE ALL DOCUMENTATION REQUIRED TO OBTAIN PERMITS FOR WORK UNDER THEIR CONTRACT. WATER SUPPLY TO COMMON AREAS SHALL BE CAPABLE OF BEING TERMINATED WITHOUT 1 REUSE OF DOCUMENTS 1. ALL MECHANICAL, ELECTRICAL, PLUMBING WORK SHALL BE PROVIDED UNDER A SEPARATE CONTRACT AND PERMIT. WATER SUPPLY TO EACH UNIT W/O AFFECTING OTHER DWELLING UNITS IN THE BUILDING. (40) 1 BEDROOM UNITS X 5% = (2) 1 BEDROOM UNITS REQUIREDBUILDINGS. SHEET TITLE COVER SHEET MECHANICAL, ELECTRICAL, PLUMBING DESIGN BUILD NOTES NOTE: VANCOUVER, WA 98684 H Western Design Group, Inc 2300 East Third Loop #110 Vancouver, WA 98661 SHEET WHERE DRAWN DOOR TAG REFER TO SCHEDULE A Architect Contact: David Hardister,AIA NE BURTON RD. & NE 79TH XX.XX Burton Park Apartments, LLC Building XX Owner BURTON PARK APARTMENTS 9. All exit doors shall be provided with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of a key or tool and mounted at a height not exceeding 48" above the finish floor. 10. Safety glass installed in all hazardous locations as per IBC. 11. The slope of the fill and cut surfaces should not be less than 2 to 1. All final slope faces should be densified and planted or seeded with appropriate vegetation in order to minimize the potential for erosion. No water should be allowed to flow freely over any slope faces. 12. All rockeries should be constructed in conformance with the general guidelines provided by the American Rockery Contractor (ARC). 13. All structural fills should be compacted to 95% of their laboratory maximum dry density as determined by ATSM D-1557 (Modified Proctor). 14. The contractor is responsible to check the plans and is to notify the designer of any errors or omissions prior to the start of construction. 14. Written dimensions have precedence over scaled dimensions 15. Provide insulation baffles at eave vents between rafters. 16. All smoke detectors shall be powered by 110v current, connected to the house electrical system, interconnect with each one so that if any one trips they will all sound. They shall also have a battery backup and be located in each bedroom and on each floor level. 17. Porch rails shall have intermediate rails spaced such that a sphere 4" in dia. cannot pass through. 18. Provide grounding electrode at electrical service consisting of a minimum 20' length of 1/2" dia. steel reinforcement of footings. Electrode shall extend 12" min. above the plate line. 19. The maximum amount of water used by new plumbing fixtures: Toilets: 1.6 gallons/flush Shower heads: 2.5 gallons/minute 20. In the event of a conflict between pertinent codes and regulations and referenced standards of thesespecifications, the more stringent of provisions shall govern. 21. Structural specifications and drawings for this work have been prepared in accordance with generally accepted engineering practice to meet minimum requirements of the latest edition of the International Building Code w/ WA and City of Vancouver ammendments. 22. Specifications and drawings indicate finished structure. Builder shall be responsible for construction methods, procedures, and conditions (including safety) except as specifically indicated otherwise in the contract documents. 23. Construction loads shall not overload structure nor shall they be in excess of design loadings indicated on drawings. Builder shall rigidly adhere to all laws, codes, and ordinances which apply to this work. He shall notify and receive clarification from owner in writing of any variations between contract documents and governing regulations. 24. All manufactured materials, components, fasteners, assemblies, etc., shall be handled and installed in accordance with manufacturer's instructions and provisions of applicable ICC research recommendations, where specific manufactured products are called for, generic equals which meet applicable standards and specifications may be used. L x 1. Ventilation: A. Attic Ventilation: Shall have a minimum net free area of 1/150 of the attic area or 1/300 net area if one half the area is soffit vent and one half is 3 ft. above plate line. Note: with enclosed rafter spaces fIow-thru venting is required with 1" of air space between insulation and roof sheathing. Also 1" air space @ soffit vents above insulation. B. Crawl Space Ventilation: Shall have a minimum net area of 1 square foot for each 150 square feet of crawlspace area. 1 vent required within 3 feet of each corner. Contractor is responsible for providing adequate venting, whether or not vents are shown. 2. Windows: Egress windows in sleeping area shall not be more than 44" from finished floor to sill and shall have an opening with minimum dimensions 20" wide 24" high with a minimum area of 5.7 square feet. All glass over 18" wide and within 18" of the floor shall comply with impact loads. Sliding glass doors shall be safety glazed with laminated air tempered glass. 3. Stairways: All stairways shall have a maximum tread rise of 7 " and a minimum tread run of 11". The greatest Riser Height and Tread Depth within any flight of stairs shall not excede the smallest by more than 3/8". Handrails to be 34" MIN - 38" MAX. Minimum headroom to be 6'-8" measured from nosing. 4. Vapor Barrier: A ground cover of 6 mil (.006") polyethylene or equivalent lapped one foot at each joint and extended up the foundation wall to at least the outside ground line, is required. See radon mitigation sheet A 5. Showers: Showers shall be either one-piece fiberglass stall unites or ceramic tile wall to 6ft. above floor minimum and shall be provided with a water resistant backing. All shower doors shall be tempered or laminated safety glass or shatter resistant plastic. 6. Fireplaces: (Site built and zero clearance) Fireplaces shall be provided with: A. Tightly fitting flue dampers, operated with a readily accessible manual or approved automatic control. B. An outside source of combustion air. Minimum duct size to be six (6) square inches with readily operable damper (outlet must be inside front of firebox). Note: All metal zero clearance fireplaces shall bear label of nationally recognized testing lab on all pieces of assembly. To be installed in accordance with label requirements and per manufacturers instructions. C. Terminate all chimney and flues a minimum of 2ft. above the highest point of the building within 10ft. of the flue. 7. When Gypsum wallboard is used as a base for tile in tub and shower and water closet areas water-resistant Gypsum backboard shall be used. 8. Smoke detectors shall receive their primary power from the building wiring. PROJECT TEAM BURTON PARK APARTMENTS - 2 STORY GENERAL NOTES ABBREVIATIONS N 1 VICINITY MAP 3. THE OWNER AND ARCHITECT ARE NOT RESPONSIBLE FOR ADDITIONAL COSTS INCURRED DUE TO DESIGN/BUILD CONTRACTOR'S ERROR AND OMISSIONS. CONSTRUCTION DRAWINGS C1.0 TYPE A UNIT TYPE A UNIT BUILDING B2 3 STORY BLDG. A1 7,380 SF BUILDING B6 3 STORY ASSUMED PROPERTY LINE BUILDING B1 3 STORY BUILDING A2 7,380 SF ASSUMED PROPERTY LINE BLDG. C 1 STORY VANCOUVER, WA 98684 TYPE A UNIT NE BURTON RD. & NE 79TH BUILDING B4 3 STORY Building A-1 TYPE A UNIT BUILDING B5 3 STORY BURTON PARK APARTMENTS BUILDING B3 3 STORY SHEET TITLE CODE ANALYSIS / SITE PLAN BUILDING A3 7,380 SF REUSE OF DOCUMENTS ASSUMED PROPERTY LINE TYPE A UNIT PROPOSED DETENTION POND TYPE A UNIT This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. BUILDING A4 7,380 SF BUILDING A5 7,380 SF DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting 3 6/22/2012 DRAWN BY CHECKED BY KK,ED DH UNIT 1-B ADAPTABLE UNIT 2B 5040HS 5040HS UNIT 2A 5040HS 5040HS 5040HS 3068 Deck 3068 3068 Deck 3068 Deck 3068 3068 3068 Deck Closet 6068SGD 6068SGD Living Rm 5040HS DN Master Bedroom 2668 3068 3068 ENTRY FOYER 2668 Linen 3068 3068 Coats 5040HS Master Bedroom 5040HS Closet UP 26 68 68 ELEC FIREPLACE BELOW SHELF Bedroom Master Bedroom DN 26 Living Rm Closet 3068 3068 Closet Coats Closet Bedroom 34" HT. SNACK BAR Living Rm 6068SGD ELECTRIC FIREPLACE BELOW SHELF Living Rm Bedroom 6068SGD Bedroom Living 6068SGD 6068SGD Closet 3068 3068 Deck 3068 3068 5040HS UNIT 1C ACCESSIBLE 5040HS Deck Deck Deck 5040HS 3068 UNIT 1D ACCESSIBLE 1 Closet 3068 3068 5040HS 5040HS UNIT 2C 5040HS UNIT 2-D 2 1 VANCOUVER, WA 98684 2668 3068 5068 5040HS ENTRY FOYER Coats Closet Master Bathroom NE BURTON RD. & NE 79TH LINEN 26 68 3068 3068 2668 3068 3068 Coats Kitchen 5068 Closet 2668 2668 ENTRY FOYER Bathroom 2 Building A-1 Linen D Laundry Kitchen D Bathroom 5068 2668 3068 Master Bathroom Kitchen W Master Bathroom 68 Bathroom W 2668 Laundry Kitchen W Laundry D Kitchen 26 D Bathroom 2 3068 W Laundry 2668 W Kitchen Laundry D 2668 D 34" HT. D LINEN W 3068 34" HT. W Laundry Bathroom Bathroom Master Bathroom 5068 Laundry D Kitchen Bathroom 5068 Laundry Closet 3068 3068 Kitchen 3068 5068 3068 5068 W 3068 Linen 3068 Linen Bathroom 34" HT. SNACK BAR 5068 3068 5068 BURTON PARK APARTMENTS LINEN 3068 2668 2668 3068 68 26 68 26 Closet 3068 2668 3068 2668 Coats 3068 2668 Coats Closet 3068 ENTRY FOYER ELECTRIC FIREPLACE BELOW SHELF Coats Closet 3068 6068SGD Closet 5068 LINEN 5040HS 26 68 5040HS Master Bedroom Closet Coats Living Rm Bedroom ELEC FIREPLACE BELOW SHELF Living 26 68 Bedroom Living Rm Bedroom Bedroom 6068SGD Closet 5040HS Deck 5040HS 5040HS UNIT 1A ADAPTABLE SHEET TITLE BUILDING PLANS/ OCCUPANCY AND EXITING ANALYSIS ENERGY NOTES REUSE OF DOCUMENTS This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. 1 DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting DRAWN BY CHECKED BY A0.1 KK,ED DH 76'-1" 1 25'-3" 11'-2" LEGEND: 3'-2" INDICATES WALLS THAT REQUIRE A DRAFTSTOP ABOVE FROM TOP OF WALL TO BOTTOM OF FLOOR OR ROOF DECK ABOVE. DRAFTSTOP CAN BE 1/2" GYP. BD. OR 3/8" STRUCTURAL PANEL OR 3/8" PARTICLE BOARD OR 1" NOMINAL WOOD 25'-6" 1 14'-1" 8'-0" 11'-2" 2x6 WOOD STUD @ 16" O.C. A2.0 A3.0 7'-0 1/2" 1 36'-8" 14'-2" 12'-10 7/8" 12'-7 1/8" 0'-3 1/2" 2 11'-2" 12'-5 1/4" 5/8" GYPSUM BOARD 17'-11" R-21 BATT INSULATION UNIT 1-B ADAPTABLE 5'-8 1/4" UNIT 1A ADAPTABLE DS 5040HS CEMENT BOARD SIDING DS 5040HS WALL TYPE '1' 16R @6 7/8" 15T@11" Deck 3'-2" UP DS 5040HS BUILDING WRAP 3068 3068 - 2x6 EXTERIOR - LOAD BEARING Deck 3068 3068 4'-0" 6'-0" DS 1/2" STRUCTURAL SHEATHING Closet 4'-0" WALL TYPE '1A' - SAME AS WALL TYPE '1' EXCEPT: - UL-U356 1 HR RATED W/ 5/8" TYPE 'X' GYP. BD. - STC50 6068SGD 6068SGD 1 1/4" 2x4 WOOD STUD @ 16" O.C. 68 Master Bathroom Kitchen 5'-9" D Bathroom 2 3'-6" 4'-8 3/8" 4'-0" Living Rm Bedroom 3068 26 68 - 2x4 INTERIOR - NON LOAD BEARING 2'-3 3/4" 2'-9" 3'-2 1/2" 3'-5 3/4" 1/2" GYPSUM BOARD Master Bedroom ELEC FIREPLACE BELOW SHELF 4'-9" 3068 4'-0" 5'-8 1/4" 8'-0" 7'-0 1/2" 11'-2" 6'-3 3/4" 14'-1" 5 1/2" 12'-10 7/8" 76'-1" 6'-0" 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting 3'-2" 2x6 WOOD STUD @ 16" O.C. 1/2" GYPSUM BOARD DRAWN BY CHECKED BY 11'-2" 11'-2" 36'-8" 14'-2" 1 DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV DS 17'-11" 25'-6" A2.0 1 12'-5 1/4" 12'-7 1/8" 1 7'-0 1/2" 25'-3" Deck UNIT 1D ADAPTABLE 0'-3 3/4" - 2x4 EXTERIOR - NON LOAD BEARING WALL TYPE '4A' - SAME AS WALL TYPE '4' EXCEPT: - WALL TO USE 2x6 WOOD STUDS @ 16" O.C. 5040HS UP UNIT 1C ACCESSIBLE 3'-2" 5040HS DS CEMENT BOARD SIDING WALL TYPE '4' 3068 16R @6 7/8" 15T@11" DS BUILDING WRAP Living Rm Bedroom Closet 5040HS R-11 BATT INSULATION (OPTIONAL) 1/2" STRUCTURAL SHEATHING 6068SGD DS 12'-7" WH 3'-6" 3068 This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. 2x4 WOOD STUD @ 16" O.C. WATER HEATER ACCESS PANEL 4'-0" Deck REUSE OF DOCUMENTS 3 1/2" 68 6068SGD 3068 WALL TYPE '3' 5'-2" Closet 2668 Coats GROUND FLOOR PLAN 5'-0 13/16" 5040HS 30 2'-3 3/4"1'-1 1/4" 3068 4'-2 3/4" 3068 2'-4 3/4" 1'-11 3/8" Fire Sprinkler Room Master Bathroom 3'-10 13/16" 3068 2'-1 1/2" ELEC FIREPLACE BELOW SHELF SHEET TITLE 6'-6" 6'-6" 6'-6 3/4" 34" HT. SNACK BAR Closet 3'-4" 16'-11" 12'-2 5/8" 5040HS WATER HEATER ACCESS PANEL 4'-9" 3068 3068 13'-7 5/16" 3'-5 3/4" 3068 2'-5" WH 5068 34" HT. SNACK BAR 6'-1 7/8" 2'-0 1/2" 12'-7" Linen 5068 4'-8 1/4" 3'-9" 2'-9 1/2" 1'-11 1/2" 2668 LINEN 3'-3 5/8" Closet 3'-7 3/8" DW Coats Bathroom 6'-5 9/16" ENTRY FOYER Kitchen 8'-10 1/2" Laundry Breezeway Kitchen 2'-2" 2668 D 34" HT. REF 2'-0" 2x4 WOOD STUD @ 16" O.C. 5'-9" W 2668 D 3 1/2" 1/2" GYPSUM BOARD 34" HT. 4'-0" Bathroom 7'-0 21/32" 7'-5 3/4" 11'-3 3/8" 3068 5'-0" 6068 DW W Laundry A2.0 1'-6" GFCI 4'-3 13/16" 3 59'-0" W VANCOUVER, WA 98684 5'-2" Closet 3068 12'-7" Laundry DW A3.0 - UL305 1 HR RATED WALL - GA FILE NO. WP 3370 - TO ACHIEVE STC50 AN EXTRA LAYER OF 5/8" GYP. BD. WAS ADDED TO EACH SIDE OF THE WALL (SOUND TEST USG-710120) - ALL JOINTS STAGGERED AND TAPED. PROVIDE ACCOUSTICAL SEALANT AROUND PERIMETER. - OPTIONAL 2x4 STUDS @ 24" O.C. W/ QUIETROCK 525 ONE SIDE AND 5/8" TYPE 'X' ON OTHER SIDE. FOLLOW MANUFACTURERS INSTALLATION REQUIREMENTS. NE BURTON RD. & NE 79TH - 2x4 INTERIOR - LOAD BEARING Building A-1 3068 34" HT. SNACK BAR DW 6068 WALL TYPE '2' Linen Kitchen Laundry D 3'-6" BURTON PARK APARTMENTS 2668 3068 ENTRY FOYER REF W 4 A2.0 3 1/2" 3068 34" HT. SNACK BAR 3'-9" 2668 3068 5068 Bathroom 3 1/2" 8 2668 Coats 6 26 LINEN Coats WATER HEATER ACCESS PANEL 3068 Closet Closet 2668 WH R-11 BATT INSULATION (SOUND) 1" AIR SPACE 1'-11 1/2" 2'-9 1/2" 5068 12'-7" 30 5040HS Master Bedroom WH WATER HEATER ACCESS PANEL 5/8" TYPE 'X' GYPSUM BOARD (2) LAYERS EACH SIDE 6'-6" ELEC FIREPLACE BELOW SHELF ELEC FIREPLACE BELOW SHELF 1 1/4" 8" Living Rm 5040HS Bedroom 16'-11" Living Rm 1 1/2" DIAMETER HANDRAIL @ +34" AFF AT EACH SIDE OF STAIR, TYP. Bedroom WALL TYPE '5' - 2x6 INTERIOR - LOAD BEARING A1.0 KK,ED DH 76'-1" 25'-3" A3.0 7'-0 1/2" 12'-7 1/8" 2 6'-3 3/4" 12'-5 1/4" 17'-11" UNIT 2B 5040HS BUILDING WRAP CEMENT BOARD SIDING 3'-2" 2'-0 3/4" Deck 2x6 WOOD STUD @ 16" O.C. 1/2" STRUCTURAL SHEATHING 1 1/2" DIAMETER HANDRAIL @ +34" AFF AT EACH SIDE OF STAIR, TYP. 5040HS 5 1/2" 11'-2" 5040HS 3068 Deck 3068 WALL TYPE '6' 3068 6068SGD Bedroom 3/4" LIGHTWEIGHT CONCRETE 3/4" T&G PLYWOOD 11 7/8" TGI WOOD JOIST @ 16" O.C. 6'-6" ELEC FIREPLACE BELOW SHELF Master Bedroom 34" HT. SNACK BAR 3068 FLOOR ASSEMBLY Coats - WIJ-1.2 ONE HOUR CEILING ASSEMBLY - ASTM E 119/NFPA251 REPORT NO. WH1-694-0159 - STC60 IIC50 W/ CUSHIONED VINYL - STC60 IIC65 W/ CARPET & PAD 3068 5'-2" 2668 ENTRY FOYER 34" HT. SNACK BAR 3'-9" 2668 3068 68 2668 3068 5/8" TYPE 'X' GYP. BD. 26 LINEN Coats WATER HEATER ACCESS PANEL 3068 Closet Closet RESILIANT CHANNELS 2668 1'-11 1/2" 2'-9 1/2" WH 12'-7" 5040HS 5040HS DN WH 5068 1 1/2" MINERAL WOOL INSULATION BATTS 68 ELEC FIREPLACE BELOW SHELF - 2x6 EXTERIOR Living Rm 30 Bedroom Closet 4'-0" 6068SGD 16'-11" Living Rm 4'-0" 6'-0" 16R @6 7/8" 15T@11" 3068 Closet 5068 12'-7" Kitchen 6068 Laundry Laundry D 3'-6" D W W D Bathroom Master Bathroom Kitchen 5'-9" 4 A2.0 3068 W REF Bathroom Linen 3 A2.0 DW 59'-0" GFCI 2 Bedroom Living Rm 6'-0" 6068SGD Deck 26 68 REUSE OF DOCUMENTS 2'-3 3/4" WATER HEATER ACCESS PANEL Master Bedroom 4'-9" 12'-7" WH ELEC FIREPLACE BELOW SHELF 3'-5 3/4" This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. 2'-9" 5040HS Coats 5'-2" Closet 2668 4'-2 3/4" 2'-4 3/4" 1'-11 3/8" 5'-0 13/16" 3068 3068 30 68 3'-2 1/2" 3068 Living Rm Bedroom 3'-6" 6068SGD 4'-0" 1 1/2" DIAMETER HANDRAIL @ +34" AFF AT EACH SIDE OF STAIR, TYP. 3068 2'-0 3/4" 2668 2'-1 1/2" 4'-0" ELEC FIREPLACE BELOW SHELF 4'-0" Fire Sprinkler Room 3'-10 13/16" 6'-6" 4'-8 3/8" 34" HT. SNACK BAR Closet 3'-4" 16'-11" 6'-6" 6'-6 3/4" 3068 3068 16R @6 7/8" 15T@11" 12'-2 5/8" 5040HS WATER HEATER ACCESS PANEL 4'-9" 3'-5 3/4" WH 5068 4'-8 1/4" 3'-9" Closet 2'-9 1/2" 1'-11 1/2" 2668 LINEN Coats 34" HT. SNACK BAR ENTRY FOYER 13'-7 5/16" SHEET TITLE SECOND FLOOR PLAN Master Bathroom 2'-3 3/4"1'-1 1/4" Linen 6'-1 7/8" 8'-10 1/2" 3'-7 3/8" 2'-0 1/2" 6'-5 9/16" 5068 2668 Kitchen Bathroom 12'-7" 7'-0 21/32" 6068 11'-3 3/8" REF D Laundry Breezeway Kitchen 5'-9" DW W Laundry Bathroom 1'-6" GFCI 3'-6" 3068 A3.0 1 4'-0" Closet 3068 DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting 3068 3068 VANCOUVER, WA 98684 UNIT 2A 12'-10 7/8" NE BURTON RD. & NE 79TH 7'-0 1/2" 11'-2" A2.0 Building A-1 8'-0" 25'-6" 1 14'-1" 1 BURTON PARK APARTMENTS 11'-2" 3'-2" 36'-8" 14'-2" Deck 5040HS UNIT 2C 3'-2" 5040HS 5040HS 6'-3 3/4" 3'-2" 8'-0" 7'-0 1/2" 11'-2" 14'-1" LEGEND: INDICATES WALLS THAT REQUIRE A DRAFTSTOP ABOVE FROM TOP OF WALL TO BOTTOM OF FLOOR OR ROOF DECK ABOVE. DRAFTSTOP CAN BE 1/2" GYP. BD. OR 3/8" STRUCTURAL PANEL OR 3/8" PARTICLE BOARD OR 1" NOMINAL WOOD 17'-11" 12'-10 7/8" 11'-2" 11'-2" DRAWN BY CHECKED BY 36'-8" 14'-2" 76'-1" 1 12'-5 1/4" 25'-6" A2.0 25'-3" UNIT 2D 12'-7 1/8" 1 7'-0 1/2" 1 NOTE: REFER TO SHEET A1.0 FOR BALANCE OF SIMILAR INFORMATION A1.1 KK,ED DH 7 6 A1.3 8 5 6:12 SLOPE RIDGE 6:12 SLOPE SHEET METAL GUTTER (TYPICAL) 6:12 SLOPE DOWNSPOUT (TYPICAL) 6:12 SLOPE EY BURTON PARK APARTMENTS 4:12 SLOPE 4817 SQ. FT. / 300 = 16 SQ. FT. 8 SQ. FT. @ EAVE REQUIRED 8 SQ. FT. @ RIDGE REQUIRED ROOF VENT (TYPICAL) RIDGE REQUIRED VENTING: - USE ROOF VENTS @ RIDGE. 1 SQ. FT. EACH EQUALLY SPACED 4:12 SLOPE - PROVIDE 1" DIAMETER HOLE W/ BIRD SCREEN IN BLOCKING @ EACH TRUSS BAY. VANCOUVER, WA 98684 VA EY VA LL LL LL EY EY LL VA VA ROOF VENT CALCULATIONS: - 1/300TH OF AREA REQUIRED - 1/600TH AT EAVE - 1/600TH AT RIDGE NE BURTON RD. & NE 79TH Y LE ROOF NOTES: - ENGINEERED ROOF TRUSSES @ 24" O.C. - 15/32" EXPOSURE 1-APA RATED PLYWOOD OR OSB SHEATHING - 30# BUILDING PAPER - COMPOSITION SHINGLES - 8" CEMENT BOARD FASCIA - GUTTERS & DOWNSPOUTS Building A-1 EY L VA RIDGE 6:12 SLOPE VA LL 6:12 SLOPE RIDGE DOWNSPOUT (TYPICAL) SHEET TITLE ROOF PLAN LE Y Y LE VA L This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. Y VA E LL LL VA EY RIDGE RIDGE EY VA L EY 6:12 SLOPE RIDGE 6:12 SLOPE DOWNSPOUT (TYPICAL) LL LL 6:12 SLOPE VA VA 6:12 SLOPE REUSE OF DOCUMENTS 6:12 SLOPE DOWNSPOUT (TYPICAL) 6:12 SLOPE SHEET METAL GUTTER (TYPICAL) 1 1 DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting 6/22/2012 DRAWN BY CHECKED BY A1.2 KK,ED DH 3 1st Floor 0' - 0" 1st Floor 0' - 0" Elevation 2 - a (Accessible) 1/4" = 1'-0" 7 2 Elevation 1 - a (Accessible) 1/4" = 1'-0" 1st Floor 0' - 0" Elevation 2 - b (Accessible) 1/4" = 1'-0" 8 Elevation 2 - c (Accessible) 1/4" = 1'-0" 1st Floor 0' - 0" 9 Elevation 2 - e (Accessible) 1/4" = 1'-0" Kitchen 4 Laundry D 3'-6" 6068 A2.0 DW 2 A3.0 SHEET TITLE UNIT PLAN ACCESSIBLE GFCI 4'-3 13/16" 3'-6" Bathroom W Laundry D 7'-0 21/32" 7'-5 3/4" 34" HT. Breezeway Kitchen REF 2'-0" 12'-7" 11'-3 3/8" 3068 5'-0" 6068 DW REUSE OF DOCUMENTS 12'-2 5/8" 5040HS WATER HEATER ACCESS PANEL 6'-6" 6'-6 3/4" 4'-8 3/8" 4'-0" 4'-8 1/4" 3'-9" 2668 WH 5068 This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. 34" HT. SNACK BAR 3068 3'-4" ELEC FIREPLACE BELOW SHELF F 16'-11" Closet 3068 2'-5" Coats 2'-9 1/2" 1'-11 1/2" 2668 LINEN 3'-3 5/8" 2'-2" Living Rm Bedroom DS UNIT 1C 1 16R @6 7/8" 15T@11" 3068 Deck 1B1B - UNIT PLAN - ACCESSIBLE 1/4" = 1'-0" 1 DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting 6068SGD 6'-0" 6 Elevation 1 - b (Accessible) 1/4" = 1'-0" VANCOUVER, WA 98684 Elevation 1 - c (Accessible) 1/4" = 1'-0" NE BURTON RD. & NE 79TH 4 1st Floor 0' - 0" Building A-1 Elevation 1 - d (Accessible) 1/4" = 1'-0" 3068 5040HS DS UP 5'-8 1/4" 5 1st Floor 0' - 0" 1st Floor 0' - 0" BURTON PARK APARTMENTS 1st Floor 0' - 0" 6/22/2012 DRAWN BY CHECKED BY A1.3 KK,ED DH 3 1st Floor 0' - 0" 1st Floor 0' - 0" Elevation 2 - a (Accessible) 1/4" = 1'-0" 7 5040HS 2 Elevation 1 - a (Accessible) 1/4" = 1'-0" 1st Floor 0' - 0" Elevation 2 - b (Accessible) 1/4" = 1'-0" 8 Elevation 2 - c (Accessible) 1/4" = 1'-0" 1st Floor 0' - 0" 9 Elevation 2 - d (Accessible) 1/4" = 1'-0" SHEET TITLE UNIT PLAN ADAPTABLE 5040HS Deck 3068 3068 Closet REUSE OF DOCUMENTS 6068SGD Living Rm Bedroom 15R @7 5/16" 14T@11" 8 10 6 26 Master Bedroom WH UP Closet This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. 1st Floor 0' - 0" ELEC FIREPLACE BELOW SHELF Elevation 2 - e (Accessible) 1/4" = 1'-0" 2668 3068 Coats 3068 3068 ENTRY FOYER Bathroom 10 7 A1.6 A1.6 5 2 8 Laundry 3 Kitchen DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting 3068 Linen A1.6 D Closet 4 5068 1 68 26 3068 2668 6 Elevation 1 - b (Accessible) 1/4" = 1'-0" VANCOUVER, WA 98684 Elevation 1 - c (Accessible) 1/4" = 1'-0" 1st Floor 0' - 0" NE BURTON RD. & NE 79TH 4 1st Floor 0' - 0" Building A-1 Elevation 1 - d (Accessible) 1/4" = 1'-0" 5040HS 5 1st Floor 0' - 0" BURTON PARK APARTMENTS 1st Floor 0' - 0" Master Bathroom 9 W 6 6/22/2012 DRAWN BY CHECKED BY 1 2B2B - UNIT PLAN - ACCESSIBLE 1/4" = 1'-0" A1.4 KK,ED DH ASPHALT COMP SHINGLE ROOF ASPHALT COMP SHINGLE ROOF 1st Floor 0' - 0" 1st Floor 0' - 0" CULTURED STONE COLUMN BASE VINYL WIDOW. SLIDER. TYP. CULTURED STONE COLUMN BASE 1 HARDI PLANK LAP SIDING 2 HARDI SHAKE SIDING HARDI SHAKE SIDING VANCOUVER, WA 98684 2nd Floor 9' - 1 3/4" NE BURTON RD. & NE 79TH VINYL WINDOW. SLIDER. TYP. 2nd Floor 9' - 1 3/4" Building A-1 HARDI PLANK LAP SIDING HARDIPANEL SIDING W/ 1x BATTENS BURTON PARK APARTMENTS HARDIPANEL SIDING W/ 1x BATTENS SHEET TITLE EXTERIOR ELEVATIONS 2nd Floor 9' - 1 3/4" 2nd Floor 9' - 1 3/4" REUSE OF DOCUMENTS 1st Floor 0' - 0" Grade -0' - 8" Foundation -2' - 4" This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. 1st Floor 0' - 0" Grade -0' - 8" Foundation -2' - 4" 3 4 1 EXTERIOR KEYNOTES 1 - CEMENT BOARD SIDING 2 - CEMENT BOARD TRIM 3 - CEMENT BOARD BELLY BAND 4 - 8x8 WOOD POST CLAD WITH SIDING 5 - WOOD GUARDRAIL 6 - WOOD ACCENT 7 - CULTURED STONE 8 - VINYL WINDOW 9 - VINYL SLIDING GLASS DOOR 10 - METAL FINISH 6 PANEL DOOR 11 - METAL FINISH FULL LITE DOOR 12 - COMPOSITION ROOF SHINGLES 13 - CEMENT BOARD ROOF FASCIA 14 - METAL FINISH ROOF GUTTERS 15 - METAL FINISH PREFABRICATED STAIR 16 - METAL FINISH PREFABRICATED RAILING 17 - METAL FINISH ROOF HAT VENT 18 - METAL FINISH LOUVERED ATTIC VENT DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting DRAWN BY CHECKED BY A2.0 KK,ED DH 26'-6" Ridge MANUFACTURED ROOF TRUSSES @ 24" O.C. T.P. HARDI SOFFIT PANEL +42" GUARDRAIL. TYPICAL HARDI SOFFIT PANEL 3" CONC. OVER WP MEMBRANE. SEE STRUCT BREEZEWAY 2nd Floor 9' - 1 3/4" 1 NOTE: SEE FLOOR PLAN FOR DRAFT STOP LOCATION AND DETAILS DRAFT STOP OF 21" OSB OR GYP. BD. OVER TRUSS. LOCATE PER PLANS. VANCOUVER, WA 98684 BURTON PARK APARTMENTS 1st Floor 0' - 0" NE BURTON RD. & NE 79TH 3'-3" BREEZEWAY 4" CONCRETE\ SLAB ON GRADE. SEE STRUCTURAL Building A-1 8x8 WD. COLUMN W/ 1x PTD. WD. WRAP. TYPICAL SHEET TITLE BUILDING SECTIONS Ridge 26'-6" MANUFACTURED ROOF TRUSSES @ 24" O.C. INTERIOR BEARING WALL REUSE OF DOCUMENTS R-38 BATT INSULATION This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. R-21 BATT INSULATION 1'-0 5/8" 2nd Floor 18' 9' - 3 1 1/2" 3/4" 4" CONCRETE SLAB ON GRADE 8'-1 1/8" 17'-2 7/8" 8'-1 1/8" 29'-5 1/2" 2nd Floor T.P. 17'-2 7/8" R-10 RIGID SLAB INSULATION 1st Floor 0' - 0" 1 DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting EXTERIOR BEARING WALL 2 DRAWN BY CHECKED BY A3.0 KK,ED DH LAP SIDING ABOVE 26GA. PREFIN FLASHING AT HEAD, RUN UP 4' UNDER FELT TYPICAL 26 GA. PREFIN METAL "Z" FLASHING AT HEAD 5/4 x4 SPFD TRIM 5/8" G.B. FILL VOID AT HEAD WITH INSUL. 5/8" G.B. 5/4x4 SPFD TRIM SEALANT SEALANT R.O. 5/8" G.B. METAL EDGE METAL EDGE SEALANT 1 ROOF SHEATHING 23/32" EXPOSURE 1 APA RATED PLYWOOD OR OSB SEE STRUCTURAL FOR NAILING R-38 BATT INSULATION 1" AIR SPACE MINIMUM 1/2" MAX. METAL EDGE SEALANT 1'-4" 1/2" GYPSUM DRYWALL 5/8" GYPSUM DRYWALL 5/4x4 SPFD TRIM 5/8" G.B. CEM. BD. LAP SIDING OVER 15# FELT R-21 BATT INSULATION 2x6 STUDS @ 16" O.C. FLOOR SHEATHING 23/32" EXPOSURE 1 APA RATED PLYWOOD OR OSB SEE STRUCTURAL FOR NAILING. GLUE REQUIRED ON EVERY JOIST. 7/8" LIGHTWEIGHT CONCRETE 9 2'-0" ENGINEERED ROOF TRUSS @ 24" O.C. R.O. MFR'S THRESHL'D SET IN MASTIC A4.0 VENILATION PER CODE INSULATING GLAZING UNITS IN VINYL FRAME DOOR ASSEMBLY 8 DECK GUARDRAIL WITH ATTACHMENT PER MANUFACTURERS INSTALLATION INSTRUCTIONS MIN 1-1/2" MINERAL WOOL BATTS -2.5 PCF 1/2" O.S.B. EXTERIOR SHEATHING 4 SLOPE 1/4"/FT. OAK SILL 2 A4.1 MTL. EDGES 2nd Floor 9' - 1 3/4" 10 A4.0 VANCOUVER, WA 98684 8 2nd Floor T.P. 17' - 2 7/8" NE BURTON RD. & NE 79TH 3 Building A-1 AL. PATIO DOOR ASSEMBLY BURTON PARK APARTMENTS METAL EDGE SHEET TITLE WALL SECTIONS (1) 11 7/8" RIM RIPPED 2x10 JOISTS @ 16" O.C. 11 7/8" TJI 210 @ 16" O.C. (2) 2x6 TOP PLATE CONTINUOUS BEAD OF SEALANT 8 5/8" GYPSUM DRYWALL OVER RESILIENT CHANNELS COMP LAP SIDING 5/4x3 1/2" SPFD TRIM BD. 5/4 x 12 PAINTED WD. TRIM RIPPED 2x10 SEE STRUCT A4.0 REUSE OF DOCUMENTS 1/2" GYPSUM DRYWALL This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. MEMBRANE SYSTEM FINISH VENTILATION AS REQUIRED CAULK R-21 BATT INSULATION 2x6 STUDS @ 16" O.C. 5 1/2" PLYWOOD OR OSB SHEATHING BUILDING WRAP HARDI SOFFIT PANEL CEMENT BOARD SIDING PATIO GUARDRAIL WITH ATTACHMENT PER MANUFACTURERS INSTALLATION INSTRUCTIONS 1X PAINTED WD. TRIM 10 1 BEVELED SLAB EDGE 2x6 P.T. MUD SILL 4" CONCRETE SLAB 6" CRUSHED GRAVEL-COMPACTED R-5 RIGID FOAM INSULATION DEX-O-TEX WATERPROOF MEMBRANE 4" DEX-O-TEX SLIP SHEET 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting 4" CONCRETE SLAB ON GRADE Grade -0' - 8" GRAVEL FILL PERFORATED DRAIN TILE Foundation -2' - 4" CONCRETE FOOTING & WALL UNEXCAVATED SOIL SHEET METAL THRESHOLD FLASHING 3 1/2" 11 1st Floor 0' - 0" 6 MIL VISQUEEN VAPOR BARRIER 3 1/2" DEX-O-TEX TRAFFIC TOPPING DOOR OR SLIDER A4.0 8" 6 DOOR OR SLIDER THRESHOLD 9 DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 2 DRAWN BY CHECKED BY 1 7 NOT FOR CONSTRUCTION A4.0 KK,ED DH VANCOUVER, WA 98684 NE BURTON RD. & NE 79TH Building A-1 BURTON PARK APARTMENTS SHEET TITLE WINDOW FLASHING DETAILS 1 REUSE OF DOCUMENTS This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. WEATHER RESISTANT BARRIER EXTERIOR SIDING PER PLAN WALL ASSEMBLY AS NOTED PRE-FINISHED METAL FLASHING GYP. BD. 2X BELLY BAND 1 DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting PROVIDE SEALANT AT TOP OF SIDING WEATHER RESISTANT BARRIER 1/2" SHEATHING 6/22/2012 DRAWN BY CHECKED BY 1 2 1 A4.1 KK,ED DH 3/4" T&G PLYWOOD 3/4" TOPPING SLAB TJI PER STRUCTURAL KITCHEN VENT THROUGH WALL BATHROOM VENT THROUGH CEILING BATHROOM VENT THROUGH WALL BATHROOM VENT THROUGH WALL DRYER VENT THROUGH WALL HORIZONTAL COOK HOOD/FAN VENT THROUGH CEILING JOISTS DRYER VENT THROUGH WALL RESILIANT CHANNELS PER MANUF. 1 LAYER OF 5/8" TYPE 'X' GYP. BD. 2X NAILER FAN OR DRYER VENT 2X NAILER 1/2" GYP. BD. WALL ASSEMBLY PER DRAWINGS 3/4" TOPPING SLAB TJI PER STRUCTURAL 2 LAYERS OF GYP. BD. (TYP.) RESILIANT CHANNELS PER MANUF. 1 LAYER OF 5/8" TYPE 'X' GYP. BD. 2X BLOCKING @ EA END OF BLOCKOUT FOR FAN UNIT 1 26 GA. (MIN) VENT THROUGH THE JOIST BAY. FIRE CAULKED AROUND ANY PENATRATION 26 GA. (MIN) FAN UNIT ENCLOSURE. FIRE CAULK AROUND ENTIRE OPENING Unit Venting Plan 1/4" = 1'-0" 3 Fan Equipment and Vent In Joist Space 1/8" = 1'-0" VANCOUVER, WA 98684 3/4" T&G PLYWOOD NE BURTON RD. & NE 79TH 1 Hour Soffit Chase 1/8" = 1'-0" BURTON PARK APARTMENTS 2 Building A-1 UP SHEET TITLE DUCTING AND VENTILATION PLAN 2 2 GENERAL NOTES: 1. 2. 3. 1 EXTERIOR WALL SHEATHING AND SIDING ALL PENATRATIONS IN THE FIRE WALLS TO BE FIRE CAULKED. ALL VENT PIPING TO BE MIN. 26. GA. ALL VENTING TO BE RUN IN JOIST CAVITIES. WHENEVER PIPING PENATRATES A RATED ASSEMBLY IT MUST BE FIRE CAULKED. ALL FAN EQUIPMENT PLACED IN THE RATED CEILING ASSEMBLY TO HAVE A 26 GA. HOUSING AND FIRE CAULKED AROUND THE PENATRATION. FAN UNIT INSTALLED INTO THE JOIST CAVITITIES TO MEET DETAIL 3 ON THIS PAGE. REUSE OF DOCUMENTS This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. 5/8" GYP. BD. ON ALL SIDES WHOLE HOUSE FAN: INTAKE AIR: HEAT SOURCE: PANASONIC WHISPERGREEN FV-08VQC5 80 CFM, CONSTANT VOLUME, MOTION SENSOR, HUMIDISTAT CONTROLLED. FAN TO BE ON A TIMER TO OPERATE UNIT AUTOMATICALLY AND ALSO HAVE A MANUAL SWITCH TO CONTROL USE IN BATHROOM. 2X BLOCKING PROVIDE WINDOW SLOTS IN EACH ROOM. IN WINDOWLESS ROOMS PROVIDE PASSING WALL VENTS WITH DAMPERS. 2X STUDS PROVIDE MARKEL IN-WALL HEATERS (TYP.) 1 BATHROOM EXHAUST FAN: KITCHEN EXHAUST FAN: LAUNDRY ROOM EXHAUST FAN: 5/8" GYP. BD. ON ALL SIDES 70 CFM REQUIRED 175 CFM REQUIRED 20 CFM REQUIRED 2 MARKEL IN WALL HEATER (TYP.) DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting 2X BLOCKING NOTE: 1. 2. DESIGN IS TO SHOW CODE COMPLIANCE AND ESTIMATING PROVISIONS. FINAL DESIGN BY G.C. AND OWNER. ALL EXHAUST VENTS MIN. OF 3 FEET FROM OPERABLE WINDOWS. 6/22/2012 DRAWN BY CHECKED BY RATED WALLS GENERAL NOTE: ALL OPENINGS IN RATED ASSEMBLES SHALL BE PROTECTED WITH APPROVED FIRE DAMPERS, OR AS PER DETAIL. PENETRATIONS IN RATED ASSEMBLIES SHALL BE FIRE CAULKED WITH 'HILTI' FS-ONE FIRESTOP SEALANT OR EQUAL. INSTALL CAULKING PER MANUFACTURERS SPECIFICATIONS. 4 Utility Penetrations @ 1 Hr Assemblies 1/8" = 1'-0" 1 A5.0 KK,ED DH RADON MITIGATION NOTES AGGREGATE A LAYER OF AGGREGATE OF 4-INCH MINIMUM THICKNESS SHALL BE PLACED BENEATH CONCRETE SLABS. THE AGGREGATE SHALL BE CONTINUOUS TO THE EXTENT PRACTICAL. GRADUATION AGGREGATE SHALL: 1. COMPLY WITH ASTM STANDARD C-33 STANDARD SPECIFICATION FOR CONCRETE AGGREGATE AND SHALL BE SIZE NO. 8 OR LARGER SIZE AGGREGATE AS LISTED IN TABLE 2, GRADING REQUIREMENTS FOR COURSE AGGREGATE; OR 2. MEET THE 1988 WASHINGTON STATE DEPARTMENT OF TRANSPORTATION SPECIFICATION 9-03.1 (3) "COURSE AGGREGATE FOR PORTLAND CEMENT CONCRETE," OR ANY EQUIVALENT SUCCESSOR STANDARDS. AGGREGATE SIZE SHALL BE OF GRADE 8 OR LARGER AS LISTED IN SECTION 9-03.1 (3) C, "GRADING"; OR 3. BE SCREENED, WASHED PEA GRAVEL FREE OF DELETERIOUS SUBSTANCES IN A MANNER CONSISTENT WITH ASTM STANDARD C-33 WITH 100 PERCENT PASSING A 1/2-INCH SIEVE AND LESS THAN 5 PERCENT PASSING A NO. 16 SIEVE. SIEVE CHARACTERISTICS SHALL CONFORM TO THOSE ACCEPTABLE UNDER ASTM STANDARD C-33. EXCEPTION: AGGREGATE SHALL NOT BE REQUIRED IF A SUBSTITUTE MATERIAL OR SYSTEM, WITH SUFFICIENT LOAD BEARING CHARACTERISTICS, AND HAVING APPROVED CAPABILITY TO PROVIDE EQUAL OR SUPERIOR AIR FLOW, IS INSTALLED. SOIL-GAS RETARDER MEMBRANE A SOIL-GAS RETARDER MEMBRANE, CONSISTING OF AT LEAST ONE LAYER OF VIRGIN POLYETHYLENE WITH A THICKNESS OF AT LEAST 6 MIL, OR EQUIVALENT FLEXIBLE SHEET MATERIAL, SHALL BE EITHER PLACED DIRECTLY UNDER ALL CONCRETE SLABS SO THAT THE SLAB IS IN DIRECT CONTACT WITH THE MEMBRANE, OR ON TOP OF THE AGGREGATE WITH 2 INCHES MINIMUM OF FINE SAND OR PEA GRAVEL INSTALLED BETWEEN THE CONCRETE SLAB AND MEMBRANE. THE FLEXIBLE SHEET SHALL EXTEND TO THE FOUNDATION WALL OR TO THE OUTSIDE EDGE OF THE MONOLITHIC SLAB. SEAMS SHALL OVERLAP AT LEAST 12 INCHES. THE MEMBRANE SHALL ALSO BE FITTED TIGHTLY TO ALL PIPES, WIRES, AND OTHER PENETRATIONS OF THE MEMBRANE AND SEALED WITH AN APPROVED SEALANT OR TAPE. ALL PUNCTURES OR TEARS SHALL BE REPAIRED WITH THE SAME OR APPROVED MATERIAL AND SIMILARLY LAPPED AND SEALED. ONE CONTINUOUS SEALED PIPE SHALL RUN FROM A POINT WITHIN THE AGGREGATE UNDER EACH CONCRETE SLAB TO A POINT OUTSIDE THE BUILDING. JOINTS AND CONNECTIONS SHALL BE PERMANENTLY GAS TIGHT. THE CONTINUOUS SEALED PIPE SHALL INTERFACE WITH THE AGGREGATE IN THE FOLLOWING MANNER, OR BY OTHER APPROVED EQUAL METHOD. THE PIPE SHALL BE PERMANENTLY CONNECTED TO A "T" WITHIN THE AGGREGATE AREA SO THAT THE TWO END OPENINGS OF THE "T" LIE WITHIN THE AGGREGATE AREA. A MINIMUM OF 5 FEET OF PERFORATED DRAIN PIPE OF 3 INCHES MINIMUM DIAMETER SHALL JOIN TO AND EXTEND FROM THE "T". THE PERFORATED PIPE SHALL REMAIN IN THE AGGREGATE AREA AND SHALL NOT BE CAPPED AT THE ENDS. THE "T" AND ITS PERFORATED PIPE EXTENSIONS SHALL BE LOCATED AT LEAST 5 FEET HORIZONTALLY FROM THE EXTERIOR PERIMETER OF THE AGGREGATE AREA. THE CONTINUOUS SEALED PIPE SHALL TERMINATE NO LESS THAN 12 INCHES ABOVE THE EAVE, AND MORE THAN 10 HORIZONTAL FEET FROM A WOODSTOVE OR FIREPLACE CHIMNEY, OR OPERABLE WINDOW. THE CONTINUOUS SEALED PIPE SHALL BE LABELED "RADON VENT." THE LABEL SHALL BE PLACED SO AS TO REMAIN VISIBLE TO AN OCCUPANT. THE MINIMUM PIPE DIAMETER SHALL BE 3 INCHES UNLESS OTHERWISE APPROVED. ACCEPTABLE SEALED PLASTIC PIPE SHALL BE SMOOTH WALLED, AND MAY INCLUDE EITHER PVC SCHEDULE 40 OR ABS SCHEDULE OF EQUIVALENT WALL THICKNESS. THE ENTIRE SEALED PIPE SYSTEM SHALL BE SLOPED TO DRAIN TO THE SUBSLAB AGGREGATE. THE SEALED PIPE SYSTEM MAY PASS THROUGH AN UNCONDITIONED ATTIC BEFORE EXITING THE BUILDING; BUT TO THE EXTENT PRACTICABLE, THE SEALED PIPE SHALL BE LOCATED INSIDE THE THERMAL ENVELOPE OF THE BUILDING IN ORDER TO ENHANCE PASSIVE STACK VENTING. EXCEPTION: A FAN FOR SUBSLAB DEPRESSURIZATION SYSTEM INCLUDES THE FOLLOWING: 1. SOIL-GAS RETARDER MEMBRANE AS SPECIFIED IN SECTION 1203.6.3.2.4 2. SEALING OF PENETRATIONS AND JOINTS AS SPECIFIED IN SECTION 1203.6.3.2.5 3. A 3-INCH CONTINUOUS SEALED RADON PIPE SHALL RUN FROM A POINT WITHIN THE AGGREGATE UNDER EACH CONCRETE SLAB TO A POINT OUTSIDE THE BUILDING 4. JOINTS AND CONNECTIONS SHALL BE GAS TIGHT, AND MAY BE OF EITHER PVC SCHEDULE 40 OR ABS SCHEDULE OF EQUIVALENT IN WALL THICKNESS 5. A LABEL OF "RADON VENT" SHALL BE PLACED ON THE PIPE SO AS TO REMAIN VISIBLE TO AN OCCUPANT 6. FAN CIRCUIT AND WIRING AS SPECIFIED IN SECTION 1203.6.3.2.7 AND A FAN 3" MINIMUM SEALED RADON VENT PIPE (TYP.) TO BE VENTED THROUGH THE ROOF (TYP.) 3" MINIMUM SEALED RADON VENT PIPE (TYP.) TO BE VENTED THROUGH THE ROOF (TYP.) SHEET TITLE RADON MITIGATION PLAN IF THE SUBSLAB DEPRESSURIZATION SYSTEM IS EXHAUSTED THROUGH THE CONCRETE FOUNDATION WALL OR RIM JOIST, THE EXHAUST TERMINUS SHALL BE A MINIMUM OF 6 FEET FROM OPERABLE WINDOWS OR OUTDOOR AIR INTAKE VENTS AND SHALL BE DIRECTED AWAY FROM OPERABLE WINDOWS AND OUTDOOR AIR INTAKE VENTS TO PREVENT RADON REENTRAINMENT. FAN CIRCUIT AND WIRING AND LOCATION AN AREA FOR LOCATION OF AN IN-LINE FAN SHALL BE PROVIDED. THE LOCATION SHALL BE AS CLOSE AS PRACTICABLE TO THE RADON VENT PIPE'S POINT OF EXIT FROM THE BUILDING, OR SHALL BE OUTSIDE THE BUILDING SHELL; AND SHALL BE LOCATED SO THAT THE FAN AND ALL DOWNSTREAM PIPING IS ISOLATED FROM THE INDOOR AIR. PROVISIONS SHALL BE MADE TO ALLOW FUTURE ACTIVATION OF AN INLINE FAN ON THE RADON VENT PIPE WITHOUT THE NEED TO PLACE NEW WIRING. A 110 VOLT POWER SUPPLY SHALL BE PROVIDED AT A JUNCTION BOX NEAR THE FAN LOCATION. REUSE OF DOCUMENTS This document, and the ideas and designs incorporated, as an instrument of professional service is the property of Western Design Group, Inc. and is not to be used, in whole or in part, for any reason without the written authorization of Western Design Group, Inc. SEPARATE AGGREGATE AREAS IF THE 4-INCH AGGREGATE AREA UNDERNEATH THE CONCRETE SLAB IS NOT CONTINUOUS, BUT IS SEPARATED INTO DISTINCT ISOLATED AGGREGATE AREAS BY A FOOTING OR OTHER BARRIER, A MINIMUM OF ONE RADON VENT PIPE SHALL BE INSTALLED INTO EACH SEPARATE AGGREGATE AREA. UP VANCOUVER, WA 98684 RADON VENT NE BURTON RD. & NE 79TH UP BURTON PARK APARTMENTS ALL PENETRATIONS AND JOINTS IN CONCRETE SLABS OR OTHER FLOOR SYSTEMS AND WALLS BELOW GRADE SHALL BE SEALED BY AN APPROVED SEALANT TO CREATE AN AIR BARRIER TO LIMIT THE MOVEMENT OF SOIL-GAS INTO THE INDOOR AIR. SEALANTS SHALL BE APPROVED BY THE MANUFACTURER FOR THE INTENDED PURPOSE. SEALANT JOINTS SHALL CONFORM TO MANUFACTURER'S SPECIFICATIONS. THE SEALANT SHALL BE PLACED AND TOOLED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. THERE SHALL BE NO GAPS OR VOIDS AFTER THE SEALANT HAS CURED. Building A-1 SEALING OF PENETRATIONS AND JOINTS EXCEPTION: SEPARATE AGGREGATE AREAS MAY BE CONSIDERED A SINGLE AREA IF A MINIMUM 3-INCH DIAMETER CONNECTION JOINING THE SEPARATE AREAS IS PROVIDED FOR EVERY 30 FEET OF BARRIER SEPARATING THOSE AREAS. RADON PIPING NOTES: 1. 2. 3. 4. 5. 6. 7. 8. 1 ALL RADON PIPING TO BE SEALED TO PREVENT ANY LEAKS. ALL RADON PIPING MUST BE CLEARLY LABELED IN ALL WALL CAVITIES AND IN THE ATTIC SPACE. ALL PIPING ENCASED IN CONCRETE TO BE WRAPPED TO PREVENT DAMAGE, TYP. SLAB VENT PIPES ARE TO EXTEND A MINIMUM OF 5'-0" BEYOND ANY CONCRETE THAT ENCLOSES IT. RADON PIPING IS TO BE RUN UP THROUGH THE THICKENED SLAB INTO THE CENTER OF THE FIRE SEPARATION WALL AND CONTINUE ON INTO THE ATTIC. ANY PENATRATIONS IN THE FIRE WALL OR DRAFT-STOPPING ARE TO BE FIRE CAULKED AND SEALED PER CURRENT CODE. ANY VENTING THROUGH THE ROOF HAS TO BE A MINIMUM OF 4'-0" AWAY FROM THE EDGE OF ANY FIRE WALL OR ATTIC DRAFTSTOP. ANY RADON VENTS THROUGH THE ROOF MUST BE A MINIMUM OF 10'-0" FROM ANY OPENING OR AIR INTAKE. 3 DATE ISSUE 01.20.12 PRELIM 02.02.12 PRELIM 2 04.27.12 PROGRESS 05.14.12 PRICING 06.22.12 PC SUBMIT 08.21.12 CTY COMM 10.31.12 SITE REV 12.26.12 DS LOCATE 01.22.13 Construction 01.23.13 venting 3 6/22/2012 DRAWN BY CHECKED BY 1 Radon Mitigation 1/4" = 1'-0" 1 A5.1 KK,ED DH