ADMS 3.5.1 Energy Losses Functional Specification ADMS 3.5.1 Energy Losses Table of Contents 1. REVISION HISTORY .................................................................................................. 1 2. DEFINITIONS AND ABBREVIATIONS ...................................................................... 2 3. REFERENCES ........................................................................................................... 3 4. INTRODUCTION ........................................................................................................ 4 5. OVERVIEW ................................................................................................................ 5 5.1. Architecture ...................................................................................................... 5 5.2. Input................................................................................................................... 5 5.2.1. Options .................................................................................................. 6 5.2.1.1. EL Options .............................................................................. 6 5.2.1.2. OL Options .............................................................................. 6 5.3. Output................................................................................................................ 7 5.4. Triggers ............................................................................................................. 7 6. FUNCTIONALITY ....................................................................................................... 8 6.1. Energy Losses .................................................................................................. 8 6.2. Operational Losses ........................................................................................ 10 7. METHODOLOGY ..................................................................................................... 14 7.1. Energy Losses ................................................................................................ 14 7.2. Operational Losses ........................................................................................ 15 8. ERROR MESSAGES................................................................................................ 18 I Proprietary and Confidential ADMS 3.5.1 Energy Losses Table of Figures Figure 6.1 – Energy Losses in Function Execution Manager ............................................ 8 Figure 6.2 – Energy Losses Options dialog ...................................................................... 9 Figure 6.3 – EL Report window – Overview tab .............................................................. 10 Figure 6.4 – EL Report window – Individual tab .............................................................. 10 Figure 6.5 – Operational Losses in Function Execution Manager ................................... 11 Figure 6.6 – Operational Losses Options dialog ............................................................. 11 Figure 6.7 – OL Report window – Overview tab .............................................................. 12 Figure 6.8 – OL Report window – Individual tab.............................................................. 13 Figure 7.1 – PI results used for OL calculation................................................................ 16 Figure 7.2 – Storing PI results - Simplified diagram ........................................................ 16 II Proprietary and Confidential ADMS 3.5.1 Energy Losses 1. REVISION HISTORY Version Authors Date Comments 1.0 Dejan Vuletić 15-Nov-2014 Initial version 1.1 Dejan Vuletić 15-Nov-2014 Modified structure of Updated document. 1.2 Branislav Brbaklic 21-Nov-2014 Document Update 1.3 Dejan Vuletić 09-Feb-2015 Document Update 1.4 Ken Zanewich 18-Mar-2015 NA Review and edits 1 chapters. Proprietary and Confidential ADMS 3.5.1 Energy Losses 2. DEFINITIONS AND ABBREVIATIONS Definition/Abbreviation Description ADMS Advanced Distribution Management System EL ADMS Energy Losses Application OL ADMS Operational Losses Application FEM Function Execution Manager LF Load Flow MV Medium Voltage PI Performance Indices 2 Proprietary and Confidential ADMS 3.5.1 Energy Losses 3. REFERENCES # Title Description 1. FS Power Applications Infrastructure Provides functional specification of ADMS Power Applications global aspects. 3 Proprietary and Confidential ADMS 3.5.1 Energy Losses 4. INTRODUCTION The problem with increased levels of power, as well as energy losses is a common problem in modern utilities, due to the constant increase of power grid loads and need for higher power quality . The ADMS Losses applications provide a global insight into the power/energy losses in a utilities entire radial or weakly meshed, balanced or unbalanced distribution (MV) network, for a specified network state and configuration, for a specified time period. The ADMS Losses applications are available in two modes: ADMS Energy Losses (EL) which calculates losses on the basis of simulated load flow calculations and ADMS Operational Losses (OL) which calculates losses on the basis of data stored in historical data base during real time system operation. 4 Proprietary and Confidential ADMS 3.5.1 Energy Losses 5. OVERVIEW EL&OL provide an assessment of the power/energy losses for a specified calculation area (the area consists of selected feeders, transformer areas and substations). Based on this, the application enables the identification of the most critical parts of the network regarding energy losses. Having a clear insight into the losses in the considered network, EL&OL provide a basis for reducing these losses and improving network operation. Reduction of losses not only means direct cost reductions, but it implicitly means a better voltage profile and balancing of loads as well. Loss reduction is a very important goal for development planning. Therefore, EL&OL are often used as important tools for network planning. 5.1. Architecture Both EL&OL use a common power application architecture described in the ‘FS Power Applications Infrastructure’ document [1]. The EL application is dependent on Load Flow calculations and the OL application is dependent on data stored in the historical data base (consisting of production real time data regarding customer interruptions). 5.2. Input Static input data for both EL&OL applications contains the network data model that includes an appropriate mathematical representation (simulation model) of the network where the network topology and network elements are prepared for calculations [1]. The dynamic input data for the EL application includes a specific network load provided by the user (by mode selection) and the current network configuration. In addition to the topological state of the network, the input data set for the OL application includes information about losses, consumption, generation and injected power of circuits from the past, collected from historical data base. Also, appropriate options related to the selection of intervals from historical data necessary for energy calculations, needs to be selected. Apart from static and dynamic data, the input data sets for both EL&OL include a list of feeders and transformer areas where losses are to be calculated. 5 Proprietary and Confidential ADMS 3.5.1 Energy Losses 5.2.1. Options 5.2.1.1. EL Options Name Initial value Range Description Current load Mode, Mode with the average load for a specific period, Detail mode. Time step for the detail mode can be: Load selection Current Mode load 15 minutes, 30 minutes, 1 hour, 2 hours, 6 hours. Determines which kind of mode will be used during the calculation Range for the period selection is [-2 year, +1 year] considering the current moment. 5.2.1.2. OL Options Name Initial value Range Description Period of evaluation Period of one month (end date is current date and start date is one month ago) Determines which 1/1/1900 – Current date period of time in the past (Period from history only) the calculation of losses will be performed. 6 Proprietary and Confidential ADMS 3.5.1 Energy Losses 5.3. Output The main outputs of EL&OL are as follows: Active/reactive energy losses, Active/reactive consumed energy, Active/reactive generated energy, Active/reactive injected energy. All results from above are calculated for feeders and transformer areas. Furthermore, EL provides aggregated results for substations and the entire portion of the network that was selected. All calculations are followed by user oriented reports. 5.4. Triggers EL is aimed for what-if analysis. It can be executed upon user request only, in both realtime and simulation modes. OL can be executed upon user request in both real-time and simulation modes. This application is dependent on data stored in the historical data base (based on production real time data regarding customer interruptions). This data is reached from both real time and simulation contexts in the production environment. 7 Proprietary and Confidential ADMS 3.5.1 Energy Losses 6. FUNCTIONALITY 6.1. Energy Losses The OL application is shown in the Function Execution Manager (FEM) by selecting Energy Losses from the main DMD menu (Figure 6.1). After that, users choose that part of the network where EL is to be performed. Transformer areas and feeders can also be selected for the EL calculation. Figure 6.1 – Energy Losses in Function Execution Manager The mode used for EL calculation needs to be selected in the Energy Losses Options dialog (Figure 6.2): The calculation can be performed for the current load. If EL is used in real-time, the last estimated load will be considered during the calculation. Otherwise, in simulation mode, the value used for consumption will be equal to the load specified at the moment defined as the simulation time, If the average load is selected, a specific period must be defined. The average load during a defined period will be determined and sent to the calculation engine, and EL will be performed for this configuration, If the detailed mode is selected, a specific period and a time step must be defined. For additional information on EL modes, refer to Methodology. 8 Proprietary and Confidential ADMS 3.5.1 Energy Losses Figure 6.2 – Energy Losses Options dialog During the EL calculation, results from the Load Flow (LF) and Performance Indices (PI) applications are used. The most important values are those PI results related to generated, injected and consumed active (real) and reactive power, as well as calculated active and reactive power losses. All these results are summarized and presented per circuit (feeder, transformer area and substation). Given that energy is needed, EL uses proper PI results (power) and performs multiplication using time intervals in order to obtain EL results (energy) for circuits (feeders, transformer areas and substations). EL results are presented in a report and are shown in 2 tabs: Overview and Individual. The Overview tab (Figure 6.3) contains basic results: Tables in the upper part of the report present the following results: o o The Active Energy [kWh] graph presents the following results: o Injected – Active energy injected in the selected circuit, Generation – Active energy generated in the selected circuit, Consumption – Active energy consumed in the selected circuit, o Losses – Active energy losses in the selected circuit. o o Active electric energy losses in the selected circuit – WP Losses (kWh, %), Reactive electric energy losses in the selected circuit – WQ Losses (kVArh, %). The Reactive Energy [kVArh] graph presents the following results: o o o o Injected – Reactive energy injected in the selected circuit, Generation – Reactive energy generated in the selected circuit, Consumption – Reactive energy consumed in the selected circuit, Losses – Reactive energy losses in the selected circuit. 9 Proprietary and Confidential ADMS 3.5.1 Energy Losses Figure 6.3 – EL Report window – Overview tab The Individual tab (Figure 6.4) presents all the above mentioned results in a table. Figure 6.4 – EL Report window – Individual tab 6.2. Operational Losses The OL application is shown in FEM by selecting Operational Losses from the main DMD menu (Figure 6.5). After that, to the user selects circuits (feeders or transformer areas) on which the OL application is performed. 10 Proprietary and Confidential ADMS 3.5.1 Energy Losses Figure 6.5 – Operational Losses in Function Execution Manager The period of calculation needs to be selected in the Operational Losses Options dialog (Figure 6.6): Figure 6.6 – Operational Losses Options dialog This calculation can be performed for a selected period in the past. The lower time limit (lowest value for Start) is 1/1/1900. This means that data about losses must be available for this duration and thus be available in historical database (i.e. previously entered in from old records). End can be set to a maximal value of the current date or to some date in the past – but End date must be closer to present than Start. During the OL calculation, historical results of LF and PI are used. The most important values are PI results related to generated, injected and consumed active (real) and reactive power as well as calculated active and reactive power losses. All of these results are summarized and presented per circuit (feeder, transformer area and substation). Given that energy is needed, OL uses proper PI results (power) and performs multiplication using 11 Proprietary and Confidential ADMS 3.5.1 Energy Losses time intervals in order to obtain OL results (energy) for circuits (feeders, transformer areas and substations). OL results are actually historical EL results i.e. losses for some period of the past. OL results are presented in a report and are shown in 2 tabs: Overview and Individual. The Overview tab (Figure 6.7) contains basic results: Tables in the upper part of the report present the following results: o o The Active Energy [kWh] graph presents the following results: o o o o Active electric energy losses in the selected circuit – WP Losses (kWh, %), Reactive electric energy losses in the selected circuit – WQ Losses (kVArh, %). Injected – Active energy injected in the selected circuit, Generation – Active energy generated in the selected circuit, Consumption – Active energy consumed in the selected circuit, Losses – Active energy losses in the selected circuit. The Reactive Energy [kVArh] graph presents the following results: o Injected – Reactive energy injected in the selected circuit, Generation – Reactive energy generated in the selected circuit, Consumption – Reactive energy consumed in the selected circuit, o Losses – Reactive energy losses in the selected circuit. o o Figure 6.7 – OL Report window – Overview tab The Individual tab (Figure 6.8) presents all the above mentioned results a table. 12 Proprietary and Confidential ADMS 3.5.1 Energy Losses Figure 6.8 – OL Report window – Individual tab 13 Proprietary and Confidential ADMS 3.5.1 Energy Losses 7. METHODOLOGY 7.1. Energy Losses The EL application deals with predicted losses (in the predicted (estimated) system state, using the LF application) in any user defined period of time. Distribution of losses per network elements and their grouping by supply elements (substations, transformers, feeders) provide a clear insight into the network state. The following modes of the EL application are available: Current mode – In this mode, the LF application is used only once with the current state. In this way, energy losses, consumed energy, generation energy and injected energy for the last hour (equal to powers) are calculated, Average mode – In this mode, the user selects a time period. The LF application is used only once with the average state (by losses) in that period. Afterwards, results are multiplied with the time interval. In this way, energy losses, consumed energy, generation energy and injected energy for the time period are calculated, Detail mode – In this mode, the user selects a time period and resolution of LF calculations triggering. In detail mode selected time period is divided into sub–periods (according to resolution) that are considered with the same level of consumption. Typical days are identified in each sub-period: working day, Saturday, Sunday and holiday. For a working day, at least one representative is taken (all 5 working days are described with the same set of normalized daily load profiles) or up to 5 representatives (each of 5 working days is described with different set of normalized daily load profiles). Numbers of days that are recognized as one of the typical days are calculated for each sub-period (e.g., a number of Saturdays is calculated in the sub-period, number of Sundays, etc.). Calculation of losses for one of the typical days is performed for each specific moment, taking into account the calculation time step (the time step is configurable: 15 minutes, 30 minutes, 1, 2 or 6 hours). For example, for 1 hour time step, the calculation will be performed 24 times (for each hour during the 24 hours period). The consumption for every hour is taken from provided daily load curves. In this way, the value of consumption is provided at every consumption point. This data is used as the input for the LF application. The LF application calculates the network state (e.g., voltage in every node of the distribution system, active/reactive power flows). The network state is the input for the PI calculation. This application provides power losses, while energy losses are calculated assuming that the given state lasts for the next hour (for a 1 hour time step for example). Calculated losses for each element are summarized 14 Proprietary and Confidential ADMS 3.5.1 Energy Losses for the entire period (24 calculation results for 1 hour time step example). This calculation is performed for all typical days. Losses per each of the typical days are multiplied by the number of the days in the sub-period and the calculated result is added to the sum for subperiod losses. Finally, total period losses are calculated by adding sub-period losses. Obviously, a significant number of calculations have to be performed for the EL application. Therefore, the request for extremely fast and efficient calculations makes sense. A branch oriented technique is the only one that can fulfill this request and this technique is applied in EL. 7.2. Operational Losses The OL application deals with historical losses data for some parts of the network, for any user defined period of time in the past. During the use of ADMS in the real time production environment, the load flow application followed by the performance indices calculation is triggered frequently. These applications could be triggered as part of the state estimation application (either periodically or driven by a significant measurement value change), triggered by a topology state change or even on demand. Each time the LF and PI are triggered, the results of these applications are provided to the system. In order to be available for additional analysis, some of these results are stored in the historical data base for further usage. The Load Flow Historical Configuration can be used for selecting those parameters which are going to be stored in the historical data base. By default, PI results that are needed by the OL application are always stored in the historical data base (they are mandatory). These PI result parameters are the real and reactive consumption power, losses, generation and injected power of feeder and transformer area circuits (Figure 7.1). 15 Proprietary and Confidential ADMS 3.5.1 Energy Losses Figure 7.1 – PI results used for OL calculation This means that each time that LF and PI are triggered (and calculated) during their use in the production real time environment, proper results (i.e. the power) will be stored for each feeder and transformer area in the network. t1 t2 t3 t4 tn time line PI res1 PI resn Historical data base Figure 7.2 – Storing PI results - Simplified diagram 16 Proprietary and Confidential ADMS 3.5.1 Energy Losses When the OL application is triggered, it uses a query to pick all the above mentioned values recorded in the historical data base and by calculating integral values it provides the: Active/reactive energy losses, Active/reactive consumed energy, Active/reactive generated energy, Active/reactive injected energy. 17 Proprietary and Confidential ADMS 3.5.1 Energy Losses 8. ERROR MESSAGES Message Severity Description Results are questionable because Warning Load Flow results are questionable. During the EL calculation, some of the LF calculation(s) provide questionable results. Results are bad because Load Warning Flow results are bad. During the EL calculation, some of the LF calculation(s) provide bad results. Note that these messages are related to the EL mode. OL will present only those error messages related to data base deployment issues. 18 Proprietary and Confidential