Condition monitoring of the
transformer (back to basics)
3 Comments
Hi this is Steven Mill! I’m back with a back to basics article about condition monitoring of the transformer. Hope it will
help y’all!
The transformer is the most crucial part in electrical distribution system as it is the most expensive equipment in an
electrical distribution system. If a transformer fail unexpectedly, not only it will a ect the electrical supply but also it will
cost you time and money. Hence it is important to detect early sign of fault to avoid power outage and extra cost.
In this article, we will discuss several techniques used to monitor the condition of the transformer. Those techniques are:
1. Acoustic Monitoring
2. Infrared Monitoring
3. Dissolved Gas Analysis
4. High Performance Liquid Chromatography
5. Partial Discharge
6. Frequency Response Analysis
7. Power Factor
8. Winding Resistance
9. Core Insulation Resistance
Acoustic Monitoring of the transformer
It is clear that if the load of the transformer increases, the noise will also increase. Hence several measurement is
needed to monitor transformer’s performance by measuring the noise such as [1] :
The basic of noise level, ie. When the transformer is new.
Changes in noise level over time, at a given load.
Relative level of noise compared with the background noise.
engineering.electrical-equipment.org/electrical-distribution/condition-monitoring-transformer.html

1/9
8/25/2019
▷ Condition monitoring of the transformer (back to basics)
Electrical Equipment
Home
Guide 
Categories 
Resources 
About us 

Figure 1. Acoustic monitoring | image: mitrasgroup.com
Infrared Monitoring
Infrared monitoring is the method to measure the performance of the transformer by detect the hotspots that occur
because, for example, improper cable connection or winding failure.
Figure 2. Infrared test detect the hotspot of the
transformer | image: ltl.ca
Dissolve Gas Analysis (DGA)

engineering.electrical-equipment.org/electrical-distribution/condition-monitoring-transformer.html
2/9
8/25/2019
▷ Condition monitoring of the transformer (back to basics)
Electrical
Equipment
due to decomposition of
transformer insulation oil. When the fault is major, the production of the decomposed gas are
Whenever oil transformer experience abnormal thermal, electrical stress, and other faults, several gases are produced
more and they get collected in Bucholz relay. However
when
are not signi
cantly high,the gases
Home
Guidethe
Categories
Resources
Aboutwill
us get
 faults


enough time to dissolve back in the oil. Hence it is necessary to analyse the quantity of di erent gases dissolve in

transformer.
By using interpretation technique (Key gases, gases ratio, or data mining) we can deduce fault indication by interpreting
the DGA tests result. The fault that could be detected by DGA tests are:
Electrical discharge
Partial discharge
Thermal fault in oil
Arcing in Tank tap changer
Overheating of cellulose
Degradation of cellulose by electrical fault
High Performance Liquid Chromatography
This method is developed in order to overcome DGA insensitiveness when lower temperatures (100 to 1300 C) are
concerned. The method correlates well with cellulose aging determined from Degree of Polymarisation (DP)
measurements [2].
DP measurements represents the length of the cellulose chain while HPLC identify the presence of furanes and
furfurans, created as the length of the cellulose chain shortens, as part of the aging process.
HPLC has been found to be sensitive in detecting aging at relatively low temperature and to provide strong evidence of
aging when transformers have been overloaded [2].
Partial Discharge
Partial discharge is electrical discharge which does not completely bridge the two electrodes. On a transformer, partial
discharge can occur in void of winding material or in gas bubble in an oil. Partial discharge on the transformer can be
detected by DGA test. However, a speci c particular discharge test is performed to obtain speci c location of the fault
and more reliable result.
A partial discharge measurement consist of:
Transformer being tested
Coupling capacitor
High voltage supply
Partial discharge detector
engineering.electrical-equipment.org/electrical-distribution/condition-monitoring-transformer.html

3/9
8/25/2019
▷ Condition monitoring of the transformer (back to basics)
Electrical Equipment
Software for analysis
The partial discharge is measured by analysing
the voltage
drop
transformer
terminal. ThisAbout
voltage
Home
Guide
Categories
Resources
uscalculated

 at the
 line

further to measure q, the apparent charge of the partial discharge. The detail of the partial discharge measurement will
be explain speci cally in other article.
Frequency Response Analysis (FRA)
Frequency response analysis is used to detect fault of the transformer, particularly to determine the displacement of the
winding.
Any electrical equipment always consists of resistance, inductance, and capacitance RLC that is a function of frequency.
The RLC impedance versus frequency characteristic is then used to assess electrical and mechanical condition of a
transformer. Laboratory test have demonstrated the sensitiveness of this technique.
FRA can be used to detect mechanical damage and winding deformation of the transformer after fault happen. If short
circuit occur in the transformer, it can su er heavy mechanical damage from the very large electromagnetic force.
Winding deformation also can be caused by lightning or system switching. After such an event, the engineer need to
know whether it is safe to re-energise the transformer by doing FRA test.
FRA is normally used to analyse [1] :
Change in the response of the winding
Di erence between the responses of the three phase of the same transformer
Di erences between the responses of the transformer of the same design
Option require that FRA has been previously performed on the transformer, whilst option b and c doesn’t.

engineering.electrical-equipment.org/electrical-distribution/condition-monitoring-transformer.html
4/9
8/25/2019
▷ Condition monitoring of the transformer (back to basics)
Figure 3. FRA of a new transformer | image:
Electrical Equipment
globecore.com
Home
Guide 
Categories 
Resources 
About us 

Power Factor
Power factor measurement is performed to assess the dielectric condition of the transformer. Power factor testing is an
e ective method to detect and help isolate conditions such as moisture, carbonization, and contamination in bushings,
windings and liquid insulation. In addition to power factor testing, transformer excitation current measurements will
help detect winding and core problems.
However, the fact the measurement is an overall quantity for the winding and therefore it is practically impossible to
determine whether there is a problem of the whole winding, e.g. contamination by sludge or carbon deposit, or localised
fault.
Power factor test is performed by applying voltage and measure the leakage/loss current of electrical insulation [3]. The
leakage comprises of two components:
Resistive current (Ir)
Capacitive current (Ic)
Polarisation Spectrum

engineering.electrical-equipment.org/electrical-distribution/condition-monitoring-transformer.html
5/9
8/25/2019
▷ Condition monitoring of the transformer (back to basics)
Electrical
Equipment
being seen as a more reliable
indication of dryness of the transformer than moisture in oil measurements.
This technique is used to measured water content in the paper in an oil-paper insulation system and is increasingly
Home
Guide 
Categories 
Resources 
About us 
The test is performed by charging the transformer dielectric by 2000VDC voltage for a particular charger time,

discharged for half time, and then the peak and initial slope and the recovery voltage are measured. The dielectric is
then fully discharged before a new measurement is made for a di erent charge time. Measurements can be made for
charge times from 20ms to 5000s. The condition of the dielectric is characterised by the dominant time constant for the
peak recovery voltage and by the characteristic slope of the initial slope versus peak recovery voltage plot [1].
However there is uncertainty of the results if the test is performed in a few very old transformer as oil acidity and paper
degradation can complicate the result.
Winding Resistance
This test is performed to check the transformer winding, terminal connection and tap changer, and also to calculate the
load loss value. Loose connections and high contact resistance can initiate increasing levels of ethane and or ethylene.
Winding resistance can be measured using micro-ohmmeter. The results then compare with factory measurements with
a correction factor is needed. The following formula is used to compare the result:
Where,
Rs = Resistance at the factory reference temperature.
Rm = Measured resistance
Ts = Factory reference temperature (usually 750 C)
Tm = Temperature at which measurements were taken
Tk = A constant, 234.50 C for coper, 2250 C for aluminium
Core Insulation Resistance
Additional core ground can be detected by DGA. However, core insulation resistance is performed when the winding
resistance shows that all of tap changer and connection contacts are in good condition whilst DGA test show signi cant
proportion of ethane, ethylene, and possibly methane.
The test is done by disconnecting the intentional ground. The resistance is measured in mega ohms by a DC megger or
may be determined from calculation. Make sure to always earth the core and the tank before measuring the insulation

engineering.electrical-equipment.org/electrical-distribution/condition-monitoring-transformer.html
6/9
8/25/2019
▷ Condition monitoring of the transformer (back to basics)
Electrical
determined by measureEquipment
the resistance between each winding and all other earthed windings.
resistance. Next, short circuit the both winding terminals of the transformer. After that, core insulation resistance is
Home
Guide 
Categories 
Resources 
About us 
The following table show the condition of the core insulation resistance for di erent measured readings [4]:

References
[1] D. Hoyle and R. MacKinlay, “Transformers 3 (Electrical Performance Testing),” in Asset Management, Maintenance &
Condition Monitoring, Newcastle Upon Tyne, Newcatle University, 2015, p. 7.
[2] P. D. J. Allan, “Transformer Magnetic Circuit,” in Transformers, Newcastle, Newcastle University, 2015, p. 30.
“megger.com,”
[3] Megger, [Online]. Available: http://en.megger.com/getmedia/7050fe9b-7fdc-45a4-ba864d4f2cb8b114/Transformers_AG_en_VO1.PDF/. [Accessed 17 April 2016].
[4] “IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus Part 1: Oil Filled Power Transformers, Regulators,
and Reactors,” IEEE Standard 62-1995, 1995.
Thanks again for reading me!
Steven Mill
Did this article helped? Do you think it lacks information? Tell us in the comments below.
#insulation resistance #partial discharge #the transformer


3 Comments
engineering.electrical-equipment.org/electrical-distribution/condition-monitoring-transformer.html


7/9
8/25/2019
▷ Condition monitoring of the transformer (back to basics)
Electrical Equipment
Tom Okello
Home
Guide 
Categories 
Resources 
About us 

2016/06/24 at 9:27 am
This reduces the shutdown time
Reply
Jacob Enco
2019/05/23 at 5:46 am
This is an excellent system that you have developed here Steven, seems very comprehensive and
easily applied to all sorts of di erent transformers.
Reply
w11stop
2019/06/18 at 9:36 am
I have been using transformers since long time and the above explained is just amazing so
simple and clean, I guess the aged transformers measurement can also be 150 < R < 1500. This
will create more power. I have used it before.
Reply
Leave a Comment
Comment
Name *
Email *
Website
Post Comment

engineering.electrical-equipment.org/electrical-distribution/condition-monitoring-transformer.html
8/9
8/25/2019
▷ Condition monitoring of the transformer (back to basics)
Electrical Equipment
Copyright © 2019. Electrical Equipment.
Home
Guide 
Categories 
Resources 
About us 


engineering.electrical-equipment.org/electrical-distribution/condition-monitoring-transformer.html
9/9
Download