NFPA 20 1-8 (3.2) NFPA Official Definitions Authority Having Jurisdiction.* The organization, office, or individual responsible for approving equipment, materials, an installation, or a procedure. A-1-8 (3.2.2) Authority Having Jurisdiction. The phrase “authority having jurisdiction” is used in NFPA documents in a broad manner, since jurisdictions and approval agencies vary, as do their responsibilities. Where public safety is primary, the authority having jurisdiction may be a federal, state, local, or other regional department or individual such as a fire chief; fire marshal; chief of a fire prevention bureau, labor department, or health department; building official; electrical inspector; or others having statutory authority. For insurance purposes, an insurance inspection department, rating bureau, or other insurance company representative may be the authority having jurisdiction. In many circumstances, the property owner or his or her designated agent assumes the role of the authority having jurisdiction; at government installations, the commanding officer or departmental official may be the authority having jurisdiction. NFPA 20 (3.2.1) Approved.* Acceptable to the authority having jurisdiction. A-1-8 (A.3.2.1) Approved. The National Fire Protection Association does not approve, inspect, or certify any installations, procedures, equipment, or materials; nor does it approve or evaluate testing laboratories. In determining the acceptability of installations, procedures, equipment, or materials, the authority having jurisdiction may base acceptance on compliance with NFPA or other appropriate standards. In the absence of such standards, said authority may require evidence of proper installation, procedure, or use. The authority having jurisdiction may also refer to the listings or labeling practices of an organization ( UL or <FM> ) that is concerned with product evaluations and is thus in a position to determine compliance with appropriate standards for the current production of listed items. WATER SUPPLY NFPA 20 (5.6) The most common sources of fire protection water are: city water, above ground tank, below ground tank, well, or an open body of water ( pond, river, lake, etc. ) NFPA 20 (6.1.2) Centrifugal pumps shall not be used where a static suction lift is required. Find out how many GPM are required and how much PSI is needed to make the sprinkler and/or stand pipe system work… Will the “proposed” water supply and fire pump meet the system demand ? Will the water supply be adequate at 150% of the fire pump rated flow??? NFPA 20 (5.6.2) (5.6.5.1) NFPA 20 (5.6.2.2) Where the water supply from a public service main is not adequate in quality, quantity, or pressure, an alternative water source “SHALL” be provided. NFPA 20 (5.6.5) Head. The head (suction pressure) available from a water supply shall be figured on the basis of a flow of 150 percent of the rated capacity of the fire pump. This head should be determined by a flow test of the water supply prior to ordering the pump. --SAMPLE-- NOTE: Water supply flow test - MUST BE CONDUCTED BEFORE A PUMP IS SPECIFIED AND ORDERED! (5.6.5) This water supply has a 6” line and an 8” that will feed a 1000 GPM pump. The top curve has both lines open, the lower curve has only the 6” open. In the worst condition (6” only) the line will provide 1000 GPM @ 45 PSI. Theoretical Conditions P U M P H E A 323 ‘ 231 ‘ . NFPA 20 Theoretical Maximum Churn HEAD “Must not exceed” 140 % of Rated HEAD NFPA 20 100% “Rated” Condition 500 GPM @ 231 ‘ HEAD NFPA 20 Theoretical Minimum Head AT 150% of RATED FLOW - Head Must Be “Above “ 65% of Rated Head 500 GPM STATE PUMP FLOW in GPM 750 GPM of OHIO FIRE SCHOOL - BGSU 6 Total Head (H), Horizontal Pumps.* The measure of the “work increase” per pound (kilogram) of liquid, imparted to the liquid by the pump, and therefore the algebraic difference between the total discharge head and the total suction head. Where “positive” suction head exists, the total head ( work increase ) = the total discharge head ‘minus’ ( - ) the total suction head. Total Head (H), Vertical Turbine Pumps.* The distance from the pumping water level to the center of the discharge gauge ‘plus’ ( + ) the total discharge head. CALIBRATED ?? CALIBRATED ?? PSI / HEAD (ft) STATE of OHIO FIRE SCHOOL - BGSU 8 HORIZONTAL PUMPS To determine “ H ” (net PSI) subtract Suction PSI from Discharge PSI 150 PSI 50 PSI 100 PSI 231’ (ft) To determine FEET of HEAD multiply “ H “ (net PSI) X 2.31 The suction pressure must be (0 psi) or higher when pump is operating at 150 %. When suction is from a tank the pressure is permitted to drop to (-3 psi). NFPA 20 (5.14.3) . “RATED” 100 % FLOW . “RATED ACTUAL CITY WATER FROM PUMP TEST STATE FLOW IN GPM “ 150 % C 100% FLOW “ “ FLOW . . H E A D B . . . A “CHURN” Pressure of OHIO FIRE SCHOOL - BGSU 10 PUMP FLOW DETERMINATION WITH FLOW METER STATE of OHIO FIRE SCHOOL - BGSU 11 NOZZLE (PLAY PIPE) AND PITOT TUBE PUMP FLOW STATE of OHIO FIRE SCHOOL - BGSU DETERMINATION 12 <FM> FLOW CHART UL / FM CENTRIFUGAL FIRE PUMPS PACKAGED PUMP HOUSE Prefabricated Fire Pump House SITE PREPARATION : Slab or Footer NOTE : No Spreader Bars ! STATE of OHIO FIRE SCHOOL - BGSU 19 Field Erected Pump House or Pump Room Vertical In-Line Horizontal Split - Case Vertical Turbine To Test Head Jockey Pump STATE of OHIO FIRE SCHOOL - BGSU 24 Horizontal Split - Case Fire Pump Water Seal Piping NOTE: Water seal piping is not provided on UL Fire Pumps with suction pressure of 30 psi or more ! YOU MUST ACCURATELY DETERMINE THE SUCTION PRESSURE “BEFORE” THE PUMP IS ORDERED !! NFPA 20 (5.2.2) (5.6.2.3) #1 Actual suction pressure MUST NOT exceed this ! “ACTUAL” Suction pressure MUST be determined BEFORE you order the pump ! NFPA 20 (5.2.2) (5.6.2.3) Look at the pipe fittings !! This pump installation develops 213 PSI at churn. A 125 lb flanged fitting is rated at 175 PSI maximum working pressure !! NFPA 20 (5.7.4.1) NO RODS !!! SAFE ?? NFPA 13 15.1.6.1.1 STATE of OHIO FIRE SCHOOL - BGSU 28 NFPA 20 (5.7.4.1) (5.7.4.2) Variable Speed PLC (5.18.1.3) (5.18.7) STATE of OHIO FIRE SCHOOL - BGSU 29 Circulation Relief Valve ¾” is the MINIMUM size for up to 2500 GPM Rated Pump*. 1” MIN. for larger pumps ??? NFPA 20 (5.11) STATE of OHIO FIRE SCHOOL - BGSU * 30 55 L 918 19 - 20 Circulation “Case” Relief Valve NFPA 20 2-6 (5.11) NOTE : Not required on diesel engine-driven HSC fire pumps unless the engine is radiator-cooled ! * 10691 FWC Typical CIRCULATION (CASE) RELIEF VALVE Assembly – The valve must be installed (VERTICALLY) on the pump discharge before the discharge check valve NFPA 20 (5.11.1.2) NOTE: (Optional) Y strainer can be used when foreign material (sand or other debris) is present in the water. ORIFICE FLOW NOTE: Above (optional) Backpressure orifice assembly installed in ¾” case relief valve discharge to create back pressure and reduce cavitation. STATE of OHIO FIRE SCHOOL - BGSU 32 Automatic Air Air Release Release Automatic NFPA 20 20 2-6 2-6 (6.3.3) NFPA NOTE : Automatic air release valve installed NFPA 20 STATE of OHIO FIRE SCHOOL - BGSU 34 (5.14) PIPE SIZE ? NFPA 20 (5.14.3.4) ! Elbows and tees with a centerline plane parallel to a horizontal split-case pump shaft shall be avoided. See Figure A-2-9.6. (5.14.6.3.1) If there is a parallel elbow : YOU MUST HAVE 10 PIPE DIAMETERS of STRAIGHT PIPE BETWEEN THE ELBOW AND PUMP SUCTION FLANGE (5.14.6.3.2) STATE of OHIO FIRE SCHOOL - BGSU 35 NFPA 20 2-9.6.4 (5.14.6.4) STATE of OHIO FIRE SCHOOL - BGSU 36 NFPA 20 2-9.6.4 (5.14.6.4) SUCTION SUCTION NFPA 20 SUCTION 2-9.6.3 Elbows and tees with a centerline plane parallel to a horizontal split-case pump shaft shall be avoided. See Figure A-2-9.6. (5.14.6.3.1) STATE of OHIO FIRE SCHOOL - BGSU 38 CORRECTED !!! NOTE: No ELBOWS STATE of OHIO FIRE SCHOOL - BGSU 39 OSY Suction Valve NOTE: Backflow Preventer! NOTE: The long straight run of suction pipe after a HORIZONTAL 90 DEGREE ELBOW ! More than 10 pipe diameters ? (5.14.6.3.2) STATE of OHIO FIRE SCHOOL - BGSU 41 Is this Suction Piping OK ? SUCTION SUPPLY City Water (5.14.6.3.3) Is this HSC vertical installation “REALLY” a space saver ?? IS IT CORRECT ?? OK ? SUCTION DISCHARGE NFPA 20 (5.14.6.3.1) STATE of OHIO FIRE SCHOOL - BGSU 43 NOTE: Backflow Preventer on DISCHARGE side of Pump !! (5.26) (5.14.9) City By -Pass Study and understand the piping ! Ask questions if you are not sure ! PUMP Suction #2 STATE of OHIO FIRE NOTE : Left Hand Rotation ! * Counter Clockwise ! CONFIRM BEFORE you order the PUMP !! NFPA 20 (5.22) SCHOOL - BGSU 44 ? y-Pass City Water B Test Header Control Valve and Piping #3 What is the SUPPLY Voltage ? Is a Transfer Switch required ? DOUBLE CHECK and CONFIRM BEFORE you order the pump NOTE: Test Header Piping is Connected Between the Pump Discharge Check Valve and the Discharge (System) Shut - Off Valve. NFPA 20 (A.5.19.3.1) Test Header Control Valve and Piping FLOW NOTE : No drain valve on bottom of test head pipe ! NFPA 20 (5.19.3.3.1) FIRE PUMP TEST CONNECTION (5.19.3) #4 What hose threads are required on the hose valves in your jurisdiction ? CHECK and CONFIRM before you order the pump ! NFPA 20 (5.19.3.2) FIRE PUMP TEST HEAD Fire Pump Test Head Must be located where the motor and controller will not be damaged by spraying or splashing water. Preferably outside of the pump house or the pump room ! NFPA 20 (A.5.19.3.1) NFPA 20 A-2-14.3.1 TEST HEAD ?? HOSE /TEST VALVES (A.5.19.3.1) STATE of OHIO FIRE SCHOOL - BGSU 50 What coupling will be accepted by LAHJ ? FIND OUT ! ASK ! “UL” Listed ?? NFPA 20 (6.5) #5 FALK Steel Flex – APPROVED ?? STATE of OHIO FIRE SCHOOL - BGSU 51 Drive Shaft – APPROVED ? STATE of OHIO FIRE SCHOOL - BGSU 52 <FM> and IRI Bulletin 91-9 DO NOT USE Elastomer Couplings ON UL/FM FIRE PUMPS ! < FM> 9-2006 IRI Bulletin 91-9 LOOSE SET-SCREWS ???? TB Woods Elastomer Coupling STATE of OHIO FIRE SCHOOL - BGSU 57 Diesel Driven HSC Fire Pumps Engine HP De-rate (11.2.2) * 3% for every 1000’ ALT. above 300’ 1% for every 10 degrees (F) above 77 #6 NEW: NFPA 20 (11.2.4.2) Pressure-Limiting Drivers (5.18.6.3) 100 PSI 170 PSI 240 PSI FOR TESTING (14.2.7.3.7.3) NOTE : With a PLD All pump discharge fittings, TO and including the system shut off valve, must be rated for the MAXIMUM discharge (CHURN) CLARKE Fire Protection Products System Relief Valve is Required when a Variable Speed – OR -Pressure Limiting Driver is used (5.18.1.3 ) * -------also--------Required when diesel fire pump churn pressure X 1.21 (plus maximum static suction) exceeds the maximum working pressure of the system components NFPA 20 (5.18.1.1) * #7 REQUIRED ? (5.18.1.1) NOTE: This Pump did not require a main relief valve since the sum of the churn pressure times 121% plus the max. suction pressure is only 142 PSI. No Relief Valve ? STATE of OHIO FIRE SCHOOL - BGSU 63 Combustion Air Louver NOTE: Relief valve is piped to waste outside of building (5.18.6) (A.5.18.5) Water supply is from a ground storage tank NOTE: Flexible Dresser Pipe Couplings to allow for tank settling! ( A.5.17 ) Note: Packing drain lines run to a floor drain.(5.12.6.2) Relief valve discharge is permitted to be piped back to the above ground storage tank (5.18.6.3) When Pump Maximum Discharge Pressure is evaluated with the 121 % rule NFPA 20 (A.5.18.1) STATE of OHIO FIRE SCHOOL - BGSU 65 NOTE: System (Main) Relief Valve (if used) is connected to the pump discharge BEFORE the Discharge Check Valve !! (5.18.3) Engine Cooling Water Piping – NFPA 20 (11.2.6.3) (5.18.5) e Wast e v l f Va Relie .6) (5.18 STATE of OHIO FIRE SCHOOL - BGSU 66 Where the cooling water contains foreign material such as leaves, grass, wood chips, etc – duplex filter type strainers should be provided. NFPA 20 (A.11.2.6.4) STATE of OHIO FIRE SCHOOL - BGSU 67 ENGINE cooling waste water MUST be piped so the flow can be VISUALLY observed and confirmed. The discharge pipe MUST be at least one size larger than the inlet. NFPA 20 (11.2.6.6) ste a rW e t Wa ain g lin n Dr .6.6) o o C Ope 11.2 ( To A 20 P NF P EMERGENCY MANUAL STARTING PROCEDURE - NFPA 20 (11.6.6) C F C = Cooling Water = Fuel = Crank EMERGENCY MANUAL STARTING PROCEDURE (11.6.6) CUMMINS SET at 120 % of Rated RPM ***** NOTE ! #1 COOLING WATER #2 FUEL #3 CRANK BE SURE THAT YOU KNOW WHERE THE OVERSPEED RESET IS ON EVERY TYPE OF ENGINE THAT YOU SELL or INSTALL !! INSTRUCT THE OWNER’S REPRESENTATIVE OR OPERATOR. #1 For EMERGENCY OPERATION of “ANY ENGINE” the by-pass AND normal COOLING WATER VALVES must ALL be - OPEN ! With Newer Engines, the toggle switch, when in MANUAL will turn on both FUEL and COOLING WATER #2 #3 CRANK BATTERY 1 or 2 STATE of OHIO FIRE SCHOOL - BGSU 74 NFPA 20 (11.5.3) Exhaust pipes shall be installed with clearances of at least 9” to combustible material. Insulate or guard exhaust pipe??? NFPA 20 (11.5.3.3) NOTE: Victaulic fittings with rubber gaskets ? FLEX CONNECTOR ¼” MAX. MISALIGNMENT ?? Exhaust Fan and Air Intake Louver NFPA 20 (11.3.2.4) MAX 120 degrees F NFPA 20 (11.3.2.3) Fuel Return (12.4.1.3 - 11) Tank must be kept 2/3 full ! NOTE : UL Listed tanks must have a metal “ UL ” nameplate attached to the tank ! LOOK FOR IT ! STATE of OHIO FIRE SCHOOL - BGSU 80 Top 5% and bottom 5% of tank volume is not used in determining capacity of tank. NFPA 20 8-4.3 (11.4) * Bottom 5% FUEL Tank Drains NFPA 20 A-8-4.6 (A.11.4.6) Fuel Supply Valve locked in OPEN position …NFPA 20 A-8-4.6 (A.11.4.6) NEW: 2003 NFPA 20 (11.4.6.2) Fuel lines no copper or galvanized The fuel supply opening to the engine shall be no lower than the engine fuel pump centerline. NFPA 20 (11.4.5.4) Fuel Return Fuel Level (11.4.5.7) Fuel tank capacity Low Fuel Switch * SET AT 2/3 (12.4.1.3) NFPA 20 (11.4.3) * Tank location inside NFPA 20 (11.4.5.6) Fill and vent piping STATE NFPA 20 (11.4.5.8) of OHIO FIRE SCHOOL - BGSU 83 The flash arrester should be a minimum 11’- 0” above the top of the fuel tank NFPA 20 (A.11.4.6) 10 ‘ NOTE : Dual Flash Arresters (VENTS) for “DOUBLE WALL” Fuel Tanks ! Tank Fill SHOULD BE Piped to the outside (A.11.4.5) 5 PSI Hydro-test at the JOB ?? To Engine Some “LAHJ” REQUIRE a containment dike, even when a double wall tank is provided ! CHECK and LEARN THE LOCAL CODES ! #8 Vertical In-Line Fire Pump Suction Inlet ALL Pump Rooms are Required to have a FLOOR DRAIN!!! (5.12.6.2) Circulation “CASE” Relief Valve Piped To A Floor Drain. (5.11)* STATE of OHIO FIRE SCHOOL - Packing Drain Lines Run to a Floor Drain. Do not combine with case relief valve piping! !! BGSU (5.11.1.5) 89 #9 NOTE STRAINER! 10 p i dia. pe ?? NFPA 20 (6.3.4) NOTE: Strainer requirement was removed after 2007STATE ! of OHIO FIRE SCHOOL - BGSU 90 NO SUCTION STRAINER ?? WHY NOT ? STATE of OHIO (6.3.4) A Hand Hole is “NOT” a Strainer!! Could You Get Rocks and Boards out of this small “ FIRE SCHOOL 91 PIPE PLUG- “BGSU opening ?? Could YOU get this stuff out of a “PIPE PLUG OPENING” in the bottom of an Inline Fire Pump ? Could this be why a strainer Is “REQUIRED” ? Vertical Turbine Fire Pump NFPA 20 (7.4.1) Motor HP and THRUST limits must meet or exceed those of the Fire Pump. CHECK ! (7.5.1.1) (9.5.2) #10 NOTE: Automatic air release NFPA 20 (7.3.5.2.3) “SHALL BE” Located between the fire pump and the discharge check valve. * NOTE: Automatic air release “SHALL BE” Located in the highest point in the discharge line, between the fire pump and the discharge check valve. NFPA STATE of OHIO FIRE 20 (7.3.5.2.3) * SCHOOL - BGSU 95 NFPA 20 (7.6.2.3) ACCESS FOR REMOVAL ? STATE of OHIO FIRE SCHOOL - BGSU 96 NFPA 20 ( 7.4.3.7 ) I– beams must be parallel to the driver ! One degree of off-set is the preferred angle, per drive shaft manufacturers!! NFPA 20 (6.5) (7.5.1.7.2) STATE of OHIO FIRE SCHOOL - BGSU 99 #11 CHECK the pump HP and THRUST requirements. CHECK the gear HP and THRUST limits. CHECK the engine HP rating. THIS MUST BE DONE BEFORE THE PUMP IS ORDERED !! ( 7.5.1.6.4 ) NFPA 20 (7.6.1.3) Top Shaft Nut is used to raise shaft and impellers approximately 1/8 “ inch. (see instruction book) STATE of OHIO FIRE SCHOOL - BGSU 101 Screen openings equal to 1 sq. in. for every GPM (pump capacity at 150%) (at LOWEST Water LEVEL) NFPA 20 (5.14.8) #12 Confirm proper submergence (Pump Length) * Water Vel, 2’/sec Max * Water Vel. 1’/sec Max NFPA 20 (A.7.2.2.2) (5.14.8) (7.2.2.2) Removable screens NFPA 20 (5.14.8.3) Intake size NFPA 20 (5.14.8.4) Removable screens NFPA 20 A4-2.2.2 (5.14.8.3) Intake size NFPA 20 A4-2.2 (5.14.8.4) With a vertical turbine fire pump a plugged screen will affect the water level in the sump and a plugged basket strainer on the bottom of the pump will reduce the total pump performance. NFPA 20 2003 Zebra Mussel Infestation (5.14.8.12) STATE of OHIO FIRE SCHOOL - BGSU 106 VTFP INTAKE PROBLEMS……….. Removable screens NFPA 20 A4-2.2.2 (5.14.8.3) Intake size ??? NFPA 20 A4-2.2 (5.14.8.4) 2 ft/sec and 1 Sq. Inch per GPM at 150% Flow ? Pond Maintenance -ORLack of !!! Proper pond Maintenance PART 2 FIRE PUMP Acceptance Testing In The State of OHIO FIRE PUMP ACCEPTANCE TEST 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. Check for company and individual LICENSING. Check for HYDRO and FLUSHING CERTIFICATES. Check for CERTIFIED shop test curve vs. SYSTEM DEMAND. Has the pump been properly ALIGNED and PRE-TESTED??? Record all pump, driver, and controller data. (HP, VOLTAGE, etc.) Look system over…sensing lines, reducers, piping , water supply…. Check for CERTIFICATE of CALIBRATION for test equip. (SAFE??) Decide in advance just what is to take place during the test Operate the pump at churn (no flow)….temp., brgs., packing, etc. Record PSI, RPM, AMPS, VOLTS, (compare and plot results). Operate the pump at additional flow points 50%, 100%, 150%,. Record PSI, RPM, AMPS, VOLTS, (compare and plot results). 6 AUTO Starts and 6 MANUAL Starts. (One Full Load Start) Controller and Driver alarms connected / tested (electric and diesel) Start and Stop PSI for Main Fire Pump and Jockey Pump. Low Suction Control Set Point AND Alarm Connected??? Operators trained in maintenance and weekly testing??? Review test results - ASK QUESTIONS!!!!!! Do it again ??? STOP!!!! Don’t accept it if the data is not CORRECT!!!! 1. Check for company and individual LICENSING as REQUIRED by STATE or LAHJ. CHECK EVERYONE who touches the equipment…pump guy, fitters, controller guy, and engine guy!!! They all must have a license to service, test, repair, or install any fire protection equipment in the State of Ohio. Compare with driver’s license….. Check every year….. RECORD the information……. RECORD NAMES OF ALL FIELD ACCEPTANCE TEST PERSONNEL (LAHJ) FIRE DEPT OFFICIAL OWNER’S REPRESENTATIVE MAINTENANCE PERSONNEL INSTALLING CONTRACTOR AUTHORIZED FIRE PUMP REP AUTHORIZED CONTROLLER REP AUTHORIZED ENGINE REP INSURANCE REPRESENTATIVE STATE of OHIO FIRE SCHOOL - BGSU 114 1. Check for HYDRO and FLUSHING CERTIFICATES. NFPA 20 11-1.1 (14.1) Was the Underground and Aboveground piping installed, flushed, and hydro-tested by a “Licensed” contractor ? Did “YOU” witness flushing and hydro-test?? Did installing contractor “OFFER” to have you witness the above and provide you with the mandatory test certificates …… NFPA 20 11-1.3 (14.1.3) Someone had to sign and witness (WHO ??) NO TEST CERTIFICATES???? WHY NOT??? NFPA 20 (14.1.3) What happens when the pump plugs with rocks or a pipe fitting blows apart????? NFPA 20 (14.1.1.1) FLUSHING Table (14.1.1.1[a]) Minimum Flush Rates. Contractor may have a calculated system demand which, if greater, will require higher flush rates than those listed below. Pipe Size in. mm 4 102 6 152 8 203 10 254 12 305 Flow Rate gpm 590 1,360 2,350 3,670 5,290 L/min 2,233 5,148 8,895 13,891 20,023 ROCKS IN IMPELLER Was this system properly flushed?? NFPA 20 (14.1) System was flushed for 2 hours with 3 hoses ! Problem : Hoses were ¾” garden hoses !!! 3. Check for PUMP CERTIFIED SHOP TEST CURVE. Compare it to the SYSTEM DEMAND. NFPA 20 2-16 and 11-2.3 (14.2.4) Find out how many GPM are required and how much PSI is needed to make the sprinkler system work… Will the fire pump and water supply do it ? Fire Pumps are selected for “SYSTEM DESIGNS” which can utilize any pump flow up to 150% of rated capacity. NFPA 20 2-3 and A-2-3 (5.8) Sample Pump Curve 4. Has the Pump and Driver been ALIGNED, LUBRICATED, and PRE-TESTED??? Pump and driver MUST be field-aligned NFPA 20 3-5 (6.5.2) and pre-tested PRIOR to the field acceptance test - includes electrical NFPA 20 (14.2.3) so that inspector’s time is not wasted standing around…….. MANY jurisdictions charge an additional fee if retesting is required due to problems with a system which has not been pre-tested prior to the acceptance test!!!! STATE of OHIO FIRE SCHOOL - BGSU 124 STATE of OHIO FIRE SCHOOL - BGSU 125 GAP MUST BE EQUAL - TOP TO BOTTOM AND SIDE TO SIDE. Within .005” Angular Alignment USE OF DIAL INDICATORS OR LASERS IS PREFERRED. STATE of OHIO FIRE SCHOOL - BGSU 126 NOTE : The coupling halves should remain disconnected until rotation has been checked! Parallel alignment should be less than .005 “VERTICAL STATEand of OHIO HORIZONTAL” FIRE SCHOOL - BGSU 127 FALK Steelflex Coupling AFTER alignment and rotation have been checked the coupling should be lubricated and re-assembled. Be sure to check the set screws for tightness STATE of OHIO FIRE SCHOOL - BGSU 128 After checking the alignment, leave the pump and driver uncoupled until after rotation check ! Pump rotation should be checked with the coupling not connected……..* 4 Year Old Pump Pump was 6 % Low. STATE of OHIO FIRE SCHOOL - BGSU 130 NOTE: The quarter on a properly installed, grouted, aligned, and lubricated fire pump!!! 125 HP, 1760 RPM Motor in operation, NO VIBRATION ! STATE of OHIO FIRE SCHOOL - BGSU NFPA 20 ( 14.2.6 )131 After greasing be sure to check torque of ALL bolts and set screws ! Add Grease slowly ! Check For Excess Grease NOTE: Insert clean grease slowly until old grease is forced out of the drain hole with PLUG REMOVED !! NOTE : Operate the pump for 15 – 30 min. before replacing the plug ! Gear oil full ? Check it ! Motor oil full ? Check it ! What oil did they use ?? ASK !! Coolant level full ? Engine Lube Oil and Coolant Checked ? Engine Guy ? HAS THE PUMP BEEN PRE-TESTED ?? Is it required ? STATE of OHIO FIRE SCHOOL - BGSU 136 5. RECORD all equipment data: pump, driver, and controller. (HP, RPM, VOLTAGE, SN, etc.) Are the fire pump, driver, and controller ALL “UL” UL listed or “FM” FM approved???? CHECK THE NAME PLATES !!! Motor and controller voltage and HP must be the same!!! 200 volt is “not” the same as 230 volt!!! The required pump HP must not exceed the driver rated HP X 1.15 SF!!! STATE of OHIO FIRE SCHOOL - BGSU 139 Incoming Power Supply (voltage) MUST Be the “SAME” as the Main Fire Pump Controller “AND” the UL Listed Fire Pump Motor !! NFPA 20 (9.1.3) NFPA 70 Article 695 CHECK IT !!* STATE of OHIO FIRE SCHOOL - BGSU 140 * THE AVAILABLE POWER MUST MATCH THE FIRE PUMP MOTOR NAMEPLATE AND CONTROLLER NAMEPLATE VOLTAGES - LOOK FOR CHANGED OR ALTERED NAMEPLATES THAT ATTEMPT TO COVER UP A MISTAKE !!!! * NFPA 20 (10.3.4.4) Means shall be provided on the exterior of the controller for measuring all line amps and volts. Is it “SAFE”? Is it “CORRECT”? Power, sensing lines, reducers, UL/FM piping , water supply. supply Jockey and main fire pump must each have a separate ½ “ sensing line with 2 ea. 3/32 “ orifices located at least 5’ – 0” apart . `NFPA 20 7-5.2.1 and appendix!! (10.5.2.1.6) Case relief valve (electric fire pumps) piped to a REQUIRED floor drain in the pump room??? NFPA 20 2-6.1 and 2-7.6 (5.12.6.2) Do not pipe Case Relief Valve discharge and Packing Drain lines together into a common drain line (5.11.1.5) Pump coupling and guard secured??? IS THIS A CONFINED SPACE???? Is the “TEST SET UP” (test hoses, rack, and play pipes) pump location “SAFE”? OSHA APPROVED ??? Would “YOU” go down here to test this pump???? NFPA 25 and ( A.5.12) DRAINAGE and VENTILATION ) 4.7.1 A.4.8 NOTE : This fire pump develops 165 psi at churn ! The class 125 fittings are good for a maximum working pressure of 175 psi. (5.7.4.1) Note : Rods on transition piece!! STATE of OHIO FIRE SCHOOL - BGSU 146 Look at the pipe fittings !! This pump installation develops 213 PSI at churn. A 125 lb flanged fitting is rated at 175 PSI maximum working pressure !! NFPA 20 (5.7.4.1) NO RODS !!! SAFE ?? NFPA 13 15.1.6.1.1 STATE of OHIO FIRE SCHOOL - BGSU 147 Test Header outside of the pump house or “IN” the pump room ? NFPA 20 (A.5.19.3.1) TEST HEAD ?? STATE of OHIO FIRE SCHOOL - BGSU 148 PRESSURE RECORDER Has the Voltage Been Checked ?? Check NFPA 70E and NFPA 25 A.4.8 WHERE DOES THE POWER COME FROM ? IS THERE ANOTHER DISCONNECT OR FUSES ??? STATE of OHIO FIRE SCHOOL - BGSU 149 Each “Fire Pump” Controller MUST have IT’S OWN Pressure Sensing Line and Pressure Recorder NFPA 20 (10.5.2.1.6) and (12.5.2.1.6) * NOTE: Main fire pump controller sensing line is connected between the pump discharge check valve and the system shut - off valve. (10.5.2.1.6) NFPA 20 (10.5.2.1.6) Pressure Recorder MISSING! NFPA 20 10.5.2.1* One sensing line Two (2) CONTROLLERS ?? One sensing line for 3 controllers ?? Pressure Recorder Each fire pump controller must have it’s own recorder !! (10.5.2.1.6) *On the pump suction, a listed OSY valve is required: no valve, other than a listed OSY valve is allowed within 50 feet of the pump suction flange NFPA 20 (5.14.5.2)* *When located in the suction pipe of a fire pump, back flow prevention devices, check valves, and pipeline strainers (for in-line pumps) shall be no closer than 10 pipe diameters from the pump suction flange. flange NFPA 20 (5.14.6.3.1) (5.26.3)* OSY Valve NOTE ROTATION ? SUCTION Counter-Clockwise LEFT Hand * Impeller Turns Toward The Suction ! Have The Wire Connections Been Checked By the Electrician and/or Controller Guy ? STATE of OHIO FIRE SCHOOL - BGSU 156 (5.14.6.4) ! Elbows and tees with a centerline plane parallel to a horizontal split-case pump shaft shall be avoided. See Figure A-2-9.6. (5.14.6.3.1) If there is a parallel elbow : YOU MUST HAVE 10 PIPE DIAMETERS of STRAIGHT PIPE BETWEEN THE ELBOW AND PUMP SUCTION FLANGE (5.14.6.3.2) STATE of OHIO FIRE SCHOOL - BGSU 157 OSY Suction Valve NOTE: Backflow Preventer! NOTE: The long straight run of suction pipe after a HORIZONTAL 90 DEGREE ELBOW ! More than 10 pipe diameters ? (5.14.6.3.2) STATE of OHIO FIRE SCHOOL - BGSU 158 OSY Valve NOTE STRAINER! NFPA 20 3-3.4 (6.3.4) 10 p i dia. pe ?? Have The Wire Connections been Checked at “BOTH” The Engine and Controller ??? Wires Correct and Terminals “TIGHT” Dual Batteries Batteries Properly Connected and Electrolyte Topped Off ?? USE CAUTION WHEN FILLING AND CONNECTING LEAD ACID BATTERIES !!! DO NOT USE FORKED CONNECTORS FM F27-92 7. Check for CERTIFICATE of CALIBRATION for test equip. “TEST GAUGES” and “CLAMP-ON VOLT/AMMETERS” should be recalibrated and certified every 12 months (by an approved testing and calibration facility)….Most never get calibrated and certified ! NFPA 20 (A.14.2.7.1) “TEST GAUGES” will have an accuracy of; 0.25% 0.5% (ASME Grade 3A) or sometimes(ASME Grade 2A) pocket “TEST GAUGES” or inspectors “TEST GAUGES”. DEMAND a “Certificate of Calibration” from an approved testing and calibration facility –then- Check and Verify the Serial Numbers! If you suspect a problem, write down the phone number of the calibration facility and phone them!! Look for “TEST GAUGE” on the dial. Calibrated “TEST GAUGES” plus CALIBRATION DOCUMENTATION as per NFPA 20 A-11-2.6.1 (A.14.2.7.1) 8. Decide in advance just what is to take place during the testing…. WHO WILL TAKE CHARGE ? What test equipment will be used ? What flow points (PITOTS) will be targeted ? Who will do what ???? TAKE THE PITOT READINGS ? ADJUST and HOLD THE TEST VALVES ? TAKE PRESSURE AND RPM READINGS ? RECORD and PLOT THE TEST RESULTS ? TAKE THE ELECTRICAL READINGS ? PRE RUN EQUIPMENT CHECK LIST ?? SOMEONE HAS TO TAKE CHARGE OF THE PUMP TEST ? Will It Be The Sprinkler Guy, The Local Fire Official, The Pump Guy, The Insurance Guy, or The Owners Rep ? SOMEONE HAS TO STEP UP TO THE PLATE !! FLOW TEST EQUIPMENT FLOW METER When a flow meter is used, you must have an air vent valve or auto air release valve to eliminate ALL air from the flow meter piping ! 10 X D 4XD STATE of OHIO FIRE SCHOOL - BGSU 170 <FM> Short Play Pipe 1 1/8 ” Nozzle 1 ¾ ” Nozzle Underwriters Play Pipe Pitot Tube FREE FLOW WITH HOSES AND PLAYPIPES STATE of OHIO FIRE SCHOOL - BGSU 172 Each additional pitot tube, used during the test, will increase the chance for error! Use 1 pitot tube and 1 gauge which has been checked prior to the start of the test! STATE of OHIO FIRE SCHOOL - BGSU 173 STATE of OHIO FIRE SCHOOL - BGSU 174 In Areas where water shortages exist, the test water can be discharged back the ! STATE of to OHIO FIREstored SCHOOL - supply BGSU 175 THERBOLIZER 6 STATE of OHIO FIRE SCHOOL - BGSU 176 Test Header arranged to SAFELY discharge directly to the Pond STATE of OHIO FIRE SCHOOL - BGSU 177 STATE of OHIO FIRE SCHOOL - BGSU 178 What Flow Points Will Be Targeted? CHURN” A“Pressure . . B “RATED 100% FLOW “ 1 Hose, Pitot of 32 PSI % FLOW “ C “2150 Hoses, Pitots of 18 PSI STATE of OHIO FIRE SCHOOL - BGSU 179 . <FM> FLOW CHART Who will observe and record the test results ?? To determine (H) (net PSI) subtract Suction PSI from Discharge PSI 150 PSI 50 PSI 100 PSI 231’ (ft) To determine FEET of HEAD multiply (H) (net PSI) X 2.31* WHO Will Take The Pitot Readings ?? Does that person know the CORRECT Procedure ?STATE of OHIO FIRE SCHOOL - BGSU 182 To Obtain a Correct Pressure Reading With A Pitot Tube, It “MUST” Be Held In The Center of The Flow Stream And It “MUST” Be Kept Perpendicular To the Flow Stream Hold The HOSE TEST VALVES After the Pitot Readings have been obtained. Will These Hose Valves Vibrate or Chatter Open ? STATE of OHIO FIRE SCHOOL - BGSU 184 NFPA 70E and OSHA 1910.333 NEC Digest - Feb. 2006 Only “QUALIFIED” persons are permitted to work on or near “LIVE” exposed parts of electrical equipment. 3. Distinguish live parts. (WHAT’S HOT, WHAT’S NOT ?) 4. Determine nominal voltage and protection required. 5. Determine the minimum required safe clearance or safe working distances. (4 feet / 12 inches ) * ARC-FLASH 12 Inches MINIMUM OSHA may cite non-compliance with 29CFR 1910.335(a)(1)(i) which requires the use of protective equipment when working where a potential electrical hazard does exist.** -OR- 29CFR 1910.132(d)(1), which requires employer assessment of workplace hazards and the use of personal protective equipment. These regulations are supported by NFPA 70E. NFPA 70E, is NOT LAW, however, it helps employers by providing education, guidance, and “how-to” for compliance. FIRE PUMP “PRE-RUN” CHECK LIST LAST CHANCE - PRIOR TO TEST CONFIRM CONFIRM CONFIRM CONFIRM CONFIRM CONFIRM CONFIRM CONFIRM CONFIRM THAT PUMP BASE IS PROPERLY GROUTED THAT ALL EQUIPMENT IS ALIGNED AND LUBRICATED THAT COUPLING GUARDS ARE INSTALLED CASE RELIEF, AIR RELEASE, COOLING WATER ALL CORRECT THAT POWER IS CORRECT and “ON” THAT WATER IS AVAILABLE and “ON” (PUMP PRIMED) THAT PUMP HAS PROPER ROTATION THAT VALVES ARE IN CORRECT POSITION FOR TESTING SAFE TEST SET UP (HOSES, PLAYPIPES, WATER DISPOSAL) CONFIRM THAT SYSTEM PRESSURE IS AT OR ABOVE EXPECTED FIRE PUMP CHURN PRESSURE (USE THE JOCKEY PUMP) -OR- IT IS PREFERABLE TO ISOLATE THE SYSTEM “CLOSE THE DISCHARGE (SYSTEM) VALVE” KEEP IT CLOSED DURING FLOW TESTING ! ** Base is not grouted!!! (6.4.1) Gear Oil Full ? Double Check It ! Motor Oil Full ? Check It ! LAST CHANCE !!! What Oil Did They Use ?? ASK !! Is The Engine Oil and Coolant Correct ? Checked By Engine Guy ?? Block Heater Working ?? 120 Degrees F (11.6.5.2) NOTE : Guard Is In Place ! NFPA 20 (5.12.7) ** NOTE : Cooling Water For Gear Connected ! Flow Visible ?? (7.5.1.6.5) ENGINE COOLING WATER ON IS THE POWER ON ?? Has the Voltage Been CONFIRMED and controller digital readout (amps/volts) compared to readings taken with a “CALIBRATED” hand held amp / volt multimeter ?? Supply “OSY” Valve OPEN, Water Available, and pump primed ?? NOTE ROTATION ? Clockwise / Right Hand Impeller Turns Toward The Suction ! ** SUCT ION This Pump Base Has Been Properly Grouted ! (6.4.1) FIRE PUMP TEST HEAD OUTSIDE ! ! Hose valves closed and hoses connected ? Playpipes secured so water can be SAFELY disposed of during flow testing ?? System Pressure at or above “EXPECTED” Fire Pump Churn Pressure -orDischarge (System) Valve CLOSED During the Flow Test ??** Outside Hose Valves Closed ?? OPEN Test Header Valve 1/2” Test Head Drain Valve Closed ?? (Bottom of Test Head Pipe ! ) TEST HEAD CONTROL VALVE OPEN FOR TEST ??? ½” TEST HEAD DRAIN VALVE CLOSED FOR TEST ! 9. Operate the pump at CHURN PSI (POINT A on CURVE) Momentarily Operate the Pump - Check for rotation, vibration, pressures, leaks, unusual sounds. Start The Pump Again: Check the pump for vibration, temperature, case relief valve operation (Electric) or cooling water flow (Diesel), bearing temp, packing leakage, pump pressures, RPM, Electrical (Controller Guy), etc. “DO NOT” stand in front of electrical panels or motor junction boxes and keep the controller doors closed during the initial starts (THINK SAFETY - 4 Foot Rule). Note the test start time… time Pump must be operated for AT LEAST ONE HOUR for “ENTIRE” acceptance test ! NFPA 20 11-2.11 ( 14.2.12 ) Packing and bearings SHOULD stay cool or warm to the touch!! (14.2.5) PACKING LEAKAGE: 1 – 2 Drops per second +/Adjust as Needed ¼ Turn ! Does the pump and motor stay COOL ? (14.2.5) Packing Drain Lines Piped to a Floor Drain !! Case Relief Valve “FULL” Stream Discharge To an Open Floor Drain ? 10. Record Churn PSI Readings, RPM, AMPS, VOLTS, Look at the factory shop test curve and plot the Churn Pressure in feet of head, head (no-flow POINT A). How close is it ???? NFPA 20 11-2.3 ( 14.2.4.2 ) NOTE: Some pumps will require a correction for (RPM) speed !!! NFPA 20 A-11-2.6.3 ( A.14.2.7.3.f ) REMEMBER THIS - TO GET FEET OF HEAD !! 1 PSI = 2.31 FEET OF HEAD -or.433 PSI = 1 FOOT OF HEAD CHURN” A“Pressure . 11. Operate the pump at additional “TARGETED” flow points : 50%, 100%, 150%, Etc. With the hose valves closed, SLOWLY open test head valve to pressurize test head (If it is not already open and pressurized). (DISCHARGE (SYSTEM) VALVE and TEST HEAD DRAIN VALVE SHOULD ALREADY BE CLOSED) Open and adjust appropriate number of hose valves to obtain each targeted flow point (PITOT). You should already know how many hose streams and what Pitot Readings will be required to obtain “EACH” Targeted Flow point!! Double check pitot readings, do not allow hose valves to vibrate open after obtaining the targeted pitot readings, and make sure that there are “NO” kinks in the hoses !!! NOTE: On High Pressure Systems (above 150 PSI) it may be desirable to Open the proper number of hose valves and regulate the pitot pressures with the Test Header Control Valve. AVERAGE the pitot readings (NO MATTER HOW CAREFUL YOU ARE, ALL OF THE PITOT READINGS WILL NOT BE THE SAME) !! 12. Record PSI, RPM, AMPS, VOLTS, (compare and plot results on the factory curve). Do the field test results duplicate the factory shop test curve for EACH flow point ??? NFPA 20 11-2.3 ( 14.2.4.2) If any results are “OFF” Double Check PITOT Readings? Correct for RPM ? ( On Small Pumps check the Case Relief Valve flow. The case relief discharge flow could be as much as 5% to 10% of the rated flow of smaller pumps !! ) If Total Head (Net PSI) PSI is STILL low, do we need to correct for velocity head? Triple Check PITOT Readings, hose valves vibrating open, gauge piping plugged, RPM low??? AS A LAST RESORT : before you pull the cover to check for rocks - retest using a backup set of calibrated “TEST GAUGES” and backup pitot tube with gauge! . . . B “RATED 100% FLOW “1 Hose, Pitot of 32 PSI C “ 150 % FLOW “ 2 Hoses, Pitots of 18 PSI STATE of OHIO FIRE SCHOOL - BGSU 208 LOW TEST RESULTS ? WHY ? Are there any kinks in the hoses?? Hose Valves Vibrating Open ? Is this guy doing his job ? Did Someone Stay Outside to Adjust and Hold The HOSE VALVES (especially ANGLE Valves) to Keep Them From Vibrating Open ? STATE of OHIO FIRE SCHOOL - BGSU 210 DOUBLE or TRIPLE Check Pitot Readings !! CONFIRM Pitot Gauge accuracy prior to testing ! STATE of OHIO FIRE SCHOOL - BGSU 211 ? Check pitot tube and gauge for fouling , which might occur during test? Half of all field test problems involve the “USE” of, or the “MIS-USE” of, Hose Monsters Each additional pitot tube, used during the test, will increase the chance for error! Use 1 pitot tube and 1 gauge which has been checked prior to the start of the test! Calibrated Test Gauges ( liquid filled gauges are NOT Test gauges )* STATE of OHIO FIRE SCHOOL - BGSU 214 Gauge connection piping must have a full flow when flushed (checked) PRIOR to flow testing of the fire pump. Check for an obstruction during testing, if test results are not correct ! STATE of OHIO FIRE SCHOOL - BGSU 215 DO NOT connect test gauges to case relief valve piping ! STATE of OHIO FIRE SCHOOL - BGSU 216 On small fire pumps the case relief valve discharge may be as much as 10% of the rated flow - if it has not shut off during the test. STATE of OHIO FIRE SCHOOL - BGSU 217 Main system relief valve must be closed for testing !** Failure to do so will result in low (POOR) test results ! STATE of OHIO FIRE SCHOOL - BGSU 218 (5.14) PIPE SIZE ? NFPA 20 (5.14.3.4) ! Elbows and tees with a centerline plane parallel to a horizontal split-case pump shaft shall be avoided. See Figure A-2-9.6. (5.14.6.3.1) If there is a parallel elbow : YOU MUST HAVE 10 PIPE DIAMETERS of STRAIGHT PIPE BETWEEN THE ELBOW AND PUMP SUCTION FLANGE (5.14.6.3.2)** STATE of OHIO FIRE SCHOOL - BGSU 219 Curve will continue to drop off as the flow increases Impeller is not centered in the case. Pump Not De-burred VTFP Best Lateral Setting Top Shaft Nut is used to raise shaft and impellers approximately 1/8 “ inch. (see instruction book) LOW PERFORMANCE MAY RESULT IF LATERAL IS NOT CORRECT ! 225 STATE of OHIO FIRE SCHOOL - BGSU Check Submergence (MEASURE) how far down (feet) the water level is from the gauge center line, at each flow point ! REMEMBER : This must be added to the reading ( TH ) on the discharge TEST GAUGE ! ADD + WL ?? STATE of OHIO FIRE SCHOOL - BGSU 226 VTFP INTAKE PROBLEMS……….. Removable screens NFPA 20 A4-2.2.2 (5.14.8.3) Intake size ??? NFPA 20 A4-2.2 (5.14.8.4) 2 ft/sec and 1 Sq. Inch per GPM at 150% Flow ? Removable screens? Check for fouling (build-up) ! OHIO FIRE SCHOOL - BGSU STATE of 229 With a vertical turbine fire pump a plugged screen will affect (lower) the water level in the sump! Check (measure) the water level in the sump during each and every flow point ! STATE of OHIO FIRE SCHOOL - BGSU 230 A plugged basket strainer on the bottom of the pump will reduce the total pump performance. Underwater Inspection of Basket Strainer STATE of OHIO FIRE SCHOOL - BGSU 232 13. * “6” AUTO starts and “6” MANUAL starts * (one “FULL LOAD” start) When an electric fire pump is provided with an automatic transfer switch, at least half of the starts should be performed while the fire pump is connected to the emergency power source (with one start under peak load). ** NFPA 20 (14.2.8) (14.2.7.4) ** When a diesel driven fire pump is provided, the starts shall be divided between both sets of batteries. NFPA 20 (14.2.8.7) NOTE: Pumps should be operated for 5 Min. for each start (This will allow the Motor and Controller time to Cool Down) 1. Controller and Driver alarms connected, tested, and demonstrated + low suction… A. Electric requires Power Available, Phase Reversal, Pump Running, and Controller Connected to Alt. Source …..… NFPA 20 (10.4.7.2) (These are “TROUBLE” TROUBLE or “SUPERVISORY” alarms) alarms B. Diesel engine is much more involved…..* Engine Trouble High temp, low oil pressure, over crank - fail to start, charger fail, battery fail, over speed, low fuel, Switch Not in Auto, and Engine Run…….NFPA 20 (12.6.7.3) (These are “TROUBLE” TROUBLE or “SUPERVISORY” alarms) alarms Pressure Recorder Installed / Operational ??? EACH Fire Pump Controller is required to be furnished with a pressure recorder. (ELECTRONIC or CHART TYPE) NFPA 20 (10.5.2.1.6 and 12.6.9.1) Main Fire Pump and Jockey Pump. Use a “TEST GAUGE” to confirm set points. NFPA 20 A-11-2.6 (A.14.2.7) Jockey “STOP” = Fire Pump churn pressure plus (+) lowest static suction pressure ! Jockey “START” = Jockey Stop PSI less (-) 10 PSI Fire Pump “START” = Jockey Start less (-) 5 –10 PSI “MANUAL” Fire Pump “STOP” = ( Must be used when Fire Pump is a sole supply pump) ! - or - (if permitted by L.A.H.J.) “AUTOMATIC” Fire Pump “STOP” = (Fire Pump churn + lowest static suction) Joc ke y P um p STATE of OHIO FIRE SCHOOL - BGSU 239 Near The Maximum R /O At P O ST to Set Jockey Pump ain Fire Pump !! M e th of re su es Pr (CHURN) Discharge - 20 PSI Less 10 at T R A ST To Set Jockey Pump Jockey Pu mp Contro l STATE of OHIO FIRE SCHOOL - BGSU 240 16. Low Suction Shut Down Panel/Device Listed, Tested AND “Alarm” Connected ? Required by some states to protect the public water supply, when it is used as the main water source. Set to lock out the fire pump at 20 PSI, after a 30 second delay - with manual re-set only (OHIO) and ALARM must be monitored (5.23). (5.23) Must be FM or UL listed for Fire Protection Equipment – not UL Industrial !! NFPA 13 15.1.8.3 Is the “EQUIPMENT” or “DEVICE” listed in the UL or FM Directory for Fire Protection Equipment ? CHECK THE BOOK ! See if you can find this low suction control listed in the UL or FM Directory for Fire Protection Equipment ??? See if you can find this low suction “DEVICE” listed in the UL or FM Directory for Fire Protection Equipment ?? Ohio EPA and Ohio Department of Health CHECK WITH “ YOUR” LAHJ ? Suction Control Valve Should be located between the pump discharge and the discharge check valve ! Sensing line for suction control valve and/or low suction shut down panel should be at least ½” (Copper, 300 Stainless, or Brass) and include provision UL/FM Suction Control Valve In the State of Ohio a UL or FM Listed low suction shut down control is required to protect a public water supply – this is in addition to any suction control valve (which may “ALSO” be required by others) . ½” Suction Pressure sensing line ! NFPA 13 - Chapter 15 15.1.8* Connection from Waterworks System. 15.1.8.1 Where connections are made from public waterworks systems, it might be necessary to guard against possible contamination of the public supply. 15.1.8.2 The requirements of the public health authority having jurisdiction shall be determined and followed. FIND OUT WHAT “ YOUR ” STATE or CITY REQUIRES !! NFPA 13 15.1.8.3 Where equipment is installed to guard against possible contamination of the public water system, such “EQUIPMENT” and “DEVICES” SHALL be listed for “FIRE PROTECTION SERVICE”. SERVICE” 17. Operators trained in required maintenance, weekly operation, testing, and record keeping ??? Did the pump rep provide a weekly check list and go over the required weekly testing, maintenance, and inspections of the pump, driver, and controller ??? NFPA 20 (14.3 ) NFPA 25 4.1 - 4.3 If not, he is not doing his job!!! Weekly Check list should include those items required by NFPA 25 Chapter 8. 8 Develop a check list of your own for both “electric” and “diesel” Fire Pumps. -OR- Make a copy of NFPA 25, Chapter 8 for the owner or his representative to use as a guide for weekly checks. “TRAIN THEM !! Review ALL Required Weekly/Annual Maintenance NOTE: Clean Grease Forced out of the Drain hole with PLUG REMOVED !! Check For Excess Grease Annual Alignment Check AFTER alignment has been re-checked (ANNUALLY) the coupling should be lubricated and reassembled. Be sure to check the set screws for tightness STATE of OHIO FIRE SCHOOL - BGSU 254 HAVE THESE FOLKS BEEN PROPERLY TRAINED? ??? This is the ONLY “WM” case relief valve – on record, that had a tight shut off with “NO” nuisance leakage - until they had to buy a new pump !! STATE of OHIO FIRE SCHOOL - BGSU 256 EMERGENCY MANUAL STARTING PROCEDURE (11.6.6) CUMMINS SET at 120 % of Rated RPM ** NOTE ! #1 COOLING WATER #2 FUEL #3 CRANK BE SURE THAT YOU KNOW WHERE THE OVERSPEED RESET IS ON EVERY TYPE OF ENGINE THAT YOU SELL !! INSTRUCT (TRAIN) THE OWNER’S REPRESENTATIVE OR OPERATOR. STATE of OHIO FIRE SCHOOL - BGSU 257 18. Review test results … ASK QUESTIONS ! Do it again if the results do not look correct ??? Did the pump rep try to rush the testing???? Did the pump rep get nervous or defensive when you questioned any of the results or test procedures??? Were the PUMP test results at or above the factory shop test curve and within ½ % ( the minimum accuracy of a CALIBRATED TEST GAUGE ) ??? NFPA 20 (14.2.4.2) Did the pump run for one hour (all testing)??? NFPA 20 (14.2.12) 19. STOP ! Don’t accept it if the pump test results do not duplicate the shop test curve or the system is not CORRECT ! L.A.H.J. ( INSPECTOR ) : YOUR NAME and REPUTATION goes on the bottom line: Approved and Accepted By: NAME : …………………………………………. FIRE PUMP “Annual” FLOW TEST 1. Check for company and individual LICENSING. 2. Check for HYDRO and FLUSH CERTIFICATES (if work has been done). 3. Look system over…housekeeping, sensing lines, leaks, piping , etc. 4. Record all pump, driver, and controller data. (HP, VOLTAGE, etc.) 5. Has the pump been properly Maintained and ALIGNED ANNUALY??? (CHECK) 6. Review Records of weekly testing and maintenance that was performed. 7. Check for CERTIFICATE of CALIBRATION for ALL flow test equip. (SAFE??) 8. Decide in advance just what is to take place during the flow test. 9. Operate the pump at Churn (no flow)….temp., brgs., packing, relief, etc. 10. Record Churn Test Results (compare with test results from previous year). 11. Operate the pump at additional flow points 100%, 150%,. 12. Record Test Results , compare with previous year ( within 5 % nameplate?). 13. 1 AUTO Start and 2 MANUAL Starts (One Full Load Start) 14. Controller and Driver alarms TESTED (electric and diesel) (CHECK) 15. Confirm Start and Stop PSI for Main Fire Pump and Jockey Pump. 16. Low Suction Control Operation, Set Point, Time Delay, AND Alarm TESTED ? 17. Review ALL results - ASK QUESTIONS!! - ANY CONCERNS?? - Do it again ? 18. STOP ! INVESTIGATE ! If the PUMP is more than 5 % below nameplate !