Open Phase Condition in Transformers Transformers

advertisement
26/5/2018
Open Phase Condition in Transformers | Transformers
GENERALPAC.COM (/)

Making power systems intuitive
Open Phase Condition in Transformers
In the paper written by Amir Norouzi, titled "Open Phase Conditions in Transformes Analysis and
Protection Algorithms," the reaction of three phase transformers is discussed when one of the
three phases on the HV side becomes open. When this occurs, the voltages and currents greatly
depends on the winding connection and the core construction of the transformer.
Aurthor of Paper: Amir Norouzi
Representing Company: GE Digital Energy
Download Paper (PDF) (http://cloud.generalpac.com/article-content/Open-Phase-Condition-InTransformer-Analysis/doc-paper.pdf)
https://generalpac.com/transformers/open-phase-condition-in-transformers
1/15
26/5/2018
Open Phase Condition in Transformers | Transformers
 BACK
(/index.php?option=com_content&view=article&id=327&Itemid=721)
 Open Phase Condition in Transformers (/transformers/open-phase-conditionin-transformers)
 Difference Between Core Form and Shell Form Power Transformers
(/transformers/difference-between-core-form-and-shell-form-power-transformers)
Powered by
Publish for Free
Summary: Amir Norouzi writes about the behavior of three phase transformers when one of the
phases is lost. This condition is commonly called a "single phasing". Upon a single phasing
condition, Amir describes how voltages and currents (on both the HV side and LV side) greatly
depends on the transformer winding connection (delta, wye, wye-grounded etc) as well as the
transformer's core construction. Single phasing condition is very difficult to detect by relays where
the CTs are monitoring current on the LV side of the transformer. Amir then presents algorithms
that identify and detect open phase conditions.
https://generalpac.com/transformers/open-phase-condition-in-transformers
2/15
26/5/2018
Open Phase Condition in Transformers | Transformers
An open phase condition occurs frequent in the power system especially in medium voltage (33kV
or below) applications. They also occur in rural or remote areas where the chances of broken
conductors, loose connections, and blown fuses are high.
For example, if a 12.5kV to 4.16kV three phase transformer was connected Wye-grounded Wye-grounded, if only the A phase fuse operated open on the HV side similar to Figure 6 below,
this would be considered as a Phase Open or a Single Phasing condition.
This condition is very difficult detect by protective relays. Given the transformer winding
connection and transformer connection type, the voltages and currents may be fairly
balanced especially in low-loading conditions. In fact, the ground overcurrent or negativesequence overcurrent protection may not even detect the Open Phase condition due to the
symmetry and balance of voltages and currents. This condition may even go unnoticed for a
period of time. Open Phase conditions greatly depend on the transformer winding
configuration, the transformer core construction, and the transformer loading.
https://generalpac.com/transformers/open-phase-condition-in-transformers
3/15
26/5/2018
Open Phase Condition in Transformers | Transformers
Section II: Three Phase Transformer Construction
Types
In Section II-A of the paper, Amir briefly describes the transformer construction types in an effort to
provide foresight - that transformer constructions actually make a difference in an Open Phase
condition.
The Three-Leg Core Type Transformer is shown in Figure 1 below. This three phase transformer
can have a Delta connected primary or a Wye connected primary. Similarly, there are also Fourleg and a Five-leg Core Type transformers construction available by manufacturers. All three
construction types provide their own respective advantages. But they also have their own
disadvantages.
Advantages of Three-Leg Core Type Transformer
Makes high voltage insulation easier
Less Leakage Flux
Disadvantages of Three-Leg Core Type Transformer
https://generalpac.com/transformers/open-phase-condition-in-transformers
4/15
26/5/2018
Open Phase Condition in Transformers | Transformers
No return path for zero sequence flux.
Zero sequence flux travels through the air gap or tank which has a much higher
magnetic reluctance than the core.
Due to the high magnetic reluctance of zero sequence flux, the three-leg core type
require much higher amount of zero sequence magnetizing current which lead to
saturation and excessive heating. This issue is addressed with Four-leg and Five-leg
contractions.
The Four-Leg and Five-Leg Core Type have similar performances compared to Three-Leg
Core when it comes to the zero sequence flux. Both types provides a low reluctance path for
zero sequence flux (through the core instead). As a result, we get low zero sequence
magnetizing current and large magnetizing reactance.
https://generalpac.com/transformers/open-phase-condition-in-transformers
5/15
26/5/2018
Open Phase Condition in Transformers | Transformers
The Four-Leg and Five-Leg Core Type have similar performances compared to Three-Leg
Core when it comes to the zero sequence flux. Both types provides a low reluctance path for
zero sequence flux (through the core instead). As a result, we get low zero sequence
magnetizing current and large magnetizing reactance.
https://generalpac.com/transformers/open-phase-condition-in-transformers
6/15
26/5/2018
Open Phase Condition in Transformers | Transformers
The Five-Leg Core helps reduce the size of the yoke as it will carry less zero sequence flux
resulting in a smaller transformer size.
Advantages of a Shell Type Transformer
Provides a return path for zero sequence flux which means the path has a very small
magnetic reluctance (because the flux travels through the core) as opposed to a ThreeLeg core type transformer.
Due to a small magnetic reluctance, it requires smaller amount of zero sequence
magnetizing current which lead to less saturation and less heating.
Section III: Analysis of Open Phase Condition
https://generalpac.com/transformers/open-phase-condition-in-transformers
7/15
26/5/2018
Open Phase Condition in Transformers | Transformers
In this section, Amir analyzes voltages and currents for three phase transformers given that one of
three phases is open, or in other words, we have an Open Phase or Single Phasing condition. To
analyze this condition, the following assumptions must be stated clearly:
1. Open phase condition or loss of a phase refers to one phase of three phases being
physically and unintentionally disconnected on the primary side of the transformer. This could
occur for several reasons such as a loose cable, a broken conductor, a blown fuse, a circuit
breaker with one defective contact, etc.
2. Primary and high side (and HV) terms are used interchangeably
3. Secondary and low side (and LV) terms are used interchangeably
4. Open phase is assumed to have occurred on the primary side of a transformer.
5. There are no current transformers (CT) or protection voltage transformers (PT) on the high
voltage terminals of the transformers being discussed.
Section III-A: HV side investigation
In this section, Amir describes voltages and currents from the HV prospective given an open
phase condition with the assumptions described above. Since we are only looking at the HV side
of the transformer, the LV winding connection is irrelevant. Or in other words, it doesn't matter if
the LV winding connection is a Delta, Wye, or Wye-grounded connection. The analysis in Section
III-A is independent of the LV winding.
It is to be noted that a HV Wye-grounded transformer connection has different voltage and current
characteristics compared to the HV Wye-ungrounded or a HV Delta connection during an open
phase condition. This is a very important distinction to make and keep in mind as we go through
the analysis.
Section III-A-1: HV (primary) Wye-grounded
connection
If the HV side of the transformer (primary side) was connected Wye-grounded similar to Figure 6
and we had a 3-Leg Core Type transformer connection, the primary winding with the lost phase
will have an induced voltage equal to the voltage before the open phase condition.
This basically means that if we look at the voltage alone across the transformer windings before
and after the phase was lost, it will be the same. We should expect no difference in voltage on the
HV side for a loss of phase given the conditions above. This is counter-intuitive however, it has to
https://generalpac.com/transformers/open-phase-condition-in-transformers
8/15
26/5/2018
Open Phase Condition in Transformers | Transformers
do with the summation of fluxes for three-leg core type transformer that Amir eloquently described
in Section III-A-1 (page 4).
To summarize this point clearly: we should have expect no discernable difference in
voltage across the HV winding for an open-phase condition (as opposed to balanced
conditions) given the following scenario
Utility grid is supplying strong three-phase balanced voltages prior to open-phase
condition
Transformer HV winding connection is Wye-grounded.
The LV winding connection doesn't matter
Transformer is a 3-Leg Core Construction Type
Since the HV winding still develops voltage across the winding even though the phase
was lost, the corresponding LV winding will also develop voltage across it, and the LV
phase/line currents will be relatively balanced - as if the phase was never lost. From the
load's prospective, it sees no difference between Open Phase vs balanced conditions.
Remember, this is only for HV transformer connected Wye-grounded and the
construction is a 3-Leg Core Type.
For other construction-types such as a 4-leg, 5-leg core type or a shell construction type, (given a
Wye-grounded primary) if we have an open phase condition, we will have very little voltage
developed across the winding for which the phase was lost. For example, if phase A fuse was
blown as shown in Figure 6, we will have very little voltage across winding A on the HV side which
results into very little voltage across winding a on the LV side.
To summarize this point clearly: we should expect very little (or even zero) voltage develop
across the winding for which the phase was lost given the following scenario
Utility grid is supplying strong three-phase balanced voltages prior to open-phase
condition
Transformer HV winding connection is Wye-grounded
The LV winding connection doesn't matter
Transformer is a 4-Leg Core Type, or 5-Leg Core Type, or Shell Type construction
Since HV winding will not develop very much voltage across the winding for which the
phase was lost, the corresponding LV winding will not develop very much voltage
across it. So from the load's prospective, it receives abnormal voltages and currents
https://generalpac.com/transformers/open-phase-condition-in-transformers
9/15
26/5/2018
Open Phase Condition in Transformers | Transformers
from two phases but very little (or even zero) from the phase that was lost on the HV
side.
Section III-A-2: HV (primary) Wye-ungrounded or
Delta Connection
In this section, Amir goes through the same exact scenario but this time, he discusses what would
happen to the voltage across the transformer winding if we had an ungrounded primary
connection. An ungrounded primary connection means that we have either a delta connection or
an ungrounded Wye connection.
https://generalpac.com/transformers/open-phase-condition-in-transformers
10/15
26/5/2018
Open Phase Condition in Transformers | Transformers
Amir describes Figure 7 as a DAB or a D1 transformer connection. However, this illustration
appears to be a DAC or a D11 connection. This is easily verified by looking at the polarity of
the transformer winding. Figure 7 clearly indicates that the polarity side of winding A is
connected to the non-polarity side of winding C -- suggesting a DAC connection.
For a D11 transformer connection similar to Figure 7, we should expect the voltage developed
across winding B to be not affected by the blown fuse on line A. Therefore winding B voltage is
healthy and we should expect it to equal VBC.
We should expect the voltage to develop across winding A and winding C to equal one half of
VBC voltage. It's half because VBC is the voltage that's measured across winding A and winding
C in series. Because they are in series in an open phase condition, it's very similar to a voltage
divider type of problem. If we assume the impedance of all three windings are exactly the same,
then the voltage developed across both winding A and winding C will be exactly one half of the
source voltage. The negative sign comes into play as a result of how we've decided to measure
the voltage across winding A and winding C.
So to recap, we will get the following voltage if:
VωB = VBC
1
VωA = VωC = −
2
1
VBC =
2
VBC ∠180°
1. The fuse in line A operates open and creates an open phase or single phasing condition
2. We have a DAC or a D11 transformer connection
3. Our system has an ABC phase sequence
4. This is irrespective of the transformer construction type. It doesn't matter if we have a 3-Leg,
4-leg, 5-leg Core Type construction transformer. Or if we have a Shell Type construction
transformer.
5. Since the HV delta connection is an ungrounded-primary, one of the windings will see the full
system voltage provided by the utility grid. However, the other two windings will only develop
half of the system voltage. Therefore only half of the voltage will be developed across two
windings on the LV side. From the loads prospective, they will receive unbalance set of
voltages and currents. One winding to be full but the other two will be half.
https://generalpac.com/transformers/open-phase-condition-in-transformers
11/15
26/5/2018
Open Phase Condition in Transformers | Transformers
For a HV Wye-ungrounded connection, the process is very similar to the delta connection.
However, the following voltages are developed across the Wye-ungrounded windings.
VωA = 0
1
VωB =
2
VBC
1
VωB = −
ILine,
ILine,
https://generalpac.com/transformers/open-phase-condition-in-transformers
B
A
2
VBC
= 0
= −ILine,
C
12/15
26/5/2018
Open Phase Condition in Transformers | Transformers
It makes sense to for winding A to be zero because we have a Wye connected transformer.
Winding B and Winding C will have one-half of the VBC voltage. Again, the process is very similar
to a voltage divider. We get a negative sign in front of winding C because of how we've decided to
measure the voltages. And Line current A is equal to zero which makes sense. Line current C is
going to equal the magnitude of line current B however, the sign will be opposite. So they both will
have same magnitude but will flow in the opposite direction.
A few points to summarize for the HV Wye-ungrounded connection:
1. The fuse in line A operates open and creates an open phase or single phasing
condition
2. We have a Wye-ungrounded connection
3. Our system has an ABC phase sequence
4. This is irrespective of the transformer construction type. It doesn't matter if we have a 3Leg, 4-leg, 5-leg Core Type construction transformer. Or if we have a Shell Type
construction transformer.
5. Since the HV connection is an ungrounded-primary (we have a Wye-ungrounded
connection), one of the windings will see the no voltage developed at all. However, the
other two will develop only half of the system line-to-line voltage. Therefore only half of
the voltage will be developed across two windings on the LV side. And one winding will
have no voltage at all. From the loads prospective, they will receive half of the voltages
from two windings of the transformer. The currents through those windings will be equal
magnitude but in opposite direction. And no voltage and no current from the third
winding at all. So the voltages and currents overall will be highly unbalanced.
In a very similar manor, Amir goes through the scenario of an open phase condition for a Wyegrounded - Delta transformer connection as shown in Figure 9. As well as a Delta - Wye-grounded
transformer connection shown in Figure 14.
https://generalpac.com/transformers/open-phase-condition-in-transformers
13/15
26/5/2018
Open Phase Condition in Transformers | Transformers
 Prev (/transformers/introduction-to-the-wye-wye-transformer-part-4)
https://generalpac.com/transformers/open-phase-condition-in-transformers
14/15
26/5/2018
Open Phase Condition in Transformers | Transformers
Table of Content

 Open Phase Condition in Transformers
 Section II: Transformer Construction Types
 Section III: Analysis of Open Phase Condition
 Reference(s)
GeneralPAC.com
https://generalpac.com/transformers/open-phase-condition-in-transformers
15/15