0.375∠78 Ω =7.7479∠78 pu (1100 V)2⁄ 25 kVA EE 506 - Power System Analysis & Design Solution Manual ZHV(pu) = Problem No. 01 Base Voltage = 1.1 kV. Base KVA = 106. What is base impedance? ZHV(pu) =7.7479 ∠78 pu Solution: (1.1 kV)2 ZBase = 6 10 kVA ZBase = 1.21 mΩ Problem No. 02 If the resistance in ohms is 5 Ω, find the per unit value. Given base kVA = 10 and base kV = 11. Solution: (11 kV)2 ZBase = 6 = 12.1 kΩ 10 kVA 5Ω Rpu = 12.1 kΩ Rpu = 413. 223 pu Problem No. 03 A single phase two – winding transformer is rated 25 kVA, 1100/440 volts, 50 Hz. The equivalent leakage impedance of the transformer referred to the low voltage side is 0.06 ∠78° Ω. Using transformer rating as base values, determine the per – unit leakage impedance referred to low voltage winding and referred to high voltage winding. Solution: ZLV(pu) = 0.06 ∠78 Ω =7.7479∠78 pu (440 V)2⁄ 25 kVA ZLV(pu) =7.7479∠78 pu 1100 2 ZHV = (0.06 ∠78 Ω) ( ) = 0.375∠78 Ω 440 Problem No. 04 A single-phase transformer is rated at 2.5 kVA, 11/0.4 kV. If the leakage reactance is 0.96 Ω when referred to low – voltage side, then determine its leakage reactance in per unit. Solution: Zpu = 0.96 Ω (0.4 kV)2⁄ 2.5 kVA Zpu = 0.015 pu Problem No. 05 For a 110/440 V, 25 kVA, single – phase transformer, primary and secondary leakage reactances are 0.04 Ω and 0.10 Ω respectively. Show that net pu leakage reactance of the transformer referred to LV side is same as referred to HV side. Solution: 440 V 2 Zeq(HV) = 0.10 Ω+0.04 Ω ( ) = 0.74 Ω 110 V 0.74 Ω Zeq(HV) = (440 V)2⁄ pu 25 kVA Zeq(HV) = 0.0956 pu pu 110 2 Zeq(LV) = 0.04 Ω + 0.10 Ω ( ) = 0.04625 Ω 440 0.04625 Ω Zeq(LV) = pu (110)2⁄ 25 kVA Zeq(LV) = 0.0956 pu pu Problem No. 06 An 11/0.4 kV, 200 kVA transformer has an equivalent impedance of 2.4+j12.4 Ω referred to HV side. Determine the base values for the pu system, the per unit equivalent impedance and the equivalent impedance rop at one – half rated current. Solution: SBase = 200 kVA VBase = 11 kV (11 kV)2 ZBase(HV) = 200 kVA ZBase(HV) = 605 Ω (0.4 kV)2 ZBase(LV) = 200 kVA ZBase(LV) = 0.8 Ω IBase(HV) = 200 kVA 11 kV IBase(HV) = 18.1818 A IBase(LV) = 200 kVA 0.4 kV IBase(LV) = 500 A ZHV(pu) = 2.4+j12.4 ZBase(HV) ZHV(pu) = 0.0209∠79.0459 pu @ Half Load ZHVpu = 2.4+j12.4 1210.0012 ZHVpu =0.0104 ∠79.0459 pu Problem No. 07 Determine the per unit impedance of a transmission line having an impedance of 30 + j110 Ω on 100 MVA and 132 kV base voltage. Solution: Zpu = 30+j110 (132 kV)2⁄ 100 MVA Zpu = 0.6544∠74.7449 pu Problem No. 08 A 30 MVA, 11 kV generator has a reactance of 0.2 pu referred to its ratings as bases. Determine the per unit reactance when referred to base KVA of 50000 kVA and base kV of 33 kV. Solution: SNew VOld 2 XNew = XOld ( )( ) SOld VNew 50 MVA 11 kV 2 Xg(New) =0.2 ( )( ) 30 MVA 33 kV Xg(New) =0.0370 pu Problem No. 09 The transformation ratio of the step – up transformer is 11/220 kV. The base MVA = 100 and base kV = 11 on the generator side. What is the base kV on the transmission side? 1 IBaseHV =18.1818 A ( ) 2 Solution: IBaseHV =9.0909 A VBaseTL =11 kV ( ZBaseHV = 11 kV =1210.0012 Ω 9.0909 A ZActual = Zpu (1210.0012 Ω) ZActual =25.2890∠79.0459 Ω VBaseTL =220 kV 220 kV ) 11 kV Problem No. 10 Three generators are rated as follows: Generator 1: 100 MVA, 33 kV, reactance = 10% Generator 2: 150 MVA, 32 kV, reactance = 8% Generator 3: 110 MVA, 30 kV, reactance = 12% Choosing 200 MVA and 35 kV as base quantities, compute per unit reactances of the three generators referred to these base quantities. Draw reactance diagram and mark per unit reactances. The three generators are connected to common bus – bars. Problem No. 11 Figure 17 shows single line diagram of a single – phase circuit. Using the base values of 3 kVA and 230 V, draw the per – unit circuit diagram and determine the per – unit impedances and per – unit source voltage. Also, calculate the load current both in per unit and in Amperes. Solution: Reactance Diagram Solution: Per- Unit Diagram Xg1 XT1 Xg3 Xg2 XL XT2 Xg Vg1 Ipu Vg3 Vg2 Vg SBase = 20 MVA VBase = 35 kV Vg1 = 33⁄35 = 0.9429 pu Vg2 = 32⁄35 = 0.9143 pu Vg3 = 30⁄35 = 0.8571 pu 10 200 33 2 Xg1 = ( ) ( ) ( ) 100 100 35 @Section 1 SBase = 3 kVA VBase1 = 230 V Vg = 220 V⁄230 V 8 200 32 2 Xg2 = ( ) ( ) ( ) 100 150 35 Vg = 0.9565 pu Xg = 0 pu 3 kVA 230 V 2 XT1 =0.1 ( )( ) 3 kVA 230 V Xg2 = 0.0892 pu XT1 =0.1 pu Xg1 = 0.1778 pu Xg3 = ( 2 12 200 30 )( )( ) 100 110 35 Xg1 = 0.1603 pu @Section 2 433 V VBase2 =230 V ( ) = 433 V 230 V Zload XT1 = 0.1 ( 3 kVA 433 V )( ) =0.1 pu 3 kVA 433 V 20% reactance each. Draw the per – unit circuit diagram. (433)2 ZBase2 = =62.4963 Ω 3 kVA XL = 3⁄Z Base2 XL = 0.0480 pu 2 XT2 =0.1 ( 3 kVA 440 V )( ) 2 kVA 433 V Solution: Per-Unit Diagram @Section 3 120 V VBase3 = 433 V ( ) = 118.0909 V 440 V 2 3 kVA 120 V XT2 = 0.1 ( )( ) = 0.1549 pu 2 kVA 118.0909 V XL XT1 XT2 = 0.1549 pu Xm1 Xm2 Xm3 Xg M Vg @Region 1 SBase = 110 MVA VBase1 = 33 kV Vg = 33 kV⁄33 kV ZLoad = 0.1838∠20.5560 pu Vg = 1 pu By Ohm’s Law: Ipu = 2.3574∠-64.9029 pu 3 kVA ILoad = (Ipu )(IBase3 ) = (Ipu ) ( ) √3 (118.0909) ILoad = 14.6675 ∠ -64.9029 A Problem No. 12 A 100 MVA, 33 kV, three phase generator has a reactance of 15%. The generator is connected to the motors through a transmission line and transformers as shown. Motors have rated inputs of 40 MVA, 30 MVA and 20 MVA at 30 kV with M M Vm1 Vm2 Vm3 (118.0909 V)2 ZBase3 = = 4.6485 Ω 3 kVA 0.8+j0.3 ZLoad = ZBase3 0.9565 Ipu = 0+j0.1+j0.048+j0.1549+0.1838∠20.5560 XT2 Xg = 0.15 ( 110 MVA 33 kV 2 )( ) 100 MVA 33 kV Xg = 0.1650 pu 110 MVA 32 kV 2 XT1 = 0.08 ( )( ) 110 MVA 33 kV XT1 = 0.0752 pu @Region 2 110 kV VBase2 =33 kV ( ) =113.4375 kV 32 kV ZBase2 = (113.4375 kV)2 =116.9824 Ω 110 MVA XL = 60 Solution: ZBase2 15 MVA 66 kV XL = 0.5129 pu Zp 2 110 MVA 110 kV XT2 =0.08 ( )( ) 110 MVA 113.4375 kV XT2 = 0.0752 Zp = 110 MVA 30 kV 2 Xm1 =0.2 ( )( ) 40 MVA 33 kV Xm1 = 0.4545 pu ZP = j0.0873 pu Zp = 2 110 MVA 30 kV Xm3 =0.2 ( )( ) 20 MVA 33 kV Xm3 = 0.9091 pu Problem No. 13 The three – phase ratings of a three – winding transformer are: Primary – Y – connected, 66 kV, 15 MVA Secondary – Y – connected, 13.2 kV, 10 MVA Tertiary – Δ – connected, 2.3 kV, 5 MVA Neglecting resistances, the leakage impedances are: ZPS = 0.08 pu on 15 MVA, 66 kV base ZPT = 0.10 pu on 15 MVA, 66 kV base ZST = 0.09 pu on 10 MVA, 13.2 kV base Find the per unit impedances of the star – connected equivalent circuit for a base of 15 MVA, 66 kV base in the primary circuit. ZS = 5 MVA 2.3 kV Zt ZPS + ZPT - ZST 2 @Region 3 VBase3 = VBase2 = 33 kV 30kV Vm1 = Vm2 = Vm3 = 33kV Vm1 = Vm2 = Vm3 = 0.9091 pu 110 MVA 30 kV 2 Xm2 =0.2 ( )( ) 30 MVA 33 kV Xm2 = 0.6061 pu Zs 10 MVA 13.2 kV 15 13.2 2 0.08+0.01- [0.09 ( ) ( )] 10 66 2 ZST + ZSP - ZPT 2 2 ZS = 2 10 66 10 66 0.09+ [0.08 ( ) ( ) ] - [0.1 ( ) ( )] 15 13.2 15 13.2 2 ZS = - j0.1217 pu ZT = ZTS + ZTP - ZPS 2 5 66 2 5 13.2 2 [0.10 ( ) ( ) ] + [0.09 ( ) ( ) ]− 15 2.3 10 2.3 2 Zp = 5 66 [0.08 ( ) ( ) ] 15 2.3 2 ZP = j3.4839 pu Problem No. 14 Draw the per – unit impedance diagram of the system shown in Figure 19. Assumed base values are 100 MVA and 100 kV. G1: 50 MVA, 12.2 kV, Xg1 = 0.10 pu G2: 20 MVA, 13.8 kV, Xg2 = 0.10 pu T1: 80 MVA, 12.2/132 kV, XT1 = 0.10 pu T2: 40 MVA, 13.8/132 kV, XT2 = 0.10 pu Load: 50 MVA, 0.8 pf lagging operating at 124 kV. Problem No. 17 Figure 22 shows single – line diagram of a power system. Solution: Problem No. 15 Figure 20 shows a sample power system network. Find the current supplied by the generator, the transmission line current, the load current, the load voltage and the power consumed by the load. Solution: Problem No. 16 The single line diagram of a three – phase system is shown in Figure 21. Select a common base of 100 MVA and 13.8 kV on the generator side. Draw per – unit impedance diagram. G: 90 MVA, 13.8 kV, Xg = 18% T1: 50 MVA, 13.8/220 kV, XT1 = 10% T2: 50 MVA, 220/11 kV, XT2 = 10% T3: 50 MVA, 13.8/132 kV, XT3 = 10% T4: 50 MVA, 132/11 kV, XT4 = 10% M: 80 MVA, 10.45 kV, Xm = 20% Load: 57 MVA, 0.8 pf (lagging) at 10.45 kV. Xline1 = 50 Ω Xline2 = 70 Ω Solution: The ratings of the generators and transformers are given below: G1: 25 MVA, 6.6 kV, Xg1 = 0.2 pu G2: 15 MVA, 6.6 kV, Xg2 = 0.15 pu G3: 30 MVA, 13.2 kV, Xg3 = 0.15 pu T1: 30 MVA, 6.6 ∆ - 115 Y kV, XT1 = 0.1 pu T2: 15 MVA, 6.6 ∆ - 115 Y kV, XT2 = 0.1 pu T3: 1 – phase unit each rated 10 MVA, 6.9/69 kV, XT3 = 0.1 pu Draw the per – unit circuit diagram using base values of 30 MVA and 6.6 kV in the circuit of generator 1 Solution: