HAZARDOUS AREA MOTOR/DRIVE PROTECTION PRINCIPLES AND OPTIMUM SELECTION CRITERIA Copyright Material PCIC Europe Paper No. PCIC Middle East ME17-4 Dip.-Ing Hugo Stadler Eur Ing Steve Jackson MA BSc CEng Siemens Germany Siemens UK Abstract - This paper will provide an overview of hazardous area classifications including the implications of the latest IEC standards and the LV/HV motor & drive protection principles of ‘nonsparking’, ‘increased safety’, ‘flame proof’ and ‘pressurised’. The relative advantages for each technique will then be discussed for different scenarios such as atmosphere, overload, starting, inverter operation, size, weight, flexibility and cost. Three components are required to make a hazardous situation: - flammable material, oxygen and an ignition source. B. Definition of Zones Zone 0 - 1 - 2: Gas & Vapors Zone 20 - 21 - 22: Dust N America Div 1 Class I ~ Gas Zone 1 Div 2 Class I ~ Gas Zone 2 Index Terms – Hazardous Area, Protection, Motors, Increased Safety, Flame Proof, Non-Sparking, Purge. Occurrence: rare, short time ( <10h/a) I. INTRODUCTION This paper will cover hazardous area basics, a description and comparison of motor Ex protection types followed by advice on matching drives to Ex motors and a cost evaluation. II. HAZARDOUS DRIVES AREA MOTORS Occurrence: occasional (10h/a < 1000h/a) Occurrence: permanent, long term (>1000h/a) Fig 2 Hazardous Area Zones Zones are defined on the probability of a hazard occurring in that area. Zone 0 which has a permanent threat of an occurrence is generally not suitable for any sort of electrical machine. & Ignition source A. Ex-protection in Electrical Apparatus C. Precautions Risk minimization – basic principles according to EN 1127-1.Protection measures have to be undertaken in the following sequence: Primary Ex-protection Prevent hazardous atmospheres Limit concentration of flammable material Inertization (add Nitrogen, Carbon Dioxide) EXPLOSION Secondary Ex-protection Avoid every potential ignition source Tertiary Ex-protection Limit the consequences of an explosion to a harmless degree. Explosive atmosphere: gas, vapor, fog, dust and air in Correct dispersion and concentration Protection methods for electrical machines are part of the secondary precaution to avoid every potential ignition source. Fig 1 Conditions for Explosion 1 D. Classification of Electrical Equipment Directive 94/9/EC Equipment Equipment group category EN 60079-0 EPL Types of protection Equipment Equipment Examples group Protection Level Ex ia M2 Ex d, Ex e Ma Z0 ~ 1G Ex ia Z1 ~ 2G Ex d, Ex e, Ex px Gb high Z2 ~ 3G Ex nA, Ex pz Gc increased Z20 ~ 1D Ex ia, Ex ta Da very high Z21 ~ 2D Ex tb, pD, mD Z22 ~ 3D Ex tc, pD, mD I II III Gas groups: IIA - Methane, ammonia, ethyl alcohol, etc. IIB - Town gas, ethylene, hydrogen sulfide, etc. IIC - Hydrogen, acetylene, etc. Ingression protection to IP55 - dust protected and water jets is standard for all types of Ex motors which is equivalent to NEMA 3. IP56 - dust protected and heavy seas are also common. Dust tight IP65 is required for IIIC conductive dust and is possible for roller bearing HV motors. Level of protection M1 I II IIB gas group and T3 (200°C) temperature class motors are by far the most common. very high Mb high Ga very high Db high Dc increased F. Protection Classes Electrical machines Dust groups: (IP55) IIIA - Combustible flyings IIIB - Non-conductive dust IIIC - Conductive dust (IP65) Monitoring devices Intrinsic safety (ia, ib) Flameproof enclosure (d) > (db) Pressurized apparatus (p) Encapsulation (m) Fig 3 Electrical Equipment Classification Increased safety (e) >(eb) In the Equipment Category designations M means Mines, G means Gases and D means Dust. This paper will only focus on the G Gases category. Non sparking(nA)>(ec) Regulation 94/9/EG ATEX, European Norms, IEC- Norms Fig 5 Classes of Protection Electrical machines use different protection methods than monitoring devices. However motors may have installed monitoring devices that require separate protection. Classification of Gases and Vapours Gas Groups IIA (US Group D) IIB (US Group C) IIC (US Group A) Ammonia, methane, ethane Town gas, acrylonitrile Hydrogen Ethyl alcohol, n-butane Benzene, n-hexane Acetaldehyde Ignition temperature G. Non Sparking “nA” in future “ec” Permissible temperature class > 450°C T1 Max. 450°C Ethylene, ethylene Ethyne oxide (acetylene) > 300°C … ≤ 450°C T2 Max. 300°C Hydrogen sulfide > 200°C … ≤ 300°C T3 Max. 200°C > 135°C … ≤ 200°C T4 Max. 135°C > 100°C … ≤ 135°C T5 Max. 100°C > 85°C … ≤ 100°C T6 Max. 85°C Ethyl ether Carbon disulfide Powder filling (q) Construction standards In approximate terms the Explosion Protection Levels (EPL) Ga, Gb, Gc correspond to the Equipment Categories 1G, 2G and 3G which align with the Zones 0, 1 and 2. The latest IEC standards mean that nA (non sparking) will become ec (for EPL increased zone 2); e (increased safety) will become eb (for EPL high - zone 1) and d (flameproof) will become db (for EPL high – zone 1). This terminology is mandatory from 2018. E. Oil immersion (o) Combustibility increases (maximum experimental safe gap, minimum ignition energy becomes smaller) Ex-protection Construction standards Non Sparking EN 60079-0 60079-15 “nA“ (EN 50014 EN 50021) Basic principle Arcs and sparks are prevented during normal operation. Maximum surface temperature does not exceed the limits of temperature class. “nA” will considered as “ec” in the future EN 60079-7 Installation Equipment protection level Zone 2 Gc Fig 6 Non Sparking Motor Fig 4 Gases and Vapours Classification According to EN 60079-15 this is an explosion protection type in which the risk of ignition sources occurring during normal operation is minimised by utilising additional methods which can be: Hydrogen is a very combustible gas but has a high ignition temp. The higher the gas combustibility the lower the Minimum Ignition Energy (MIE) and the lower the Minimum Ignition Current (MIC) for intrinsic safety circuits; and the smaller the Maximum Experimental Safe Gap (MESG) for Ex d machines. The higher the ignition temperature; the higher the allowable surface temperature; and the lower the permissible temperature class. nA – non-sparking nC – enclosed break nL – limited energy nR – restricted breathing 2 nA is the most appropriate method of protection for electrical machines. In future nA (non sparking) will become ec for Equipment Protection Level (EPL) increased - zone 2. That is Ex n motors can only be used in zone 2. A flameproof motor must fulfil three prime requirements. Firstly the design must limit the outside surface temperature not to exceed the permitted temperature class. Secondly the explosion resistance must ensure that an explosion cannot spread to the external surroundings. Lastly the pressure resistance prevents any lasting damage or deformation to the protection of the motor following explosions within the enclosure. A rotor design ignition risk assessment is required for Ex n motors >100kw and other than S1 or S2 operating modes. A stator winding ignition risk assessment is required for motors >1kV and other than S1 or S2 operating modes. (EN 60079-15) Basic principle Ex d motors typically can handle up to a T4 temperature class and with special designs even T5 and T6 can be achieved. In future d (flameproof) will become db for EPL high – zone 1. Equipment is designed to prevent hazardous temperatures, sparks and arcs during normal operation. Ignition during breakdown is prevented by additional mechanical, electrical and thermic safety measures. An Ex d motor may have withstood many internal explosions during its’ lifetime without affecting operation. H. Increased Safety “e” in future “eb” Ex-protection Construction standards Increased safety EN 60079-0 60079-7 “e“ (EN 50014 EN 50019) Installation Equipment protection level Zone 1 Gb Zone 2 Gc J. Ex-protection Pressurised “px“ “py“ “pz“ Pressurized Apparatus “p” Construction standards EN 60079-0 60079-2 (EN 50014 EN 50016) Basic principle All parts capable of igniting flammable gases are placed inside an enclosure, pressurized by a protective gas (min. 0.5bar). The surrounding atmosphere cannot enter during operation. Fig 7 Increased Safety Motor Installation Ex e motors are always de-rated to prevent hazardous temperatures, sparks and arcs during normal operation including start-up. This de-rating makes Ex e motors unpopular and not widely used. In addition Ex e motors typically can only handle a T3 temperature class. In future e (increased safety) will become eb for EPL high - zone 1. Ex-protection EN Flameproof 60079-0 60079-1 “d“ (EN 50014 EN 50018) Gc Leakage Loss Compensation is generally used for electrical machines rather than a continuous purge. Flameproof “d” in future “db” Construction standards Gb Fig 9 Pressurized Motor The “px” system where a pressurised enclosure which reduces the device protection level inside the pressurised enclosure housing from Gb (zone 1) to “not at risk of explosions” is the most common. The “py” system is not suitable for motors and the “pz” method can be used for zone 2 but is not popular. A stator winding ignition risk assessment is required for motors >1kV. (EN 60079-14) also anticondensation heaters must be fitted and additional protection during start-up maybe required (purging, measure gas concentration etc.) I. Equipment protection level Zone 1 Zone 2 K. Protection Comparison for Low Temps Basic principle LV-Motors All parts capable of igniting flammable gases are placed inside a flameproof enclosure. An explosion inside is not propagated outside the enclosure. The outer parts of the flameproof enclosure do not exceed permissible surface temperatures. HV-Motors Ex nA Ex e Ex d + + o Low temperatures Ex nA Ex e Ex d Ex px + + o o BVS 11 ATEX E 084 X Installation Equipment protection level Zone 1 Zone 2 Gb Gc w The range of ambient temperatures is 40°C down to -20°C. This temperature range may be extended to 60°C down to -40°C with a special electrical or thermal design in which suitable terminal boxes, materials and components are used, or with the data for the electrical ratings. L Fig 10 Low Temp Protection Comparison Fig 8 Flameproof Motor 3 Motors in all explosion protection types are available for low temperatures down to -40°C and below. However, often supplementary measures must be utilized for low temperature operation. It should also be noted that at low temperatures, the strength values of the motor materials decrease, especially plastics. L. Protection Comparison for Inverter Use LV-Motors prevent the outside temperature class limit. Ex e Ex d o - ++ Inverter operation Ex nA Ex e Ex d Ex px o - ++ + the HV-Motors Ex nA Ex e Ex d o - + Ex nA Ex e Ex d Ex px o - + - Monitoring investment w L Additional effort for testing and certification Thermal sole protection means that the PTC is the ONLY temperature protection device. Ex nA -Motor DOL-operation: Motor protection switch and/or thermal monitoring Ex e-Motor DOL-operation: certified motor prot. Switch with Is/Ir-tE-timecurve and/or thermal monitoring Inverter operation: thermal monitoring by LV-PTC‘s / HV– PT100 thermal sole protection test required HV with anti-cond. heater Inverter operation: thermal monitoring by LV-PTC‘s / HV– PT100 certified thermal sole protection test required HV with anti-cond. heater Ex p-Motor DOL-operation: Motor protection switch and/or thermal monitoring plus Ex p -monitoring Ex d-Motor DOL-operation: Motor protection switch and/or thermal monitoring Inverter operation: thermal monitoring by LV-PTC‘s / HV– PT100 thermal sole protection test required Inverter operation: thermal monitoring by LV-PTC‘s / HV– PT100 plus Ex p -monitoring thermal sole protection test required Fig 12 Monitoring Investment Comparison * dependent on x exceeding LV-Motors HV-Motors Ex nA surface inverter type, counter torque characteristic and speed range M. Protection Comparison by Weight LV-Motors Fig 11 Inverter Use Protection Comparison Non-sparking machines must, as a minimum, first be type tested as a system with the actual inverter to be used or a comparable one. For Ex nA it must be ensured that the permissible inner as well as outer temperature does not exceed the temperature class limit during operation, particularly at low speeds when the cooling fan may also be running slowly. HV-Motors Ex nA Ex e Ex d ++ o - Weight Weight comparison for LV motors KG/KW 22.5 Ex e Ex d Ex px ++ - - ++ Weight comparison for HV-motors KG 18000 20.0 Ex nA - 1PS1 Ex e - 1PS2 Ex d - 1PS5 17.5 15.0 12.5 16000 Ex nA - 1PS1 14000 Ex e - 1PS2 Ex d - 1PS5 12000 Ex px - 1PS6 10000 10.0 8000 7.5 6000 5.0 Ex e motors must always be tested and certified as a complete system together with the actual inverter to be used (the only exception is PTB certification with significant power de-rating – taking into account the thermal reserves – and only for a square law load torque). Ex nA 4000 2.5 2000 0.0 90 100 112 132 160 180 200 225 250 280 315 0 250kW Shaft height 710kW 1250kW 4000kW Fig 13 Weight Protection Comparison Ex nA and Ex p motors have the lowest weight. Generally Ex e motors with the same power rating are at least one or two frame sizes larger (especially for 2 and 4-pole motors) and are therefore heavier. The higher the power rating, the more significant the differences in the corresponding shaft heights. Ex p motors can always be operated with an inverter. However if the purge system fails it must be ensured that the inner temperatures do not exceed the permissible temperature class limit. This also applies to mounted/installed components, for example heating systems. Generally, an Ex d motor has the same active part as an Ex nA or Ex p motor. However, the enclosure and the end shields are significantly bigger and therefore also heavier as they must withstand high explosion pressures. N. Protection Comparison for Large Power For all Ex e, Ex nA and Ex p motors, the permissible inverter must be specified on the certificate, and the necessary tripping device on the manufacturer's declaration or on the Ex certificate. LV-Motors The inner components of Ex d motors e.g. heating system, do not generally require an Ex version. The installed temperature sensors are selected and located so that they trip earlier before the motor surface reaches the temperature limit. This is the reason that other inverters can be used with Ex d motors, assuming that the company operating the drive system complies with the regulations specified by the motor manufacturer. HV-Motors Ex nA Ex e Ex d o - o Large power rating Ex nA Ex e Ex d Ex px ++ -- o ++ Output power limits 6kV/50Hz air cooled. kW 12000 10000 8000 Ex nA Ex e 6000 Ex d 4000 Ex px 2000 Thermal sole protection test means that the temperature sensor trip (PTC in winding) is tested because it is the sole (only) means of protection to 0 2-pole 4-pole 6-pole 8-pole Fig 14 Large Power Protection Comparison 4 HV Ex d motors, as a result of the necessary explosion protection, can only have higher power ratings in IC511/IC516 (tube cooling, tubes concentrically arranged around the stator core); a mounted cooler is not possible. 1000mm is the maximum shaft height that can still be tested in the worlds largest Ex d test laboratory. As a consequence, the maximum power for a 4-pole motor with 6kV is approx. 8 MW. P. Protection Comparison by Ops Costs LV-Motors HV-Motors Ex nA Ex e Ex d + ++ + o - ++ Flexibility for applications 92.0% 96.0% 90.0% 88.0% 84.0% 95.5% Ex nA / Exd / Ex p Ex e - 1PS2 95.0% Ex e - 1PS2 94.5% 80.0% 94.0% 78.0% 3kW 55kW 250kW 250kW 710kW 710kW 1250kW 4000kW Fig 16 Ops Costs Protection Comparison As a result of the lower thermal utilization, an Ex e motor has lower copper losses, and therefore in comparison, a higher efficiency. For Ex p motors, the costs associated with the purging air supply (purchase, installation and operating costs) is an additional cost, which depending on the motor size and bearing design, can amount to several thousand Euros per year. Ex nA Ex e Ex d Ex px o - ++ + Q. Protection Comparison Summary Table LV-Motors Ambient temperatures Process reliability Ex nA / Ex d / Ex p 82.0% DOL / Inverter operation independent installation - 96.5% 94.0% HV-Motors Ex d + 97.0% 96.0% O. Protection Comparison for Flexibility Ex e Ex px ++ 97.5% 98.0% When it comes to higher power ratings, there are no restrictions for Ex nA and Ex p motors. LV-Motors Ex d + Comparison of efficiency for HV-Motors 100.0% 86.0% Ex nA Ex e Operational costs Comparison of efficiency for LV-Motors 2 and 4 pole Ex e motors, with power ratings above approx. 2.5 MW are no longer practical because achieving a reasonable (long) safe locked rotor time (te) it is necessary to reduce the starting current, which leads to a low starting torque. Ex nA Applications Duty types Fig 15 Flexibility Protection Comparison Ex d motors have the best flexibility, because in principle, they can be designed for normal line operation, intermittent duty, inverter operation as well as heavy-duty starting. For an Ex nA motor, intermittent duty is no longer considered normal operation; as a consequence, starting must also be taken into account in the explosion protection assessment, which makes it similar to an Ex e motor. HV-Motors Ex nA Ex e Ex d -++ o o o + + o o o ++ o o + o ++ ++ o + o ++ o ++ ++ ++ + + ++ + ++ + o ++ + o Ex nA Ex e Ex d Ex px -++ o o o + + o o o ++ ++ o + o ++ ++ o + -++ o ++ + ++ + o ++ + ++ + o ++ + o ++ ++ o o + o ++ + + ++ ++ + - Operation in Zone 1 – Gas/Vapors Gas group ((IIA, IIB, IIC) Temperature class (T3-T6) Dust ignition proof Ability for corrosive cooling medium Low temperatures Overload operation Heavy duty starting Inverter operation Monitoring investment Weight Large power rating Flexibility for applications Operational costs Maintenance costs Comparison based on experience from Service and Engineering information Fig 17 Comparison Summary Table Evaluation Key ++ Very well suited + Well suited 0 Suited Less suited -Not suited Intermittent duty is only possible for an Ex p motor if it is continually purged (also at standstill). R. Cost Comparison An essential advantage of Ex d high-voltage motors, when compared to Ex p and Ex e motors (which must be purged before starting) is that following a power failure or after the motor has been switched off, it can be immediately restarted. 6kV / 50Hz – 1500rpm - AT -20/+40°C, air cooled 150% Ex nA (1PS1) Ex e (1PS2)* Ex d (1PS4) Ex px (1PS6) 140% 130% 120% 110% 100% 90% 300kW 800kW 1600kW Fig 18 Cost Comparison 5 2500kW 5000kW Ex na motors are always the most cost effective but are only suitable for zone 2 operation. Ex e motors are always expensive because they are de-rated. Ex p are the most expensive when small but become cheaper the bigger the motor size because the purge system becomes less as a proportion of the total motor cost. Ex d becomes the most expensive as the explosion proof enclosure becomes a larger proportion of the total motor cost. S. [3] EN 1127-1:2011 Explosive atmospheres. Explosion prevention and protection. Basic concepts and methodology [4] Directive 2014/34/EU Equipment for potentially explosive atmospheres (ATEX) [5] EN 60079-1:2014. Explosive atmospheres. Equipment protection by flameproof enclosures "d". [6] EN 60079-2:2014. Explosive atmospheres. Equipment protection by pressurized enclosure "p". [7] EN 60079-7:2015. Explosive atmospheres. Equipment protection by increased safety "e" [8] EN 60079-15:2010. Explosive atmospheres. Equipment protection by type of protection "n". [9] EN 60079-14:2014. Explosive atmospheres. Electrical installations design, selection and erection [10] Barata et al. “Flameproof Motors operating in the Artic Circle without the need for preheating” PCIC Europe Conference Record, BER-61 2016. [11] Munro et al. “Are the IEC requirements for overpressure testing of Ex d equipment appropriate?” PCIC Europe Conference Record, BER-41 2016. [12] Mistry et al. “What is new in next edition of IEC 60079-7 standard of Ex e motors?” PCIC Europe Conference Record, LO-109 2015. [13] Neleman et al. “Motor Controls for Ex Motors in Hazardous Areas: An Application Guide” PCIC Europe Conference Record, BA-06 2009. Info required for Ideal Motor Selection Certification Norm Installation Country e.g.: Gost / Russia Driven Equipment e.g..: Pump Mg ~ n² Operation mode e.g. DOL or Inverter overload duty cycle Zone, Gas group Temperature -class e.g.: IIC T4 Cooling temperature altitude e.g. -45/+40°C 1000m Starting conditions e.g. 3/2 cold/hot 80% RV Required cooling type e.g. IC411, IC511, IC81W etc. Fig 19 Motor Selection Info Required VI. It is easier to optimise the proposed motor/drive solution when more information can be specified at the quotation stage. III. Dipl.-Ing Hugo Stadler Hugo Stadler graduated from the Fachhochschule Regensburg with an Electrical Engineer Dipl.-Ing. (FH). After six years in the development department for variable speed drives at SIEMENS (Loher) he moved into the sales department and served key customers in the Oil & Gas and Chemical industry. Hugo’s competence is electrical motors, frequency inverters and ex-protection with over 40 years service and experience with the SIEMENS (Loher) company. Today Hugo Stadler is responsible for the SIEMENS sales of LV drive systems to the Oil & Gas industry. CONCLUSION Flameproof Ex d motors provide the best flexibility across LV and HV ranges; they can also be used with any manufacturer’s inverter without special testing. However, Ex d motors become increasingly expensive & heavy with a maximum limit of circa 8MW, so Ex p is better for larger sizes. IV. Eur Ing Steve Jackson MA BSc CEng ACKNOWLEDGEMENTS Steve Jackson graduated from the University of Bath Chemical Engineering School with a BSc (Hons) in 1982. During 2016 he enhanced his academic qualifications with a Masters in Sales Management from the University of Portsmouth. In 1987 Steve became a Chartered Engineer and in 1994 a European Engineer. He has been a Member of the Institute of Measurement and Control for nearly 30 years. Over the course of his career Steve has worked for Fisher Controls, Elsag Bailey, ABB, Endress+Hauser and for the last 12 years SIEMENS – in the fields of automation, instrumentation, process analytics and electrical engineering. Steve is also a committee member for the Energy Industries Council (EIC). The authors acknowledge the contributions made to this paper over the years by such hazardous area motor luminaries as Helmut Hasch, Karl Hofbauer, Klaus Neupert, Thomas Mutzl, Thomas Fuchs and Ulrich Schanzer. V. VITA REFERENCES [1] Siemens Loher, Ruhstorf Explosion proof drives – Planning and Engineering Course: DR-EX-PL [2] Siemens ABC of Motors Manual – October 2009 6 VII. APPENDIX Enlarged Figures Directive 94/9/EC Equipment Equipment group category EPL Types of protection Equipment Equipment Examples group Protection Level M1 Ex ia M2 Ex d, Ex e Z0 ~ 1G Ex ia Z1 ~ 2G Ex d, Ex e, Ex px Z2 ~ 3G Level of protection Ma very high Mb high Ga very high Gb high Ex nA, Ex pz Gc increased Z20 ~ 1D Ex ia, Ex ta Da very high Z21 ~ 2D Ex tb, pD, mD Db high Z22 ~ 3D Ex tc, pD, mD Dc increased I II EN 60079-0 I II III Dust groups: (IP55) IIIA - Combustible flyings IIIB - Non-conductive dust IIIC - Conductive dust (IP65) Gas groups: IIA - Methane, ammonia, ethyl alcohol, etc. IIB - Town gas, ethylene, hydrogen sulfide, etc. IIC - Hydrogen, acetylene, etc. Fig 3 Electrical Equipment Classification LV-Motors HV-Motors Ex nA Ex e Ex d o - ++ Inverter operation Ex nA Ex e Ex d Ex px o - ++ + Additional effort for testing and certification Thermal sole protection means that the PTC is the ONLY temperature protection device. * dependent on x Fig 11 Inverter Use Protection Comparison 7 inverter type, counter torque characteristic and speed range LV-Motors HV-Motors Ex nA Ex e Ex d ++ o - Ex nA Ex e Ex d Ex px ++ - - ++ Weight Weight comparison for LV motors KG/KW 22.5 Weight comparison for HV-motors KG 18000 20.0 Ex nA - 1PS1 Ex e - 1PS2 Ex d - 1PS5 17.5 15.0 12.5 Ex nA - 1PS1 16000 Ex e - 1PS2 14000 Ex d - 1PS5 12000 Ex px - 1PS6 10000 10.0 8000 7.5 6000 5.0 4000 2.5 2000 0.0 90 100 112 132 160 180 200 225 250 280 315 0 250kW Shaft height 710kW 1250kW 4000kW Fig 13 Weight Protection Comparison LV-Motors HV-Motors Ex nA Ex e Ex d -++ o o o + + o o o ++ o o + o ++ ++ o + o ++ o ++ ++ ++ + + ++ + ++ + o ++ + o Operation in Zone 1 – Gas/Vapors Gas group ((IIA, IIB, IIC) Temperature class (T3-T6) Dust ignition proof Ability for corrosive cooling medium Low temperatures Overload operation Heavy duty starting Inverter operation Monitoring investment Weight Large power rating Flexibility for applications Operational costs Maintenance costs Ex nA Ex e Ex d Ex px -++ o o o + + o o o ++ ++ o + o ++ ++ o + -++ o ++ + ++ + o ++ + ++ + o ++ + o ++ ++ o o + o ++ + + ++ ++ + - Comparison based on experience from Service and Engineering information Fig 17 Comparison Summary Table Fig 20 Gas Hazard Marking – in future the EPL will be added to the end eg ‘……………Ex d IIC T4 Gb’ 8