Symmetrical Components and Unbalanced Faults By Dr. E. Matlotse Symmetrical Components and Unbalanced Faults • Different types of unbalanced faults are single line-to-ground fault, line-to-line fault and double line-to-ground fault. • Since the one-line diagram simplifies the solution of balanced 3-Ф problems, the method of symmetrical components that resolves the solution of unbalanced circuit into a number of balanced circuits is used. Symmetrical Components and Unbalanced Faults • Ultimately, then this approach is applied to the unbalanced faults, which permits the treatment of the problem on a simple per phase basis. Fundamental of Symmetrical Components • Symmetrical Components allow unbalanced phase quantities such as currents and voltages to be replaced by three separate balanced symmetrical components. (a) (b) (c) • Fig. 1: Representation of Symmetrical Components Fundamental of Symmetrical Components • Refer to the phasor representation of a 3-Ф balanced current shown in fig. 1(a). • By convention, the direction of rotation of the phasors is taken to be counterclockwise. • Three phasors are written as 1 1 2 1 I b I a 240 a I a 1 1 1 I c I a 120 aI a I a1 I a1 0 I a1 (1) Fundamental of Symmetrical Components • Where we have defined an operator a that causes a counterclockwise rotation of 120⁰, such that a 1120 0.5 j 0.866 (2) a 2 1240 0.5 j 0.866 a 3 1360 1 j 0 • The order of the phasors is abc and this is designated as the +ve phase sequence Fundamental of Symmetrical Components • When the order is acb as shown in fig. 1(b), it is called the –ve phase sequence. • -ve phase sequence quantities are represented as 2 2 2 I b I a 120 aI a I c2 I a2 240 a 2 I a2 I a2 I a2 0 I a2 (3) Fundamental of Symmetrical Components • When analysing certain types of unbalanced faults, it will be found that a 3rd set of balanced phasors must be introduced . • These are called the zero phase sequence which are found in phase with each other. • Zero phase sequence currents, as shown in fig. 1(c) are 0 0 0 (4) I a Ib Ic Fundamental of Symmetrical Components Fig. 2: Resolution of unbalanced phasor into symmetrical components Fundamental of Symmetrical Components • Supersripts 1, 2 and 0 are being used to represent +ve, -ve and zero-sequence quantities, respectively. Fundamental of Symmetrical Components • Refer to 3-Ф unbalanced currents, Ia, Ib and Ic shown in fig. 2. • We are aiming to find the three symmetrical components of the current such that I a I a0 I a1 I a2 0 1 2 Ib Ib Ib Ib 0 1 2 I c I c I c I c (5) Fundamental of Symmetrical Components • According to the expression of the symmetrical components as given by (1), (3) and (4), we can rewrite (5) all in terms of phase a components 0 2 1 2 I b I a a I a aI a 0 1 2 2 I c I a aI a a I a I a I a0 I a1 I a2 (6) Fundamental of Symmetrical Components or I a 1 1 I 1 a 2 b I c 1 a 1 I a0 1 a I a a 2 I a2 (7) • We rewrite the above equation in matrix notation as abc 012 (8) I AI a Fundamental of Symmetrical Components • Where A is known as symmetrical component transformation matrix (SCTM) which transforms phasor currents I abc into component currents I a012 and is 1 1 1 (9) A 1 a 2 a 1 a a 2 • Solving (8) for symmetrical components of current yields (10) I a012 A1 I abc Fundamental of Symmetrical Components • Inverse of A is A 1 1 1 1 1 a 3 1 a 2 1 a 2 a (11) • From (9) and (11), we have A 1 1 * A 3 (12) Fundamental of Symmetrical Components • Substituting for A1 in (10), we get I a0 1 1 1 1 I a 3 1 a I a2 1 a 2 1 I a a 2 I b a I c (13) • Similar formulae exist for voltage • Therefore, the unbalanced phase voltage in terms of the symmetrical components are Fundamental of Symmetrical Components 0 2 1 2 Vb Va a Va aVa Vc Va0 aVa1 a 2Va2 Va Va0 Va1 Va2 (14) • In matrix notation V abc 012 AVa (15) Fundamental of Symmetrical Components • Symmetrical components in terms of the unbalanced voltages 1 Va Vb Vc 3 1 Va1 Va aVb a 2Vc 3 1 Va2 Va a 2Vb aVc 3 Va0 • In matrix notation Va012 A1V abc (16) (17) Sequence Networks of a Loaded Generator • Figure below presents a 3-Ф synchronous generator with neutral grounded through an impedance Zn. • Generator (shown on the next slide) is supplying a 3-Ф balanced load Sequence Networks of a Loaded Generator Fig. 1: 3-Ф balanced source and impedance Sequence Networks of a Loaded Generator • Synchronous machine generates balanced 3-Ф internal voltages and is represented as a +ve sequence set of phasors abc 12 E a E a (1) a • The machine under consideration is supplying a 3-Ф balanced load. • Applying KVC to each phase, we get Va E a Z s I a Z n I n Vb Eb Z s I b Z n I n Vc Ec Z s I c Z n I n (2) Sequence Networks of a Loaded Generator • Substituting for I n I a I b I c and formulating (2) in matrix form, we have Va Ea Z s Z n V E Z n b b Vc Ec Z n Zn Zs Zn Zn Ia I b Z s Z n I c Zn Zn (3) • In compact form, we have V abc E abc Z abc I abc (4) Sequence Networks of a Loaded Generator • Where V abc is the phase terminal voltage vector and I abc is the phase current vector. • Transforming the terminal voltages and current phasors into their symmetrical components results in (5) AVa012 AE a012 Z abc AI a012 Sequence Networks of a Loaded Generator • Multiplying the above by A1 , we have Va012 Ea012 A1Z abc AI a012 (6) Ea012 Z 012 I a012 where Z 012 1 1 1 1 a 3 1 a 2 1 Z s Z n a 2 Z n a Z n Zn Zs Zn Zn 1 1 1 a 2 Z s Z n 1 a Zn Zn 1 a a 2 (7) Sequence Networks of a Loaded Generator • Finally, Z 012 Z s 3Z n 0 0 0 Zs 0 0 Z 0 0 0 Z s 0 0 Z1 0 0 0 Z 2 (8) • Since the generated emf is balanced, there is only +ve sequence voltage as shown below 0 (9) E 012 E a a 0 Sequence Networks of a Loaded Generator • Substituting for Ea012 and Va0 0 Z 0 1 Va E a 0 Va2 0 0 • In component form Z 012 0 Z1 0 into (6), we have 0 I a0 0 I a1 Z 2 I a2 Va0 0 Z 0 I a0 1 1 1 Va Ea Z I a 2 2 2 Va 0 Z I a (10) (11) Sequence Networks of a Loaded Generator • 3 above equations can be represented by the 3 equivalent sequence networks shown below Fig.2: Sequence networks (a) +ve-sequence (b) –vesequence and zero-sequence Line-to-Ground Fault • Fig. 1 shows a 3-Ф generator with neutral grounded through impedance Zn Fig. 1: Line-to-ground fault on phase a Line-to-Ground Fault • Assuming that a line-to-ground fault occurs on phase a through impedance Zn. • Also, assuming the generator is initially on noload, the boundary conditions at the fault point are (1) Va Z f I a Ib Ic 0 (2) Line-to-Ground Fault • Substituting for Ib I c 0 , the symmetrical components of currents are I a0 1 1 1 1 I a 3 1 a I a2 1 a 2 1 I a a 2 0 a 0 (3) • From the above relation, we have I a0 I a1 I a2 1 Ia 3 (4) Line-to-Ground Fault • Phase a voltage in terms of symmetrical components (5) Va Va0 Va1 Va2 • Substituting forVa0 , Va1 and Va2 and noting that I a0 I a1 I a2 , we have Va Ea (Z 1 Z 2 Z 0 ) I a0 (6) • where Z 0 Z s 3Z n . Substituting for Va and noting I a 3I a0 , we have Line-to-Ground Fault 3Z f I a0 Ea (Z 1 Z 2 Z 0 ) I a0 I a0 Ea Z Z Z 3Z f 1 2 0 (7) • Fault current is I a 3I a0 3Ea 1 Z Z 2 Z 0 3Z f (8) Line-to-Ground Fault • Resulting network is Fig. 2: Sequence network connection for line-toground fault Line-to-Line Fault • Fig. 1: Line-to-line fault between phases b and c Line-to-Line Fault • A 3-Ф generator with a fault through impedance Zf between phases b and c is shown in fig. 1. • Assuming the generator is initially on no-load, the conditions at the fault point are Vb Vc Z f I b (1) (2) Ib Ic 0 (3) Ia 0 Line-to-Line Fault • Substituting for I a 0 and I c I b , the symmetrical components of currents are I a0 1 1 1 1 I a 3 1 a I a2 1 a 2 1 0 a 2 I b a I b (4) • From the above equation, I a0 0 1 I a1 (a a 2 ) I b 3 (5) (6) Line-to-Line Fault 1 I a2 (a 2 a) I b 3 (7) I a1 I a2 (8) Vb Vc (a 2 a)(Va1 Va2 ) Z f I b (9) • From (6) and (7), we have • We have Line-to-Line Fault • Substituting for Va1 and Va2 and noting yields I a2 I a1 , (a 2 a)[( Ea Z 1I a1 ) (0 Z 2 I a2 )] Z f I b (a 2 a)[( Ea Z 1I a1 ) (Z 2 I a1 )] Z f I b (a 2 a)[( Ea (Z 1 Z 2 ) I a1 ] Z f I b (10) Line-to-Line Fault • Substituting for I b from (6), yields, (a a)[( Ea ( Z Z 2 1 [( Ea ( Z Z 1 2 2 ) I a1 ] ) I a1 ] 3I a1 Zf 2 ( a a ) 3I a1 Zf 2 2 ( a a )( a a ) (11) Line-to-Line Fault • Since (a a 2 ) (a 2 a) 3 and solving for Ea ( Z Z 1 2 ) I a1 I a1 3I a1 Zf 3 Ea (Z 1 Z 2 ) I a1 Z f I a1 I a1 Ea Z1 Z 2 Z f (12) Line-to-Line Fault • Phase currents are I a 1 1 I 1 a 2 b I c 1 a 1 0 a I a1 a 2 I a1 (13) I b I c (a 2 a) I a1 (14) Line-to-Line Fault • Resulting circuit is Fig. 2: Sequence connection for line-to-line fault Double Line-to-Ground Fault Fig. 1: Double line-to-ground fault Double Line-to-Ground Fault • A 3-Ф generator with a fault on phases b and c through an impedance Zf to ground is shown in fig. 1. • Assuming the generator is initially on no-load, the conditions at the fault point are Vb Vc Z f ( I b I c ) (1) I a I a0 I a1 I a2 0 (2) Double Line-to-Ground Fault • Using the same arguments as cases for the other faults, the resulting equation for this kind of a fault is I a1 Ea Z1 Z 2 ( Z 0 3Z f ) Z 2 Z 0 3Z f (3) Double Line-to-Ground Fault • Therefore, resulting network connection is Fig. 2: Sequence network connection for double line-to-ground fault Example The one-line diagram of a simple power system in the figure below. The neutral of each generator is grounded through a currentlimiting reactor of 0.25/3 per unit on a 100 MVA base. The system data expressed in per unit on a common 100 MVA base is tabulated below. The generators are running on no-load at their rated voltage and rated frequency with their emfs in phase. Example • Figure: The one-line diagram Example Item Base MVA Voltage Rating X1 X2 X0 G1 100 20 kV 0.15 0.15 0.05 G2 100 20 kV 0.15 0.15 0.05 T1 100 20 /220 kV 0.1 0.1 0.1 T2 100 20 /220 kV 0.1 0.1 0.1 L12 100 220 kV 0.125 0.125 0.3 L13 100 220 kV 0.15 0.15 0.35 L23 100 220 kV 0.25 0.25 0.7125 Example Determine the fault current for the following faults: (a) A single-line-to-ground fault at bus 3 through a fault impedance Zf = j0.10 per unit (b) A line-to-line fault at bus 3 through a fault impedance Zf = j0.10 per unit Solution • The +ve-sequence network Solution • To find the Thevenin’s impedance viewed from the faulted bus (bus 3), we convert the delta formed by buses 123 to an equivalent Y Z1S ( j 0.125)( j 0.15) j 0.0357143 pu ( j 0.125) ( j 0.15) ( j 0.25) Z 2S ( j 0.125)( j 0.25) j 0.0595238 pu ( j 0.125) ( j 0.15) ( j 0.25) Z 3S ( j 0.15)( j 0.25) j 0.0714286 pu ( j 0.125) ( j 0.15) ( j 0.25) Solution The resulting network is Solution The positive and negative-sequence Thevenin impedances are 1 2 Z 33 Z33 \ ( j 0.0357143 j 0.15 j 0.1)( j 0.059524 j 0.1 j 0.15) j 0.0714286 ( j 0.0357143 j 0.15 j 0.1) ( j 0.059524 j 0.1 j 0.15) j 0.22 pu Solution The zero-sequence impedance network Solution To establish its Thevenin impedance viewed from the faulted bus, we convert the delta formed by buses 123 to an equivalent Y Z1S ( j 0.30)( j 0.35) j 0.07703595 pu ( j 0.30) ( j 0.35) ( j 0.7125) Z 2S ( j 0.30)( j 0.7125) j 0.156933235 pu ( j 0.30) ( j 0.35) ( j 0.7125) Z 3S ( j 0.35)( j 0.7125) j 0.183088774 pu ( j 0.30) ( j 0.35) ( j 0.7125) Solution The resulting circuit is Solution The zero-sequence Thevenin impedance is 0 Z 33 ( j 0.077064 j 0.1 j 0.05 j 0.25)( j 0.156881 j 0.1) j 0.183088774 ( j 0.077064 j 0.1 j 0.05 j 0.25) ( j 0.156881 j 0.1) j 0.35 pu Solution Single line-to-ground fault at bus 3 is 3 V 0 1 2 a (0) I3 I3 I3 1 Z 33 Z 332 Z 330 3Z f 1 j 0.9174 pu j 0.22 j 0.22 j 0.35 3( j 0.1) Solution The fault current is I 3a 1 1 b 2 I 1 a 3 I 3c 1 a 1 I 30 3I 3a j 2.7523 0 pu a I 3 0 0 2 0 a I 3 0 0 Solution (b) The zero-sequence component of current is zero 0 I3 0 The +ve and –ve sequence components of the Fault are a V (0) I 31 I 32 1 3 2 Z 33 Z 33 Z f 1 j1.8519 pu j 0.22 j 0.22 ( j 0.1) Solution The fault current is I 3a 1 1 b 2 I 1 a 3 I 3c 1 a 1 0 0 a j1.8519 3.2075 pu a 2 j1.8519 3.2075