FINITE ELEMENT ANALYSIS OF POWER
TRANSFORMER
Dr. N. Vasantha Gowri and Zainab Akthar
Chaitanya Bharathi Institute of Technology, Hyderabad, India
ABSTRACT
Failure in power transformer can be catastrophic to electric systems, since
transformers play a vital role in the power sector. Metallic particles in transformer oil
lead to Partial discharge which can result in serious conditions. The existence of
conducting particle in the winding of a transformer accumulates electrical stress.
Simulations are carried out for the electrical analysis of power transformer. The
impact of this electrical stress on particle at different position has been analyzed in
this paper.
Key words: Partial Discharge, Power Transformer, finite element method.
Cite this Article: Dr. N. Vasantha Gowri and Zainab Akthar, Finite Element Analysis
of Power Transformer, International Journal of Mechanical Engineering and
Technology 10(4), 2019, pp. 488–495.
http://www.iaeme.com/IJMET/issues.asp?JType=IJMET&VType=10&IType=4
1. INTRODUCTION
Power Transformer being a vital element in the electrical network, is anatomized such as to
protect it from any catastrophic failure. The transformer collapse can be perilous. To avoid
transformer from being damaged, its testing and analysis is necessity. Studies divulge that
over 85% of failure in HV equipment is due to Partial Discharge (PD).The integrity of
insulation HV equipment is needed to be confirmed with PD analysis in each stage of
manufacturing, commissioning for the reliability of HV winding of transformer. Analysis of
PD is performed for quality assessment of the insulation. The PD analysis detects the
incapacitated points in the insulation. As a part of investigation on PD, analysis of PD due to
particle movement is transformer is studied using CFD [1]. Fluid flow was carried out to find
the setting point of different particles. Mar Lar Myint [2] analyses the transformer through
FEA for determining the electric stress. The current density for low and high voltage winding
is chosen and verified through finite element indicating low voltage winding has higher
current density than high voltage winding. DU Zhi-ye [3] presents the method of calculating
parameter required for propagation characteristic of PD pulses in electric equipment. 2D FEM
model is structured using ANSYS considering winding and transformer core made of iron.
The simulation shows that maximum voltage winding decreases along the winding. Carlos M.
FONTE [4] uses CFD analysis to analyse the flow distribution and heat removal in the core of
a power transformer. Monte-Carlo simulation [5] is used for determining the random
movement of metallic particle in HV transformer. Here, strike of particle is observed
http://www.iaeme.com/IJMET/index.asp
488
editor@iaeme.com
Dr. N. Vasantha Gowri and Zainab Akthar
conveying that in forced oil cooled transformer indicating whether particle is touching
winding which is determined by velocity of oil and random solid angle at any instant of time.
Linsou Zeng [6] analyses the maximum electric field intensity and distribution of electric field
at HV lead of SFP-400000/500 transformer. The result obtained from it is a reference value to
insulation design of ultrahigh power transformer.
This paper represents a conceptual modelling of conducting metallic copper particle of
different size and position present on the HV winding in power transformer is implemented
through Electric module in ANSYS.
2. SIMULATION
The Power Transformer considered for analysis is 100MVA, 220KV with interleaved disc
winding. The turns in a disc winding are wounded radially outward with winding moving
from one disc to another, connecting at their ends to form a complete winding. Figure 1 shows
the configuration of interleaved configuration of transformer, which is used in transformer for
ensure the robust construction and greater mechanical strength. Discs are distanced from one
another with vertical strips attached with the pressboard.
Figure 1. Interleaved disc winding of transformer
IEC 60270 defines Partial Discharge as localized dielectric discharges in a partial area of a
solid or liquid electrical dielectric insulation system under high-voltage stress. PD activity is
influenced by the availability of conducting particle in transformer. This paper deals with
electrical analysis of transformer winding with the availability of particle at low, medium and
highest voltage disc. Electrical stress on the particle is measured by using finite element
method (FEM) and presented in this paper.
HV winding of this transformer comprises of two parts with one part containing 58 discs
which is identical with the other. As only high voltage side of the transformer is prone to PD,
analysis is done for the HV side only. The height of 58 discs is 975.3mm. The gap between
cylinder and disc is 8mm. The width of a given transformer is 61mm and height of each disc
is 12.85 mm respectively. The outer and inner diameter of coil is 1408mm and 1286mm
respectively. The spacing between discs is 4mm.The geometrical designing is done in
Computer Aided Three-dimensional Interactive Application (Catia V5 R20). Figure 2
illustrates the cross-section of HV winding of a power transformer.
http://www.iaeme.com/IJMET/index.asp
489
editor@iaeme.com
Finite Element Analysis of Power Transformer
Figure 2. HV winding of a transformer
Each disc of HV winding is energized with voltages. Highest voltage in this transformer is
127.12KV and the disc with least voltage is 77.09KV. Discs are numbered from top to
bottom.The physical properties of solid and liquid insulation transformer material are taken
into consideration for simulation. The typical values are shown in Table 1.
Table 1 Material Properties
S.No.
Material
1.
Oil
2.
Paper
3.
Pressboard
Properties
Density (Kg/m3)
Specific heat (J/kg-k)
Thermal Conductivity (W/m-k)
Viscosity (kg/m-s)
Density
Specific heat
Thermal Conductivity
Density
Specific heat
Thermal Conductivity
Values
890
2000
0.109
0.02403
900
1500
0.5
1066
1260
0.151
A spherical particle of copper material is made available near the highest, low and
medium voltage disc. For the simulation, following discs with voltages are considered for the
electrical impact.
High voltage at Disc 1:
127.12 KV
Medium voltage at Disc 52: 82.34 KV
Low voltage at Disc 58:
77.09 KV
3. RESULT
Electrical analysis helps in peruse about electrical voltage, current, electrical field intensity
and current density of a model.The particle is made available at the places as discussed above.
It also includes analysis by altering the size of metallic particle by changing the diameter.
Three points of impacts are considered in this investigation at one of the higher, medium and
lower voltage discs. Points of impacts are derived from REF [1].
3.1. Electrical analysis of at disc no. 52
The copper spherical particle of diameter 1mm is considered to be present on the disc 52 with
medium voltage of 82.34 kV. Cross-section of energized HV winding is shown in figure 3.
http://www.iaeme.com/IJMET/index.asp
490
editor@iaeme.com
Dr. N. Vasantha Gowri and Zainab Akthar
Figure 3 Cross section of energized HV winding
Electric field intensity on the particle when particle strikes on disc 52 is given in Figure 4.
The Electric field intensity elucidates the strength of electric field at a point, due to the
presence of electric voltage. On particle, it is 1.2986e-9 KV/cm.
Figure 4. Electric Field Intensity on the particle
Figure 5 represents Directional current density which allows viewing individual vector
component as contours. Its value is 2.2695e-006 mA/µm2 in x-direction.
Figure 5 Directional Current Density
http://www.iaeme.com/IJMET/index.asp
491
editor@iaeme.com
Finite Element Analysis of Power Transformer
Figure 6 shows the simulation result for total current density due to the presence of
electric voltage, the amount of current flowing through per unit area which is 8.6061
mA/µm2.
Figure 6. Total Current Density
3.2. Electric analysis of dia. 2mm on disc 52
Here, analysis result is observed with increased diameter. Figure 7 shows the conducting
particle of diameter 2mm is present on disc no. 52.The electric field intensity is analysed.
Figure 7 Electric Field Intensity
Figure 8 shows the EFI due to the presence of electric voltage with increased diameter of
size 2mm is 5.9762e-7KV/cm on the particle.
Figure 8 Electric Field Intensity on conducting particle
http://www.iaeme.com/IJMET/index.asp
492
editor@iaeme.com
Dr. N. Vasantha Gowri and Zainab Akthar
Figure 9 shows the directional field at the palce of particle and measured as 3.5999e-003
mA/ µm2. It gives electric field intensity on the particle in x-direction.
Figure 9 DFI on particle
Figure 10 shows the Current density on the particle which is measured by tool as 1.11e-3
mA/ µm2.
Figure 10 Current density on 2 mm sphericle particle
Similar analysis was considered by changing the size of particle of diameter 1mm, 2mm,
4mm and placing it in different positions with disc no. 52, 58 and 1. The analysis of the above
discussed is presented in Table 2.
Position of
particle
(on disc)
Size of particle
Table 2 Electrical Result
1mm
52
2mm
52
1mm
58
2mm
58
Electric Field
Intensity(KV/cm)
With
particle
Without
particle
1.2986e-6
Current Density
(mA/ µm2)
With
particle
8.6061e-6
1.0913e-10
5.9762e
-7
6.0849e-8
1.11e
1.2227e-6
-3
2.3104e-3
1.1017e-10
4.4862e-7
http://www.iaeme.com/IJMET/index.asp
Without
particle
5.9764e-8
3.8785e-3
493
editor@iaeme.com
Finite Element Analysis of Power Transformer
1mm
1
2mm
1
4mm
1
1.204e-9
8.2302e-6
9.9398e-10 1.7795e-10 5.2903e-6
2.9837e-10
9.7287e-8
1.8763e-6
4. CONCLUSIONS
Relative study of PD analysis is done on the disc without and with the presence of conducting
copper particle in different positions. The analysis is performed for the electrical stress on the
particle due to voltage of the disc of the HV winding of transformer. From the above analysis
it can be concluded that the electric field intensity and current density is comparatively
negligible with the absence of particle. When the conducting metallic particle is present,
electric field intensity is found to be increased. The stress on the smaller particle is found
slightly higher than that on bigger size due to the fact that the stress will be more on sharp
corners and edges. Current Density on the particle is increasing with the increase in diameter.
REFERENCES
[1]
N. Vasantha Gowri, M. Ramalinga Raju, B.P.Singh, “Analysis of Partial Discharge due to
Movement of Spherical Particle in Power Transformer Using Computational Fluid
Dynamics” International Journal of Engineering & Technology.
[2]
Mar Lar Myint, Yan Aung Oo, “Analysis of Distribution Transformer Design Using
FEA”International Journal of Scientific Research Engineering & Technology (IJSRET),
ISSN 2278 – 0882, Volume 3, Issue 4, July 2014
[3]
DU Zhi-ye, ZHAO Chun,RUAN Jiang-Jun,YU Shi-Feng YUN Wen-Bing, “Calculation
Of Distribution Parameters For Researchon Propagation Characteristic Of Pdin
Transformer Winding”.
[4]
Carlos M. Fonte Jose Carlos B. Lopes Madalena M. Diasrenato G. Sousa Hugo M.
Campelo R. Castro Lopes, “CFD Analysis Of Core Type Power Transformers” 21st
International Conference On Electricity Distribution Frankfurt, 6-9 June 2011Paper
0361Paper No 0361
[5]
N. Vasantha Gowri, M Ramlinga Raju, B. P Singh, “Monte - Carlo Simulation of Particle
Movementin an Un-Energized Transformer” 2014 Annual Report Conference on
Electrical Insulation and Dielectric Phenomena.
[6]
Linsuo Zeng, Peng Xiao, Shan Bai, Yan Wu, and Yuanhai Xia, “Analysis of Electric Field
of HV Lead inUltrahigh Voltage Power Transformer”.
[7]
Shi Chen and Tadeusz Czaszejko, “Partial discharge test circuit as a spark
gaptransmitter”IEEE Electrical Insulation Magazine May/June 2011- Vol. 27, No. 3pp.3644.
[8]
Yuan Li, Qiaogen Zhang, Yi Zhao, Tonglei Wang, Guangqi Liu, Ke Wang, “The
Influence of Temperature on Partial Discharges and Wormhole Effect of Oil-paper
Insulation under DC Voltage” 2017 Electrical Insulation Conference (EIC), Baltimore,
MD, USA, 11 - 14 June 2017.
[9]
Kamran DAWOOD, Bora ALBOYACI, Mehmet Aytac CINAR, Olus SONMEZ,
“Modelling and Analysis of Transformer using Numerical and Analytical Methods”.
[10]
Preethy V. Warrier, Preetha P.K., “Electromagnetic Analysis of Transformer Using
Solidworks” 2015 IEEE International Conference on Technological Advancements in
Power & Energy.
http://www.iaeme.com/IJMET/index.asp
494
editor@iaeme.com
Dr. N. Vasantha Gowri and Zainab Akthar
[11]
N. A. M. Amin, M. T. Ishak, M.H.A. Hamid, M. S. Abd Rahman, “Partial Discharge
Investigation on Palm Oil Using Needle-Plane Electrode Configuration and Electric Field
Distribution Using ANSYS Maxwell” 2017 International Conference on High Voltage
Engineering and Power System, October 2-5, 2017, Bali, Indonesia.
[12]
Chao Tang, Song Zhang, Qian Wang and Jian Hao, “Thermal Stability of Modified
Insulation Paper Cellulose Based on Molecular Dynamics Simulation”.
[13]
C. Thirumurugan, G.B. Kumbhar, “Effect of Electrode Configurations and Gap Spacings
on Partial Discharge Characteristics of Oil-Pressboard Insulation System” 2015 IEEE 11th
International Conference on the Properties and Applications of Dielectric
Materials(ICPADM).
[14]
Sandeep Patel, “Mathematical Modelling of Disc Type Winding Of Transformer”
International Journal of Engineering Research & Technology(IJERT) ISSN: 2278-0181
Vol.2 Issue 9, September – 2013.
[15]
Nor Azizah Mohd Yusoff, Kasrul Abdul Karim, Sharin Ab Ghani, Tole Sutikno, Auzani
Jidin, “Multiphase Transformer Modelling using Finite Element Method” International
Journal of Power Electronics and Drive System(IJPEDS) Vol. 6, No. 1, March 2015, pp.
56-64 ISSN: 2088-8694.