Non-Linear Load Related terms: Reactor, Landing Gear, Transients, Voltage, Thyristors, Current Harmonic, Deflections, Harmonics, Transformers View all Topics Learn more about Non-Linear Load Motors, Generators, and Controls Robert J. Alonzo P.E., in Electrical Codes, Standards, Recommended Practices and Regulations, 2010 Harmonic Mitigation There are several methods used for the mitigation of the harmonics produced by non-linear loads such as variable frequency drives. Some methods are required because of the type of rectifier used in the VFD, the type of DC to AC inverter used, failure to utilize adequate harmonic filtering, etc. Some of the harmonic mitigation methods include: Use of 18 pulse VFD drives AC drives with active front ends – transistor rectifiers with a microprocessor controlled gate circuit AC drives with active shunt filters Use of AC input reactors Use of phase shift transformers with the VFD rectifiers Use of K-Factor transformers or derating transformers Use of DC link reactors Use of tuned LC (inductive/capacitive) or trap filters Insertion of delta-wye transformers in the feeder to minimize harmonic currents The use of K-Factor transformers or derating transformers for use with nonlinear loads is not in itself a harmonic mitigation method. They are, however, a damage mitigation method for transformers subjected to harmonic loading. ANSI/IEEE C57.12.00, IEEE Standard for Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers indicates: that power transformers should not be expected to carry load currents with harmonic factor in excess of 5% of rating. [40] IEEE C57.12.01, IEEE Standard General Requirements for Dry-Type Distribution and Power Transformers Including Those with Solid-Cast and/or Resin Encapsulated Windings similarly provides recommendations for dry type transformers. IEEE Standard C57.110, IEEE Recommended Practice for Establishing Liquid-Filled and Dry-Type Power and Distribution Transformer Capability When Supplying Nonsinusoidal Load Currents was developed to deal with the problem of harmonic generating nonlinear loads. The UL Standards used in association with K-Factor transformers are UL 1561, Dry-Type General Purpose and Power Transformers and UL 1562, Standard for Transformers, Distribution, Dry-Type – Over 600 Volts. Another standard associated with harmonic generating loads for transformers is IEEE Standard C57.18.10, IEEE Standard Practices and Requirements for Semiconductor Power Rectifier Transformers. Transformer use with harmonic generating loads is also addressed in the IEEE Emerald Book, IEEE 1100, IEEE Recommended Practice for Powering and Grounding Electronic Equipment. K-Factor is a mathematical representation to characterize a transformer's ability to withstand overheating from harmonic loading without loss of normal life expectancy. UL 1561 and 1562 list two equations for determining K-Factors [41, 42]. The first is as follows: (Eq. 8.5) where K is the unit-less weighing factor (K-Factor), Ih is the per unit harmonic current component related to the fundamental frequency, and h is the harmonic order number. A K-Factor value of 1.0 would indicate a liner load with no harmonics. As the value of K increases, so does the effect of harmonic heating. The per unit current Ih is expressed such that the total RMS current is one ampere, i.e.: (Eq. 8.6) The mathematical expression Ih could be determined for harmonic components from the first harmonic to some very high harmonic value. It would be difficult to perform this calculation without accepting some level of harmonic as the normally accepted maximum effective harmonic level above which harmonic order components are very small in magnitude. The square of the harmonic component number can become a large number. There have been suggestions limiting the calculation to the 25th or 50th harmonic component. Many of the available harmonic analyzer equipment produce harmonic current reading in the per unit format, making insertion of any collected current data into the mathematical relationship in Eq. 8.6 above very simple. The second equation used by UL to establish the K-Factor for a transformer is shown in Equation 8.7. (Eq. 8.7) where fh is the frequency in Hertz and h is the harmonic order component. Underwriters Laboratories recognizes K-Factors of 4, 9, 13, 20, 30, 40, and 50 as standard transformer ratings. Phase shift transformers are sometimes used in variable frequency drive rectifier sections to minimize harmonic effects. IEEE C57.153, IEEE Guide for the Application, Specification, and Testing of Phase-Shifting Transformers and IEC 62032 Ed. 1, Guide for the Application, Specification, and Testing of Phase-Shifting Transformers (IEEE Standard C57.135) provide guidance with the utilization of phase shift transformers. Long cables, connecting a power source to a motor/VFD, contain a series of natural self-inductive components and shunt distributed natural capacitive components. Natural resonant conditions can develop from those inductive and capacitive components, should the proper excitement conditions develop. Resonant conditions development can occur as a result of the presence of 5th, 7th, 11th, 13th, etc. harmonic components feeding the motor load. The only natural damping factor for the created resonant voltage and current waveforms is the resistance of the line conductors feeding the motor. Resonant conditions can produce insulation damaging voltage levels and overheat motor connections. The introduction of a series connected inductive choke is one method to attenuate or eliminate the resonant waveform. The choke will act as a low-pass filter, attenuating the higher harmonic components and passing the lower fundamental frequency components to the motor. Three percent and 5% line reactors are commonly used to accomplish that task. VFD generated harmonic waveform components can also cause motor winding and bearing heating problems. Because of that potential, the use of motors with a 1.15 service factor, energy efficient motors, or VFD rated motors is recommended. Alternating current VFD-driven excited motors, operating with large inertia loads, can in some circumstances act as an induction generator, causing the voltage on the DC bus to rise above normal operating levels. To protect the VFD rectifier section from damage a braking resistor, can be inserted in parallel with the line to ground capacitor filter in that section. The braking resistor can be activated by an electronic component called a brake chopper. That component will conduct, tying the braking resistor to the circuit neutral when DC Bus voltage levels reach a predetermined point. That action will divert motor generated current from the DC bus, preventing damage to the VFD. PWM VFDs can also cause current flow into motor rotor bearings by capacitive coupling. It can induce a rotor shaft voltage of up to 30 Volts [43]. The high switching frequency of an IGBT inverter can result in inducing current pulses in the motor bearings, if the rotor is not properly grounded. Large motors can develop circulating current between the rotor, shaft bearings, and the stator frame because of motor stator winding capacitive leakage current. The leakage current will eventually overcome the impedance of the bearing lubrication film in a process called bearing fluting. That process will result in a rhythmic pattern of pitting and gouges on the bearing race. Current flow through the bearings can eventually result in bearing overheating and failure. There are several methods to minimize VFD induced motor bearing failures. They include: Proper selection of motor feeder cable and minimizing its length Insertion of a filter at the motor terminal end of the cable Use of motor insulated bearings Use of non-conductive mechanical couplings in the motor Addition of a motor shaft grounding device Ensure proper grounding of a motor and VFD Selection of VFD-rated motors manufactured with insulation meeting the requirements of NEMA Standard MG1 Part 31; Paragraph 40.4.2 In situations where single-phase to ground connected harmonic generating nonlinear loads are fed over a three-phase, four-wire feeder circuit, IEEE 1100 [44] recommends the use of a delta-wye three-phase transformer on that feeder. The triplen harmonics from the nonlinear loads will be trapped in the transformer primary (delta) windings, reducing the introduction of those harmonics to other parts of the electrical distribution system. The delta-wye transformer selected for that task must be listed or certified for that service. > Read full chapter Power Quality – Harmonics in Power Systems DrC.R. Bayliss CEng FIET, B.J. Hardy CEng FIET, in Transmission and Distribution Electrical Engineering (Fourth Edition), 2012 24.3.1 General Harmonic distortion needs to be defined as either ‘current distortion’ or ‘voltage distortion.’ Non-linear loads, unlike linear loads, draw a non-sinusoidal current from a sinusoidal voltage supply. The distortion to the normal incoming sinusoidal current wave can be considered to result from the load emitting harmonic currents that distort the incoming current. These emitted harmonic currents, like any generated current, will circulate via available paths and return to the other pole of the non-linear load. In doing so, they cause harmonic voltage drops in all the impedances through which they pass which distort the normal supply sinusoidal voltage. The aim must therefore be to shunt the emitted harmonic currents into low impedance paths as close to the non-linear load as possible to minimize the resulting voltage distortion, as the voltage distortion will cause harmonic currents to flow in other linear and non-linear connected loads, such as motors, with deleterious effects. Zero-sequence triplen harmonic currents present a further problem as they are constrained to zero-sequence paths such as neutral conductors which can then become overloaded and present a serious risk as neutral conductors are not normally protected against overloading. > Read full chapter Computer-Aided Method NTVPM for Evaluating the Performance of Vehicles with Flexible Tracks J.Y. Wong Ph.D., D.Sc., in Terramechanics and Off-Road Vehicle Engineering (Second Edition), 2010 The characteristics of roadwheel suspensions are fully taken into consideration in NTVPM. Pivot-arm suspensions, such as torsion bar suspensions and hydro-pneumatic suspensions, and translational spring suspensions, with linear or non-linear load–deflection characteristics, can be simulated. The non-linear behaviour of the suspension may be characterized using a polynomial up to the fifth order. On highly deformable terrain, such as deep snow, track sinkage may be greater than vehicle ground clearance. Thus, the vehicle belly (hull) may be in contact with the terrain surface. This would induce additional drag due to belly–terrain interaction. It may also reduce vehicle traction due to the belly supporting part of the vehicle weight which causes the reduction of the load applied on the track. The effects of belly–terrain interaction on vehicle performance have been taken into account. All pertinent terrain characteristics, including the pressure–sinkage and shearing characteristics and the response to repetitive loading, measured by the bevameter technique described in Chapters 3, 4 and 5Chapter 3Chapter 4Chapter 5, are taken into consideration. The basic features of the computer-aided method have been validated by means of full-scale vehicle tests on various types of terrain. Thus, NTVPM provides the engineer with a comprehensive and realistic tool for performance and design evaluation of vehicles with flexible tracks, from a traction perspective. It has been successfully employed by off-road vehicle manufacturers in the development of new products and by governmental agencies in the evaluation of vehicle candidates in North America, Europe and Asia. > Read full chapter Hybrid wind–diesel energy systems G. Bhuvaneswari, R. Balasubramanian, in Stand-Alone and Hybrid Wind Energy Systems, 2010 6.5.4 Loads As mentioned earlier, the loads have been categorized into three types in accordance with their priorities. The loads can be passive loads such as lighting and heating loads; they can be active loads consisting of industrial drives; they can be non-linear loads drawing harmonic-rich currents such as rectifier-fed DC motors, fluorescent lamps with electronic ballasts or power supply systems feeding computers or other medical electronic systems. Depending upon the studies that are undertaken for the system, the loads can be modelled suitably. If simple domestic loads have to be modelled, they are represented by a constant power lumped load. If power quality at the distribution level has to be studied for industrial drive kind of loads, a detailed model of the drive unit has to be adopted. The generator should be in a position to supply all these loads and still maintain a power factor of unity. This will be made possible by making use of power quality conditioners. > Read full chapter Buckling of a Column with Non-Linear Lateral Supports H.S. Tsien, in Collected Works of H.S. Tsien (1938–1956), 2012 During the investigation of the buckling phenomenon of thin spherical shells [1] and thin cylindrical shells[2], it was found that for these structures the load sustained is not a linear function of the deflection even when the stresses are below the elastic limit and are proportional to the corresponding strains. This non-linear load vs. deflection relation gives a buckling phenomenon entirely different from that of the classical theory. However, the exact solution of these problems involves a pair of non-linear partial differential equations. It is difficult to obtain an exact solution. The method adopted in these investigations is the so-called energy method, where a plausible form of deflection of the shell is assumed, first with certain undetermined parameters, and then these parameters are determined by the condition that the first variation of the strain energy of the system must be zero. Although this method yields quite satisfactory results for the cases investigated, it is felt that due to the novel nature of the problem, an exact solution is very desirable. Experiments on a column with non-linear lateral supports[3] show that the essential characteristics of the buckling of curved shells can be reproduced by this structure. The problem of a column with non-linear lateral supports is, however, much simpler than the problem of curved shells, and an exact solution can be obtained without any mathematical difficulty. In the present paper, an exact solution of the column problem will be carried out. > Read full chapter The power supply Ben Duncan A.M.I.O.A., A.M.A.E.S., M.C.C.S, in High Performance Audio Power Amplifiers, 1996 Power factor To discover either the overall efficiency of a power amplifier, or just that of its PSU, we first need to measure the current drawn off the AC supply when driving a known number of watts into a defined load. Excepting those amplifiers fitted with ‘unity’ PFC both 50/60HZ passive and switching power supplies present a highly non-linear as well as reactive load to the AC power line; the periodic AC current generally leads the AC voltage. PSUs using certain ‘smart’ electronic techniques (effectively now outlawed for sale in Europe) may present even more complex non linear loads. For these reasons alone, power input requires careful definition, to screen out the effects of non-unity Power Factor (a perfectly resistive load has a power factor of 1.0; for many amplifiers, PF is around 0.8 to 0.6) and associated high peak currents. The latter aggravate losses in cables, leading to voltage droop, hence power and efficiency losses. For the most part, these effects are essentially external to the amplifier. They're also liable to be significant only if the incoming line power cabling has too high a resistance; or the socketry in line is dirty or loose. But, with high peak currents, the cable gauge needed may be many times that suggested on the basis of safe current rating alone. The efficiency comparisons that follow assume a competent, low resistance installation. An audit of the accuracy of power input measurements would need to take account of auxiliary circuitry, subtracting the power drawn by fans, lamps, LEDs and relays. > Read full chapter IGBT Applications B. Jayant Baliga, in The IGBT Device, 2015 17.4.1 Fuji Electric 200-kVA UPS In 1990, the Fuji Electric Company reported the development of a 200-kVA UPS using IGBTs for use by financial institutions [9]. The goal of this UPS is to provide power to computers that are sensitive to power source voltage fluctuations and prevent halting operations. The authors state [9]: “As compared with the conventional type UPS using bipolar junction transistors, this UPS utilizing IGBT provides an equivalent efficiency in spite of having an approximately 10-times higher switching frequency. As a result, the new UPS has realized a compact, lightweight, low acoustic noise and high performance design resulting in a reduced input harmonic current (less than 5% THD), and also a reduced output voltage distortion (less than 8% THD) under non-linear load.” The specifications for this 200-kVA UPS equipment are provided in Table 17.3. These results demonstrate that IGBTs became the chosen power device technology for UPS systems by 1990. Table 17.3. Fuji Electric Insulated-Gate Bipolar Transistor-Based 200-kVA UPS from 1990 Item Specification Input voltage 200 V ±10% Input frequency 50 or 60 Hz ±5% Input phases/wires 3 phases/3 wires Capacity 220 kVA; 160 kW Input power factor Over 95% THD input current Under 5% Output voltage 200 V Voltage accuracy ±1.5% Output frequency 50 or 60 Hz Output frequency accuracy ±0.1% Output phases/wires 3 phases/3 wires Load power factor 0.7 lagging to 1.0 Transient output voltage fluctuation (a) 100% sudden load change—±8% (b) 10% input voltage sudden change—±5% (c) Major power interruption and recovery—±5% (d) UPS bypass switching—±8% Response time 100 ms Output waveform THD 100% linear load—under 5% 100% nonlinear load—under 8% Voltage imbalance between phases 100% unbalanced load—±3% The topology for the Fuji Electric 200-kVA UPS is shown in Fig. 17.5. Two 100-kVA units are configured in parallel here [9]. Each unit consists of a converter with high power factor, a PWM inverter, an inverter transformer, and AC filters. The converters make use of IGBT modules operated at 8 kHz to achieve a high input power factor to reduce harmonics introduced into the input power line. The inverters are also built using IGBT modules operated at a PWM carrier frequency of 8 kHz. This allows delivering AC sinusoidal output waveforms with low distortion using small AC filters. A bypass path with thyristors is included to handle the situations when the UPS may fail and need servicing. Figure 17.5. Configuration of the Fuji electric uninterruptible power supplies. IGBT modules with ratings of 600 V and 150 A were used for this UPS application. In order to reach the 200-kVA UPS capability, six IGBT modules were connected in parallel to create the IGBT stack shown in Fig. 17.6. Each stack includes the gate drive circuits, the electrolytic DC bus capacitors, and fuses. The snubber circuit was sufficiently small to fit directly on top of each IGBT module. Figure 17.6. Insulated-gate bipolar transistor (IGBT) stack for the Fuji electric uninterruptible power supplies. The UPS configuration described above with IGBTs was able to achieve an efficiency of 90% over a range of 20–100% of the total output power. It delivered a compact, light weight UPS unit with low acoustic noise for use of customers in the financial sector. > Read full chapter Harmonic Models of Transformers Mohammad A.S. Masoum, Ewald F. Fuchs, in Power Quality in Power Systems and Electrical Machines (Second Edition), 2015 2.4.3 Time-Domain Simulation of Power Transformers Time-domain techniques use analytical functions to model transformer primary and secondary circuits and core characteristics [17–25]. Saturation and hysteresis effects, as well as eddy-current losses, are included with acceptable degrees of accuracy. These techniques are mostly used for the electromagnetic transient analysis (such as inrush currents, overvoltages, geomagnetically induced currents, and out-of-phase synchronization) of multiphase and multilimb core-type power transformers under (un)balanced (non)sinusoidal excitations with (non)linear loads. The main limitation of time-domain techniques is the relatively long computing time required to solve the set of differential equations representing transformer dynamic behavior. They are not usually used for steady-state analyses. Harmonic modeling of power transformers in the time domain are performed by some popular software packages and circuit simulators such as EMTP [24] and DSPICE (Daisy’s version of circuit simulator SPICE [25]). The electromagnetic mathematical model of multiphase, multilimb core-type transformer is obtained by combining its electric and the magnetic cir- cuits [35–37]. The principle of duality is usually applied to simplify the magnetic circuit. Figure 2.22 illustrates the topology and the electric equivalent circuit for the general case of a five-limb transformer, from which other configurations such as three-phase, three-limb, and single-phase ones can be derived. The open ends of the nonlinear multiport inductance matrix L (or its inverse, the reluctance matrix ) allow the connection for any electrical configuration of the source and the load at the terminals of the transformer. Figure 2.22. Time-domain harmonic model of power transformers; (a) general topology for the three-phase, five-limb structure, (b) equivalent circuit [23]. Most time-domain techniques are based on a set of differential equations defining transformer electric and magnetic behaviors. Their computational effort involves the numerical integration of ordinary differential equations (ODEs), which is an iterative and time-consuming process. Other techniques use Newton methodology to accelerate the solution [22,23]. Transformer currents and/or flux linkages are usually selected as variables. Difficulties arise in the computation and upgrading of magnetic variables (e.g., flux linkages), which requires the solution of the magnetic circuit or application of the nonlinear hysteresis characteristics, as discussed in Section 2.4.2. In the next section, time-domain modeling based on state-space formulation of transformer variables is explained. Either transformer currents and/or flux linkages may be used as the state variables. Some models [22,23] prefer flux linkages since they change more slowly than currents and more computational stability is achieved. 2.4.3.1 State-Space Formulation The state equation for an m-phase, n-winding transformer in vector form is [19] (2-40) where , , , , and are the terminal voltage vector, the current vector, the resistance matrix, the leakage inductance matrix, and the flux linkage vector, respectively. The flux linkage vector can be expressed in terms of the core flux vector by (2-41) where is the transformation ratio matrix (number of turns) and is the core-flux vector. In general, the core fluxes are nonlinear functions of the magnetomotive forces (), therefore, can be expressed as (2-42) where is a m × m Jacobian matrix. The magnetomotive force vector can be expressed in terms of the terminal current vector by (2-43) where is a matrix that can be determined from matrix and the configuration of the transformer. Substituting Eqs. 2-42 and 2-43 into Eq. 2-40, we obtain (2-44) Defining the nonlinear incremental (core) inductance (2-45) the transformer state equation is finally expressed as follows: (2-46) Equations 2-45 and 2-46 are the starting point for all modeling techniques based on the decoupling of magnetic and electric circuits. The basic difficulty is the calculation of the elements of the Jacobian at each integration step. The incorporation of nonlinear effects (such as magnetic saturation and hysteresis) and the computation of are performed by appropriate modifications of the differential and algebraic equations (Eqs. 2-40 to 2-46). As discussed in Section 2.4.2, numerous possibilities are available for accurate representation of transformer saturation and hysteresis. However, there is a trade-off between accuracy and computational speed of the solution. Figure 2.23 shows the flowchart of the nonlinear iterative algorithm for transformer modeling based on Eqs. 2-40 to 2-46, where elements of can be derived from the solution of transformer magnetic circuit with a piecewise linear (Fig. 2.16b) or an incremental (Fig. 2.16c) magnetizing characteristic [19]. Figure 2.23. Flowchart of the time-domain iterative algorithm for transformer modeling [19]. 2.4.3.2 Transformer Steady-State Solution from the Time-Domain Simulation Conventional time-domain transformer models based on the brute force (BF) procedure [22,23] are not usually used for the computation of the periodic steady-state solution because of the computational effort involved requiring the numerical integration of ODEs until the initial transient decays. This drawback is overcome with the introduction of numerical differentiation (ND) and Newton techniques to enhance the acceleration of convergence [22,23]. > Read full chapter Inverter-fed Induction Motor Drives Austin Hughes, Bill Drury, in Electric Motors and Drives (Fourth Edition), 2013 5.1 Harmonic currents Harmonic current is generated by the input rectifier of an a.c. drive. The essential circuit for a typical a.c. variable-speed drive is shown in Figure 8.1. The utility supply is rectified by the diode bridge, and the resulting d.c. voltage is smoothed by the d.c. link capacitor and, for drives rated typically at over 2.2 kW, the d.c. current is smoothed by an inductor in the d.c. circuit. The d.c. voltage is then chopped up in the inverter stage, which uses PWM to create a sinusoidal output voltage of adjustable voltage and frequency. While small drive ratings may have a single-phase supply, we will consider a 3-phase supply. We see from Figure 8.5 that current flows into the rectifier as a series of pulses that occur whenever the supply voltage exceeds that of the d.c. link, which is when the diodes start to conduct. The amplitude of these pulses is much larger than the fundamental component, which is shown by the dashed line. Figure 8.5. Typical current from utility supply for a 1.5 kW 3-phase drive. Figure 8.6 shows the spectral analysis of the current waveform in Figure 8.5. Figure 8.6. Harmonic spectrum of the current waveform shown in Figure 8.5. Note that all currents shown in spectra comprise lines at multiples of the 50 Hz utility frequency. Because the waveform is symmetrical in the positive and negative half-cycles, apart from imperfections, even-order harmonics are present only at a very low level. The odd-order harmonics are quite high, but they diminish with increasing harmonic number. For the 3-phase input bridge there are no triplen harmonics, and by the 25th harmonic the level is negligible. The frequency of this harmonic for a 50 Hz supply is 1250 Hz, which is in the audio frequency part of the electromagnetic spectrum and well below the radio-frequency part, which is generally considered to begin at 150 kHz. This is important, because it shows that supply harmonics are low-frequency effects, which are quite different from radio-frequency EMC effects. They are not sensitive to fine details of layout and screening of circuits, and any remedial measures which are required use conventional electrical power techniques such as tuned power-factor capacitors and phase-shifting transformers. This should not be confused with the various techniques used to control electrical interference from fast switching devices, sparking electrical contacts, etc. The actual magnitudes of the current harmonics depend on the detailed design of the drive, specifically the values of d.c. link capacitance and, where used, d.c. link inductance, as well as the impedance of the utility system to which it is connected, and the other non-linear loads on the system. We should make clear that industrial problems due to harmonics are unusual, although with the steady increase in the use of electronic equipment, they may be more common in the future. Problems have occurred most frequently in office buildings with a very high density of personal computers, and in cases where most of the supply capacity is used by electronic equipment such as drives, converters and uninterruptible power supplies (UPS). As a general rule, if the total rectifier loading (drives, UPS, PCs, etc.) on a power system comprises less than 20% of its current capacity then harmonics are unlikely to be a limiting factor. In many industrial installations the capacity of the supply considerably exceeds the installed load, and a large proportion of the load is not a significant generator of harmonics – uncontrolled (direct-on-line) induction motors and resistive heating elements generate minimal harmonics. If rectifier loading exceeds 20% then a harmonic control plan should be in place. This requires some experience and guidance can often be sought from equipment suppliers. The good news is that if it is considered that a problem will exist with the estimated level of harmonics then there are a number of options available to reduce the distortion to acceptable levels. A.C. drives rated over 2.2 kW tend to be designed with inductance built into the d.c. link and/or the a.c. input circuit. This gives the better supply current waveform and dramatically improved spectrum as shown in Figures 8.7 and 8.8, respectively, which are again for a 1.5 kW drive for ease of comparison with the previous illustrations. (In this case the inductance in each line is specified as ‘2%’, which means that when rated fundamental current flows in the line, the volt-drop across the inductor is equal to 2% of the supply voltage.) Note the change of vertical scale between Figures 8.5 and 8.7, which may tend to obscure the fact that the pulses of current now reach about 5 A, rather than the 17 A or so previously, but the fundamental component remains at 4 A because the load is the same. (Remember that while we have just demonstrated the tremendous improvement in supply harmonics achieved by adding d.c. link inductance to a 1.5 kW drive, standard drives would rarely be manufactured with any inductance because while the harmonic spectrum looks worrying, the currents are at such a low level that they would rarely cause practical problems.) Figure 8.7. Input current waveform for the 3-phase 1.5 kW drive with d.c. and 2% a.c. inductors. Figure 8.8. Harmonic spectrum of the improved current waveform shown in Figure 8.7. Standard 3-phase drives rated up to about 200 kW tend to use conventional 6-pulse rectifiers. At higher powers, it may be necessary to increase the pulse number to improve the supply-side waveform, and this involves a special transformer with two separate secondary windings, as shown for a 12-pulse rectifier in Figure 8.9. Figure 8.9. Basic 12-pulse rectifier arrangement. The voltages in the transformer secondary star and delta windings have the same magnitude but a relative phase shift of 30°. Each winding has its own set of six diodes, and each produces a 6-pulse output voltage. The two outputs are generally connected in parallel, and, because of the phase shift, the resultant voltage consists of 12 pulses of 30° per cycle, rather than the six pulses of 60° shown, for example, in Figure 2.13. The phase shift of 30° is equivalent to 180° at the fifth and seventh harmonics (as well as 17, 19, 29, 31, etc.), so that flux and hence primary current at these harmonics cancels in the transformer, and the resultant primary waveform therefore approximates well to a sinusoid, as shown for the 150 kW drive in Figure 8.10. Figure 8.10. Input current waveform for 150 kW drive with 12-pulse rectifier. The use of drive systems with an input rectifier/converter using PWM which generates negligible harmonic current in the utility supply is becoming increasingly common. This also permits the return of power from the load to the supply, and is discussed later in section 7. > Read full chapter ScienceDirect is Elsevier’s leading information solution for researchers. Copyright © 2018 Elsevier B.V. or its licensors or contributors. ScienceDirect ® is a registered trademark of Elsevier B.V. Terms and conditions apply.