Computed By: Eng. H.S & E.S Project: Date: Checked By: Eng. M. Gamal Approved By: By: Dr. H. Soliman Foam Fire Fighting System Calculations Design parameters Solution Density 0.16 gpm/ft2 Discharge Time 10.0 min Foam Concentration 3% Sprinklers Spacing 3.0 m Sprinklers K-Factor 5.6 gpm/psi1/2 Safety Factor 10% Protected space dimensions Name of Protected Space LFO Length 20.0 m Width 10.0 m Height 5.0 m Area 200.0 m 2 Volume 1,000 m 3 Foam system characteristics Discharge rate Solution volume Foam volume 344 3,444 gallon 114 gallon No of Sprinklers per length 7 No of Sprinklers per width 4 Total No. of Sprinklers Sizing is based on NFPA-16 gpm 28 2152.8 ft 2