H/P Alarm Con. Ambient T High Y Water Spray Or Additional Cooling N N Compressor Breaker Trip Indoor Unit Issue Reset or Replace Clean Air Intake Air Intake Choked Compressor Contactor Burnt/Spoiled Replace Contactor Bypass Overload Protection Condenser Fan Overload Protection Faulty Compressor mechanism Stuck Replace Compressor Reconnect Power Cable Power Cable Wrong Connection Breaker Rated Current Low Adjust Rated Current Replace Condenser Fan Condenser Fan Burnt/Spoiled H/P Sensor faulty Adjust or Replace Replace Capacitor Condenser Fan Capacitor Spoiled H/P Switch Faulty Adjust or Replace Replace Fan Speed Controller Fan Speed Controller Spoiled Software Issue Adjust Settings or Upload Firmware Adjust Settings or Upload Firmware Controller H/P Port Faulty Loosen Contact or Damage Tighten Wire or Replace Controller Over Charging Release Refrigerant Low Air Flow Condenser Fan Faulty Outdoor Unit Issue Software Issue