CAUTION
Equipment components are sensitive to electrostatic discharge
(ESD). Undetectable permanent damage can result if you do not use proper ESD procedures. Ground yourself, your work surface, and this equipment before removing any cover from this equipment. If your facility is not equipped to work with these components, contact SEL about returning this device and related SEL equipment for service.
!
DANGER
Contact with instrument terminals can cause electrical shock that can result in injury or death.
!
ATTENTION
Les composants de cet équipement sont sensibles aux décharges électrostatiques (DES). Des dommages permanents non-décelables peuvent résulter de l’absence de précautions contre les DES. Raccordez-vous correctement à la terre, ainsi que la surface de travail et l’appareil avant d’en retirer un panneau. Si vous n’êtes pas équipés pour travailler avec ce type de composants, contacter SEL afin de retourner l’appareil pour un service en usine.
!
DANGER
Tout contact avec les bornes de l’appareil peut causer un choc
électrique pouvant entraîner des blessuers ou la mort.
© 2010 by Schweitzer Engineering Laboratories, Inc. All rights reserved.
All brand or product names appearing in this document are the trademark or registered trademark of their respective holders. No SEL trademarks may be used without written permission. SEL products appearing in this document may be covered by US and Foreign patents.
Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded under federal and international copyright and patent laws in its products, including without limitation software, firmware, and documentation.
The information in this manual is provided for informational use only and is subject to change without notice. Schweitzer Engineering
Laboratories, Inc. has approved only the English language manual.
This product is covered by the standard SEL 10-year warranty. For warranty details, visit www.selinc.com or contact your customer service representative.
PM351P-04
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide Date Code 2010021 1
Table of Contents
INTRODUCTION ............................................................................................................. 1
About This Quick-Start Installation and User's Guide .................................................................. 1
Safety Information ...................................................................................................................... 1
INSTALLATION ............................................................................................................... 3
Making the PT Ratio Setting for the Various SEL-351P-3 Options in Figure 9 ........................... 10
Making the CT Ratio Setting for the SEL-351P-3 in Figure 11 .................................................. 13
Mounting .................................................................................................................................. 17
Panel Cutout...................................................................................................................... 17
Mounting Holes ................................................................................................................. 17
Wire Harness Mounting ..................................................................................................... 17
Side Panel Connections ............................................................................................................. 17
Extra I/O ........................................................................................................................... 17
User-Supplied Connectors.................................................................................................. 18
Current and Voltage Connections .............................................................................................. 18
Voltage Inputs ................................................................................................................... 18
Current Inputs ................................................................................................................... 19
POWER Connector J6 and POWER IN Connector J7 Details .................................................... 19
24 Vdc Battery .................................................................................................................. 19
12 Vdc Power Output ........................................................................................................ 19
CONTROL Connector J5 Details .............................................................................................. 20
24 Vdc Whetting Voltage ................................................................................................... 20
Capacitor Voltage Monitor and Charger Control ................................................................ 20
Boost Power Switch........................................................................................................... 20
Trip and Close Outputs...................................................................................................... 21
SF6 Pressure Sensor .......................................................................................................... 21
Checks Before the SEL-351P-3 Is Put in Service ....................................................................... 22
COMMUNICATIONS ..................................................................................................... 23
Getting Started With Communications ....................................................................................... 23
Communications Connections Example ..................................................................................... 24
Serial Ports ............................................................................................................................... 25
Serial Port Default Settings ....................................................................................................... 25
EIA-232 Pinout Functions for Ports 2, 3, and F ......................................................................... 25
EIA-485 Pinout Functions for Port 1 ......................................................................................... 26
Serial Communications Port Pin Function Definitions ................................................................ 26
Communications Cables ............................................................................................................ 26
Cable Diagrams ........................................................................................................................ 27
Commands ................................................................................................................................ 27
Event Reports ........................................................................................................................... 31
Access Levels and Password Protection ..................................................................................... 32
View or Change Passwords ....................................................................................................... 33
Disable Passwords .................................................................................................................... 33
Password Jumper ...................................................................................................................... 34
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide i
Table of Contents
FRONT-PANEL INTERFACE ....................................................................................... 36
Status and Trip Target LEDs ..................................................................................................... 38
Pushbuttons ............................................................................................................................... 39
Pushbutton Primary Functions ................................................................................................... 41
Operator Controls ...................................................................................................................... 44
SETTINGS..................................................................................................................... 50
Curve Information ..................................................................................................................... 50
Factory EZ Settings ................................................................................................................... 52
Settings Descriptions ................................................................................................................. 55
Settings Groups 1 (Main) and 2 (Alternate) EZ Settings ............................................................. 55
Global EZ Settings .................................................................................................................... 78
TESTING ....................................................................................................................... 87
Testing the SEL-351P-3 Without Regularly Installed Apparatus................................................. 87
Logic Settings Changes ...................................................................................................... 87
Front Panel Status LEDs .................................................................................................... 87
Recloser Simulator ............................................................................................................. 88
Output Contacts ................................................................................................................. 88
Overcurrent Element Timing Test Setup ..................................................................................... 89
BATTERY...................................................................................................................... 90
Battery Operation Overview ...................................................................................................... 90
Battery-Related Settings ............................................................................................................ 90
Battery Status ............................................................................................................................ 91
Battery Status via Front Panel ............................................................................................ 91
Battery Status via Serial Port ............................................................................................. 91
Automatic Battery Load Test ..................................................................................................... 92
Battery Load Test via Front Panel .............................................................................................. 92
Battery Load Test via Serial Port ............................................................................................... 93
SPECIFICATIONS ......................................................................................................... 94
SEL-351P-3 recloser controls with AC voltage inputs rated 3 Vac nominal or AC current inputs rated 0.01 A nominal (IN channel rated 0.005 A nominal) are not tested to the following standards: IEEE C37.90.1, IEEE C37.90.2, IEC 801-4, IEC 255-22-3, IEC
255-22-4, and IEC 255-22-5. ............................................................................................. 96
Relay Element Pickup Ranges and Accuracies............................................................................ 96
Instantaneous/Definite-Time Overcurrent Elements ............................................................. 96
Time-Overcurrent Elements ................................................................................................ 97
Under- and Overvoltage Elements ....................................................................................... 97
Synchronism-Check Elements ............................................................................................. 97
Under- and Overfrequency Elements ................................................................................... 97
Timers ............................................................................................................................... 98
Metering Accuracy .................................................................................................................... 98
Factory Assistance..................................................................................................................... 98 ii SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Table of Contents
APPENDIX A: QUICK-START GUIDE CHANGE INFORMATION ................................ 99
APPENDIX B: REPLACE EXISTING PANACEA OR AMAZON RECLOSER
CONTROLS WITH THE SEL-351P-3 RECLOSER CONTROL .................................. 100
Steps for Recloser Control Replacement ............................................................................100
Table 1: SEL-351P-3 Voltage and Current Options ........................................................................... 14
Table 2: SEL EIA-232 Serial Communications Cable Guide ............................................................. 26
Table 3: SEL-351P-3 Recloser Control Command Summary ............................................................. 28
Table 4: Event Report Parameters ..................................................................................................... 32
Table 5: Access Level, Summary Information ................................................................................... 33
Table 6: Front-Panel Pushbutton Secondary Functions ...................................................................... 40
Table 7: Recloser Curve Designations ............................................................................................... 51
Table 8: US, IEC, and User-Programmable Curve Designations ........................................................ 51
Table 9: EZ Settings Quick Reference ............................................................................................... 53
Table 10: Seconds-to-Cycles Conversion (60 Hz) ................................................................................ 63
Table 11: Recloser Interrupt Data ....................................................................................................... 79
Table 12: Battery Status Information Accessed From the Front Panel .................................................. 91
Figure 1: SEL-351P-3 Recloser Control Dimensions ............................................................................ 3
Figure 2: SEL-351P-3 Recloser Control Panel Cutout Dimensions ....................................................... 3
Figure 3: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J3 and Current
Connector J10—Traditional Option....................................................................................... 4
Figure 4: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J4 and Current
Connector J10 ....................................................................................................................... 5
Figure 5: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J3 and Current
Connector J11 ....................................................................................................................... 6
Figure 6: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J4 and Current
Connector J11 ....................................................................................................................... 7
Figure 7: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J8/J9 and Current
Connector J10 ....................................................................................................................... 8
Figure 8: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J8/J9 and Current
Connector J11 ....................................................................................................................... 9
Figure 9: SEL-351P-3 Voltage Connector Options ............................................................................. 10
Figure 10: SEL-351P-3 Current Connector J10—Traditional Option .................................................... 11
Figure 11: SEL-351P-3 Current Connector J11 .................................................................................... 12
Figure 12: SEL-351P-3 Relay Inputs, Outputs, and Communications Ports .......................................... 15
Figure 13: Trip and Close Circuit, Breaker Status, and SF6 Pressure Connections ................................ 16
Figure 14: SEL-351P-3 Recloser Control Communications Connections Example ................................ 24
Figure 15: Jumper, Connector, and Major Component Locations on the SEL-351P-3 Recloser
Control Main Board ............................................................................................................ 35
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide iii
Table of Contents
Figure 16: SEL-351P-3 Recloser Control Front-Panel Interface (English) ............................................. 36
Figure 17: SEL-351P-3 Recloser Control Front-Panel Interface (Spanish) ............................................. 37
Figure 18: Status and Trip Target LEDs (English) ................................................................................ 38
Figure 19: Status and Trip Target LEDs (Spanish) ............................................................................... 39
Figure 20: Primary and Secondary Functions of Front-Panel Pushbuttons (English) .............................. 39
Figure 21: Primary and Secondary Functions of Front-Panel Pushbuttons (Spanish) .............................. 40
Figure 22: Recloser Simulator Connections to SEL-351P-3 (only a 52a available) ................................ 88
Figure 23: Existing Connector and Wiring for Incoming AC Power into an Existing Panacea or
Amazon Recloser Control Cabinet ..................................................................................... 102
Figure 24: Cable C5586 for bringing AC Power to the SEL-351P-3 Recloser Control ......................... 103
Figure 25: Cable C5586 connected to bring AC Power from the Rear of the Existing Cabinet to the SEL-351P-3 Recloser Control ...................................................................................... 103 iv SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Introduction
I
Replace Existing Panacea or
Amazon Recloser Controls:
See Appendix B .
The SEL-351P-3 interfaces only with a Whipp & Bourne
GVR Recloser.
This SEL-351P-3 Recloser Control Quick-Start Installation and User’s
Guide helps you install, communicate with, set, and test the SEL-351P-3 in its EZ (“easy”) mode of operation. The EZ mode performs traditional recloser control functions and operations.
When using the SEL-351P-3 as a traditional line recloser control, it is only necessary to access the EZ Level (Access Level E) Settings. See the
SEL-351P-3 Instruction Manual for complete information regarding the full functionality of the SEL-351P-3.
The following sections are covered in this documentation:
• Table of Contents
• Introduction
• Installation
• Settings
• Testing
• Battery
• Communications • Specifications
• Front-Panel Interface • Changes ( Appendix A )
• Replacement ( Appendix B )
This Quick-Start Installation and User’s Guide does not cover all of the possible conditions or circumstances that can occur during the installation, operation, or testing of the SEL-351P-3. If additional information is necessary to install, communicate with, or make settings to the control that is not provided in this documentation, please refer to the SEL-351P-3
Instruction Manual or contact SEL for assistance.
This Quick-Start Installation and User’s Guide contains three types of hazard statements:
CAUTION : indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury or equipment damage.
WARNING : indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
DANGER: indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury.
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 1
Introduction
!
!
!
!
!
CAUTION: The SEL-351P-3 contains devices sensitive to
Electrostatic Discharge (ESD). When working on the relay module with cover removed, work surfaces and personnel must be properly grounded or equipment damage may result.
CAUTION: Do not connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the Settings section of this guide for programming procedures. Failure to comply can result in control and recloser misoperation, equipment damage, and personal injury.
WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this guide. Improper installation, handling, or maintenance can result in death, severe personal injury, and/or equipment damage.
WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury, and/or equipment damage.
DANGER: Contact with instrument terminals may cause electric shock that can result in injury or death.
2 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Installation
I
See following Mounting subsection.
Figure 1: SEL-351P-3 Recloser Control Dimensions
Figure 2: SEL-351P-3 Recloser Control Panel Cutout Dimensions
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 3
Installation
Serial Port and IRIG-B:
The serial ports and IRIG-B are explained in the
Communications section.
Ratings:
Ratings for optoisolated inputs, output contacts, current inputs, voltage inputs, and power inputs/outputs are given in the
Specifications section.
N/C Symbol:
A few of the connector terminals are labeled N/C (not connected). see Figure 9(a) for voltage connector J3 details see Figure 10 for current connector J10 details see Table 1 for all voltage and current options/ratings
Figure 3: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J3 and Current
Connector J10—Traditional Option
4 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Installation see Figure 9(b) for voltage connector J4 details see Figure 10 for current connector J10 details see Table 1 for all voltage and current options/ratings
Figure 4: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J4 and Current
Connector J10
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 5
Installation see Figure 9(a) for voltage connector J3 details see Figure 11 for current connector J11 details see Table 1 for all voltage and current options/ratings
Figure 5: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J3 and Current
Connector J11
6 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Installation see Figure 9(b) for voltage connector J4 details see Figure 11 for current connector J11 details see Table 1 for all voltage and current options/ratings
Figure 6: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J4 and Current
Connector J11
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 7
Installation see Figure 9(c) for voltage connector J8/J9 details see Figure 10 for current connector J10 details see Table 1 for all voltage and current options/ratings
Figure 7: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J8/J9 and Current
Connector J10
8 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Installation see Figure 9(c) for voltage connector J8/J9 details see Figure 11 for current connector J11 details see Table 1 for all voltage and current options/ratings
Figure 8: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J8/J9 and Current
Connector J11
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 9
Installation
7
2
8
3
10
5
9
4
6
1
Connector J3
V1
V2
V3
N/C
VS
Connector J4
12
6
8
2
9
3
11
5
10
4
7
1
N/C
N/C
VS
V1
V2
V3
5
2
4
6
3
1
2
1
Connector J9
V1
V2
V3
VS
Connector J8
(a) (b) (c)
(a) Voltage Connector J3: V1, V2, V3, and VS (300 Vac nominal)—Traditional
Option
(b) Voltage Connector J4: V1, V2, V3 (3 Vac), and VS (300 Vac nominal)
(c) Voltage Connector J8/J9: V1, V2, V3, and VS (3 Vac nominal) see Table 1 for all voltage and current options/ratings
Figure 9: SEL-351P-3 Voltage Connector Options
Figure 9(a) shows the traditional (300 Vac) voltage inputs, where the PT
Ratio setting (see the Settings section) is set with the ratio of the external primary potential transformers (not shown).
Figure 9(b) and Figure 9(c) have low-level (3 Vac) voltage inputs. The
SEL-351P-3 does not internally scale these low-level (3 Vac) voltage inputs any different than the traditional (300 Vac) voltage inputs. Thus,
1.2 Vac applied to the low-level (3 Vac) voltage inputs appears the same to the SEL-351P-3 as 120 Vac applied to the traditional (300 Vac) voltage inputs. Thus a PT Ratio setting made for the low-level (3 Vac) voltage inputs has to take into account this factor of 100 (= 300 Vac/
3 Vac) difference. For example, if the external voltage step-down device
(for the low-level [3 Vac] voltage inputs) has a ratio of 10,000, then it would need to be adjusted by this factor of 100 for a PT Ratio setting:
10 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Installation
PT Ratio = 10,000 x (1/100) = 100
This adjusted PT Ratio setting makes the primary voltage metering correct. The secondary voltage metering values for the low-level (3 Vac) voltage inputs still appear as 100 times their actual magnitude (e.g., 1.2
Vac applied to the low-level [3 Vac] voltage inputs appears as 120 V secondary in the secondary voltage metering)—nothing can be done about this.
Voltage elements in the “regular” settings (see the SEL-351P-3
Instruction Manual ) are set in Volts secondary. Thus, for a voltage element to pick up for 1.2 Vac applied to the low-level (3 Vac) voltage inputs, the voltage element pickup in the SEL-351P-3 needs to be set at
120 V secondary (= 1.2 x 100). Again, the factor of 100 (= 300 Vac/
3 Vac) comes into play for the low-level (3 Vac) voltage inputs.
If the PT Ratio setting does not apply to all the voltage inputs (voltage inputs V1, V2, and V3 require a different setting than voltage input VS, as is likely in Figure 9(b) with its mixture of 3 Vac and 300 Vac voltage inputs), then separate potential transformer ratio settings are needed (see
“regular” settings PTR and PTRS discussed in the SEL-351P-3
Instruction Manual ).
GVR Recloser
(partial) SEL-351P-3 (partial)
Connector J10 umbilical cable (partial)
5
6
3
4
1
2
7
8
9
N/C
I1
I2
I3
IN
I1, I2, I3 (1 Amp nominal) and IN (0.05 Amp nominal) see Table 1 for all voltage and current options/ratings
Figure 10: SEL-351P-3 Current Connector J10—Traditional Option
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 11
Installation
I1, I2, I3 (0.01 Amp nominal) and IN (0.005 Amp nominal) see Table 1 for all voltage and current options/ratings
Figure 11: SEL-351P-3 Current Connector J11
The interposing current transformers in Figure 11 are integral to particular GVR Recloser models. They require the particular SEL-351P-3 current inputs shown in Figure 11 and further explained/referenced in
Table 1. The winding turns of the interposing current transformers are literally the turns on the indicated sides. For current passing through the interposing current transformers (left-to-right), the current is transformed down:
• by a factor of 1/200 (= 5/1000) for current inputs I1, I2, and I3
• and by a factor of 1/20 (= 50/1000) for current input IN
For example, 1 A from the primary current transformers on the left-hand side of Figure 11 is transformed down to
• 0.005 A [= 1 A x (1/200)] for current inputs I1, I2, and I3
• and 0.05 A (= 1 A x (1/20)] for current input IN after it passes (left-to-right) through the interposing current transformers.
12 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Installation
The CT Ratio setting (see the Settings section) is traditionally set with the ratio of the primary current transformer (the current transformers on the left-hand side of Figure 11, transforming primary current to secondary levels). For example, if the primary current transformers on the left-hand side of Figure 11 are ratio 400, then the traditional setting is: CT Ratio =
400.0.
But, Figure 11 is a unique setup, with the combination of the interposing current transformers inside the GVR Recloser and the internal
SEL-351P-3 low-level current-input circuitry on the right-hand side. With this unique setup, a traditional CT Ratio setting causes primary current to appear as half the true magnitude to the SEL-351P-3. Thus, if 400 A primary is flowing on the primary system on the left-hand side of
Figure 11, the SEL-351P-3 on the right-hand side (with setting CT Ratio
= 400.0) only perceives 200 A primary. Likewise, the SEL-351P-3 perceives only half the true secondary current. For example, if there is 1 A secondary flowing out of the primary current transformers on the left-hand side of Figure 11, the SEL-351P-3 on the right-hand side perceives only
0.5 A secondary. This “half magnitude” perception on the part of the
SEL-351P-3 in Figure 11 applies to all the current channels I1, I2, I3, and
IN.
The solution to this “half magnitude” problem for the SEL-351P-3 in
Figure 11 (for primary current values) is to double the CT Ratio setting.
Thus, a traditional setting of CT Ratio = 400.0 (for primary current transformers of ratio 400) is doubled to CT Ratio = 800.0 (= 2 x 400.0).
Then, primary current metering values appear correct and EZ settings made in Amps primary (see the Settings section) are made as they normally would be, without any adjustment.
This “doubling of the CT Ratio setting” to handle primary current values
(metering and EZ settings) makes no change to secondary metering values from the SEL-351P-3 in Figure 11—secondary metering values still appear as half the traditionally expected magnitude—nothing can be done about this. Likewise, if “regular” settings are made in Amps secondary
(not in Amps primary, as with the EZ settings in the Settings section), then adjustments would have to be made. For example, if a “regular” setting is traditionally set 1 A secondary, then it would be set 0.5 A secondary instead, for a Figure 11 setup. “Regular” settings (made in
Amps secondary) are discussed in the SEL-351P-3 Instruction Manual .
For many traditional recloser installations, only EZ settings need be made
(see the Settings section) and “regular” settings do not have to be made.
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 13
Installation
Side-Panel
Figure
Figure 3
(traditional option)
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
J4
J10
J3
J11
J4
J11
J8/J9
J10
J8/J9
J11
Table 1: SEL-351P-3 Voltage and Current Options
Voltage and
Current
Connectors
J3
J10
Detail
Figures
Figure 9(a)
Figure 10
Figure 9(b)
Figure 10
Figure 9(a)
Figure 11
Figure 9(b)
Figure 11
Figure 9(c)
Figure 10
Figure 9(c)
Figure 11
Voltage and Current Inputs
Nominal Ratings
Ordering Option
(see Model
Option Table)
2X V1, V2, V3, VS: 300 Vac
I1, I2, I3: 1 Amp
IN: 0.05 Amp
V1, V2, V3: 3 Vac
VS: 300 Vac
I1, I2, I3: 1 Amp
IN: 0.05 Amp
V1, V2, V3, VS: 300 Vac
I1, I2, I3: 0.01 Amp
IN: 0.005 Amp
V1, V2, V3: 3 Vac
VS: 300 Vac
I1, I2, I3: 0.01 Amp
IN: 0.005 Amp
V1, V2, V3, VS: 3 Vac
I1, I2, I3: 1 Amp
IN: 0.05 Amp
V1, V2, V3, VS: 3 Vac
I1, I2, I3: 0.01 Amp
IN: 0.005 Amp
AX
BX
CX
DX
EX
14 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Installation
Voltage and Current
Connectors:
The voltage and current connectors (J3 and J10, respectively) in Figure 12 are for the traditional option shown in Figure 3. See Table 1 for all available voltage and current options.
Power Supply Connection:
Only one 120/240 Vac power supply connection is made – either to connector J7
(terminals 1 and 2) or to connector J6 (terminals 4 and
8). For replacement of existing
Panacea or Amazon Recloser
Controls, the Vac power connection will be made to connector J7—see
Appendix B .
Figure 12: SEL-351P-3 Relay Inputs, Outputs, and Communications Ports
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 15
Installation breaker aux. contacts b a
Trip and
Close
Logic to 24Vdc battery
(POWER connector J6) trip cap fully charged close cap charged
>20 Vdc close
24Vdc inside
SEL-351P-3
Battery
Charger
Charger
Control
13
36/24
Vdc
1
Power
Supply
5
2
10
CONTROL connector
J5 see Note 1 outside
SEL-351P-3 recloser
(partial)
52b
52a
Control Signal to
Cap Charger trip
Boost Power
Switch
16
9 see
Note 1
6
14
7
Power to
Cap Charger
Trip Cap
Close Cap
Cap Return
GVR Recloser (partial)
Manual
Isolator trip
Magnetic
Actuator close
15
8
Note 1: Terminal 9 is also the return for the 24 Vdc whetting voltage on terminal 1, when terminal 1 is paralleled to additional applications (e.g., to whet opto-inputs
IN101 - IN106). Terminal 1 has a load limit of 0.1 A and should be fused for protection (Bussman GMD-0.125 fuse or equivalent).
low pressure
Pressure
Sensor
Whetting
Voltage
+
-
3
11
-
+ pressure
+
-
4
12
SF6 Gas
Pressure
Sensor setting
SF6 low pressure warning threshold
Figure 13: Trip and Close Circuit, Breaker Status, and SF6 Pressure Connections
16 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Installation
Room for Connectors and Wiring:
The dimensions in Figure 1 do not make any allowances for connectors and wiring that may be attached to the side panel
(see Figure 12). Some connections (e.g., fiber-optic modems) can protrude up to 4 inches (about 10 cm) out from the surface of the side panel.
Refer to Figure 1 and Figure 2.
Panel Cutout
The front view dimensions 7.00 x 13.00 inches (177.8 x 330.2 mm) refer to the panel cutout dimensions needed for mounting the SEL-SEL-351P-3.
The panel cutout dimensions are slightly smaller than the SEL-351P-3 front-panel overlay, thus providing appropriate coverage of the
SEL-351P-3 front panel when mounted, yet allowing for front panel interface access. SEL-351P-3 front panel overlay details can be seen in
Figure 16 (English) and Figure 17 (Spanish).
Mounting Holes
The six mounting holes are each 0.20 inch (5.2 mm) diameter. A size #6-
32 bolt or mounting stud, with lock nuts is recommended.
Wire Harness Mounting
The two studs on both the top and bottom of the SEL-351P-3 can be used to attach wire clamps for a wire harness draped over the top of the unit (or underneath). The studs accept #10-32 lock nuts.
Refer to Figure 3 through Figure 12. Figure 9 through Figure 12 show what is “behind” the side panel connections shown in Figure 3 through
Figure 8. See Table 1 for all voltage and current options/ratings.
!
WARNING: Connect the GROUND terminal to ground before making any other connection on the side panel. The GROUND spade is 0.25 x 0.03 inches (6.4 x 0.8 mm).
Explained in Other Sections:
The serial ports and IRIG-B shown in Figure 12 are explained in the Communications section. The front-panel
LEDs and operator controls are explained in the Front-Panel
Interface section.
Extra I/O
The extra I/O (output contacts OUT101 through ALARM and optoisolated inputs IN101 through IN106) is not needed for the basic recloser control functions. The extra I/O is available for SCADA connection or other control and is not polarity sensitive. See the
Specifications section for ratings.
The connectors for the extra I/O accept wire size AWG 24 to 12. Strip the wires to 0.3 inch (8 mm) and install with a small slotted-tip screwdriver.
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 17
Installation
User-Supplied Connectors
Connectors J3 through J11 (depending on model; see Table 1 and its figure references) on the side panel are the receptacle end (female), with recessed male terminals inside. The user supplies the complementary plug end (male), with recessed female terminals inside. Each plug end (male) is a different size and uniquely keyed and cannot be inserted into any other receptacle end (female):
J3 Molex Mini-Fit, Jr. order no. 39-01-2105
J4 Molex Mini-Fit, Jr. order no. 39-01-2125
J5 Molex Mini-Fit, Jr.
J6 Molex Mini-Fit, Jr.
J7 Molex Mini-Fit, Jr.
J8 Molex Mini-Fit, Jr. order no. 39-01-2165 order no. 39-01-2085 order no. 39-01-2025 order no. 39-01-2025
J9 Molex Mini-Fit, Jr.
J10 TYCO order no. 39-01-2065 order no. 770021-1
J11 Souriau Connection Technology order no. SMS9P1
The user-supplied plug ends (male) require the following corresponding female terminals be installed in a recessed fashion inside the connector:
Molex order no. 39-00-0055
Tyco
Souriau order no. 770008-4 order no. SM20M1S6
Special tools and procedures are required to install terminals/wiring into the user-supplied connectors.
See Table 1 for all voltage and current options/ratings.
The SEL-351P-3 has three analog voltage input terminal connections labeled V1, V2, and V3. Wiring to the power system (potential transformer connections and recloser primary bushing connections) can be random, but correct power system “A-B-C” designation is still needed within the SEL-351P-3 algorithms. EZ Settings and Global EZ settings
(True three-phase voltage connected, Phantom voltages, V123 Terminal
Conn., I123 Terminal Conn., CT Polarity) define how transition occurs between the power system wiring and the SEL-351P-3 relay algorithm.
Frequency Measurement
Voltage input V1 (VOLTAGES connector) also provides the frequency measurement (e.g., for underfrequency load shedding).
Voltage Inputs
Voltage inputs V1, V2, and V3 are the three phase voltage inputs. Voltage input VS is the synchronism check voltage input. Voltage input VS can be used for other functions besides just synchronism check—see Section 3 in the SEL-351P-3 Instruction Manual .
18 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Enable Fault Location if
Three-Phase Voltage is connected:
Use SET n command
[n = 1 (main settings), n = 2 (alternate settings)]
Make the line parameter settings:
Z1MAG, Z1ANG
Z0MAG, Z0ANG, LL
Enable fault locating:
EFLOC = Y
See SET commands in Table 3 in the Communications section.
Installation
Current Inputs
Residual current is derived internally from phase current channels I1, I2, and I3. Residual ground overcurrent elements operate off of this derived residual current.
Neutral ground and sensitive earth fault (SEF) overcurrent elements operate off of current channel IN.
The EZ settings presume that current channel IN is connected residually with phase current channels I1, I2, and I3 by the user. This is required to satisfy the pickup range sensitivity for fast and delay curve-ground overcurrent elements (i.e., for the current input option in Figure 10; for ground overcurrent element pickups below 0.1 A secondary, a neutral ground overcurrent element is used automatically; for ground overcurrent element pickups 0.1 A secondary and above, a residual ground overcurrent element is used automatically).
See the Settings section for more EZ settings details.
Power Supply Connection:
Only one 120/240 Vac power supply connection is made, either to connector J7
(terminals 1 and 2) or to connector J6 (terminals 4 and
8). See Figure 12 and accompanying side-panel note.
24 Vdc Battery
The 24 Vdc battery to power the SEL-351P-3 and external trip/close capacitors (when Vac power is not present on terminals 1 and 2 of
POWER IN connector J7) is connected to POWER connector J6, terminals 6 (+) and 2 (–). See the Battery section for more details.
NOTE: Anytime nominal Vac power is applied to the SEL-351P-3
(terminals 1 and 2 of POWER IN connector J7), the unit automatically turns on and the AC SUPPLY/ALIM CA LED illuminates.
If no power is connected to the SEL-351P-3 (unit is off) and then 24 Vdc battery power is connected to POWER connector
J6 terminals 6 (+) and 2 (–), the unit remains off until the
WAKE UP/DESPERTAR operator control is pressed.
12 Vdc Power Output
12 Vdc power is available on POWER connector J6, terminals 5 (+) and 1
(–). It is used for such applications as powering radios. It is currentlimited and has the following specifications:
Voltage Range Fluctuation: 11–14 Vdc
Maximum Capability: 6 W continuous; 13 W for one second
!
WARNING: No grounds can be installed on the circuits connected to the 12 Vdc voltage source. This voltage source is grounded inside the SEL-351P-3.
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 19
Installation
Figure 13 shows greater detail on what is connected to either side of
CONTROL connector J5.
Fuse the 24 Vdc
Whetting Voltage:
Read Note1 in Figure 13.
24 Vdc Whetting Voltage
The 24 Vdc voltage on terminal 1 whets the 52a and 52b breaker auxiliary contacts, which are connected through terminals 5 and 13, respectively. It can also whet the 24 Vdc optoisolated inputs IN101 through IN106 using terminal 9 as a return.
Optoisolated inputs IN101 through IN106 can be configured via settings to operate on ac voltage. See the Optoisolated Input Ratings subsection in the Specifications section for more information on ac operation.
!
WARNING: No grounds can be installed on the circuits connected to the 24 Vdc whetting voltage.
This voltage source is grounded inside the SEL-351P-3.
Connect Battery and Charge
Capacitors for Auto-
Reclosing
Factory-default settings require that the 24 Vdc battery be connected and healthy and the trip and close capacitors be fully charged in order for autoreclosing to proceed after a reclose interval times out.
Capacitor Voltage Monitor and Charger Control
Terminals 6 and 14 monitor trip and close capacitor voltages, respectively.
Terminal 6 indicates when the trip capacitor is fully charged (> 80 V).
The presumption is if the trip capacitor is fully charged to > 80 V, the close capacitor is, likewise, fully charged.
Terminal 14 indicates when the close capacitor is charged to at least 20 V.
Exceeding this 20 V threshold causes the capacitor charger control output
(terminals 10 and 2) to go below 24 Vdc (it is nominally 40 Vdc). This low output signal to the external capacitor charger causes the charger to go to a higher charge rate to quickly charge the capacitors to 90 V.
External Power Supply
An external power supply is also supplying power to the external trip/close capacitor charger, if ac power is present.
If ac power is off, then the external power supply provides no power and the 24 Vdc battery is the only source of power (via the closed Boost
Power Switch) for the external trip/close capacitor charger.
Boost Power Switch
The Boost Power Switch on terminal 16 is usually open when ac power is present. This allows the battery charger inside the SEL-351P-3 module to charge the 24 Vdc battery without outside interference.
The Boost Power Switch closes for any of the following occurrences:
• Trip
• Close
• Start of reclose cycle
• Loss of ac power
The closed Boost Power Switch provides 24 Vdc battery power to an external trip/close capacitor charger. Thus, the battery charger is turned
20 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Installation off while the Boost Power Switch is closed. About two minutes after trip, close, and reclose cycle operations cease (and if ac power is present), the
Boost Power Switch opens again and battery charging resumes.
If the Boost Power Switch is closed due to loss of ac power, it remains closed until the 24 Vdc battery is automatically disconnected (discharging for too long or battery voltage too low—see battery-related settings in the
Battery section). If ac power returns sooner, then there is about a two minute delay before the Boost Power Switch opens again and battery charging resumes.
Trip and Close Outputs
Combinations of FET outputs connected to terminals 7, 8, and 15 provide tripping/closing of the recloser by energizing the magnetic actuator in one direction or the other. The FET outputs are connected in an H-bridge arrangement, with the magnetic actuator in the middle of the H-bridge circuit. The magnetic actuator causes the recloser to:
• open for current in the “trip” direction
• or close for current in the opposite/”close” direction
When the SEL-351P-3 trips the recloser, one trip FET output turns on to connect the trip capacitor (terminal 6) to the magnetic actuator (terminal
7). The other trip FET output completes the circuit from terminal 15 to the capacitor return on terminal 8. At the end of the trip operation, the trip
FET outputs turn off, forcing the extinguishing of the trip current.
When the SEL-351P-3 closes the recloser, one close FET output turns on to connect the close capacitor (terminal 14) to the magnetic actuator
(terminal 15). The other trip FET output completes the circuit from terminal 7 to the capacitor return on terminal 8. At the end of the close operation, the close FET outputs turn off, forcing the extinguishing of the close current.
SF6 Pressure Sensor
Terminals 3 and 11 provide whetting voltage for the SF6 gas pressure sensor on the recloser. Terminals 4 and 12 take in the SF6 gas pressure sensor signal and compare it to an EZ setting threshold for low pressure indication. See the Settings section for more EZ settings details.
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 21
Installation
! CAUTION: Do not connect the SEL-351P-3 to an energized recloser until all control settings have been properly programmed and verified and all front-panel operator controls are in their proper state (see
Figure 16 or Figure 17). Refer to the Settings section of this guide for programming procedures. Failure to comply can result in control and recloser misoperation, equipment damage, and personal injury.
Settings Group 3
With factory settings, the LIVE
LINE ENABLED/LINEA VIVA
HABILITADA operator control activates Settings Group 3 when it is engaged—see explanation in the Operator
Controls subsection in the
Front-Panel Interface section.
Thus, certain future settings changes made to Settings
Groups 1 and/or 2 should perhaps be made to Settings
Group 3, too.
If the alternate settings are not going to be used, copy the main settings
(Settings Group 1) to the alternate settings (Settings Group 2) with the
COPY command (i.e., COP 1 2 ; see Table 3 in the Communications section). The settings in both settings groups will then be the same. If the
ALTERNATE SETTINGS/AJUSTES ALTERNATIVOS operator control pushbutton is accidentally pressed (switching the active settings group), the SEL-351P-3 still operates on the same settings. Refer to the
Factory EZ Settings subsection in the Settings section for more information on main and alternate settings.
Set the date and time with the DATE and TIME commands ( DAT and
TIM , respectively; see Table 3 in the Communications section).
22 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Communications
C
Topics covered in this section:
• Serial Port Connectors
• Communications Cables
• Commands
• Access Levels
• Password Protection
You can view and change control settings, and obtain event and status information either from the front-panel interface or via one of the serial ports.
You can access many of the features of the SEL-351P-3 from the front panel; however, some features can only be accessed from one of the serial ports. Table 3 provides the serial port commands (with descriptions) as well as the corresponding front-panel pushbutton, if applicable.
Before you attempt communications with the SEL-351P-3, via either the serial ports or the front-panel interface, the following precautions must be taken:
Hint:
For the best display, use
VT-100 terminal emulation or the closest variation.
• Verify that the SEL-351P-3 has been properly installed and that the settings have been programmed by qualified personnel.
Terminal Emulation
Programs:
Examples of PC-based terminal emulation programs include: ProComm Plus ® ,
Relay Gold ® , Microsoft ®
Windows ® Terminal and
HyperTerminal, SmartCOM ® , and CROSSTALK ® .
• Become familiar with and understand the information presented in the Communications, Front-Panel Interface , and Settings sections.
For serial port communications, the previous two precautions apply. You must also carry out the following:
• Select the appropriate communications cable (usually SEL Cable
C234A—see Table 2).
Default Settings for Front
Panel Serial Port:
Baud Rate = 38400
Data Bits = 8
Parity = N
Stop Bits = 1
• Choose a terminal emulation program on your personal computer
(PC) to communicate with the SEL-351P-3.
• Set the communications parameters for the connected PC communications port to the default settings. (Press the ENTER key, and the SEL-351P-3 will respond with a “=” prompt, which indicates Level 0 access is established—see Table 5.)
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 23
Communications
You can connect the serial port to a computer serial port for local communications or to a modem for remote communications. Other devices useful for automated communications are SEL Communications
Processors.
You can use a variety of terminal emulation programs on your personal computer to communicate with the SEL-351P-3. Figure 14 presents some example SEL-351P-3 communications connections (see Table 2 and contact SEL for more information).
DATA AND TIME-SYNCHRONIZATION* CONNECTIONS
SEL
Communications
Processor
PORT 2
(METALLIC)
Cable #C273A
SEL-351P
Fiber-Optic Cable
#C273AFZ or #C273AF0
SEL
Communications
Processor
SEL-351P
SEL-2810
PORT 2
SEL-351P
Metallic Cable Connection Optical Cable Connection
* Demodulated IRIG-B time code can be input into the connector for either serial port 1 or serial port 2, but not both at the same time.
EIA-485 CONNECTIONS (if ordered with EIA-485 port)
Computer
PORT 1
SEL-351P (#1)
PORT 1
SEL-351P (#2)
PORT 1
SEL-351P (#32)
LOCAL CONNECTIONS
C ONNECT TO THE SEL
C OMMUNICATIONS P ROCESSOR
ONCE AND COMMUNICATE WITH
ANY CONNECTED SEL R ELAY OR
R
ECLOSER
C
ONTROL
OR
. . .
C
ONNECT TO THE
SEL-351P
R
ECLOSER
C
ONTROL
INDIVIDUALLY VIA THE
F
RONT
-
P
ANEL
S
ERIAL
P
ORT
Cable
#C234A
PORT 2 Side Panel
SEL-351P (#1)
PORT F Front Panel
Front Panel
SEL-2032
PORT 2 Side Panel
SEL-351P (#2)
PORT F Front Panel
DWG: M351P056
Figure 14: SEL-351P-3 Recloser Control Communications Connections Example
24 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Communications
Three EIA-232 serial communications ports are available:
• Serial Port 2 (side panel)
• Serial Port 3 (side panel)
• Serial Port F (front panel)
An EIA-485 serial communications port is available as an ordering option:
• Serial Port 1 (side panel)
DNP Port:
Serial port 3 is factory-set as a
DNP port, with baud rate =
19200. See Appendix H:
Distributed Network Protocol
(DNP3) in the SEL-351P-3
Instruction Manual for more
The default settings for serial ports 1, 2, and F are:
Baud Rate = 2400 (ports 1 and 2); 38400 (port F)
Data Bits = 8
Parity = N
Stop Bits = 1
The serial port default settings can be changed from the front-panel interface or from the serial communications port itself. After connecting the appropriate communications cable and setting the terminal emulator, press the <Enter> key, and the control will respond with a “=” prompt, which indicates Level 0 access is established—see Table 5.
DWG: M351R078
DB-9 Connector Pinout (female) for EIA-232 Serial Ports
Make Only One IRIG-B
Connection:
If making an IRIG-B connection, connect demodulated IRIG-B time code to either the serial
Port 2 or serial Port 1 connector
(see the following EIA-485
Pinout Functions for Port 1 ), but not both .
1 N/C* or +5 Vdc
2 RXD
N/C* or +5 Vdc
RXD
3 TXD TXD
4 +IRIG-B N/C
N/C
RXD
TXD
N/C
5, 9 GND GND
6 -IRIG-B N/C
7 RTS
8 CTS
RTS
CTS
GND
N/C
RTS
CTS
* Pin 1 not connected for Ports 2 and 3 when shipped from the factory.
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 25
Communications
1
SERIAL PORT 1
2 3 4 5 N/C
IRIG-B
+ _
7 8
Pin Function Pin
1 +TX
Function
5 SHIELD
PIN EIA-485
2 -TX
3 +RX
4 -RX
6 N/C
7 +IRIG-B
8 -IRIG-B
Pin Function Definition
Convenient IRIG-B
Connection:
Serial Port 2 provides the most convenient connection for demodulated IRIG-B time code. See the top of Figure 14 and SEL Cable 273A in
Table 2, and the corresponding cable diagram.
+5 Vdc (0.5 Amp limit)
RXD, RX
TXD, TX
IRIG-B
5 Vdc Power Connection
Receive Data
Transmit Data
IRIG-B Time-Code Input
GND Ground
RTS
CTS
DCD
DTR
DSR
Request To Send
Clear To Send
Data Carrier Detect
Data Terminal Ready
Data Set Ready
Other Cables Available:
Table 2 lists the most commonly used cables (see corresponding cable diagrams on the following page). Contact SEL for information on other available cables.
Table 2: SEL EIA-232 Serial Communications Cable Guide
Connect From:
SEL-351P-3
Connect To:
Computer (9-pin)
SEL Cable:
C234A
C227A
C273A
Processor
SEL-351P-3 Modem C222
26 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Communications
The following cable diagrams correspond to the cables listed in Table 2
(most commonly used cables). The male/female references in the cable diagrams refer to the cable connectors, not the device they are connecting to (which would be the opposite gender). Contact SEL for information on other available cables.
SEL-351P-3 Recloser Control to Computer
Cable C234A
SEL-351P-3 9-Pin *DTE Device
9-Pin Male
“D” Subconnector
9-Pin Female
“D” Subconnector
RXD 2
TXD 3
GND 5
CTS 8
3 TXD
2 RXD
5 GND
8 CTS
* DTE = Data Terminal Equipment (Computer, Terminal,
Printer, etc.)
SEL-351P-3 Recloser Control to Computer
Cable C227A
SEL-351P-3 25-Pin *DTE Device
9-Pin Male
“D” Subconnector
GND 5
TXD 3
RXD 2
GND 9
CTS 8
25-Pin Female
“D” Subconnector
7 GND
3 RXD
2 TXD
1 GND
4 RTS
SEL-351P-3 Recloser Control to
SEL Communications Processor
Cable C273A
* DTE = Data Terminal Equipment (Computer,
Terminal, Printer, etc.)
SEL-351P-3 Recloser Control to Modem
Cable C222
Processor
9-Pin Male
“D” Subconnector
TXD 3
RXD 2
IRIG+ 4
GND 5
IRIG- 6
CTS 8
RTS 7
9-Pin Male
“D” Subconnector
3 TXD
4 IRIG+
5 GND
6 IRIG-
7 RTS
8 CTS
9-Pin Male
“D” Subconnector
GND 5
TXD 3
RTS 7
RXD 2
CTS 8
GND 9
25-Pin Male
“D” Subconnector
7 GND
1 GND
** DCE = Data Communications Equipment
(Modem, etc.)
Commands, passwords, or settings you type appear in bold/uppercase: DAKOTA .
Computer keys you press appear in bold/brackets :
<Enter> .
The following serial port commands are available for use with the
SEL-351P-3. Much of the information available from the serial port commands is also available via the front-panel pushbuttons (see
Pushbutton Primary Functions in the following section).
The commands are shown in upper-case letters, but they can also be entered using lower-case letters.
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 27
Communications
Table 3: SEL-351P-3 Recloser Control Command Summary
Access Level
Available
Commands
Access
Level 0
ACC
EZA
Access
Level 1
2AC and
BAC
BRE
BRE A
COM
COU
Description
The only operation that can be performed at Access Level 0 is to go to Access Levels 1 or E. The screen prompt is: = (see Table 5)
Enter Access Level 1.
Enter Access Level E.
The Access Level 1 commands primarily allow the user to look at information (e.g., settings, metering), not change it. The screen prompt is: => (see Table 5)
Enter Access Level 2.
Enter Breaker Access Level (Access Level B).
Display breaker/recloser contact wear report.
Display breaker/recloser contact wear and trip operation report.
M IRRORED B ITS
® communications statistics.
Display SEL OGIC
® counter values.
DAT Show date.
DAT m/d/y Enter date in this manner if Date Format setting DATE_F = MDY.
DAT y/m/d Enter date in this manner if Date Format setting DATE_F = YMD.
EVE n Show event report number n with 1/4-cycle resolution.
EVE L n
EVE R n
Show event report number n with 1/16-cycle resolution.
EVE C n
Show raw event report number n with 1/16-cycle resolution.
Show compressed event report number n for use with SEL-5601
Analytic Assistant.
EZA
GRO
Enter EZ Access Level (Access Level E).
Display active group number.
HIS n
HIS C
IRI
MET k
MET D
MET E
MET M
Show brief summary of the n latest event reports.
Clear the brief summary and corresponding event reports.
Force synchronization attempt of internal relay clock to IRIG-B timecode input.
Display instantaneous metering data. Enter k for repeat count.
Display demand and peak demand data.
Display energy metering data.
Display maximum/minimum metering data.
Corresponding
Front-Panel
Pushbutton
(English/Spanish)
OTHER/VARIOS
OTHER/VARIOS
OTHER/VARIOS
OTHER/VARIOS
OTHER/VARIOS
GROUP/CONFIG
GRUPO
EVENTS/EVENTOS
METER/MEDICIÓN
METER/MEDICIÓN
METER/MEDICIÓN
METER/MEDICIÓN
28 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Communications
Access Level and
Available
Commands
MET RD
MET RE
MET RM
MET RP
QUI
Reset demand metering data.
Description
Reset energy metering data.
Reset maximum/minimum metering data.
Corresponding
Front-Panel
Pushbutton
(English/Spanish)
METER/MEDICIÓN
METER/MEDICIÓN
METER/MEDICIÓN
METER/MEDICIÓN
SER n
Reset peak demand metering data.
Quit. Returns to Access Level 0. Terminates SEL Distributed Port
Switch Protocol (LMD) connection.
Show the latest report. n rows in the Sequential Events Recorder (SER) event
SER m n
SER d1
Show rows m through n in the Sequential Events Recorder (SER) event report.
Show rows in the Sequential Events Recorder (SER) event report from date d1.
SER d1 d2 Show rows in the Sequential Events Recorder (SER) event report from date d1 to d2. Entry of dates is dependent on the Date Format setting
DATE_F (= MDY or YMD).
SHO n Show relay settings (overcurrent, reclosing, timers, etc.) for Group n . SET/CONFIG
SHO L n Show SEL OGIC control equation settings for Group n .
SHO EZ n Show EZ settings for Group n . SET/CONFIG
SHO FZ
SHO G
SHO P
SHO R
SHO T
STA
TAR R
TAR
TIM n n k
Show FZ settings (global EZ settings).
Show global settings.
Show Port n settings.
Show Sequential Events Recorder (SER) settings.
Show text label settings.
Show relay self-test status. STA C resets self-test warnings/failures.
Reset the front-panel tripping targets.
Display Relay Word row. If n = 0 through 59, display row n . If n is an element name (e.g., 50A1) display the row containing element n .
Enter k for repeat count.
Show or set time (24-hour time). Show time presently in the relay by entering just TIM (e.g., time 22:47:36 is entered with the following command: TIM 22:47:36).
SET/CONFIG
SET/CONFIG
SET/CONFIG
STATUS/DIAGNO
TARGET
RESET/PRUEBO
LAMP.
OTHER/VARIOS
OTHER/VARIOS
TRI Trigger an event report.
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 29
Communications
Access Level and
Available
Commands
Access
Level E
BTT
Description
The Access Level E commands allow the user to access and change the EZ settings as well as Level 1 commands. The screen prompt is: =+> (see Table 5)
Display status of latest battery discharge test and the time remaining until next battery discharge test.
BTT NOW Force new battery discharge test immediately.
SET EZ
SET FZ
Change recloser control EZ settings.
Change recloser control global EZ settings.
Access
Level B
The Access Level B commands primarily allow the user to operate relay parameters and output contacts. All Access Level 1 and E commands can also be executed from Access Level B. The screen prompt is: ==> (see Table 5)
BRE W
BRE W A
BRE R
CLO
GRO n
OPE
PUL n k
Corresponding
Front-Panel
Pushbutton
(English/Spanish)
OTHER/VARIOS
SET/CONFIG
SET/CONFIG
Preload breaker/recloser contact wear.
Preload breaker/recloser contact wear and trip operation counters.
Open the circuit breaker.
Pulse output contact n (OUT101 through OUT107, ALARM) for k
(1–30) seconds. Parameter n must be specified; k defaults to 1 if not specified.
OTHER/VARIOS
OTHER/VARIOS
Reset breaker/recloser contact wear and trip operation counters.
Close the circuit breaker.
OTHER/VARIOS
Change active group to group n . GROUP/CONFIG
GRUPO
CNTRL/CONTROL
AUX.
Access
Level 2
CON
COP
PAS n m n
PAS 1 xxxxxx
The Access Level 2 commands allow unlimited access to relay settings, parameters, and output contacts. All Access Level 1, E, and B commands are available from Access Level 2. The screen prompt is: =>> (see Table 5)
Control Relay Word bit RB n , Remote Bit n where n = 1 through 16.
Execute CON n , and the relay responds: CONTROL RB n . Then reply with one of the following:
SRB n set Remote Bit n (assert RB n ).
CRB n clear Remote Bit n (deassert RB n ).
PRB n pulse Remote Bit n (assert RB n for 1/4 cycle).
Copy relay and logic settings from Group m to Group n .
Show existing Access Level 1, B, and 2 passwords. SET/CONFIG
Change Access Level 1 password to xxxxxx . SET/CONFIG
30 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Communications
Access Level and
Available
Commands
PAS E xxxxxx
PAS B xxxxxx
PAS 2 xxxxxx
PAS 1
DISABLE
PAS E
DISABLE
PAS B
DISABLE
PAS 2
DISABLE
SET n
SET L n
SET EZ n
SET FZ
SET G
SET P n
SET R
SET T
VER
Description
Corresponding
Front-Panel
Pushbutton
(English/Spanish)
Change Access Level E password to xxxxxx . SET/CONFIG
Change Access Level B password to xxxxxx . SET/CONFIG
Change Access Level 2 password to xxxxxx . SET/CONFIG
Disables Access Level 1 password.
Note: “DISABLE” must be entered in uppercase.
Disables Access Level E password.
Note: “DISABLE” must be entered in uppercase.
Disables Access Level B password.
Note: “DISABLE” must be entered in uppercase.
Disables Access Level 2 password.
Note: “DISABLE” must be entered in uppercase.
Change relay settings (overcurrent, reclosing, timers, etc.) for
Group n .
SET/CONFIG
Change SEL OGIC control equation settings for Group n .
Change EZ settings for Group n . SET/CONFIG
Change FZ settings (global EZ settings).
Change global settings.
SET/CONFIG
SET/CONFIG
Change port n settings.
Change Sequential Events Recorder (SER) settings.
Change text label settings.
Show version information.
SET/CONFIG
Note:
The event report length is selectable: 15 or 30 cycles.
More options are available to customize event reports.
Refer to Section 12 in the
SEL-351P-3 Instruction
Manual for more event information.
Event reports are automatically triggered at the beginning of a fault and when the SEL-351P-3 issues a trip. Event report length is 15 cycles
(factory default). The latest twenty-eight 15-cycle event reports are stored in nonvolatile memory.
To obtain event report information use the EVE command. There are numerous options that allow you to customize event information. For descriptions and examples of all options, refer to the SEL-351P-3
Instruction Manual . The general command format is:
EVE [ n A D ]
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 31
Communications
The parameters in brackets [ ] are optional. The following table defines the parameters [ n A D ] that can be issued with the EVE command to customize the report format.
Table 4: Event Report Parameters
Parameter n Choose event number (1–28). Defaults to 1 if not specified.
Description
A Specifies that the analog section of the event is to be displayed (current, voltage, frequency, contact outputs, and optoisolated inputs).
D Specifies that the digital section (Protection and Control
Elements) of the event is to be displayed.
Summary event information can be viewed at the control front-panel LCD using the front-panel pushbuttons. Press the EVENTS/EVENTOS pushbutton (primary function) and the appropriate left/right and up/down pushbuttons (secondary function) to view event information.
If no parameters are issued with the EVE command, then you will automatically receive both the analog (A) and digital (D) sections of the event report.
Passwords Required With
Front-Panel Pushbuttons?
See Pushbutton Primary
Functions subsection in the
Front-Panel Interface section.
Issue serial port commands to the SEL-351P-3 to view metering values, change recloser control settings, obtain event information, etc. The available serial port commands are listed in Table 3. The commands can be accessed only from the corresponding access level as shown in the table, but a higher access level can access the serial port commands in a lower access level.
Access Level 0 (the lowest access level)
Access Level 1
Access Level E (EZ access level)
Access Level B
Access Level 2 (the highest access level)
As a security measure, entry to a particular access level (except Access
Level 0) requires a unique password. This allows the user to set up a password system to deny unqualified or unauthorized personnel access to higher levels.
The SEL-351P-3 ships from the factory with default passwords (see
Table 5). If restrictions are to be placed on personnel using the
SEL-351P-3, the factory default passwords must be changed. Make sure that password information is stored for future reference in the event that it is lost or forgotten.
32 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Access
Level
0
1
E
B
2
Communications
Access
Command
ACC
EZA
BAC
Table 5: Access Level, Summary Information
Prompt
=
=>
=+>
==>
Factory
Default
Password
Description of Access Level
Command Privileges
Signifies serial communications are established.
The only operation available here is go to Access
Level 1 or Access Level E.
OTTER Primarily allows you to only look at information
(i.e., metering, settings), not change it.
DAKOTA Primarily allows the user to change the EZ group settings and global EZ settings.
EDITH Primarily allows the user to operate output contacts or change the active setting group.
2AC and output contacts.
Want to View a Password?
If you have the Access Level 1 and 2 passwords, enter Access
Level 1, then Access Level 2, execute the PAS command, and view all passwords.
Lost or Forgotten Password?
When passwords are lost or forgotten, you can view the passwords by putting the main board password jumper in place. See the following
Password Jumper subsection.
Want to Operate Without
Passwords?
See the following Disable
Passwords and Password
Jumper subsections.
The PAS command allows you to inspect or change existing passwords
(must be in Access Level 2). To inspect passwords, type PAS<Enter> .
=>> PAS < Enter >
1:OTTER
E:DAKOTA
B:EDITH
2:TAIL
=>>
The factory default passwords for Access Levels 1, E, B, and 2 are shown above. To change the password for Access Level E to BIKE, enter the following:
=>> PAS E BIKE < Enter >
Set
=>>
After entering new passwords, type PAS < Enter > to inspect them. Verify they are what you intended, and record the new passwords.
Passwords may include up to six characters. Valid characters consist of:
‘A–Z’, ‘a–z’, ‘0–9’, ‘-’, and ‘.’. Upper- and lower-case letters are treated as different characters.
If you wish to disable password protection for a specific access level
(must be in Access Level 2), simply set the password to DISABLE (must
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 33
Communications be uppercase). For example, to disable the Access Level 1 password, type the following:
=>> PAS 1 DISABLE < Enter >
Password Disabled
=>>
The password protection for Access Level 1 is now disabled.
The following Password Jumper subsection describes how password protection for all access levels can be disabled by a hardware password jumper.
!
CAUTION: The relay module contains devices sensitive to
Electrostatic Discharge (ESD).
When working on the relay module with front or top cover removed, work surfaces and personnel must be properly grounded or equipment damage may result.
This subsection provides instructions for putting the password jumper in place if you wish to operate the SEL-351P-3 without password protection or in the event that the passwords are lost or forgotten.
When the password jumper (JMP6-A) is ON (in place), password protection is disabled. Figure 15 shows the general location of the password jumper.
When the password jumper is OFF (removed/not in place), password protection is enabled. This is how the SEL-351P-3 ships from the factory.
Then the only way to disable password protection is with the PAS command (see preceding Disable Passwords subsection).
To change the password jumper position, carry out the following steps:
1.
De-energize the SEL-351P-3.
2.
Disconnect all connections to the SEL-351P-3 (remove GROUND last).
3.
Take SEL-351P-3 to an ESD (Electrostatic Discharge) protected work area.
4.
Remove eight Phillips-head screws from front and left side panel of
SEL-351P-3.
5.
Disconnect the ribbon cables from the front panel.
6.
Remove front panel of SEL-351P-3.
7.
Locate the jumper(s) to be changed (refer to Figure 15). Change the jumper position.
8.
Reconnect ribbon cables to front panel.
9.
Replace eight Phillips-head screws in front and left side panel of
SEL-351P-3 relay module.
10.
Reconnect all connections to the SEL-351P-3 (reconnect
GROUND first).
11.
Reenergize the SEL-351P-3.
34 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Communications
Figure 15: Jumper, Connector, and Major Component Locations on the SEL-351P-3 Recloser
Control Main Board
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 35
Front-Panel Interface
F
-P
I
English and Spanish
The following figures in this section show labeling for the
English and Spanish models.
Both models operate the same way with factory default settings.
Topics covered in this section:
• Status and Trip Target LEDs
• Pushbuttons
• Operator Controls
User-Configurable Labels
Both models come with standard or user-configurable labels. The dashed lines in the figures indicate the areas for user-configurable labels.
Display (default display shows IA,
IB, IC, and IN primary currents)
Low Capacitor Voltage Alarm on Display
With factory-default settings, the front-panel display will show the following message:
LOW TRIP/CLOSE
CAPACITOR VOLTAG if the external trip or close capacitor voltage is low (see capacitor connections in
Figure 13). This message will also display when the
SEL-351P-3 is powered up, but not connected to the external trip and close capacitors (e.g., the SEL-351P-3 relay module is powered up for a bench test, with no standard installation connections made).
Pushbuttons
Status and Trip
Target LEDs
Operator
Controls
Figure 16: SEL-351P-3 Recloser Control Front-Panel Interface (English)
Target LED Label
Opening
Operator
Control Label i4680c
Opening
36 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
Display (default display shows IA,
IB, IC, and IN primary currents)
Pushbuttons
Status and Trip
Target LEDs
Target LED Label
Opening
Operator
Control Label
Operator
Controls
Figure 17: SEL-351P-3 Recloser Control Front-Panel Interface (Spanish) i4682c
Opening
37 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
SEL-351P-3
Recloser Control is enabled
Most of the Status and Trip Target LEDs and Operator Controls can change function (if desired by the user) by programming at a higher logic level (see the SEL-351P-3 Instruction Manual ). This Front-Panel
Interface section discusses each function as shipped from the factory and inscribed on the front panel.
Indicates any of the following battery problems:
- discharge test failure
- disconnected
- cannot be charged
- monitor/charger failure
Indicates that a trip occurred
(overcurrent or otherwise)
High-set overcurrent element trip
Vac power is present
Low SF6 gas pressure in recloser
Fast curve overcurrent element trip
Underfrequency trip
CONTROL
ENABLED
AC
SUPPLY
BATTERY
PROBLEM
LOW
PRESSURE TRIP
FAST
CURVE
HIGH
CURRENT
UNDER
FREQ.
Control in reset state and ready for reclose cycle
RESET CYCLE LOCKOUT A B C EF / G SEF
CONTROL STATE
Control actively in trip/reclose cycle mode
All reclose attempts unsuccessful, control in lockout state
Figure 18: Status and Trip Target LEDs (English)
Phase A, B, or C involved in fault
FAULT TYPE
Ground involved in fault
DWG: M351P057
Sensitive earth fault overcurrent element trip
38 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
SEL-351P-3
Recloser Control is enabled
Indicates any of the following battery problems:
- discharge test failure
- disconnected
- cannot be charged
- monitor/charger failure
Vac power is present
Low SF6 gas pressure in recloser
Indicates that a trip occurred
(overcurrent or otherwise)
Fast curve overcurrent element trip
High-set overcurrent element trip
Underfrequency trip
Control in reset state and ready for reclose cycle
Control actively in trip/reclose cycle mode
All reclose attempts unsuccessful, control in lockout state
Figure 19: Status and Trip Target LEDs (Spanish)
Phase A, B, or C involved in fault
Ground involved in fault
Sensitive earth fault overcurrent element trip
The front-panel pushbuttons shown in Figure 20 and Figure 21 allow access to settings, metering values, event information, and other functions and information.
Primary Functions
TARGET
RESET
METER EVENTS STATUS OTHER SET CNTRL GROUP
LAMP
TEST CANCEL SELECT EXIT
DWG: M351R043
Secondary Functions
Figure 20: Primary and Secondary Functions of Front-Panel Pushbuttons (English)
39 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
Figure 21: Primary and Secondary Functions of Front-Panel Pushbuttons (Spanish)
The front-panel pushbuttons (except TARGET RESET/LAMP
TEST/PRUEBA LAMP./RESTABLECER) have dual functions (primary and secondary functions). The primary function is the text printed on the pushbutton. After a primary function is selected (e.g., the
STATUS/DIAGNO pushbutton is pressed), the secondary function pushbuttons (e.g., CANCEL/CANCELAR, SELECT/ACEPTAR, left/right arrows, up/down arrows, EXIT/SALIR) are then enabled. The secondary functions allow the user to scroll through information, activate settings/control, etc., on the LCD. The following table lists the primary and secondary functions for the pushbuttons shown in Figure 20 (English) and Figure 21 (Spanish).
Table 6: Front-Panel Pushbutton Secondary Functions
Primary Function Secondary Function
TARGET RESET/PRUEBA LAMP. HELP—Provides help only with front-panel
SET commands.
EVENTS/EVENTOS
STATUS/DIAGNO
OTHER/VARIOS
SET/CONFIG
CNTRL/CONTROL AUX.
GROUP/CONFIG GRUPO edit or escape to upper command level.
SELECT/ACEPTAR—Select displayed option or setting.
—Scroll left on display.
—Scroll right on display.
—Scroll up on display or increment value.
—Scroll down on display or decrement value.
EXIT/SALIR—Exit entirely from command and return to default display.
Many of the pushbutton primary functions correspond to serial port commands. Some of the pushbutton primary functions require a password to execute. Refer to Communications section for serial port command, access level, and password information.
40 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
Primary
Function
Corresponding
Serial Port
Command Access Level
TAR R 1
TARGET
RESET
LAMP
TEST
Password for
Front-Panel
Access
None
Description
Illuminate all front-panel LEDs for 1 second and clear trip-latched targets
TRIP/DISPARO, FAST CURVE/CURVA
RÁPIDA, HIGH CURRENT/ALTA
CORRIENTE, UNDER FREQ./BAJA
FREC., A, B, C, G/N, and SEF.
RESTABLECER
METER
Primary
Functions
Corresponding
Serial Port
Command
INST MET
Access Level
1
Password for
Front-Panel
Access
None
ENERGY
MAX/MIN
DISPLAY
RESET
DISPLAY MET E
RESET
DEMAND
MET RE
MET M
MET RM
DISPLAY MET D
RESET MET RD
MET RP
1
1
1
1
1
1
1 None
None
None
None
None
None
None
Description
Display instantaneous magnitudes (and angles if applicable) of meter values.
Display energy meter values.
Reset energy meter values.
Display maximum/minimum meter values.
Reset maximum/minimum meter values.
Display demand and peak demand meter values.
Reset demand meter values.
Reset peak meter values.
41 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
Primary
Function
Corresponding
Serial Port
Command
HIS
Access Level
1
Password for
Front-Panel
Access
None
Description
Show SEL-351P-3 event data.
EVENTS
EVENTOS
Primary
Function
STATUS
Corresponding
Serial Port
Command
STA
Access Level
1
Password for
Front-Panel
Access
None
Description
Show SEL-351P-3 diagnostic and battery information.
OTHER
Primary
Functions
Corresponding
Serial Port
Command Access Level
BTT BTT E
DATE DAT
TIME TIM
1
1
79 N/A N/A
Password for
Front-Panel
Access
Level E
None
None
None
TAR TAR
BRK_MON
DISPLAY BRE A
RESET BRE R
1
1
B
None
None
Level B
Description
Force 1 Amp load test on battery.
Show or set SEL-351P-3 date.
Show or set SEL-351P-3 time.
Show SEL-351P-3 set reclosures and current reclose count.
Show status of internal SEL-351P-3 elements on LCD display and second row of front-panel target LEDs.
Show recloser wear and trip operation counters.
Reset recloser wear and trip operation counters.
42 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
SET
Primary
Functions
SHOW
EZ
FZ
GROUP
GLOBAL
PORT
PASS
SET
EZ
FZ
GROUP
GLOBAL
PORT
PASS
Corresponding
Serial Port
Command
SHO EZ
SHO FZ
SHO
SHO G
SHO P
PASS
SET EZ
SET FZ
SET
SET G
SET P
PASS
Access Level
1
1
1
1
1
1
2
2
2
2
E
E
Password for
Front-Panel
Access
None
None
None
None
None
None
Level E
Level E
Level 2
Level 2
Level 2
Level 2
Description
Show EZ settings (group 1–6).
Show FZ settings (global EZ settings).
Show GROUP settings (group 1–6).
Show GLOBAL settings.
Show PORT settings.
Show passwords.
Set EZ settings (group 1–6).
Set FZ settings (global EZ settings).
Set GROUP settings (group 1–6).
Set GLOBAL settings.
Set PORT settings.
Set passwords.
CNTRL
Primary
Functions
EXTRA
CONTROL
POSITION
N/A
Corresponding
Serial Port
Command
OPERATE
OUTPUT
CONTACT
TEST
PUL
Access Level
N/A
2
Password for
Front-Panel
Access
None
Level 2
Description
View position of or operate extra userconfigured switch-type control.
Pulse output contact (OUT101–ALARM) for 1 second.
43 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
GROUP
Primary
Functions
Corresponding
Serial Port
Command
ACTIVE
GROUP
DISPLAY GRO
CHANGE GRO n
Access Level
1
B
Password for
Front-Panel
Access
None
Level B
Description
Show active setting group.
Change active setting group to setting group n .
Except for the REMOTE ENABLED/REMOTO HABILITADO operator control pushbutton, all the following operator control pushbuttons should be pressed momentarily to execute their function.
Note: The functions described below are based on the factory default settings and operator control labels. The operator-control labels can be user-configured.
Press the PROTECTION ENABLED/PROTECCION
HABILITADA operator control pushbutton to enable/disable all overcurrent element tripping. Corresponding LED illuminates to indicate the enabled state.
Pressing the CLOSE operator control also enables protection
(indicated by the PROTECTION ENABLED/PROTECCION
HABILITADA LED illuminating) if it is not already enabled.
LED
Operator Control
Pushbutton
44 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
Press the RECLOSE ENABLED/RECIERRE HABILITADO operator control pushbutton to enable/disable auto reclosing.
Corresponding LED illuminates to indicate the enabled state.
The RECLOSE ENABLED/RECIERRE HABILITADO operator control is overridden by the operation of the LIVE LINE
ENABLED/LINEA VIVA HABILITADA operator control in the following scenario:
Initial state: RECLOSE ENABLED/RECIERRE
HABILITADO “on” or “off” and LIVE LINE
ENABLED/LINEA VIVA HABILITADA
“off.”
Action: Press LIVE LINE ENABLED/LINEA VIVA
HABILITADA operator control pushbutton.
HABILITADO “off” and LIVE LINE
ENABLED/LINEA VIVA HABILITADA
“on.” The RECLOSE
ENABLED/RECIERRE HABILITADO operator control is now nonfunctional
(remains “off”).
RECLOSE ENABLED/RECIERRE HABILITADO cannot be turned “on” again, until LIVE LINE ENABLED/LINEA VIVA
HABILITADA is turned “off.” Once LIVE LINE
ENABLED/LINEA VIVA HABILITADA is “off,” the RECLOSE
ENABLED/RECIERRE HABILITADO operator control is then functional, but remains “off” until the RECLOSE
ENABLED/RECIERRE HABILITADO operator control pushbutton is pressed again.
The EARTH FAULT ENABLED/FALLA A TIERRA
HABILITADA and SEF ENABLED/SEF HABILITADO operator controls are interlocked as follows:
Initial state of both operators controls:
Press operator control: disabled
SEF enabled
EARTH FAULT/
FALLA A TIERRA
Final state of both operator controls: enabled disabled
EARTH FAULT ENABLED cannot be turned “off” again, until
SEF ENABLED is turned “off.” Once SEF ENABLED is “off,” the
EARTH FAULT ENABLED operator control is then functional, but remains “on” until the EARTH FAULT ENABLED operator control pushbutton is pressed again.
45
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
Continually press the REMOTE ENABLED/REMOTO
HABILITADO operator control pushbutton for three (3) seconds to engage/disengage the remote control. While this pushbutton is pressed, the corresponding LED flashes on and off, indicating a pending engagement or disengagement of the remote control. The
LED illuminates constantly to indicate the engaged state (“on”).
REMOTE ENABLED/REMOTO HABILITADO “on” (local control is “off”):
All the other operator controls (except WAKE
UP/DESPERTAR) are inoperable. Remote control of these functions (via the serial port or optoisolated input) is enabled.
REMOTE ENABLED/REMOTO HABILITADO “off” (local control is “on”):
The other operator controls are operable. Remote control of these functions (via the serial port or optoisolated input) is disabled.
Press the LIVE LINE ENABLED/LINEA VIVA HABILITADA operator control pushbutton to enable/disable the live line function.
Corresponding LED illuminates to indicate the enabled state.
While the live line function is enabled, no closing or auto reclosing can take place via the control (e.g., the CLOSE/CIERRE operator control is inoperative). The LIVE LINE ENABLED/LINEA VIVA
HABILITADA operator overrides the RECLOSE
ENABLED/RECIERRE HABILITADO operator control (see previous RECLOSE ENABLED/RECIERRE HABILITADO operator control description).
While the live line function is enabled, the active settings group is
Settings Group 3. When the live line function is then disabled, the active setting group reverts back to the previous active setting group
(Settings Group 1 or Settings Group 2).
Press the ALTERNATE SETTINGS/AJUSTES ALTERNATIVOS operator control pushbutton to switch the active setting group between the main setting group (Settings Group 1) and the alternate setting group (Settings Group 2). Corresponding LED illuminates to indicate that the alternate setting group is active. This LED illuminates only when Settings Group 2 is the active setting group (it does not illuminate for Settings Group 1 or 3).
The LIVE LINE ENABLED/LINEA VIVA HABILITADO operator control switches the active setting group to Settings
Group 3 (see previous LIVE LINE ENABLED/LINEA VIVA
HABILITADA operator control description).
(press for 3 sec)
(pulsar por 3 seg)
46 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Press the WAKE UP/DESPERTAR operator control pushbutton to wake up the SEL-351P-3 if the front panel is dark (the unit put itself to sleep after an extended outage). After the unit wakes up, the front panel illuminates, and the unit can then be interrogated via the front panel or serial port.
The WAKE UP/DESPERTAR operator control is also used to turn on the SEL-351P-3 after the battery has been installed (see the installation steps in the Installation section).
The SEL-351P-3 wakes up automatically from an extended outage when power returns to the unit.
Front-Panel Interface
47 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
Press the CLOSE/CIERRE operator control pushbutton to close the recloser. The corresponding RECLOSER
CLOSED/RESTAURADOR CERRADO LED illuminates to indicate the recloser is closed.
The CLOSE/CIERRE operator control pushbutton does not have to be continually pressed to allow for cold load pickup (i.e., disable fast curves, and desensitize delay curves and SEF element). There is automatic allowance for cold load pickup. See Cold Load Pickup
Scheme (No. 33) settings in the Settings section.
Option : Set a delay, so the operator can press the CLOSE/CIERRE operator control pushbutton and then move a safe distance away from the recloser before the SEL-351P-3 issues a close (the
CLOSE/CIERRE operator control comes with no set delay in the factory settings). With a set delay, press the CLOSE/CIERRE operator control pushbutton momentarily, and notice that the corresponding RECLOSER CLOSED/RESTAURADOR
CERRADO LED flashes on and off during the delay time, indicating a pending close. Abort the pending close by pressing the
CLOSE/CIERRE operator control pushbutton again or by pressing the TRIP/DISPARO operator control pushbutton. This delay setting for the CLOSE/CIERRE operator control is PB8D (range: 0 to 3600 cycles; factory-set at 0 cycles—no delay). The delay is set via the
SET G command (PB8D is not an EZ setting). See Section 1:
Factory-Set Logic in the SEL-351P-3 Instruction Manual for more information.
English
Spanish
Pressing the CLOSE/CIERRE operator control also enables protection (indicated by the PROTECTION
ENABLED/PROTECCION HABILITADA LED illuminating) if it is not already enabled.
Note: The time-delay setting for the PB8 operator control (global setting PB8D) should be left set to the factory default of
PB8D = 0 cycles (no time delay) if the control is programmed to operate independently of the close logic. If
PB8D > 0 cycles, the operation of corresponding Relay
Word bit PB8 will be supervised by SEL OGIC setting ULCL
(unlatch close). If ULCL is asserted (logical 1), this operator will be effectively disabled.
RECLOSER
CLOSED
RESTAURADOR
CERRADO
48 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Front-Panel Interface
Press the TRIP/DISPARO operator control pushbutton to trip the recloser (and take the control to the lockout state). The corresponding RECLOSER OPEN/RESTAURADOR ABIERTO
LED illuminates to indicate the recloser is open.
Option : Set a delay, so the operator can press the TRIP/DISPARO operator control pushbutton and then move a safe distance away from the recloser before the SEL-351P-3 issues a trip (the
TRIP/DISPARO operator control comes with no set delay in the factory settings). With a set delay, press the TRIP/DISPARO operator control pushbutton momentarily and notice the corresponding RECLOSER OPEN/RESTAURADOR ABIERTO
LED flashes on and off during the delay time, indicating a pending trip. Abort the pending trip by pressing the TRIP/DISPARO operator control pushbutton again or by pressing the
CLOSE/CIERRE operator control pushbutton. This delay setting for the TRIP/DISPARO operator control is PB9D (range: 0 to 3600 cycles; factory-set at 0 cycles—no delay). The delay is set via the
SET G command (PB9D is not an EZ Setting). See Section 1:
Factory-Set Logic in the SEL-351P-3 Instruction Manual for more information.
Note: The time-delay setting for the PB9 operator control (global setting PB9D) should be left set to the factory default of
PB9D = 0 cycles (no time delay) if the control is programmed to operate independently of the trip logic.
English
Spanish
RECLOSER
OPEN
RESTAURADOR
ABIERTO
49 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
S
Important:
This Quick-Start Installation and User's Guide provides only information applicable to the EZ settings—settings associated with traditional recloser control operations.
This section details the EZ (“easy”) settings—the settings used to perform traditional recloser control operations.
Topics covered in this section:
• Curve Designations
• EZ (“Easy”) Settings
• Global EZ Settings
• EZ Settings Sheets (end of Settings section)
Curve Modifiers Available for Any Curve Type:
• Constant Time Adder
• Vert. Multiplier/Time Dial
• Min. Response Time
High Current Options
Available for Phase and
Ground:
• High Current Trip
• High Current Lockout
Fast and delay curves are available for phase and ground overcurrent protection. These curves can be set with any of the numerous resident curve choices:
• Recloser Curves (see Table 7)
• US Curves (see Table 8)
• IEC Curves (see Table 8)
• User-Programmable Curves (see Table 8)
The recloser curves in Table 7 show both the older electronic control designation and the newer microprocessor-based control designation. The recloser curves can be specified in a curve setting using either designation.
For example, a given traditional recloser curve has the following two designations:
Older electronic control designation: A
Newer microprocessor-based control designation: 101
Traditional recloser curve A and curve 101 are the same curve —use either designation in making curve settings in the SEL-351P-3.
50 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Curves Conform to Standard:
The US and IEC curves conform to IEEE C37.112-1996
IEEE Standard Inverse-Time
Characteristic Equations for
Overcurrent Relays .
Settings
Table 7: Recloser Curve Designations
Recloser Curve Cross Reference—Old to New
Old
E
F
G
H
A
B
C
D
J
KP
L
M
N
New Old
101 P
117 R
133 T
116 V
132 W
163 Y
121 Z
122 1
164 2
162 3
107 4
118 5
104 6
New Old
135 15
140 16
106 17
114 18
136
New
115 7
105 8
152
113
161 8PLUS 111
137 9 131
138 KG
120 11
134 13
102 14
165
141
142
119
112
139
103
151
Table 8: US, IEC, and User-Programmable Curve Designations
US Curve Description
U2 inverse
IEC Curve
C1
C2
C3
Description class A (standard inverse) class B (very inverse) class C (extremely inverse)
User Designed Curves:
Created with SEL-5804 software.
• 3.5” high-density disk
• Requires Windows 3.1 or later
User-Programmable
Curves (factory-set)
DEF_01
DEF_05
DEF_1
DEF_5
Description definite-time curve (0.1 seconds) definite-time curve (0.5 seconds) definite-time curve (1.0 seconds) definite-time curve (5.0 seconds)
The four (4) user-programmable curves are factory-set as shown in
Table 8, with definite-time characteristics. User-designed curves (created with the SEL-5804 TOC [Time-Overcurrent] Recloser Curve Designer software package) can be downloaded instead to any of the four userprogrammable curves in the SEL-351P-3.
51 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
View EZ Settings With
Commands:
SHO EZ 1 (Group 1)
SHO EZ 2 (Group 2)
SHO FZ (Global)
See Table 3 in the
Communications section.
Set EZ Settings With
Commands:
SET EZ 1 (Group 1)
SET EZ 2 (Group 2)
SET FZ (Global)
See Table 3 in the
Communications section.
Settings Group 3
With factory settings, the LIVE
LINE ENABLED/LINEA VIVA
HABILITADA operator control activates Settings Group 3 when it is engaged—see explanation in the Operator
Controls subsection in the
Front-Panel Interface section.
Thus, certain future settings changes made to Settings
Groups 1 and/or 2 should perhaps be made to Settings
Group 3, too.
The SEL-351P-3 ships with the factory EZ settings shown in Table 9.
The corresponding number references provide a quick way to find the settings (or subsettings) in the Settings Descriptions subsection that follows.
The reference to Settings Groups 1 and 2 at the top of Table 9 refers to the two choices for the active setting group:
Settings Group 1 = main settings
Settings Group 2 = alternate settings
Refer to the Operator Controls subsection in the Front-Panel Interface section (ALTERNATE SETTINGS/AJUSTES ALTERNATIVOS operator control pushbutton) for more information on how to switch between these two setting groups. In the factory EZ settings, these two setting groups are set the same (Settings Group 3 set the same, too—see side bar note).
The Global EZ settings at the end of Table 9 apply to both settings
Groups 1 and 2 (and Settings Group 3—see side bar note).
Those factory settings indicated with an asterisk (*) in Table 9 are hidden with these particular factory settings. As a general rule, if a main setting is set to N, then the subsettings that follow are hidden. The following
Settings Descriptions subsection explains the details behind hiding the settings. Complete setting ranges are also given in the Settings
Descriptions subsection.
!
WARNING: Anytime an EZ setting is changed, review all the EZ settings before enabling the new settings. Pay close attention in circumstances where a setting was once set to OFF or N and then later turned on (enabled)—other related settings may need to be turned on, though may still be set to OFF or N.
52 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
53
Settings
Table 9: EZ Settings Quick Reference
No. Settings Groups 1 (Main) and 2 (Alternate) EZ
Settings:
Factory Settings:
1
2
3
4
5
6
7
8
9
Control Identifier
Circuit Identifier
CT Ratio
PT Ratio
Min. trip - phase (A pri.)
Min. trip - ground (A pri.)
Min. trip - SEF (A pri.)
Fast curve - phase
Time dial - phase fast curve
EM reset - phase fast curve
Fast curve - ground
Time dial - ground fast curve
EM reset - ground fast curve
10 Delay curve - phase
Time dial - phase delay curve
EM reset - phase delay curve
11
12 Time delay - SEF (cycles)
13 Operations - phase fast curve
14
15
16
17
Delay curve - ground
Time dial - ground delay curve
EM reset - ground delay curve
Operations - ground fast curve
Operations to lockout - phase
Operations to lockout - ground
Operations to lockout - SEF
18 Reclose interval 1 (cycles)
19 Reclose interval 2 (cycles)
N
C1
0.10
N
50.00
3
3
4
4
4
32.25
45.00
C5
0.05
N
C5
0.05
N
C1
0.10
SEL-351P-3 RECLOSER
CONTROL
FEEDER
400.0
100.0
200.00
20.00
10.00
20 Reclose interval 3 (cycles) 245.00
21 Reclose interval 4 (cycles)
22
23
24
25
26
27
28
Reset time for auto reclose (cycles)
Reset time from lockout (cycles)
Close power wait time (cycles)
Complex fast curve - phase (Y/N)
Const. time adder - phase fast curve (cycles)
Vert. multiplier - phase fast curve
Min. response - phase fast curve (cycles)
Complex fast curve - ground (Y/N)
Const. time adder - ground fast curve (cycles)
Vert. multiplier - ground fast curve
Min. response - ground fast curve (cycles)
Complex delay curve - phase (Y/N)
Const. time adder - phase delay curve (cycles)
Vert. multiplier - phase delay curve
Min. response - phase delay curve (cycles)
Complex delay curve - ground (Y/N)
Const. time adder - ground delay curve (cycles)
Vert. multiplier - ground delay curve
Min. response - ground delay curve (cycles)
N
0.00*
1.00*
0.00*
N
0.00*
1.00*
0.00*
0.00*
50.00
50.00
0.00
N
0.00*
1.00*
0.00*
N
0.00*
1.00*
0.00*
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Settings Groups 1 (Main) and 2 (Alternate) EZ
Settings:
Factory Settings:
29 High current trip - phase (Y/N)
High current trip - phase (multiple)
Time delay - phase high current trip (cycles)
Activate high current trip - phase
30 High current trip - ground (Y/N)
High current trip - ground (multiple)
Time delay - ground high current trip (cycles)
Activate high current trip - ground
31 High current lockout - phase (Y/N)
High current lockout - phase (multiple)
Activate high current lockout - phase
32 High current lockout - ground (Y/N)
High current lockout - ground (multiple)
Activate high current lockout - ground
33 Cold load pickup scheme (Y/N)
Cold load pickup - phase (multiple)
Cold load pickup - ground (multiple)
Loss of load diversity time (cycles)
Restore min. trips - time limit (cycles)
Restore min. trip - phase (Y/N)
Restore min. trip - ground (Y/N)
Restore min. trip - SEF (Y/N)
34 Sequence coordination (Y/N)
35 Ground trip precedence (Y/N)
36 Underfrequency load shedding (Y/N)
Underfrequency pickup (Hz)
Underfrequency time delay (cycles)
37 Demand meter time constant (min.)
Global EZ Settings:
38
39
40
System Frequency (Hz)
Phase Rotation
Recloser Wear Monitor (AUTO,Y,N)
Interrupt rating (A pri.)
41 Reset trip-latched LEDs on close (Y,Y1,N,N1)
42 True three-phase voltage connected (Y,N)
43 Phantom voltages from (VA,VB,VC,VAB,VBC,VCA,OFF) OFF
44 V123 Terminal Conn. (A,B,C,AB,BC,CA,OFF)
45
46
47
48
49
50
51
I123 Terminal Conn. (ABC,ACB,BAC,BCA,CAB,CBA)
CT Polarity (POS,NEG)
Battery Amp-hours (6.5 – 20.0)
Power-off Delay After AC Loss (OFF, 1 – 1440 min)
Power-off Delay After Wake Up (OFF, 1 – 1440 min)
Power-off Voltage Level 1 (19.2 – 24 Vdc)
SF6 low pressure warning threshold in atmospheres (0.9 -
A
ABC
POS
8.0
180
20
20.5
1.1
2)
*See comments preceding Table 9.
50
ABC
AUTO
12500
Y
N
OFF*
0.00*
OFF*
N*
N*
N*
N
N*
N
OFF*
6.00*
5
N
OFF*
OFF*
N
OFF*
OFF*
N
OFF*
N
OFF*
0.00*
OFF*
N
OFF*
0.00*
OFF*
54 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
!
WARNING: Anytime an EZ setting is changed, review all the EZ settings before enabling the new settings. Pay close attention in circumstances where a setting was once set to OFF or N and then later turned on (enabled)—other related settings may need to be turned on, though may still be set to OFF or N.
No. Setting Default
SEL-351P-3
RECLOSER
CONTROL
Range
0–9, A–Z, - , / , . , space
Incr.
The Control Identifier setting contains the control installation designation (e.g., SEL-351P-3 RECLOSER
CONTROL). This identifier is listed at the top of event, history, meter, and status reports (see Table 3).
• This setting may be up to 30 characters long.
• This setting cannot be made via the front-panel interface.
No. Setting
2 Circuit Identifier
Default
FEEDER
Range
0–9, A–Z, - , / , . , space
Incr.
The Circuit Identifier setting contains the greater circuit or substation designation (e.g., FEEDER). This identifier is listed at the top of event, history, meter, and status reports (see Table 3).
• This setting may be up to 30 characters long.
• This setting cannot be made via the front-panel interface.
No. Setting Default
400.0 1.0–6000.0
Range Incr.
0.1
The CT Ratio (current transformer [CT] ratio) setting programs the SEL-351P-3 to operate with a recloser CT ratio (e.g., for the recloser CT ratio 400:1, the setting CT Ratio = 400.0 is made). See recloser
CTs (connected to the primary system) on the left-hand side of Figure 10 and Figure 11.
• See discussion following Figure 11 for more CT Ratio setting considerations for SEL-351P-3 models with low-level (0.01 phase/0.005 neutral) current inputs.
• WARNING: The following settings change in accordance to the CT Ratio setting:
Min. trip - phase (No. 5)
Min. trip - ground (No. 6)
Min. trip - SEF (No. 7)
55 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting Default Range
100.0 1.0–10000.0
Incr.
0.1
The PT Ratio (potential transformer [PT] ratio) setting programs the SEL-351P-3 to operate with the effective ratio of the external voltage step-down device connected to the voltage inputs of Figure 9 (e.g., for the PT ratio of 7200:120, the setting PT Ratio = 60.0 is made).
• For applications where single-phase Vac power is the only voltage brought to the SEL-351P-3 (and also connected to a voltage input of Figure 9(a) for metering/monitoring), the PT ratio should still be entered, otherwise the SEL-351P-3 voltage metering/monitoring information will not be accurate.
Enter the effective power transformer ratio, relative to the Vac secondary winding.
• See discussion following Figure 9 for more PT Ratio setting considerations for SEL-351P-3 models with low-level (3 Vac) voltage inputs as shown in Figure 9(b) and Figure 9(c).
No. Setting
5 Min. trip - phase
Default
200.00
Range
OFF, 40.00–1279.99 Amps primary
Incr.
0.01
The Min. trip - phase in primary amps.
setting determines the minimum phase current threshold for overcurrent detection
The displayed Amps primary setting range for Min. trip - phase is calculated by multiplying the effective
Amps secondary range [0.10 to 3.20] by the CT Ratio (No. 3) [400.0]:
(0.10 to 3.20) • 400.0 = 40.00 to 1280.00 range (Amps primary)
If the CT Ratio setting changes, the displayed Amps primary setting range for Min. trip - phase changes accordingly. Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 1279.99 instead of 1280.00).
• WARNING: If Min. trip - phase (No. 5) , Min. trip - ground (No. 6), and Min. trip - SEF (No. 7) are all set to OFF, then overcurrent protection and reclosing are disabled.
• WARNING: If Min. trip - phase is set to OFF, then the following settings are all hidden and set to
OFF or N:
Fast curve - phase (No. 8)
Delay curve - phase (No. 10)
Complex fast curve - phase (No. 25)
Complex delay curve - phase (No. 27)
Operations - phase fast curve (No. 13)
Operations to lockout - phase (No. 15)
High current trip - phase (No. 29)
High current lockout - phase (No. 31)
56 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
6 Min. trip - ground
Default
20.00
Range
OFF, 2.00–1279.99 Amps primary
Incr.
0.01
The Min. trip - ground setting determines the minimum ground current threshold for overcurrent detection in primary amps.
The displayed Amps primary setting range for Min. trip - ground is calculated by multiplying the effective
Amps secondary range [0.005 to 3.20] by the CT Ratio (No. 3) [400.0]:
(0.005 to 3.20) • 400.0 = 2.00 to 1280.00 range (Amps primary)
If the CT Ratio setting changes, the displayed Amps primary setting range for Min. trip - ground changes accordingly. Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 1279.99 instead of 1280.00).
If Min. trip - ground is effectively set <0.1 Amp secondary (e.g., for CT ratio [No. 3] = 400.0, Min. trip - ground <40.00 Amps primary), then the corresponding curves flatten out above 1.5 Amps secondary (e.g., for CT ratio [No. 3] = 400.0, Fast curve - ground [No. 9] and Delay curve - ground [No. 11] flatten out above 600 Amps primary).
• WARNING: If Min. trip - phase (No. 5) , Min. trip - ground (No. 6), and Min. trip - SEF (No. 7) are all set to OFF, then overcurrent protection and reclosing are disabled.
• WARNING: If Min. trip - ground is set to OFF, then the following settings are all hidden and set to
OFF or N:
Fast curve - ground (No. 9)
Delay curve - ground (No. 11)
Operations - ground fast curve (No. 14)
Operations to lockout - ground (No. 16)
Complex fast curve - ground (No. 26)
Complex delay curve - ground (No. 28)
High current trip - ground (No. 30)
High current lockout - ground (No. 32)
No. Setting
7 Min. trip - SEF
Default
10.00
Range
OFF, 2.00–599.99 Amps primary
Incr.
0.01
The Min. trip - SEF setting determines the minimum sensitive earth fault threshold for overcurrent detection set in primary Amps.
The displayed Amps primary setting range for Min. trip - SEF is calculated by multiplying the effective
Amps secondary range [0.005 to 1.500] by the CT Ratio (No. 3) [400.0]:
(0.005 to 1.500) • 400.0 = 2.00 to 600.00 range (Amps primary)
If the CT Ratio setting changes, the displayed Amps primary setting range for Min. trip - ground changes accordingly. Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 599.99 instead of 600.00).
• WARNING: If Min. trip - phase (No. 5) , Min. trip - ground (No. 6), and Min. trip - SEF (No. 7) are all set to OFF, then overcurrent protection and reclosing are disabled.
• WARNING: If Min. trip - SEF is set to OFF, then the following settings are all hidden and set to zero (0) and OFF, respectively:
Time delay - SEF (No. 12)
Operations to lockout - SEF (No. 17)
57 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
8 Fast curve - phase
Default
C5
Range
OFF, U1–U5, C1–C5, recloser or user curve
The Fast curve - phase setting selects the time-overcurrent curve for phase fast curve tripping. Curve designations are provided in Table 7 and Table 8.
Incr.
• This setting is hidden and set to OFF if Min. trip - phase (No. 5) is set to OFF.
• If Fast curve - phase is programmed with a US (U1–U5) or IEC (C1–C5) curve, enter the following two settings:
Setting
Time-dial - phase fast curve
Default Range
0.05 0.50–15.00 for US curves U1–U5
0.05–1.00 for IEC curves C1–C5
The Time-dial - phase fast curve multiplier.
setting shifts the US or IEC curve in time by the entered
Incr.
0.01
0.01
• This setting is hidden and nonoperative if Fast curve - phase is programmed with a recloser or user curve.
Setting
EM reset - phase fast curve
Default
N Y/N
Range Incr.
The EM reset - phase fast curve or IEC curve, if set to Y.
setting enables the electromechanical reset emulation for the US
• This setting is usually set to N, except for special applications.
• This setting is hidden and set to N if Fast curve - phase is programmed with a recloser or user curve.
No.
9
Setting
Fast curve - ground
Default
C5
Range
OFF, U1–U5, C1–C5, recloser or user curve
Incr.
The Fast curve - ground setting selects the time-overcurrent curve for ground fast curve tripping. Curve designations are provided in Table 7 and Table 8.
If Min. trip - ground (No. 6) is effectively set <0.1 Amp secondary (e.g., for CT ratio [No. 3] = 400.0,
Min. trip - ground (No. 6) <40.00 Amps primary), then Fast curve - ground flattens out above 1.5 Amps secondary (e.g., for CT ratio [No. 3] = 400.0, Fast curve - ground flattens out above 600 Amps primary).
• This setting is hidden and set to OFF if Min. trip -ground (No. 6) is set to OFF.
• If Fast curve - ground is programmed with a US (U1–U5) or IEC (C1–C5) curve, enter the following two settings:
58 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
Setting
Time-dial - ground fast curve
Default
0.05
Range
0.50–15.00 for US curves U1–U5
0.05–1.00 for IEC curves C1–C5
The Time-dial - ground fast curve multiplier.
setting shifts the US or IEC curve in time by the entered
Incr.
0.01
0.01
• This setting is hidden and nonoperative if Fast curve - ground is programmed with a recloser or user curve.
Setting
EM reset - ground fast curve
Default
N Y/N
Range Incr.
The EM reset - ground fast curve
US or IEC curve, if set to Y.
setting enables the electromechanical reset emulation for the
• This setting is usually set to N, except for special applications.
• This setting is hidden and set to N if Fast curve - ground is programmed with a recloser or user curve.
No.
10
Setting
Delay curve - phase
Default
C1
Range
OFF, U1–U5, C1–C5, recloser or user curve
Incr.
The Delay curve - phase setting selects the time-overcurrent curve for phase delay curve tripping. Curve designations are provided in Table 7 and Table 8.
• This setting is hidden and set to OFF if Min. trip -phase (No. 5) is set to OFF.
• If Delay curve - phase is programmed with a US (U1–U5) or IEC (C1–C5) curve, enter the following two settings:
Setting
Time-dial - phase delay curve
Default
0.10
Range
0.50–15.00 for US curves U1–U5
0.05–1.00 for IEC curves C1–C5
The Time-dial - phase delay curve multiplier.
setting shifts the US or IEC curve in time by the entered
Incr.
0.01
0.01
• This setting is hidden and nonoperative if Delay curve - phase is programmed with a recloser or user curve.
Setting
EM reset - phase delay curve
Default
N Y/N
Range Incr.
The EM reset - phase delay curve
US or IEC curve, if set to Y.
setting enables the electromechanical reset emulation for the
• This setting is usually set to N, except for special applications.
• This setting is hidden and set to N if Delay curve - phase is programmed with a recloser or user curve.
59 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No.
11
Setting
Delay curve - ground
Default
C1
Range
OFF, U1–U5, C1–C5, recloser or user curve
Incr.
The Delay curve - ground setting selects the time-overcurrent curve for ground fast curve tripping. Curve designations are provided in Table 7 and Table 8.
If Min. trip - ground (No. 6) is effectively set <0.1 Amp secondary (e.g., for CT ratio [No. 3] = 400.0,
Min. trip - ground [No. 6] <40.00 Amps primary), then Delay curve - ground flattens out above 1.5
Amps secondary (e.g., for primary).
CT ratio [No. 3] = 400.0, Delay curve - ground flattens out above 600 Amps
• This setting is hidden and set to OFF if Min. trip - ground (No. 6) is set to OFF.
• If Delay curve - ground is programmed with a US (U1–U5) or IEC (C1–C5) curve, enter the following two settings:
Setting
Time-dial - ground delay curve
Default
0.10
Range
0.50–15.00 for US curves U1–U5
0.05–1.00 for IEC curves C1–C5
The Time-dial - ground delay curve multiplier.
setting shifts the US or IEC curve in time by the entered
Incr.
0.01
0.01
• This setting is hidden and nonoperative if Delay curve - ground is programmed with a recloser or user curve.
Setting
EM reset - ground delay curve
Default
N Y/N
Range Incr.
The EM reset - ground delay curve
US or IEC curve, if set to Y.
setting enables the electromechanical reset emulation for the
• This setting is usually set to N, except for special applications.
• This setting is hidden and set to N if Delay curve - ground is programmed with a recloser or user curve.
No. Setting
12 Time delay - SEF
Default
50.00
Range
0–16000.00 cycles
Incr.
0.25 cyc.
The Time delay - SEF setting programs an intentional time delay for the definite-time SEF (sensitive earth fault) overcurrent element. This is in addition to the built-in 2-cycle time delay.
• This setting is hidden and set to zero (0) if Min. trip - SEF (No. 7) is set to OFF.
60 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
13 Operations - phase fast curve
Default Range Incr.
1
The Operations - phase fast curve setting determines the number of phase fast curve trip operations (e.g., if Operations - phase fast curve = 2, then the phase fast curve is enabled for the first two [2] trip operations).
• This setting is hidden and set to OFF if Fast curve - phase (No. 8) is set to OFF.
• This setting only enables the phase fast curve operations; it does not disable the phase delay curve (the phase delay curve is always active). Traditional protection schemes use fast curves followed by delay curves so the delay curves do not have to be defeated. If a slower first operation than second operation is desired, higher logic level settings changes are required .
No. Setting
14 Operations - ground fast curve
Default Range Incr.
1
The Operations - ground fast curve setting determines the number of ground fast curve trip operations
(e.g., if Operations - ground fast curve = 2, then the ground fast curve is enabled for the first two [2] trip operations).
• This setting is hidden and set to OFF if Fast curve - ground (No. 9) is set to OFF.
• This setting only enables the ground fast curve operations; it does not disable the ground delay curve
(the ground delay curve is always active, provided that the EARTH FAULT ENABLED/FALLA A
TIERRA HABILITADA operator control is on). Traditional protection schemes use fast curves followed by delay curves so the delay curves do not have to be defeated. If a slower first operation than second operation is desired, higher logic level settings changes are required.
No. Setting
15 Operations to lockout - phase
Default Range Incr.
1
The Operations to lockout - phase setting determines the total number of phase curve trip operations. The difference between setting Operations to lockout - phase and setting Operations - phase fast curve
(No. 13) is the number of remaining phase delay curve operations (e.g., 4 – 2 = 2).
The setting range for Operations to lockout - phase adjusts according to Operations - phase fast curve
(e.g., if Operations - phase fast curve = 2, then the range for Operations to lockout - phase is from 2 to 5).
• If Delay curve - phase (No. 10) = OFF, then Operations to lockout - phase is set automatically equal to Operations - phase fast curve , and there are no phase delay curve operations (e.g., 2 – 2 = 0).
• This setting is hidden and set to OFF if Min. trip - phase (No. 5) is set to OFF.
• WARNING: If Operations to lockout - phase (No. 15), Operations to lockout - ground (No. 16), and
Operations to lockout - SEF (No. 17) are all set to OFF, then overcurrent protection and reclosing are disabled.
However, if both Min. trip - phase (No. 5) and Delay curve - phase (No. 10) are set to values other than OFF, the phase delay curve element is still active. If absolutely no phase protection is desired (e.g.,
“switch” mode), Min. trip - phase (No. 5) or Delay curve - phase (No. 10) must also be set to OFF.
61 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
16 Operations to lockout - ground
Default Range Incr.
1
The Operations to lockout - ground setting determines the total number of ground curve trip operations.
The difference between setting Operations to lockout - ground and setting Operations - ground fast curve
(No. 14) is the number of remaining ground delay curve operations (e.g., 4 – 2 = 2).
The setting range for Operations to lockout - ground adjusts according to Operations - ground fast curve
(e.g., if Operations - ground fast curve = 2, then the range for Operations to lockout - ground is from 2 to 5).
• If Delay curve - ground (No. 11) = OFF, then Operations to lockout - ground is set automatically equal to Operations - ground fast curve , and there are no ground delay curve operations (e.g., 2 – 2 =
0).
• This setting is hidden and set to OFF if Min. trip - ground (No. 6) is set to OFF.
• WARNING: If Operations to lockout - phase (No. 15), Operations to lockout - ground (No. 16), and
Operations to lockout - SEF (No. 17) are all set to OFF, then overcurrent protection and reclosing are disabled.
However, if both Min. trip - ground (No. 6) and Delay curve - ground (No. 11) are set to values other than OFF, the ground delay curve element is still active (provided the EARTH FAULT
ENABLED/FALLA A TIERRA HABILITADA operator control is on). If absolutely no ground protection is desired (e.g., “switch” mode), Min. trip - ground (No. 6) or Delay curve - ground (No.
11) must also be set to OFF.
No.
17
Setting
Operations to lockout - SEF
Default
OFF OFF, 1–5
Range Incr.
1
The Operations to lockout - SEF operations.
setting determines the number of SEF (sensitive earth fault) element trip
• This setting is hidden and set to OFF if Min. trip - SEF (No. 7) is set to OFF.
• WARNING: If Operations to lockout - phase (No. 15), Operations to lockout - ground (No. 16), and
Operations to lockout - SEF (No. 17) are all set to OFF, then overcurrent protection and reclosing are disabled. See similar warnings for preceding setting number 15 and setting number 16.
62 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
Table 10: Seconds-to-Cycles Conversion (60 Hz)
Seconds
(50 Hz)
Cycles
(60 Hz)
Seconds
(50 Hz)
Cycles
(60 Hz)
0.3 15 18
0.5 25 30
15 750 900
1 50 60 30 1500
2 100 2700
3 150 3600
5 250 5400
10 500 600 180 9000 for 50 Hz systems: _____ seconds • 50 cycles/second = _____ cycles
_____ minutes • 3000 cycles/minute = _____ cycles for 60 Hz systems: _____ seconds • 60 cycles/second = _____ cycles
_____ minutes • 3600 cycles/minute = _____ cycles
63 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
18 Reclose interval 1
19 Reclose interval 2
20 Reclose interval 3
21 Reclose interval 4
Default
32.50
45.00
245.00
0.00
Range (see Note below)
0–999999.00 cycles
0–999999.00 cycles
0–999999.00 cycles
0–999999.00 cycles
Incr.
0.25 cyc.
0.25 cyc.
0.25 cyc.
0.25 cyc.
The Reclose interval settings (1 through 4) are each successively and individually timed. Reclose interval timing cannot proceed until the following two conditions are met:
• The trip condition has gone away.
• The recloser has opened.
At the end of a reclose interval, an auto reclose attempt is made.
The number of available
15, 16, or 17) setting.
Reclose interval settings corresponds to the highest set Operations to lockout (No.
For example, if the highest set Operations to lockout setting is Operations to lockout - phase (No. 15) = 4, then settings Reclose interval 1 , Reclose interval 2 , and Reclose interval 3 are available (three reclose attempts). Because it is not available, Reclose interval 4 is hidden and set to zero (0).
The number of reclosing attempts (i.e., available Reclose interval settings) is always one less than the number of trip operations (e.g., 4 “trips” – 1 = 3 “reclosures”).
• All the Reclose interval settings are hidden and set to zero (0) if none of the Operations to lockout
(No. 15, 16, or 17) settings are set greater than 1 (reclosing is disabled; 1 “trip” – 1 = 0 “reclosures”).
• If a Reclose interval setting is set to zero (0), the corresponding auto reclose attempt and any following auto reclose attempts are aborted.
• Note: Reclose intervals should not be set less than 30 cycles, otherwise the control will go to lockout prematurely.
No. Setting
22 Reset time for auto reclose
23 Reset time from lockout
Default
50.00
50.00
Range
0–999999.00 cycles
0–999999.00 cycles
Incr.
0.25 cyc.
0.25 cyc.
The Reset time for auto reclose setting qualifies an auto reclose of the recloser. The Reset time from lockout setting qualifies a manual/remote close of the recloser from the lockout state. Traditionally, the
Reset time from lockout setting is set shorter than the Reset time for auto reclose setting.
Reset timing is blocked (and the reset timer is reloaded) if any overcurrent elements are picked up. Reset timing can only proceed if all the overcurrent elements are continually dropped out.
• Both the Reset time for auto reclose and Reset time from lockout settings are hidden and set to zero
(0) if none of the Operations to lockout (No. 15, 16, or 17) settings are set greater than 1 (reclosing is disabled; 1 “trip” – 1 = 0 “reclosures”).
64 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
24 Close power wait time
Default
0.00
Range
0–16000.00 cycles
Incr.
0.25 cyc.
The Close power wait time setting is a time window that starts timing after a reclose interval times out.
During this time window, the SEL-351P-3 checks the trip and close capacitors connected to it:
• If the trip and close capacitors are charged, this indicates that the close power for the recloser is present, and reclosing proceeds.
• If the trip and close capacitors are not charged, this indicates that the close power for the recloser is not present and reclosing is stalled. If the trip and close capacitors are not charged throughout the time window, reclosing is aborted at the end of the time window, and the SEL-351P-3 goes to the lockout state.
The 24 Vdc battery also has to be connected and healthy in order for reclosing to proceed.
• If Close power wait time is set to 0 cycles, then the SEL-351P-3 makes only one check for charged trip and close capacitors, after a reclose interval times out.
• This setting is hidden and set to 0 cycles if none of the Operations to lockout (No. 15, 16, or 17) settings are set greater than 1 (reclosing is disabled; 1 “trip” – 1 = 0 “reclosures”).
No.
25
Setting
Complex fast curve - phase
Default
N Y/N
Range Incr.
The
Y.
Complex fast curve - phase setting enables the following three settings for the phase fast curve, if set to
• This setting is hidden and set to N if Fast curve - phase (No. 8) is set to OFF.
Const. time adder - phase fast curve
Setting Default
0.00 0–60.00 cycles
Range Incr.
0.25 cyc.
The Const. time adder - phase fast curve set to other than 0 cycles.
setting adds a constant time to the phase fast curve, if
• This setting is hidden and set to zero (0) if Complex fast curve - phase is set to N.
Vert. multiplier - phase fast curve
Setting Default Range
1.00 0.10–2.00
Incr.
0.01
The Vert. multiplier - phase fast curve setting shifts the phase fast curve in time, by the entered multiplier, if Fast curve - phase (No. 8) is programmed with a recloser or user curve. If no particular multiplier is desired, set Vert. multiplier - phase fast curve equal to 1.00.
• If Fast curve - phase (No. 8) is programmed with a US (U1–U5) or IEC (C1–C5) curve, Vert. multiplier - phase fast curve is hidden and nonoperative. The preceding Time-dial - phase fast curve (No. 8) subsetting provides the US and IEC curves with an effective vertical multiplier, instead.
• This setting has no multiplying effect on the Constant time adder - phase fast curve and Min. response time - phase fast curve settings. They all operate independently.
• This setting is hidden and set to 1.00 if Complex fast curve - phase is set to N and Fast curve-phase (No. 8) is programmed with a recloser or user curve.
65 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
Setting
Min. response - phase fast curve
Default
0.00 0–60.00 cycles
Range Incr.
0.25 cyc.
The phase fast curve can trip no faster than the Min. response time - phase fast curve setting.
If the Min. response time - phase fast curve setting is set equal to zero (0), it has no effect on the phase fast curve. If the Min. response time - phase fast curve setting is set equal to 15 cycles, for example, the phase fast curve cannot trip on the portion of the curve that is faster than 15 cycles—the phase fast curve effectively flattens out at 15 cycles.
• This setting is hidden and set to zero (0) if Complex fast curve - phase is set to N.
No.
26
Setting
Complex fast curve - ground
Default
N Y/N
Range Incr.
The Complex fast curve - ground to Y.
setting enables the following three settings for the ground fast curve, if set
• This setting is hidden and set to N if Fast curve - ground (No. 9) is set to OFF.
Const. time adder - ground fast curve
Setting Default
0.00 0–60.00 cycles
Range Incr.
0.25 cyc.
The Const. time adder - ground fast curve if set to other than 0 cycles.
setting adds a constant time to the ground fast curve,
• This setting is hidden and set to zero (0) if Complex fast curve - ground is set to N.
Vert. multiplier - ground fast curve
Setting Default Range
1.00 0.10–2.00
Incr.
0.01
The Vert. multiplier - ground fast curve setting shifts the ground fast curve in time, by the entered multiplier, if Fast curve - ground (No. 9) is programmed with a recloser or user curve. If no particular multiplier is desired, set Vert. multiplier - ground fast curve equal to 1.00.
• If Fast curve - ground (No. 9) is programmed with a US (U1–U5) or IEC (C1–C5) curve, Vert. multiplier - ground fast curve is hidden and nonoperative. The preceding Time-dial - ground fast curve (No. 9) subsetting provides the US and IEC curves with an effective vertical multiplier, instead.
• This setting has no multiplying effect on the Constant time adder - ground fast curve and
Min. response time - ground fast curve settings. They all operate independently.
• This setting is hidden and set to 1.00 if Complex fast curve - ground is set to N and Fast curve-ground (No. 9) is programmed with a recloser or user curve.
Setting
Min. response - ground fast curve
Default
0.00 0–60.00 cycles
Range Incr.
0.25 cyc.
The phase fast curve can trip no faster than the Min. response time - ground fast curve setting.
If the Min. response time - ground fast curve setting is set equal to zero (0), it has no effect on the ground fast curve. If the Min. response time - ground fast curve setting is set equal to 15 cycles, for example, the ground fast curve cannot trip on the portion of the curve that is faster than 15 cycles— the ground fast curve effectively flattens out at 15 cycles.
• This setting is hidden and set to zero (0) if Complex fast curve - ground is set to N.
66 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
27 Complex delay curve - phase
Default
N Y/N
Range Incr.
The Complex delay curve - phase set to Y.
setting enables the following three settings for the phase delay curve, if
• This setting is hidden and set to N if Delay curve - phase (No. 10) is set to OFF.
Setting
Const. time adder - phase delay curve
Default
0.00 0–60.00 cycles
Range Incr.
0.25 cyc.
The Const. time adder - phase delay curve if set other than 0 cycles.
setting adds a constant time to the phase delay curve,
• This setting is hidden and set to zero (0) if Complex delay curve - phase is set to N.
Setting
Vert. multiplier - phase delay curve
Default Range
1.00 0.10–2.00
Incr.
0.01
The Vert. multiplier - phase delay curve setting shifts the phase delay curve in time, by the entered multiplier, if Delay curve - phase (No. 10) is programmed with a recloser or user curve. If no particular multiplier is desired, set Vert. multiplier - phase delay curve equal to 1.00.
• If Delay curve - phase (No. 10) is programmed with a US (U1–U5) or IEC (C1–C5) curve,
Vert. multiplier - phase delay curve is hidden and nonoperative. The preceding Time-dial - phase delay curve (No. 10) subsetting provides the US and IEC curves with an effective vertical multiplier, instead.
• This setting has no multiplying effect on the Constant time adder - phase delay curve and
Min. response time - phase delay curve settings. They all operate independently.
• This setting is hidden and set to 1.00 if Complex delay curve - phase is set to N and Delay curve-phase (No. 10) is programmed with a recloser or user curve.
Setting
Min. response - phase delay curve
Default
0.00 0–60.00 cycles
Range Incr.
0.25 cyc.
The phase delay curve can trip no faster than the Min. response time - phase delay curve setting.
If the Min. response time - phase delay curve setting is set equal to zero (0), it has no effect on the phase delay curve. If the Min. response time - phase delay curve setting is set equal to 15 cycles, for example, the phase delay curve cannot trip on the portion of the curve that is faster than 15 cycles—the phase delay curve effectively flattens out at 15 cycles.
• This setting is hidden and set to zero (0) if Complex delay curve - phase is set to N.
67 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
28 Complex delay curve - ground
Default
N Y/N
Range Incr.
The Complex delay curve - ground if set to Y.
setting enables the following three settings for the ground delay curve,
• This setting is hidden and set to N if Delay curve - ground (No. 11) is set to OFF.
Setting
Const. time adder - ground delay curve
Default
0.00 0–60.00 cycles
Range Incr.
0.25 cyc.
The Const. time adder - ground delay curve curve, if set other than 0 cycles.
setting adds a constant time to the ground delay
• This setting is hidden and set to zero (0) if Complex delay curve - ground is set to N.
Setting
Vert. multiplier - ground delay curve
Default Range
1.00 0.10–2.00
Incr.
0.01
The Vert. multiplier - ground delay curve setting shifts the phase delay curve in time, by the entered multiplier, if Delay curve - ground (No. 11) is programmed with a recloser or user curve. If no particular multiplier is desired, set Vert. multiplier - ground delay curve equal to 1.00.
• If Delay curve - ground (No. 11) is programmed with a US (U1–U5) or IEC (C1–C5) curve,
Vert. multiplier - ground delay curve is hidden and nonoperative. The preceding Time-dial - ground delay curve (No. 11)—setting provides the US and IEC curves with an effective vertical multiplier, instead.
• This setting has no multiplying effect on the Constant time adder - ground delay curve and
Min. response time - ground delay curve settings. They all operate independently.
• This setting is hidden and set to 1.00 if Complex delay curve - ground is set to N and Delay curve - ground (No. 11) is programmed with a recloser or user curve.
Setting
Min. response - ground delay curve
Default
0.00 0–60.00 cycles
Range Incr.
0.25 cyc.
The ground delay curve can trip no faster than the Min. response time - ground delay curve setting.
If the Min. response time - ground delay curve setting is set equal to zero (0), it has no effect on the ground delay curve. If the Min. response time - ground delay curve setting is set equal to
15 cycles, for example, the ground delay curve cannot trip on the portion of the curve that is faster than 15 cycles—the ground delay curve effectively flattens out at 15 cycles.
• This setting is hidden and set to zero (0) if Complex delay curve - ground is set to N.
68 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No.
29
Setting
High current trip - phase
Default
N Y/N
Range Incr.
The High current trip - phase setting enables the following three settings for phase high current tripping, if set to Y. Phase high current tripping is not affected by the cold load pickup scheme.
• This setting is hidden and set to N if Fast curve - phase (No. 8) and Delay curve - phase (No. 10) are both set to OFF.
Setting
High current trip - phase
Default
OFF OFF, 1.00–39.99 multiples of Min. trip - phase
Range Incr.
0.01
The High current trip - phase (multiples of Min. trip - phase ) setting determines the phase current threshold for phase high current tripping.
High current trip - phase = 12.00 (multiples of Min. trip - phase ) and Min. trip - phase (No. 5) = 200.00 Amps primary, then the phase current threshold for phase high current tripping operates at a value equal to:
12.00 • 200.00 Amps primary = 2400.00 Amps primary
The upper limit of this setting (40.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - phase (No. 5) [200.00]:
(20 • 400.0)/200.00 = 40.00 multiples (upper limit)
Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 39.99 instead of 40.00).
• This setting is hidden and set to OFF if High current trip - phase is set to N.
Setting
Time delay - phase high current trip
Default
0.00
Range
0–16000.00 cycles
Incr.
0.25 cyc.
The Time delay - phase high current trip setting programs an intentional time delay for the phase high current tripping. If set to zero (0), phase high current tripping operates instantaneously.
• This setting is hidden and set to zero (0) if High current trip - phase is set to N.
Setting
Activate high current trip - phase
Default Range Incr.
1
The Activate high current trip - phase enabled (e.g., if
setting determines when phase high current tripping is
Activate high current trip - phase = 2, then phase high current tripping is enabled for the second [2nd] trip operation and every following trip operation).
The setting range for Activate high current trip - phase adjusts according to Operations to lockout
- phase (e.g., if Operations to lockout - phase = 4, then the range for Activate high current trip - phase is from 1 to 4).
• This setting is hidden and set to OFF if High current trip - phase is set to N.
69 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No.
30
Setting
High current trip - ground
Default
N Y/N
Range
The High current trip - ground setting enables the following three settings for ground high current tripping, if set to Y. Ground high current tripping is not affected by the cold load pickup scheme.
Incr.
• This setting is hidden and set to N if Fast curve - ground (No. 9) and Delay curve - ground (No. 11) are both set to OFF.
Setting
High current trip - ground
Default
OFF OFF, 1.00–399.99 multiples of Min. trip - ground
Range Incr.
0.01
The High current trip - ground (multiples of Min. trip - ground current threshold for ground high current tripping.
) setting determines the ground
High current trip - ground = 44.00 (multiples of Min. trip - ground ) and
Min. trip - ground (No. 6) = 20.00 Amps primary, then the ground current threshold for ground high current tripping operates at a value equal to:
44.00 • 20.00 Amps primary = 880.00 Amps primary
The upper limit of this setting (400.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - ground (No. 6) [20.00]:
(20 • 400.0)/20.00 = 400.00 multiples (upper limit)
Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 399.99 instead of 400.00).
• This setting is hidden and set to OFF if High current trip - ground is set to N.
Setting
Time delay - ground high current trip
Default
0.00
Range
0–16000.00 cycles
Incr.
0.25 cyc.
The Time delay - ground high current trip setting programs an intentional time delay for the ground high current tripping. If set to zero (0), ground high current tripping operates instantaneously.
• This setting is hidden and set to zero (0) if High current trip - ground is set to N.
Setting
Activate high current trip - ground
Default Range Incr.
1
The Activate high current trip - ground enabled (e.g., if
setting determines when ground high current tripping is
Activate high current trip - ground = 2, then ground high current tripping is enabled for the second [2nd] trip operation and every following trip operation).
The setting range for Activate high current trip - ground adjusts according to Operations to lockout - ground (e.g., if Operations to lockout - ground = 4, then the range for Activate high current trip - ground is from 1 to 4).
• This setting is hidden and set to OFF if High current trip - ground is set to N.
70 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
31 High current lockout - phase
Default
N Y/N
Range Incr.
The High current lockout - phase setting enables the following two settings for phase high current lockout, if set to Y. Phase high current lockout is not affected by the cold load pickup scheme.
• This setting is hidden and set to N if Fast curve - phase (No. 8) and Delay curve - phase (No. 10) are both set to OFF.
Setting
High current lockout - phase
Default
OFF OFF, 1.00–39.99 multiples of Min. trip - phase
Range Incr.
0.01
The High current lockout - phase (multiples of Min. trip - phase ) setting determines the exceeded phase current threshold at which the SEL-351P-3 goes to the lockout state immediately when tripping.
High current lockout - phase = 13.00 (multiples of Min. trip - phase ) and
Min. trip - phase (No. 5) = 200.00 Amps primary, then the phase current threshold for phase high current lockout operates at a value equal to:
13.00 • 200.00 Amps primary = 2600.00 Amps primary
The upper limit of this setting (40.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - phase (No. 5) [200.00]:
(20 • 400.0)/200.00 = 40.00 multiples (upper limit)
Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 39.99 instead of 40.00).
• This setting is hidden and set to OFF if High current lockout - phase is set to N.
Setting
Activate high current lockout - phase
Default Range Incr.
1
The Activate high current lockout - phase enabled (e.g., if
setting determines when phase high current lockout is
Activate high current lockout - phase = 3, then phase high current tripping is enabled for the third [3rd] trip operation and every following trip operation).
The setting range for Activate high current lockout - phase adjusts according to Operations to lockout - phase (e.g., if Operations to lockout - phase = 4, then the range for Activate high current lockout - phase is from 1 to 4).
• This setting is hidden and set to OFF if High current lockout - phase is set to N.
71 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
32 High current lockout - ground
Default
N Y/N
Range Incr.
The High current lockout - ground setting enables the following two settings for ground high current lockout, if set to Y. High current lockout ground is not affected by the cold load pickup scheme.
• This setting is hidden and set to N if Fast curve - ground (No. 9) and Delay curve - ground (No. 11) are both set to OFF.
Setting
High current lockout - ground
Default
OFF OFF, 1.00–399.99 multiples of Min. trip - ground
Range Incr.
0.01
The High current lockout - ground (multiples of Min. trip - ground ) setting determines the exceeded ground current threshold at which the SEL-351P-3 goes to the lockout state immediately when tripping.
High current lockout - ground = 45.00 (multiples of Min. trip - ground ) and Min. trip - ground (No. 6) = 20.00 Amps primary, then the ground current threshold for ground high current lockout operates at a value equal to:
45.00 • 20.00 Amps primary = 900.00 Amps primary
The upper limit of this setting (400.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - ground (No. 6) [20.00]:
(20 • 400.0)/20.00 = 400.00 multiples (upper limit)
Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 399.99 instead of 400.00).
• This setting is hidden and set to OFF if High current lockout - ground is set to N.
Setting
Activate high current lockout - ground
Default Range Incr.
1
The Activate high current lockout - ground enabled (e.g., if
setting determines when ground high current lockout is
Activate high current lockout - ground = 3, then ground high current tripping is enabled for the third [3rd] trip operation and every following trip operation).
The setting range for Activate high current lockout - ground adjusts according to Operations to lockout - ground (e.g., if Operations to lockout - ground = 4, then the range for Activate high current lockout - ground is from 1 to 4).
• This setting is hidden and set to OFF if High current lockout - ground is set to N.
72 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No.
33
Setting
Cold load pickup scheme
Default
N Y/N
Range
The Cold load pickup scheme setting enables the cold load pickup scheme when set to Y.
Incr.
• This setting is hidden and set to N if Delay curve - phase (No. 10) is set to OFF and Delay curve - ground (No. 11) is set to OFF.
• If Cold load pickup scheme is set to Y, then you are prompted to program the following settings:
Setting
Cold load pickup - phase
Default
OFF OFF, 1.00–39.99 multiples of Min. trip - phase
Range Incr.
0.01
The Cold load pickup - phase setting determines the phase current threshold for overcurrent detection when the Cold load pickup scheme is active.
Cold load pickup - phase = 1.70 (multiples of Min. trip - phase ), Min. trip - phase (No. 5) = 200.00 Amps primary, and the cold load pickup scheme is active, then the phase current threshold for overcurrent detection operates at a value equal to:
1.70 • 200.00 Amps primary = 340.00 Amps primary
The upper limit of this setting (40.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - phase (No. 5) [200.00]:
(20 • 400.0)/200.00 = 40.00 multiples (upper limit)
Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 39.99 instead of 40.00).
• If Cold load pickup - phase is set to OFF, then the phase current threshold for overcurrent detection remains unchanged (threshold remains equal to Min. trip - phase [No. 5]).
• This setting is hidden and set to OFF if Cold load pickup scheme is set to N or Delay curve -
phase (No. 10) is set to OFF.
73 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
Setting
Cold load pickup - ground
Default
OFF
Range
OFF, 1.00–399.99 multiples of Min. trip - ground
Incr.
0.01
The Cold load pickup - ground setting determines the ground current threshold for overcurrent detection when the Cold load pickup scheme current threshold for overcurrent detection).
is active (also applied to SEF element as the SEF
Cold load pickup - ground = 1.50 (multiples of Min. trip - ground ),
Min. trip - ground (No. 6) = 20.00 Amps primary, and the cold load pickup scheme is active, then the ground current threshold for overcurrent detection operates at a value equal to:
1.50 • 20.00 Amps primary = 30.00 Amps primary
The SEF current threshold for overcurrent detection also operates at a value equal to 30 Amps primary when the cold load pickup scheme is active.
The upper limit of this setting (400.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - ground (No. 6) [20.00]:
(20 • 400.0)/20.00 = 400.00 multiples (upper limit)
Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 399.99 instead of 400.00).
• If Cold load pickup - ground is set to OFF, then the ground current threshold for overcurrent detection remains unchanged (threshold remains equal to setting Min. trip - ground [No. 6]) and the SEF current threshold for overcurrent detection remains unchanged (threshold remains equal to setting Min. trip - SEF [No. 7]).
• This setting is hidden and set to OFF if Cold load pickup scheme is set to N or Delay curve - ground (No. 11) is set to OFF.
Setting
Loss of load diversity time
Default
0.00
Range
0–999999.00 cycles
The Loss of load diversity timer starts to time if both the following are true:
Incr.
0.25 cyc.
• The recloser is open.
• The control is in the lockout state or reclosing is defeated.
When the Loss of load diversity timer times out, the cold load pickup scheme is activated , causing the following to occur:
• Fast curves are disabled.
• Delay curves and SEF element are desensitized per preceding cold load pickup settings (the curves are not shifted—coordination is maintained).
When the recloser is closed, the cold load pickup scheme remains active. If the recloser remains closed, the current thresholds for overcurrent detection return naturally to their regular Min. trip
(No. 5, 6, or 7) levels when the inrush current goes below these respective regular levels for at least
15 seconds. The respective fast curves are enabled again. This return to normal conditions is separate for phase, ground, and SEF elements (e.g., ground could return to normal before phase or SEF, depending on the subsidence rates of inrush currents).
• This setting is hidden and set to zero (0) if Cold load pickup scheme is set to N.
74 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
Setting
Restore min. trips - time limit
Default
OFF
Range
OFF, 0–999999.00 cycles
Incr.
0.25 cyc.
The Restore min. trips - time limit is an option to force current thresholds for overcurrent detection from temporary cold load pickup values back to regular Min. trip (No. 5, 6, or 7) levels. This time limit is set if the user is concerned about an overcurrent element being desensitized too long in the cold load inrush scheme ( force the threshold back, do not let it return naturally as described with the preceding Loss of load diversity timer setting).
Restore min. trips - time limit ≠ OFF:
The Restore min. trips - time limit following are true:
starts to time if the recloser is closed and both of the
• The cold load pickup scheme is active for at least one element (see preceding Cold load pickup and Loss of load diversity settings).
• At least one of the following three Restore min. trip settings is set to Y.
If the recloser remains closed, the Restore min. trips - time limit times out and selected current thresholds for overcurrent detection (see following three Restore min. trip settings) are forced back to their respective regular Min. trip (No. 4, 5, and 6) levels. The respective fast curves are also enabled again. The natural return to the regular Min. trip levels (described with the preceding Loss of load diversity timer setting) can also occur if the inrush current goes below the Min. trip level for at least 15 seconds before Restore min. trips - time limit times out.
Restore min. trips - time limit = OFF:
If the cold load pickup scheme is active, then the current thresholds for overcurrent detection can only return back to their regular Min. trip levels naturally as described with the preceding Loss of load diversity timer setting.
• This setting is hidden and set to OFF if Cold load pickup scheme is set to N.
Setting
Restore min. trip - phase
Default
N Y/N
Range
Restore min. trip - phase = Y:
Incr.
If the cold load pickup scheme is active, the phase current threshold for overcurrent detection is forced back to the regular Min. trip - phase (No. 5) level when the preceding Restore min. trips - time limit times out.
Restore min. trip - phase = N:
If the cold load pickup scheme is active, the phase current threshold for overcurrent detection can only return back to its regular Min. trip - phase level naturally as described with the preceding Loss of load diversity timer setting.
• This setting is hidden and set to N if Restore min. trips - time limit is set to OFF or Delay curve - phase (No. 10) is set to OFF.
75 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
Setting
Restore min. trip - ground
Restore min. trip - ground = Y:
Default
N Y/N
Range Incr.
If the cold load pickup scheme is active, the ground current threshold for overcurrent detection is forced back to the regular Min. trip - ground (No. 6) level when the preceding Restore min. trips - time limit times out.
Restore min. trip - ground = N:
If the cold load pickup scheme is active, the ground current threshold for overcurrent detection can only return back to its regular Min. trip - ground level naturally as described with the preceding Loss of load diversity timer setting.
• This setting is hidden and set to N if Restore min. trips - time limit is set to OFF or Delay curve - ground (No. 11) is set to OFF.
Setting
Restore min. trip - SEF
Restore min. trip - SEF = Y:
Default
N Y/N
Range Incr.
If the cold load pickup scheme is active, the SEF current threshold for overcurrent detection is forced back to the regular Min. trip - SEF (No. 7) level when the preceding Restore min. trips
- time limit times out. The ground current threshold for overcurrent detection derived from setting Cold load pickup - ground is also applied to the SEF element (as the SEF current threshold for overcurrent detection).
Restore min. trip - SEF = N:
If the cold load pickup scheme is active, the SEF current threshold for overcurrent detection can only return back to its regular Min. trip - SEF level naturally as described with the preceding
Loss of load diversity timer setting.
• This setting is hidden and set to N if Restore min. trips - time limit is set to OFF, Delay curve - ground (No. 11) is set to OFF, or Min. trip - SEF (No. 7) is set to OFF.
76 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting Default
N Y/N
Range Incr.
The Sequence coordination setting keeps the SEL-351P-3 in step with a downstream recloser control, preventing the overreaching SEL-351P-3 Fast curve elements from tripping for faults beyond the downstream recloser.
Sequence coordination advances the operations counter each time the following sequence occurs:
• The SEL-351P-3 is in the reset state.
• Fast curve - phase (No. 8) or Fast curve - ground (No. 9) element picks up and starts timing for a fault.
• Fast curve - phase (No. 8) or Fast curve - ground (No. 9) element remains picked up for at least
1.25 cycles, but then drops out before tripping (fault was interrupted by downstream device closer to the fault).
When the operations counter is advanced beyond the corresponding Operations - phase fast curve (No. 13) or Operations - ground fast curve (No. 14), no more advancing of the operations counter occurs (the Fast curve elements are disabled). The Fast curve elements are enabled again (the operations counter is reset) after a time period equal to Reset time for auto reclose (No. 22).
• This setting is hidden and set to N if the Fast curve - phase and the Fast curve - ground settings are both set to OFF.
No.
35
Setting
Ground trip precedence
Ground trip precedence = Y:
Default
N Y/N
Range Incr.
• If the ground fault current is above the Min. trip - ground (No. 6) level at the time of trip, the operations to lockout follows Operations to lockout - ground (No. 16).
• If ground fault current is below the Min. trip - ground (No. 6) level and phase fault current is above the Min. trip - phase (No. 5) level at the time of trip, the determination to go to lockout is controlled by Operations to lockout - phase (No. 15).
Ground trip precedence = N:
• If ground fault current is above the Min. trip - ground (No. 6) level and phase fault current is below the Min. trip - phase (No. 5) level at the time of trip, the determination to go to lockout is controlled by Operations to lockout - ground (No. 16).
• If phase fault current is above the Min. trip - phase (No. 5) at the time of trip, the determination to go to lockout is controlled by Operations to lockout - phase (No. 15).
• Note: The Operations to lockout - SEF (No. 17) is independent of Ground trip precedence .
• This setting is hidden and set to N if Operations to lockout - phase (No. 15) = OFF, Operations to lockout - ground (No. 16) = OFF, or the Operations to lockout - phase setting equals (=) the
Operations to lockout - ground setting.
77 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting Default
N Y/N
Range Incr. shedding
The
Y.
Underfrequency load shedding setting enables the underfrequency load shedding scheme, if set to
• If Underfrequency load shedding is set to Y, enter the following two settings:
Setting
Underfrequency pickup
Default
OFF
Range
OFF, 40.10–65.00 Hz
Incr.
0.01 Hz
The Underfrequency pickup shedding.
setting determines the frequency threshold for underfrequency load
Setting
Underfrequency time delay
Default
6.00
Range
2.00–16000.00 cycles
The Underfrequency time delay shedding.
setting determines the time delay for underfrequency load
Incr.
0.25 cyc.
No. Setting
37 Demand meter time constant
Default
5
Range
5, 10, 15, 30, 60 minutes
The Demand meter time constant setting determines the thermal demand meter response time.
Incr.
No. Setting
38 System Frequency
Enter nominal System frequency .
Default
50 50, 60 Hz
Range Incr.
No. Setting
39 Phase Rotation
Enter system Phase rotation .
Default
ABC ABC, ACB
Range Incr.
No. Setting
40 Recloser Wear Monitor
Recloser Wear Monitor = Y:
Default
AUTO AUTO, Y, N
Range Incr.
The recloser wear monitor must be set at a higher level, with the SET G command (see the SEL-351P-3
Instruction Manual ). This setting is usually selected if a circuit breaker is connected to the SEL-351P-3 instead of a GVR recloser.
Recloser Wear Monitor = N:
The recloser wear monitor is turned off.
Recloser Wear Monitor = AUTO:
This setting is usually selected if a GVR recloser is connected to the SEL-351P-3. Enter the following setting:
78 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
Setting
Interrupt rating
Default
12000
Range
6000, 8000, 10000, 12500, 16000
Amps primary
Incr.
1
Make this setting by finding your recloser model in Table 11 and then entering the corresponding value.
• This setting is hidden and nonoperative if Recloser Wear Monitor ≠ AUTO.
Table 11: Recloser Interrupt Data
Recloser Model
GVR (15.5 kV, 6 kA)
GVR (38 kV, 8 kA)
GVR (38 kV, 10 kA)
GVR (15.5 kV, 12.5 kA)
GVR (27 kV, 12.5 kA)
GVR (15.5 kV, 16 kA)
Interrupt Rating (Amps primary)
6000
8000
10000
12500
12500
16000
No. Setting
41 Reset trip-latched LEDs on close
Default Range
Y Y,Y1,N,N1
Incr.
Figure 18 and Figure 19 show the front-panel trip-latched LEDs. They are: TRIP/DISPARO, FAST
CURVE/CURVA RAPIDA, HIGH CURRENT/ALTA CORRIENTE, UNDER FREQ./BAJA FREC., and all
FAULT TYPE/TIPO DE FALLA LEDs.
These LEDs latch in at the rising edge of trip and remain illuminated—even after power is turned off and then on again.
Reset trip-latched LEDs on close = Y or Y1:
The trip-latched LEDs extinguish automatically when the recloser closes.
Reset trip-latched LEDs on close = N or N1:
The trip-latched LEDs extinguish automatically (or are newly latched in) when the SEL-351P-3 trips again.
Settings options Y1 and N1 disable the embedded 3-second qualifying time delay on the LOCK operator control (see the Operator Controls subsection in the Front-Panel Interface section). In this mode, the LOCK operator control effectively operates as the other operator controls, with no time delay.
No. Setting Default
N Y/N
Range connected
If True three-phase voltage is connected to the SEL-351P-3, the indication provided by A, B, and C
FAULT TYPE/TIPO DE FALLA LEDs is made more secure (see Figure 18 and Figure 19).
Incr.
No. Setting
43 Phantom voltages from
Default
NO
Range
VA,VB,VC,VAB,VBC,VCA,OFF
Incr.
If True three-phase voltage is set to N, the phantom voltage setting is available. In this mode the relay generates three balanced voltages, for metering only, from a single phase-to-ground or phase-to-phase connected voltage. Regardless of the phase selected, the voltage must be physically connected to phase V1.
79 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
44 V123 Terminal Conn. or
V123 Terminal Conn.
Default Range
A A,B,C,AB,BC,CA,OFF
ABC,ACB,BAC,BCA,CAB,CBA
Incr.
The voltage terminal connection setting allows the transition from the power system A-B-C wiring to the
SEL-351P-3 recloser control terminals V1-V2-V3.
If True three-phase voltage (#42) is set to N and Phantom voltages (#43) is set to OFF, voltage terminal connections A, B, C, AB, BC, CA, and OFF are available. When settings are saved, if V123 Terminal
Connection setting is out of range, the setting defaults to A.
If True three-phase voltage is set to Y, then voltage terminal connections ABC, ACB, BAC, BCA, CAB, and CBA are available. When settings are saved, if V123 Terminal Connection setting is out of range, the setting defaults to ABC.
No.
45
Setting
I123 Terminal Conn.
Default
ABC
Range
ABC, ACB, BAC, BCA, CAB,
CBA
Incr.
The current terminal connection setting allows the transition from the power system A-B-C wiring to the
SEL-351P-3 recloser control current terminals I1-I2-I3.
No.
46
Setting
CT Polarity
Default
POS POS, NEG
Range Incr.
The CT Polarity setting provides an easy way to change the polarity of the measured current signals, thus the resulting power direction and impedances.
No. Setting
47 Battery Amp-hours
Default
8.0
Range
6.5–20.0 Amp-hours
This is the amp-hour rating of the 24 Vdc battery system connected to pins 6 [+] and 2 [–] on POWER connector J6.
Incr.
0.1
No. Setting
48 Power-off Delay After AC
Loss
Default
180
Range
OFF, 1–1440 min
Incr.
1
The Power-off Delay After AC Loss setting value starts timing when the 24 Vdc battery takes over powering the SEL-351P-3 when Vac power goes away (e.g., a feeder outage occurs). If the outage persists, this setting value eventually times out and shuts down the SEL-351P-3 to conserve battery power. The SEL-351P-3 can only awaken if Vac power returns or the front-panel WAKE UP/DESPERTAR pushbutton is pressed.
80 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
No. Setting
49 Power-off Delay After Wake
Up
Default
20
Range
OFF, 1–1440 min
Incr.
1
The Power-off Delay After Wake Up setting value starts timing when the SEL-351P-3 has been awakened by pressing the front-panel WAKE UP/DESPERTAR pushbutton. If Vac power doesn't return (i.e., the outage persists), this setting value eventually times out and shuts down the SEL-351P-3 to conserve battery power.
The SEL-351P-3 can only awaken if Vac power returns or the front-panel WAKE UP/DESPERTAR pushbutton is pressed (and battery voltage is adequate).
No.
50
Setting
Power-off Voltage Level 1
Default
20.5 19.2–24 Vdc
Range Incr.
0.1
The Power-off Delay Voltage Level 1 setting shuts down the SEL-351P-3 (to conserve battery power) when the 24 Vdc battery has been powering the SEL-351P-3 and the battery voltage declines to the setting level (or below) for a qualified time of 5 seconds. The SEL-351P-3 can only awaken if Vac power returns or the frontpanel WAKE UP/DESPERTAR pushbutton is pressed (and battery voltage is adequate).
No. Setting
51 SF6 low pressure warning threshold in atm.
Default Range Incr.
1.1 0.9–2.0 atmospheres 0.1
The SF6 gas pressure inside the GVR recloser is typically at 1.3 atmospheres (atm). If the pressure goes below the SF6 low pressure warning threshold, then the ALARM output contact pulse for 5 seconds. The present SF6 gas pressure can be accessed with the STATUS command (see Table 3 in the Communications section).
Pressure sensing in the SEL-351P-3 has a 5-minute time constant with a 95 percent response. For example, if the SF6 gas pressure is suddenly lost and recloser tank pressure goes from 1.30 atm. to atmospheric pressure
(1.00 atm), after 5 minutes the SEL-351P-3 reports the SF6 gas pressure at around:
1.30 – 0.95 • (1.30 – 1.00) = 1.02 atm
81 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
ETTINGS
HEETS
FOR THE
ECLOSER
ONTROL
Page 1 of 5
Date
!
WARNING: Anytime an EZ setting is changed, review all the EZ settings before enabling the new settings. Pay close attention in circumstances where a setting was once set to OFF or N and then later turned on (enabled)—other related settings may need to be turned on, though may still be set to OFF or N.
Settings Groups 1 (Main) and 2 (Alternate)
EZ Settings (SET EZ n command; n = 1, 2):
Control Identifier (30 characters)
Circuit Identifier (30 characters)
CT Ratio
PT Ratio
Min. trip - phase
Min. trip - ground
Ranges given for
CT Ratio = 400.0
Min. trip - SEF
Fast curve - phase (see Page 4 of 4)
Time dial - phase fast curve
EM reset - phase fast curve
Fast curve - ground (see Page 4 of 4)
Time dial - ground fast curve
EM reset - ground fast curve
Delay curve - phase (see Page 4 of 4)
Time dial - phase delay curve
EM reset - phase delay curve
Delay curve - ground (see Page 4 of 4)
Time dial - ground delay curve
EM reset - ground delay curve
Time delay - SEF
Operations - phase fast curve
Operations - ground fast curve
Operations to lockout - phase
Operations to lockout - ground
Operations to lockout - SEF
Reclose interval 1
Reclose interval 2
Reclose interval 3
Reclose interval 4
Do not set less than
30 cycles, or premature lockout results
Range:
0–9, A–Z, -, /, ., space
0–9, A–Z, -, /, ., space
1.0–6000.0
1.0–10000.0
OFF, 40.00–1280.00 A primary
OFF, 2.00–1280.00 A primary
OFF, 2.00–600.00 A primary
OFF, U1–U5 (US), C1–C5 (IEC)
0.50–15.00 (U1–U5),
0.05–1.00 (C1–C5)
Y/N
OFF, U1–U5 (US), C1–C5 (IEC)
0.50–15.00 (U1–U5),
0.05–1.00 (C1–C5)
Y/N
OFF, U1–U5 (US), C1–C5 (IEC)
0.50–15.00 (U1–U5),
0.05–1.00 (C1–C5)
Y/N
OFF, U1–U5 (US), C1–C5 (IEC)
0.50–15.00 (U1–U5),
0.05–1.00 (C1–C5)
Y/N
0–16000.00 cycles
OFF, 1–5
OFF, 1–5
OFF, 1–5
OFF, 1–5
OFF, 1–5
0–999999.00 cycles
0–999999.00 cycles
0–999999.00 cycles
0–999999.00 cycles
--
--
0.01
--
--
0.01
--
--
Incr.:
--
--
1
1
0.01
0.01
0.01
--
0.01
0.01
1
1
--
0.25
1
1
1
0.25
Settings:
0.25
0.25
0.25
82 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
FOR THE
ETTINGS
HEETS
Range:
0–999999.00 cycles
ECLOSER
ONTROL
Settings Groups 1 (Main) and 2 (Alternate)
EZ Settings (SET EZ n command; n = 1, 2):
Reset time for auto reclose
Incr.:
0.25
Page 2 of 5
Date
Settings:
Reset time from lockout
Close power wait time
Complex fast curve - phase
Const. time adder - phase fast curve
Vert. multiplier - phase fast curve
Min. response - phase fast curve
Complex fast curve - ground
Const. time adder - ground fast curve
Vert. multiplier - ground fast curve
Min. response - ground fast curve
Complex delay curve - phase
Const. time adder - phase delay curve
Vert. multiplier - phase delay curve
Min. response - phase delay curve
Complex delay curve - ground
Const. time adder - ground delay curve
Vert. multiplier - ground delay curve
Min. response - ground delay curve
High current trip - phase
High current trip - phase (range given for
CT Ratio = 400.0)
Time delay - phase high current trip
Activate high current trip - phase
High current trip - ground
High current trip - ground (range given for
CT Ratio = 400.0)
Time delay - ground high current trip
Activate high current trip - ground
High current lockout - phase
High current lockout - phase (range given for CT Ratio = 400.0)
Activate high current lockout - phase
0–999999.00 cycles
0–16000.00 cycles
Y/N
0–60.00 cycles
0.10–2.00
0–60.00 cycles
Y/N
0–60.00 cycles
0.10–2.00
0–60.00 cycles
Y/N
0–60.00 cycles
0.10–2.00
0–60.00 cycles
Y/N
0–60.00 cycles
0.10–2.00
0–60.00 cycles
Y/N
1.00–(8000/Min. trip - phase) multiples of Min. trip - phase
0–16000.00 cycles
OFF, 1–5
Y/N
1.00–(8000/Min. trip - ground) multiples of Min. trip - ground
0–16000.00 cycles
OFF, 1–5
Y/N
1.00–(8000/Min. trip - phase) multiples of Min. trip - phase
OFF, 1–5
0.01
0.25
--
0.25
0.01
0.25
--
0.25
0.01
0.25
--
0.01
0.25
0.25
--
0.25
0.01
0.25
--
0.25
0.25
1
--
0.01
0.25
1
--
0.01
1
83 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
FOR THE
Settings Groups 1 (Main) and 2 (Alternate)
EZ Settings (SET EZ n command; n = 1, 2):
High current lockout - ground
High current lockout - ground (range given for CT Ratio = 400.0)
Activate high current lockout - ground
Cold load pickup scheme
Cold load pickup - phase (range given for
CT Ratio = 400.0)
Cold load pickup - ground (range given for
CT Ratio = 400.0)
Loss of load diversity time
Restore min. trips - time limit
Restore min. trip - phase
Restore min. trip - ground
Restore min. trip - SEF
Sequence coordination
Ground trip precedence
Underfrequency load shedding
Underfrequency pickup
Underfrequency time delay
Demand meter time constant
Global EZ Settings (SET FZ command):
ETTINGS
HEETS
ECLOSER
ONTROL
Range:
Y/N
1.00–(8000/Min. trip - ground) multiples of Min. trip - ground
OFF, 1–5
Y/N
1.00–(8000/Min. trip - phase) multiples of Min. trip - phase
1.00–(8000/Min. trip - ground) multiples of Min. trip - ground
0–999999.00 cycles
OFF, 0–999999.00 cycles
Y/N
Y/N
Y/N
Y/N
Y/N
Y/N
OFF, 40.10–65.00 Hz
2–16000.00 cycles
5, 10, 15, 30, 60 minutes
--
--
--
--
0.25
0.25
--
--
0.01
0.25
--
Incr.:
--
0.01
1
--
0.01
0.01
System Frequency
Phase Rotation
Recloser Wear Monitor
Interrupt rating
Reset trip-latched LEDs on close
True three-phase voltage connected
Phantom voltages from
Voltage terminal connections (V1, V2, V3)
V123 terminal connections
If True three-phase voltage connected = N and Phantom voltages = OFF
Or
If True three-phase voltage connected = Y, then
Current terminal connections (I1, I2, I3)
I123 terminal connections
50, 60 Hz
ABC, ACB
AUTO, Y, N
6000, 8000, 10000, 12500, 16000
A pri.
Y,Y1,N,N1
Y/N
(VA,VB,VC,VAB,VBC,VCA,OFF)
A, B, C, AB, BC, CA, OFF
ABC, ACB, BAC, BCA, CAB, CBA
ABC, ACB, BAC, BCA, CAB, CBA
--
--
--
--
--
--
--
--
--
--
Page 3 of 5
Date
Settings:
84 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
ETTINGS
HEETS
FOR THE
ECLOSER
ONTROL
Settings Groups 1 (Main) and 2 (Alternate)
EZ Settings (SET EZ n command; n = 1, 2): Range: Incr.:
CT polarity POS, NEG --
Page 4 of 5
Date
Settings:
Battery Amp-hours
Power-off Delay After AC Loss
Power-off Delay After Wake Up
Power-off Voltage Level 1
6.5–20.0 Amp-hours
OFF, 1–1440 min
OFF, 1–1440 min
19.2–24 Vdc
0.1
1
1
0.1
SF6 low pressure warning threshold in atm.
0.9–2.0 atmospheres 0.1
85 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Settings
Recloser Curve Designations
ETTINGS
HEETS
FOR THE
ECLOSER
ONTROL
Quick Reference for Curve
Settings:
Fast curve - phase
Fast curve - ground
Delay curve - phase
Delay curve - ground
Use Any Mix of Old and New
Recloser Curve Designations
When Making Curve
Recloser Curve Cross Reference—Old to New
Old
J
KP
L
M
N
F
G
H
A
B
C
D
E
New Old
101 P
117 R
133 T
116 V
132 W
163 Y
121 Z
122 1
164 2
162 3
107 4
118 5
104 6
New Old
135 15
140 16
106 17
114 18
136
New
115 7
105 8
152
113
161 8PLUS 111
137 9 131
138 KG 165
120 11
134 13
102 14
141
142
119
112
139
103
151
Page 5 of 5
Date
US, IEC, and User-Programmable Curve Designations
US Curve Description
U2 inverse
IEC Curve
C1
C2
C3
Description class A (standard inverse) class B (very inverse) class C (extremely inverse)
User-Programmable
Curves (factory-set)
DEF_01
DEF_05
DEF_1
DEF_5
Description definite-time curve (0.1 seconds) definite-time curve (0.5 seconds) definite-time curve (1.0 seconds) definite-time curve (5.0 seconds)
86 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Testing
T
Read and understand preceding sections so that the SEL-351P-3 can be safely grounded, powered up, and set. Especially understand the
Installation section.
Observe Recloser Count
Sequencing During Testing:
See Pushbutton Primary
Functions subsection in the
Front-Panel Interface section
(OTHER/VARIOS pushbutton—select "79").
Refer to Figure 12 and Figure 13 in the Installation section. If the regularly installed apparatus outside the SEL-351P-3 (i.e., the recloser, the external capacitor circuitry, and batteries) is not available during testing, then some settings and connections changes have to be made to compensate.
Logic Settings Changes
Refer to the SEL-351P-3 Instruction Manual , Section 10: Serial Port
Communications and Commands , specifically the SHO and SET commands. Factory default logic settings are listed under the SHO L command. Make the following logic settings changes with the SET L command:
* CL = (PB8*!LT5+CC*LT5+/IN102*LT5)*LT6
[normal setting is:
CL =
(PB8*!LT5+CC*LT5+/IN102*LT5)*LT6*TRCAP*CLCAP]
The dependence on the trip and close capacitors is removed as a requirement to issue a front panel close via the CLOSE/CIERRE operator control or via the serial port close command. See the
Close Logic subsection in Section 1: Factory-Set Logic in the
SEL-351P-3 Instruction Manual for explanation about the CL logic setting.
* 79CLS = 1
[normal setting is:
79CLS = TRCAP*CLCAP*!BADBAT*!DTFAIL]
The dependence on the trip and close capacitors and the batteries is removed as a requirement to issue an auto-reclose. See the
Reclose Supervision Logic subsection in Section 1: Factory-Set
Logic in the SEL-351P-3 Instruction Manual for explanation about the 79CLS logic setting.
Important: When testing is finished, return these settings back to normal.
Front Panel Status LEDs
Ignore the BATTERY PROBLEM/PROBLEMA BATERIA LED.
87 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Testing
Recloser Simulator
If the recloser simulator can provide both 52a and 52b recloser auxiliary contact operation, then connect as per Figure 13 in the Installation section (terminals 1, 5, and 13 of CONTROL connector J5). The 52a and
52b contacts have to be dry contacts (terminal 1 of CONTROL connector
J5 provides the whetting voltage).
If the recloser simulator can provide only 52a recloser auxiliary contact operation, then connect as per Figure 22 (terminals 1, 5, and 13 of
CONTROL connector J5). The 52a contact has to be a dry contact
(terminal 1 of CONTROL connector J5 provides the whetting voltage).
CONTROL connector
J5 recloser simulator
(partial)
13 see Note
1
5
52a
Note : Terminal 1 has a load limit of 0.1 A and should be fused for protection (Bussman
GMD-0.125 fuse or equivalent).
DWG: M351P054
Figure 22: Recloser Simulator Connections to SEL-351P-3 (only a 52a available)
Output Contacts
Unless the recloser simulator is designed to accept the same trip/close output that the GVR recloser accepts from the SEL-351P-3 outputs
(terminals 7, 8, and 15 of CONTROL connector J5; see Figure 12 and
Figure 13), program two of the programmable output contacts for the trip and close function, respectively and connect these output contacts to the recloser simulator:
OUT101 = TRIP
OUT102 = CLOSE
Program additional output contacts as needed (e.g., program an extra trip contact for overcurrent element timing: OUT103 = TRIP). Program the output contacts with the SET L command.
Refer to the SEL-351P-3 Instruction Manual , Section 10: Serial Port
Communications and Commands , specifically the SHO and SET commands. Factory default logic settings are listed under the SHO L command.
88 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Testing
Remember, REMOTE
ENABLED/REMOTO
HABILITADO Controls Other
Operator Controls:
See Operator Controls subsection in the Front-Panel
Interface section.
* Set the operations settings “=1” (i.e., Operations-phase fast curve
= 1, Operations-ground fast curve = 1, Operations to lockoutphase = 1, and Operations to lockout-ground = 1).
* Set the other curves, not being tested, to OFF (e.g., if testing
Delay curve-ground, set Fast curve-phase = OFF, Fast curveground = OFF, and Delay curve-phase = OFF).
* If testing a ground overcurrent element, enable the ground overcurrent element with the EARTH FAULT
ENABLED/FALLA A TIERRA HABILITADA operator control—otherwise disable the earth fault/ground overcurrent elements with the EARTH FAULT ENABLED/FALLA A
TIERRA HABILITADA operator control.
* If testing the SEF overcurrent element, enable the SEF overcurrent element with the SEF ENABLED/SEF
HABILITADO operator control—otherwise disable the SEF overcurrent element with the SEF ENABLED/SEF
HABILITADO operator control.
* Program additional output contacts as needed to connect to a timing unit (e.g., program an extra trip contact for overcurrent element timing—see preceding Output Contacts subsection).
* Delay and fast curve overcurrent element specifications are found in the Specifications section (Time-Overcurrent Elements). The curve characteristics are listed in Section 9: Setting the
SEL-351P-3 Recloser Control in the SEL-351P-3 Instruction
Manual.
89 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Battery
B
Battery Connections:
Connect a 24 volt lead-acid battery to terminals 6 (+) and
2 (–) of POWER connector J6
(see Figure 12 ).
When ac power is interrupted to the SEL-351P-3, a 24 volt lead-acid battery supplies power to the SEL-351P-3.
The battery discharges to keep the SEL-351P-3 operating until any of the following occur:
• AC power is restored (the SEL-351P-3 continues to operate and the battery starts charging again)
• A battery discharge time limit is reached, the battery is automatically disconnected internally, and the SEL-351P-3 turns off (see following settings discussion)
• A battery discharge voltage limit is reached, the battery is automatically disconnected internally, and the SEL-351P-3 turns off (see following settings discussion)
After the SEL-351P-3 turns off, it wakes up if any of the following occur:
• AC power is restored
• The WAKE UP/DESPERTAR operator control is pressed and the
24 volt battery is reconnected internally
The following four battery-related settings are made with the SET FZ
(global EZ settings) command:
• Battery Amp-hours (6.5–20.0)
• Power-off Delay After AC Loss (OFF, 1–1440 min)
• Power-off Delay After Wake Up (OFF, 1–1440 min)
• Power-off Voltage Level 1 (19.2–24Vdc)
See the Settings section for explanations and default settings.
90 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Battery
Review May be Necessary:
This battery test section makes use of front-panel pushbuttons and serial port commands.
Review the Communications and Front-Panel Interface sections if needed.
Was It a Load Test Failure?
If the BATTERY PROBLEM/
BATERIA PROBLEMA LED is illuminated and MODE doesn’t display BADBAT, then the battery failed the latest load test. See the following Load
Test subsections.
The status of the battery can be checked via the front panel or serial port.
Battery Status via Front Panel
The BATTERY PROBLEM/PROBLEMA BATERIA LED illuminates for any of the following battery problems:
* Load test failure
* Damaged (battery cannot charge)
Press the STATUS pushbutton on the front panel of the SEL-351P-3 to access more battery status information. With the secondary function up/down arrow pushbuttons, move to different status screens. Those of interest for the battery are listed in Table 12.
Table 12: Battery Status Information Accessed From the Front Panel
Display Description
MODE = CHARGE battery is charging
MODE = DISCHG
MODE = DISTST battery is discharging battery load test in progress
MODE = BADBAT battery cannot charge
HRS_LFT = hh:mm–hours and minutes left to run on battery in discharge mode before the SEL-351P-3 puts itself to sleep (dependent on settings “Power-off Delay After AC Loss” and “Power-off Delay
After Wake Up”). Shows XX:XX if battery is charging.
12V_AUX =
VBAT =
IBAT =
12 V power output level–available via terminals 5(+) and 1(-) of
POWER connector J6 (see Figure 12) voltage level of 24 V battery current level (in mA) at which the 24 V battery is charging or discharging (preceded by a minus sign for discharging)
Battery Status via Serial Port
Execute the STATUS command, and have the same information available via the preceding front-panel STATUS/DIAGNO pushbutton.
91 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Battery
The SEL-351P-3 automatically load tests the 24 V battery about every 24 hours.
An internal 24-hour timer cumulatively times whenever the SEL-351P-3 is in the charge mode (120 Vac is powering the SEL-351P-3 and charging the battery; charge rate is 100 mA or less). Even if the battery is fully charged (and not discharging), the SEL-351P-3 is still in the charge mode.
After the 24-hour timer times out (and the SEL-351P-3 is still in the charge mode), an internal 1 Amp load is automatically paralleled with the battery for as many as 5 seconds. If battery voltage drops below 22.0 V during this load test, the test stops and the BATTERY
PROBLEM/PROBLEMA BATERIA LED illuminates and stays illuminated until the next battery test is successful. This load test failure condition can be routed to an output contact if desired (see the Battery
System Monitor subsection in Section 8 of the SEL-351P-3 Recloser
Control Instruction Manual ).
1.
Press the OTHER/VARIOS pushbutton on the front panel of the
SEL-351P-3.
A new screen appears, with BTT (battery test) as one of the choices.
2.
With the arrow pushbuttons, move the underscore to BTT.
3.
To test the battery, press the SELECT/ACEPTAR pushbutton. The battery load test proceeds, and the following message is displayed:
Testing Battery
. . . . . OK/FAIL
The periods on the second line appear consecutively as each second of the five-second load test times by. At the end of the test, OK or FAIL is displayed. If the battery fails the 1 Amp load test (same criteria as described previously in Automatic Battery Load Test ), the BATTERY
PROBLEM/PROBLEMA BATERIA LED illuminates and stays illuminated until the next battery load test is successful. This load test failure condition can be routed to an output contact if desired (see Battery
System Monitor in Section 8 of the SEL-351P-3 Recloser Control
Instruction Manual ).
92 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Battery
1.
Execute the BTT NOW command and the following message is displayed:
Battery test initiated. Duration 5 seconds
.
.
.
.
.
Battery test state is: OK/FAILED
The periods appear on each consecutive line as each second of the fivesecond battery load test times. At the end of the test, OK or FAILED is displayed. If the battery fails the 1 Amp load test (same criteria as described previously in Automatic Battery Load Test ), the BATTERY
PROBLEM/PROBLEMA BATERIA LED illuminates and stays illuminated until the next battery load test is successful. This load test failure condition can be routed to an output contact if desired (see the
Battery System Monitor subsection in Section 8 of the SEL-351P-3
Recloser Control Instruction Manual ).
2.
Execute the BTT command to see how much time remains until the next automatic battery discharge test. If the battery is okay (it is charging or discharging), the following message is displayed:
Battery test state is: OK/FAILED Time until next battery test:
XX.X hours
The “next battery test” is the automatic load test described previously in
Automatic Battery Load Test .
Value XX.X gives time until the next battery test to the nearest tenth of an hour. If 24+ is displayed for value XX.X, this infers an indeterminate amount of time until the next automatic load test (the battery is either discharging or it is charging at a rate greater than 100 mA).
93 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Specifications
S
Terminal
Connections
Stranded copper wire. Minimum temperature rating of 105°C.
Plug-in Connectors, Tightening Torque:
Minimum: 4.4 in-lb (0.5 Nm)
Maximum: 8.8 in-lb (1.0 Nm)
Power Supply 85–264 Vac
12 Vdc Output 11–14 Vdc, 6 W continuous, 13 W for 1 second.
AC Voltage
Inputs
AC Current
Inputs
Voltage Inputs V1, V2, V3, and V
300 V
L-N seconds.
S
.
continuous option (connect any voltage up to 300 Vac). 600 V
L-N
for 10
Burden: 0.03 VA @ 67 V; 0.06 VA @ 120 V; 0.8 VA @ 300 V.
3 V
L-N
continuous option (connect any voltage up to 3 Vac).
1 A nominal option: 3 A continuous, 100 A for 1 second, linear to 20 A symmetrical.
250 A for 1 cycle.
Burden: 0.13 VA @ 1 A, 1.31 VA @ 3 A.
0.01 A nominal option: 0.03 A continuous, 1A for 1 second, linear to 0.2 A symmetrical.
2.5 A for 1 cycle.
Sensitive Earth Fault
0.05 A nominal channel IN current input option: 1.5 A continuous, 20 A for 1 second, linear to 1.5 A symmetrical.
100 A for 1 cycle.
Burden: 0.0004 VA @ 0.05 A, 0.36 VA @ 1.5 A.
0.005 A nominal channel IN current input option: 0.15 A continuous, 2 A for 1 second, linear to 0.15 A symmetrical.
10 A for 1 cycle.
Frequency and
Rotation
60/50 Hz system frequency and ABC/ACB phase rotation are user-settable.
Frequency tracking range: 40.1–65 Hz (voltage connection to V1 required for frequency tracking).
94 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
95
Specifications
Output Contacts
Except Trip and
Close
Trip and Close
Outputs
Optoisolated
Input Ratings
Per IEC 255-0-20:1974 , using the simplified method of assessment:
6 A continuous carry
30 A make per IEEE C37.90-1989
100 A for one second
270 Vac/360 Vdc MOV for differential surge protection
Pickup/dropout time: < 5 ms
Breaking Capacity (L/R = 40 ms):
24 V
48 V
125 V
250 V
0.5 A
0.5 A
0.3 A
0.2 A
10,000 operations
10,000 operations
10,000 operations
10,000 operations
Cyclic Capacity (L/R = 40 ms):
24 V 0.5 A
48 V
125 V
250 V
0.5 A
0.3 A
0.2 A
2.5 cycles per second
2.5 cycles per second
2.5 cycles per second
2.5 cycles per second
Made for interface only to the Hawker Siddeley Switchgear Ltd./Whipp & Bourne
GVR Relcoser.
24 Vdc: on for 16.0–30 Vdc
Optoisolated
Input Ratings
(when used with ac control signals)
With nominal control voltage applied, each optoisolated input draws approximately 4 mA of current.
24 Vdc: on for 12.8–30.0 Vac
AC mode is selectable for each input via Global settings IN101D–IN106D. AC input recognition delay from time of switching: 0.75 cycles maximum pickup;
1.25 cycles maximum dropout.
Time-Code Input Relay module accepts demodulated IRIG-B time-code input at Port 1 and Port 2
(Port 1 is an optional EIA-485 port). Do not connect the time-code input into both
Port 1 and Port 2 at the same time. Relay time is synchronized to within ± 5 ms of time-source input.
Serial
Communications
Two side-panel and one front-panel EIA-232 serial communications ports.
One optional side panel EIA-485 serial port with 2100 Vdc of isolation.
Routine Dielectric
Test
Per-port baud rate selections: 300, 1200, 2400, 4800, 9600, 19200, 38400.
Control ac power: 2500 Vac for 10 seconds.
Optoisolated inputs, analog inputs, and output contacts except Trip and Close:
3100 Vdc for 10 seconds.
Operating Temp.
Relay module: –40° to +85°C (–40° to +185°F)
[LCD contrast impaired for temps. below –20°C (–4°F)]
Environment IEC 68-2-30:1980 Basic environmental testing procedures, Part 2: Test - Tests
Ca; Damp heat, cyclic . Severity Level: (12 + 12-hr cycle).
RFI and
Interference Tests
IEEE C37.90.1-2002 IEEE SWC Tests for Protective Relays and Relay Systems
(2.5 kV oscillatory, 4 kV fast transient) (type test).
IEEE C37.90.2-1995 Standard, Withstand Capability of Relay Systems to
Radiated Electromagnetic Interference from Transceivers, 35 V/m (type test with enclosure door open).
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Specifications
IEC 801-4:1988 Electromagnetic compatibility for industrial-process measurement and control equipment, Part 4: Electrical fast transient/burst requirements , Severity Level: 4 (4 kV on optional power supply, 2 kV on inputs and outputs) (type test).
IEC 255-22-1:2007 Electrical disturbance tests for measuring relays and protection equipment, Part 1: 1 MHz burst disturbance tests. Severity Level 3
(2.5 kV common mode, 1.0 kV differential) (type test).
IEC 255-22-3:2000 Electrical relays, Section 3: Radiated electromagnetic field disturbance tests , Severity Level: 3 (10 V/m) (type test).
IEC 255-22-4:2008 Electrical disturbance tests for measuring relays and protection equipment, Section 4: Fast transient disturbance test (type test).
IEC 255-5:2000 Electrical relays, Part 5: Insulation tests for electrical relays,
Section 6: Dielectric Tests, Series C (2500 Vac on analog inputs including control ac power; 3100 Vdc on power supply inputs, contact inputs, and contact outputs excluding Trip and Close). Section 8: Impulse Voltage Tests , 0.5 Joule, 5 kV (type test).
Impulse Tests IEC 255-21-1:1988 Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on measuring relays and protection equipment, Section 1 - Vibration tests (sinusoidal), Class 1 (relay module only).
Vibration and
Shock Test
IEC 255-21-2:1988 Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on measuring relays and protection equipment, Section 2 - Shock and bump tests, Class 1 (relay module only).
IEC 255-21-3:1993 Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on measuring relays and protection equipment, Section 3 - Seismic tests, Class 2 (relay module only).
ESD Test IEC 255-22-2:2008 Electrical disturbance tests for measuring relays and protective equipment, Section 2: Electrostatic discharge tests , Severity Level: 4
(8 kV contact discharge all points except serial ports, 15 kV air discharge to all other points) (type test).
SEL-351P-3 recloser controls with AC voltage inputs rated 3 Vac nominal or AC current inputs rated
0.01 A nominal (IN channel rated 0.005 A nominal) are not tested to the following standards:
IEEE C37.90.1, IEEE C37.90.2, IEC 801-4, IEC 255-22-3, IEC 255-22-4, and IEC 255-22-5.
Pickup Range:
Instantaneous/Definite-Time Overcurrent Elements
0.05–20.00 A, 0.01 A steps (1 A nominal)
0.20–34.00 A, 0.01 A steps (1 A nominal—for phase-to-phase elements)
0.005–1.500 A, 0.001 A steps (0.05 A nominal channel IN current input)
Steady-State Pickup Accuracy: ±0.01 A and ±3% of setting (1 A nominal)
±1 mA and ±5% of setting (0.05 A nominal channel IN current input)
96 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
97
Specifications
Transient Overreach:
Time Delay:
Timer Accuracy:
±5% of pickup
0.00–16,000.00 cycles, 0.25-cycle steps
±0.25 cycle and ± 0.1% of setting
Pickup Range:
Time-Overcurrent Elements
0.10–3.20 A, 0.01 A steps (1 A nominal)
0.005–0.160 A, 0.001 A steps (0.05 A nominal channel IN current input)
Steady-State Pickup Accuracy:
Time Dial Range:
Curve Timing Accuracy:
±0.01 A and ±3% of setting (1 A nominal)
±1 mA and ±5% of setting (0.05 A nominal channel IN current input)
0.50–15.00, 0.01 steps (US)
0.05–1.00, 0.01 steps (IEC)
0.10–2.00, 0.01 steps (recloser curves)
±1.50 cycles and ±4% of curve time for current between 2 and 30 multiples of pickup
Pickup Ranges:
Under and Overvoltage Elements
0.0–150.0 V, 0.1 V steps (various elements; 300
Vac voltage inputs)
0.0–260.0 V, 0.1 V steps (phase-to-phase elements; 300 Vac voltage inputs)
Steady-State Pickup Accuracy:
Transient Overreach:
±1 V and ±5% of setting
±5% of pickup
Synchronism-Check Elements
Slip Frequency Pickup Range: 0.005–0.500 Hz, 0.001 Hz steps
Slip Frequency Pickup Accuracy:
Phase Angle Range:
Phase Angle Accuracy:
±0.003 Hz
0–80°, 1° steps
±4°
Under- and Overfrequency Elements
Pickup Range:
Steady-State plus Transient Overshoot:
40.10–65.00 Hz, 0.01 Hz steps
±0.01 Hz
Time Delay:
Timer Accuracy:
2.00–16,000.00 cycles, 0.25-cycle steps
±0.25 cycle and ±0.1% of setting
SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
Specifications
Timers
Pickup Ranges:
0.00–999,999.00 cycles, 0.25-cycle steps
(reclosing relay and some programmable timers)
0.00–16,000.00 cycles, 0.25-cycle steps (some programmable and other various timers)
Pickup and dropout accuracy for all timers: ±0.25 cycle and ±0.1% of setting
Accuracies are specified at 20 ° C and at nominal system frequency unless noted otherwise.
Voltages V
A
, V
B
, V
C
, V
S
, 3V
0
, V
1
, V
2
±0.2% (33.5–150 V; 300 Vac voltage inputs)
Currents I
A
, I
B
, I
C
±3.0 mA and ±0.1% (0.1–2 A) (1 A nominal)
Temperature coefficient:
[(0.0002%)/(°C) 2 ] * (___°C – 20°C) 2
(see example below)
Currents I
N
, I
1
, 3I
0
, 3I
2
±0.01 A and ±3% (0.1–20 A) (1 A nominal)
±1 mA and ±5% (0.01–1.5 A) (0.05 A nominal channel IN current input)
Phase Angle Accuracy ±1.0°
Metering accuracy calculation example for currents I
A coefficient:
, I
B
, and I
C
due to preceding stated temperature
For temperature of 40 ° C, the additional error for currents I
A
, I
B
, and I
C
is:
[(0.0002%)/( ° C) 2 ] * (40°C – 20°C) 2 = 0.08%
We appreciate your interest in SEL products and services. If you have questions or comments, please contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court
Pullman, WA USA 99163-5603 USA
Telephone: +1.509.332.1890
Fax: +1.509.332.7990
Internet: www.selinc.com
Email: info@selinc.com
98 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
APPENDIX A: Quick-Start Guide Change Information
APPENDIX A: Q
-S
G
C
I
Changes in this guide to date are summarized below (most recent revisions listed at top).
Revision
Date
Summary of Revisions
The Quick-Start Guide Change Information section has been created to begin a record of revisions to this manual. All changes will be recorded in this Summary of Revisions table.
20100211 • Initial version.
99 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
APPENDIX B: Replace Existing Panacea or Amazon Recloser Controls With the SEL-351P-3 Recloser Control
APPENDIX B: R
E
P
A
R
C
W
SEL-351P-3
R
C
Panacea and Amazon
Recloser Controls Are
Essentially the Same:
Panacea and Amazon
Recloser Controls are essentially the same, just different front-panel panel labeling/language. These recloser controls are also referred to as the SEL-351P-2
Recloser Control (or the older
SEL-351P-1 or SEL-351P
How the SEL-351P-3
Recloser Control Differs
From the Panacea and
Amazon Recloser Controls:
• Powered by AC power
(read this Appendix) instead of DC power.
• Battery charger is constantvoltage, not constant current (changes in batterrelated settings, too—see
Battery section.
• Various voltage and current options (see Table 1).
Panacea or Amazon Recloser Controls can be replaced with the
SEL-351P-3 Recloser Control, but accommodation has to be made to power the SEL-351P-3 Recloser Control with AC power (see Power
Supply Range in the Specifications section). The AC power connection details are given in this section. No other changes have to be made. The
DC voltage that powered Panacea or Amazon Recloser Controls (via terminals 16 and 9 of CONTROL connector J5) is still connected up to the SEL-351P-3 Recloser Control, but this DC voltage no longer provides power to the SEL-351P-3 Recloser Control (see Figure 13).
Near the top of Figure 3 (and Figure 4 through Figure 8—see Table 1 for
SEL-351P-3 Recloser Control model differences), notice the new addition of the POWER IN connector J7 on the SEL-351P-3 Recloser Control
(compared to Panacea or Amazon Recloser Controls)—this is where AC power is connected. See the Power Supply Connection side bar note accompanying Figure 12 and note the internal connection of POWER IN connector J7 (terminals 1 and 2) and POWER connector J6 (terminals 4 and 8) shown in Figure 12. Connecting AC power to POWER IN connector J7 (terminals 1 and 2) will “heat up” POWER connector J6
(terminals 4 and 8). In existing Panacea or Amazon Recloser Control cabinets, no connection is made to terminals 4 and 8 of POWER connector J6. Thus, terminals 4 and 8 of POWER connector J6 remain effectively unused in this recloser control replacement process.
Steps for Recloser Control Replacement
1.
Verify the cabinet (containing the Panacea or Amazon Recloser
Control) is properly grounded.
2.
De-energize the entire cabinet for the Panacea or Amazon Recloser
Control, including the incoming AC power.
3.
Remove the side panel connections to the Panacea or Amazon
Recloser Control. Remove the side panel GROUND connection last.
4.
Remove the Panacea or Amazon Recloser Control from the cabinet swing panel.
5.
Find the existing connector for AC power in the rear of the cabinet
(see Figure 23). Trace the existing wiring to this existing connector and confirm that it brings in AC power from outside the cabinet.
These existing wires should already be completely de-energized, per previous steps.
100 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
APPENDIX B: Replace Existing Panacea or Amazon Recloser Controls With the SEL-351P-3 Recloser Control
The existing connector shown in Figure 23 could possibly differ in type and wiring connections.
Consult with the cabinet manufacturer.
6.
Remove this existing connector in Figure 23 from its mating connector in the rear of the cabinet.
7.
If not already tagged for identification, tag the existing Line (Hot) and Neutral wires shown in Figure 23.
8.
Remove the existing Line (Hot) and Neutral wires from the existing connector in Figure 23. Do not remove the existing Ground wire.
9.
Figure 24 shows cable C5586 which will bring AC power from the existing connector in the rear of the cabinet to the SEL-351P-3
Recloser Control.
10.
Carefully install the blade for the white wire of cable C5586 into the Neutral wire position of the existing connector, along with the existing Neutral wire. Place the blade (white wire) to allow maximum room for reinstalling the existing Neutral wire. Tighten the combination of blade (white wire) and existing Neutral wire, following the tightening torque recommendations of the cabinet manufacturer.
11.
Carefully install the blade for the black wire of cable C5586 into the Line (Hot) wire position of the existing connector, along with the existing Line (Hot) wire. Place the blade (black wire) to allow maximum room for reinstalling the existing Line (Hot) wire.
Tighten the combination of blade (black wire) and existing Line
(Hot) wire, following the tightening torque recommendations of the cabinet manufacturer.
12.
The resultant wiring on the existing connector should now appear as the top portion of Figure 25 (cable C5586 is not yet connected to the SEL-351P-3 Recloser Control).
13.
Reconnect this rewired existing connector to its mating connector in the rear of the cabinet.
14.
Install the SEL-351P-3 Recloser Control on the cabinet swing panel.
Make the GROUND connection on the SEL-351P-3 Recloser Control side panel. Do not make any other connections yet.
Route cable C5586 so that it makes a sensible path to the swing panel and can be connected to POWER IN connector J7 on the SEL-351P-3
Recloser Control (do not make any connection yet). Use wire ties to fix cable C5586 in place enroute. Make allowance for the transition to the swing panel, so that cable C5586 does not become pinched, strained, or otherwise damaged at the swing panel hinge transition. Do not connect cable C5586 to the SEL-351P-3 Recloser Control yet.
15.
Re-energize the cabinet, including the incoming AC power.
16.
Make any necessary measurements, including the AC voltage on the cable C5586 connector, verifying its adequacy (see Power
Supply Range in the Specifications section).
101 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
APPENDIX B: Replace Existing Panacea or Amazon Recloser Controls With the SEL-351P-3 Recloser Control
17.
If the SEL-351P-3 Recloser Control has not been set yet, connect cable C5586 to POWER IN connector J7 on the SEL-351P-3
Recloser Control side panel as shown in the bottom portion of
Figure 25 (skip to the next step if settings have already been made).
The connector clip on cable C5586 will positively lock in place on
POWER IN connector J7. Do not make any other connections yet.
In a few seconds, the CONTROL ENABLED/CONTROL
HABILITADO LED and the AC SUPPLY/ALIM CA LED will illuminate. See the Low Capacitor Voltage Alarm on Display side bar note accompanying Figure 16. Make settings. When finished making settings, disconnect cable C5586 from POWER IN connector J7 on the SEL-351P-3 Recloser Control side panel, entirely de-energizing the SEL-351P-3 Recloser Control.
18.
Reconnect the power system current and voltage to the respective
CURENTS and VOLTAGES connectors on the SEL-351P-3
Recloser Control side panel (see Table 1 for various voltage and current options). Then, reconnect CONTROL connector J5 and
POWER connector J6. The SEL-351P-3 Recloser Control should still be de-energized.
19.
Connect cable C5586 to POWER IN connector J7 on the
SEL-351P-3 Recloser Control side panel as shown in the bottom portion of Figure 25. The connector clip on cable C5586 will positively lock in place on POWER IN connector J7. In a few seconds, the CONTROL ENABLED/CONTROL HABILITADO
LED and the AC SUPPLY/ALIM CA LED will illuminate. See the
Low Capacitor Voltage Alarm on Display side bar note accompanying Figure 16.
20.
Perform any other necessary commissioning.
Figure 23: Existing Connector and Wiring for Incoming AC Power into an Existing Panacea or Amazon Recloser Control Cabinet
102 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide
APPENDIX B: Replace Existing Panacea or Amazon Recloser Controls With the SEL-351P-3 Recloser Control blades black white clip
Cable
C5586
Figure 24: Cable C5586 for bringing AC Power to the SEL-351P-3 Recloser Control
Figure 25: Cable C5586 connected to bring AC Power from the Rear of the Existing Cabinet to the SEL-351P-3 Recloser Control
103 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide