SEL-351P-3

Recloser Control

Quick-Start Installation and User’s Guide

2010021 1

*PM351P-04*

!

CAUTION

Equipment components are sensitive to electrostatic discharge

(ESD). Undetectable permanent damage can result if you do not use proper ESD procedures. Ground yourself, your work surface, and this equipment before removing any cover from this equipment. If your facility is not equipped to work with these components, contact SEL about returning this device and related SEL equipment for service.

!

DANGER

Contact with instrument terminals can cause electrical shock that can result in injury or death.

!

ATTENTION

Les composants de cet équipement sont sensibles aux décharges électrostatiques (DES). Des dommages permanents non-décelables peuvent résulter de l’absence de précautions contre les DES. Raccordez-vous correctement à la terre, ainsi que la surface de travail et l’appareil avant d’en retirer un panneau. Si vous n’êtes pas équipés pour travailler avec ce type de composants, contacter SEL afin de retourner l’appareil pour un service en usine.

!

DANGER

Tout contact avec les bornes de l’appareil peut causer un choc

électrique pouvant entraîner des blessuers ou la mort.

© 2010 by Schweitzer Engineering Laboratories, Inc. All rights reserved.

All brand or product names appearing in this document are the trademark or registered trademark of their respective holders. No SEL trademarks may be used without written permission. SEL products appearing in this document may be covered by US and Foreign patents.

Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded under federal and international copyright and patent laws in its products, including without limitation software, firmware, and documentation.

The information in this manual is provided for informational use only and is subject to change without notice. Schweitzer Engineering

Laboratories, Inc. has approved only the English language manual.

This product is covered by the standard SEL 10-year warranty. For warranty details, visit www.selinc.com or contact your customer service representative.

PM351P-04

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide Date Code 2010021 1

Table of Contents

TABLE OF CONTENTS

INTRODUCTION ............................................................................................................. 1

About This Quick-Start Installation and User's Guide .................................................................. 1

Safety Information ...................................................................................................................... 1

INSTALLATION ............................................................................................................... 3

Making the PT Ratio Setting for the Various SEL-351P-3 Options in Figure 9 ........................... 10

Making the CT Ratio Setting for the SEL-351P-3 in Figure 11 .................................................. 13

Mounting .................................................................................................................................. 17

Panel Cutout...................................................................................................................... 17

Mounting Holes ................................................................................................................. 17

Wire Harness Mounting ..................................................................................................... 17

Side Panel Connections ............................................................................................................. 17

Extra I/O ........................................................................................................................... 17

User-Supplied Connectors.................................................................................................. 18

Current and Voltage Connections .............................................................................................. 18

Voltage Inputs ................................................................................................................... 18

Current Inputs ................................................................................................................... 19

POWER Connector J6 and POWER IN Connector J7 Details .................................................... 19

24 Vdc Battery .................................................................................................................. 19

12 Vdc Power Output ........................................................................................................ 19

CONTROL Connector J5 Details .............................................................................................. 20

24 Vdc Whetting Voltage ................................................................................................... 20

Capacitor Voltage Monitor and Charger Control ................................................................ 20

Boost Power Switch........................................................................................................... 20

Trip and Close Outputs...................................................................................................... 21

SF6 Pressure Sensor .......................................................................................................... 21

Checks Before the SEL-351P-3 Is Put in Service ....................................................................... 22

COMMUNICATIONS ..................................................................................................... 23

Getting Started With Communications ....................................................................................... 23

Communications Connections Example ..................................................................................... 24

Serial Ports ............................................................................................................................... 25

Serial Port Default Settings ....................................................................................................... 25

EIA-232 Pinout Functions for Ports 2, 3, and F ......................................................................... 25

EIA-485 Pinout Functions for Port 1 ......................................................................................... 26

Serial Communications Port Pin Function Definitions ................................................................ 26

Communications Cables ............................................................................................................ 26

Cable Diagrams ........................................................................................................................ 27

Commands ................................................................................................................................ 27

Event Reports ........................................................................................................................... 31

Access Levels and Password Protection ..................................................................................... 32

View or Change Passwords ....................................................................................................... 33

Disable Passwords .................................................................................................................... 33

Password Jumper ...................................................................................................................... 34

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide i

Table of Contents

FRONT-PANEL INTERFACE ....................................................................................... 36

Status and Trip Target LEDs ..................................................................................................... 38

Pushbuttons ............................................................................................................................... 39

Pushbutton Primary Functions ................................................................................................... 41

Operator Controls ...................................................................................................................... 44

SETTINGS..................................................................................................................... 50

Curve Information ..................................................................................................................... 50

Factory EZ Settings ................................................................................................................... 52

Settings Descriptions ................................................................................................................. 55

Settings Groups 1 (Main) and 2 (Alternate) EZ Settings ............................................................. 55

Global EZ Settings .................................................................................................................... 78

TESTING ....................................................................................................................... 87

Testing the SEL-351P-3 Without Regularly Installed Apparatus................................................. 87

Logic Settings Changes ...................................................................................................... 87

Front Panel Status LEDs .................................................................................................... 87

Recloser Simulator ............................................................................................................. 88

Output Contacts ................................................................................................................. 88

Overcurrent Element Timing Test Setup ..................................................................................... 89

BATTERY...................................................................................................................... 90

Battery Operation Overview ...................................................................................................... 90

Battery-Related Settings ............................................................................................................ 90

Battery Status ............................................................................................................................ 91

Battery Status via Front Panel ............................................................................................ 91

Battery Status via Serial Port ............................................................................................. 91

Automatic Battery Load Test ..................................................................................................... 92

Battery Load Test via Front Panel .............................................................................................. 92

Battery Load Test via Serial Port ............................................................................................... 93

SPECIFICATIONS ......................................................................................................... 94

SEL-351P-3 recloser controls with AC voltage inputs rated 3 Vac nominal or AC current inputs rated 0.01 A nominal (IN channel rated 0.005 A nominal) are not tested to the following standards: IEEE C37.90.1, IEEE C37.90.2, IEC 801-4, IEC 255-22-3, IEC

255-22-4, and IEC 255-22-5. ............................................................................................. 96

Relay Element Pickup Ranges and Accuracies............................................................................ 96

Instantaneous/Definite-Time Overcurrent Elements ............................................................. 96

Time-Overcurrent Elements ................................................................................................ 97

Under- and Overvoltage Elements ....................................................................................... 97

Synchronism-Check Elements ............................................................................................. 97

Under- and Overfrequency Elements ................................................................................... 97

Timers ............................................................................................................................... 98

Metering Accuracy .................................................................................................................... 98

Factory Assistance..................................................................................................................... 98 ii SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Table of Contents

APPENDIX A: QUICK-START GUIDE CHANGE INFORMATION ................................ 99

APPENDIX B: REPLACE EXISTING PANACEA OR AMAZON RECLOSER

CONTROLS WITH THE SEL-351P-3 RECLOSER CONTROL .................................. 100

Steps for Recloser Control Replacement ............................................................................100

TABLES

Table 1: SEL-351P-3 Voltage and Current Options ........................................................................... 14

Table 2: SEL EIA-232 Serial Communications Cable Guide ............................................................. 26

Table 3: SEL-351P-3 Recloser Control Command Summary ............................................................. 28

Table 4: Event Report Parameters ..................................................................................................... 32

Table 5: Access Level, Summary Information ................................................................................... 33

Table 6: Front-Panel Pushbutton Secondary Functions ...................................................................... 40

Table 7: Recloser Curve Designations ............................................................................................... 51

Table 8: US, IEC, and User-Programmable Curve Designations ........................................................ 51

Table 9: EZ Settings Quick Reference ............................................................................................... 53

Table 10: Seconds-to-Cycles Conversion (60 Hz) ................................................................................ 63

Table 11: Recloser Interrupt Data ....................................................................................................... 79

Table 12: Battery Status Information Accessed From the Front Panel .................................................. 91

FIGURES

Figure 1: SEL-351P-3 Recloser Control Dimensions ............................................................................ 3

Figure 2: SEL-351P-3 Recloser Control Panel Cutout Dimensions ....................................................... 3

Figure 3: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J3 and Current

Connector J10—Traditional Option....................................................................................... 4

Figure 4: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J4 and Current

Connector J10 ....................................................................................................................... 5

Figure 5: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J3 and Current

Connector J11 ....................................................................................................................... 6

Figure 6: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J4 and Current

Connector J11 ....................................................................................................................... 7

Figure 7: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J8/J9 and Current

Connector J10 ....................................................................................................................... 8

Figure 8: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J8/J9 and Current

Connector J11 ....................................................................................................................... 9

Figure 9: SEL-351P-3 Voltage Connector Options ............................................................................. 10

Figure 10: SEL-351P-3 Current Connector J10—Traditional Option .................................................... 11

Figure 11: SEL-351P-3 Current Connector J11 .................................................................................... 12

Figure 12: SEL-351P-3 Relay Inputs, Outputs, and Communications Ports .......................................... 15

Figure 13: Trip and Close Circuit, Breaker Status, and SF6 Pressure Connections ................................ 16

Figure 14: SEL-351P-3 Recloser Control Communications Connections Example ................................ 24

Figure 15: Jumper, Connector, and Major Component Locations on the SEL-351P-3 Recloser

Control Main Board ............................................................................................................ 35

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide iii

Table of Contents

Figure 16: SEL-351P-3 Recloser Control Front-Panel Interface (English) ............................................. 36

Figure 17: SEL-351P-3 Recloser Control Front-Panel Interface (Spanish) ............................................. 37

Figure 18: Status and Trip Target LEDs (English) ................................................................................ 38

Figure 19: Status and Trip Target LEDs (Spanish) ............................................................................... 39

Figure 20: Primary and Secondary Functions of Front-Panel Pushbuttons (English) .............................. 39

Figure 21: Primary and Secondary Functions of Front-Panel Pushbuttons (Spanish) .............................. 40

Figure 22: Recloser Simulator Connections to SEL-351P-3 (only a 52a available) ................................ 88

Figure 23: Existing Connector and Wiring for Incoming AC Power into an Existing Panacea or

Amazon Recloser Control Cabinet ..................................................................................... 102

Figure 24: Cable C5586 for bringing AC Power to the SEL-351P-3 Recloser Control ......................... 103

Figure 25: Cable C5586 connected to bring AC Power from the Rear of the Existing Cabinet to the SEL-351P-3 Recloser Control ...................................................................................... 103 iv SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Introduction

I

NTRODUCTION

About This Quick-Start Installation and User's Guide

Replace Existing Panacea or

Amazon Recloser Controls:

See Appendix B .

The SEL-351P-3 interfaces only with a Whipp & Bourne

GVR Recloser.

This SEL-351P-3 Recloser Control Quick-Start Installation and User’s

Guide helps you install, communicate with, set, and test the SEL-351P-3 in its EZ (“easy”) mode of operation. The EZ mode performs traditional recloser control functions and operations.

When using the SEL-351P-3 as a traditional line recloser control, it is only necessary to access the EZ Level (Access Level E) Settings. See the

SEL-351P-3 Instruction Manual for complete information regarding the full functionality of the SEL-351P-3.

The following sections are covered in this documentation:

• Table of Contents

• Introduction

• Installation

• Settings

• Testing

• Battery

• Communications • Specifications

• Front-Panel Interface • Changes ( Appendix A )

• Replacement ( Appendix B )

Safety Information

This Quick-Start Installation and User’s Guide does not cover all of the possible conditions or circumstances that can occur during the installation, operation, or testing of the SEL-351P-3. If additional information is necessary to install, communicate with, or make settings to the control that is not provided in this documentation, please refer to the SEL-351P-3

Instruction Manual or contact SEL for assistance.

This Quick-Start Installation and User’s Guide contains three types of hazard statements:

CAUTION : indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury or equipment damage.

WARNING : indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.

DANGER: indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury.

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 1

Introduction

!

!

!

!

!

CAUTION: The SEL-351P-3 contains devices sensitive to

Electrostatic Discharge (ESD). When working on the relay module with cover removed, work surfaces and personnel must be properly grounded or equipment damage may result.

CAUTION: Do not connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the Settings section of this guide for programming procedures. Failure to comply can result in control and recloser misoperation, equipment damage, and personal injury.

WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this guide. Improper installation, handling, or maintenance can result in death, severe personal injury, and/or equipment damage.

WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury, and/or equipment damage.

DANGER: Contact with instrument terminals may cause electric shock that can result in injury or death.

2 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Installation

I

NSTALLATION

See following Mounting subsection.

Figure 1: SEL-351P-3 Recloser Control Dimensions

Figure 2: SEL-351P-3 Recloser Control Panel Cutout Dimensions

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 3

Installation

Serial Port and IRIG-B:

The serial ports and IRIG-B are explained in the

Communications section.

Ratings:

Ratings for optoisolated inputs, output contacts, current inputs, voltage inputs, and power inputs/outputs are given in the

Specifications section.

N/C Symbol:

A few of the connector terminals are labeled N/C (not connected). see Figure 9(a) for voltage connector J3 details see Figure 10 for current connector J10 details see Table 1 for all voltage and current options/ratings

Figure 3: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J3 and Current

Connector J10—Traditional Option

4 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Installation see Figure 9(b) for voltage connector J4 details see Figure 10 for current connector J10 details see Table 1 for all voltage and current options/ratings

Figure 4: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J4 and Current

Connector J10

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 5

Installation see Figure 9(a) for voltage connector J3 details see Figure 11 for current connector J11 details see Table 1 for all voltage and current options/ratings

Figure 5: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J3 and Current

Connector J11

6 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Installation see Figure 9(b) for voltage connector J4 details see Figure 11 for current connector J11 details see Table 1 for all voltage and current options/ratings

Figure 6: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J4 and Current

Connector J11

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 7

Installation see Figure 9(c) for voltage connector J8/J9 details see Figure 10 for current connector J10 details see Table 1 for all voltage and current options/ratings

Figure 7: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J8/J9 and Current

Connector J10

8 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Installation see Figure 9(c) for voltage connector J8/J9 details see Figure 11 for current connector J11 details see Table 1 for all voltage and current options/ratings

Figure 8: SEL-351P-3 Recloser Control Side Panel with Voltage Connector J8/J9 and Current

Connector J11

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 9

Installation

7

2

8

3

10

5

9

4

6

1

Connector J3

V1

V2

V3

N/C

VS

Connector J4

12

6

8

2

9

3

11

5

10

4

7

1

N/C

N/C

VS

V1

V2

V3

5

2

4

6

3

1

2

1

Connector J9

V1

V2

V3

VS

Connector J8

(a) (b) (c)

(a) Voltage Connector J3: V1, V2, V3, and VS (300 Vac nominal)—Traditional

Option

(b) Voltage Connector J4: V1, V2, V3 (3 Vac), and VS (300 Vac nominal)

(c) Voltage Connector J8/J9: V1, V2, V3, and VS (3 Vac nominal) see Table 1 for all voltage and current options/ratings

Figure 9: SEL-351P-3 Voltage Connector Options

Making the PT Ratio Setting for the Various SEL-351P-3 Options in

Figure 9

Figure 9(a) shows the traditional (300 Vac) voltage inputs, where the PT

Ratio setting (see the Settings section) is set with the ratio of the external primary potential transformers (not shown).

Figure 9(b) and Figure 9(c) have low-level (3 Vac) voltage inputs. The

SEL-351P-3 does not internally scale these low-level (3 Vac) voltage inputs any different than the traditional (300 Vac) voltage inputs. Thus,

1.2 Vac applied to the low-level (3 Vac) voltage inputs appears the same to the SEL-351P-3 as 120 Vac applied to the traditional (300 Vac) voltage inputs. Thus a PT Ratio setting made for the low-level (3 Vac) voltage inputs has to take into account this factor of 100 (= 300 Vac/

3 Vac) difference. For example, if the external voltage step-down device

(for the low-level [3 Vac] voltage inputs) has a ratio of 10,000, then it would need to be adjusted by this factor of 100 for a PT Ratio setting:

10 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Installation

PT Ratio = 10,000 x (1/100) = 100

This adjusted PT Ratio setting makes the primary voltage metering correct. The secondary voltage metering values for the low-level (3 Vac) voltage inputs still appear as 100 times their actual magnitude (e.g., 1.2

Vac applied to the low-level [3 Vac] voltage inputs appears as 120 V secondary in the secondary voltage metering)—nothing can be done about this.

Voltage elements in the “regular” settings (see the SEL-351P-3

Instruction Manual ) are set in Volts secondary. Thus, for a voltage element to pick up for 1.2 Vac applied to the low-level (3 Vac) voltage inputs, the voltage element pickup in the SEL-351P-3 needs to be set at

120 V secondary (= 1.2 x 100). Again, the factor of 100 (= 300 Vac/

3 Vac) comes into play for the low-level (3 Vac) voltage inputs.

If the PT Ratio setting does not apply to all the voltage inputs (voltage inputs V1, V2, and V3 require a different setting than voltage input VS, as is likely in Figure 9(b) with its mixture of 3 Vac and 300 Vac voltage inputs), then separate potential transformer ratio settings are needed (see

“regular” settings PTR and PTRS discussed in the SEL-351P-3

Instruction Manual ).

GVR Recloser

(partial) SEL-351P-3 (partial)

Connector J10 umbilical cable (partial)

5

6

3

4

1

2

7

8

9

N/C

I1

I2

I3

IN

I1, I2, I3 (1 Amp nominal) and IN (0.05 Amp nominal) see Table 1 for all voltage and current options/ratings

Figure 10: SEL-351P-3 Current Connector J10—Traditional Option

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 11

Installation

I1, I2, I3 (0.01 Amp nominal) and IN (0.005 Amp nominal) see Table 1 for all voltage and current options/ratings

Figure 11: SEL-351P-3 Current Connector J11

The interposing current transformers in Figure 11 are integral to particular GVR Recloser models. They require the particular SEL-351P-3 current inputs shown in Figure 11 and further explained/referenced in

Table 1. The winding turns of the interposing current transformers are literally the turns on the indicated sides. For current passing through the interposing current transformers (left-to-right), the current is transformed down:

• by a factor of 1/200 (= 5/1000) for current inputs I1, I2, and I3

• and by a factor of 1/20 (= 50/1000) for current input IN

For example, 1 A from the primary current transformers on the left-hand side of Figure 11 is transformed down to

• 0.005 A [= 1 A x (1/200)] for current inputs I1, I2, and I3

• and 0.05 A (= 1 A x (1/20)] for current input IN after it passes (left-to-right) through the interposing current transformers.

12 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Installation

Making the CT Ratio Setting for the SEL-351P-3 in Figure 11

The CT Ratio setting (see the Settings section) is traditionally set with the ratio of the primary current transformer (the current transformers on the left-hand side of Figure 11, transforming primary current to secondary levels). For example, if the primary current transformers on the left-hand side of Figure 11 are ratio 400, then the traditional setting is: CT Ratio =

400.0.

But, Figure 11 is a unique setup, with the combination of the interposing current transformers inside the GVR Recloser and the internal

SEL-351P-3 low-level current-input circuitry on the right-hand side. With this unique setup, a traditional CT Ratio setting causes primary current to appear as half the true magnitude to the SEL-351P-3. Thus, if 400 A primary is flowing on the primary system on the left-hand side of

Figure 11, the SEL-351P-3 on the right-hand side (with setting CT Ratio

= 400.0) only perceives 200 A primary. Likewise, the SEL-351P-3 perceives only half the true secondary current. For example, if there is 1 A secondary flowing out of the primary current transformers on the left-hand side of Figure 11, the SEL-351P-3 on the right-hand side perceives only

0.5 A secondary. This “half magnitude” perception on the part of the

SEL-351P-3 in Figure 11 applies to all the current channels I1, I2, I3, and

IN.

The solution to this “half magnitude” problem for the SEL-351P-3 in

Figure 11 (for primary current values) is to double the CT Ratio setting.

Thus, a traditional setting of CT Ratio = 400.0 (for primary current transformers of ratio 400) is doubled to CT Ratio = 800.0 (= 2 x 400.0).

Then, primary current metering values appear correct and EZ settings made in Amps primary (see the Settings section) are made as they normally would be, without any adjustment.

This “doubling of the CT Ratio setting” to handle primary current values

(metering and EZ settings) makes no change to secondary metering values from the SEL-351P-3 in Figure 11—secondary metering values still appear as half the traditionally expected magnitude—nothing can be done about this. Likewise, if “regular” settings are made in Amps secondary

(not in Amps primary, as with the EZ settings in the Settings section), then adjustments would have to be made. For example, if a “regular” setting is traditionally set 1 A secondary, then it would be set 0.5 A secondary instead, for a Figure 11 setup. “Regular” settings (made in

Amps secondary) are discussed in the SEL-351P-3 Instruction Manual .

For many traditional recloser installations, only EZ settings need be made

(see the Settings section) and “regular” settings do not have to be made.

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 13

Installation

Side-Panel

Figure

Figure 3

(traditional option)

Figure 4

Figure 5

Figure 6

Figure 7

Figure 8

J4

J10

J3

J11

J4

J11

J8/J9

J10

J8/J9

J11

Table 1: SEL-351P-3 Voltage and Current Options

Voltage and

Current

Connectors

J3

J10

Detail

Figures

Figure 9(a)

Figure 10

Figure 9(b)

Figure 10

Figure 9(a)

Figure 11

Figure 9(b)

Figure 11

Figure 9(c)

Figure 10

Figure 9(c)

Figure 11

Voltage and Current Inputs

Nominal Ratings

Ordering Option

(see Model

Option Table)

2X V1, V2, V3, VS: 300 Vac

I1, I2, I3: 1 Amp

IN: 0.05 Amp

V1, V2, V3: 3 Vac

VS: 300 Vac

I1, I2, I3: 1 Amp

IN: 0.05 Amp

V1, V2, V3, VS: 300 Vac

I1, I2, I3: 0.01 Amp

IN: 0.005 Amp

V1, V2, V3: 3 Vac

VS: 300 Vac

I1, I2, I3: 0.01 Amp

IN: 0.005 Amp

V1, V2, V3, VS: 3 Vac

I1, I2, I3: 1 Amp

IN: 0.05 Amp

V1, V2, V3, VS: 3 Vac

I1, I2, I3: 0.01 Amp

IN: 0.005 Amp

AX

BX

CX

DX

EX

14 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Installation

Voltage and Current

Connectors:

The voltage and current connectors (J3 and J10, respectively) in Figure 12 are for the traditional option shown in Figure 3. See Table 1 for all available voltage and current options.

Power Supply Connection:

Only one 120/240 Vac power supply connection is made – either to connector J7

(terminals 1 and 2) or to connector J6 (terminals 4 and

8). For replacement of existing

Panacea or Amazon Recloser

Controls, the Vac power connection will be made to connector J7—see

Appendix B .

Figure 12: SEL-351P-3 Relay Inputs, Outputs, and Communications Ports

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 15

Installation breaker aux. contacts b a

Trip and

Close

Logic to 24Vdc battery

(POWER connector J6) trip cap fully charged close cap charged

>20 Vdc close

24Vdc inside

SEL-351P-3

Battery

Charger

Charger

Control

13

36/24

Vdc

1

Power

Supply

5

2

10

CONTROL connector

J5 see Note 1 outside

SEL-351P-3 recloser

(partial)

52b

52a

Control Signal to

Cap Charger trip

Boost Power

Switch

16

9 see

Note 1

6

14

7

Power to

Cap Charger

Trip Cap

Close Cap

Cap Return

GVR Recloser (partial)

Manual

Isolator trip

Magnetic

Actuator close

15

8

Note 1: Terminal 9 is also the return for the 24 Vdc whetting voltage on terminal 1, when terminal 1 is paralleled to additional applications (e.g., to whet opto-inputs

IN101 - IN106). Terminal 1 has a load limit of 0.1 A and should be fused for protection (Bussman GMD-0.125 fuse or equivalent).

low pressure

Pressure

Sensor

Whetting

Voltage

+

-

3

11

-

+ pressure

+

-

4

12

SF6 Gas

Pressure

Sensor setting

SF6 low pressure warning threshold

Figure 13: Trip and Close Circuit, Breaker Status, and SF6 Pressure Connections

16 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Installation

Mounting

Room for Connectors and Wiring:

The dimensions in Figure 1 do not make any allowances for connectors and wiring that may be attached to the side panel

(see Figure 12). Some connections (e.g., fiber-optic modems) can protrude up to 4 inches (about 10 cm) out from the surface of the side panel.

Refer to Figure 1 and Figure 2.

Panel Cutout

The front view dimensions 7.00 x 13.00 inches (177.8 x 330.2 mm) refer to the panel cutout dimensions needed for mounting the SEL-SEL-351P-3.

The panel cutout dimensions are slightly smaller than the SEL-351P-3 front-panel overlay, thus providing appropriate coverage of the

SEL-351P-3 front panel when mounted, yet allowing for front panel interface access. SEL-351P-3 front panel overlay details can be seen in

Figure 16 (English) and Figure 17 (Spanish).

Mounting Holes

The six mounting holes are each 0.20 inch (5.2 mm) diameter. A size #6-

32 bolt or mounting stud, with lock nuts is recommended.

Wire Harness Mounting

The two studs on both the top and bottom of the SEL-351P-3 can be used to attach wire clamps for a wire harness draped over the top of the unit (or underneath). The studs accept #10-32 lock nuts.

Side Panel Connections

Refer to Figure 3 through Figure 12. Figure 9 through Figure 12 show what is “behind” the side panel connections shown in Figure 3 through

Figure 8. See Table 1 for all voltage and current options/ratings.

!

WARNING: Connect the GROUND terminal to ground before making any other connection on the side panel. The GROUND spade is 0.25 x 0.03 inches (6.4 x 0.8 mm).

Explained in Other Sections:

The serial ports and IRIG-B shown in Figure 12 are explained in the Communications section. The front-panel

LEDs and operator controls are explained in the Front-Panel

Interface section.

Extra I/O

The extra I/O (output contacts OUT101 through ALARM and optoisolated inputs IN101 through IN106) is not needed for the basic recloser control functions. The extra I/O is available for SCADA connection or other control and is not polarity sensitive. See the

Specifications section for ratings.

The connectors for the extra I/O accept wire size AWG 24 to 12. Strip the wires to 0.3 inch (8 mm) and install with a small slotted-tip screwdriver.

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 17

Installation

User-Supplied Connectors

Connectors J3 through J11 (depending on model; see Table 1 and its figure references) on the side panel are the receptacle end (female), with recessed male terminals inside. The user supplies the complementary plug end (male), with recessed female terminals inside. Each plug end (male) is a different size and uniquely keyed and cannot be inserted into any other receptacle end (female):

J3 Molex Mini-Fit, Jr. order no. 39-01-2105

J4 Molex Mini-Fit, Jr. order no. 39-01-2125

J5 Molex Mini-Fit, Jr.

J6 Molex Mini-Fit, Jr.

J7 Molex Mini-Fit, Jr.

J8 Molex Mini-Fit, Jr. order no. 39-01-2165 order no. 39-01-2085 order no. 39-01-2025 order no. 39-01-2025

J9 Molex Mini-Fit, Jr.

J10 TYCO order no. 39-01-2065 order no. 770021-1

J11 Souriau Connection Technology order no. SMS9P1

The user-supplied plug ends (male) require the following corresponding female terminals be installed in a recessed fashion inside the connector:

Molex order no. 39-00-0055

Tyco

Souriau order no. 770008-4 order no. SM20M1S6

Special tools and procedures are required to install terminals/wiring into the user-supplied connectors.

Current and Voltage Connections

See Table 1 for all voltage and current options/ratings.

The SEL-351P-3 has three analog voltage input terminal connections labeled V1, V2, and V3. Wiring to the power system (potential transformer connections and recloser primary bushing connections) can be random, but correct power system “A-B-C” designation is still needed within the SEL-351P-3 algorithms. EZ Settings and Global EZ settings

(True three-phase voltage connected, Phantom voltages, V123 Terminal

Conn., I123 Terminal Conn., CT Polarity) define how transition occurs between the power system wiring and the SEL-351P-3 relay algorithm.

Frequency Measurement

Voltage input V1 (VOLTAGES connector) also provides the frequency measurement (e.g., for underfrequency load shedding).

Voltage Inputs

Voltage inputs V1, V2, and V3 are the three phase voltage inputs. Voltage input VS is the synchronism check voltage input. Voltage input VS can be used for other functions besides just synchronism check—see Section 3 in the SEL-351P-3 Instruction Manual .

18 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Enable Fault Location if

Three-Phase Voltage is connected:

Use SET n command

[n = 1 (main settings), n = 2 (alternate settings)]

Make the line parameter settings:

Z1MAG, Z1ANG

Z0MAG, Z0ANG, LL

Enable fault locating:

EFLOC = Y

See SET commands in Table 3 in the Communications section.

Installation

Current Inputs

Residual current is derived internally from phase current channels I1, I2, and I3. Residual ground overcurrent elements operate off of this derived residual current.

Neutral ground and sensitive earth fault (SEF) overcurrent elements operate off of current channel IN.

The EZ settings presume that current channel IN is connected residually with phase current channels I1, I2, and I3 by the user. This is required to satisfy the pickup range sensitivity for fast and delay curve-ground overcurrent elements (i.e., for the current input option in Figure 10; for ground overcurrent element pickups below 0.1 A secondary, a neutral ground overcurrent element is used automatically; for ground overcurrent element pickups 0.1 A secondary and above, a residual ground overcurrent element is used automatically).

See the Settings section for more EZ settings details.

POWER Connector J6 and POWER IN Connector J7 Details

Power Supply Connection:

Only one 120/240 Vac power supply connection is made, either to connector J7

(terminals 1 and 2) or to connector J6 (terminals 4 and

8). See Figure 12 and accompanying side-panel note.

24 Vdc Battery

The 24 Vdc battery to power the SEL-351P-3 and external trip/close capacitors (when Vac power is not present on terminals 1 and 2 of

POWER IN connector J7) is connected to POWER connector J6, terminals 6 (+) and 2 (–). See the Battery section for more details.

NOTE: Anytime nominal Vac power is applied to the SEL-351P-3

(terminals 1 and 2 of POWER IN connector J7), the unit automatically turns on and the AC SUPPLY/ALIM CA LED illuminates.

If no power is connected to the SEL-351P-3 (unit is off) and then 24 Vdc battery power is connected to POWER connector

J6 terminals 6 (+) and 2 (–), the unit remains off until the

WAKE UP/DESPERTAR operator control is pressed.

12 Vdc Power Output

12 Vdc power is available on POWER connector J6, terminals 5 (+) and 1

(–). It is used for such applications as powering radios. It is currentlimited and has the following specifications:

Voltage Range Fluctuation: 11–14 Vdc

Maximum Capability: 6 W continuous; 13 W for one second

!

WARNING: No grounds can be installed on the circuits connected to the 12 Vdc voltage source. This voltage source is grounded inside the SEL-351P-3.

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 19

Installation

CONTROL Connector J5 Details

Figure 13 shows greater detail on what is connected to either side of

CONTROL connector J5.

Fuse the 24 Vdc

Whetting Voltage:

Read Note1 in Figure 13.

24 Vdc Whetting Voltage

The 24 Vdc voltage on terminal 1 whets the 52a and 52b breaker auxiliary contacts, which are connected through terminals 5 and 13, respectively. It can also whet the 24 Vdc optoisolated inputs IN101 through IN106 using terminal 9 as a return.

Optoisolated inputs IN101 through IN106 can be configured via settings to operate on ac voltage. See the Optoisolated Input Ratings subsection in the Specifications section for more information on ac operation.

!

WARNING: No grounds can be installed on the circuits connected to the 24 Vdc whetting voltage.

This voltage source is grounded inside the SEL-351P-3.

Connect Battery and Charge

Capacitors for Auto-

Reclosing

Factory-default settings require that the 24 Vdc battery be connected and healthy and the trip and close capacitors be fully charged in order for autoreclosing to proceed after a reclose interval times out.

Capacitor Voltage Monitor and Charger Control

Terminals 6 and 14 monitor trip and close capacitor voltages, respectively.

Terminal 6 indicates when the trip capacitor is fully charged (> 80 V).

The presumption is if the trip capacitor is fully charged to > 80 V, the close capacitor is, likewise, fully charged.

Terminal 14 indicates when the close capacitor is charged to at least 20 V.

Exceeding this 20 V threshold causes the capacitor charger control output

(terminals 10 and 2) to go below 24 Vdc (it is nominally 40 Vdc). This low output signal to the external capacitor charger causes the charger to go to a higher charge rate to quickly charge the capacitors to 90 V.

External Power Supply

An external power supply is also supplying power to the external trip/close capacitor charger, if ac power is present.

If ac power is off, then the external power supply provides no power and the 24 Vdc battery is the only source of power (via the closed Boost

Power Switch) for the external trip/close capacitor charger.

Boost Power Switch

The Boost Power Switch on terminal 16 is usually open when ac power is present. This allows the battery charger inside the SEL-351P-3 module to charge the 24 Vdc battery without outside interference.

The Boost Power Switch closes for any of the following occurrences:

• Trip

• Close

• Start of reclose cycle

• Loss of ac power

The closed Boost Power Switch provides 24 Vdc battery power to an external trip/close capacitor charger. Thus, the battery charger is turned

20 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Installation off while the Boost Power Switch is closed. About two minutes after trip, close, and reclose cycle operations cease (and if ac power is present), the

Boost Power Switch opens again and battery charging resumes.

If the Boost Power Switch is closed due to loss of ac power, it remains closed until the 24 Vdc battery is automatically disconnected (discharging for too long or battery voltage too low—see battery-related settings in the

Battery section). If ac power returns sooner, then there is about a two minute delay before the Boost Power Switch opens again and battery charging resumes.

Trip and Close Outputs

Combinations of FET outputs connected to terminals 7, 8, and 15 provide tripping/closing of the recloser by energizing the magnetic actuator in one direction or the other. The FET outputs are connected in an H-bridge arrangement, with the magnetic actuator in the middle of the H-bridge circuit. The magnetic actuator causes the recloser to:

• open for current in the “trip” direction

• or close for current in the opposite/”close” direction

When the SEL-351P-3 trips the recloser, one trip FET output turns on to connect the trip capacitor (terminal 6) to the magnetic actuator (terminal

7). The other trip FET output completes the circuit from terminal 15 to the capacitor return on terminal 8. At the end of the trip operation, the trip

FET outputs turn off, forcing the extinguishing of the trip current.

When the SEL-351P-3 closes the recloser, one close FET output turns on to connect the close capacitor (terminal 14) to the magnetic actuator

(terminal 15). The other trip FET output completes the circuit from terminal 7 to the capacitor return on terminal 8. At the end of the close operation, the close FET outputs turn off, forcing the extinguishing of the close current.

SF6 Pressure Sensor

Terminals 3 and 11 provide whetting voltage for the SF6 gas pressure sensor on the recloser. Terminals 4 and 12 take in the SF6 gas pressure sensor signal and compare it to an EZ setting threshold for low pressure indication. See the Settings section for more EZ settings details.

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 21

Installation

Checks Before the SEL-351P-3 Is Put in Service

! CAUTION: Do not connect the SEL-351P-3 to an energized recloser until all control settings have been properly programmed and verified and all front-panel operator controls are in their proper state (see

Figure 16 or Figure 17). Refer to the Settings section of this guide for programming procedures. Failure to comply can result in control and recloser misoperation, equipment damage, and personal injury.

Settings Group 3

With factory settings, the LIVE

LINE ENABLED/LINEA VIVA

HABILITADA operator control activates Settings Group 3 when it is engaged—see explanation in the Operator

Controls subsection in the

Front-Panel Interface section.

Thus, certain future settings changes made to Settings

Groups 1 and/or 2 should perhaps be made to Settings

Group 3, too.

If the alternate settings are not going to be used, copy the main settings

(Settings Group 1) to the alternate settings (Settings Group 2) with the

COPY command (i.e., COP 1 2 ; see Table 3 in the Communications section). The settings in both settings groups will then be the same. If the

ALTERNATE SETTINGS/AJUSTES ALTERNATIVOS operator control pushbutton is accidentally pressed (switching the active settings group), the SEL-351P-3 still operates on the same settings. Refer to the

Factory EZ Settings subsection in the Settings section for more information on main and alternate settings.

Set the date and time with the DATE and TIME commands ( DAT and

TIM , respectively; see Table 3 in the Communications section).

22 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Communications

C

OMMUNICATIONS

Topics covered in this section:

• Serial Port Connectors

• Communications Cables

• Commands

• Access Levels

• Password Protection

You can view and change control settings, and obtain event and status information either from the front-panel interface or via one of the serial ports.

You can access many of the features of the SEL-351P-3 from the front panel; however, some features can only be accessed from one of the serial ports. Table 3 provides the serial port commands (with descriptions) as well as the corresponding front-panel pushbutton, if applicable.

Getting Started With Communications

Before you attempt communications with the SEL-351P-3, via either the serial ports or the front-panel interface, the following precautions must be taken:

Hint:

For the best display, use

VT-100 terminal emulation or the closest variation.

• Verify that the SEL-351P-3 has been properly installed and that the settings have been programmed by qualified personnel.

Terminal Emulation

Programs:

Examples of PC-based terminal emulation programs include: ProComm Plus ® ,

Relay Gold ® , Microsoft ®

Windows ® Terminal and

HyperTerminal, SmartCOM ® , and CROSSTALK ® .

• Become familiar with and understand the information presented in the Communications, Front-Panel Interface , and Settings sections.

For serial port communications, the previous two precautions apply. You must also carry out the following:

• Select the appropriate communications cable (usually SEL Cable

C234A—see Table 2).

Default Settings for Front

Panel Serial Port:

Baud Rate = 38400

Data Bits = 8

Parity = N

Stop Bits = 1

• Choose a terminal emulation program on your personal computer

(PC) to communicate with the SEL-351P-3.

• Set the communications parameters for the connected PC communications port to the default settings. (Press the ENTER key, and the SEL-351P-3 will respond with a “=” prompt, which indicates Level 0 access is established—see Table 5.)

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 23

Communications

Communications Connections Example

You can connect the serial port to a computer serial port for local communications or to a modem for remote communications. Other devices useful for automated communications are SEL Communications

Processors.

You can use a variety of terminal emulation programs on your personal computer to communicate with the SEL-351P-3. Figure 14 presents some example SEL-351P-3 communications connections (see Table 2 and contact SEL for more information).

DATA AND TIME-SYNCHRONIZATION* CONNECTIONS

SEL

Communications

Processor

PORT 2

(METALLIC)

Cable #C273A

SEL-351P

Fiber-Optic Cable

#C273AFZ or #C273AF0

SEL

Communications

Processor

SEL-351P

SEL-2810

PORT 2

SEL-351P

Metallic Cable Connection Optical Cable Connection

* Demodulated IRIG-B time code can be input into the connector for either serial port 1 or serial port 2, but not both at the same time.

EIA-485 CONNECTIONS (if ordered with EIA-485 port)

Protection, Integration,

Automation, and Control by SEL.

Computer

PORT 1

SEL-351P (#1)

PORT 1

SEL-351P (#2)

PORT 1

SEL-351P (#32)

LOCAL CONNECTIONS

C ONNECT TO THE SEL

C OMMUNICATIONS P ROCESSOR

ONCE AND COMMUNICATE WITH

ANY CONNECTED SEL R ELAY OR

R

ECLOSER

C

ONTROL

OR

. . .

C

ONNECT TO THE

SEL-351P

R

ECLOSER

C

ONTROL

INDIVIDUALLY VIA THE

F

RONT

-

P

ANEL

S

ERIAL

P

ORT

Cable

#C234A

PORT 2 Side Panel

SEL-351P (#1)

PORT F Front Panel

Front Panel

SEL-2032

PORT 2 Side Panel

SEL-351P (#2)

PORT F Front Panel

DWG: M351P056

Figure 14: SEL-351P-3 Recloser Control Communications Connections Example

24 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Communications

Serial Ports

Three EIA-232 serial communications ports are available:

• Serial Port 2 (side panel)

• Serial Port 3 (side panel)

• Serial Port F (front panel)

An EIA-485 serial communications port is available as an ordering option:

• Serial Port 1 (side panel)

Serial Port Default Settings

DNP Port:

Serial port 3 is factory-set as a

DNP port, with baud rate =

19200. See Appendix H:

Distributed Network Protocol

(DNP3) in the SEL-351P-3

Instruction Manual for more

The default settings for serial ports 1, 2, and F are:

Baud Rate = 2400 (ports 1 and 2); 38400 (port F)

Data Bits = 8

Parity = N

Stop Bits = 1

The serial port default settings can be changed from the front-panel interface or from the serial communications port itself. After connecting the appropriate communications cable and setting the terminal emulator, press the <Enter> key, and the control will respond with a “=” prompt, which indicates Level 0 access is established—see Table 5.

EIA-232 Pinout Functions for Ports 2, 3, and F

DWG: M351R078

DB-9 Connector Pinout (female) for EIA-232 Serial Ports

Make Only One IRIG-B

Connection:

If making an IRIG-B connection, connect demodulated IRIG-B time code to either the serial

Port 2 or serial Port 1 connector

(see the following EIA-485

Pinout Functions for Port 1 ), but not both .

1 N/C* or +5 Vdc

2 RXD

N/C* or +5 Vdc

RXD

3 TXD TXD

4 +IRIG-B N/C

N/C

RXD

TXD

N/C

5, 9 GND GND

6 -IRIG-B N/C

7 RTS

8 CTS

RTS

CTS

GND

N/C

RTS

CTS

* Pin 1 not connected for Ports 2 and 3 when shipped from the factory.

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 25

Communications

EIA-485 Pinout Functions for Port 1

1

SERIAL PORT 1

2 3 4 5 N/C

IRIG-B

+ _

7 8

Pin Function Pin

1 +TX

Function

5 SHIELD

PIN EIA-485

2 -TX

3 +RX

4 -RX

6 N/C

7 +IRIG-B

8 -IRIG-B

Serial Communications Port Pin Function Definitions

Pin Function Definition

Convenient IRIG-B

Connection:

Serial Port 2 provides the most convenient connection for demodulated IRIG-B time code. See the top of Figure 14 and SEL Cable 273A in

Table 2, and the corresponding cable diagram.

+5 Vdc (0.5 Amp limit)

RXD, RX

TXD, TX

IRIG-B

5 Vdc Power Connection

Receive Data

Transmit Data

IRIG-B Time-Code Input

GND Ground

RTS

CTS

DCD

DTR

DSR

Request To Send

Clear To Send

Data Carrier Detect

Data Terminal Ready

Data Set Ready

Communications Cables

Other Cables Available:

Table 2 lists the most commonly used cables (see corresponding cable diagrams on the following page). Contact SEL for information on other available cables.

Table 2: SEL EIA-232 Serial Communications Cable Guide

Connect From:

SEL-351P-3

Connect To:

Computer (9-pin)

SEL Cable:

C234A

C227A

C273A

Processor

SEL-351P-3 Modem C222

26 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Communications

Cable Diagrams

The following cable diagrams correspond to the cables listed in Table 2

(most commonly used cables). The male/female references in the cable diagrams refer to the cable connectors, not the device they are connecting to (which would be the opposite gender). Contact SEL for information on other available cables.

SEL-351P-3 Recloser Control to Computer

Cable C234A

SEL-351P-3 9-Pin *DTE Device

9-Pin Male

“D” Subconnector

9-Pin Female

“D” Subconnector

RXD 2

TXD 3

GND 5

CTS 8

3 TXD

2 RXD

5 GND

8 CTS

* DTE = Data Terminal Equipment (Computer, Terminal,

Printer, etc.)

SEL-351P-3 Recloser Control to Computer

Cable C227A

SEL-351P-3 25-Pin *DTE Device

9-Pin Male

“D” Subconnector

GND 5

TXD 3

RXD 2

GND 9

CTS 8

25-Pin Female

“D” Subconnector

7 GND

3 RXD

2 TXD

1 GND

4 RTS

SEL-351P-3 Recloser Control to

SEL Communications Processor

Cable C273A

* DTE = Data Terminal Equipment (Computer,

Terminal, Printer, etc.)

SEL-351P-3 Recloser Control to Modem

Cable C222

Processor

9-Pin Male

“D” Subconnector

TXD 3

RXD 2

IRIG+ 4

GND 5

IRIG- 6

CTS 8

RTS 7

9-Pin Male

“D” Subconnector

3 TXD

4 IRIG+

5 GND

6 IRIG-

7 RTS

8 CTS

9-Pin Male

“D” Subconnector

GND 5

TXD 3

RTS 7

RXD 2

CTS 8

GND 9

25-Pin Male

“D” Subconnector

7 GND

1 GND

** DCE = Data Communications Equipment

(Modem, etc.)

Commands

Commands, passwords, or settings you type appear in bold/uppercase: DAKOTA .

Computer keys you press appear in bold/brackets :

<Enter> .

The following serial port commands are available for use with the

SEL-351P-3. Much of the information available from the serial port commands is also available via the front-panel pushbuttons (see

Pushbutton Primary Functions in the following section).

The commands are shown in upper-case letters, but they can also be entered using lower-case letters.

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 27

Communications

Table 3: SEL-351P-3 Recloser Control Command Summary

Access Level

Available

Commands

Access

Level 0

ACC

EZA

Access

Level 1

2AC and

BAC

BRE

BRE A

COM

COU

Description

The only operation that can be performed at Access Level 0 is to go to Access Levels 1 or E. The screen prompt is: = (see Table 5)

Enter Access Level 1.

Enter Access Level E.

The Access Level 1 commands primarily allow the user to look at information (e.g., settings, metering), not change it. The screen prompt is: => (see Table 5)

Enter Access Level 2.

Enter Breaker Access Level (Access Level B).

Display breaker/recloser contact wear report.

Display breaker/recloser contact wear and trip operation report.

M IRRORED B ITS

® communications statistics.

Display SEL OGIC

® counter values.

DAT Show date.

DAT m/d/y Enter date in this manner if Date Format setting DATE_F = MDY.

DAT y/m/d Enter date in this manner if Date Format setting DATE_F = YMD.

EVE n Show event report number n with 1/4-cycle resolution.

EVE L n

EVE R n

Show event report number n with 1/16-cycle resolution.

EVE C n

Show raw event report number n with 1/16-cycle resolution.

Show compressed event report number n for use with SEL-5601

Analytic Assistant.

EZA

GRO

Enter EZ Access Level (Access Level E).

Display active group number.

HIS n

HIS C

IRI

MET k

MET D

MET E

MET M

Show brief summary of the n latest event reports.

Clear the brief summary and corresponding event reports.

Force synchronization attempt of internal relay clock to IRIG-B timecode input.

Display instantaneous metering data. Enter k for repeat count.

Display demand and peak demand data.

Display energy metering data.

Display maximum/minimum metering data.

Corresponding

Front-Panel

Pushbutton

(English/Spanish)

OTHER/VARIOS

OTHER/VARIOS

OTHER/VARIOS

OTHER/VARIOS

OTHER/VARIOS

GROUP/CONFIG

GRUPO

EVENTS/EVENTOS

METER/MEDICIÓN

METER/MEDICIÓN

METER/MEDICIÓN

METER/MEDICIÓN

28 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Communications

Access Level and

Available

Commands

MET RD

MET RE

MET RM

MET RP

QUI

Reset demand metering data.

Description

Reset energy metering data.

Reset maximum/minimum metering data.

Corresponding

Front-Panel

Pushbutton

(English/Spanish)

METER/MEDICIÓN

METER/MEDICIÓN

METER/MEDICIÓN

METER/MEDICIÓN

SER n

Reset peak demand metering data.

Quit. Returns to Access Level 0. Terminates SEL Distributed Port

Switch Protocol (LMD) connection.

Show the latest report. n rows in the Sequential Events Recorder (SER) event

SER m n

SER d1

Show rows m through n in the Sequential Events Recorder (SER) event report.

Show rows in the Sequential Events Recorder (SER) event report from date d1.

SER d1 d2 Show rows in the Sequential Events Recorder (SER) event report from date d1 to d2. Entry of dates is dependent on the Date Format setting

DATE_F (= MDY or YMD).

SHO n Show relay settings (overcurrent, reclosing, timers, etc.) for Group n . SET/CONFIG

SHO L n Show SEL OGIC control equation settings for Group n .

SHO EZ n Show EZ settings for Group n . SET/CONFIG

SHO FZ

SHO G

SHO P

SHO R

SHO T

STA

TAR R

TAR

TIM n n k

Show FZ settings (global EZ settings).

Show global settings.

Show Port n settings.

Show Sequential Events Recorder (SER) settings.

Show text label settings.

Show relay self-test status. STA C resets self-test warnings/failures.

Reset the front-panel tripping targets.

Display Relay Word row. If n = 0 through 59, display row n . If n is an element name (e.g., 50A1) display the row containing element n .

Enter k for repeat count.

Show or set time (24-hour time). Show time presently in the relay by entering just TIM (e.g., time 22:47:36 is entered with the following command: TIM 22:47:36).

SET/CONFIG

SET/CONFIG

SET/CONFIG

STATUS/DIAGNO

TARGET

RESET/PRUEBO

LAMP.

OTHER/VARIOS

OTHER/VARIOS

TRI Trigger an event report.

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 29

Communications

Access Level and

Available

Commands

Access

Level E

BTT

Description

The Access Level E commands allow the user to access and change the EZ settings as well as Level 1 commands. The screen prompt is: =+> (see Table 5)

Display status of latest battery discharge test and the time remaining until next battery discharge test.

BTT NOW Force new battery discharge test immediately.

SET EZ

SET FZ

Change recloser control EZ settings.

Change recloser control global EZ settings.

Access

Level B

The Access Level B commands primarily allow the user to operate relay parameters and output contacts. All Access Level 1 and E commands can also be executed from Access Level B. The screen prompt is: ==> (see Table 5)

BRE W

BRE W A

BRE R

CLO

GRO n

OPE

PUL n k

Corresponding

Front-Panel

Pushbutton

(English/Spanish)

OTHER/VARIOS

SET/CONFIG

SET/CONFIG

Preload breaker/recloser contact wear.

Preload breaker/recloser contact wear and trip operation counters.

Open the circuit breaker.

Pulse output contact n (OUT101 through OUT107, ALARM) for k

(1–30) seconds. Parameter n must be specified; k defaults to 1 if not specified.

OTHER/VARIOS

OTHER/VARIOS

Reset breaker/recloser contact wear and trip operation counters.

Close the circuit breaker.

OTHER/VARIOS

Change active group to group n . GROUP/CONFIG

GRUPO

CNTRL/CONTROL

AUX.

Access

Level 2

CON

COP

PAS n m n

PAS 1 xxxxxx

The Access Level 2 commands allow unlimited access to relay settings, parameters, and output contacts. All Access Level 1, E, and B commands are available from Access Level 2. The screen prompt is: =>> (see Table 5)

Control Relay Word bit RB n , Remote Bit n where n = 1 through 16.

Execute CON n , and the relay responds: CONTROL RB n . Then reply with one of the following:

SRB n set Remote Bit n (assert RB n ).

CRB n clear Remote Bit n (deassert RB n ).

PRB n pulse Remote Bit n (assert RB n for 1/4 cycle).

Copy relay and logic settings from Group m to Group n .

Show existing Access Level 1, B, and 2 passwords. SET/CONFIG

Change Access Level 1 password to xxxxxx . SET/CONFIG

30 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Communications

Access Level and

Available

Commands

PAS E xxxxxx

PAS B xxxxxx

PAS 2 xxxxxx

PAS 1

DISABLE

PAS E

DISABLE

PAS B

DISABLE

PAS 2

DISABLE

SET n

SET L n

SET EZ n

SET FZ

SET G

SET P n

SET R

SET T

VER

Description

Corresponding

Front-Panel

Pushbutton

(English/Spanish)

Change Access Level E password to xxxxxx . SET/CONFIG

Change Access Level B password to xxxxxx . SET/CONFIG

Change Access Level 2 password to xxxxxx . SET/CONFIG

Disables Access Level 1 password.

Note: “DISABLE” must be entered in uppercase.

Disables Access Level E password.

Note: “DISABLE” must be entered in uppercase.

Disables Access Level B password.

Note: “DISABLE” must be entered in uppercase.

Disables Access Level 2 password.

Note: “DISABLE” must be entered in uppercase.

Change relay settings (overcurrent, reclosing, timers, etc.) for

Group n .

SET/CONFIG

Change SEL OGIC control equation settings for Group n .

Change EZ settings for Group n . SET/CONFIG

Change FZ settings (global EZ settings).

Change global settings.

SET/CONFIG

SET/CONFIG

Change port n settings.

Change Sequential Events Recorder (SER) settings.

Change text label settings.

Show version information.

SET/CONFIG

Event Reports

Note:

The event report length is selectable: 15 or 30 cycles.

More options are available to customize event reports.

Refer to Section 12 in the

SEL-351P-3 Instruction

Manual for more event information.

Event reports are automatically triggered at the beginning of a fault and when the SEL-351P-3 issues a trip. Event report length is 15 cycles

(factory default). The latest twenty-eight 15-cycle event reports are stored in nonvolatile memory.

To obtain event report information use the EVE command. There are numerous options that allow you to customize event information. For descriptions and examples of all options, refer to the SEL-351P-3

Instruction Manual . The general command format is:

EVE [ n A D ]

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 31

Communications

The parameters in brackets [ ] are optional. The following table defines the parameters [ n A D ] that can be issued with the EVE command to customize the report format.

Table 4: Event Report Parameters

Parameter n Choose event number (1–28). Defaults to 1 if not specified.

Description

A Specifies that the analog section of the event is to be displayed (current, voltage, frequency, contact outputs, and optoisolated inputs).

D Specifies that the digital section (Protection and Control

Elements) of the event is to be displayed.

Summary event information can be viewed at the control front-panel LCD using the front-panel pushbuttons. Press the EVENTS/EVENTOS pushbutton (primary function) and the appropriate left/right and up/down pushbuttons (secondary function) to view event information.

If no parameters are issued with the EVE command, then you will automatically receive both the analog (A) and digital (D) sections of the event report.

Access Levels and Password Protection

Passwords Required With

Front-Panel Pushbuttons?

See Pushbutton Primary

Functions subsection in the

Front-Panel Interface section.

Issue serial port commands to the SEL-351P-3 to view metering values, change recloser control settings, obtain event information, etc. The available serial port commands are listed in Table 3. The commands can be accessed only from the corresponding access level as shown in the table, but a higher access level can access the serial port commands in a lower access level.

Access Level 0 (the lowest access level)

Access Level 1

Access Level E (EZ access level)

Access Level B

Access Level 2 (the highest access level)

As a security measure, entry to a particular access level (except Access

Level 0) requires a unique password. This allows the user to set up a password system to deny unqualified or unauthorized personnel access to higher levels.

The SEL-351P-3 ships from the factory with default passwords (see

Table 5). If restrictions are to be placed on personnel using the

SEL-351P-3, the factory default passwords must be changed. Make sure that password information is stored for future reference in the event that it is lost or forgotten.

32 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Access

Level

0

1

E

B

2

Communications

Access

Command

ACC

EZA

BAC

Table 5: Access Level, Summary Information

Prompt

=

=>

=+>

==>

Factory

Default

Password

Description of Access Level

Command Privileges

Signifies serial communications are established.

The only operation available here is go to Access

Level 1 or Access Level E.

OTTER Primarily allows you to only look at information

(i.e., metering, settings), not change it.

DAKOTA Primarily allows the user to change the EZ group settings and global EZ settings.

EDITH Primarily allows the user to operate output contacts or change the active setting group.

2AC and output contacts.

View or Change Passwords

Want to View a Password?

If you have the Access Level 1 and 2 passwords, enter Access

Level 1, then Access Level 2, execute the PAS command, and view all passwords.

Lost or Forgotten Password?

When passwords are lost or forgotten, you can view the passwords by putting the main board password jumper in place. See the following

Password Jumper subsection.

Want to Operate Without

Passwords?

See the following Disable

Passwords and Password

Jumper subsections.

The PAS command allows you to inspect or change existing passwords

(must be in Access Level 2). To inspect passwords, type PAS<Enter> .

=>> PAS < Enter >

1:OTTER

E:DAKOTA

B:EDITH

2:TAIL

=>>

The factory default passwords for Access Levels 1, E, B, and 2 are shown above. To change the password for Access Level E to BIKE, enter the following:

=>> PAS E BIKE < Enter >

Set

=>>

After entering new passwords, type PAS < Enter > to inspect them. Verify they are what you intended, and record the new passwords.

Passwords may include up to six characters. Valid characters consist of:

‘A–Z’, ‘a–z’, ‘0–9’, ‘-’, and ‘.’. Upper- and lower-case letters are treated as different characters.

Disable Passwords

If you wish to disable password protection for a specific access level

(must be in Access Level 2), simply set the password to DISABLE (must

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 33

Communications be uppercase). For example, to disable the Access Level 1 password, type the following:

=>> PAS 1 DISABLE < Enter >

Password Disabled

=>>

The password protection for Access Level 1 is now disabled.

The following Password Jumper subsection describes how password protection for all access levels can be disabled by a hardware password jumper.

Password Jumper

!

CAUTION: The relay module contains devices sensitive to

Electrostatic Discharge (ESD).

When working on the relay module with front or top cover removed, work surfaces and personnel must be properly grounded or equipment damage may result.

This subsection provides instructions for putting the password jumper in place if you wish to operate the SEL-351P-3 without password protection or in the event that the passwords are lost or forgotten.

When the password jumper (JMP6-A) is ON (in place), password protection is disabled. Figure 15 shows the general location of the password jumper.

When the password jumper is OFF (removed/not in place), password protection is enabled. This is how the SEL-351P-3 ships from the factory.

Then the only way to disable password protection is with the PAS command (see preceding Disable Passwords subsection).

To change the password jumper position, carry out the following steps:

1.

De-energize the SEL-351P-3.

2.

Disconnect all connections to the SEL-351P-3 (remove GROUND last).

3.

Take SEL-351P-3 to an ESD (Electrostatic Discharge) protected work area.

4.

Remove eight Phillips-head screws from front and left side panel of

SEL-351P-3.

5.

Disconnect the ribbon cables from the front panel.

6.

Remove front panel of SEL-351P-3.

7.

Locate the jumper(s) to be changed (refer to Figure 15). Change the jumper position.

8.

Reconnect ribbon cables to front panel.

9.

Replace eight Phillips-head screws in front and left side panel of

SEL-351P-3 relay module.

10.

Reconnect all connections to the SEL-351P-3 (reconnect

GROUND first).

11.

Reenergize the SEL-351P-3.

34 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Communications

Figure 15: Jumper, Connector, and Major Component Locations on the SEL-351P-3 Recloser

Control Main Board

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide 35

Front-Panel Interface

F

RONT

-P

ANEL

I

NTERFACE

English and Spanish

The following figures in this section show labeling for the

English and Spanish models.

Both models operate the same way with factory default settings.

Topics covered in this section:

• Status and Trip Target LEDs

• Pushbuttons

• Operator Controls

User-Configurable Labels

Both models come with standard or user-configurable labels. The dashed lines in the figures indicate the areas for user-configurable labels.

Display (default display shows IA,

IB, IC, and IN primary currents)

Low Capacitor Voltage Alarm on Display

With factory-default settings, the front-panel display will show the following message:

LOW TRIP/CLOSE

CAPACITOR VOLTAG if the external trip or close capacitor voltage is low (see capacitor connections in

Figure 13). This message will also display when the

SEL-351P-3 is powered up, but not connected to the external trip and close capacitors (e.g., the SEL-351P-3 relay module is powered up for a bench test, with no standard installation connections made).

Pushbuttons

Status and Trip

Target LEDs

Operator

Controls

Figure 16: SEL-351P-3 Recloser Control Front-Panel Interface (English)

Target LED Label

Opening

Operator

Control Label i4680c

Opening

36 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

Display (default display shows IA,

IB, IC, and IN primary currents)

Pushbuttons

Status and Trip

Target LEDs

Target LED Label

Opening

Operator

Control Label

Operator

Controls

Figure 17: SEL-351P-3 Recloser Control Front-Panel Interface (Spanish) i4682c

Opening

37 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

Status and Trip Target LEDs

SEL-351P-3

Recloser Control is enabled

Most of the Status and Trip Target LEDs and Operator Controls can change function (if desired by the user) by programming at a higher logic level (see the SEL-351P-3 Instruction Manual ). This Front-Panel

Interface section discusses each function as shipped from the factory and inscribed on the front panel.

Indicates any of the following battery problems:

- discharge test failure

- disconnected

- cannot be charged

- monitor/charger failure

Indicates that a trip occurred

(overcurrent or otherwise)

High-set overcurrent element trip

Vac power is present

Low SF6 gas pressure in recloser

Fast curve overcurrent element trip

Underfrequency trip

CONTROL

ENABLED

AC

SUPPLY

BATTERY

PROBLEM

LOW

PRESSURE TRIP

FAST

CURVE

HIGH

CURRENT

UNDER

FREQ.

Control in reset state and ready for reclose cycle

RESET CYCLE LOCKOUT A B C EF / G SEF

CONTROL STATE

Control actively in trip/reclose cycle mode

All reclose attempts unsuccessful, control in lockout state

Figure 18: Status and Trip Target LEDs (English)

Phase A, B, or C involved in fault

FAULT TYPE

Ground involved in fault

DWG: M351P057

Sensitive earth fault overcurrent element trip

38 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

SEL-351P-3

Recloser Control is enabled

Indicates any of the following battery problems:

- discharge test failure

- disconnected

- cannot be charged

- monitor/charger failure

Vac power is present

Low SF6 gas pressure in recloser

Indicates that a trip occurred

(overcurrent or otherwise)

Fast curve overcurrent element trip

High-set overcurrent element trip

Underfrequency trip

Control in reset state and ready for reclose cycle

Control actively in trip/reclose cycle mode

All reclose attempts unsuccessful, control in lockout state

Figure 19: Status and Trip Target LEDs (Spanish)

Phase A, B, or C involved in fault

Ground involved in fault

Pushbuttons

Sensitive earth fault overcurrent element trip

The front-panel pushbuttons shown in Figure 20 and Figure 21 allow access to settings, metering values, event information, and other functions and information.

Primary Functions

TARGET

RESET

METER EVENTS STATUS OTHER SET CNTRL GROUP

LAMP

TEST CANCEL SELECT EXIT

DWG: M351R043

Secondary Functions

Figure 20: Primary and Secondary Functions of Front-Panel Pushbuttons (English)

39 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

Figure 21: Primary and Secondary Functions of Front-Panel Pushbuttons (Spanish)

The front-panel pushbuttons (except TARGET RESET/LAMP

TEST/PRUEBA LAMP./RESTABLECER) have dual functions (primary and secondary functions). The primary function is the text printed on the pushbutton. After a primary function is selected (e.g., the

STATUS/DIAGNO pushbutton is pressed), the secondary function pushbuttons (e.g., CANCEL/CANCELAR, SELECT/ACEPTAR, left/right arrows, up/down arrows, EXIT/SALIR) are then enabled. The secondary functions allow the user to scroll through information, activate settings/control, etc., on the LCD. The following table lists the primary and secondary functions for the pushbuttons shown in Figure 20 (English) and Figure 21 (Spanish).

Table 6: Front-Panel Pushbutton Secondary Functions

Primary Function Secondary Function

TARGET RESET/PRUEBA LAMP. HELP—Provides help only with front-panel

SET commands.

EVENTS/EVENTOS

STATUS/DIAGNO

OTHER/VARIOS

SET/CONFIG

CNTRL/CONTROL AUX.

GROUP/CONFIG GRUPO edit or escape to upper command level.

SELECT/ACEPTAR—Select displayed option or setting.

 —Scroll left on display.

 —Scroll right on display.

 —Scroll up on display or increment value.

 —Scroll down on display or decrement value.

EXIT/SALIR—Exit entirely from command and return to default display.

Many of the pushbutton primary functions correspond to serial port commands. Some of the pushbutton primary functions require a password to execute. Refer to Communications section for serial port command, access level, and password information.

40 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

Pushbutton Primary Functions

Primary

Function

Corresponding

Serial Port

Command Access Level

TAR R 1

TARGET

RESET

LAMP

TEST

Password for

Front-Panel

Access

None

Description

Illuminate all front-panel LEDs for 1 second and clear trip-latched targets

TRIP/DISPARO, FAST CURVE/CURVA

RÁPIDA, HIGH CURRENT/ALTA

CORRIENTE, UNDER FREQ./BAJA

FREC., A, B, C, G/N, and SEF.

RESTABLECER

METER

Primary

Functions

Corresponding

Serial Port

Command

INST MET

Access Level

1

Password for

Front-Panel

Access

None

ENERGY

MAX/MIN

DISPLAY

RESET

DISPLAY MET E

RESET

DEMAND

MET RE

MET M

MET RM

DISPLAY MET D

RESET MET RD

MET RP

1

1

1

1

1

1

1 None

None

None

None

None

None

None

Description

Display instantaneous magnitudes (and angles if applicable) of meter values.

Display energy meter values.

Reset energy meter values.

Display maximum/minimum meter values.

Reset maximum/minimum meter values.

Display demand and peak demand meter values.

Reset demand meter values.

Reset peak meter values.

41 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

Primary

Function

Corresponding

Serial Port

Command

HIS

Access Level

1

Password for

Front-Panel

Access

None

Description

Show SEL-351P-3 event data.

EVENTS

EVENTOS

Primary

Function

STATUS

Corresponding

Serial Port

Command

STA

Access Level

1

Password for

Front-Panel

Access

None

Description

Show SEL-351P-3 diagnostic and battery information.

OTHER

Primary

Functions

Corresponding

Serial Port

Command Access Level

BTT BTT E

DATE DAT

TIME TIM

1

1

79 N/A N/A

Password for

Front-Panel

Access

Level E

None

None

None

TAR TAR

BRK_MON

DISPLAY BRE A

RESET BRE R

1

1

B

None

None

Level B

Description

Force 1 Amp load test on battery.

Show or set SEL-351P-3 date.

Show or set SEL-351P-3 time.

Show SEL-351P-3 set reclosures and current reclose count.

Show status of internal SEL-351P-3 elements on LCD display and second row of front-panel target LEDs.

Show recloser wear and trip operation counters.

Reset recloser wear and trip operation counters.

42 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

SET

Primary

Functions

SHOW

EZ

FZ

GROUP

GLOBAL

PORT

PASS

SET

EZ

FZ

GROUP

GLOBAL

PORT

PASS

Corresponding

Serial Port

Command

SHO EZ

SHO FZ

SHO

SHO G

SHO P

PASS

SET EZ

SET FZ

SET

SET G

SET P

PASS

Access Level

1

1

1

1

1

1

2

2

2

2

E

E

Password for

Front-Panel

Access

None

None

None

None

None

None

Level E

Level E

Level 2

Level 2

Level 2

Level 2

Description

Show EZ settings (group 1–6).

Show FZ settings (global EZ settings).

Show GROUP settings (group 1–6).

Show GLOBAL settings.

Show PORT settings.

Show passwords.

Set EZ settings (group 1–6).

Set FZ settings (global EZ settings).

Set GROUP settings (group 1–6).

Set GLOBAL settings.

Set PORT settings.

Set passwords.

CNTRL

Primary

Functions

EXTRA

CONTROL

POSITION

N/A

Corresponding

Serial Port

Command

OPERATE

OUTPUT

CONTACT

TEST

PUL

Access Level

N/A

2

Password for

Front-Panel

Access

None

Level 2

Description

View position of or operate extra userconfigured switch-type control.

Pulse output contact (OUT101–ALARM) for 1 second.

43 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

GROUP

Primary

Functions

Corresponding

Serial Port

Command

ACTIVE

GROUP

DISPLAY GRO

CHANGE GRO n

Access Level

1

B

Password for

Front-Panel

Access

None

Level B

Description

Show active setting group.

Change active setting group to setting group n .

Operator Controls

Except for the REMOTE ENABLED/REMOTO HABILITADO operator control pushbutton, all the following operator control pushbuttons should be pressed momentarily to execute their function.

Note: The functions described below are based on the factory default settings and operator control labels. The operator-control labels can be user-configured.

Press the PROTECTION ENABLED/PROTECCION

HABILITADA operator control pushbutton to enable/disable all overcurrent element tripping. Corresponding LED illuminates to indicate the enabled state.

Pressing the CLOSE operator control also enables protection

(indicated by the PROTECTION ENABLED/PROTECCION

HABILITADA LED illuminating) if it is not already enabled.

LED

PROTECTION

ENABLED

PROTECCION

HABILITADA

Operator Control

Pushbutton

44 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

Press the RECLOSE ENABLED/RECIERRE HABILITADO operator control pushbutton to enable/disable auto reclosing.

Corresponding LED illuminates to indicate the enabled state.

The RECLOSE ENABLED/RECIERRE HABILITADO operator control is overridden by the operation of the LIVE LINE

ENABLED/LINEA VIVA HABILITADA operator control in the following scenario:

Initial state: RECLOSE ENABLED/RECIERRE

HABILITADO “on” or “off” and LIVE LINE

ENABLED/LINEA VIVA HABILITADA

“off.”

Action: Press LIVE LINE ENABLED/LINEA VIVA

HABILITADA operator control pushbutton.

HABILITADO “off” and LIVE LINE

ENABLED/LINEA VIVA HABILITADA

“on.” The RECLOSE

ENABLED/RECIERRE HABILITADO operator control is now nonfunctional

(remains “off”).

RECLOSE ENABLED/RECIERRE HABILITADO cannot be turned “on” again, until LIVE LINE ENABLED/LINEA VIVA

HABILITADA is turned “off.” Once LIVE LINE

ENABLED/LINEA VIVA HABILITADA is “off,” the RECLOSE

ENABLED/RECIERRE HABILITADO operator control is then functional, but remains “off” until the RECLOSE

ENABLED/RECIERRE HABILITADO operator control pushbutton is pressed again.

The EARTH FAULT ENABLED/FALLA A TIERRA

HABILITADA and SEF ENABLED/SEF HABILITADO operator controls are interlocked as follows:

Initial state of both operators controls:

Press operator control: disabled

SEF enabled

EARTH FAULT/

FALLA A TIERRA

Final state of both operator controls: enabled disabled

EARTH FAULT ENABLED cannot be turned “off” again, until

SEF ENABLED is turned “off.” Once SEF ENABLED is “off,” the

EARTH FAULT ENABLED operator control is then functional, but remains “on” until the EARTH FAULT ENABLED operator control pushbutton is pressed again.

45

RECLOSE

ENABLED

RECIERRE

HABILITADO

EARTH FAULT

ENABLED

FALLA A TIERRA

HABILITADA

SEF

ENABLED

SEF

HABILITADO

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

Continually press the REMOTE ENABLED/REMOTO

HABILITADO operator control pushbutton for three (3) seconds to engage/disengage the remote control. While this pushbutton is pressed, the corresponding LED flashes on and off, indicating a pending engagement or disengagement of the remote control. The

LED illuminates constantly to indicate the engaged state (“on”).

REMOTE ENABLED/REMOTO HABILITADO “on” (local control is “off”):

All the other operator controls (except WAKE

UP/DESPERTAR) are inoperable. Remote control of these functions (via the serial port or optoisolated input) is enabled.

REMOTE ENABLED/REMOTO HABILITADO “off” (local control is “on”):

The other operator controls are operable. Remote control of these functions (via the serial port or optoisolated input) is disabled.

Press the LIVE LINE ENABLED/LINEA VIVA HABILITADA operator control pushbutton to enable/disable the live line function.

Corresponding LED illuminates to indicate the enabled state.

While the live line function is enabled, no closing or auto reclosing can take place via the control (e.g., the CLOSE/CIERRE operator control is inoperative). The LIVE LINE ENABLED/LINEA VIVA

HABILITADA operator overrides the RECLOSE

ENABLED/RECIERRE HABILITADO operator control (see previous RECLOSE ENABLED/RECIERRE HABILITADO operator control description).

While the live line function is enabled, the active settings group is

Settings Group 3. When the live line function is then disabled, the active setting group reverts back to the previous active setting group

(Settings Group 1 or Settings Group 2).

Press the ALTERNATE SETTINGS/AJUSTES ALTERNATIVOS operator control pushbutton to switch the active setting group between the main setting group (Settings Group 1) and the alternate setting group (Settings Group 2). Corresponding LED illuminates to indicate that the alternate setting group is active. This LED illuminates only when Settings Group 2 is the active setting group (it does not illuminate for Settings Group 1 or 3).

The LIVE LINE ENABLED/LINEA VIVA HABILITADO operator control switches the active setting group to Settings

Group 3 (see previous LIVE LINE ENABLED/LINEA VIVA

HABILITADA operator control description).

REMOTE

ENABLED

(press for 3 sec)

REMOTO

HABILITADO

(pulsar por 3 seg)

LIVE LINE

ENABLED

LINEA VIVA

HABILITADA

ALTERNATE

SETTINGS

AJUSTES

ALTERNATIVOS

46 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Press the WAKE UP/DESPERTAR operator control pushbutton to wake up the SEL-351P-3 if the front panel is dark (the unit put itself to sleep after an extended outage). After the unit wakes up, the front panel illuminates, and the unit can then be interrogated via the front panel or serial port.

The WAKE UP/DESPERTAR operator control is also used to turn on the SEL-351P-3 after the battery has been installed (see the installation steps in the Installation section).

The SEL-351P-3 wakes up automatically from an extended outage when power returns to the unit.

Front-Panel Interface

WAKE UP

DESPERTAR

47 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

Press the CLOSE/CIERRE operator control pushbutton to close the recloser. The corresponding RECLOSER

CLOSED/RESTAURADOR CERRADO LED illuminates to indicate the recloser is closed.

The CLOSE/CIERRE operator control pushbutton does not have to be continually pressed to allow for cold load pickup (i.e., disable fast curves, and desensitize delay curves and SEF element). There is automatic allowance for cold load pickup. See Cold Load Pickup

Scheme (No. 33) settings in the Settings section.

Option : Set a delay, so the operator can press the CLOSE/CIERRE operator control pushbutton and then move a safe distance away from the recloser before the SEL-351P-3 issues a close (the

CLOSE/CIERRE operator control comes with no set delay in the factory settings). With a set delay, press the CLOSE/CIERRE operator control pushbutton momentarily, and notice that the corresponding RECLOSER CLOSED/RESTAURADOR

CERRADO LED flashes on and off during the delay time, indicating a pending close. Abort the pending close by pressing the

CLOSE/CIERRE operator control pushbutton again or by pressing the TRIP/DISPARO operator control pushbutton. This delay setting for the CLOSE/CIERRE operator control is PB8D (range: 0 to 3600 cycles; factory-set at 0 cycles—no delay). The delay is set via the

SET G command (PB8D is not an EZ setting). See Section 1:

Factory-Set Logic in the SEL-351P-3 Instruction Manual for more information.

English

Spanish

Pressing the CLOSE/CIERRE operator control also enables protection (indicated by the PROTECTION

ENABLED/PROTECCION HABILITADA LED illuminating) if it is not already enabled.

Note: The time-delay setting for the PB8 operator control (global setting PB8D) should be left set to the factory default of

PB8D = 0 cycles (no time delay) if the control is programmed to operate independently of the close logic. If

PB8D > 0 cycles, the operation of corresponding Relay

Word bit PB8 will be supervised by SEL OGIC setting ULCL

(unlatch close). If ULCL is asserted (logical 1), this operator will be effectively disabled.

RECLOSER

CLOSED

CLOSE

RESTAURADOR

CERRADO

CIERRE

48 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Front-Panel Interface

Press the TRIP/DISPARO operator control pushbutton to trip the recloser (and take the control to the lockout state). The corresponding RECLOSER OPEN/RESTAURADOR ABIERTO

LED illuminates to indicate the recloser is open.

Option : Set a delay, so the operator can press the TRIP/DISPARO operator control pushbutton and then move a safe distance away from the recloser before the SEL-351P-3 issues a trip (the

TRIP/DISPARO operator control comes with no set delay in the factory settings). With a set delay, press the TRIP/DISPARO operator control pushbutton momentarily and notice the corresponding RECLOSER OPEN/RESTAURADOR ABIERTO

LED flashes on and off during the delay time, indicating a pending trip. Abort the pending trip by pressing the TRIP/DISPARO operator control pushbutton again or by pressing the

CLOSE/CIERRE operator control pushbutton. This delay setting for the TRIP/DISPARO operator control is PB9D (range: 0 to 3600 cycles; factory-set at 0 cycles—no delay). The delay is set via the

SET G command (PB9D is not an EZ Setting). See Section 1:

Factory-Set Logic in the SEL-351P-3 Instruction Manual for more information.

Note: The time-delay setting for the PB9 operator control (global setting PB9D) should be left set to the factory default of

PB9D = 0 cycles (no time delay) if the control is programmed to operate independently of the trip logic.

English

Spanish

RECLOSER

OPEN

TRIP

RESTAURADOR

ABIERTO

DISPARO

49 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

S

ETTINGS

Important:

This Quick-Start Installation and User's Guide provides only information applicable to the EZ settings—settings associated with traditional recloser control operations.

This section details the EZ (“easy”) settings—the settings used to perform traditional recloser control operations.

Topics covered in this section:

• Curve Designations

• EZ (“Easy”) Settings

• Global EZ Settings

• EZ Settings Sheets (end of Settings section)

Curve Information

Curve Modifiers Available for Any Curve Type:

• Constant Time Adder

• Vert. Multiplier/Time Dial

• Min. Response Time

High Current Options

Available for Phase and

Ground:

• High Current Trip

• High Current Lockout

Fast and delay curves are available for phase and ground overcurrent protection. These curves can be set with any of the numerous resident curve choices:

• Recloser Curves (see Table 7)

• US Curves (see Table 8)

• IEC Curves (see Table 8)

• User-Programmable Curves (see Table 8)

The recloser curves in Table 7 show both the older electronic control designation and the newer microprocessor-based control designation. The recloser curves can be specified in a curve setting using either designation.

For example, a given traditional recloser curve has the following two designations:

Older electronic control designation: A

Newer microprocessor-based control designation: 101

Traditional recloser curve A and curve 101 are the same curve —use either designation in making curve settings in the SEL-351P-3.

50 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

All 38 Traditional

Recloser Curves are Available!

Curves Conform to Standard:

The US and IEC curves conform to IEEE C37.112-1996

IEEE Standard Inverse-Time

Characteristic Equations for

Overcurrent Relays .

Settings

Table 7: Recloser Curve Designations

Recloser Curve Cross Reference—Old to New

Old

E

F

G

H

A

B

C

D

J

KP

L

M

N

New Old

101 P

117 R

133 T

116 V

132 W

163 Y

121 Z

122 1

164 2

162 3

107 4

118 5

104 6

New Old

135 15

140 16

106 17

114 18

136

New

115 7

105 8

152

113

161 8PLUS 111

137 9 131

138 KG

120 11

134 13

102 14

165

141

142

119

112

139

103

151

Table 8: US, IEC, and User-Programmable Curve Designations

US Curve Description

U2 inverse

IEC Curve

C1

C2

C3

Description class A (standard inverse) class B (very inverse) class C (extremely inverse)

User Designed Curves:

Created with SEL-5804 software.

• 3.5” high-density disk

• Requires Windows 3.1 or later

User-Programmable

Curves (factory-set)

DEF_01

DEF_05

DEF_1

DEF_5

Description definite-time curve (0.1 seconds) definite-time curve (0.5 seconds) definite-time curve (1.0 seconds) definite-time curve (5.0 seconds)

The four (4) user-programmable curves are factory-set as shown in

Table 8, with definite-time characteristics. User-designed curves (created with the SEL-5804 TOC [Time-Overcurrent] Recloser Curve Designer software package) can be downloaded instead to any of the four userprogrammable curves in the SEL-351P-3.

51 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

Factory EZ Settings

View EZ Settings With

Commands:

SHO EZ 1 (Group 1)

SHO EZ 2 (Group 2)

SHO FZ (Global)

See Table 3 in the

Communications section.

Set EZ Settings With

Commands:

SET EZ 1 (Group 1)

SET EZ 2 (Group 2)

SET FZ (Global)

See Table 3 in the

Communications section.

Settings Group 3

With factory settings, the LIVE

LINE ENABLED/LINEA VIVA

HABILITADA operator control activates Settings Group 3 when it is engaged—see explanation in the Operator

Controls subsection in the

Front-Panel Interface section.

Thus, certain future settings changes made to Settings

Groups 1 and/or 2 should perhaps be made to Settings

Group 3, too.

The SEL-351P-3 ships with the factory EZ settings shown in Table 9.

The corresponding number references provide a quick way to find the settings (or subsettings) in the Settings Descriptions subsection that follows.

The reference to Settings Groups 1 and 2 at the top of Table 9 refers to the two choices for the active setting group:

Settings Group 1 = main settings

Settings Group 2 = alternate settings

Refer to the Operator Controls subsection in the Front-Panel Interface section (ALTERNATE SETTINGS/AJUSTES ALTERNATIVOS operator control pushbutton) for more information on how to switch between these two setting groups. In the factory EZ settings, these two setting groups are set the same (Settings Group 3 set the same, too—see side bar note).

The Global EZ settings at the end of Table 9 apply to both settings

Groups 1 and 2 (and Settings Group 3—see side bar note).

Those factory settings indicated with an asterisk (*) in Table 9 are hidden with these particular factory settings. As a general rule, if a main setting is set to N, then the subsettings that follow are hidden. The following

Settings Descriptions subsection explains the details behind hiding the settings. Complete setting ranges are also given in the Settings

Descriptions subsection.

!

WARNING: Anytime an EZ setting is changed, review all the EZ settings before enabling the new settings. Pay close attention in circumstances where a setting was once set to OFF or N and then later turned on (enabled)—other related settings may need to be turned on, though may still be set to OFF or N.

52 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

53

Settings

Table 9: EZ Settings Quick Reference

No. Settings Groups 1 (Main) and 2 (Alternate) EZ

Settings:

Factory Settings:

1

2

3

4

5

6

7

8

9

Control Identifier

Circuit Identifier

CT Ratio

PT Ratio

Min. trip - phase (A pri.)

Min. trip - ground (A pri.)

Min. trip - SEF (A pri.)

Fast curve - phase

Time dial - phase fast curve

EM reset - phase fast curve

Fast curve - ground

Time dial - ground fast curve

EM reset - ground fast curve

10 Delay curve - phase

Time dial - phase delay curve

EM reset - phase delay curve

11

12 Time delay - SEF (cycles)

13 Operations - phase fast curve

14

15

16

17

Delay curve - ground

Time dial - ground delay curve

EM reset - ground delay curve

Operations - ground fast curve

Operations to lockout - phase

Operations to lockout - ground

Operations to lockout - SEF

18 Reclose interval 1 (cycles)

19 Reclose interval 2 (cycles)

N

C1

0.10

N

50.00

3

3

4

4

4

32.25

45.00

C5

0.05

N

C5

0.05

N

C1

0.10

SEL-351P-3 RECLOSER

CONTROL

FEEDER

400.0

100.0

200.00

20.00

10.00

20 Reclose interval 3 (cycles) 245.00

21 Reclose interval 4 (cycles)

22

23

24

25

26

27

28

Reset time for auto reclose (cycles)

Reset time from lockout (cycles)

Close power wait time (cycles)

Complex fast curve - phase (Y/N)

Const. time adder - phase fast curve (cycles)

Vert. multiplier - phase fast curve

Min. response - phase fast curve (cycles)

Complex fast curve - ground (Y/N)

Const. time adder - ground fast curve (cycles)

Vert. multiplier - ground fast curve

Min. response - ground fast curve (cycles)

Complex delay curve - phase (Y/N)

Const. time adder - phase delay curve (cycles)

Vert. multiplier - phase delay curve

Min. response - phase delay curve (cycles)

Complex delay curve - ground (Y/N)

Const. time adder - ground delay curve (cycles)

Vert. multiplier - ground delay curve

Min. response - ground delay curve (cycles)

N

0.00*

1.00*

0.00*

N

0.00*

1.00*

0.00*

0.00*

50.00

50.00

0.00

N

0.00*

1.00*

0.00*

N

0.00*

1.00*

0.00*

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Settings Groups 1 (Main) and 2 (Alternate) EZ

Settings:

Factory Settings:

29 High current trip - phase (Y/N)

High current trip - phase (multiple)

Time delay - phase high current trip (cycles)

Activate high current trip - phase

30 High current trip - ground (Y/N)

High current trip - ground (multiple)

Time delay - ground high current trip (cycles)

Activate high current trip - ground

31 High current lockout - phase (Y/N)

High current lockout - phase (multiple)

Activate high current lockout - phase

32 High current lockout - ground (Y/N)

High current lockout - ground (multiple)

Activate high current lockout - ground

33 Cold load pickup scheme (Y/N)

Cold load pickup - phase (multiple)

Cold load pickup - ground (multiple)

Loss of load diversity time (cycles)

Restore min. trips - time limit (cycles)

Restore min. trip - phase (Y/N)

Restore min. trip - ground (Y/N)

Restore min. trip - SEF (Y/N)

34 Sequence coordination (Y/N)

35 Ground trip precedence (Y/N)

36 Underfrequency load shedding (Y/N)

Underfrequency pickup (Hz)

Underfrequency time delay (cycles)

37 Demand meter time constant (min.)

Global EZ Settings:

38

39

40

System Frequency (Hz)

Phase Rotation

Recloser Wear Monitor (AUTO,Y,N)

Interrupt rating (A pri.)

41 Reset trip-latched LEDs on close (Y,Y1,N,N1)

42 True three-phase voltage connected (Y,N)

43 Phantom voltages from (VA,VB,VC,VAB,VBC,VCA,OFF) OFF

44 V123 Terminal Conn. (A,B,C,AB,BC,CA,OFF)

45

46

47

48

49

50

51

I123 Terminal Conn. (ABC,ACB,BAC,BCA,CAB,CBA)

CT Polarity (POS,NEG)

Battery Amp-hours (6.5 – 20.0)

Power-off Delay After AC Loss (OFF, 1 – 1440 min)

Power-off Delay After Wake Up (OFF, 1 – 1440 min)

Power-off Voltage Level 1 (19.2 – 24 Vdc)

SF6 low pressure warning threshold in atmospheres (0.9 -

A

ABC

POS

8.0

180

20

20.5

1.1

2)

*See comments preceding Table 9.

50

ABC

AUTO

12500

Y

N

OFF*

0.00*

OFF*

N*

N*

N*

N

N*

N

OFF*

6.00*

5

N

OFF*

OFF*

N

OFF*

OFF*

N

OFF*

N

OFF*

0.00*

OFF*

N

OFF*

0.00*

OFF*

54 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

Settings Descriptions

!

WARNING: Anytime an EZ setting is changed, review all the EZ settings before enabling the new settings. Pay close attention in circumstances where a setting was once set to OFF or N and then later turned on (enabled)—other related settings may need to be turned on, though may still be set to OFF or N.

Settings Groups 1 (Main) and 2 (Alternate) EZ Settings

No. Setting Default

SEL-351P-3

RECLOSER

CONTROL

Range

0–9, A–Z, - , / , . , space

Incr.

The Control Identifier setting contains the control installation designation (e.g., SEL-351P-3 RECLOSER

CONTROL). This identifier is listed at the top of event, history, meter, and status reports (see Table 3).

• This setting may be up to 30 characters long.

• This setting cannot be made via the front-panel interface.

No. Setting

2 Circuit Identifier

Default

FEEDER

Range

0–9, A–Z, - , / , . , space

Incr.

The Circuit Identifier setting contains the greater circuit or substation designation (e.g., FEEDER). This identifier is listed at the top of event, history, meter, and status reports (see Table 3).

• This setting may be up to 30 characters long.

• This setting cannot be made via the front-panel interface.

No. Setting Default

400.0 1.0–6000.0

Range Incr.

0.1

The CT Ratio (current transformer [CT] ratio) setting programs the SEL-351P-3 to operate with a recloser CT ratio (e.g., for the recloser CT ratio 400:1, the setting CT Ratio = 400.0 is made). See recloser

CTs (connected to the primary system) on the left-hand side of Figure 10 and Figure 11.

• See discussion following Figure 11 for more CT Ratio setting considerations for SEL-351P-3 models with low-level (0.01 phase/0.005 neutral) current inputs.

• WARNING: The following settings change in accordance to the CT Ratio setting:

Min. trip - phase (No. 5)

Min. trip - ground (No. 6)

Min. trip - SEF (No. 7)

55 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting Default Range

100.0 1.0–10000.0

Incr.

0.1

The PT Ratio (potential transformer [PT] ratio) setting programs the SEL-351P-3 to operate with the effective ratio of the external voltage step-down device connected to the voltage inputs of Figure 9 (e.g., for the PT ratio of 7200:120, the setting PT Ratio = 60.0 is made).

• For applications where single-phase Vac power is the only voltage brought to the SEL-351P-3 (and also connected to a voltage input of Figure 9(a) for metering/monitoring), the PT ratio should still be entered, otherwise the SEL-351P-3 voltage metering/monitoring information will not be accurate.

Enter the effective power transformer ratio, relative to the Vac secondary winding.

• See discussion following Figure 9 for more PT Ratio setting considerations for SEL-351P-3 models with low-level (3 Vac) voltage inputs as shown in Figure 9(b) and Figure 9(c).

No. Setting

5 Min. trip - phase

Default

200.00

Range

OFF, 40.00–1279.99 Amps primary

Incr.

0.01

The Min. trip - phase in primary amps.

setting determines the minimum phase current threshold for overcurrent detection

The displayed Amps primary setting range for Min. trip - phase is calculated by multiplying the effective

Amps secondary range [0.10 to 3.20] by the CT Ratio (No. 3) [400.0]:

(0.10 to 3.20) • 400.0 = 40.00 to 1280.00 range (Amps primary)

If the CT Ratio setting changes, the displayed Amps primary setting range for Min. trip - phase changes accordingly. Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 1279.99 instead of 1280.00).

• WARNING: If Min. trip - phase (No. 5) , Min. trip - ground (No. 6), and Min. trip - SEF (No. 7) are all set to OFF, then overcurrent protection and reclosing are disabled.

• WARNING: If Min. trip - phase is set to OFF, then the following settings are all hidden and set to

OFF or N:

Fast curve - phase (No. 8)

Delay curve - phase (No. 10)

Complex fast curve - phase (No. 25)

Complex delay curve - phase (No. 27)

Operations - phase fast curve (No. 13)

Operations to lockout - phase (No. 15)

High current trip - phase (No. 29)

High current lockout - phase (No. 31)

56 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

6 Min. trip - ground

Default

20.00

Range

OFF, 2.00–1279.99 Amps primary

Incr.

0.01

The Min. trip - ground setting determines the minimum ground current threshold for overcurrent detection in primary amps.

The displayed Amps primary setting range for Min. trip - ground is calculated by multiplying the effective

Amps secondary range [0.005 to 3.20] by the CT Ratio (No. 3) [400.0]:

(0.005 to 3.20) • 400.0 = 2.00 to 1280.00 range (Amps primary)

If the CT Ratio setting changes, the displayed Amps primary setting range for Min. trip - ground changes accordingly. Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 1279.99 instead of 1280.00).

If Min. trip - ground is effectively set <0.1 Amp secondary (e.g., for CT ratio [No. 3] = 400.0, Min. trip - ground <40.00 Amps primary), then the corresponding curves flatten out above 1.5 Amps secondary (e.g., for CT ratio [No. 3] = 400.0, Fast curve - ground [No. 9] and Delay curve - ground [No. 11] flatten out above 600 Amps primary).

• WARNING: If Min. trip - phase (No. 5) , Min. trip - ground (No. 6), and Min. trip - SEF (No. 7) are all set to OFF, then overcurrent protection and reclosing are disabled.

• WARNING: If Min. trip - ground is set to OFF, then the following settings are all hidden and set to

OFF or N:

Fast curve - ground (No. 9)

Delay curve - ground (No. 11)

Operations - ground fast curve (No. 14)

Operations to lockout - ground (No. 16)

Complex fast curve - ground (No. 26)

Complex delay curve - ground (No. 28)

High current trip - ground (No. 30)

High current lockout - ground (No. 32)

No. Setting

7 Min. trip - SEF

Default

10.00

Range

OFF, 2.00–599.99 Amps primary

Incr.

0.01

The Min. trip - SEF setting determines the minimum sensitive earth fault threshold for overcurrent detection set in primary Amps.

The displayed Amps primary setting range for Min. trip - SEF is calculated by multiplying the effective

Amps secondary range [0.005 to 1.500] by the CT Ratio (No. 3) [400.0]:

(0.005 to 1.500) • 400.0 = 2.00 to 600.00 range (Amps primary)

If the CT Ratio setting changes, the displayed Amps primary setting range for Min. trip - ground changes accordingly. Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 599.99 instead of 600.00).

• WARNING: If Min. trip - phase (No. 5) , Min. trip - ground (No. 6), and Min. trip - SEF (No. 7) are all set to OFF, then overcurrent protection and reclosing are disabled.

• WARNING: If Min. trip - SEF is set to OFF, then the following settings are all hidden and set to zero (0) and OFF, respectively:

Time delay - SEF (No. 12)

Operations to lockout - SEF (No. 17)

57 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

8 Fast curve - phase

Default

C5

Range

OFF, U1–U5, C1–C5, recloser or user curve

The Fast curve - phase setting selects the time-overcurrent curve for phase fast curve tripping. Curve designations are provided in Table 7 and Table 8.

Incr.

• This setting is hidden and set to OFF if Min. trip - phase (No. 5) is set to OFF.

• If Fast curve - phase is programmed with a US (U1–U5) or IEC (C1–C5) curve, enter the following two settings:

Setting

Time-dial - phase fast curve

Default Range

0.05 0.50–15.00 for US curves U1–U5

0.05–1.00 for IEC curves C1–C5

The Time-dial - phase fast curve multiplier.

setting shifts the US or IEC curve in time by the entered

Incr.

0.01

0.01

• This setting is hidden and nonoperative if Fast curve - phase is programmed with a recloser or user curve.

Setting

EM reset - phase fast curve

Default

N Y/N

Range Incr.

The EM reset - phase fast curve or IEC curve, if set to Y.

setting enables the electromechanical reset emulation for the US

• This setting is usually set to N, except for special applications.

• This setting is hidden and set to N if Fast curve - phase is programmed with a recloser or user curve.

No.

9

Setting

Fast curve - ground

Default

C5

Range

OFF, U1–U5, C1–C5, recloser or user curve

Incr.

The Fast curve - ground setting selects the time-overcurrent curve for ground fast curve tripping. Curve designations are provided in Table 7 and Table 8.

If Min. trip - ground (No. 6) is effectively set <0.1 Amp secondary (e.g., for CT ratio [No. 3] = 400.0,

Min. trip - ground (No. 6) <40.00 Amps primary), then Fast curve - ground flattens out above 1.5 Amps secondary (e.g., for CT ratio [No. 3] = 400.0, Fast curve - ground flattens out above 600 Amps primary).

• This setting is hidden and set to OFF if Min. trip -ground (No. 6) is set to OFF.

• If Fast curve - ground is programmed with a US (U1–U5) or IEC (C1–C5) curve, enter the following two settings:

58 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

Setting

Time-dial - ground fast curve

Default

0.05

Range

0.50–15.00 for US curves U1–U5

0.05–1.00 for IEC curves C1–C5

The Time-dial - ground fast curve multiplier.

setting shifts the US or IEC curve in time by the entered

Incr.

0.01

0.01

• This setting is hidden and nonoperative if Fast curve - ground is programmed with a recloser or user curve.

Setting

EM reset - ground fast curve

Default

N Y/N

Range Incr.

The EM reset - ground fast curve

US or IEC curve, if set to Y.

setting enables the electromechanical reset emulation for the

• This setting is usually set to N, except for special applications.

• This setting is hidden and set to N if Fast curve - ground is programmed with a recloser or user curve.

No.

10

Setting

Delay curve - phase

Default

C1

Range

OFF, U1–U5, C1–C5, recloser or user curve

Incr.

The Delay curve - phase setting selects the time-overcurrent curve for phase delay curve tripping. Curve designations are provided in Table 7 and Table 8.

• This setting is hidden and set to OFF if Min. trip -phase (No. 5) is set to OFF.

• If Delay curve - phase is programmed with a US (U1–U5) or IEC (C1–C5) curve, enter the following two settings:

Setting

Time-dial - phase delay curve

Default

0.10

Range

0.50–15.00 for US curves U1–U5

0.05–1.00 for IEC curves C1–C5

The Time-dial - phase delay curve multiplier.

setting shifts the US or IEC curve in time by the entered

Incr.

0.01

0.01

• This setting is hidden and nonoperative if Delay curve - phase is programmed with a recloser or user curve.

Setting

EM reset - phase delay curve

Default

N Y/N

Range Incr.

The EM reset - phase delay curve

US or IEC curve, if set to Y.

setting enables the electromechanical reset emulation for the

• This setting is usually set to N, except for special applications.

• This setting is hidden and set to N if Delay curve - phase is programmed with a recloser or user curve.

59 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No.

11

Setting

Delay curve - ground

Default

C1

Range

OFF, U1–U5, C1–C5, recloser or user curve

Incr.

The Delay curve - ground setting selects the time-overcurrent curve for ground fast curve tripping. Curve designations are provided in Table 7 and Table 8.

If Min. trip - ground (No. 6) is effectively set <0.1 Amp secondary (e.g., for CT ratio [No. 3] = 400.0,

Min. trip - ground [No. 6] <40.00 Amps primary), then Delay curve - ground flattens out above 1.5

Amps secondary (e.g., for primary).

CT ratio [No. 3] = 400.0, Delay curve - ground flattens out above 600 Amps

• This setting is hidden and set to OFF if Min. trip - ground (No. 6) is set to OFF.

• If Delay curve - ground is programmed with a US (U1–U5) or IEC (C1–C5) curve, enter the following two settings:

Setting

Time-dial - ground delay curve

Default

0.10

Range

0.50–15.00 for US curves U1–U5

0.05–1.00 for IEC curves C1–C5

The Time-dial - ground delay curve multiplier.

setting shifts the US or IEC curve in time by the entered

Incr.

0.01

0.01

• This setting is hidden and nonoperative if Delay curve - ground is programmed with a recloser or user curve.

Setting

EM reset - ground delay curve

Default

N Y/N

Range Incr.

The EM reset - ground delay curve

US or IEC curve, if set to Y.

setting enables the electromechanical reset emulation for the

• This setting is usually set to N, except for special applications.

• This setting is hidden and set to N if Delay curve - ground is programmed with a recloser or user curve.

No. Setting

12 Time delay - SEF

Default

50.00

Range

0–16000.00 cycles

Incr.

0.25 cyc.

The Time delay - SEF setting programs an intentional time delay for the definite-time SEF (sensitive earth fault) overcurrent element. This is in addition to the built-in 2-cycle time delay.

• This setting is hidden and set to zero (0) if Min. trip - SEF (No. 7) is set to OFF.

60 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

13 Operations - phase fast curve

Default Range Incr.

1

The Operations - phase fast curve setting determines the number of phase fast curve trip operations (e.g., if Operations - phase fast curve = 2, then the phase fast curve is enabled for the first two [2] trip operations).

• This setting is hidden and set to OFF if Fast curve - phase (No. 8) is set to OFF.

• This setting only enables the phase fast curve operations; it does not disable the phase delay curve (the phase delay curve is always active). Traditional protection schemes use fast curves followed by delay curves so the delay curves do not have to be defeated. If a slower first operation than second operation is desired, higher logic level settings changes are required .

No. Setting

14 Operations - ground fast curve

Default Range Incr.

1

The Operations - ground fast curve setting determines the number of ground fast curve trip operations

(e.g., if Operations - ground fast curve = 2, then the ground fast curve is enabled for the first two [2] trip operations).

• This setting is hidden and set to OFF if Fast curve - ground (No. 9) is set to OFF.

• This setting only enables the ground fast curve operations; it does not disable the ground delay curve

(the ground delay curve is always active, provided that the EARTH FAULT ENABLED/FALLA A

TIERRA HABILITADA operator control is on). Traditional protection schemes use fast curves followed by delay curves so the delay curves do not have to be defeated. If a slower first operation than second operation is desired, higher logic level settings changes are required.

No. Setting

15 Operations to lockout - phase

Default Range Incr.

1

The Operations to lockout - phase setting determines the total number of phase curve trip operations. The difference between setting Operations to lockout - phase and setting Operations - phase fast curve

(No. 13) is the number of remaining phase delay curve operations (e.g., 4 – 2 = 2).

The setting range for Operations to lockout - phase adjusts according to Operations - phase fast curve

(e.g., if Operations - phase fast curve = 2, then the range for Operations to lockout - phase is from 2 to 5).

• If Delay curve - phase (No. 10) = OFF, then Operations to lockout - phase is set automatically equal to Operations - phase fast curve , and there are no phase delay curve operations (e.g., 2 – 2 = 0).

• This setting is hidden and set to OFF if Min. trip - phase (No. 5) is set to OFF.

• WARNING: If Operations to lockout - phase (No. 15), Operations to lockout - ground (No. 16), and

Operations to lockout - SEF (No. 17) are all set to OFF, then overcurrent protection and reclosing are disabled.

However, if both Min. trip - phase (No. 5) and Delay curve - phase (No. 10) are set to values other than OFF, the phase delay curve element is still active. If absolutely no phase protection is desired (e.g.,

“switch” mode), Min. trip - phase (No. 5) or Delay curve - phase (No. 10) must also be set to OFF.

61 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

16 Operations to lockout - ground

Default Range Incr.

1

The Operations to lockout - ground setting determines the total number of ground curve trip operations.

The difference between setting Operations to lockout - ground and setting Operations - ground fast curve

(No. 14) is the number of remaining ground delay curve operations (e.g., 4 – 2 = 2).

The setting range for Operations to lockout - ground adjusts according to Operations - ground fast curve

(e.g., if Operations - ground fast curve = 2, then the range for Operations to lockout - ground is from 2 to 5).

• If Delay curve - ground (No. 11) = OFF, then Operations to lockout - ground is set automatically equal to Operations - ground fast curve , and there are no ground delay curve operations (e.g., 2 – 2 =

0).

• This setting is hidden and set to OFF if Min. trip - ground (No. 6) is set to OFF.

• WARNING: If Operations to lockout - phase (No. 15), Operations to lockout - ground (No. 16), and

Operations to lockout - SEF (No. 17) are all set to OFF, then overcurrent protection and reclosing are disabled.

However, if both Min. trip - ground (No. 6) and Delay curve - ground (No. 11) are set to values other than OFF, the ground delay curve element is still active (provided the EARTH FAULT

ENABLED/FALLA A TIERRA HABILITADA operator control is on). If absolutely no ground protection is desired (e.g., “switch” mode), Min. trip - ground (No. 6) or Delay curve - ground (No.

11) must also be set to OFF.

No.

17

Setting

Operations to lockout - SEF

Default

OFF OFF, 1–5

Range Incr.

1

The Operations to lockout - SEF operations.

setting determines the number of SEF (sensitive earth fault) element trip

• This setting is hidden and set to OFF if Min. trip - SEF (No. 7) is set to OFF.

• WARNING: If Operations to lockout - phase (No. 15), Operations to lockout - ground (No. 16), and

Operations to lockout - SEF (No. 17) are all set to OFF, then overcurrent protection and reclosing are disabled. See similar warnings for preceding setting number 15 and setting number 16.

62 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

Table 10: Seconds-to-Cycles Conversion (60 Hz)

Seconds

(50 Hz)

Cycles

(60 Hz)

Seconds

(50 Hz)

Cycles

(60 Hz)

0.3 15 18

0.5 25 30

15 750 900

1 50 60 30 1500

2 100 2700

3 150 3600

5 250 5400

10 500 600 180 9000 for 50 Hz systems: _____ seconds • 50 cycles/second = _____ cycles

_____ minutes • 3000 cycles/minute = _____ cycles for 60 Hz systems: _____ seconds • 60 cycles/second = _____ cycles

_____ minutes • 3600 cycles/minute = _____ cycles

63 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

18 Reclose interval 1

19 Reclose interval 2

20 Reclose interval 3

21 Reclose interval 4

Default

32.50

45.00

245.00

0.00

Range (see Note below)

0–999999.00 cycles

0–999999.00 cycles

0–999999.00 cycles

0–999999.00 cycles

Incr.

0.25 cyc.

0.25 cyc.

0.25 cyc.

0.25 cyc.

The Reclose interval settings (1 through 4) are each successively and individually timed. Reclose interval timing cannot proceed until the following two conditions are met:

• The trip condition has gone away.

• The recloser has opened.

At the end of a reclose interval, an auto reclose attempt is made.

The number of available

15, 16, or 17) setting.

Reclose interval settings corresponds to the highest set Operations to lockout (No.

For example, if the highest set Operations to lockout setting is Operations to lockout - phase (No. 15) = 4, then settings Reclose interval 1 , Reclose interval 2 , and Reclose interval 3 are available (three reclose attempts). Because it is not available, Reclose interval 4 is hidden and set to zero (0).

The number of reclosing attempts (i.e., available Reclose interval settings) is always one less than the number of trip operations (e.g., 4 “trips” – 1 = 3 “reclosures”).

• All the Reclose interval settings are hidden and set to zero (0) if none of the Operations to lockout

(No. 15, 16, or 17) settings are set greater than 1 (reclosing is disabled; 1 “trip” – 1 = 0 “reclosures”).

• If a Reclose interval setting is set to zero (0), the corresponding auto reclose attempt and any following auto reclose attempts are aborted.

• Note: Reclose intervals should not be set less than 30 cycles, otherwise the control will go to lockout prematurely.

No. Setting

22 Reset time for auto reclose

23 Reset time from lockout

Default

50.00

50.00

Range

0–999999.00 cycles

0–999999.00 cycles

Incr.

0.25 cyc.

0.25 cyc.

The Reset time for auto reclose setting qualifies an auto reclose of the recloser. The Reset time from lockout setting qualifies a manual/remote close of the recloser from the lockout state. Traditionally, the

Reset time from lockout setting is set shorter than the Reset time for auto reclose setting.

Reset timing is blocked (and the reset timer is reloaded) if any overcurrent elements are picked up. Reset timing can only proceed if all the overcurrent elements are continually dropped out.

• Both the Reset time for auto reclose and Reset time from lockout settings are hidden and set to zero

(0) if none of the Operations to lockout (No. 15, 16, or 17) settings are set greater than 1 (reclosing is disabled; 1 “trip” – 1 = 0 “reclosures”).

64 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

24 Close power wait time

Default

0.00

Range

0–16000.00 cycles

Incr.

0.25 cyc.

The Close power wait time setting is a time window that starts timing after a reclose interval times out.

During this time window, the SEL-351P-3 checks the trip and close capacitors connected to it:

• If the trip and close capacitors are charged, this indicates that the close power for the recloser is present, and reclosing proceeds.

• If the trip and close capacitors are not charged, this indicates that the close power for the recloser is not present and reclosing is stalled. If the trip and close capacitors are not charged throughout the time window, reclosing is aborted at the end of the time window, and the SEL-351P-3 goes to the lockout state.

The 24 Vdc battery also has to be connected and healthy in order for reclosing to proceed.

• If Close power wait time is set to 0 cycles, then the SEL-351P-3 makes only one check for charged trip and close capacitors, after a reclose interval times out.

• This setting is hidden and set to 0 cycles if none of the Operations to lockout (No. 15, 16, or 17) settings are set greater than 1 (reclosing is disabled; 1 “trip” – 1 = 0 “reclosures”).

No.

25

Setting

Complex fast curve - phase

Default

N Y/N

Range Incr.

The

Y.

Complex fast curve - phase setting enables the following three settings for the phase fast curve, if set to

• This setting is hidden and set to N if Fast curve - phase (No. 8) is set to OFF.

Const. time adder - phase fast curve

Setting Default

0.00 0–60.00 cycles

Range Incr.

0.25 cyc.

The Const. time adder - phase fast curve set to other than 0 cycles.

setting adds a constant time to the phase fast curve, if

• This setting is hidden and set to zero (0) if Complex fast curve - phase is set to N.

Vert. multiplier - phase fast curve

Setting Default Range

1.00 0.10–2.00

Incr.

0.01

The Vert. multiplier - phase fast curve setting shifts the phase fast curve in time, by the entered multiplier, if Fast curve - phase (No. 8) is programmed with a recloser or user curve. If no particular multiplier is desired, set Vert. multiplier - phase fast curve equal to 1.00.

• If Fast curve - phase (No. 8) is programmed with a US (U1–U5) or IEC (C1–C5) curve, Vert. multiplier - phase fast curve is hidden and nonoperative. The preceding Time-dial - phase fast curve (No. 8) subsetting provides the US and IEC curves with an effective vertical multiplier, instead.

• This setting has no multiplying effect on the Constant time adder - phase fast curve and Min. response time - phase fast curve settings. They all operate independently.

• This setting is hidden and set to 1.00 if Complex fast curve - phase is set to N and Fast curve-phase (No. 8) is programmed with a recloser or user curve.

65 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

Setting

Min. response - phase fast curve

Default

0.00 0–60.00 cycles

Range Incr.

0.25 cyc.

The phase fast curve can trip no faster than the Min. response time - phase fast curve setting.

If the Min. response time - phase fast curve setting is set equal to zero (0), it has no effect on the phase fast curve. If the Min. response time - phase fast curve setting is set equal to 15 cycles, for example, the phase fast curve cannot trip on the portion of the curve that is faster than 15 cycles—the phase fast curve effectively flattens out at 15 cycles.

• This setting is hidden and set to zero (0) if Complex fast curve - phase is set to N.

No.

26

Setting

Complex fast curve - ground

Default

N Y/N

Range Incr.

The Complex fast curve - ground to Y.

setting enables the following three settings for the ground fast curve, if set

• This setting is hidden and set to N if Fast curve - ground (No. 9) is set to OFF.

Const. time adder - ground fast curve

Setting Default

0.00 0–60.00 cycles

Range Incr.

0.25 cyc.

The Const. time adder - ground fast curve if set to other than 0 cycles.

setting adds a constant time to the ground fast curve,

• This setting is hidden and set to zero (0) if Complex fast curve - ground is set to N.

Vert. multiplier - ground fast curve

Setting Default Range

1.00 0.10–2.00

Incr.

0.01

The Vert. multiplier - ground fast curve setting shifts the ground fast curve in time, by the entered multiplier, if Fast curve - ground (No. 9) is programmed with a recloser or user curve. If no particular multiplier is desired, set Vert. multiplier - ground fast curve equal to 1.00.

• If Fast curve - ground (No. 9) is programmed with a US (U1–U5) or IEC (C1–C5) curve, Vert. multiplier - ground fast curve is hidden and nonoperative. The preceding Time-dial - ground fast curve (No. 9) subsetting provides the US and IEC curves with an effective vertical multiplier, instead.

• This setting has no multiplying effect on the Constant time adder - ground fast curve and

Min. response time - ground fast curve settings. They all operate independently.

• This setting is hidden and set to 1.00 if Complex fast curve - ground is set to N and Fast curve-ground (No. 9) is programmed with a recloser or user curve.

Setting

Min. response - ground fast curve

Default

0.00 0–60.00 cycles

Range Incr.

0.25 cyc.

The phase fast curve can trip no faster than the Min. response time - ground fast curve setting.

If the Min. response time - ground fast curve setting is set equal to zero (0), it has no effect on the ground fast curve. If the Min. response time - ground fast curve setting is set equal to 15 cycles, for example, the ground fast curve cannot trip on the portion of the curve that is faster than 15 cycles— the ground fast curve effectively flattens out at 15 cycles.

• This setting is hidden and set to zero (0) if Complex fast curve - ground is set to N.

66 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

27 Complex delay curve - phase

Default

N Y/N

Range Incr.

The Complex delay curve - phase set to Y.

setting enables the following three settings for the phase delay curve, if

• This setting is hidden and set to N if Delay curve - phase (No. 10) is set to OFF.

Setting

Const. time adder - phase delay curve

Default

0.00 0–60.00 cycles

Range Incr.

0.25 cyc.

The Const. time adder - phase delay curve if set other than 0 cycles.

setting adds a constant time to the phase delay curve,

• This setting is hidden and set to zero (0) if Complex delay curve - phase is set to N.

Setting

Vert. multiplier - phase delay curve

Default Range

1.00 0.10–2.00

Incr.

0.01

The Vert. multiplier - phase delay curve setting shifts the phase delay curve in time, by the entered multiplier, if Delay curve - phase (No. 10) is programmed with a recloser or user curve. If no particular multiplier is desired, set Vert. multiplier - phase delay curve equal to 1.00.

• If Delay curve - phase (No. 10) is programmed with a US (U1–U5) or IEC (C1–C5) curve,

Vert. multiplier - phase delay curve is hidden and nonoperative. The preceding Time-dial - phase delay curve (No. 10) subsetting provides the US and IEC curves with an effective vertical multiplier, instead.

• This setting has no multiplying effect on the Constant time adder - phase delay curve and

Min. response time - phase delay curve settings. They all operate independently.

• This setting is hidden and set to 1.00 if Complex delay curve - phase is set to N and Delay curve-phase (No. 10) is programmed with a recloser or user curve.

Setting

Min. response - phase delay curve

Default

0.00 0–60.00 cycles

Range Incr.

0.25 cyc.

The phase delay curve can trip no faster than the Min. response time - phase delay curve setting.

If the Min. response time - phase delay curve setting is set equal to zero (0), it has no effect on the phase delay curve. If the Min. response time - phase delay curve setting is set equal to 15 cycles, for example, the phase delay curve cannot trip on the portion of the curve that is faster than 15 cycles—the phase delay curve effectively flattens out at 15 cycles.

• This setting is hidden and set to zero (0) if Complex delay curve - phase is set to N.

67 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

28 Complex delay curve - ground

Default

N Y/N

Range Incr.

The Complex delay curve - ground if set to Y.

setting enables the following three settings for the ground delay curve,

• This setting is hidden and set to N if Delay curve - ground (No. 11) is set to OFF.

Setting

Const. time adder - ground delay curve

Default

0.00 0–60.00 cycles

Range Incr.

0.25 cyc.

The Const. time adder - ground delay curve curve, if set other than 0 cycles.

setting adds a constant time to the ground delay

• This setting is hidden and set to zero (0) if Complex delay curve - ground is set to N.

Setting

Vert. multiplier - ground delay curve

Default Range

1.00 0.10–2.00

Incr.

0.01

The Vert. multiplier - ground delay curve setting shifts the phase delay curve in time, by the entered multiplier, if Delay curve - ground (No. 11) is programmed with a recloser or user curve. If no particular multiplier is desired, set Vert. multiplier - ground delay curve equal to 1.00.

• If Delay curve - ground (No. 11) is programmed with a US (U1–U5) or IEC (C1–C5) curve,

Vert. multiplier - ground delay curve is hidden and nonoperative. The preceding Time-dial - ground delay curve (No. 11)—setting provides the US and IEC curves with an effective vertical multiplier, instead.

• This setting has no multiplying effect on the Constant time adder - ground delay curve and

Min. response time - ground delay curve settings. They all operate independently.

• This setting is hidden and set to 1.00 if Complex delay curve - ground is set to N and Delay curve - ground (No. 11) is programmed with a recloser or user curve.

Setting

Min. response - ground delay curve

Default

0.00 0–60.00 cycles

Range Incr.

0.25 cyc.

The ground delay curve can trip no faster than the Min. response time - ground delay curve setting.

If the Min. response time - ground delay curve setting is set equal to zero (0), it has no effect on the ground delay curve. If the Min. response time - ground delay curve setting is set equal to

15 cycles, for example, the ground delay curve cannot trip on the portion of the curve that is faster than 15 cycles—the ground delay curve effectively flattens out at 15 cycles.

• This setting is hidden and set to zero (0) if Complex delay curve - ground is set to N.

68 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No.

29

Setting

High current trip - phase

Default

N Y/N

Range Incr.

The High current trip - phase setting enables the following three settings for phase high current tripping, if set to Y. Phase high current tripping is not affected by the cold load pickup scheme.

• This setting is hidden and set to N if Fast curve - phase (No. 8) and Delay curve - phase (No. 10) are both set to OFF.

Setting

High current trip - phase

Default

OFF OFF, 1.00–39.99 multiples of Min. trip - phase

Range Incr.

0.01

The High current trip - phase (multiples of Min. trip - phase ) setting determines the phase current threshold for phase high current tripping.

High current trip - phase = 12.00 (multiples of Min. trip - phase ) and Min. trip - phase (No. 5) = 200.00 Amps primary, then the phase current threshold for phase high current tripping operates at a value equal to:

12.00 • 200.00 Amps primary = 2400.00 Amps primary

The upper limit of this setting (40.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - phase (No. 5) [200.00]:

(20 • 400.0)/200.00 = 40.00 multiples (upper limit)

Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 39.99 instead of 40.00).

• This setting is hidden and set to OFF if High current trip - phase is set to N.

Setting

Time delay - phase high current trip

Default

0.00

Range

0–16000.00 cycles

Incr.

0.25 cyc.

The Time delay - phase high current trip setting programs an intentional time delay for the phase high current tripping. If set to zero (0), phase high current tripping operates instantaneously.

• This setting is hidden and set to zero (0) if High current trip - phase is set to N.

Setting

Activate high current trip - phase

Default Range Incr.

1

The Activate high current trip - phase enabled (e.g., if

setting determines when phase high current tripping is

Activate high current trip - phase = 2, then phase high current tripping is enabled for the second [2nd] trip operation and every following trip operation).

The setting range for Activate high current trip - phase adjusts according to Operations to lockout

- phase (e.g., if Operations to lockout - phase = 4, then the range for Activate high current trip - phase is from 1 to 4).

• This setting is hidden and set to OFF if High current trip - phase is set to N.

69 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No.

30

Setting

High current trip - ground

Default

N Y/N

Range

The High current trip - ground setting enables the following three settings for ground high current tripping, if set to Y. Ground high current tripping is not affected by the cold load pickup scheme.

Incr.

• This setting is hidden and set to N if Fast curve - ground (No. 9) and Delay curve - ground (No. 11) are both set to OFF.

Setting

High current trip - ground

Default

OFF OFF, 1.00–399.99 multiples of Min. trip - ground

Range Incr.

0.01

The High current trip - ground (multiples of Min. trip - ground current threshold for ground high current tripping.

) setting determines the ground

High current trip - ground = 44.00 (multiples of Min. trip - ground ) and

Min. trip - ground (No. 6) = 20.00 Amps primary, then the ground current threshold for ground high current tripping operates at a value equal to:

44.00 • 20.00 Amps primary = 880.00 Amps primary

The upper limit of this setting (400.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - ground (No. 6) [20.00]:

(20 • 400.0)/20.00 = 400.00 multiples (upper limit)

Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 399.99 instead of 400.00).

• This setting is hidden and set to OFF if High current trip - ground is set to N.

Setting

Time delay - ground high current trip

Default

0.00

Range

0–16000.00 cycles

Incr.

0.25 cyc.

The Time delay - ground high current trip setting programs an intentional time delay for the ground high current tripping. If set to zero (0), ground high current tripping operates instantaneously.

• This setting is hidden and set to zero (0) if High current trip - ground is set to N.

Setting

Activate high current trip - ground

Default Range Incr.

1

The Activate high current trip - ground enabled (e.g., if

setting determines when ground high current tripping is

Activate high current trip - ground = 2, then ground high current tripping is enabled for the second [2nd] trip operation and every following trip operation).

The setting range for Activate high current trip - ground adjusts according to Operations to lockout - ground (e.g., if Operations to lockout - ground = 4, then the range for Activate high current trip - ground is from 1 to 4).

• This setting is hidden and set to OFF if High current trip - ground is set to N.

70 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

31 High current lockout - phase

Default

N Y/N

Range Incr.

The High current lockout - phase setting enables the following two settings for phase high current lockout, if set to Y. Phase high current lockout is not affected by the cold load pickup scheme.

• This setting is hidden and set to N if Fast curve - phase (No. 8) and Delay curve - phase (No. 10) are both set to OFF.

Setting

High current lockout - phase

Default

OFF OFF, 1.00–39.99 multiples of Min. trip - phase

Range Incr.

0.01

The High current lockout - phase (multiples of Min. trip - phase ) setting determines the exceeded phase current threshold at which the SEL-351P-3 goes to the lockout state immediately when tripping.

High current lockout - phase = 13.00 (multiples of Min. trip - phase ) and

Min. trip - phase (No. 5) = 200.00 Amps primary, then the phase current threshold for phase high current lockout operates at a value equal to:

13.00 • 200.00 Amps primary = 2600.00 Amps primary

The upper limit of this setting (40.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - phase (No. 5) [200.00]:

(20 • 400.0)/200.00 = 40.00 multiples (upper limit)

Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 39.99 instead of 40.00).

• This setting is hidden and set to OFF if High current lockout - phase is set to N.

Setting

Activate high current lockout - phase

Default Range Incr.

1

The Activate high current lockout - phase enabled (e.g., if

setting determines when phase high current lockout is

Activate high current lockout - phase = 3, then phase high current tripping is enabled for the third [3rd] trip operation and every following trip operation).

The setting range for Activate high current lockout - phase adjusts according to Operations to lockout - phase (e.g., if Operations to lockout - phase = 4, then the range for Activate high current lockout - phase is from 1 to 4).

• This setting is hidden and set to OFF if High current lockout - phase is set to N.

71 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

32 High current lockout - ground

Default

N Y/N

Range Incr.

The High current lockout - ground setting enables the following two settings for ground high current lockout, if set to Y. High current lockout ground is not affected by the cold load pickup scheme.

• This setting is hidden and set to N if Fast curve - ground (No. 9) and Delay curve - ground (No. 11) are both set to OFF.

Setting

High current lockout - ground

Default

OFF OFF, 1.00–399.99 multiples of Min. trip - ground

Range Incr.

0.01

The High current lockout - ground (multiples of Min. trip - ground ) setting determines the exceeded ground current threshold at which the SEL-351P-3 goes to the lockout state immediately when tripping.

High current lockout - ground = 45.00 (multiples of Min. trip - ground ) and Min. trip - ground (No. 6) = 20.00 Amps primary, then the ground current threshold for ground high current lockout operates at a value equal to:

45.00 • 20.00 Amps primary = 900.00 Amps primary

The upper limit of this setting (400.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - ground (No. 6) [20.00]:

(20 • 400.0)/20.00 = 400.00 multiples (upper limit)

Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 399.99 instead of 400.00).

• This setting is hidden and set to OFF if High current lockout - ground is set to N.

Setting

Activate high current lockout - ground

Default Range Incr.

1

The Activate high current lockout - ground enabled (e.g., if

setting determines when ground high current lockout is

Activate high current lockout - ground = 3, then ground high current tripping is enabled for the third [3rd] trip operation and every following trip operation).

The setting range for Activate high current lockout - ground adjusts according to Operations to lockout - ground (e.g., if Operations to lockout - ground = 4, then the range for Activate high current lockout - ground is from 1 to 4).

• This setting is hidden and set to OFF if High current lockout - ground is set to N.

72 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No.

33

Setting

Cold load pickup scheme

Default

N Y/N

Range

The Cold load pickup scheme setting enables the cold load pickup scheme when set to Y.

Incr.

• This setting is hidden and set to N if Delay curve - phase (No. 10) is set to OFF and Delay curve - ground (No. 11) is set to OFF.

• If Cold load pickup scheme is set to Y, then you are prompted to program the following settings:

Setting

Cold load pickup - phase

Default

OFF OFF, 1.00–39.99 multiples of Min. trip - phase

Range Incr.

0.01

The Cold load pickup - phase setting determines the phase current threshold for overcurrent detection when the Cold load pickup scheme is active.

Cold load pickup - phase = 1.70 (multiples of Min. trip - phase ), Min. trip - phase (No. 5) = 200.00 Amps primary, and the cold load pickup scheme is active, then the phase current threshold for overcurrent detection operates at a value equal to:

1.70 • 200.00 Amps primary = 340.00 Amps primary

The upper limit of this setting (40.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - phase (No. 5) [200.00]:

(20 • 400.0)/200.00 = 40.00 multiples (upper limit)

Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 39.99 instead of 40.00).

• If Cold load pickup - phase is set to OFF, then the phase current threshold for overcurrent detection remains unchanged (threshold remains equal to Min. trip - phase [No. 5]).

• This setting is hidden and set to OFF if Cold load pickup scheme is set to N or Delay curve -

phase (No. 10) is set to OFF.

73 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

Setting

Cold load pickup - ground

Default

OFF

Range

OFF, 1.00–399.99 multiples of Min. trip - ground

Incr.

0.01

The Cold load pickup - ground setting determines the ground current threshold for overcurrent detection when the Cold load pickup scheme current threshold for overcurrent detection).

is active (also applied to SEF element as the SEF

Cold load pickup - ground = 1.50 (multiples of Min. trip - ground ),

Min. trip - ground (No. 6) = 20.00 Amps primary, and the cold load pickup scheme is active, then the ground current threshold for overcurrent detection operates at a value equal to:

1.50 • 20.00 Amps primary = 30.00 Amps primary

The SEF current threshold for overcurrent detection also operates at a value equal to 30 Amps primary when the cold load pickup scheme is active.

The upper limit of this setting (400.00 multiples) is calculated from the Amps secondary range upper limit [20] and settings CT Ratio (No. 3) [400.0] and Min. trip - ground (No. 6) [20.00]:

(20 • 400.0)/20.00 = 400.00 multiples (upper limit)

Due to processor calculations and rounding techniques, displayed range numbers may appear slightly different than expected (e.g., 399.99 instead of 400.00).

• If Cold load pickup - ground is set to OFF, then the ground current threshold for overcurrent detection remains unchanged (threshold remains equal to setting Min. trip - ground [No. 6]) and the SEF current threshold for overcurrent detection remains unchanged (threshold remains equal to setting Min. trip - SEF [No. 7]).

• This setting is hidden and set to OFF if Cold load pickup scheme is set to N or Delay curve - ground (No. 11) is set to OFF.

Setting

Loss of load diversity time

Default

0.00

Range

0–999999.00 cycles

The Loss of load diversity timer starts to time if both the following are true:

Incr.

0.25 cyc.

• The recloser is open.

• The control is in the lockout state or reclosing is defeated.

When the Loss of load diversity timer times out, the cold load pickup scheme is activated , causing the following to occur:

• Fast curves are disabled.

• Delay curves and SEF element are desensitized per preceding cold load pickup settings (the curves are not shifted—coordination is maintained).

When the recloser is closed, the cold load pickup scheme remains active. If the recloser remains closed, the current thresholds for overcurrent detection return naturally to their regular Min. trip

(No. 5, 6, or 7) levels when the inrush current goes below these respective regular levels for at least

15 seconds. The respective fast curves are enabled again. This return to normal conditions is separate for phase, ground, and SEF elements (e.g., ground could return to normal before phase or SEF, depending on the subsidence rates of inrush currents).

• This setting is hidden and set to zero (0) if Cold load pickup scheme is set to N.

74 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

Setting

Restore min. trips - time limit

Default

OFF

Range

OFF, 0–999999.00 cycles

Incr.

0.25 cyc.

The Restore min. trips - time limit is an option to force current thresholds for overcurrent detection from temporary cold load pickup values back to regular Min. trip (No. 5, 6, or 7) levels. This time limit is set if the user is concerned about an overcurrent element being desensitized too long in the cold load inrush scheme ( force the threshold back, do not let it return naturally as described with the preceding Loss of load diversity timer setting).

Restore min. trips - time limit ≠ OFF:

The Restore min. trips - time limit following are true:

starts to time if the recloser is closed and both of the

• The cold load pickup scheme is active for at least one element (see preceding Cold load pickup and Loss of load diversity settings).

• At least one of the following three Restore min. trip settings is set to Y.

If the recloser remains closed, the Restore min. trips - time limit times out and selected current thresholds for overcurrent detection (see following three Restore min. trip settings) are forced back to their respective regular Min. trip (No. 4, 5, and 6) levels. The respective fast curves are also enabled again. The natural return to the regular Min. trip levels (described with the preceding Loss of load diversity timer setting) can also occur if the inrush current goes below the Min. trip level for at least 15 seconds before Restore min. trips - time limit times out.

Restore min. trips - time limit = OFF:

If the cold load pickup scheme is active, then the current thresholds for overcurrent detection can only return back to their regular Min. trip levels naturally as described with the preceding Loss of load diversity timer setting.

• This setting is hidden and set to OFF if Cold load pickup scheme is set to N.

Setting

Restore min. trip - phase

Default

N Y/N

Range

Restore min. trip - phase = Y:

Incr.

If the cold load pickup scheme is active, the phase current threshold for overcurrent detection is forced back to the regular Min. trip - phase (No. 5) level when the preceding Restore min. trips - time limit times out.

Restore min. trip - phase = N:

If the cold load pickup scheme is active, the phase current threshold for overcurrent detection can only return back to its regular Min. trip - phase level naturally as described with the preceding Loss of load diversity timer setting.

• This setting is hidden and set to N if Restore min. trips - time limit is set to OFF or Delay curve - phase (No. 10) is set to OFF.

75 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

Setting

Restore min. trip - ground

Restore min. trip - ground = Y:

Default

N Y/N

Range Incr.

If the cold load pickup scheme is active, the ground current threshold for overcurrent detection is forced back to the regular Min. trip - ground (No. 6) level when the preceding Restore min. trips - time limit times out.

Restore min. trip - ground = N:

If the cold load pickup scheme is active, the ground current threshold for overcurrent detection can only return back to its regular Min. trip - ground level naturally as described with the preceding Loss of load diversity timer setting.

• This setting is hidden and set to N if Restore min. trips - time limit is set to OFF or Delay curve - ground (No. 11) is set to OFF.

Setting

Restore min. trip - SEF

Restore min. trip - SEF = Y:

Default

N Y/N

Range Incr.

If the cold load pickup scheme is active, the SEF current threshold for overcurrent detection is forced back to the regular Min. trip - SEF (No. 7) level when the preceding Restore min. trips

- time limit times out. The ground current threshold for overcurrent detection derived from setting Cold load pickup - ground is also applied to the SEF element (as the SEF current threshold for overcurrent detection).

Restore min. trip - SEF = N:

If the cold load pickup scheme is active, the SEF current threshold for overcurrent detection can only return back to its regular Min. trip - SEF level naturally as described with the preceding

Loss of load diversity timer setting.

• This setting is hidden and set to N if Restore min. trips - time limit is set to OFF, Delay curve - ground (No. 11) is set to OFF, or Min. trip - SEF (No. 7) is set to OFF.

76 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting Default

N Y/N

Range Incr.

The Sequence coordination setting keeps the SEL-351P-3 in step with a downstream recloser control, preventing the overreaching SEL-351P-3 Fast curve elements from tripping for faults beyond the downstream recloser.

Sequence coordination advances the operations counter each time the following sequence occurs:

• The SEL-351P-3 is in the reset state.

• Fast curve - phase (No. 8) or Fast curve - ground (No. 9) element picks up and starts timing for a fault.

• Fast curve - phase (No. 8) or Fast curve - ground (No. 9) element remains picked up for at least

1.25 cycles, but then drops out before tripping (fault was interrupted by downstream device closer to the fault).

When the operations counter is advanced beyond the corresponding Operations - phase fast curve (No. 13) or Operations - ground fast curve (No. 14), no more advancing of the operations counter occurs (the Fast curve elements are disabled). The Fast curve elements are enabled again (the operations counter is reset) after a time period equal to Reset time for auto reclose (No. 22).

• This setting is hidden and set to N if the Fast curve - phase and the Fast curve - ground settings are both set to OFF.

No.

35

Setting

Ground trip precedence

Ground trip precedence = Y:

Default

N Y/N

Range Incr.

• If the ground fault current is above the Min. trip - ground (No. 6) level at the time of trip, the operations to lockout follows Operations to lockout - ground (No. 16).

• If ground fault current is below the Min. trip - ground (No. 6) level and phase fault current is above the Min. trip - phase (No. 5) level at the time of trip, the determination to go to lockout is controlled by Operations to lockout - phase (No. 15).

Ground trip precedence = N:

• If ground fault current is above the Min. trip - ground (No. 6) level and phase fault current is below the Min. trip - phase (No. 5) level at the time of trip, the determination to go to lockout is controlled by Operations to lockout - ground (No. 16).

• If phase fault current is above the Min. trip - phase (No. 5) at the time of trip, the determination to go to lockout is controlled by Operations to lockout - phase (No. 15).

• Note: The Operations to lockout - SEF (No. 17) is independent of Ground trip precedence .

• This setting is hidden and set to N if Operations to lockout - phase (No. 15) = OFF, Operations to lockout - ground (No. 16) = OFF, or the Operations to lockout - phase setting equals (=) the

Operations to lockout - ground setting.

77 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting Default

N Y/N

Range Incr. shedding

The

Y.

Underfrequency load shedding setting enables the underfrequency load shedding scheme, if set to

• If Underfrequency load shedding is set to Y, enter the following two settings:

Setting

Underfrequency pickup

Default

OFF

Range

OFF, 40.10–65.00 Hz

Incr.

0.01 Hz

The Underfrequency pickup shedding.

setting determines the frequency threshold for underfrequency load

Setting

Underfrequency time delay

Default

6.00

Range

2.00–16000.00 cycles

The Underfrequency time delay shedding.

setting determines the time delay for underfrequency load

Incr.

0.25 cyc.

No. Setting

37 Demand meter time constant

Default

5

Range

5, 10, 15, 30, 60 minutes

The Demand meter time constant setting determines the thermal demand meter response time.

Incr.

Global EZ Settings

No. Setting

38 System Frequency

Enter nominal System frequency .

Default

50 50, 60 Hz

Range Incr.

No. Setting

39 Phase Rotation

Enter system Phase rotation .

Default

ABC ABC, ACB

Range Incr.

No. Setting

40 Recloser Wear Monitor

Recloser Wear Monitor = Y:

Default

AUTO AUTO, Y, N

Range Incr.

The recloser wear monitor must be set at a higher level, with the SET G command (see the SEL-351P-3

Instruction Manual ). This setting is usually selected if a circuit breaker is connected to the SEL-351P-3 instead of a GVR recloser.

Recloser Wear Monitor = N:

The recloser wear monitor is turned off.

Recloser Wear Monitor = AUTO:

This setting is usually selected if a GVR recloser is connected to the SEL-351P-3. Enter the following setting:

78 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

Setting

Interrupt rating

Default

12000

Range

6000, 8000, 10000, 12500, 16000

Amps primary

Incr.

1

Make this setting by finding your recloser model in Table 11 and then entering the corresponding value.

• This setting is hidden and nonoperative if Recloser Wear Monitor ≠ AUTO.

Table 11: Recloser Interrupt Data

Recloser Model

GVR (15.5 kV, 6 kA)

GVR (38 kV, 8 kA)

GVR (38 kV, 10 kA)

GVR (15.5 kV, 12.5 kA)

GVR (27 kV, 12.5 kA)

GVR (15.5 kV, 16 kA)

Interrupt Rating (Amps primary)

6000

8000

10000

12500

12500

16000

No. Setting

41 Reset trip-latched LEDs on close

Default Range

Y Y,Y1,N,N1

Incr.

Figure 18 and Figure 19 show the front-panel trip-latched LEDs. They are: TRIP/DISPARO, FAST

CURVE/CURVA RAPIDA, HIGH CURRENT/ALTA CORRIENTE, UNDER FREQ./BAJA FREC., and all

FAULT TYPE/TIPO DE FALLA LEDs.

These LEDs latch in at the rising edge of trip and remain illuminated—even after power is turned off and then on again.

Reset trip-latched LEDs on close = Y or Y1:

The trip-latched LEDs extinguish automatically when the recloser closes.

Reset trip-latched LEDs on close = N or N1:

The trip-latched LEDs extinguish automatically (or are newly latched in) when the SEL-351P-3 trips again.

Settings options Y1 and N1 disable the embedded 3-second qualifying time delay on the LOCK operator control (see the Operator Controls subsection in the Front-Panel Interface section). In this mode, the LOCK operator control effectively operates as the other operator controls, with no time delay.

No. Setting Default

N Y/N

Range connected

If True three-phase voltage is connected to the SEL-351P-3, the indication provided by A, B, and C

FAULT TYPE/TIPO DE FALLA LEDs is made more secure (see Figure 18 and Figure 19).

Incr.

No. Setting

43 Phantom voltages from

Default

NO

Range

VA,VB,VC,VAB,VBC,VCA,OFF

Incr.

If True three-phase voltage is set to N, the phantom voltage setting is available. In this mode the relay generates three balanced voltages, for metering only, from a single phase-to-ground or phase-to-phase connected voltage. Regardless of the phase selected, the voltage must be physically connected to phase V1.

79 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

44 V123 Terminal Conn. or

V123 Terminal Conn.

Default Range

A A,B,C,AB,BC,CA,OFF

ABC,ACB,BAC,BCA,CAB,CBA

Incr.

The voltage terminal connection setting allows the transition from the power system A-B-C wiring to the

SEL-351P-3 recloser control terminals V1-V2-V3.

If True three-phase voltage (#42) is set to N and Phantom voltages (#43) is set to OFF, voltage terminal connections A, B, C, AB, BC, CA, and OFF are available. When settings are saved, if V123 Terminal

Connection setting is out of range, the setting defaults to A.

If True three-phase voltage is set to Y, then voltage terminal connections ABC, ACB, BAC, BCA, CAB, and CBA are available. When settings are saved, if V123 Terminal Connection setting is out of range, the setting defaults to ABC.

No.

45

Setting

I123 Terminal Conn.

Default

ABC

Range

ABC, ACB, BAC, BCA, CAB,

CBA

Incr.

The current terminal connection setting allows the transition from the power system A-B-C wiring to the

SEL-351P-3 recloser control current terminals I1-I2-I3.

No.

46

Setting

CT Polarity

Default

POS POS, NEG

Range Incr.

The CT Polarity setting provides an easy way to change the polarity of the measured current signals, thus the resulting power direction and impedances.

No. Setting

47 Battery Amp-hours

Default

8.0

Range

6.5–20.0 Amp-hours

This is the amp-hour rating of the 24 Vdc battery system connected to pins 6 [+] and 2 [–] on POWER connector J6.

Incr.

0.1

No. Setting

48 Power-off Delay After AC

Loss

Default

180

Range

OFF, 1–1440 min

Incr.

1

The Power-off Delay After AC Loss setting value starts timing when the 24 Vdc battery takes over powering the SEL-351P-3 when Vac power goes away (e.g., a feeder outage occurs). If the outage persists, this setting value eventually times out and shuts down the SEL-351P-3 to conserve battery power. The SEL-351P-3 can only awaken if Vac power returns or the front-panel WAKE UP/DESPERTAR pushbutton is pressed.

80 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

No. Setting

49 Power-off Delay After Wake

Up

Default

20

Range

OFF, 1–1440 min

Incr.

1

The Power-off Delay After Wake Up setting value starts timing when the SEL-351P-3 has been awakened by pressing the front-panel WAKE UP/DESPERTAR pushbutton. If Vac power doesn't return (i.e., the outage persists), this setting value eventually times out and shuts down the SEL-351P-3 to conserve battery power.

The SEL-351P-3 can only awaken if Vac power returns or the front-panel WAKE UP/DESPERTAR pushbutton is pressed (and battery voltage is adequate).

No.

50

Setting

Power-off Voltage Level 1

Default

20.5 19.2–24 Vdc

Range Incr.

0.1

The Power-off Delay Voltage Level 1 setting shuts down the SEL-351P-3 (to conserve battery power) when the 24 Vdc battery has been powering the SEL-351P-3 and the battery voltage declines to the setting level (or below) for a qualified time of 5 seconds. The SEL-351P-3 can only awaken if Vac power returns or the frontpanel WAKE UP/DESPERTAR pushbutton is pressed (and battery voltage is adequate).

No. Setting

51 SF6 low pressure warning threshold in atm.

Default Range Incr.

1.1 0.9–2.0 atmospheres 0.1

The SF6 gas pressure inside the GVR recloser is typically at 1.3 atmospheres (atm). If the pressure goes below the SF6 low pressure warning threshold, then the ALARM output contact pulse for 5 seconds. The present SF6 gas pressure can be accessed with the STATUS command (see Table 3 in the Communications section).

Pressure sensing in the SEL-351P-3 has a 5-minute time constant with a 95 percent response. For example, if the SF6 gas pressure is suddenly lost and recloser tank pressure goes from 1.30 atm. to atmospheric pressure

(1.00 atm), after 5 minutes the SEL-351P-3 reports the SF6 gas pressure at around:

1.30 – 0.95 • (1.30 – 1.00) = 1.02 atm

81 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

EZ S

ETTINGS

S

HEETS

FOR THE

SEL-351P-3 R

ECLOSER

C

ONTROL

Page 1 of 5

Date

!

WARNING: Anytime an EZ setting is changed, review all the EZ settings before enabling the new settings. Pay close attention in circumstances where a setting was once set to OFF or N and then later turned on (enabled)—other related settings may need to be turned on, though may still be set to OFF or N.

Settings Groups 1 (Main) and 2 (Alternate)

EZ Settings (SET EZ n command; n = 1, 2):

Control Identifier (30 characters)

Circuit Identifier (30 characters)

CT Ratio

PT Ratio

Min. trip - phase

Min. trip - ground

Ranges given for

CT Ratio = 400.0

Min. trip - SEF

Fast curve - phase (see Page 4 of 4)

Time dial - phase fast curve

EM reset - phase fast curve

Fast curve - ground (see Page 4 of 4)

Time dial - ground fast curve

EM reset - ground fast curve

Delay curve - phase (see Page 4 of 4)

Time dial - phase delay curve

EM reset - phase delay curve

Delay curve - ground (see Page 4 of 4)

Time dial - ground delay curve

EM reset - ground delay curve

Time delay - SEF

Operations - phase fast curve

Operations - ground fast curve

Operations to lockout - phase

Operations to lockout - ground

Operations to lockout - SEF

Reclose interval 1

Reclose interval 2

Reclose interval 3

Reclose interval 4

Do not set less than

30 cycles, or premature lockout results

Range:

0–9, A–Z, -, /, ., space

0–9, A–Z, -, /, ., space

1.0–6000.0

1.0–10000.0

OFF, 40.00–1280.00 A primary

OFF, 2.00–1280.00 A primary

OFF, 2.00–600.00 A primary

OFF, U1–U5 (US), C1–C5 (IEC)

0.50–15.00 (U1–U5),

0.05–1.00 (C1–C5)

Y/N

OFF, U1–U5 (US), C1–C5 (IEC)

0.50–15.00 (U1–U5),

0.05–1.00 (C1–C5)

Y/N

OFF, U1–U5 (US), C1–C5 (IEC)

0.50–15.00 (U1–U5),

0.05–1.00 (C1–C5)

Y/N

OFF, U1–U5 (US), C1–C5 (IEC)

0.50–15.00 (U1–U5),

0.05–1.00 (C1–C5)

Y/N

0–16000.00 cycles

OFF, 1–5

OFF, 1–5

OFF, 1–5

OFF, 1–5

OFF, 1–5

0–999999.00 cycles

0–999999.00 cycles

0–999999.00 cycles

0–999999.00 cycles

--

--

0.01

--

--

0.01

--

--

Incr.:

--

--

1

1

0.01

0.01

0.01

--

0.01

0.01

1

1

--

0.25

1

1

1

0.25

Settings:

0.25

0.25

0.25

82 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

FOR THE

EZ S

ETTINGS

S

HEETS

Range:

0–999999.00 cycles

SEL-351P-3 R

ECLOSER

C

ONTROL

Settings Groups 1 (Main) and 2 (Alternate)

EZ Settings (SET EZ n command; n = 1, 2):

Reset time for auto reclose

Incr.:

0.25

Page 2 of 5

Date

Settings:

Reset time from lockout

Close power wait time

Complex fast curve - phase

Const. time adder - phase fast curve

Vert. multiplier - phase fast curve

Min. response - phase fast curve

Complex fast curve - ground

Const. time adder - ground fast curve

Vert. multiplier - ground fast curve

Min. response - ground fast curve

Complex delay curve - phase

Const. time adder - phase delay curve

Vert. multiplier - phase delay curve

Min. response - phase delay curve

Complex delay curve - ground

Const. time adder - ground delay curve

Vert. multiplier - ground delay curve

Min. response - ground delay curve

High current trip - phase

High current trip - phase (range given for

CT Ratio = 400.0)

Time delay - phase high current trip

Activate high current trip - phase

High current trip - ground

High current trip - ground (range given for

CT Ratio = 400.0)

Time delay - ground high current trip

Activate high current trip - ground

High current lockout - phase

High current lockout - phase (range given for CT Ratio = 400.0)

Activate high current lockout - phase

0–999999.00 cycles

0–16000.00 cycles

Y/N

0–60.00 cycles

0.10–2.00

0–60.00 cycles

Y/N

0–60.00 cycles

0.10–2.00

0–60.00 cycles

Y/N

0–60.00 cycles

0.10–2.00

0–60.00 cycles

Y/N

0–60.00 cycles

0.10–2.00

0–60.00 cycles

Y/N

1.00–(8000/Min. trip - phase) multiples of Min. trip - phase

0–16000.00 cycles

OFF, 1–5

Y/N

1.00–(8000/Min. trip - ground) multiples of Min. trip - ground

0–16000.00 cycles

OFF, 1–5

Y/N

1.00–(8000/Min. trip - phase) multiples of Min. trip - phase

OFF, 1–5

0.01

0.25

--

0.25

0.01

0.25

--

0.25

0.01

0.25

--

0.01

0.25

0.25

--

0.25

0.01

0.25

--

0.25

0.25

1

--

0.01

0.25

1

--

0.01

1

83 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

FOR THE

EZ

Settings Groups 1 (Main) and 2 (Alternate)

EZ Settings (SET EZ n command; n = 1, 2):

High current lockout - ground

High current lockout - ground (range given for CT Ratio = 400.0)

Activate high current lockout - ground

Cold load pickup scheme

Cold load pickup - phase (range given for

CT Ratio = 400.0)

Cold load pickup - ground (range given for

CT Ratio = 400.0)

Loss of load diversity time

Restore min. trips - time limit

Restore min. trip - phase

Restore min. trip - ground

Restore min. trip - SEF

Sequence coordination

Ground trip precedence

Underfrequency load shedding

Underfrequency pickup

Underfrequency time delay

Demand meter time constant

Global EZ Settings (SET FZ command):

S

ETTINGS

S

HEETS

SEL-351P-3 R

ECLOSER

C

ONTROL

Range:

Y/N

1.00–(8000/Min. trip - ground) multiples of Min. trip - ground

OFF, 1–5

Y/N

1.00–(8000/Min. trip - phase) multiples of Min. trip - phase

1.00–(8000/Min. trip - ground) multiples of Min. trip - ground

0–999999.00 cycles

OFF, 0–999999.00 cycles

Y/N

Y/N

Y/N

Y/N

Y/N

Y/N

OFF, 40.10–65.00 Hz

2–16000.00 cycles

5, 10, 15, 30, 60 minutes

--

--

--

--

0.25

0.25

--

--

0.01

0.25

--

Incr.:

--

0.01

1

--

0.01

0.01

System Frequency

Phase Rotation

Recloser Wear Monitor

Interrupt rating

Reset trip-latched LEDs on close

True three-phase voltage connected

Phantom voltages from

Voltage terminal connections (V1, V2, V3)

V123 terminal connections

If True three-phase voltage connected = N and Phantom voltages = OFF

Or

If True three-phase voltage connected = Y, then

Current terminal connections (I1, I2, I3)

I123 terminal connections

50, 60 Hz

ABC, ACB

AUTO, Y, N

6000, 8000, 10000, 12500, 16000

A pri.

Y,Y1,N,N1

Y/N

(VA,VB,VC,VAB,VBC,VCA,OFF)

A, B, C, AB, BC, CA, OFF

ABC, ACB, BAC, BCA, CAB, CBA

ABC, ACB, BAC, BCA, CAB, CBA

--

--

--

--

--

--

--

--

--

--

Page 3 of 5

Date

Settings:

84 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

EZ S

ETTINGS

S

HEETS

FOR THE

SEL-351P-3 R

ECLOSER

C

ONTROL

Settings Groups 1 (Main) and 2 (Alternate)

EZ Settings (SET EZ n command; n = 1, 2): Range: Incr.:

CT polarity POS, NEG --

Page 4 of 5

Date

Settings:

Battery Amp-hours

Power-off Delay After AC Loss

Power-off Delay After Wake Up

Power-off Voltage Level 1

6.5–20.0 Amp-hours

OFF, 1–1440 min

OFF, 1–1440 min

19.2–24 Vdc

0.1

1

1

0.1

SF6 low pressure warning threshold in atm.

0.9–2.0 atmospheres 0.1

85 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Settings

Recloser Curve Designations

EZ S

ETTINGS

S

HEETS

FOR THE

SEL-351P-3 R

ECLOSER

C

ONTROL

Quick Reference for Curve

Settings:

Fast curve - phase

Fast curve - ground

Delay curve - phase

Delay curve - ground

Use Any Mix of Old and New

Recloser Curve Designations

When Making Curve

Recloser Curve Cross Reference—Old to New

Old

J

KP

L

M

N

F

G

H

A

B

C

D

E

New Old

101 P

117 R

133 T

116 V

132 W

163 Y

121 Z

122 1

164 2

162 3

107 4

118 5

104 6

New Old

135 15

140 16

106 17

114 18

136

New

115 7

105 8

152

113

161 8PLUS 111

137 9 131

138 KG 165

120 11

134 13

102 14

141

142

119

112

139

103

151

Page 5 of 5

Date

US, IEC, and User-Programmable Curve Designations

US Curve Description

U2 inverse

IEC Curve

C1

C2

C3

Description class A (standard inverse) class B (very inverse) class C (extremely inverse)

User-Programmable

Curves (factory-set)

DEF_01

DEF_05

DEF_1

DEF_5

Description definite-time curve (0.1 seconds) definite-time curve (0.5 seconds) definite-time curve (1.0 seconds) definite-time curve (5.0 seconds)

86 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Testing

T

ESTING

Read and understand preceding sections so that the SEL-351P-3 can be safely grounded, powered up, and set. Especially understand the

Installation section.

Testing the SEL-351P-3 Without Regularly Installed Apparatus

Observe Recloser Count

Sequencing During Testing:

See Pushbutton Primary

Functions subsection in the

Front-Panel Interface section

(OTHER/VARIOS pushbutton—select "79").

Refer to Figure 12 and Figure 13 in the Installation section. If the regularly installed apparatus outside the SEL-351P-3 (i.e., the recloser, the external capacitor circuitry, and batteries) is not available during testing, then some settings and connections changes have to be made to compensate.

Logic Settings Changes

Refer to the SEL-351P-3 Instruction Manual , Section 10: Serial Port

Communications and Commands , specifically the SHO and SET commands. Factory default logic settings are listed under the SHO L command. Make the following logic settings changes with the SET L command:

* CL = (PB8*!LT5+CC*LT5+/IN102*LT5)*LT6

[normal setting is:

CL =

(PB8*!LT5+CC*LT5+/IN102*LT5)*LT6*TRCAP*CLCAP]

The dependence on the trip and close capacitors is removed as a requirement to issue a front panel close via the CLOSE/CIERRE operator control or via the serial port close command. See the

Close Logic subsection in Section 1: Factory-Set Logic in the

SEL-351P-3 Instruction Manual for explanation about the CL logic setting.

* 79CLS = 1

[normal setting is:

79CLS = TRCAP*CLCAP*!BADBAT*!DTFAIL]

The dependence on the trip and close capacitors and the batteries is removed as a requirement to issue an auto-reclose. See the

Reclose Supervision Logic subsection in Section 1: Factory-Set

Logic in the SEL-351P-3 Instruction Manual for explanation about the 79CLS logic setting.

Important: When testing is finished, return these settings back to normal.

Front Panel Status LEDs

Ignore the BATTERY PROBLEM/PROBLEMA BATERIA LED.

87 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Testing

Recloser Simulator

If the recloser simulator can provide both 52a and 52b recloser auxiliary contact operation, then connect as per Figure 13 in the Installation section (terminals 1, 5, and 13 of CONTROL connector J5). The 52a and

52b contacts have to be dry contacts (terminal 1 of CONTROL connector

J5 provides the whetting voltage).

If the recloser simulator can provide only 52a recloser auxiliary contact operation, then connect as per Figure 22 (terminals 1, 5, and 13 of

CONTROL connector J5). The 52a contact has to be a dry contact

(terminal 1 of CONTROL connector J5 provides the whetting voltage).

CONTROL connector

J5 recloser simulator

(partial)

13 see Note

1

5

52a

Note : Terminal 1 has a load limit of 0.1 A and should be fused for protection (Bussman

GMD-0.125 fuse or equivalent).

DWG: M351P054

Figure 22: Recloser Simulator Connections to SEL-351P-3 (only a 52a available)

Output Contacts

Unless the recloser simulator is designed to accept the same trip/close output that the GVR recloser accepts from the SEL-351P-3 outputs

(terminals 7, 8, and 15 of CONTROL connector J5; see Figure 12 and

Figure 13), program two of the programmable output contacts for the trip and close function, respectively and connect these output contacts to the recloser simulator:

OUT101 = TRIP

OUT102 = CLOSE

Program additional output contacts as needed (e.g., program an extra trip contact for overcurrent element timing: OUT103 = TRIP). Program the output contacts with the SET L command.

Refer to the SEL-351P-3 Instruction Manual , Section 10: Serial Port

Communications and Commands , specifically the SHO and SET commands. Factory default logic settings are listed under the SHO L command.

88 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Testing

Overcurrent Element Timing Test Setup

Remember, REMOTE

ENABLED/REMOTO

HABILITADO Controls Other

Operator Controls:

See Operator Controls subsection in the Front-Panel

Interface section.

* Set the operations settings “=1” (i.e., Operations-phase fast curve

= 1, Operations-ground fast curve = 1, Operations to lockoutphase = 1, and Operations to lockout-ground = 1).

* Set the other curves, not being tested, to OFF (e.g., if testing

Delay curve-ground, set Fast curve-phase = OFF, Fast curveground = OFF, and Delay curve-phase = OFF).

* If testing a ground overcurrent element, enable the ground overcurrent element with the EARTH FAULT

ENABLED/FALLA A TIERRA HABILITADA operator control—otherwise disable the earth fault/ground overcurrent elements with the EARTH FAULT ENABLED/FALLA A

TIERRA HABILITADA operator control.

* If testing the SEF overcurrent element, enable the SEF overcurrent element with the SEF ENABLED/SEF

HABILITADO operator control—otherwise disable the SEF overcurrent element with the SEF ENABLED/SEF

HABILITADO operator control.

* Program additional output contacts as needed to connect to a timing unit (e.g., program an extra trip contact for overcurrent element timing—see preceding Output Contacts subsection).

* Delay and fast curve overcurrent element specifications are found in the Specifications section (Time-Overcurrent Elements). The curve characteristics are listed in Section 9: Setting the

SEL-351P-3 Recloser Control in the SEL-351P-3 Instruction

Manual.

89 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Battery

B

ATTERY

Battery Operation Overview

Battery Connections:

Connect a 24 volt lead-acid battery to terminals 6 (+) and

2 (–) of POWER connector J6

(see Figure 12 ).

When ac power is interrupted to the SEL-351P-3, a 24 volt lead-acid battery supplies power to the SEL-351P-3.

The battery discharges to keep the SEL-351P-3 operating until any of the following occur:

• AC power is restored (the SEL-351P-3 continues to operate and the battery starts charging again)

• A battery discharge time limit is reached, the battery is automatically disconnected internally, and the SEL-351P-3 turns off (see following settings discussion)

• A battery discharge voltage limit is reached, the battery is automatically disconnected internally, and the SEL-351P-3 turns off (see following settings discussion)

After the SEL-351P-3 turns off, it wakes up if any of the following occur:

• AC power is restored

• The WAKE UP/DESPERTAR operator control is pressed and the

24 volt battery is reconnected internally

Battery-Related Settings

The following four battery-related settings are made with the SET FZ

(global EZ settings) command:

• Battery Amp-hours (6.5–20.0)

• Power-off Delay After AC Loss (OFF, 1–1440 min)

• Power-off Delay After Wake Up (OFF, 1–1440 min)

• Power-off Voltage Level 1 (19.2–24Vdc)

See the Settings section for explanations and default settings.

90 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Battery

Battery Status

Review May be Necessary:

This battery test section makes use of front-panel pushbuttons and serial port commands.

Review the Communications and Front-Panel Interface sections if needed.

Was It a Load Test Failure?

If the BATTERY PROBLEM/

BATERIA PROBLEMA LED is illuminated and MODE doesn’t display BADBAT, then the battery failed the latest load test. See the following Load

Test subsections.

The status of the battery can be checked via the front panel or serial port.

Battery Status via Front Panel

The BATTERY PROBLEM/PROBLEMA BATERIA LED illuminates for any of the following battery problems:

* Load test failure

* Damaged (battery cannot charge)

Press the STATUS pushbutton on the front panel of the SEL-351P-3 to access more battery status information. With the secondary function up/down arrow pushbuttons, move to different status screens. Those of interest for the battery are listed in Table 12.

Table 12: Battery Status Information Accessed From the Front Panel

Display Description

MODE = CHARGE battery is charging

MODE = DISCHG

MODE = DISTST battery is discharging battery load test in progress

MODE = BADBAT battery cannot charge

HRS_LFT = hh:mm–hours and minutes left to run on battery in discharge mode before the SEL-351P-3 puts itself to sleep (dependent on settings “Power-off Delay After AC Loss” and “Power-off Delay

After Wake Up”). Shows XX:XX if battery is charging.

12V_AUX =

VBAT =

IBAT =

12 V power output level–available via terminals 5(+) and 1(-) of

POWER connector J6 (see Figure 12) voltage level of 24 V battery current level (in mA) at which the 24 V battery is charging or discharging (preceded by a minus sign for discharging)

Battery Status via Serial Port

Execute the STATUS command, and have the same information available via the preceding front-panel STATUS/DIAGNO pushbutton.

91 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Battery

Automatic Battery Load Test

The SEL-351P-3 automatically load tests the 24 V battery about every 24 hours.

An internal 24-hour timer cumulatively times whenever the SEL-351P-3 is in the charge mode (120 Vac is powering the SEL-351P-3 and charging the battery; charge rate is 100 mA or less). Even if the battery is fully charged (and not discharging), the SEL-351P-3 is still in the charge mode.

After the 24-hour timer times out (and the SEL-351P-3 is still in the charge mode), an internal 1 Amp load is automatically paralleled with the battery for as many as 5 seconds. If battery voltage drops below 22.0 V during this load test, the test stops and the BATTERY

PROBLEM/PROBLEMA BATERIA LED illuminates and stays illuminated until the next battery test is successful. This load test failure condition can be routed to an output contact if desired (see the Battery

System Monitor subsection in Section 8 of the SEL-351P-3 Recloser

Control Instruction Manual ).

Battery Load Test via Front Panel

1.

Press the OTHER/VARIOS pushbutton on the front panel of the

SEL-351P-3.

A new screen appears, with BTT (battery test) as one of the choices.

2.

With the arrow pushbuttons, move the underscore to BTT.

3.

To test the battery, press the SELECT/ACEPTAR pushbutton. The battery load test proceeds, and the following message is displayed:

Testing Battery

. . . . . OK/FAIL

The periods on the second line appear consecutively as each second of the five-second load test times by. At the end of the test, OK or FAIL is displayed. If the battery fails the 1 Amp load test (same criteria as described previously in Automatic Battery Load Test ), the BATTERY

PROBLEM/PROBLEMA BATERIA LED illuminates and stays illuminated until the next battery load test is successful. This load test failure condition can be routed to an output contact if desired (see Battery

System Monitor in Section 8 of the SEL-351P-3 Recloser Control

Instruction Manual ).

92 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Battery

Battery Load Test via Serial Port

1.

Execute the BTT NOW command and the following message is displayed:

Battery test initiated. Duration 5 seconds

.

.

.

.

.

Battery test state is: OK/FAILED

The periods appear on each consecutive line as each second of the fivesecond battery load test times. At the end of the test, OK or FAILED is displayed. If the battery fails the 1 Amp load test (same criteria as described previously in Automatic Battery Load Test ), the BATTERY

PROBLEM/PROBLEMA BATERIA LED illuminates and stays illuminated until the next battery load test is successful. This load test failure condition can be routed to an output contact if desired (see the

Battery System Monitor subsection in Section 8 of the SEL-351P-3

Recloser Control Instruction Manual ).

2.

Execute the BTT command to see how much time remains until the next automatic battery discharge test. If the battery is okay (it is charging or discharging), the following message is displayed:

Battery test state is: OK/FAILED Time until next battery test:

XX.X hours

The “next battery test” is the automatic load test described previously in

Automatic Battery Load Test .

Value XX.X gives time until the next battery test to the nearest tenth of an hour. If 24+ is displayed for value XX.X, this infers an indeterminate amount of time until the next automatic load test (the battery is either discharging or it is charging at a rate greater than 100 mA).

93 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Specifications

S

PECIFICATIONS

Terminal

Connections

Stranded copper wire. Minimum temperature rating of 105°C.

Plug-in Connectors, Tightening Torque:

Minimum: 4.4 in-lb (0.5 Nm)

Maximum: 8.8 in-lb (1.0 Nm)

Power Supply 85–264 Vac

12 Vdc Output 11–14 Vdc, 6 W continuous, 13 W for 1 second.

AC Voltage

Inputs

AC Current

Inputs

Voltage Inputs V1, V2, V3, and V

300 V

L-N seconds.

S

.

continuous option (connect any voltage up to 300 Vac). 600 V

L-N

for 10

Burden: 0.03 VA @ 67 V; 0.06 VA @ 120 V; 0.8 VA @ 300 V.

3 V

L-N

continuous option (connect any voltage up to 3 Vac).

1 A nominal option: 3 A continuous, 100 A for 1 second, linear to 20 A symmetrical.

250 A for 1 cycle.

Burden: 0.13 VA @ 1 A, 1.31 VA @ 3 A.

0.01 A nominal option: 0.03 A continuous, 1A for 1 second, linear to 0.2 A symmetrical.

2.5 A for 1 cycle.

Sensitive Earth Fault

0.05 A nominal channel IN current input option: 1.5 A continuous, 20 A for 1 second, linear to 1.5 A symmetrical.

100 A for 1 cycle.

Burden: 0.0004 VA @ 0.05 A, 0.36 VA @ 1.5 A.

0.005 A nominal channel IN current input option: 0.15 A continuous, 2 A for 1 second, linear to 0.15 A symmetrical.

10 A for 1 cycle.

Frequency and

Rotation

60/50 Hz system frequency and ABC/ACB phase rotation are user-settable.

Frequency tracking range: 40.1–65 Hz (voltage connection to V1 required for frequency tracking).

94 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

95

Specifications

Output Contacts

Except Trip and

Close

Trip and Close

Outputs

Optoisolated

Input Ratings

Per IEC 255-0-20:1974 , using the simplified method of assessment:

6 A continuous carry

30 A make per IEEE C37.90-1989

100 A for one second

270 Vac/360 Vdc MOV for differential surge protection

Pickup/dropout time: < 5 ms

Breaking Capacity (L/R = 40 ms):

24 V

48 V

125 V

250 V

0.5 A

0.5 A

0.3 A

0.2 A

10,000 operations

10,000 operations

10,000 operations

10,000 operations

Cyclic Capacity (L/R = 40 ms):

24 V 0.5 A

48 V

125 V

250 V

0.5 A

0.3 A

0.2 A

2.5 cycles per second

2.5 cycles per second

2.5 cycles per second

2.5 cycles per second

Made for interface only to the Hawker Siddeley Switchgear Ltd./Whipp & Bourne

GVR Relcoser.

24 Vdc: on for 16.0–30 Vdc

Optoisolated

Input Ratings

(when used with ac control signals)

With nominal control voltage applied, each optoisolated input draws approximately 4 mA of current.

24 Vdc: on for 12.8–30.0 Vac

AC mode is selectable for each input via Global settings IN101D–IN106D. AC input recognition delay from time of switching: 0.75 cycles maximum pickup;

1.25 cycles maximum dropout.

Time-Code Input Relay module accepts demodulated IRIG-B time-code input at Port 1 and Port 2

(Port 1 is an optional EIA-485 port). Do not connect the time-code input into both

Port 1 and Port 2 at the same time. Relay time is synchronized to within ± 5 ms of time-source input.

Serial

Communications

Two side-panel and one front-panel EIA-232 serial communications ports.

One optional side panel EIA-485 serial port with 2100 Vdc of isolation.

Routine Dielectric

Test

Per-port baud rate selections: 300, 1200, 2400, 4800, 9600, 19200, 38400.

Control ac power: 2500 Vac for 10 seconds.

Optoisolated inputs, analog inputs, and output contacts except Trip and Close:

3100 Vdc for 10 seconds.

Operating Temp.

Relay module: –40° to +85°C (–40° to +185°F)

[LCD contrast impaired for temps. below –20°C (–4°F)]

Environment IEC 68-2-30:1980 Basic environmental testing procedures, Part 2: Test - Tests

Ca; Damp heat, cyclic . Severity Level: (12 + 12-hr cycle).

RFI and

Interference Tests

IEEE C37.90.1-2002 IEEE SWC Tests for Protective Relays and Relay Systems

(2.5 kV oscillatory, 4 kV fast transient) (type test).

IEEE C37.90.2-1995 Standard, Withstand Capability of Relay Systems to

Radiated Electromagnetic Interference from Transceivers, 35 V/m (type test with enclosure door open).

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Specifications

IEC 801-4:1988 Electromagnetic compatibility for industrial-process measurement and control equipment, Part 4: Electrical fast transient/burst requirements , Severity Level: 4 (4 kV on optional power supply, 2 kV on inputs and outputs) (type test).

IEC 255-22-1:2007 Electrical disturbance tests for measuring relays and protection equipment, Part 1: 1 MHz burst disturbance tests. Severity Level 3

(2.5 kV common mode, 1.0 kV differential) (type test).

IEC 255-22-3:2000 Electrical relays, Section 3: Radiated electromagnetic field disturbance tests , Severity Level: 3 (10 V/m) (type test).

IEC 255-22-4:2008 Electrical disturbance tests for measuring relays and protection equipment, Section 4: Fast transient disturbance test (type test).

IEC 255-5:2000 Electrical relays, Part 5: Insulation tests for electrical relays,

Section 6: Dielectric Tests, Series C (2500 Vac on analog inputs including control ac power; 3100 Vdc on power supply inputs, contact inputs, and contact outputs excluding Trip and Close). Section 8: Impulse Voltage Tests , 0.5 Joule, 5 kV (type test).

Impulse Tests IEC 255-21-1:1988 Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on measuring relays and protection equipment, Section 1 - Vibration tests (sinusoidal), Class 1 (relay module only).

Vibration and

Shock Test

IEC 255-21-2:1988 Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on measuring relays and protection equipment, Section 2 - Shock and bump tests, Class 1 (relay module only).

IEC 255-21-3:1993 Electrical relays, Part 21: Vibration, shock, bump, and seismic tests on measuring relays and protection equipment, Section 3 - Seismic tests, Class 2 (relay module only).

ESD Test IEC 255-22-2:2008 Electrical disturbance tests for measuring relays and protective equipment, Section 2: Electrostatic discharge tests , Severity Level: 4

(8 kV contact discharge all points except serial ports, 15 kV air discharge to all other points) (type test).

SEL-351P-3 recloser controls with AC voltage inputs rated 3 Vac nominal or AC current inputs rated

0.01 A nominal (IN channel rated 0.005 A nominal) are not tested to the following standards:

IEEE C37.90.1, IEEE C37.90.2, IEC 801-4, IEC 255-22-3, IEC 255-22-4, and IEC 255-22-5.

Relay Element Pickup Ranges and Accuracies

Pickup Range:

Instantaneous/Definite-Time Overcurrent Elements

0.05–20.00 A, 0.01 A steps (1 A nominal)

0.20–34.00 A, 0.01 A steps (1 A nominal—for phase-to-phase elements)

0.005–1.500 A, 0.001 A steps (0.05 A nominal channel IN current input)

Steady-State Pickup Accuracy: ±0.01 A and ±3% of setting (1 A nominal)

±1 mA and ±5% of setting (0.05 A nominal channel IN current input)

96 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

97

Specifications

Transient Overreach:

Time Delay:

Timer Accuracy:

±5% of pickup

0.00–16,000.00 cycles, 0.25-cycle steps

±0.25 cycle and ± 0.1% of setting

Pickup Range:

Time-Overcurrent Elements

0.10–3.20 A, 0.01 A steps (1 A nominal)

0.005–0.160 A, 0.001 A steps (0.05 A nominal channel IN current input)

Steady-State Pickup Accuracy:

Time Dial Range:

Curve Timing Accuracy:

±0.01 A and ±3% of setting (1 A nominal)

±1 mA and ±5% of setting (0.05 A nominal channel IN current input)

0.50–15.00, 0.01 steps (US)

0.05–1.00, 0.01 steps (IEC)

0.10–2.00, 0.01 steps (recloser curves)

±1.50 cycles and ±4% of curve time for current between 2 and 30 multiples of pickup

Pickup Ranges:

Under and Overvoltage Elements

0.0–150.0 V, 0.1 V steps (various elements; 300

Vac voltage inputs)

0.0–260.0 V, 0.1 V steps (phase-to-phase elements; 300 Vac voltage inputs)

Steady-State Pickup Accuracy:

Transient Overreach:

±1 V and ±5% of setting

±5% of pickup

Synchronism-Check Elements

Slip Frequency Pickup Range: 0.005–0.500 Hz, 0.001 Hz steps

Slip Frequency Pickup Accuracy:

Phase Angle Range:

Phase Angle Accuracy:

±0.003 Hz

0–80°, 1° steps

±4°

Under- and Overfrequency Elements

Pickup Range:

Steady-State plus Transient Overshoot:

40.10–65.00 Hz, 0.01 Hz steps

±0.01 Hz

Time Delay:

Timer Accuracy:

2.00–16,000.00 cycles, 0.25-cycle steps

±0.25 cycle and ±0.1% of setting

SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

Specifications

Timers

Pickup Ranges:

0.00–999,999.00 cycles, 0.25-cycle steps

(reclosing relay and some programmable timers)

0.00–16,000.00 cycles, 0.25-cycle steps (some programmable and other various timers)

Pickup and dropout accuracy for all timers: ±0.25 cycle and ±0.1% of setting

Metering Accuracy

Accuracies are specified at 20 ° C and at nominal system frequency unless noted otherwise.

Voltages V

A

, V

B

, V

C

, V

S

, 3V

0

, V

1

, V

2

±0.2% (33.5–150 V; 300 Vac voltage inputs)

Currents I

A

, I

B

, I

C

±3.0 mA and ±0.1% (0.1–2 A) (1 A nominal)

Temperature coefficient:

[(0.0002%)/(°C) 2 ] * (___°C – 20°C) 2

(see example below)

Currents I

N

, I

1

, 3I

0

, 3I

2

±0.01 A and ±3% (0.1–20 A) (1 A nominal)

±1 mA and ±5% (0.01–1.5 A) (0.05 A nominal channel IN current input)

Phase Angle Accuracy ±1.0°

Metering accuracy calculation example for currents I

A coefficient:

, I

B

, and I

C

due to preceding stated temperature

For temperature of 40 ° C, the additional error for currents I

A

, I

B

, and I

C

is:

[(0.0002%)/( ° C) 2 ] * (40°C – 20°C) 2 = 0.08%

Factory Assistance

We appreciate your interest in SEL products and services. If you have questions or comments, please contact us at:

Schweitzer Engineering Laboratories, Inc.

2350 NE Hopkins Court

Pullman, WA USA 99163-5603 USA

Telephone: +1.509.332.1890

Fax: +1.509.332.7990

Internet: www.selinc.com

Email: info@selinc.com

98 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

APPENDIX A: Quick-Start Guide Change Information

APPENDIX A: Q

UICK

-S

TART

G

UIDE

C

HANGE

I

NFORMATION

Changes in this guide to date are summarized below (most recent revisions listed at top).

Revision

Date

Summary of Revisions

The Quick-Start Guide Change Information section has been created to begin a record of revisions to this manual. All changes will be recorded in this Summary of Revisions table.

20100211 • Initial version.

99 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

APPENDIX B: Replace Existing Panacea or Amazon Recloser Controls With the SEL-351P-3 Recloser Control

APPENDIX B: R

EPLACE

E

XISTING

P

ANACEA OR

A

MAZON

R

ECLOSER

C

ONTROLS

W

ITH THE

SEL-351P-3

R

ECLOSER

C

ONTROL

Panacea and Amazon

Recloser Controls Are

Essentially the Same:

Panacea and Amazon

Recloser Controls are essentially the same, just different front-panel panel labeling/language. These recloser controls are also referred to as the SEL-351P-2

Recloser Control (or the older

SEL-351P-1 or SEL-351P

How the SEL-351P-3

Recloser Control Differs

From the Panacea and

Amazon Recloser Controls:

• Powered by AC power

(read this Appendix) instead of DC power.

• Battery charger is constantvoltage, not constant current (changes in batterrelated settings, too—see

Battery section.

• Various voltage and current options (see Table 1).

Panacea or Amazon Recloser Controls can be replaced with the

SEL-351P-3 Recloser Control, but accommodation has to be made to power the SEL-351P-3 Recloser Control with AC power (see Power

Supply Range in the Specifications section). The AC power connection details are given in this section. No other changes have to be made. The

DC voltage that powered Panacea or Amazon Recloser Controls (via terminals 16 and 9 of CONTROL connector J5) is still connected up to the SEL-351P-3 Recloser Control, but this DC voltage no longer provides power to the SEL-351P-3 Recloser Control (see Figure 13).

Near the top of Figure 3 (and Figure 4 through Figure 8—see Table 1 for

SEL-351P-3 Recloser Control model differences), notice the new addition of the POWER IN connector J7 on the SEL-351P-3 Recloser Control

(compared to Panacea or Amazon Recloser Controls)—this is where AC power is connected. See the Power Supply Connection side bar note accompanying Figure 12 and note the internal connection of POWER IN connector J7 (terminals 1 and 2) and POWER connector J6 (terminals 4 and 8) shown in Figure 12. Connecting AC power to POWER IN connector J7 (terminals 1 and 2) will “heat up” POWER connector J6

(terminals 4 and 8). In existing Panacea or Amazon Recloser Control cabinets, no connection is made to terminals 4 and 8 of POWER connector J6. Thus, terminals 4 and 8 of POWER connector J6 remain effectively unused in this recloser control replacement process.

Steps for Recloser Control Replacement

1.

Verify the cabinet (containing the Panacea or Amazon Recloser

Control) is properly grounded.

2.

De-energize the entire cabinet for the Panacea or Amazon Recloser

Control, including the incoming AC power.

3.

Remove the side panel connections to the Panacea or Amazon

Recloser Control. Remove the side panel GROUND connection last.

4.

Remove the Panacea or Amazon Recloser Control from the cabinet swing panel.

5.

Find the existing connector for AC power in the rear of the cabinet

(see Figure 23). Trace the existing wiring to this existing connector and confirm that it brings in AC power from outside the cabinet.

These existing wires should already be completely de-energized, per previous steps.

100 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

APPENDIX B: Replace Existing Panacea or Amazon Recloser Controls With the SEL-351P-3 Recloser Control

The existing connector shown in Figure 23 could possibly differ in type and wiring connections.

Consult with the cabinet manufacturer.

6.

Remove this existing connector in Figure 23 from its mating connector in the rear of the cabinet.

7.

If not already tagged for identification, tag the existing Line (Hot) and Neutral wires shown in Figure 23.

8.

Remove the existing Line (Hot) and Neutral wires from the existing connector in Figure 23. Do not remove the existing Ground wire.

9.

Figure 24 shows cable C5586 which will bring AC power from the existing connector in the rear of the cabinet to the SEL-351P-3

Recloser Control.

10.

Carefully install the blade for the white wire of cable C5586 into the Neutral wire position of the existing connector, along with the existing Neutral wire. Place the blade (white wire) to allow maximum room for reinstalling the existing Neutral wire. Tighten the combination of blade (white wire) and existing Neutral wire, following the tightening torque recommendations of the cabinet manufacturer.

11.

Carefully install the blade for the black wire of cable C5586 into the Line (Hot) wire position of the existing connector, along with the existing Line (Hot) wire. Place the blade (black wire) to allow maximum room for reinstalling the existing Line (Hot) wire.

Tighten the combination of blade (black wire) and existing Line

(Hot) wire, following the tightening torque recommendations of the cabinet manufacturer.

12.

The resultant wiring on the existing connector should now appear as the top portion of Figure 25 (cable C5586 is not yet connected to the SEL-351P-3 Recloser Control).

13.

Reconnect this rewired existing connector to its mating connector in the rear of the cabinet.

14.

Install the SEL-351P-3 Recloser Control on the cabinet swing panel.

Make the GROUND connection on the SEL-351P-3 Recloser Control side panel. Do not make any other connections yet.

Route cable C5586 so that it makes a sensible path to the swing panel and can be connected to POWER IN connector J7 on the SEL-351P-3

Recloser Control (do not make any connection yet). Use wire ties to fix cable C5586 in place enroute. Make allowance for the transition to the swing panel, so that cable C5586 does not become pinched, strained, or otherwise damaged at the swing panel hinge transition. Do not connect cable C5586 to the SEL-351P-3 Recloser Control yet.

15.

Re-energize the cabinet, including the incoming AC power.

16.

Make any necessary measurements, including the AC voltage on the cable C5586 connector, verifying its adequacy (see Power

Supply Range in the Specifications section).

101 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

APPENDIX B: Replace Existing Panacea or Amazon Recloser Controls With the SEL-351P-3 Recloser Control

17.

If the SEL-351P-3 Recloser Control has not been set yet, connect cable C5586 to POWER IN connector J7 on the SEL-351P-3

Recloser Control side panel as shown in the bottom portion of

Figure 25 (skip to the next step if settings have already been made).

The connector clip on cable C5586 will positively lock in place on

POWER IN connector J7. Do not make any other connections yet.

In a few seconds, the CONTROL ENABLED/CONTROL

HABILITADO LED and the AC SUPPLY/ALIM CA LED will illuminate. See the Low Capacitor Voltage Alarm on Display side bar note accompanying Figure 16. Make settings. When finished making settings, disconnect cable C5586 from POWER IN connector J7 on the SEL-351P-3 Recloser Control side panel, entirely de-energizing the SEL-351P-3 Recloser Control.

18.

Reconnect the power system current and voltage to the respective

CURENTS and VOLTAGES connectors on the SEL-351P-3

Recloser Control side panel (see Table 1 for various voltage and current options). Then, reconnect CONTROL connector J5 and

POWER connector J6. The SEL-351P-3 Recloser Control should still be de-energized.

19.

Connect cable C5586 to POWER IN connector J7 on the

SEL-351P-3 Recloser Control side panel as shown in the bottom portion of Figure 25. The connector clip on cable C5586 will positively lock in place on POWER IN connector J7. In a few seconds, the CONTROL ENABLED/CONTROL HABILITADO

LED and the AC SUPPLY/ALIM CA LED will illuminate. See the

Low Capacitor Voltage Alarm on Display side bar note accompanying Figure 16.

20.

Perform any other necessary commissioning.

Figure 23: Existing Connector and Wiring for Incoming AC Power into an Existing Panacea or Amazon Recloser Control Cabinet

102 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide

APPENDIX B: Replace Existing Panacea or Amazon Recloser Controls With the SEL-351P-3 Recloser Control blades black white clip

Cable

C5586

Figure 24: Cable C5586 for bringing AC Power to the SEL-351P-3 Recloser Control

Figure 25: Cable C5586 connected to bring AC Power from the Rear of the Existing Cabinet to the SEL-351P-3 Recloser Control

103 SEL-351P-3 Recloser Control Quick-Start Installation and User’s Guide