Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich UNIVERSITÄT DUISBURG – ESSEN FACHGEBIET ELEKTRISCHE ANLAGEN UND NETZE Exercises Accompanying the Lecture Series Electric Power Systems I-III Prof. Dr.-Ing. habil. Istvan Erlich 1 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich TABLE OF CONTENTS 1 The Three-Phase System .......................................................................................................... 4 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 2 Symmetrical Components ....................................................................................................... 20 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 3 Span of an overhead line ............................................................................................................. 32 Self and mutual inductances in a conductor – earth loop ........................................................ 34 Inductive coupling in a single-circuit overhead line ................................................................. 36 Inductive coupling in a double-circuit overhead line ............................................................... 38 Capacitive coupling in an overhead line.................................................................................... 39 Overhead line ............................................................................................................................... 40 Parameter of overhead lines, cables and other elements of the transmission system ........... 41 Transmission Line Performance ............................................................................................ 43 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 5 Current and power calculation in symmetrical components................................................... 21 Impedance in symmetrical components .................................................................................... 22 Unsymmetrical currents in symmetrical components .............................................................. 23 Fault conditions in natural and symmetrical components I .................................................... 24 Fault conditions in natural and symmetrical components II .................................................. 25 Sequence networks I.................................................................................................................... 26 Sequence networks II .................................................................................................................. 27 Zero Sequence equivalent circuit of transformers ................................................................... 28 Load current calculation - symmetrical voltage ....................................................................... 29 Load current calculation – unsymmetrical voltage .................................................................. 30 Transmission Line Parameters ............................................................................................... 31 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4 Working with complex numbers .................................................................................................. 5 Phasor representation of electrical quantities............................................................................. 6 Circuit analysis using phasor representation.............................................................................. 7 Impedance and power in RLC circuit ......................................................................................... 8 Calculation of equivalent circuit parameters.............................................................................. 9 Alternative schemes for power transmission ............................................................................ 10 The complex operator a .............................................................................................................. 11 Symmetrical three-phase load I ................................................................................................. 12 Symmetrical three-phase load II ................................................................................................ 13 Unsymmetrical load I .................................................................................................................. 14 Unsymmetrical load II ................................................................................................................ 15 Reactive power compensation .................................................................................................... 16 Symmetrical/unsymmetrical loads ............................................................................................. 17 Voltage drop, transmission losses with/without compensation ............................................... 18 Working with per-unit (p.u.) quantities .................................................................................... 19 Equivalent circuit and phasor diagram of a transmission line ............................................... 44 Compensation of a medium voltage line.................................................................................... 45 Transmission losses I ................................................................................................................... 46 Transmission losses II ................................................................................................................. 47 Maximum power transmission and steady state stability ........................................................ 48 Voltage stability ........................................................................................................................... 49 Calculations on a 750-kV long-range overhead transmission line .......................................... 51 Wave impedance, propagation coefficient, wave velocity and travel time ............................. 53 Traveling waves ........................................................................................................................... 54 Effect of a short-circuited line on a traveling wave .................................................................. 55 Traveling waves ........................................................................................................................... 56 Generators ............................................................................................................................... 58 5.1 5.2 5.3 5.4 5.5 Parameters and characteristic values of generators I .............................................................. 59 Control variables in a synchronous generator .......................................................................... 60 Parameters and characteristic values of generators II ............................................................ 61 Limits of capacitive loading for a generator ............................................................................. 62 Operational behavior of synchronous generators .................................................................... 63 2 Exercises Electric Power Systems I - III 5.6 5.7 6 Transformer dimensioning ......................................................................................................... 69 Determination of transformer equivalent circuit parameters ................................................. 70 Working in per unit quantities ................................................................................................... 71 Transformers in parallel operation ........................................................................................... 72 Impedance transformation ......................................................................................................... 73 Equivalent circuit of three phase MV/LV transformer ........................................................... 74 Unsymmetrical load on a transformer I .................................................................................... 75 Unsymmetrical load on a transformer II .................................................................................. 76 Zero-sequence equivalent circuit of transformers.................................................................... 77 Equivalent circuit of a three winding transformer .................................................................. 79 Behavior of a transformer under load ....................................................................................... 80 Behavior of a three winding transformer under unsymmetrical load .................................... 81 Zero-sequence network of a power system including transformers ....................................... 82 Parallel operation of transformers............................................................................................. 83 Voltage magnitude and phase angle control of transformers.................................................. 84 Autotransformer.......................................................................................................................... 85 Transformer in open delta connection ...................................................................................... 86 Effect of primary fault on secondary voltages .......................................................................... 87 Transformer in „Scott“ connection ........................................................................................... 89 Instrument transformers (IT) .................................................................................................... 90 power flow analysis ................................................................................................................. 92 7.1 7.2 7.3 7.4 7.5 8 Generator loading capability diagram ...................................................................................... 64 Steady-state and transient stability............................................................................................ 66 Transformers ........................................................................................................................... 68 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 6.10 6.11 6.12 6.13 6.14 6.15 6.16 6.17 6.18 6.19 6.20 7 UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich Power flow solution by Gauss – Seidel method......................................................................... 93 Power flow analysis by Newton – Raphson method ................................................................. 95 Regulating transformer and load sharing I .............................................................................. 96 Regulating transformer and load sharing II ............................................................................. 97 Representation of the regulating transformer in a load flow study ........................................ 98 Short Circuit analysis.............................................................................................................. 99 8.1 Comparison of a short circuit in R-L circuit and a generator .............................................. 101 8.2 Symmetrical short-circuit in a generator – transformer unit ............................................... 102 8.3 Short-circuit current computation: internal emf method vs. equivalent voltage source method I ................................................................................................................................................. 103 8.4 Short-circuit current computation: internal emf method vs. equivalent voltage source method II ................................................................................................................................................ 104 8.5 Short-circuit in a generator connected to a group of motors I .............................................. 105 8.6 Short-circuit in a generator connected to motors II............................................................... 106 8.7 Symmetrical short-circuit current computation..................................................................... 107 8.8 Mechanical and thermal stress caused by the short-circuit current..................................... 108 8.9 Calculation of short circuit currents in a meshed network ................................................... 112 8.10 Short Circuit Current Limitation ............................................................................................ 114 8.11 Analysis of unsymmetrical faults ............................................................................................. 115 8.12 Effect of transformer neutral point connection on system performance during fault ........ 117 8.13 Neutral point grounding in medium voltage networks .......................................................... 119 8.14 Problem of voltage un-symmetry in three phase transmission systems ............................... 121 8.15 Low impedance grounding in cable networks ........................................................................ 122 8.16 Transient stability analysis I .................................................................................................... 124 8.17 Transient stability analysis II ................................................................................................... 125 8.18 Transient stability analysis III ................................................................................................. 126 8.19 Transient stability analysis IV.................................................................................................. 127 3 Exercises Electric Power Systems I - III 1 UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich THE THREE-PHASE SYSTEM 4 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.1 Working with complex numbers Given: Z 1 = 2.598 + j1.5 Z 2 = 2.828 + j 2.828 Z 3 = 2.5 + j 4.33 ) i( t ) = I ⋅ sin( ωt + φi ) a. Evaluate the following expressions and give the results both in polar and Cartesian coordinates: * i. Z 1 ⋅ Z 2 ⋅Z 3 2 * ii. Z 1 + Z 2 ⋅Z 3 iii. Z 1 ⋅ Im⋅ {Z 3 } −1 b. Find the complex number I such that: { } 2 ⋅ Re{I ⋅ e } i. i( t ) = 2 ⋅ Im I ⋅ e jωt ii. i( t ) = jωt c. What is the RMS (root mean square) or “effective” value of i(t), if: i. The radian frequency ω = 2π.50 s-1 ii. The radian frequency ω = 2π.60 s-1 ) iii. A positive offset value I / 2 is added to i(t)? Fig. 1 Sine curve with and without offset 5 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.2 Phasor representation of electrical quantities Assuming u(t) = 141.4 sin(ωt + 300) V and i (t)= 11.31 cos(ωt - 300) A, determine: a. the amplitude and the RMS (root mean square) values for the voltage and the current b. the current and voltage phasors c. the complex power and the power factor d. the values of R (resistance) and X (reactance) for i. series ii. parallel connections. 6 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.3 Circuit analysis using phasor representation R i(t) i(t) u(t) L C u(t) (ii) (i) a. R For circuits (i) and (ii), give the general relationship relating the voltage u(t) to the current i(t). b. Assuming a sinusoidal applied voltage, show that the differential equations obtained in (a) can be simplified to the following algebraic equations in phasor form: U = I ⋅ ( R + jω L ) U = I ⋅( R + 1 ) jω C for (i) for (ii) where U and I are the voltage and current phasors, respectively. 7 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.4 Impedance and power in RLC circuit R L a Magnetic field energy stored in the inductance L: e Wmf = a) R in series with L 1 ⋅ L ⋅i2 2 C R Electric field energy stored in the capacitance C: a e Wef = b) R in series with C R 1 ⋅C ⋅u2 2 L e a C c) R L in parallel with C Assume the parameters in the circuits (a) – (c) above have the following values: R = 10 Ω, L = 15.9 mH, C = 0.6366 mF, f = 50 Hz. a. Calculate the impedance Zae (in Ω) as well as the admittance Yae (in S) across the terminals a – e for the circuits (a) – (c). b. Assume voltage with the value u( t ) = 2 ⋅ 220V ⋅ cos ωt is applied across the terminals a – e. Calculate I, S, P and Q for all three connections. c. Now, consider the circuit (a). Find a general expression for the product i ⋅ u L (uL : the voltage drop across the inductance L), and show that this expression corresponds to ∂Wmf ∂t d. Re-work (c) for the circuit (b) to show that the product i ⋅ uC (uC : the voltage drop across the capacitance C) corresponds to ∂Wef ∂t . e. What can you deduce from the solutions (c) and (d) with regard to the nature of Q (the reactive power)? 8 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.5 Calculation of equivalent circuit parameters XAE A UA E UE RE XE With UE = 220 V ∠ − 30° RE = 63.5 Ω jXE = j110 Ω jX AE = j10 Ω Calculate and indicate: a. the direction of currents (load and output currents) and voltages according to the generation-oriented sign convention; b. the load admittance YE; c. the current IE; d. the complex power absorbed by the load; e. the voltage across jXAE and the voltage UA; f. the real and imaginary parts as well as the active and reactive parts of the current in location E; g. the complete phasor diagram; (resolve the current in location E in real and imaginary parts as well as in active and reactive parts). 9 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.6 Alternative schemes for power transmission A generator, situated at a remote location, is intended to supply a load via a transmission line. The available conductor material for the transmission line has an overall cross-sectional area of A with an allowable current density J. The conductor can be divided into multiple conductors if and when the need arises, and is insulated for a peak voltage of U0. Determine (in terms of J, A and U0) the maximum power that can be transmitted by the line for the following alternative configurations: a. DC two wire schemethe load is supplied by a single dc source b. DC three wire schemethe load is divided into two equal parts, each supplied by a source of equal magnitude, and a common conductor is used for the return current c. Single-phase schemethe load is supplied by a single phase ac source d. Single-phase three wire schemethe load is divided into two equal parts, each supplied by an identical single-phase ac source and a common conductor is used for the return current e. Two-phase schemeThe load is supplied by a two-phase voltage system having the following relationship: ux = û cosωt V, uy = û sinωt V f. Three-phase schemeThe load is supplied by a three-phase voltage system having the following relationship: ua = û cosωt V, ub = û cos(ωt-1200) V, uc = û cos(ωt+1200) V Summarize the results obtained in (a) – (f) in a tabular form and explain why, of all the possible alternatives, the three-phase system has established itself as the standard mode in electric power supply system. 10 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.7 The complex operator a Using the definition: a = 1∠1200 simplify the following expressions: a. 1+ a + a2 b. 1- a 2 + a c. a 2 + a + j d. j a + a 2 e. ea f. a 10 g. (1 - a 2)3 h. a – 1 11 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.8 Symmetrical three-phase load I Z1 ~ L1 UL1-L2 L2 Z2 ~ L3 Z3 ~ Z 1 = Z 2 = Z 3 = 30Ω∠31.80 U L1− L 2 = 3 ⋅ 220V∠30 0 The voltage source to which the above load is attached is symmetrical. Determine: a. The line to line voltages b. The phase voltages c. U L 2− L3 ,U L 3− L1 U L1 ,U L 2 ,U L3 The line currents I L1 , I L 2 , I L 3 d. The complex powers in each phase S L1 , S L 2 , S L3 e. The total complex three phase power absorbed by the load S 3φ 12 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.9 Symmetrical three-phase load II Ia a Zab Ib b Ic c Zca Zbc The load impedances and the source voltage have the following values. Z ab = Z bc = Z ca = (30 + j 27 )Ω 2 U a = 220V∠0 0 U b = a ⋅U a U c = a ⋅U a a. Calculate the currents I a , I b , I c . b. What is the total complex power absorbed by the load and the corresponding power factor (cosϕ)? c. Assume that three pieces of capacitor batteries, each with a value of C= 25 µF, are available. Determine the power factor at the load terminals, when the capacitors are connected: i. as shown in (i), ii. as shown in (ii). Ia Ia a a Zab b c Ib Zab Ib Zca b Zbc Ic Zca C Zbc Ic c C C (i) (ii) 13 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.10 Unsymmetrical load I Consider the following circuit in which an R-C load is connected between phases a and b with phase c remaining open. V represents a voltmeter. R a Xc b V c R = Xc = 100 Ω; Ua = 220∠00 V Calculate the voltage across the voltmeter (V) if the source voltage represents: a. a positive-sequence b. a negative-sequence. 14 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.11 Unsymmetrical load II a R XL b XC c Uab = 38∠0 0 kV PR = 10 MW; Q L = Q C = PR 3 If the source voltage is known to be a symmetrical three-phase system, calculate: a. R, XL and XC b. The complex power absorbed by the load c. The currents Ia, Ib, Ic and the power factor (cos ϕ) at the generator terminals. Also show that, as seen from the generator terminals, the load can be represented by a starconnected pure resistive load and then determine the value of the corresponding resistance per phase. 15 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.12 Reactive power compensation An induction motor has the following ratings: 380 V, 20 kVA, 0.7 lag During the course of the operation of the motor, it was found out that a full load on the motor leads to the overloading of the supply line. a. Find the value of the capacitor per phase to be installed at the terminals of the motor which would reduce the line current to the allowable limit of 25 A, if the capacitors are to be connected in: i. Star ii. Delta. b. Determine the power factor (after compensation) at i. the input line ii. the motor terminals behind the capacitor bank. 16 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.13 Symmetrical/unsymmetrical loads Two three-phase loads, one star and the other delta connected, are supplied from a symmetrical three-phase source via a transmission line having the reactance 2 Ω/phase and negligible resistance. Each of the three-phase loads absorbs 20 kW at unity power factor and the rated voltage of 0.4 kV. a. Determine the load impedance per phase for both the delta and the star connected loads. b. Determine the currents in each of the load impedances and the supply line. c. Calculate the complex power and the voltage at the source end of the line. d. Assume now that, with the source voltage held constant at the value calculated under (c), the delta connected load is disconnected from the supply. Additionally, one of the impedances (phase a) in the star-connected load is parallel short-circuited. The star points of both the load and the voltage source are grounded. i. Determine the currents in phases a, b and c of the supply line. What is the power absorbed by the load? ii. What is the value of the current flowing through the neutral wire? iii. What are the values of the phase currents, when the neutral wire is disconnected? iv. From (iii), what can you deduce regarding the size of the neutral conductor compared to the phase conductors? e. Assume now that the star load is disconnected while the delta load is reconnected to the supply. Additionally, one of the load impedances (between phases a and b) is parallel short-circuited. i. Determine the phase as well as the line currents. ii. Compare the line currents calculated in e(i) and c (i) and comment on the degree of asymmetry in both cases. 17 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.14 Voltage drop, transmission losses with/without compensation ∼ Generator: Overhead line: Load: UG= 20 kV Zb= 2.5+j3 Ω ZL= 110+j50 Ω a. Draw the single-phase equivalent circuit b. Calculate: − The line current (I) − The active power (P) − The reactive power (Q) − The apparent power (S) − The complex power (S) − The power factor (cos ϕ) at the load. c. Determine the output power and the power factor at the generator terminals d. The power factor at the load is to be increased by connecting capacitors in parallel to the load. Determine the value of the capacitors per phase needed to improve the power factor to 0.98, if the capacitors are to be connected in: − Delta − Star. e. Compute the line losses with and without compensation. f. Compare the voltages at the load terminal with and without compensation. 18 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 1.15 Working with per-unit (p.u.) quantities 1 Ω j8 Ω IL 39 Ω ∼ 220 V ∠00 UL j26 Ω In the circuit shown above, a load having an impedance of 39 + j26 Ω is fed from a voltage source through a line having an impedance of 1 + j8Ω. The effective (RMS) value of the source voltage is 220 V. a. Calculate the load current IL and the voltage at the load terminal UL. b. Calculate the active and reactive power delivered to the load. c. Repeat the above calculation in per-unit choosing a base of 220 V for the voltage and 1500 VA for the apparent power S. d. Compare the values obtained in c) with those obtained in a) and b). 19 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2 SYMMETRICAL COMPONENTS 20 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2.1 Current and power calculation in symmetrical components Three identical Y-connected resistors form a load bank with a three-phase rating of 400 V, 500 kVA. The load bank has applied voltage magnitudes: Uab= 320 V Ubc= 480 V Uca= 400 V The neutral of the load is not connected to the neutral of the system. a. Find the line currents and the complex power absorbed by the load: i. without using symmetrical components ii. using the symmetrical components. b. Assuming the load is supplied from the low voltage side of a Dy-connected, 10/0.4-kVtransformer, find the line voltages and currents on the high-voltage side of the transformer both in natural and symmetrical components. 21 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2.2 Impedance in symmetrical components Consider the following circuit, which may be described by the matrix equation given below the figure. A a E Ia Zs i Ib b Ic Zg Zs Z Z Zg Z c Ua,A Ub,A Zs Z Uc,A ∆Ua Ua,A − Ua,E Z s ∆Ub = Ub,A − Ub,E = Z g ∆U U − U Z c,E c c ,A g or in compact form: Zg ∆Uabc Zs Zg Z g Ia Z g Ib , Z s Ic = Z abc Iabc Zg a. Prove that by transforming the voltage and current relationships into symmetrical components, a decoupled (i.e. zero off-diagonal elements) system can be achieved. b. Carry out the transformation and determine the diagonal elements Z 00 , Z11 und Z 22 of the transformed matrix in terms of the given parameters. 22 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2.3 Unsymmetrical currents in symmetrical components A a i E Ia b c Ib =- Ic The line currents during a short-circuit in an overhead line are known to be as follows: Ia = 0 A Ib = 2700 A ∠ 0° Ic = 2700 A ∠ 180° Calculate the corresponding current phasors in symmetrical components. 23 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2.4 Fault conditions in natural and symmetrical components I a. For a single line-to-ground (SLG) fault in phase a (depicted below), formulate the fault conditions in natural components, transform these relationships into symmetrical components and then deduce from these the interconnection of the sequence networks during fault. Ia a Ib b Ic c Ua Ub IF Uc E Single-line-to-ground (SLG) fault b. For a double line-to-ground (DLG) fault between phases b and c (depicted below), formulate the fault conditions in natural components, transform these relationships into symmetrical components and then deduce from these the interconnection of the sequence networks during fault. Ia a Ib b Ic c Ua Ub Uc IF E Double-line-to-ground (DLG) fault 24 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2.5 Fault conditions in natural and symmetrical components II A DLG fault involving a fault impedance is shown in the figure below: Ia a Ib b Ic c Ua Ub Uc ZF E a. Give the fault conditions in natural components. b. Transform then these conditions into symmetrical components. c. Sketch the equivalent circuit in accordance with the conditions determined in (b) and indicate U012 and I012 in the circuits. 25 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2.6 Sequence networks I A power system feeds a three phase symmetrical load via a capacitive overhead line (see figure below), with the star point of the load grounded through the resistance R. Ia Ua Ub Ib Ca Ic Cb Cc a Z b c Z c Z s s s Uc CaE CbE CcE R s Draw the equivalent circuit of the line in terms of symmetrical components. 26 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2.7 Sequence networks II A symmetrical three phase voltage source Uabc, with internal impedance Zi and the star point grounded through the resistance Ri, feeds a symmetrical load via a lossless line, the star point of which is also grounded through a resistance RE, see figure below. Uqa Zi s a ZV s ZV s Uqb Zi b c Uqc s Zi s R s c Ua Ub ZV s Uc RE s a. Derive the relationships, which describe the situation in natural components, and transform these into symmetrical components. b. Based on the results obtained in (a) draw the equivalent circuit in terms of symmetrical components. 27 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2.8 Zero Sequence equivalent circuit of transformers Find the zero sequence equivalent circuits of two winding transformers in the following connection: 28 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2.9 Load current calculation - symmetrical voltage A balanced three-phase Y-load (shown in the figure below) is grounded through the neutral impedance Zn. There is a mutual coupling between the three loads making up the Y-load. Ua Ub Uc Zn Each phase has a series reactance of Zs =j12 Ω, and the mutual coupling between phases is Zm =j4 Ω. A balanced three phase voltage of 220-V line to neutral voltage (the neutral of the source voltage is grounded) is applied to the load. Determine: a. the line currents by mesh analysis without using symmetrical components. b. the line currents using symmetrical components. 29 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 2.10 Load current calculation – unsymmetrical voltage A three-phase unbalanced source with the following phase to neutral voltages is applied to a load. 0 U a 200∠25 0 U b = 100∠ − 55 U 80∠100 0 c The load series impedance per phase is Zs = 8+j24Ω and the mutual impedance between phases is Zm =j4Ω . The load and source neutrals are solidly grounded. Determine: a. The load sequence impedance matrix Z012. b. The symmetrical components of voltage. c. The symmetrical components of current. d. The load phase currents. e. The complex power delivered to the load in terms of symmetrical components. f. The complex power delivered to the load in terms of the power per phase. 30 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 3 TRANSMISSION LINE PARAMETERS 31 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 3.1 Span of an overhead line An overhead conductor (aluminium conductor steel reinforced (ACSR), DIN 48204-240/40-Al/St) is suspended between two back-to-back towers with both points of connection having the same height above ground. The conductor is fastened onto the towers for a maximum sag (fmax) of 10 m at 40°C. Span length A = 150 m Conductor cross section A = 282.5 mm2 Diameter of the stranded conductor d = 21.8 mm Mass of the stranded conductor per unit m ' = 0.985 length kg m ε ϑ = 1.96 ⋅ 10 −5 ⋅ K −1 Coefficient of thermal expansion Modulus of elasticity E = 70 kN mm 2 Stress per unit length caused by ice layer d N q VZ = 5 + 0.1 mm m at –5° C, (in accordance with DIN VDE 0210) a. Based on the state equation : a2 g⋅ ρ g⋅ ρ εϑ(ϑ1 − ϑ2) = 1 − 2 24 σ1 σ2 2 2 − σ1 − σ2 , E derive a relationship for the critical span aσ max, assuming an identical tensile stress σmax for both states 1 and 2, which are defined as follows : State 1 ϑ1 = -5°C δ1 = δ + ∆δ additional ice layer ! State 2 ϑ2 = -20°C δ2 = δ State 3 ϑ3 = 40°C δ3 = δ 32 Exercises Electric Power Systems I - III δ UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich is the specific density of the stranded conductor and ∆δ is the specific density of an assumed additional ice layer; ( δ = g.ρ). b. Determine the span aσ max by using the given values and σ max = 72.1 N . mm 2 In which of the states, 1 or 2, do you expect the maximum tensile stress? c. Derive, in an analogous way, a second equation for the second span length afmax for which the same maximum sag occurs in the states 1 and 3 (see table above). In doing so, replace the tensile stresses σ1 and σ2 in the state equation by the maximum sag fmax using the equation f = δ ⋅ a2 . Is the span afmax admissible? 8⋅σ 33 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 3.2 Self and mutual inductances in a conductor – earth loop A single conductor composed of solid round wire having radius r (figure below) is used for an overhead transmission line. r D 0 x I1 a. Derive an expression for the external flux linkages (per unit length of the line) between points r (conductor radius) and D (an arbitrary point at a remote location). Also find the internal flux linkages, i.e. the flux linkages between x = 0 and x = r, and then an expression for the total flux linkages arising from the sum of the internal and external flux linkages. b. Assume a second conductor carrying the current I2 is placed in parallel to the conductor under consideration. The center-to-center distance between the two conductors is D12. Derive an expression for the mutual flux linkages. c. Assume now that, in place of the single conductor described in (a), two conductor bundles, each with the radius r and held apart by a spacer of length d, are used. Show that the external flux linkages can still be computed using the expression derived in (a) by merely replacing the conductor radius (r) by the equivalent radius of the bundle, which is rb = r ⋅ d (The total current I1 is assumed to divide equally between the two conductors). Similarly, show that the equivalent radius for a conductor bundle comprising of three conductors (each with radius r) and placed at the vertices of an 3 equilateral triangle of side d is: rb = r ⋅ d 2 d. Replace the second conductor in (c) with an earth conductor, which carries the return current. The mutual distance between the earth conductor (E) and the phase conductor (i) can be computed using the formula: 34 Exercises Electric Power Systems I - III D iE = 2 ⋅ e − 0 . 077 µ0 ⋅ ω ⋅ κ UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich ≈ 930 κ [ S ⋅ cm −1 cm ] ω = 100 ⋅ π Hz; µ 0 = 4πx10 − 4 H / km; κ = conductivity of the earth Show that the self-reactance of the conductor – earth loop per unit length can be computed using the formula: X i−E = X i + ω ⋅ µ0 D 930 ⋅ ln iE = X i + 0.14467 lg rb 2⋅π rb κ [S ⋅ cm −1 ] cm ⋅ Ω , km where Xi represents the reactance due to the internal flux linkages (refer to (b)). e. Similarly, show that mutual-reactance between two conductor – earth loops (i and k) placed at a distance of Dik from one another can be computed using the formula: X ik − E = ω ⋅ µ0 D 930 ⋅ ln iE = 0.14467 ⋅ lg D ik 2⋅π D ik κ [S ⋅ cm −1 ] cm ⋅ Ω km f. Using the following value for the earth resistance: RE = μ0 ⋅ ω ≈ 0.05 Ω / km 8 show that the self- and mutual-impedances of the line can be computed using the formulae: Z ii−E = R + R E + j( X i−E + X i ) Z ik −E = R E + jX ik −E , where R represents the line resistance per unit length. 35 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 3.3 Inductive coupling in a single-circuit overhead line The following figure depicts the tower and conductor arrangement for a 220-kV double circuit overhead line using two conductor bundles for each phase. In this exercise, only one of the systems (denoted by the small letters a b c ) is to be considered. p q 2.5 4.91 4.5 a 4.5 b 5.15 c a = 0.4 C B A 20.14 All distances in m Phase conductors: Shield wires 2 x 185/32 AlSt 185/32 AlSt r = 9.6 mm rp = 9.6 mm R = 0.079 Ω/km (for the bundle) Rp = 0.158 Ω/km Xi = 0.00678 Ω/km (for the bundle) Xip = 0.0132 Ω/km h = 11.068 m hp = 15.978 m Conductivity of the earth: κ = 10 −2 S ⋅ m −1 Earth resistance RE = 0.05 Ω/km 36 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich Assuming that the tower carries only one of the two systems, calculate the following: a. the impedance matrix Z of the un-transposed line b. the impedance matrix Z , when the line is transposed c. the sequence impedance matrix for the transposed line d. the operating impedance of the line per phase (operating impedance is to be understood as the per phase impedance per unit length for an ideally transposed line neglecting the effect of the shield wire) e. the impedance matrix Z for a transposed line taking the influence of the shied wire into consideration f. the sequence impedance matrix Z for a transposed line taking the influence of the shied wire into consideration g. the reduction factor, i.e. the ratio of the zero-sequence current flowing through the ground return to the overall zero-sequence current h. the reduction factor, if instead of the above shield wire, a 70 mm2 steel conductor with the impedance Z’PP-E = (2.39 + j2.158)Ω/km is used i. the voltages Uc and Ub in the figure below for a transposed line of 150 km length: I. neglecting the shield wire II. considering the effect of the shield wire Ip a b Ib c Ib ∑I Uc ∑I L = 150 km L = 150km Ib = 800A Ib = 800A Ub 37 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 3.4 Inductive coupling in a double-circuit overhead line Conductors are now assumed to have been placed on the other arm of the tower (in Exercise 3.3) leading to a double-circuit 220-kV-three-phase overhead line. Assuming the two systems are mirror-symmetrically arranged, determine the following: a. the impedance matrix for the un-transposed line b. the transformation matrix from natural components into symmetrical components for a double-circuit line c. the sequence impedance matrix (general) for the un-transposed line d. the sequence impedance matrix for γ-transposition e. the sequence impedance matrix for β-transposition. Sketch also the transposition scheme f. the mutual zero-sequence impedance between the two circuits determined on the basis of conductor geometry (for β-transposition) g. the total impedances (Z00)g, (Z11)g und (Z22)g for each system during parallel operation of the two systems and assuming γ- transposition h. the conductor-to-ground voltage (ULE) for the following configuration. a b c I II A B C ULE ∑I ∑I = 500 A l = 200 km; 38 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 3.5 Capacitive coupling in an overhead line For the transmission system described in Exercise (3.3): a. Show that for a completely transposed line the diagonal and off-diagonal elements of the potential coefficients matrix can be computed using the following approximate formulae: Pnn = 18 ⋅ 10 6 ⋅ ln Pnm = 9 ⋅ 10 6 ⋅ ln( 2 ⋅ hn km / F r 4 ⋅ h n2 2 D nm + 1) km / F hn = 3 h a ⋅ hb ⋅ h c b. Determine: i. the elements of the potential coefficient matrix ii. the matrix of the capacitance coefficients iii. the positive-, negative- and zero-sequence components of the capacitance coefficients iv. the positive-, negative- and zero-sequence capacitances of the line v. the operating capacitance of the line neglecting the effect of the shield wire. 39 Exercises Electric Power Systems I - III 3.6 UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich Overhead line The figure below shows the conductor arrangement for a 345-kV overhead line using two bundles for each phase. The phase conductors are assumed to be ideally transposed. d d d D D d = 45 cm D=8m Each of the conductors has the following values: r (conductor radius) = 1.085 cm R (conductor resistance) = 0.119 Ω/km Xi (internal reactance/conductor) = 0.0132 Ω/km ε0 = 1 ⋅ 10 −9 F / m 36 ⋅ π µ 0 = 4π ⋅ 10 −7 H / m a. Calculate the reactance ( X 'b ), impedance ( Z 'b ), capacitance ( C 'b ), charging reactive power ( Q 'c ), charging current ( I 'c ) all per km and the wave impedance ( Z w ), the natural load ( Pnat ). b. Re-evaluate the values in (a) if, instead of two conductors per phase, a single conductor with the same combined cross sectional area is used. c. Re-evaluate the values in (a), if instead of two, three conductor bundles were to be used for each phase? Assume conductors are placed at the vertices (tips) of an equilateral triangle of side 0.45 m, and that the total conductor cross-sectional area remains the same as in (a). d. Determine the voltage at the sending-end, when the line delivers 250 MVA load at the rated voltage and pf = 0.85 lagging e. Determine the no-load voltage at the receiving-end (the load end) of the line when the rated voltage is applied at the sending-end (the generator end) of the line. For (d) and (e), assume that the line has a length of 300 km. Use the parameters calculated in (a). Neglect the line resistance. Also, sketch the phasor diagram! 40 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 3.7 Parameter of overhead lines, cables and other elements of the transmission system a. The following figure depicts the conductor arrangement for a 380-kV-Overhead line. 7.97 b 8.63 7.00 c 4.33 a 0.5 3X380/50 AlSt All values in m r = 1.35cm Xi =0.0132 Ω/km R =0.0757/3 Ω/km Determine the following: - rb - Xb (line reactance per km), - Cb (line capacitance per km), - QC (charging reactive power per km) - IC (charging current per km), - ZW (wave impedance) - Pnat (natural power) 41 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich b. A 220-kV three-phase, radial field cable has the following values: ICE (capacitive earth fault current) = 36A/km, ZW = 36Ω Determine the line reactance and the natural power. c. The following values of a 20-kV three-phase cable are known: R (cable resistance) = 0.175 Ω/km Cb=0.33µF/km In (rated current)= 220A tanδ (loss factor)= 0.005 l (cable length) = 10km Determine the dielectric losses, the conductor losses and the charging current at the rated voltage. d. The dimensions of a cast-resin insulated bus bar arrangement are given in the figure below. Calculate the impedance and the capacitance of the bus bar system. Metallic screen 250mm Cast resin εr = 4 Conductor; κ = 3580 S/mm 35mm 15mm e. For the following 110-kV AlSt (210/36 AlSt) bus bar system, determine: - the resistance, the reactance, the line capacitance, the wave impedance and the natural power. 1.7m 3.1m 3.1m 19.3 42 Exercises Electric Power Systems I - III 4 UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich TRANSMISSION LINE PERFORMANCE 43 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 4.1 Equivalent circuit and phasor diagram of a transmission line A IA i IE Xb R ICE ICA UA E Cb Cb 2 2 UE Rated values: SE= 600 MVA cos ϕE = 0.95 lag. UE = 380 kV 3 ∠0° Parameters: IC = 0.97 A km X' b = 0.24 Ω km R' = 0.03 Ω km at 85°C l = 300 km a. Determine the parameters of the nominal π equivalent circuit b. Calculate the line voltage drop, including its real and imaginary components, for the load given above: i. Considering the line capacitance ii. Neglecting the line capacitance iii. Considering the line capacitance and assuming a load power factor of unity. c. Determine the transmission losses for b(i) – b(iii). d. Calculate the no-load voltage at the receiving-end of the line when the voltage at the sending-end is 380kV. e. Determine the maximum permissible load at a power factor of 0.95 lagging if the real part of the voltage drop is not to exceed 10%. 44 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 4.2 Compensation of a medium voltage line A load of 5 MVA, cos ϕE = 0.7 lagging is fed via a 10-kV overhead line (95 mm2 Al, R = 0.309 Ω/km, length l = 8.5 km) with UE = 10 3 Xb = 1. 3 . R kV a. What is the voltage at the sending-end of the line (UA)? b. What is the voltage at the sending-end (UA), if the voltage at the receiving-end (UE) is maintained at the rated value and a series capacitor with k = 2 (k =XC/Xb: degree of compensation) is installed at the receiving-end of the line? c. What would the voltage at the input terminals of the line (UA) be, if (instead of series compensation described in (b)) the load power factor is improved through parallel compensation from cos ϕE = 0.7 to cos ϕ´E = 0.95 ? d. Calculate the required capacitance and the corresponding reactive power output for (b) (max. line current = 350 A). e. What is the required capacitance and the corresponding reactive power output for (c)? (Assume star connection of capacitors). f. If the capacitors available in stock have values given in the table below, determine the required number of units for both (d) and (e). QCn = 50 kVar In = 8.65 A Un = 5.78 kV Cn = 4.77 µF 45 Exercises Electric Power Systems I - III 4.3 UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich Transmission losses I A three-phase line has the following parameters and rated values. L=120 km C’b=12.32 nF/km cos ϕE = 0.9lag SE=100 MVA R' = 0.079 Ω/km X’b = 0.289 Ω/km a. Calculate the transmission losses PR for following voltages at the receiving-end of the line (the load SE remains constant at the value given above). (The line capacitance Cb. i. Un = 220 kV ii. Un = 110 kV b. The rated line voltage (Un) is 110kV. Calculate and compare the transmission losses if the actual voltages on the line change as follows. Neglect Cb = 0. i. Ub = 120 kV ii. Ub = 100 kV iii. Ub = 90 kV c. A 140-MVA transformer with adjustable taps is connected to the receiving-end of a 220kV line (A – E). The transformer has the following rated values: a = 231kV/115.5 kV, xps =13.6%. Assume the voltage at the 110-kV bus-bar is to be kept constant at the rated value using the following two options. In one case the voltage UA is increased to compensate the voltage drop but the transformer tap remains at nominal position (231/115.5kV). In the second case the transformer tap setting is changed to an = 231/127 kV to keep the voltage at the load at 110 kV. Calculate and compare the line real and reactive losses (PR and Qx) in both cases. (The line capacitance is to be considered, and in both cases the line delivers 100 MVA at cosϕE = 0.9 lag). A E p 220 kV s 110 kV 46 Exercises Electric Power Systems I - III 4.4 UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich Transmission losses II A three-phase line has the following parameters and rated values. L=120 km C’b ≅ 0 cos ϕE = 0.7lag SE=100 MVA R' = 0.079 Ω/km X’b = 0.289 Ω/km UE=220 kV For this line, the influence of the power factor (cos ϕE) on line transmission losses is to be investigated. a. Derive an expression relating the line real power losses to the power flow (real and reactive power flows). b. Give the losses for the given power flow both as an absolute value and as a percentage of the real power at the receiving-end. c. Determine the losses if cos ϕE is improved through parallel compensation to 0.8/0.9/0.95. d. Determine the losses at the various power factors in (c) due only to the active/reactive current. 47 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 4.5 Maximum power transmission and steady state stability Consider the transmission system shown in the figure below in which a generator supplies power to a grid via a transformer and an overhead line. The generator is modelled as a voltage source in series with a reactance xd. The value of the generator internal voltage is assumed to be u p = 1.0 p .u . The transformer and the overhead line are both represented with their reactance. The reactances have the following values: xd = 1 p.u., xps = 0.1 p.u., xL = 2.0 p.u. Generator Transformer N ∼ jxd up jxps uG jxL Transmission line uN The grid is considered to be an infinite bus, i.e. both the amplitude and the phase angle of the voltage uN are constant and independent of the power flow. Assume u N = 1.0∠0 0 p .u . a. Using basic power equations derive an expression for the maximum possible real power pmax which the generator can deliver to the grid. b. What is the power factor corresponding to the real power determined in (a) at the grid terminals (bus N). c. Now, the reactance of the transmission line is to be compensated by inserting a series capacitor into the line in such a way that the transmission system maintains a 30 % reserve (stability margin) when the generator delivers pmax (calculated in (a)) to the grid. What is the power factor at the grid interconnection point corresponding to this load? 48 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 4.6 Voltage stability U2 U1 Load: S2= P2+jQ2=200 MW+j70 Mvar Grid Overhead line: (infinite bus) Zb= R+jX=10 +j100 Ω The voltage at the sending-end of the line (U1) is 400 kV. a. Find an implicit expression describing U 2 as a function of S2, i.e. derive the expression: * U 2 = U1 − Z b ⋅ S2 / 3 (1) * U2 b. Take the voltage U2 as the phase reference, i.e. set U2 = U2 and then solve (1) analytically, i.e. derive the relationship: U 21,2 2 A − U 12 = − ± 2 (2 A − U ) 2 2 1 4 − A2 − B 2 (2) where: A=(RP2+XQ2)/3 B=(XP2-RQ2)/3 c. Plotting (2) using the given values results in the following curve. As can be seen from the plot, there are two values for U2 corresponding to P2 = 200 MW. Which of the two values corresponds to a stable operating point? 49 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 400 350 Line to line voltage [kV] 300 250 200 150 100 50 0 0 100 200 300 Load [MW] 400 500 600 Voltage at the receiving-end of the line as a function of load power d. Indicate how the phase angle of U1 at the given load and the value of U2 determined in (c) can be calculated. 50 Exercises Electric Power Systems I - III 4.7 UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich Calculations on a 750-kV long-range overhead transmission line A 750-kV overhead line has the following values: Rated voltage Un = 750 kV Length l = 1100 km Phase conductors Four ACSR bundles, each with 400 mm2 cross-section Resistance (of the bundle) R = 0.0198 Ω/km Reactance (of the bundle) Xb = 0.289 Ω/km Susceptance (of the bundle) ωCb = 4.12 10-6 S/km Conductance (of the bundle) Gb = 0.4 X 10-6 S/km (for rainy weather) a. Calculate the wave impedance (ZW), the propagation coefficient, the wave length, the wave propagation velocity for the line. b. Determine the following three equivalent circuits and compare the circuit parameters: i. The short line approximation ii. The nominal π-equivalent circuit iii. The exact π-equivalent circuit. c. Determine the sending-end voltage, the real and reactive losses when the line delivers PE = 2000 MW at 750 kV and unity power factor at its receiving-end. d. Calculate the voltage midway along the line when the line delivers power corresponding to the wave impedance load at its receiving end at the rated voltage. e. Derive a formula for the resulting wave impedance of the line (as a function of the capacitor) when a series capacitor is inserted into the line at an equidistant point between the sending and receiving ends of the line. Hint: Solution of the wave equation for sinusoidal voltages and currents: 51 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich U A ( x ) = UE cosh( γx ) + IE Z w sinh( γx ) I A ( x ) = IE cosh( γx ) + UE sinh( γx ) Zw Wave (surge) impedance Zw = Zb Yb = R + jX b G b + j ωC b Propagation coefficient: γ = α + jβ = Z b Y b = (R + jX b )(Gb + jωC b ) 52 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 4.8 Wave impedance, propagation coefficient, wave velocity and travel time An overhead line has the following parameters: L =1.1 mH/km C = 12.25 nF/km l = 500 km The line is connected to a cable with the following parameters: L =0.45 mH/km C = 0.25µF/km l = 50 km Determine: a. The wave impedance (ZW), propagation coefficient (χ), and travel time (τ) both for the overhead line and the cable b. The reflection and refraction coefficients for the voltage as well as for the current at the junction overhead line – cable. 53 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 4.9 Traveling waves A DC source voltage U0 with an internal resistance Rs is connected to a lossless line having a wave impedance Rc. The line is terminated with a resistance RR. The travel time of the wave along the line is τ. A B Rs Ri U0 RR a. Draw a lattice (Bergeron) diagram showing the voltage and the current in the line for the period from t = 0 to t = 10τ. b. Determine the receiving-end voltage (the voltage at B) at t= 0, 2τ, 4τ, and 6τ, and hence at t=2nτ, where n is any positive integer. c. Determine the steady-state voltage at the receiving-end of the line in terms of U0, Rs, RR, and Rc. d. Verify the result in part (c) by analyzing the system as a simple DC circuit in steadystate. (Note that the line is assumed to be lossless; note also how inductances and capacitances behave in a DC circuit.) e. Assuming U0=100kV, Rc=10 Ω, find the numerical values for the steady-state voltage at B, if: i. Ri =0 Ω, RR=1000 Ω ii. Ri =10 Ω, RR=1000 Ω iii. Ri =0 Ω, RR→ ∞ iv. Ri =10 Ω, RR→ ∞ 54 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 4.10 Effect of a short-circuited line on a traveling wave Zc Ri RR U0 150 km 400 km The generator has an internal resistance Ri = 0, and the transmission line is assumed to be lossless. The elements shown in the figure have the following values: U0 = 4kV, RR = 80Ω, Zc = 100Ω, wave velocity v = 3.105km/s. The generator is equipped with a relay that trips instantaneously when the current reaches 250A. The transmission line shown in the figure above is short-circuited at t = 0 at a location 150 km away from the generator. 55 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 4.11 Traveling waves Two lines with wave impedances of 100 Ω and 500 Ω, respectively, are connected in series, as shown in the figure below. The travel time of the wave in lines 1 and 2 are τ and 2τ, respectively. While the far end of line 2 is open-circuited, line 1 is connected (at its sending-ending) to a voltage source of 100 kV amplitude, which is assumed to remain constant during the period under consideration. A Z1=100Ω τ B Z2=500Ω 2τ C U=100kV a. Sketch the lattice diagram in the space provided below for the period 0 ≤ t ≤ 12τ, indicating all reflections and refractions. A 0 B C x 1 2 3 4 5 6 7 8 9 10 11 12 t/τ 56 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich b. Using the Bergeron method, calculate and then plot against time voltages and currents at points A, B and C for 0 ≤ t ≤ 12τ. 57 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 5 GENERATORS 58 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 5.1 Parameters and characteristic values of generators I A cylindrical rotor synchronous generator has the following ratings and parameters: Sn = 125 MVA xd = 1.8 p.u. Cosϕn = 0.8 lag x’d = 0.264 p.u. Tm = 6.31s x”d = 0.156 p.u. Un = 10.5 kV a. Specify the operational conditions under which each of the reactance given in the above table is valid! Sketch the corresponding equivalent circuits and indicate the ranges of their validity. b. Determine the generator excitation voltage (Polradspannung), the sub-transient and transient voltages for no load and rated load pre-fault operating conditions. c. Assume the generator is synchronized to a large network. After synchronization, with the excitation remaining unchanged, the turbine input power is slowly increased to 50% of the generator rated power. Neglecting the armature resistance, determine the power angle (Polradwinkel) and the power factor at which the generator is operating. Is the generator over excited or under excited? d. For a three-phase fault occurring at the generator terminals, calculate (neglecting the generator resistance): i. the steady-state (Dauerkurzschlussstrom) ii. the transient and iii. the sub-transient short-circuit currents. 59 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 5.2 Control variables in a synchronous generator A cylindrical rotor synchronous generator is connected to an infinite bus as shown in the figure below. G ~ Generator Bulk power system The synchronous reactance and the rated values of the generator are as follows: Sn = 1111 MVA xd = 2.8 p.u Ra = 0 Un = 24 kV Cosϕn= 0.95 lag a. Assume the generator is synchronized to the network as shown in the figure above and delivers PG = 1050 MW at a power factor of 0.95 lagging. The voltage at the terminals of the generator is maintained at the rated value. Calculate: − The excitation (generated) voltage − The power angle − The maximum power (Pmax) b. The mechanical power is now reduced by 20% compared to the setting in (a). The excitation current remains unchanged. Calculate: − The excitation (generated) voltage − The power angle − The maximum power (Pmax) − The power factor at the terminals of the generator. c. The mechanical input power is restored to the value in (a), whereas the degree of excitation is reduced by 10 % (with the value in (a) as a base). Calculate: − The excitation (generated) voltage − The power angle − The maximum power (Pmax) − The power factor at the terminals of the generator. Is the generator now overexcited or under-excited? Justify your answer. 60 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 5.3 Parameters and characteristic values of generators II In continuation of Exercise 5.1: a. Derive a mathematical relationship, which relates the rotor speed during a short-circuit at the generator terminals and determine the rate of change of speed per second. Prior to the fault, the generator was supplying the rated load. b. Determine the negative-sequence current, if - during operation at the rated load - one of the phase conductors experiences an interruption. As a simplifying approximation, the other two phase currents are assumed to maintain their pre-fault values. Would this level of continuous negative sequence current load be permissible? c. Neglecting the effects of any controller action, determine the theoretical maximum steady state and transient output power. Assume the power increase takes place from both no load and rated load initial conditions. 61 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 5.4 Limits of capacitive loading for a generator The cylindrical rotor synchronous generator considered in Exercises 5.1 – 5.2 is now connected to a remote infinite bus through an overhead line and transformer (see figure below). In addition to the generator data given under Exercise 5.1, the following transformer and line parameters are known: Transformer xps Line = 0.15 p.u. aTr = 10.5/380 kV Sn =125 MVA C’b = 14 nF/km G a. Sketch the equivalent circuit of the generator connected to a transformer and an overhead transmission line operating on no load. Neglecting the series impedance of the line and the transformer as well as the shunt conductance of the line, describe how the system behaves for Xd ≤ Xc and Xd > Xc. Deduce from this the limit of the maximum permissible capacitive loading, if generator self-excitation is to be averted! Why is selfexcitation a dangerous phenomenon? b. Calculate the length of a 400-kV overhead line, which would cause the generator to self-excite. How would this value change if the transmission line is a double-circuit line? (Assume the breaker at the far end of the line to be open.) 62 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 5.5 Operational behavior of synchronous generators The terminal characteristic of the synchronous generator considered in Exercises 5.1 – 5.3 is to be studied in this exercise. Recall that the rated values of the machine are: Sn =125 MVA Un = 10.5 kV Cosϕn = 0.8 lag xd = 1.8 p.u a. Show that the per unit voltage at the terminals of the generator under load is given by the following relationship: u = up x ⋅i 1− d w up 2 − x d ⋅ ib , up= generator internal emf; (where u = terminal voltage; components of the load current, respectively; iw, ib = real and reactive xd = synchronous reactance. All values in per unit.) b. Assuming that the excitation as well as the real part of the load current are held at their respective rated values, show that the terminal voltage as a function only of the reactive current is given by the relationship: u = 2.08 - xd . ib c. With the excitation remaining unchanged, derive a relationship (similar to the one derived in part (b)), which relates the real current (instead of the reactive current) to the terminal voltage. The reactive current is now assumed to remain constant at the rated value. d. Based on the relationship given in part (a), small voltage changes around the operating point arising from real and reactive current variations can be determined using the relationship: ∂u ∆u = ∂i w 0 0 ∂u ⋅ ∆ib = c w ⋅ ∆i w + c b ⋅ ∆ib ⋅ ∆i w + ∂ib Calculate the coefficients cw and cb, and confirm that the influence of the reactive component of the load current (ib) on the terminal voltage (u) is significantly higher than that of the real current (iw), i.e. c b > c w . e. Determine the necessary change in the generator excitation (generator internal emf up) as a function of the change in the reactive current, if the terminal voltage is to be held constant at the rated value. 63 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 5.6 Generator loading capability diagram For this exercise the parameters given in Exercise 5.1 are to be used. a. The generator is assumed to be operating on an infinite bus ( U = U∠0° = const. ). Derive an expression, which relates the armature current to the rotor angle (δp) and the degree of excitation (ε = Up/U). b. Show how the active and reactive powers can be derived from the current loci and determine the power scale of the diagram. Also, derive from the current relationship characteristic curves of the active power vs. rotor angle (P=f(δp)) und reactive power versus rotor angle (Q = f(δp)). c. The loading capability diagram (also known as the operation chart) for this generator is to be drawn in the following steps: Step 1: Draw the phasor diagram of the machine. Up = Un 3 ∠0 0 − jX d ⋅ Ia = 6.06 kV∠0 0 − j1.59 Ω ⋅ 6.87 kA∠143.13 0 Ω Up jXdIa Ia Diagram 1: Phasor Diagram Ua Rotating the mirror image (with respect to the imaginary axis) of the above diagram by 900 gives the following diagram. 64 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich jXdIa P Ia Up Ua Diagram 2: Operating Chart i. Point P represents the rated operating point. Starting from P, draw the constant excitation circle, the circle for constant armature current, the locus of operating points for constant real power (P), and the locus of operating points for constant reactive power (Q). Additionally, locate the locus of operating points for unity power factor and constant power factor. ii. Modify Diagram 2 by multiplying (re-scaling) all lengths by U/Xd. The locus of P (real power) and Q (reactive power) is a circle having the form: (x-a)2+(y-b)2=r2. Determine the center of the circle (a, b) and its radius (r). iii. Finally, draw the load chart of the generator in the following steps: • Along the P axis mark the point for maximum power of the turbine, which is PTmax≈1.1 Pn • Mark the circular MVA arc corresponding to the maximum permissible armature current (Ia,max=1.2 Ia,r) • Construct the arc corresponding to maximum permissible excitation, which in this case corresponds to ε = 3.2. • Make a reasonable assumption with regard to the under-excitation limit and mark it on the diagram to complete the loading chart. 65 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 5.7 Steady-state and transient stability The following figure represents a section of a power system 380kV G 220kV G Sk“ =13.5GVA G G Generators: Transformers: Lines: Sn = 235 MVA Un = 15.75 kV Cos ϕ = 0.85lag xd = 1.88 x’d = 0.285 Tm=11.54 s Sn = 235 MVA Xb = 0.25Ω/km 410/15.75 kV (per system) xps = 1.88 l = 300km Transformers: Sn = 630MVA 400/231kV xps = 13% The initial condition is as follows: rated real power, 0.95 lagging power factor and rated voltage at the generator terminals. a. Determine the voltage phase angle difference between network voltage and the generator internal emf (power angle δ). Identify the available stability reserve. b. Derive a mathematical expression for the generator internal emf as a function of the power angle (δ), if the real power output of the generators is slowly increased from the rated value to the stability limit: i. without generator terminal voltage control ii. with the generator terminal voltage held constant c. How does the steady-state stability margin change, if, instead of the double line, one system is used to transmit the power given in part (a): i. without generator terminal voltage control ii. with the generator terminal voltage held constant ? d. Determine the transient power versus power angle characteristic of the generator! 66 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich e. Assume now that from a situation where both lines were operating in parallel, one of the lines is switched off. Using the equal area criterion, determine the maximum swing angle. f. Assuming rated initial condition, determine the critical clearing time for a three-phase fault occurring at the terminals of the generator. 67 Exercises Electric Power Systems I - III 6 UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich TRANSFORMERS 68 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.1 Transformer dimensioning A single phase transformer 50 Hz with circular core (see figure) has the following data : Primary voltage Up = 110 kV Secondary voltage Us = 10 kV Rated power Sn = 4.4 MVA Maximal core flux density B= 1.8 T Maximum current density in conductors Jmax = 4 A/mm2 Space factor of winding f= 66 % Specific resistance of copper σ= 2.14 10-8 Ω.m hw 400 30 40 50 40 The mechanical construction principle is shown in the above figure (distances in mm). a. Calculate the number of turns required on both the primary and the secondary sides. b. Calculate the cross-section of the copper wire for both the primary and the secondary windings. c. Should the inner coil (close to the core) be used for primary or secondary voltage? Why? d. Calculate the copper losses of the transformer at nominal power. e. Calculate the height hW of the windings (see figure). f. What is the per unit value of the short circuit voltage uk of this transformer ? Hint: µ0 = 4π 10-7 H/m 69 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.2 Determination of transformer equivalent circuit parameters The no-load and short-circuit tests carried out on a 15/0.4-kV, 400-kVA transformer provided the following results: Test Current Power Applied voltage Open-circuit Open-circuited/ short-circuited side low voltage side 0.2 A 19.2 W rated voltage Short-circuit high voltage side rated current 7 kW 28 V (line to line voltage) Determine: a. the parameters of the equivalent circuit referred to the high voltage side b. the parameters of the equivalent circuit referred to the low voltage side c. the efficiency of the transformer, when the transformer supplies half the rated power at a power factor of unity (cos phi =1). 70 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.3 Working in per unit quantities Generator T1 Transmission line ∼ UG: 13.2 kV 5 MVA 13.2 kV ∆/132 kV Y 10% 2+j10Ω T2 Load 10 MVA 300+j0 Ω 138 kV Y/69kV ∆ 8% Use a common base of 138 kV and 10 MVA. a. Draw the equivalent circuit and determine all impedance values in per unit b. Calculate the currents through T1, the transmission line, T2 and the load both in per unit and Amperes c. Determine the power consumed by the load both in per unit and MVA. 71 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.4 Transformers in parallel operation Two transformers (T1 and T2) with the following rated values are to be operated in parallel. Transformer Rated power voltage uK Copper loss T1 400 kVA 24/0.4 kV 6% 6720 W T2 160 kVA 24/0.4 kV 4% 1792 W a. Determine the load on each transformer (in percent of the rating of each transformer) when transformers T1 and T2 in a parallel operation jointly supply the load current IL = 600 A. b. Determine the maximum load current which does not lead to the overloading of any of the transformers c. Assume now the attached load draws power corresponding to the rated power of both transformers at a power factor of 0.85 lagging (i.e., 400 kVA + 160 kVA = 560 kVA, cos phi = 0.85 lag). i. Determine IT1 (the current through T1) and IT2 (the current through T2). ii. The solution in (i) will show that T2 is overloaded by over 30% while T1 is not yet fully loaded. Now determine the tap change (in percent) on transformer T1 which would reduce the load on T2 to its rated value (with the total load current attached to both transformers remaining unchanged). iii. What is the new load current on T1? iv. Show that the current through the external load remains at the value before the tap change. 72 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.5 Impedance transformation Three identical single-phase transformers have each the following rated values: 1.2kV/220 V, Sn=7.2 kVA, xps = 0.05 p.u., R = 0 The transformers are to be connected for three-phase operation. A symmetrical three phase load with an impedance 5 + j 0 Ω/phase is connected to the secondary terminals. Determine the total impedance referred to the primary as well as to the secondary sides both in Ohms and p. u. for the following transformer connections: a. Y-Y b. Y-∆ c. ∆-Y d. ∆-∆. 73 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.6 Equivalent circuit of three phase MV/LV transformer A 1-MVA MV/LV transformer has the following characteristic data: Primary voltage Unp = 10 kV Secondary voltage Uns = 0.4 kV Rated power SnT = 1000 kVA Short circuit voltage uk = 6% Copper losses Pk = 10 kW No load current IL= 0.7 A /10kV No load power PL= 2.3 kW Vector group Dy5 a. Sketch the connection of the windings indicating the direction of flux linkages in each winding. b. Calculate the leakage impedance and the shunt admittance referred to the primary side c. Give the per phase equivalent circuit neglecting the shunt branch d. By using the π-equivalent circuit (instead of the one obtained in (c)), the need for referring impedances to one side or the other can be obviated. Derive such a πequivalent circuit of this transformer in the following steps: i. Determine the nodal bus admittance matrix of the circuit obtained in (c) and substitute any referred quantity with its original value ii. Sketch an arbitrary π circuit with unknown parameters and formulate the general relationships for the elements of its nodal bus admittance matrix in terms of the parameters of the π circuit. iii. Solve for the parameters of the π circuit in (ii) by equating the corresponding elements of the two bus admittance matrices (obtained in (i) and (ii)). 74 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.7 Unsymmetrical load on a transformer I The following single-phase load occurs in a three-phase, 25MVA, 231/115.5, Yy0 transformer: 2.5 MVA, 110 / 3 kV, cos ϕ = 1 Star points Primary Secondary Open Solidly grounded a. Calculate the currents in the primary windings without using symmetrical components. b. Discuss the effect on the transformer of the unsymmetrical loading. c. Assume that the transformer contains an additional delta-connected tertiary winding. What are now the currents in all three sets of transformer windings? 75 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.8 Unsymmetrical load on a transformer II The following load occurs on the transformer described in exercise 6.7: Secondary load: cos ϕ = 1 Symmetrical load: 5 MVA, 110 kV, Single-phase load (in Phase a): 1 MVA, 110 kV/ 3 , cos ϕ = 1 Tertiary load Symmetrical load: 1 MVA, 10 kV, cos ϕ = 1 For the purposes of this exercise, the transformer is to be considered ideal. a. Determine the primary currents IA, IB, IC. b. Verify the results obtained in (a) using the relationship: S(PRIMARY)= S(SECONDARY)+S(TERTIARY). 76 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.9 Zero-sequence equivalent circuit of transformers The value of the zero-sequence impedance of a star-connected transformer winding is essentially determined by the connection of the star point. Derive the zero-sequence equivalent circuit of transformer windings in the following connection: a. Star, Star point open; IA0 ZP A B C b. Star, Star point solidly grounded; IA0 ZP A B C c. Star, Star point grounded through impedance Zn; IA0 ZP A B C Zn 77 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich d. Primary as in (c), secondary: delta connected. IA0 ZP A B C Zn 78 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.10 Equivalent circuit of a three winding transformer A three winding transformer used for power station supply has the following characteristic data: Primary voltage Unp = 20 kV Secondary voltage Uns = 6.3 kV Tertiary voltage Unt = 6.3 kV Primary rated power Snp = 40 MVA Secondary rated power Sns = 20 MVA Tertiary rated power Snt = 20 MVA Short circuit voltage prim.-sec. ukps= 8.7 % Short circuit voltage prim.-tertiary ukpt= 8.7 % Short circuit voltage sec.-tertiary ukst= 15 % Resistance prim.-sec. rps= 0.525 % Resistance prim.-tertiary rpt= 0.525 % Resistance sec.-tertiary rst= 0.88 % No load current IL= 4.62 A / 20kV No load losses PL = 29 kW a. Sketch the positive-sequence equivalent circuit of the transformer. b. Calculate the values of the elements of the equivalent circuit referred to the primary, secondary and tertiary voltage levels. 79 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.11 Behavior of a transformer under load A three winding transformer for power house load supply has the following characteristic data: Rated voltages Un = 231/115.5/10.5 kV Rated apparent power Sn = 140/140/42 MVA Relative losses Pv/Sn 1.1 10-2 No load current iL 1% Impedance prim.-sec. zps 13.6 % Copper losses prim.-sec. rps 0.4 % a. Sketch the equivalent circuit valid for nominal operation of the transformer with no load on the 10-kV side. b. Sketch the phasor diagram of primary voltage Up = f (cosϕ), cosϕ = 0ind ..1 .. 0cap for nominal values of voltage and current on the secondary side. c. Derive then from this curve a diagram for the relative voltage drop up – us = f (cosϕ) for cosϕ = 0ind ..1 .. 0cap d. What is the equation giving the total losses of n identical transformers operated in parallel as a function of the total current Ig ? Determine the current Iu at which switching from n to n-1 transformers should take place so that the total loss is minimized? e. The transformer under consideration is to be operated in parallel with a 250-MVA transformer having the values: Un=231/115.5kV, zps = 15.5 %, rps = 0.3%. Calculate: i. the load carried by each transformer for a total load of 390 MVA (S1n + S2n) ii. the ratio of copper loss to the rated power for each of the transformers the 80 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.12 Behavior of a three winding transformer under unsymmetrical load 231 kV 10.5 kV 115.5 kV IA a IB b IC c Ib Ic The following short circuit currents were measured during a double-phase-to-ground fault occurring on a three-phase, three winding, 231/115.5 kV /10.5 kV transformer (see figure above). For the purposes of this exercise, the transformer can be considered ideal. Sort-circuit currents Ia 0 Ib 5400 A ∠ 0° Ic 5400 A ∠ 240° Give a general expression for the short circuit currents on the 220 kV side in general as well as their concrete values both in the natural and the symmetrical components. 81 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.13 Zero-sequence network of a power system including transformers The zero-sequence network of a section of a power system is to be determined. a. Which vector groups of transformers permit the transmission of zero-sequence systems between primary and secondary sides? b. Comment whether or not this transmission of zero-sequence systems is desirable. c. Sketch the zero-sequence the equivalent circuit of the power system given in the figure below and calculate the values of the impedance elements. 4 units Sn=235 MVA Un=231/15.75 kV xps=14.5% S“k=2500 MVA Z0→∞ B Sn=235 MVA Un=15.75 kV x‘‘d=19% 15 kV 100 km t 110 kV s ~ p Z11+Z’11=j0.32 Ω/km Z00+Z’00‘=j1.12 Ω/km S“k=4500 MVA C 220kV 50 km 220kV 50 km t 4 transformers Sn=250/250/83 MVA Un=231/115.5/10.5 kV xps=15.5% xpt=14.8% xst=9% s 30 km 2 transformers t 110kV p s 380kV p D Z0=j50 Ω S“k=10 000 MVA Sn=630/630/210 MVA Un=400/231/31.5 kV xps=10.5% xpt=16.6% xst=11.3% A S“k=3000 MVA 82 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.14 Parallel operation of transformers Two transformers, Transformer 1 and Transformer 2, having the power ratings Sn1 and Sn2, respectively, are to be operated in parallel. a. If the two transformers jointly carry the load S, determine the complex power through Transformer 1 (S1) and Transformer 2 (S2) in relation to their short-circuit voltage (uk). b. Show that the two transformers share the load in an ideal manner, i.e. in the ratio S1 S n1 = , only if they have equal short circuit voltage. S 2 S n2 c. Determine the load in each of the parallel connected transformers and the circulating current, if any, occurring under each of the following conditions and decide, on the basis of the results obtained, if parallel operation is permissible or not. (In each case, assume equal R/X ratio.) i. different rated powers : Transformer 1 Dy5 S = 45 MVA uk = 10% a= 110/10 Transformer 2 Dy5 S = 35 MVA uk = 10% a= 110/10 ii. different short circuit voltages : Transformer 1 Dy5 S = 40 MVA uk = 10% a= 110/10 Transformer 2 Dy5 S = 40 MVA uk = 12% a= 110/10 iii. different transformation ratios : Transformer 1 Dy5 S = 40 MVA uk = 10% a= 110/10 Transformer 2 Dy5 S = 40 MVA uk = 10% a= 120/10 iv. different vector groups : Transformer 1 Dy5 S = 40 MVA uk = 10% a= 110/10 Transformer 2 Yy6 S = 40 MVA uk = 10% a= 110/10 83 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.15 Voltage magnitude and phase angle control of transformers Two buses of a system (Bus A and B) are connected through two parallel lines (Line 1 and 2). The lines have the following impedances: Line 1 = j 0,1 p. u.; Line 2 = j0,1 p. u. Bus B is a load bus with a load current of I = 1,0 p. u. ∠ − 30° . The voltage in bus A is so adjusted that the voltage at Bus B remains always constant at U = 1.0 p. u. ∠0° . Calculate the real and reactive power absorbed by the load and the share of Line 1 and 2: a. For the situation described. b. When a regulating transformer, installed at Bus B end of the Line 2, injects an emf with a value 0.03 p.u. c. When the transformer introduced in (c), instead of the voltage magnitude, causes the voltage phase angle to increase by 20. 84 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.16 Autotransformer A single-phase transformer has the following ratings: 30 kVA, 10,6 kV/0,4 kV. This transformer is reconnected as an autotransformer for 11 kV/10,6 kV operation. a. Sketch the connection of the windings. b. Find the rating of the transformer as an autotransformer and the currents in both windings. c. The efficiency of the transformer before the reconnection and under rated conditions at a load power factor of 1 was 97%. What is the efficiency of the transformer as an autotransofrmer? d. What would be the rating of the transformer for 11/0.4 kV-connection? e. Compare the results in (b) und (d) and deduce from this comparison the most suitable field of application for an autotransformer. f. Assume now that the polarity of the windings in the interconnection for 11 kV/10.6 kV operation was wrong (the primary and secondary windings were not connected additive cumulatively). What is the effect on the transformer of the wrong connection? 85 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.17 Transformer in open delta connection Three identical single-phase transformers, each rated 5 kVA, are connected in ∆-∆ to supply a rated load of 15 kVA at 380 V. It turned out later that the actual load on the transformer never exceeds 10 kVA and that only two of the three single-phase transformers would be enough to supply the load. Accordingly, the transformer between the phases a and c is to be removed and the transformer to be operated in open ∆. The operation of the transformer under this mode and at a load of 10 kVA and cosϕ=1 is to be investigated. a. Show that the three line-to-line voltages at the load terminal remain symmetrical in the open ∆ mode! b. Calculate the currents in the primary and secondary windings and in the input and output lines. c. What is the power transferred by each of the transformers? d. Is there any additional constraint that needs to be introduced, when a ∆-∆ connected is modified for an operation in open ∆ ? 86 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.18 Effect of primary fault on secondary voltages A symmetrical voltage source with its star point solidly grounded is to be connected to the primary side of a 10/0.4-kV, core type transformer, as shown in the figure below. The arrangement of the primary and secondary windings is also given in the figure. A a B b C c Primary Secondary a. Assuming that the primary and secondary windings are connected as follows, Connect only the middle phase (phase B) of the transformer primary winding to the corresponding phase of the voltage source. i. Determine the secondary voltages Ua, Ub and Uc and the primary voltages UA and UC on open-circuit ii. Calculate the secondary currents, if a star-connected load impedance with its star point grounded and having a value of 10+j0 Ω /phase is connected to the secondary terminals iii. Comment on the possibility of power transfer between any one phase (in this case phase B) of the primary winding that is connected to the source and the three secondary windings. 87 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich b. Assuming that the secondary winding remains connected as in (a), disconnect phase B of the primary from the source and connect phases A and C to the source. What voltages can be measured on open-circuit at the secondary terminals, if: i. The primary star point remains solidly grounded ii. The primary star point is not grounded? c. With the secondary winding connection remaining unchanged, now the connection of the primary windings is converted to delta. What secondary voltages (on open-circuit) can one measure, if on the primary side the connection linking the beginning of the coil phase A to the end of phase B is removed, as shown in the figure below? Would this transformer be able to supply a three-phase load connected to the secondary terminals? Explain. A B C 88 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.19 Transformer in „Scott“ connection Two single-phase transformers in a so-called „Scott“ connection supply a two phase load from a three-phase supply (figure below). A IA B IB N1 U2 3 N1 N2 N1 C IC Transformer 2 N2 U1 Transformer 1 Make the following assumptions: - The transformer is to be considered ideal - The supply line has a line-to-line voltage of 6 kV - N1/N2=13 a. What are the primary voltages in transformers 1 and 2? b. What are the secondary voltages U1 and U2 on no load? c. Assume now that transformer 1 supplies a 50 kVA load at a power factor of 0.8 lagging at the rated voltage. Transformer 2 is unloaded. Determine the currents IA, IB, and IC in the input line? d. With the load on transformer 1 remaining unchanged, load transformer 2 with 50 kVA at 0.8 lagging and rated voltage. Re-evaluate the currents IA, IB, and IC in the input line? 89 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 6.20 Instrument transformers (IT) The following figure shows the schematic diagram of connection for a current transformer (CT) and a potential transformer (PT), which collectively are called instrument transformers. Primary circuit A CT- connection V PT- connection a. If a CT is accidentally open-circuited, it would momentarily be destroyed, and similarly if a PT were inadvertently to be short-circuited, it would be damaged. Explain why. b. The total impedance on the CT due to lead resistance and metering load (known as “burden”) strongly affects the measurement accuracy. i. Give the equivalent circuit of the CT, neglecting the primary resistance and leakage reactance; Comment on the justification of neglecting the primary impedance. ii. Using the equivalent circuit, relate the measurement error (both magnitude and angle) to ZB (burden). iii. A CT with the ratio 250:5 A is known to have the following parameters (referred to the secondary side): Zs = 0.03 + j0.05 Ω Z’m = 7 + j10 Ω For a primary current of 150 A, determine the magnitude and angle error when the burden on the CT is: iii-1) 0.06 + j0 Ω; iii-2) 0.12 + j 0 Ω; iii-3) 3+j0 Ω c. In practical cases Zm does not remain constant as a result of iron core saturation. In this exercise the effect of the core saturation is to be considered. The following pair of 90 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich values are points taken from the magnetization characteristic of the 250:5 CT considered above. I’e/A 0 0,28 0,55 1 4 6.5 8 Es/V 0 5.7 11.3 11.4 11.45 11.5 12 For a primary current of 200 A, compute the magnitude and phase angle errors first neglecting core saturation and then considering the core saturation and compare the results obtained. Make the following assumptions: ZB = 3 + j 0 Ω; the impedance angle of Z’m is assumed to remain constant at 550. 91 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 7 POWER FLOW ANALYSIS 92 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 7.1 Power flow solution by Gauss – Seidel method a. Assume the following simultaneous equations are given: 2x + xy = 1 2y - xy = -1 Solve for x and y using: i. The Jacobi method ii. The Gauss – Seidel method iii. The Gauss – Seidel method using an acceleration factor of 1.6. b. A power flow analysis using the Gauss – Seidel method is to be carried out for the network, the one-line diagram of which is given below. All other necessary data are also given in the tables following the diagram. 1 2 3 4 Line data (Referred to the 230-kV side) From To R (Ω) X (Ω) Y/2 (mS) 1 2 5.34 26.66 0.097 1 3 3.91 19.68 0.073 2 4 3.91 19.68 0.073 3 4 6.72 33.64 0.121 93 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich Bus data Generation Bus Bus type P (MW) 1 Slack - 2 Load 3 Load 4 Voltage controlled Load Q (Mvar) - P (MW) 50 Q (Mvar) 30.99 Voltage (kV) 230 0 0 170 105.35 230 0 0 200 123.94 230 318 - 80 49.58 234.6 Var limit at bus 4: Qmin = -200 Mvar; Qmax =50 Mvar i. Assemble the nodal bus admittance matrix of the network ii. Formulate the power flow equations iii. Solve the power flow equations using the Gauss – Seidel method for the first iteration. 94 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 7.2 Power flow analysis by Newton – Raphson method a. Using the Newton – Raphson method, solve for x and y of the following nonlinear equations: F1(x, y) = 4y sin x + 0.6 = 0 F2(x, y) = 4y2 – 4y cos x + 0.3 = 0 Initial values: x(0) = 0 , y(0) = 1 b. Consider again the power system given in exercise 7.1 (b). With the objective of carrying out a power flow study using the polar form of the power flow equations, determine: i. the number of rows and columns of the Jacobi matrix ii. algorithms for the determination of the elements of the Jacobi matrix and the initial elements of the matrix iii. the initial power mismatch and give a brief outline of the solution procedure iv. the first iteration solution to the power flow problem. c. Derive the algorithm for the load flow study using the decoupled form of the Newton – Raphson method and determine the first iteration solution. d. Solve the power flow equations using the DC power flow model. 95 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 7.3 Regulating transformer and load sharing I Two transformers (Ta and Tb) are connected in parallel to supply a load of 0.8 + j 0.6 p.u. at a voltage of U2 = 1.0∠00 p.u. Transformer Ta has a voltage ratio equal to 1 p.u. on both primary and secondary sides on no load. The tap on the second transformer (Tb) is adjusted to yield a secondary voltage of 1.05 p.u. on open-circuit. Both transformers have an impedance of j0.1 p.u. a. Find the complex power transmitted to the load through each transformer using: i. the circulating current method (approximate solution) ii. the nodal bus admittance matrix (Ybus) method (exact solution) b. Repeat (a) except that Tb now includes a transformer having the same turns ratio as Ta but a regulating transformer with a phase shift of 30. c. Show how the presence of a phase-shifting transformer causes the [Ybus] of the entire network to become unsymmetrical. 96 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 7.4 Regulating transformer and load sharing II Two Transformers, Transformer a and Transformer b, having per unit reactances 0.2 and 0.4, respectively, are operated in parallel. Transformer a operates at nominal tap-setting, while the tap on transformer b can be changed under load. Assume a load connected to the secondary terminals of the parallel connected transformers draws 1.05 p.u. at a power factor of 0.707 lagging and rated voltage. Determine the primary voltage and the complex power delivered by each of the transformers, when the transformation ratio of transformer b is: a. 1 p.u. at a phase angle of zero, i.e. nominal setting b. 1.05 p.u. at a phase angle of zero c. 1.0 at a phase angle of 30 97 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 7.5 Representation of the regulating transformer in a load flow study Consider the power system considered in exercise (7.1). Assume now that a regulating transformer is inserted between bus 3 and the load, as shown in the figure below. The variable tap is on the network side of the transformer and the reactance of the transformer (referred to the 230-kV) side is 105.8 Ω. The resistance is to be neglected. A value of 1 is to be used as an initial estimate for t (t is the ratio of the actual tap-setting to the nominal tapsetting). The variable tap (t) of the transformer is to be regarded as a state variable in a load flow study using the Newton – Raphson method. The voltage magnitude at bus 5 is specified to be 225 kV a. Write the mismatch equations in a symbolic form b. Write equations for the jocabian elements of the column corresponding to variable t (the partial derivative with respect to t) and evaluate them using the initial estimates. c. Write equations for P and Q mismatches at buses 4 and 5 and evaluate them for the first iteration. 1 2 3 4 5 98 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8 SHORT CIRCUIT ANALYSIS 99 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich Summary of important short-circuit terminology: Initial short circuit current (Ik“) Short circuit capacity (Sk“) Equivalent voltage source at the fault location ( U " = c ⋅ Un 3 ) The first amplitude of the short-circuit current (ip) and the surge factor (κ) i p = κ ⋅ 2 ⋅ I "k κ = 1.02 + 0.98 ⋅ e −3 R / X DC component of the fault current (id.c.) i d.c. = 2 ⋅ I "k ⋅ e −2 π⋅f ⋅R ⋅t / X Voltage factor c; High- and medium voltage: cmax=1.1; cmin=1.0 Low voltage: cmin=0.95 cmax= 1.05; Short-circuit interrupting current (Ib) and the decay factor (µ) I b = μ ⋅ I"k Distance short circuit: μ =1 Short-circuit in the vicinity of a generator: µ = 0.84 + 0.26 ⋅ e −0.26⋅I µ = 0.71 + 0.51 ⋅ e −0.30⋅I " kG " kG / I rG for t min = 0.02s / I rG for t min = 0.05s µ = 0.62 + 0.72 ⋅ e −0.32⋅I " kG / I rG for t min = 0.10s µ = 0.56 + 0.94 ⋅ e −0.38⋅I " kG / I rG for t min ≥ 0.25s " t min = Minimum delay; I kG = Generator short circuit current; I rG = Genertator rated current Short-circuit interrupting power(Sb) Steady-state short-circuit current (Ik) Short-circuit duration (Tk) Thermal equivalent short-circuit current (Ith) and the parameters m and n m: thermal component of the dc current; f(κ, Tk) n: thermal component of the ac current; f(Ik“/Ik, Tk) I th = I "k ⋅ m + n 100 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.1 Comparison of a short circuit in R-L circuit and a generator A 50-Hz alternating voltage having an RMS value of 215 V is supplied to a series R – L circuit by closing the switch (S) in the figure below. The resistance and the inductance values are15 Ω and 0.27 H, respectively. a. Find the value of the dc component of current upon closing the switch if the instantaneous value of the voltage at switching is 100 V. b. What is the instantaneous value of the voltage, which will produce the maximum dc component of current upon closing the switch? c. What is the instantaneous value of the voltage, which will result in the absence of any dc component of current upon closing the switch? d. If the switch is closed when the instantaneous voltage is zero, find the instantaneous current 0.5, 1.5, and 5.5 cycles later. e. Neglecting any possible DC component in the short-circuit currents, how does the shortcircuit current versus time curve in an R – L circuit differ from a typical time behaviour of a current flowing when a synchronous generator is short-circuited at its terminals? How can this difference be explained? S R =15 Ω U =215V L =0.27 H 101 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.2 Symmetrical short-circuit in a generator – transformer unit A generator connected to a transformer is rated 100 MVA, 18 kV, with reactances of xd” = 19%, xd’ = 26%, and xd= 130%. A three-phase transformer rated 100 MVA, 220 Y/10.5∆ kV, xps= 10% is connected to the generator. The generator was operating at no load and rated voltage when a three-phase short circuit occurs between the transformer and its generator side breaker. Find (in kA): a. the sustained short-circuit current in the breaker, b. the transient, the sub-transient and the initial symmetrical RMS currents c. the maximum possible dc component of the short-circuit current in the breaker. If the location of the short-circuit is assumed to be the high-voltage side of the transformer, find d. the initial symmetrical RMS current in the transformer windings on the high voltage side e. the initial symmetrical RMS current in the transformer on the low voltage side f. the breaker interrupting current for a minimum time delay of 0.1 s. 102 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.3 Short-circuit current computation: internal emf method vs. equivalent voltage source method I A 50-Hz generator is rated 500 MVA, 20 kV, with xd”= 0.2 per unit. Prior to the fault the generator was supplying a purely resistive load of 400 MW at 20 kV connected directly across the terminals of the generato. If all three phases of the load are short-circuited simultaneously, find the initial symmetrical RMS current in the generator, using: a. the internal emf method b. the equivalent voltage source method (Thévenin theorem). . 103 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.4 Short-circuit current computation: internal emf method vs. equivalent voltage source method II A synchronous generator is rated 30 MVA, 13.2 kV, and has the sub-transient reactance of 20%. This generator is supplying a group of motors connected via a line having a reactance of 10% on the base of the machine ratings. The motors are drawing 20 MW at 0.8 power factor leading and a terminal voltage of 12.8 kV when a symmetrical three-phase fault occurs at the motor terminals. The equivalent sub-transient reactance of the motors is assumed to be 20 % (on the base of the generator rating). a. Find the sub-transient currents in the generator, the motor, and the fault by using the internal voltages of the machines. b. Solve this problem using the Thévenin theorem. Take the pre-fault load into consideration. How does the pre-fault load current affect the current flowing into the fault location? 104 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.5 Short-circuit in a generator connected to a group of motors I A 625-kVA generator with xd” = 0.20 per unit (base: 625 kVA, 2.4 kV) is connected to a bus through a circuit breaker, as shown in the figure below. Connected through circuit breakers to the same bus are three synchronous motors rated 187.5 kW, 2.4 kV, 1.0 power factor, 90% efficiency, with xd” = 0.2 per unit (base: 187.5 kVA, 2.4 kV). The motors are operating at full load, unity power factor and rated voltage, with the load equally divided among the machines. a. Draw the impedance diagram with the impedances in per unit on a base of 625 kVA, 2.4 kV. b. Find the symmetrical short-circuit current in amperes, which must be interrupted by breakers A and B of a three-phase fault at P. Simplify the calculations by neglecting the pre-fault current. c. Repeat part (b) for a three-phase fault at point Q. d. Repeat part (b) for a three-phase fault at point R. R A Q P B 105 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.6 Short-circuit in a generator connected to motors II A 25-MVA, 13.8-kV generator with xd” = 15% is connected through a transformer to a bus which supplies four identical motors, as shown in the figure below. The sub-transient reactance xd” of each motor is 20% on a base of 5 MVA, 6.9-kV. The three-phase rating of the transformer is 25 MVA, 13.8/6.9 kV, with a leakage reactance of 10%. The bus voltage of the motor is 6.9 kV when a three-phase fault occurs at point P. Determine a. the sub-transient current in the fault, b. the sub-transient current in breaker A. P A 106 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.7 Symmetrical short-circuit current computation 110kV G1 T3 220kV 220kV T6 110kV T1 T4 T5 T2 G2 T7 Q 2X240/40-Al/St T9 G9 T8 50km, double line SS2 SS3 240/40-Al/St 50km, double line SS1 SS4 Data of the network components: Xb’=0.298 Ω/km (220-kV overhead line; for the bundle in each system) Xb’=0.393 Ω/km (110-kV overhead line; for each system) Overhead line 220 kV: R/X = 0.26 Overhead line 110 kV: R/X = 0.3 G1, G2: 10.5 kV; 100 MVA; xd“ =0.16; RsG/Xd“=0.05; G9: 21 kV; 225 MVA; xd“ =0.19; RsG/Xd“=0.05; T1, T2: 120 MVA; uk =10%; ür=115 kV/10.5 kV T3 …T8: 200 MVA; uk =12%; ür=240 kV/110 kV T9: 250 MVA; uk =10%; ür=112 kV/21 kV; R/X = 0.03 Q: SkQ“=20 GVA a. Calculate the initial short-circuit current (Ik“) fort the fault location shown (SS4). b. Compute the first amplitude of the fault current. c. Calculate the fault interrupting current for the maximum interrupting time delay tv = 0.25 s d. Calculate the maximum dc component of the short-circuit current e. Estimate the significance of considering the resistive components of all impedances. 107 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.8 Mechanical and thermal stress caused by the short-circuit current 21 kV G 110 kV T G: UrG = 21 kV; SrG = 225 MVA; xd“ = 0.18; xd = 2; R/X= 0.05 T: SrT = 250 MVA; uk = 10% The generator is connected to the transformer through rectangular-shaped aluminium (Al) bars. The expected load current necessitates the use of three Al bars, each with the dimension 200 mm X 15 mm. All the bars are arranged in a horizontal plane, with the centre-to-centre distance between the phases (the main distance) am = 350 mm and the distance between the conductors within each phase (sub distance) as =15 mm. The following schematic shows the bars for one of the three phases. 1m Side view a. Which type of fault causes the maximum mechanical stress on the Al-bars? b. Determine the combined force exerted on the bars of the middle phase by the fault currents flowing in the other two phases for the fault location on the generator side terminals of the transformer (shown above). Identify the appropriate curve from the family of curves given in Figure 1 and then obtain the correction factors for each of the mutual distances appearing in your formula. (Correction factors are needed to determine the effective distance when conductors having a large dimension are used.) c. Additionally, what is the force exerted on the outer bar of the middle phase due to the currents flowing in the other bars of the same phase? d. Neglecting the phase difference between the forces obtained under (b) and (c), calculate the total force exerted on the mounting during the short-circuit. Is the force vertically or horizontally directed? 108 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich e. Determine whether or not the Al bars are capable of withstanding the thermal stress due to the short-circuit current, if the generator protection clears the fault 0.2 s after the onset of the fault. (In accordance with DIN VDE 0102, the sustained short-circuit current (Ik) for this system is assumed to be 176% of the rated generator current. (The bars are designed for a short-circuit current density (Sthr) of 87 A/mm2, which leads to a temperature rise from the operating temperature of 650C to the maximum permissible short-circuit temperature of 2000C within 1 s). Use Figures 1 and 2 to determine the factors m and n. 109 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich k1j kij Figure 1: Correction factor for main distance (am) and sub distance (as) 110 Exercises Electric Power Systems I - III Figure 2 UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich Tk.f Parameter: I“k/Ik I“k/Ik = 1 n Tk Figure 3 f.Tk 111 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.9 Calculation of short circuit currents in a meshed network A short-circuit analysis is to be carried out for the network given below F1 G1 G2 F2 ~ L1 ~ 110 kV T1 T3 T4 T2 F3 A B L3 30 kV kV L4 T5 T6 F4 10 kV kV L2 F5 M 112 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich Data: S”k = 4000 MVA G1, G2: 31.5 MVA, 6.3 kV, x”d = 0.12 T1, T2 : 31.5 MVA, 31.5/6.3 kV, xps = 0.12 T3, T4: 31.5 MVA, 110/31.5 kV, xps = 0.12 T5, T6: 16 MVA, 31.5/10.5 kV, xps = 0.11 M : 12 MW, 10kV, cos ϕ =0.8, x’M = 0.3 L1 : X’b = 0.4 Ω/km, 15 km L2 : X’b = 0.4 Ω/km, 2.5 km Calculate the initial symmetrical short circuit current I”k for the fault locations F1 ... F5, and identify the contributions by the generator (I”kG), the grid (I”kN) and the motors (I”kM). All reactances should be referred to the 110-kV level. The currents should also be given in their original voltage level. For fault locations F1 and F2, the motors can be neglected. Additionally neglect the impedances of cables L3 and L4 in all cases. 113 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.10 Short Circuit Current Limitation a. List and discuss the available options for short circuit current limitation. b. Discuss the effectiveness of the two alternatives measures for reducing short-circuit currents given below. For fault location F1 and F2 the contribution of the motors towards the fault current can be neglected: ◊ Measure 1: Coupling between SS A and B open. ◊ Measure 2: Use of inductances for short circuit current limitation with parallel Is (surge current)-limiter between transformer T3 and bus bar A, as well as T4 and SS B respectively, with bus bar coupling between SS A and B closed. Rated data of short circuit current limitation inductances : xD=10%, Un=30kV In=630 A 114 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.11 Analysis of unsymmetrical faults A synchronous machine is connected through a three-phase transformer and transmission line to a large system, as shown in the Figure 1 below: G1 T1 1 3 2 Sk“= 10 GVA X0→ ∞ Xn Fig. 1. Network Ratings and parameters of the synchronous machine, the transformer and the line are as follows: Generator G1: 100 MVA, 13.8 kV; Xd” = X1 = X2 = 0.19 Ω, X0 = 0.067 Ω, Xn = 0.095 Ω Transformer T1: 100 MVA, 13.8 kV ∆/380 kV Y; Xps = 115.5 Ω (referred to the 380-kV side) Transmission line: 100 MVA, 380 kV X1 = X2 = 21.66 Ω ; X0 = 72.2 Ω F F A B A B C C IA IB IC IA IB IC E E a) Symmetrical fault b) Single line to ground (SLG) fault F F A B A B C C IA IB IC IA IB IC E c) Double line to ground (DLG) fault E d) Double line (DL) fault Fig. 2. Fault types 115 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich For various fault locations, the fault current and the voltages at the lines not directly affected by the fault are to be computed. The fault types to be considered are shown in the Fig. 2 (fault types (a) – (d).) and the pre-fault current is to be neglected in all cases. a. Formulate the fault conditions for all four fault types. b. Transform the fault conditions (formulated in (a)) into symmetrical components, and then deduce from the result the interconnection of the sequence networks for each fault type. c. For a bolted (Zf = 0) single line-to-ground fault occurring on phase A at bus 3, determine the following: i. the sub-transient current to ground at the fault location ii. the line-to-ground voltages at the fault location as well as at the terminals of the generator iii. the sub-transient current out of phase c of the generator. d. Instead of the fault described in part (c), assume now a bolted line-to-line fault at bus 3 between phases B and C. Determine the fault current at the fault location and the currents in the lines affected by the fault at the fault location and the line-to-line voltages at the fault bus. e. Find the sub-transient fault currents and the line-to-line voltages at the fault when a double line-to-ground fault with Zf = 0 occurs at the terminals of the generator (bus 1). 116 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.12 Effect of transformer neutral point connection on system performance during fault The following 220/380 kV system is given: 4 units Sn=235 MVA Un=231/15.75 kV xps=14.5% Sk‘‘=2500 MVA Z0→∞ B Sn=235 MVA Un=15.75 kV x‘‘d=19% 15 kV 100 km t 110 kV s ~ p Z11’+Z11’=j0.32 Ω/km Z00’+Z00’=j1.12 Ω/km S‘‘k=4500 MVA 220kV 50 km C 50 km 220kV t 4 transformers Sn=250/250/83 MVA Un=231/115.5/10.5 kV xps=15.5% xpt=14.8% xst=9% s 30 km Z11 = j0.16 Ω/km Z00 = j0.56 Ω/km t p 2 transformers Data same as station B 110kV s 380kV p D Z0=j50 Ω S‘‘k=10 000 MVA full transformer or auto-transformer Sn=630/630/210 MVA Un=400/231/31.5 kV xps=10.5% xpt=16.6% xst=11.3% A S‘‘k=3000 MVA Initially, the transformer in substation D is assumed to be an auto-transformer, with the star point being solidly grounded. For a fault at the 220-kV bus bars of substation A (as indicated in the diagram), calculate: a. the initial single-phase (I‘‘k(1)) and three-phase (I‘‘k(3)) short-circuit currents b. the earth-fault factor cf c. the conductor-to-ground voltages of the unaffected phases during a single phase-toground fault using the earth-fault factor (cf) for each of the following three alternatives: i. for the given case (i.e. star points of all transformers on the 220-kV side including the star point of the auto-transformer in substation D solidly grounded) ii. with the star point of the auto-transformer in substation D remaining grounded, only one of the 220-kV star points in each of the substations A, B, and C grounded 117 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich iii. as in (ii), but the transformer in substation D is now a full transformer and only the star point on the 220-kV side is solidly grounded (the 380-kV winding is also star connected and the star point is isolated) d. the neutral point to ground voltage (UEM) of the isolated transformers in substations A, B, and C for the scenario described under alternative c (iii) above. 118 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.13 Neutral point grounding in medium voltage networks 110 kV S“k=2500 MVA t p 20 kV s 20-kV Network 100-km Overhead line 30-km Radial field cable →XN=0.176 Ω ZME xps=1.26Ω xpt=1.8Ω xst=0.51Ω (Referred to the 20-kV side) IC=0.02 A/km (Overhead line) IC=1.47 A/km (Cable) (IC=charging current) A 20-kV distribution network is being supplied by a 110-kV network via a 40-MVA transformer. The transformer reactance and the charging currents in the distribution network (referred to the 20-kV side) are given in the figure above. The positive and negative sequence reactances of the 20-kV are can be neglected against the much larger transformer reactance. a. For a single line-to-ground fault at the 20-kV bus, draw the sequence networks! Place the total capacitance (C00→CE) of the distribution network at the 20-kV bus. b. Assuming the neutral point of the transformer on the 20-kV side is isolated (ZME→∞), determine the single line-to-ground fault current (I‘‘k(1)). (Use as a voltage source: Upa1 = UNn/ 3 ) c. Assuming now resonant grounding (instead of isolated neutral point) for the transformer: i. Determine the reactance of the grounding coil (Petersen coil) for resonance tuning ii. Draw the zero-sequence network assuming a damping factor of 4% and a detuning (off-resonance factor) of -3%. Neglect the line reactance. iii. Neglecting the positive, negative and zero-sequence reactance of the transformer, calculate the single line-to-ground fault current (I“k(1)) for the damping and offresonance factors given under (ii) above. d. Assume now that the resonant grounding is replaced by an impedance grounding. 119 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich i. Determine the value of the grounding reactance, if the single line-to-ground fault current (I“k(1)) is not to exceed 1000 A. Use a source voltage of (Upa1 = 1.05 UNn/ 3 ) and neglect the effects of the zero-sequence capacitance and damping resistance. ii. Estimate the influence of the zero-sequence capacitance on the fault current. e. The 20-kV winding of the transformer is now assumed to be solidly grounded (ZME=0). i. Determine the fault current neglecting the zero-sequence line capacitance and damping. ii. How would the zero-sequence capacitance affect the result obtained in (i)?. (The source voltage (Upa1) is now assumed to be = 1.1 UNn/ 3 .) f. Discuss briefly the results obtained in (a) – (e) in relation to the magnitude of the fault current and identify the grounding option, which is best suited for this network. 120 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.14 Problem of voltage un-symmetry in three phase transmission systems For a 110-kV overhead transmission line, the effect of varying shunt admittance in each phase of the line on the voltage symmetry is to be investigated. a. The shunt elements of the line (line capacitance and conductance) are assumed to have the following relationship: G aE = G bE = G cE C aE + ∆C = C bE = C cE Derive an expression, which relates the capacitive un-symmetry to the neutral point to ground voltage (UEM) of the line. For which value of v (off-resonance factor) is the voltage un-symmetry maximum? b. Re-work part (a), when the shunt elements have the following relationship: G aE + ∆G = G bE = G cE C aE = C bE = C cE c. Repeat part(a) for the case, where all the three capacitances are different from one another, i.e. G aE = G bE = G cE C aE ≠ C bE ≠ C cE → C aE = C aE C bE = C aE + ∆C bE C cE = C aE + ∆C cE d. The following values are obtained from a control measurement on the transmission line: UEM (at v=0) = 11.6 kV∠2450 ICE = 395 A d (damping coefficient)= 2.5% Determine the capacitances CaE, CbE and CcE. 121 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.15 Low impedance grounding in cable networks The following cable loop represents part of a metropolitan distribution network. 110 kV t p A20-1 s B1 3 km ZME C1 4 km 2 km D1 20 kV S“k 3km 3 km p s 3 km CB B2 A20-2 t C2 D2 CB: Circuit Breaker Parameters of the transformers: Cable parameters (for all sections): Un = 110/20 kV Sn = 40 MVA Xps = 1.26 Ω Xpt = 1.8 Ω Xst = 0.51 Ω (All reactance referred to the 20-kV side) Zb=0.15+j0.1 Ω/km Z0=0.1+j0.64 Ω/km (Return current flows through cable screen and earth.) Further, the following data/assumptions are given: ◊ The total line-to-earth capacitance of the 20-kV network in the zero-sequence network is to be placed at the 20-kV bus, and to be calculated from the capacitive earth leakage current (ICE), which has the following values: ICE = 51A in bus A20-1 or A20-2 ICE = 85A in A20-1 with the circuit breaker to the left of bus B2 open (needed for exercise part (b)) ◊ Neglect the line capacitance in the positive and negative sequence networks ◊ Use a source voltage of Upa1 = 1.05 ⋅ UNn 3 during fault. ◊ The equivalent impedance of the 110-kV network is 0.176 Ω (referred to 20-kV side). a. For a single line-to-ground fault in bus A, calculate the fault current I“k(1) for both resistance grounding (RME =12 Ω) as well as reactance grounding (XME =12 Ω) for the following alternative scenarios: 122 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich i. The coupling switch in bus bar A open, switch at bus D open, the switch connecting the groundings of the two transformers open ii. The coupling switch in bus bar A open, switch at bus D open, the switch connecting the groundings of the two transformers closed iii. The coupling switch in bus A closed, switch at bus D open, grounding not connected to one another b. A single line-to-ground fault is now assumed to occur in B2. The following additional information is given: bus bar coupling in A open, transformer groundings not connected to one another, switch at bus D closed, circuit breaker (to the left of B2) open. Calculate the single line-to-ground fault current for both resistance grounding (RME = 12 Ω) and reactance grounding (XME = 12 Ω). c. Discuss the results obtained in (a) and (b) with regard to: i. The effectiveness of the grounding ii. The effect of the cable impedance on the fault current iii. The effect of the line capacitance on the fault current iv. Fault current in relation to grounding impedances, RME and XME. 123 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.16 Transient stability analysis I An elementary principle of dynamics states that: J⋅ d 2 δm dt 2 = Ta (1) where: J = the total moment of inertia of the rotating masses in kg.m2 δm = the angular displacement of the rotor with respect to a stationary axis in mechanical radians Ta = the net accelerating torque in N.m. On the basis of (1) and neglecting the damping torque, derive the swing equation (2), which describes the behaviour a synchronous generator subjected to a disturbance. d 2δ dt 2 = π⋅ f ⋅ ( p m − pe ) H (2) where: δ = the angular displacement of the rotor (in electrical radians) with respect to a reference frame rotating at synchronous speed H = the inertia constant in seconds pm = shaft mechanical power in per unit pe = electrical output power in per unit 124 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.17 Transient stability analysis II a. A generator in a thermal power plant has the following values: Pn = 150 MW, cos ϕn= 0.85, Un = 15 kV, n = 1500 rpm, J =75 ·103 kgm2 (the total moment of inertia of the rotating masses). Calculate: i. the stored kinetic energy of the rotating masses at nominal speed ii. the inertia constant H (in seconds) iii. the inertia constant M (in joule-seconds/mechanical radian). b. A generator with the rating of 100 MVA has an inertia constant H = 8.0 s. i. What is the stored kinetic energy of the rotating masses when the generator runs at synchronous speed? ii. At what speed would a 40-tonne lorry need to travel in order for the lorry to have this amount of kinetic energy? iii. What should the total mass of a train travelling at 100 km/h be to have the same kinetic energy? c. A 4-pole, 100-MVA, 11-kV, 50-Hz generator has an inertia constant of 8.0 s. i. What angular acceleration does the rotor experience, if the mechanical power input increases in a step from the initial value of 50 MW to 80 MW? ii. What values would the rotor angle and rotor speed assume if this acceleration were to be maintained constant at this value for 10 cycles? d. A 50-Hz generator in a power system supplies 1 p.u. power into an infinite bus via transformers and transmission lines. A fault in one of the transmission lines reduces the maximum transferable power from the pre-fault value of 2.0 p.u. to 0.5 p.u. If the maximum transferable power upon clearance of the fault is 1.5 p.u, what is the critical fault clearing angle? 125 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.18 Transient stability analysis III a. Assuming a pre-fault generator load of 1 p.u, calculate the critical fault clearing angle for a solid three-phase fault occurring at point P in the system given below. The fault is cleared by disconnecting the faulted line in both ends. j0.15 j0.15 j0.1 j0.15 j0.28 UN=1.0 j0.15 ∼ E=1.2 j0.15 j0.14 j0.14 Infinite bus j0.15 b. A solid three- phase fault is assumed to occur at point P in the system given below. All the necessary data are given in the figure and the system frequency is 50 Hz. The fault is cleared by disconnecting the faulted line in both ends. What are the critical fault clearing angle and critical fault clearing time for a pre-fault generator load of 1 p.u. j0.15 j0.1 UN=1.0 j0.5 j0.05 ∼ E =1.2 p.u H=4s j0.4 P Infinite bus c. The generator in the figure below has an inertia constant H = 4 s and feeds 1 p.u. power into the infinite bus. Further data for the system are: UN = Ut = 1.0 p.u., xd’ = 0.25 p.u., xt = 0.10 p.u., xl = 0.5 p.u., f = 50 Hz. xd’ xt xl UN ∼ Up’ Ut xl Infinite bus i. What is the value of the emf (Up’) behind the transient reactance? ii. Calculate the maximum power that can be transmitted if: − the topology of the system is as shown in the figure. − When one of the lines experiences a three-phase fault midway along the line. i. What is the accelerating power immediately after the fault described in (ii)? ii. What is the value of the rotor angle if the acceleration is maintained constant at the value calculated in (iii) for 0.05 s? iii. What is the accelerating power at the rotor angle calculated in (iv)? iv. Discuss the difference between the values obtained in (iii) and (v)! 126 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich 8.19 Transient stability analysis IV The following single-line diagram shows a generator connected through two parallel transmission lines to a large metropolitan system considered as an infinite bus. All relevant constants and parameters of the system are given in the single-line diagram and in the table following it, and resistances are to be neglected in all cases. G 1 T1 3 2 T2 Infinite bus H=5s H→∞ Equipment Generator Transformers (T1 and T2) Lines Positive and negative sequence reactance 0.12 0.10 (each) Zero sequence reactance 0.05 0.10 (each) 0.2 (each) 0.5 (each) Prior to the fault, the machine was delivering 1.4 per unit power, with both the generator terminal voltage and the infinite bus voltage maintained at 1.0 per unit. a. Symmetrical fault A symmetrical fault is assumed to occur at the sending-end terminal of one of the lines, as shown in the single-line diagram. The fault is cleared 0.25 s after its inception by simultaneously opening the circuit breakers at both ends of the faulted line. Subsequently, a successful re-closure takes place after a further 0.5 s, which restores the system to its original configuration. Using the equal area criterion, determine whether or not the generator remains in synchronism. b. Double line-to-ground fault Starting from the same pre-fault condition as (a) a double line-to-ground fault occurs at the same location described in (a). Find the equation relating the electrical output power to the power angle (P vs. δ curve) and show that, for this particular fault, the generator would not lose synchronism, even if the fault were not to be cleared. Determine the maximum angle, which the generator will reach, in the process of swinging subsequent to this fault. Hint: for numerical integration of the swing equation, use the following algorithm: 127 Exercises Electric Power Systems I - III UNIVERSITÄT DUISBURG - ESSEN FG Elektrische Anlagen und Netze Univ. Prof. Dr.-Ing. habil. I. Erlich δn = δn −1 + ∆δn (in electrical radians ) ∆δ n = ∆δ n −1 + k ⋅ Pa,n −1 k= π⋅f (∆t )2 H Pa, n = Pm, n − Pel, n (where pa = accelerating power; pm = input mechanical power; pel = output electrical power) 128