Masterclad™ 5–15 kV Arc Resistant Metal-Clad Indoor Switchgear Installation 6055-62 06/2012 ENGLISH Inspecting the Fuses Open the VT drawout compartment door to visually inspect fuses for possible damage. Replace the fuses if necessary. See “Replacing the Fuses” starting on page 38. Racking the VT Drawout Unit into the CONNECTED Position After inspecting the VT drawout unit, follow the steps below to rack it to the CONNECTED position. 1. Close the VT drawout unit compartment door. 2. Insert the racking handle into the racking port and engage the handle onto the racking shaft. 3. Rotate the racking handle clockwise until VT drawout unit is fully racked to the CONNECTED position. NOTE: If the voltage transformer drawout unit does not easily rack into the CONNECTED position, rack the unit to the DISCONNECT position, and remove any objects or debris from the compartment. Repeat this process. If results are not satisfactory, contact Schneider Electric. Voltage Transformer Drawer Figure 26 shows the voltage transformer (VT) drawer connected to the load bus. Figure 26: VT Drawer Compartment Main Bus Compartment VT Compartment Circuit Breaker Compartment 30 Cable Compartment © 2009–2012 Schneider Electric All Rights Reserved