4/30/2015 Composite Regulating Characteristic of Power Systems • In the analysis of load-frequency controls (LFCs), we are interested in the collective performance of all generators in the system. • The inter-machine oscillations and transmission system performance are therefore not considered. • We tacitly assume the coherent response of all generators to changes in system load and represent them by the equivalent generator. • The equivalent generator has an inertia constant Meq equal to the sum of the inertia constants of all the generating units and is driven by the combined mechanical outputs of the individual turbines. • The composite power/frequency characteristic of a power system depends on the combined effect of the droops of all generator speed governors. • It is also depends on the frequency characteristic of all the loads in the system. • For a system with n generators and a composite loaddamping constant of D, the steady state frequency deviation following a load change is given by, • The effect of governor speed droop and frequency sensitivity of load on the net frequency change are illustrated below. System equivalent for LFC analysis • where • Thus, the composite frequency characteristic of the system is • Normally expressed in MW/Hz. • Sometimes referred to as the stiffness of the system • The composite regulating characteristic of the system is equal to -: Example 2 :Two generators rated 200 MW and 400 MW are operating in a parallel. The droop characteristics of their governors are 4% and 5%, respectively. From no load to full load. Assuming that the generators are operating at 50 Hz at no load, • How would a load of 600 MW be shared between them ? • What will be the system frequency at this load ? Composite governor and load characteristic 1