Concrete Flag Pavements Design and Construction Guide Concrete Masonry Walling Single-Leaf Masonry Design Manual Concrete Masonry Association of Australia Queensland Promotions Committee Single-Leaf Masonry Design Manual Click on this heading to return to ‘Contents’ CONTENTS Click on subject to go to it 1 INTRODUCTION 2 1.1 General 2 1.2 Application of Designs 2 1.3 Material Properties 3 1.4 Earthquake Loading 3 1.5 Typical Details 3 2 SIMPLIFIED DESIGN OF EXTERNAL WALLS 3 TABULAR DESIGN OF EXTERNAL WALLS 11 4 BRACING DESIGN 17 5 6 7 5 4.1 Method 17 4.2 Racking Forces 17 4.3 Bracing Wall Location 20 4.4 Bracing Wall Capacities 21 CONNECTION DETAILS 23 5.1 Truss Tie Down 23 5.2 Fixing to Gable Ends 25 5.3 Timber Floor Fixing 25 BASEMENT WALLS 26 6.1 General 26 6.2 Drainage 26 6.3 Tanking 27 WATERPROOFING RECOMMENDATIONS FOR HOUSING 28 7.1 Joint Finishing 28 7.2 Weatherproofing Application 28 7.3 Window Installation 28 Prepared by: Ron Marshall Consulting Pty Ltd Disclaimer: The Concrete Masonry Association of Australia Limited is a non-profit organisation sponsored by the concrete masonry industry in Australia to provide information on the many uses of concrete masonry products. Since the information provided is intended for general guidance only and in no way replaces the service of professional consultants on particular projects, no liability can be accepted by the Association for its use. Industry Support. Most of the manufacturers of quality concrete masonry products in Australia are members of the Concrete Masonry Association of Australia (CMAA). It is recommended that advice be obtained from local CMAA members to adapt or supplement information contained in this Guide. Remember, when working with cement and concrete/mortar or manufactured or prefabricated concrete products, ALWAYS follow the manufacturer's instructions and seek advice about working safely with the products from the manufacturer, your nearest WorkCover Authority or Worksafe Australia. 1 Single-Leaf Masonry Design Manual 1 Introduction 1.1 General NOTE: Lintels are always designed to span the full opening width. ■ Bond beams are provided at intermediate floor and roof levels. The floor and ceiling systems are connected to the bond beams and act as diaphragms to transfer the racking forces horizontally to bracing walls. Cathedral ceilings with a slope exceeding 35° and unlined ceilings do not act as a diaphragm unless wind bracing is provided. ■ Uplift forces on the roof are resisted by connecting the roof to bond beams and lintels with connections designed to carry the uplift forces. The bond beams span between vertical reinforcement that transfers the uplift to the foundations. A typical bond beam/lintel layout is shown in Figure 1.1. ■ The amount of load applied to the top of the wall is determined by the width of roof it supports. This width (called Dimension “A”) is determined in accordance with Figure 1.2. This design manual has been prepared for the Concrete Masonry Association of Australia, Queensland Promotions Committee for use by building designers. The information is intended primarily for single-leaf concrete masonry houses, but the tables are applicable to other buildings. Designs for single-leaf buildings in this manual have been provided on two levels. The first level is simplified diagrams that are suitable for most houses or for initial designs. Where the house is more complex or it is required to fine-tune the design, then the Tabular Design is provided. 1.2 Application of Designs The design details in this manual are applicable to buildings complying with the following: ■ The size of the building complies with the geometric limitations given in Australian Standard AS 4055–1992 Wind loads for housing, except the floor-to-ceiling height, may go to 3.0 m with the appropriate increase in applied forces. ■ The footings are in accordance with Local Authority requirements with starter bars cast in and lapping with all vertical reinforcement in the walls. ■ Grouted reinforced cores provide the bending strength to resist the wind pressure on the external walls by spanning vertically between floors or a floor and a roof. Vertical wall reinforcement is anchored into bond beams. Figure 1.1 shows a typical layout of wall reinforcement ■ 'A1' Load and tie-down point '1' Figure 1.2 'A2' 'A3' Load and tie-down point '3' Load and tie-down point '2' Determination of Dimension “A” Wind loads on openings are transferred to the side of the opening or to a central frame or mullions in the opening. Where there is no central frame or mullion, such as a roller door or similar, the effective “opening width” for wall design will be the full opening size. Where there is central frames or mullions, the “opening width” for wall design is the width of the panel adjacent to the edge of the opening. Lintel reinforcement Bond beam reinforcement Opening Lintel reinforcement Window Opening Pier between openings Bar at corners Figure 1.1 Reinforced cores at sides of all openings Vertical bars in grouted cores spaced along wall Typical Wall and Reinforcement Layout 2 One-course bond beam under all windows Single-Leaf Masonry Design Manual 1.3 Material Properties 1.4 The design tables in this Manual are based on materials with the following properties: ■ Characteristic Unconfined Compressive Strength of concrete masonry units, f’uc = 15 MPa ■ Characteristic Compressive Strength of grout, f’c = 20 MPa ■ Yield Strength of reinforcement, f’sy = 500 MPa ■ Mortar Type, M3 140 or 190 1-N16 bar 1.5 60 to bar bottom Minimum 1-N12 bar Knock-out bond beam block Typical Details Typical details for various components are shown in Figures 1.3 to 1.7. Where an N16 bar is required in the details, 2-N12 bars may be used as an alternative. 140 or 190 60 to bar bottom Earthquake Loading Buildings designed for wind loading N2 and greater will satisfy Earthquake Design Categories H1 and H2, applicable in Queensland. 260 to bar bottom Minimum 1-N12 bar Knock-out bond beam blocks Standard blocks 140 or 190 Minimum 1-N12 bar Knock-out block 460 to bar bottom Standard block Minimum 1-N12 bar Knock-out block Standard blocks TYPE 1 Figure 1.3 60 to bar bottom Standard blocks TYPE 2 TYPE 3 Typical Details for Bond Beams Supporting a Roof Wall vertical reinforcement above floor level Wall vertical reinforcement above floor level Starter-bars at same size and location as wall vertical reinforcement, lapped 450 min. Vertical wall reinforcement above floor level, lapped 450 min. with reinforcement from below Wall vertical reinforcement from below floor level bent into top face of floor slab 1-N12 bar 1-N12 bar 1-course bond beam using knock-out block 1-course bond beam using knock-out block Block saw-cut at floor soffit level CONCRETE FLOOR Figure 1.4 Bearer bolted to bond beam TIMBER FLOOR Typical Details for Bond Beams Supporting a Floor Wall vertical reinforcement Starter-bars at same size and location as wall vertical reinforcement, lapped 450 min. Floor slab reinforcement Wall vertical reinforcement Wall vertical reinforcement Starter-bars at same size and location as wall vertical reinforcement, lapped 450 min. Floor slab reinforcement L6 ties at 600 centres Integral footing Strip footing Starter-bars at same size and location as wall vertical reinforcement, lapped 450 min. Floor slab reinforcement Knock-out block with inside face removed L8 or N10 ties at 600 centres Strip footing Figure 1.5 Typical Details of Connections to Footings 3 Single-Leaf Masonry Design Manual Top reinforcement carried beyond the support 140* or 190 Bottom reinforcement carried beyond the support 60 to bar bottom 1-N12, N16 or N20 bar 3/4 lintel block* L8 fitments at 150 crs with N16 & N20 bars 290 L8 fitments at 150 crs for full width of opening with N16 & N20 bars 1-N12, N16 or N20 bar Top reinforcement carried beyond the support 290 * for 140-mm-thick walls, use 15.02 block cut on site and turned on end Cut out end and web NOTE: For required bar size, see Tables 3.5, 3.6 and 3.7 TYPE A – TYPICAL ELEVATION 215 to bar bottom 290 15.02 block TYPE A – SECTION 140 or 190 Bottom reinforcement carried beyond the support 60 to bar bottom 1-N12, N16 or N20 bar 390 L8 fitments at 200 crs for full width of opening with N16 & N20 bars L8 fitments at 200 crs with N16 & N20 bars Knock-out block 1-N12, N16 or N20 bar Lintel block 260 to bar bottom 390 NOTE: For required bar size, see Tables 3.5, 3.6 and 3.7 TYPE B – SECTION TYPE B – TYPICAL ELEVATION Top reinforcement carried beyond the support 140 or 190 Bottom reinforcement carried beyond the support 60 to bar bottom 1-N12, N16 or N20 bar Knock-out block 590 L8 fitments at 200 crs with N16 & N20 bars L8 fitments at 200 crs for full width of opening with N16 & N20 bars Standard block 1-N12, N16 or N20 bar Lintel block NOTE: For required bar size, see Tables 3.5, 3.6 and 3.7 TYPE C – SECTION TYPE C – TYPICAL ELEVATION Figure 1.6 Typical Details for Lintels Supporting a Roof 140 or 190 1-N16 bar or 1-N20 bar Knock-out block Lintel block L8 fitments at 200 crs 1-N16 bar or 1-N20 bar 140 or 190 60 to bar bottom 315 to bar bottom 1-N16 bar or 1-N20 bar Knock-out block 390 Standard block L8 fitments at 200 crs NOTE: For required bar size, see Table 3.8 Figure 1.7 515 to bar bottom Lintel block 1-N16 bar or 1-N20 bar TYPE BB – TYPICAL SECTION 60 to bar bottom NOTE: For required bar size, see Table 3.8 TYPE CC – TYPICAL SECTION Details of Lintels Supporting Timber Floors 4 590 460 to bar bottom 590 Single-Leaf Masonry Design Manual 2 Table 2.1 Simplified Design of External Walls For earthquake classifications H1, H2 and H3, the details given for wind category N2 are suitable. The lintel details are only suitable for standard roof truss loading. Where there is either floor loadings or girder-truss loadings, use lintel design tables (Tables 3.8 and 3.9) in Chapter 3 of this manual. Where the building geometry is other than shown, design should be in accordance with Chapter 3. 1-N16 L8 fitments at 150 crs Leaf thickness (mm) Wind Classification Wall height (mm) Page number 2.1 2.2 2.3 140 140 140 N1, N2 & N3 N1, N2 & N3 N1, N2 & N3 2400 2500 2700 5 5 6 2.4 2.5 140 140 N4 & C1 N4 & C1 2400 2700 6 7 2.6 2.7 140 140 N5 & C2 N5 & C2 2500 2700 7 7 2.8 2.9 2.10 190 190 190 N1, N2 & N3 N1, N2 & N3 N1, N2 & N3 2400 2500 2700 8 8 9 2.11 2.12 190 190 N4 & C1 N4 & C1 2400 2700 9 10 2.13 2.14 190 190 N5 & C2 N5 & C2 2500 2700 10 10 Figure number External wall reinforcement may be detailed using Figures 2.1 to 2.14 for the wind classification and dimensional limitations as noted on the drawings and summarised in Table 2.1. Summary of Design Parameters L8 fitments at 150 crs 300 1-N16 1-N16 300 1-N16 2400 1-N12 1-N12 at edge of opening 1-N12 at corners 600 Figure 2.1 2400 2-N12 in 400 x 150 pier 400 1-N12 at edge of opening 1-N12 at 2000 crs in wall NOTE: Drawing not to scale 2400 1-N12 at edge of all openings 2400 maximum Wall Reinforcement for 140-mm Leaf for Wind Classifications N1, N2 and N3 and 2400-mm Wall Height 1-N16 L8 fitments at 200 crs L8 fitments at 200 crs 400 1-N16 1-N16 400 1-N16 2500 1-N12 1-N12 at edge of opening 1-N12 at corners 600 Figure 2.2 2400 2-N12 in 400 x 150 pier 400 1-N12 at edge of opening 1-N12 at 2000 crs in wall NOTE: Drawing not to scale 2400 1-N12 at edge of all openings 3000 maximum Wall Reinforcement for 140-mm Leaf for Wind Classifications N1, N2 and N3 and 2500-mm Wall Height 5 Single-Leaf Masonry Design Manual 1-N12 1-N12 1-N16 600 1-N12 600 1-N12 2700 1-N12 1-N12 at edge of opening 1-N12 at corners 600 2400 2-N12 in 400 x 150 pier 400 1-N12 at 2000 crs in wall 1-N12 at edge of opening NOTE: Drawing not to scale 2400 1-N12 at edge of all openings 3000 maximum DOUBLE GARAGE WITH PIER 1-N16 L8 fitments at 200 crs 1-N16 600 1-N12 600 1-N12 1-N20 2700 1-N12 1-N12 at edge of opening 1-N12 at corners 600 1-N12 at edge of opening 1-N12 at 2000 crs in wall NOTE: Drawing not to scale 5400 1-N12 at edge of all openings 3000 maximum DOUBLE GARAGE WITHOUT PIER Figure 2.3 Wall Reinforcement for 140-mm Leaf for Wind Classifications N1, N2 and N3 and 2700-mm Wall Height 1-N16 L8 fitments at 150 crs 1-N16 300 L8 fitments at 150 crs 1-N16 300 1-N16 1-N16 1-N16 2400 1-N12 1-N12 (if near corner) 1-N12 at corners 600 Figure 2.4 2400 2-N12 in 400 x 150 pier 400 2-N12 at openings ≤ 2.4 m 1-N12 at 1800 crs in wall NOTE: Drawing not to scale 2400 1-N12 for openings ≤ 1.2 m, 2-N12 for > 1.2 m ≤ 2.4 m 2400 maximum Wall Reinforcement for 140-mm Leaf for Wind Classifications N4 and C1 and 2400-mm Wall Height 6 Single-Leaf Masonry Design Manual 1-N20 L8 fitments at 200 crs 600 1-N20 1-N12 1-N12 1-N12 1-N12 600 2700 1-N12 1-N12 (if near corner) 1-N12 at corners 600 Figure 2.5 3-N12 at edge of opening 1-N12 at 1400 crs in wall NOTE: Drawing not to scale 5400 1-N12 for openings ≤ 1.2 m, 2-N12 for > 1.2 m ≤ 3.0 m 3000 maximum Wall Reinforcement for 140-mm Leaf for Wind Classifications N4 and C1 and 2700-mm Wall Height 1-N16 L8 fitments at 200 crs 1-N16 400 L8 fitments at 200 crs 1-N16 400 1-N16 1-N16 1-N16 2500 600 x 300 T-pier 1-N12 1-N16 in stem of pier 1-N12 (if near corner) 1-N12 at corners 600 Figure 2.6 2400 2-N12 in face of pier 600 2-N12 at edge of opening 1-N12 at 1200 crs in wall NOTE: Drawing not to scale 2400 2-N12 at edges of openings 2400 maximum Wall Reinforcement for 140-mm Leaf for Wind Classifications N5 and C2 and 2500-mm Wall Height 1-N12 1-N12 1-N12 600 1-N12 1-N12 600 1-N12 2700 600 x 300 T-pier 1-N12 1-N16 in stem of pier 1-N12 (if near corner) 1-N12 at corners 600 Figure 2.7 2400 2-N12 in face of pier 600 3-N12 at openings ≤ 2.4 m 1-N12 at 1000 crs in wall NOTE: Drawing not to scale 2400 2-N12 for openings ≤ 1.8 m, 3-N12 for > 1.8 m ≤ 2.4 m 2400 maximum Wall Reinforcement for 140-mm Leaf for Wind Classifications N5 and C2 and 2700-mm Wall Height 7 Single-Leaf Masonry Design Manual 1-N16 L8 fitments at 150 crs L8 fitments at 150 crs 300 1-N16 300 1-N16 1-N16 2400 1-N12 1-N12 at edge of opening 1-N12 at corners 600 Figure 2.8 2400 2-N12 in 400 x 200 pier 400 1-N12 at edge of opening 1-N12 at 2000 crs in wall NOTE: Drawing not to scale 2400 1-N12 at edge of all openings 2400 maximum Wall Reinforcement for 190-mm Leaf for Wind Categories N1, N2 and N3 and 2400-mm Wall Height 1-N12 1-N16 400 L8 fitments at 200 crs 1-N16 400 1-N12 1-N16 2500 1-N12 1-N12 at edge of opening 1-N12 at corners 600 Figure 2.9 2400 2-N12 in 400 x 200 pier 400 1-N12 at edge of opening 1-N12 at 2000 crs in wall NOTE: Drawing not to scale 2400 1-N12 at edge of all openings 3000 maximum Wall Reinforcement for 190-mm Leaf for Wind Categories N1, N2 and N3 and 2500-mm Wall Height 8 Single-Leaf Masonry Design Manual 1-N12 1-N12 600 1-N12 600 1-N12 2700 1-N12 1-N12 at edge of opening 1-N12 at corners 600 2400 2-N12 in 400 x 200 pier 400 1-N12 at edge of opening 1-N12 at 2000 crs in wall NOTE: Drawing not to scale 2400 1-N12 at edges of openings 3000 maximum DOUBLE GARAGE WITH PIER 1-N16 L8 fitments at 200 crs 1-N12 600 600 1-N12 1-N20 2700 1-N12 1-N12 (if near corner) 1-N12 at corners 600 2-N12 at edge of opening 1-N12 at 2000 crs in wall NOTE: Drawing not to scale 5400 1-N12 at edges of openings 3000 maximum DOUBLE GARAGE WITHOUT PIER Figure 2.10 Wall Reinforcement for 190-mm Leaf for Wind Classifications N1, N2 and N3 and 2700-mm Wall Height 1-N16 L8 fitments at 150 crs 1-N16 300 L8 fitments at 150 crs 1-N16 300 1-N16 1-N16 1-N16 2400 1-N12 1-N12 (if near corner) 1-N12 at corners 600 Figure 2.11 2400 2-N12 in 400 x 200 pier 400 1-N12 at 1800 crs in wall 1-N12 at edges of openings NOTE: Drawing not to scale 3000 maximum 1-N12 at edge of opening 2400 Wall Reinforcement for 190-mm Leaf for Wind Classifications N4 and C1 and 2400-mm Wall Height 9 Single-Leaf Masonry Design Manual 1-N20 L8 fitments at 200 crs 600 1-N20 1-N12 1-N12 1-N12 1-N12 600 2700 1-N12 1-N12 (if near corner) 1-N12 at corners 600 Figure 2.12 2-N12 at edge of opening 1-N12 at 1800 crs in wall NOTE: Drawing not to scale 5400 1-N12 for openings ≤ 1.8 m, 2-N12 for > 1.8 m ≤ 3.0 m 3000 maximum Wall Reinforcement for 190-mm Leaf for Wind Classifications N4 and C1 and 2700-mm Wall Height 1-N16 L8 fitments at 200 crs 1-N16 400 L8 fitments at 200 crs 1-N16 400 1-N16 1-N16 1-N16 2500 1-N12 1-N12 (if near corner) 1-N12 at corners 600 Figure 2.13 2400 2-N12 in 600 x 200 pier 600 2-N12 at openings ≤ 2.4 m 1-N12 at 1600 crs in wall NOTE: Drawing not to scale 2400 1-N12 for openings ≤ 1.2 m, 2-N12 for > 1.2 m ≤ 2.4 m 2400 maximum Wall Reinforcement for 190-mm Leaf for Wind Classifications N5 and C2 and 2500-mm Wall Height 1-N12 600 1-N12 1-N12 1-N12 1-N12 1-N12 600 2700 1-N12 1-N12 (if near corner) 1-N12 at corners 600 Figure 2.14 2400 2-N12 in 600 x 200 pier 600 2-N12 at openings ≤ 2.4 m 1-N12 at 1400 crs in wall NOTE: Drawing not to scale 2400 1-N12 for openings ≤ 1.2 m, 2-N12 for > 1.2 m ≤ 2.4 m 2400 maximum Wall Reinforcement for 190-mm Leaf for Wind Classifications N5 and C2 and 2700-mm Wall Height 10 Single-Leaf Masonry Design Manual 3 Tabular Design of External Walls The member sizes, reinforcement and general detailing can be determined from the Figures and Tables referred to in the following steps: Step 1 1.1 Size and Distribution of Vertical Reinforcement Maximum reinforcement spacing along walls DETAILING DESIGN COMMENTARY Table 3.1 (page 12) Table 3.1 (page 12) The amount of wall supported by a reinforced core is half the distance to the adjacent reinforced cores. The distance to the next rod can be determined by adding it to the distance from the previous rod, then checking that the sum does not exceed the maximum allowable given in Table 3.1. Note the spacing between rods can be different. 1.2 Reinforcement in piers between openings DETAILING DESIGN COMMENTARY Table 3.2 (page 12) Table 3.2 (page 12) Where there is a pier between two openings, determine the size and reinforcement required in the pier by adding the opening widths together and referring to Table 3.2. 1.3 Reinforcement beside openings DETAILING DESIGN COMMENTARY Table 3.3 (page 13) Table 3.3 (page 13) The maximum opening size depends on the wind area and the reinforcement beside the opening. Use Table 3.3 to determine the reinforcement size and details. 1.4 Maximum reinforcement spacing adjacent to openings DETAILING DESIGN COMMENTARY Table 3.4 (page 13) Table 3.4 (page 13) The maximum distance to the first rod from the side of an opening depends on the opening size and the reinforcement at the edge of the opening. Use Table 3.4 to determine to determine spacing. 1.5 Reinforcement at girder trusses DETAILING DESIGN COMMENTARY – – Place a vertical bar within 100 mm of all girder trusses. Step 2 2.1 Reinforcement and Details of Lintels Lintels supporting roofs DETAILING DESIGN COMMENTARY Figure 1.6 (page 4) Table 3.5 (page 14) Table 3.6 (page 15) Table 3.7 (page 16) For standard trusses, the maximum amount of roof that can be carried is given in Table 3.5 (metal roofs} and Table 3.6 (tile roofs). Where possible, girder trusses landing on a lintel should be avoided, even over small openings, and not permitted over long openings. Where girder trusses landing on lintels cannot be avoided, Table 3.7 gives the maximum area of roof, including any standard trusses, that can be carried by the lintel. 2.2 Lintels supporting floors DETAILING DESIGN COMMENTARY Figure 3.1 (page 16) Table 3.8 (page 16) The maximum amount of supported floor width to be carried by a lintel is given in Table 3.8. Step 3 3.1 Reinforcement and Details of Bond Beams Bond beams supporting roofs DETAILING DESIGN COMMENTARY Figure 1.3 (page 3) Table 3.9 (page 16) Roof bond beam acting vertically transfers uplift forces from the roof trusses to the vertical reinforcement. The minimum number of courses in a bond beam supporting a roof depends on the wind area and the span of the roof trusses. For standard roof trusses see Table 3.9. If a girder truss lands on the bond beam, a tie-down rod must be placed within 100 mm of the truss. 3.2 Bond beams supporting floors DETAILING DESIGN COMMENTARY Figure 1.4 (page 3) Use 1-N12 bar Bond Beams supporting floors need only to provide positive attachment for the floor. Normally one course deep with 1-N12 bar will be sufficient. 11 Single-Leaf Masonry Design Manual Table 3.1 Selection and Detailing of Maximum Reinforcement Spacing Along Walls Maximum sum of adjacent bar spacing, s1 + s2 (m) Wall details 140 or 190 1-N12 bar in grouted core 1-N12 bar in grouted core s1 190 s2 1-N16 bar in grouted core 1-N16 bar in grouted core s1 Table 3.2 1-N12 bar in grouted core 1-N16 bar in grouted core s2 Wind Class. 140-mm-leaf wall Wall height (m) 2.4 2.7 3.0 3.3 3.6 190-mm-leaf wall Wall height (m) 2.4 2.7 3.0 3.3 3.6 N2 N3 N4 N5 N6 4.0 4.0 3.7 2.6 – 4.0 4.0 2.9 2.0 – 4.0 3.5 2.4 1.6 – 4.0 2.9 2.0 – – 3.8 2.4 1.6 – – 4.0 4.0 4.0 3.6 2.7 4.0 4.0 4.0 2.9 2.1 4.0 4.0 3.3 2.3 1.7 4.0 4.0 2.8 1.9 – 4.0 3.4 2.3 1.6 – C1 C2 C3 C4 4.0 2.7 1.9 – 3.2 2.2 – – 2.6 1.7 – – 2.1 – – – 1.8 – – – 4.0 3.9 2.7 2.0 4.0 3.0 2.1 1.6 3.7 2.5 1.7 – 3.0 2.0 – – 2.5 1.7 – – N2 N3 N4 N5 N6 – – – – – – – – – – – – – – – – – – – – – – – – – 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 3.7 4.0 4.0 4.0 4.0 3.0 4.0 4.0 4.0 3.3 2.5 4.0 3.4 4.0 2.8 2.1 C1 C2 C3 C4 – – – – – – – – – – – – – – – – – – – – 4.0 4.0 4.0 3.4 4.0 4.0 3.7 2.7 4.0 4.0 3.0 2.2 4.0 3.6 2.5 1.8 4.0 3.0 2.1 1.5 Selection and Detailing of Pier Reinforcement Wind Class. Maximum allowable sum of openings, w1 + w2 (m) 140-mm-leaf wall 190-mm-leaf wall Wall height (m) Wall height (m) 2.4 2.7 3.0 3.3 3.6 2.4 2.7 3.0 3.3 3.6 1-N12 bar in grouted core N2 N3 N4 N5 N6 5.2 3.2 2.0 – – 4.0 2.5 – – – 3.2 1.9 – – – 2.6 – – – – 2.1 – – – – 9.9 6.3 4.1 2.7 1.9 7.7 4.9 3.1 2.1 – 6.2 3.9 2.5 – – 5.0 3.1 2.0 – – 4.2 2.6 – – – w2 C1 C2 C3 C4 2.3 – – – – – – – – – – – – – – – – – – – 4.5 2.9 1.9 – 3.5 2.2 – – 2.8 – – – 2.2 – – – 1.8 – – – N2 N3 N4 N5 N6 10.8 6.8 4.4 2.9 1.9 8.5 5.3 3.3 2.1 – 6.7 4.2 2.6 – – 5.5 3.3 2.0 – – 4.5 2.7 – – – 10.8 10.8 8.4 5.7 4.0 10.8 10.0 6.5 4.4 3.0 10.8 8.0 5.2 3.4 2.4 10.4 6.5 4.2 2.7 1.8 8.6 5.4 3.4 2.2 – C1 C2 C3 C4 4.9 3.1 2.0 – 3.7 2.3 – – 2.9 1.8 – – 2.3 – – – 1.8 – – – 9.4 6.1 4.0 2.8 7.3 4.7 3.1 2.1 5.8 3.6 2.4 – 4.7 2.9 1.9 – 3.8 2.4 – – N2 N3 N4 N5 N6 10.8 10.8 10.8 10.8 – 10.8 10.8 10.8 10.8 – 10.8 10.8 10.8 8.9 – 10.8 10.8 10.7 7.3 – 10.8 10.8 8.9 6.0 – 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 9.2 C1 C2 C3 C4 10.8 10.8 10.4 – 10.8 10.8 8.1 – 10.8 9.6 6.4 – 10.8 7.8 5.2 – 9.9 6.4 4.3 – 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 9.9 10.8 10.8 10.8 8.0 10.8 10.8 9.3 6.7 Pier details 140 or 190 w1 190 2-N12 bars in grouted cores 140 or 190 w1 390 w2 190 Medium-duty ties at 400 crs 1-N16 bar 290 140 2-N12 bars w1 140-mm-LEAF WALL 590 w2 190 Medium-duty ties at 400 crs 1-N16 bar 390 190 2-N12 bars w1 590 w2 190-mm-LEAF WALL 12 Single-Leaf Masonry Design Manual Table 3.3 Selection and Detailing of Reinforcement Beside Openings Maximum allowable opening size, w1 (m) Opening details 1-N12 bar in grouted core 140 or 190 1-N12 bar in grouted core w1 2-N12 bars in grouted cores 140 or 190 2-N12 bars in grouted cores w1 2-N16 bars in grouted cores 190 2-N16 bars in grouted cores w1 Table 3.4 Wind Class. 140-mm-leaf wall Wall height (m) 2.4 2.7 3.0 3.3 3.6 190-mm-leaf wall Wall height (m) 2.4 2.7 3.0 3.3 3.6 N2 N3 N4 N5 N6 5.4 4.6 2.9 1.9 – 5.4 3.5 2.2 1.3 – 4.6 2.8 1.7 1.0 – 3.7 2.2 1.3 – – 3.0 1.7 1.0 – – 5.4 5.4 4.5 2.9 2.0 5.4 5.3 3.4 2.2 1.4 5.4 4.2 2.6 1.7 1.1 5.4 3.4 2.1 1.3 – 4.6 2.7 1.7 1.0 – C1 C2 C3 C4 3.3 2.0 1.2 – 2.5 1.5 – – 1.9 1.1 – – 1.5 – – – 1.1 – – – 5.0 3.2 2.0 1.3 3.8 2.4 1.5 0.9 3.0 1.8 1.1 – 2.4 1.4 – – 1.9 1.1 – – N2 N3 N4 N5 N6 5.4 5.4 5.4 3.7 – 5.4 5.4 4.3 2.7 – 5.4 5.4 3.3 2.0 – 5.4 4.3 2.6 1.5 – 5.4 3.5 2.0 1.1 – 5.4 5.4 5.4 5.4 4.0 5.4 5.4 5.4 4.4 3.0 5.4 5.4 5.3 3.4 2.2 5.4 5.4 4.2 2.6 1.6 5.4 5.4 3.4 2.0 1.2 C1 C2 C3 C4 5.4 4.0 2.5 – 4.9 3.0 1.8 – 3.8 2.2 1.2 – 2.9 1.7 – – 2.3 1.2 – – 5.4 5.4 4.1 2.7 5.4 4.7 3.0 1.9 5.4 3.7 2.2 1.4 4.7 2.8 1.7 1.0 3.8 2.2 1.2 – N2 N3 N4 N5 N6 – – – – – – – – – – – – – – – – – – – – – – – – – 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 5.4 5.4 5.4 4.9 3.3 5.4 5.4 5.4 3.9 2.6 C1 C2 C3 C4 – – – – – – – – – – – – – – – – – – – – 5.4 5.4 5.4 5.0 5.4 5.4 5.4 3.8 5.4 5.4 4.2 2.9 5.4 5.2 3.3 2.2 5.4 4.2 2.6 1.7 Selection and Detailing of Maximum Reinforcement Spacing Adjacent to Openings Maximum adjacent bar spacing plus opening, s1 + w1(m) Wall and opening details 140 or 190 1-N12 bar in grouted core s1 140 or 190 1-N12 bar in grouted core s1 190 1-N16 bar in grouted core s1 1-N12 bar in grouted core w1 2-N12 bars in grouted cores w1 2-N16 bars in grouted cores w1 Wind Class. 140-mm-leaf wall Wall height (m) 2.4 2.7 3.0 3.3 3.6 190-mm-leaf wall Wall height (m) 2.4 2.7 3.0 3.3 3.6 N2 N3 N4 N5 N6 7.4 5.0 3.3 2.3 – 6.2 3.9 2.6 1.7 – 5.0 3.2 2.1 1.4 – 4.1 2.6 1.7 – – 3.4 2.1 1.4 – – 7.4 7.3 4.9 3.3 2.4 7.4 5.7 3.8 2.6 1.8 7.2 4.6 3.0 2.1 1.5 5.9 3.8 2.5 1.7 – 5.0 3.1 2.1 1.4 – C1 C2 C3 C4 3.7 2.4 1.2 – 2.9 1.9 – – 2.3 1.5 – – 1.9 – – – 1.5 – – – 5.4 3.6 2.4 1.7 4.2 2.8 1.9 1.3 3.4 2.2 1.5 – 2.8 1.8 – – 2.3 1.5 – – N2 N3 N4 N5 N6 7.4 7.4 6.2 4.1 – 7.4 7.4 4.7 3.1 – 7.4 5.8 3.7 2.4 – 7.4 4.7 3.0 1.9 – 6.3 3.9 2.4 1.5 – 7.4 7.4 7.4 6.2 4.4 7.4 7.4 7.4 4.8 3.4 7.4 7.4 5.7 3.8 2.6 7.4 7.1 4.6 3.0 2.0 7.4 5.9 3.8 2.4 1.6 C1 C2 C3 C4 6.9 4.4 2.9 – 5.3 3.4 2.2 – 4.2 2.6 1.6 – 3.3 2.1 – – 2.7 1.6 – – 7.4 6.7 4.5 3.1 7.4 5.1 3.4 2.3 6.3 4.1 2.6 1.8 5.1 3.2 2.1 1.4 4.2 2.6 1.6 – N2 N3 N4 N5 N6 – – – – – – – – – – – – – – – – – – – – – – – – – 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 5.8 7.4 7.4 7.4 6.5 4.6 7.4 7.4 7.4 5.3 3.7 7.4 7.4 6.5 4.3 3.0 C1 C2 C3 C4 – – – – – – – – – – – – – – – – – – – – 7.4 7.4 7.4 5.4 7.4 7.4 5.9 4.2 7.4 7.0 4.6 3.3 7.4 5.6 3.7 2.6 6.8 4.6 3.0 2.1 13 Single-Leaf Masonry Design Manual Table 3.5 Selection of Lintels Supporting Standard Trusses with Metal Roofing Material Maximum allowable value of dimension ‘A’ (m) 140-mm-wide lintels 190-mm-wide lintels (1) Wind Opening Type A with: class. (m) N12 N16 N20 Type B(1) with: N12 N16 N20 Type C(1) with: N12 N16 N20 Type A(1) with: N12 N16 N20 Type B(1) with: N12 N16 N20 Type C(1) with: N12 N16 N20 N1 and N2 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 9.0 9.0 8.5 6.3 5.0 – – – – 9.0 9.0 9.0 9.0 8.5 – – – – 9.0 9.0 9.0 9.0 8.5 – – – – 9.0 9.0 9.0 7.7 6.1 4.2 2.7 – – 9.0 9.0 9.0 9.0 9.0 8.3 5.6 – – 9.0 9.0 9.0 9.0 9.0 9.0 6.3 – – 9.0 9.0 9.0 9.0 9.0 8.4 5.5 3.7 2.5 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.5 6.4 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 7.9 5.0 – – – – 9.0 9.0 9.0 9.0 9.0 – – – – 9.0 9.0 9.0 9.0 9.0 – – – – 9.0 9.0 9.0 9.0 6.1 3.7 2.1 – – 9.0 9.0 9.0 9.0 9.0 8.2 5.4 – – 9.0 9.0 9.0 9.0 9.0 9.0 8.5 – – 9.0 9.0 9.0 9.0 9.0 7.6 4.7 2.9 1.6 9.0 9.0 9.0 9.0 9.0 9.0 9.0 7.8 5.7 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 N3 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 9.0 8.2 6.6 5.3 4.5 – – – – 9.0 9.0 9.0 9.0 8.3 – – – – 9.0 9.0 9.0 9.0 8.3 – – – – 9.0 9.0 9.0 7.7 6.1 4.2 2.7 – – 9.0 9.0 9.0 9.0 9.0 8.3 5.6 – – 9.0 9.0 9.0 9.0 9.0 9.0 6.3 – – 9.0 9.0 9.0 9.0 9.0 8.4 5.5 3.7 2.5 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.5 6.4 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.7 6.9 5.0 – – – – 9.0 9.0 9.0 9.0 9.0 – – – – 9.0 9.0 9.0 9.0 9.0 – – – – 9.0 9.0 9.0 9.0 6.1 3.7 2.1 – – 9.0 9.0 9.0 9.0 9.0 8.2 5.4 – – 9.0 9.0 9.0 9.0 9.0 9.0 8.5 – – 9.0 9.0 9.0 9.0 9.0 7.6 4.7 2.9 1.6 9.0 9.0 9.0 9.0 9.0 9.0 9.0 7.8 5.7 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 N4 and C1 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 7.4 5.7 4.6 3.6 3.1 – – – – 9.0 9.0 9.0 8.0 5.7 – – – – 9.0 9.0 9.0 8.0 5.7 – – – – 9.0 9.0 6.7 5.3 4.5 3.9 2.7 – – 9.0 9.0 9.0 9.0 8.8 6.6 5.0 – – 9.0 9.0 9.0 9.0 9.0 8.6 6.3 – – 9.0 9.0 9.0 8.4 7.8 6.6 5.1 3.7 2.5 9.0 9.0 9.0 9.0 9.0 9.0 8.3 6.7 5.7 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.1 9.0 7.5 6.0 4.8 3.9 – – – – 9.0 9.0 9.0 8.7 6.3 – – – – 9.0 9.0 9.0 9.0 7.8 – – – – 9.0 9.0 9.0 7.7 5.6 3.7 2.1 – – 9.0 9.0 9.0 9.0 8.3 7.0 5.3 – – 9.0 9.0 9.0 9.0 9.0 9.0 7.5 – – 9.0 9.0 9.0 9.0 8.2 7.0 4.7 2.9 1.6 9.0 9.0 9.0 9.0 9.0 9.0 8.7 7.1 6.1 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.7 N5 and C2 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 4.3 3.4 2.7 2.1 1.8 – – – – 9.0 9.0 8.1 4.7 3.4 – – – – 9.0 9.0 8.1 4.7 3.4 – – – – 6.7 5.3 3.9 3.1 2.6 2.3 2.0 – – 9.0 9.0 9.0 7.3 5.2 3.9 2.9 – – 9.0 9.0 9.0 9.0 6.8 5.0 3.8 – – 9.0 9.0 7.2 5.5 4.6 3.9 3.0 2.5 2.1 9.0 9.0 9.0 9.0 8.7 6.5 4.9 4.0 3.4 9.0 9.0 9.0 9.0 9.0 9.0 7.1 5.7 4.8 5.7 4.4 3.5 2.8 2.3 – – – – 9.0 9.0 8.7 5.1 3.7 – – – – 9.0 9.0 9.0 6.4 4.6 – – – – 9.0 7.0 5.2 4.1 3.3 2.5 2.0 – – 9.0 9.0 9.0 7.0 5.5 4.1 3.1 – – 9.0 9.0 9.0 9.0 7.9 5.9 4.4 – – 9.0 9.0 9.0 7.4 5.4 4.1 3.2 2.6 1.6 9.0 9.0 9.0 9.0 9.0 6.8 5.1 4.2 3.6 9.0 9.0 9.0 9.0 9.0 9.0 7.5 6.0 5.1 N6 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 4.1 3.2 2.5 2.0 1.6 – – – – 9.0 9.0 6.3 3.7 2.7 – – – – 9.0 9.0 7.9 4.6 3.3 – – – – 6.3 5.1 3.8 3.0 2.4 1.8 1.4 – – 9.0 9.0 9.0 5.5 3.9 3.0 2.3 – – 9.0 9.0 9.0 8.0 5.7 4.3 3.2 – – 9.0 9.0 6.9 5.3 3.9 3.0 2.3 1.9 1.6 9.0 9.0 9.0 9.0 6.5 4.9 3.7 3.0 2.6 9.0 9.0 9.0 9.0 9.0 7.2 5.4 4.4 3.7 C3 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 3.8 2.9 2.3 1.9 1.5 – – – – 9.0 9.0 5.8 3.4 2.4 – – – – 9.0 9.0 7.3 4.2 3.0 – – – – 5.8 4.7 3.5 2.7 2.2 1.7 1.3 – – 9.0 9.0 8.7 5.1 3.6 2.7 2.1 – – 9.0 9.0 9.0 7.4 5.3 3.9 2.9 – – 9.0 9.0 6.4 4.9 3.6 2.7 2.1 1.8 1.5 9.0 9.0 9.0 8.4 6.0 4.5 3.4 2.8 2.4 9.0 9.0 9.0 9.0 8.9 6.6 5.0 4.0 3.4 C4 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 2.7 2.1 1.7 1.4 1.2 – – – – 9.0 7.1 4.2 2.5 1.8 – – – – 9.0 9.0 5.3 3.1 2.2 – – – – 4.3 3.4 2.5 2.0 1.6 1.2 1.0 – – 9.0 9.0 6.3 3.7 2.7 2.0 1.5 – – 9.0 9.0 9.0 5.4 3.8 2.9 2.1 – – 8.8 7.4 4.6 3.6 2.6 2.0 1.5 1.3 1.1 9.0 9.0 9.0 6.1 4.4 3.3 2.5 2.0 1.7 9.0 9.0 9.0 9.0 6.5 4.8 3.6 2.9 2.5 'A1' Lintel '1' 'A2' Lintel '2' Standard truss with metal roofing (1) See Figure 1.6 (page 4) for details 14 Single-Leaf Masonry Design Manual Table 3.6 Selection of Lintels Supporting Standard Trusses with Tile Roofing Material Maximum allowable value of dimension ‘A’ (m) 140-mm-wide lintels 190-mm-wide lintels (1) Wind Opening Type A with: class. (m) N12 N16 N20 Type B(1) with: N12 N16 N20 Type C(1) with: N12 N16 N20 Type A(1) with: N12 N16 N20 Type B(1) with: N12 N16 N20 Type C(1) with: N12 N16 N20 N1 and N2 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 9.0 7.0 4.9 3.7 2.9 – – – – 9.0 9.0 9.0 7.4 4.9 – – – – 9.0 9.0 9.0 7.4 4.9 – – – – 9.0 9.0 6.2 4.5 3.6 2.5 1.5 – – 9.0 9.0 9.0 9.0 7.0 4.8 3.3 – – 9.0 9.0 9.0 9.0 7.7 5.3 3.7 – – 9.0 9.0 9.0 9.0 7.2 4.9 3.2 2.2 1.5 9.0 9.0 9.0 9.0 9.0 9.0 6.7 5.0 3.8 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.1 6.4 9.0 9.0 6.4 4.6 2.9 – – – – 9.0 9.0 9.0 8.5 5.6 – – – – 9.0 9.0 9.0 9.0 6.7 – – – – 9.0 9.0 8.0 5.7 3.5 2.2 1.2 – – 9.0 9.0 9.0 9.0 7.1 4.8 3.1 – – 9.0 9.0 9.0 9.0 9.0 7.3 5.0 – – 9.0 9.0 9.0 9.0 6.9 4.4 2.7 1.7 0.9 9.0 9.0 9.0 9.0 9.0 9.0 6.4 4.6 3.3 9.0 9.0 9.0 9.0 9.0 9.0 9.0 7.9 6.1 N3 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 9.0 7.0 4.9 3.7 2.9 – – – – 9.0 9.0 9.0 7.4 4.9 – – – – 9.0 9.0 9.0 7.4 4.9 – – – – 9.0 9.0 6.2 4.5 3.6 2.5 1.5 – – 9.0 9.0 9.0 9.0 7.0 4.8 3.3 – – 9.0 9.0 9.0 9.0 7.7 5.3 3.7 – – 9.0 9.0 9.0 9.0 7.2 4.9 3.2 2.2 1.5 9.0 9.0 9.0 9.0 9.0 9.0 6.7 5.0 3.8 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.1 6.4 9.0 9.0 6.4 4.6 2.9 – – – – 9.0 9.0 9.0 8.5 5.6 – – – – 9.0 9.0 9.0 9.0 6.7 – – – – 9.0 9.0 8.0 5.7 3.5 2.2 1.2 – – 9.0 9.0 9.0 9.0 7.1 4.8 3.1 – – 9.0 9.0 9.0 9.0 9.0 7.3 5.0 – – 9.0 9.0 9.0 9.0 6.9 4.4 2.7 1.7 0.9 9.0 9.0 9.0 9.0 9.0 9.0 6.4 4.6 3.3 9.0 9.0 9.0 9.0 9.0 9.0 9.0 7.9 6.1 N4 and C1 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 8.2 6.4 4.9 3.7 2.9 – – – – 9.0 9.0 9.0 7.4 4.9 – – – – 9.0 9.0 9.0 7.4 4.9 – – – – 9.0 9.0 6.2 4.5 3.6 2.5 1.5 – – 9.0 9.0 8.2 6.5 5.5 4.7 3.3 – – 9.0 9.0 9.0 9.0 7.7 5.3 3.7 – – 9.0 9.0 9.0 9.0 7.2 4.9 3.2 2.2 1.5 9.0 9.0 9.0 9.0 9.0 9.0 6.7 5.0 3.8 9.0 9.0 9.0 9.0 9.0 9.0 9.0 8.1 6.4 9.0 8.3 6.4 4.6 2.9 – – – – 9.0 9.0 9.0 8.5 5.6 – – – – 9.0 9.0 9.0 9.0 6.7 – – – – 9.0 9.0 8.0 5.7 3.5 2.2 1.2 – – 9.0 9.0 9.0 9.0 7.1 4.8 3.1 – – 9.0 9.0 9.0 9.0 9.0 7.3 5.0 – – 9.0 9.0 9.0 9.0 6.9 4.4 2.7 1.7 0.9 9.0 9.0 9.0 9.0 9.0 9.0 6.4 4.6 3.3 9.0 9.0 9.0 9.0 9.0 9.0 9.0 7.9 6.1 N5 and C2 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 4.9 3.8 3.1 2.4 2.1 – – – – 9.0 9.0 9.0 5.3 3.8 – – – – 9.0 9.0 9.0 5.3 3.8 – – – – 7.6 6.1 4.5 3.5 3.0 2.5 1.5 – – 9.0 9.0 9.0 8.3 5.9 4.4 3.3 – – 9.0 9.0 9.0 9.0 7.7 5.3 3.7 – – 9.0 9.0 8.2 6.3 5.2 4.4 3.2 2.2 1.5 9.0 9.0 9.0 9.0 9.0 7.4 5.6 4.5 3.8 9.0 9.0 9.0 9.0 9.0 8.0 6.0 4.9 4.1 6.4 5.0 4.0 3.2 2.6 – – – – 9.0 9.0 9.0 5.8 4.2 – – – – 9.0 9.0 9.0 7.3 5.2 – – – – 9.0 8.0 5.9 4.7 3.5 2.2 1.2 – – 9.0 9.0 9.0 8.7 6.2 4.8 3.1 – – 9.0 9.0 9.0 9.0 9.0 6.7 5.0 – – 9.0 9.0 9.0 8.4 6.1 4.4 2.7 1.7 0.9 9.0 9.0 9.0 9.0 9.0 7.7 5.9 4.6 3.3 9.0 9.0 9.0 9.0 9.0 9.0 8.5 6.9 5.8 N6 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 4.5 3.5 2.8 2.2 1.9 – – – – 9.0 9.0 6.9 4.0 2.9 – – – – 9.0 9.0 8.7 5.0 3.6 – – – – 7.0 5.6 4.1 3.3 2.6 2.0 1.2 – – 9.0 9.0 9.0 6.0 4.3 3.3 2.5 – – 9.0 9.0 9.0 8.2 6.3 4.7 3.5 – – 9.0 9.0 7.6 5.8 4.3 3.3 2.5 1.7 0.9 9.0 9.0 9.0 9.0 7.2 5.4 4.1 3.3 2.8 9.0 9.0 9.0 9.0 9.0 7.9 5.9 4.8 4.0 C3 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 4.1 3.2 2.5 2.0 1.7 – – – – 9.0 7.6 6.0 3.7 2.7 – – – – 9.0 8.0 6.3 4.6 3.3 – – – – 6.4 5.1 3.8 3.0 2.4 1.8 1.2 – – 9.0 9.0 9.0 5.5 4.0 3.0 2.3 – – 9.0 9.0 9.0 7.5 5.7 4.3 3.2 – – 9.0 9.0 6.9 5.3 3.9 3.0 2.3 1.7 0.9 9.0 9.0 9.0 9.0 6.6 4.9 3.7 3.0 2.6 9.0 9.0 9.0 9.0 9.0 7.2 5.4 4.4 3.7 C4 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 2.9 2.3 1.8 1.4 1.2 – – – – 7.0 5.4 4.3 2.6 1.9 – – – – 7.3 5.7 4.5 3.3 2.4 – – – – 4.5 3.6 2.7 2.1 1.7 1.3 1.0 – – 9.0 9.0 6.7 3.9 2.8 2.1 1.6 – – 9.0 9.0 6.9 5.4 4.1 3.0 2.3 – – 9.0 7.9 4.9 3.8 2.8 2.1 1.6 1.4 0.9 9.0 9.0 9.0 6.5 4.7 3.5 2.7 2.2 1.9 9.0 9.0 9.0 9.0 6.9 5.2 3.9 3.1 2.6 'A1' 'A2' Lintel '2' Lintel '1' Standard truss with tile roofing (1) See Figure 1.6 (page 4) for details 15 Single-Leaf Masonry Design Manual Table 3.7 Selection of Lintels Supporting Girder Roof Trusses Maximum supported roof area, including standard trusses (m2) 140-mm-wide lintels 190-mm-wide lintels Opening (m) Type B(1) with: N16 N20 Type C(1) with: N16 N20 Type B(1) with: N16 N20 Type C(1) with: N16 N20 N1 and N2 0.9 1.2 1.8 2.4 3.0 33 30 20 15 12 34 31 22 16 13 75 58 40 30 23 80 65 54 45 36 36 31 21 15 12 38 34 30 23 17 76 59 40 30 23 89 72 59 46 37 N3 0.9 1.2 1.8 2.4 3.0 33 30 20 15 12 34 31 22 16 13 75 58 40 30 23 80 65 54 45 36 36 31 21 15 12 38 34 30 23 17 76 59 40 30 23 89 72 59 46 37 N4 and C1 0.9 1.2 1.8 2.4 3.0 28 25 20 16 12 28 26 22 16 13 60 50 35 27 22 61 51 44 40 33 30 28 21 17 12 31 29 27 23 17 64 50 36 28 23 68 57 48 42 34 N5 and C2 0.9 1.2 1.8 2.4 3.0 18 16 13 10 – 18 17 16 14 11 39 32 22 17 14 40 33 28 26 21 20 18 14 11 – 20 19 18 16 13 41 33 23 18 15 44 37 31 27 23 Wind class. (1) See Figure 1.6 (page 4) for details Table 3.8 Selection of Lintels Supporting a Timber Floor Maximum supported width (m) 140-mm-wide lintels Determination of supported width Lintel Assumed floor loadings: Dead load – 2 kPa (including partitions) Live load – 1.5 kPa = = Supported width First support Opening (m) Type BB(1) with: N16 N20 N16 0.9 1.2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 3.0 3.0 3.0 2.3 1.7 1.4 – – – 3.0 3.0 3.0 2.6 1.9 1.5 – – – 3.0 3.0 3.0 3.0 2.9 2.2 1.8 1.5 1.2 190-mm-wide lintels Type CC(1) with: N20 Type BB(1) with: N16 N20 Type CC(1) with: N16 N20 3.0 3.0 3.0 3.0 3.0 2.3 1.9 1.6 1.4 3.0 3.0 3.0 2.8 2.1 1.7 – – – 3.0 3.0 3.0 3.0 3.0 2.4 1.8 1.4 1.1 3.0 3.0 3.0 3.0 2.2 1.8 – – – 3.0 3.0 3.0 3.0 3.0 2.7 2.2 1.8 1.6 (1) See Figure 1.7 (page 4) for details Table 3.9 Selection of Bond Beams Supporting Standard Truss Roofs Maximum allowable value of dimension ‘A’ (m) 140-mm-leaf wall 190-mm leaf-wall Determination of dimension ‘A’ 'A1' Bond beam '1' 'A2' Bond beam '2' Wind Class. Bond beams(1) Type 1 Type 2 Type 3 Bond beams(1) Type 1 Type 2 Type 3 N2 N3 N4 N5 N6 9 7 – – – 9 9 9 6 – 9 9 9 9 7 9 9 5 – – 9 9 9 7 5 9 9 9 9 9 C1 C2 C3 C4 – – – – 9 6 – – 9 9 7 – – – – – 9 9 5 – 9 9 9 7 (1) See Figure 1.3 (page 3) for details 16 Single-Leaf Masonry Design Manual 4 4.1 Bracing Design 4.2 Method Determine the racking forces imposed on the building in both directions from Tables 4.1, 4.2 and 4.3 for the wind classification Bracing walls of sufficient number and strength must be located through the building to resist the racking forces from the wind and earthquake. The sum of the capacities of all bracing walls in each direction must exceed the total racking force in the relevant direction. The bracing walls can be either all masonry, other wall types or a combination of both. The external walls will act as bracing walls in either direction. Table 4.1 Racking Forces For earthquake loads on housing, H1 racking forces can be taken as equivalent to N2 wind classification and H2 and H3 racking forces equivalent to N3 wind classification. Note, these tables are extracts from Australian Standards AS 1684.2–1999 and AS 1684.3–1999 and are limit state loads (ultimate loads based on AS 1170.2) for consistency with limit state design. Wind Force Per Unit Length, Normal to Length of Buildings with Hip or Gable Ends Wind force to be resisted (kN/m) [Total force (kN) = building length (m) x wind force (kN/m)] Hip or gable Length Hip or gable Length n tio ec Dir ind w of n tio ec Dir ind w of Width Width Single-storey or upper-storey Lower-storey of two storeys Roof slope (degrees) Roof slope (degrees) Wind Class. Building width (m) 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 N1 4 6 8 10 12 14 16 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.0 1.2 1.4 1.5 1.7 1.9 2.0 1.2 1.5 1.7 2.0 2.2 2.4 2.6 1.4 1.6 1.9 2.2 2.5 2.8 3.1 1.5 1.9 2.3 2.7 3.1 3.5 3.8 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.8 2.9 3.0 3.1 2.8 2.9 3.0 3.2 3.4 3.6 3.8 3.2 3.4 3.6 3.9 4.2 4.4 4.7 3.4 3.7 3.9 4.2 4.5 4.8 5.1 3.5 3.8 4.2 4.6 5.0 5.4 5.9 N2 4 6 8 10 12 14 16 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.2 1.3 1.5 1.6 1.8 1.9 2.0 1.4 1.7 2.0 2.2 2.5 2.7 2.9 1.8 2.1 2.5 2.8 3.2 3.5 3.8 2.0 2.3 2.8 3.2 3.6 4.0 4.4 2.2 2.7 3.3 3.9 4.5 5.0 5.5 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.8 3.9 4.0 4.1 4.3 3.8 4.0 4.2 4.5 4.7 5.0 5.3 4.4 4.7 5.0 5.4 5.7 6.1 6.5 4.7 5.1 5.4 5.8 6.2 6.6 7.1 4.9 5.3 5.9 6.4 6.9 7.5 8.1 N3 and C1 4 6 8 10 12 14 16 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.3 2.5 2.7 2.9 3.1 2.2 2.6 3.1 3.5 3.9 4.2 4.6 2.8 3.3 3.9 4.4 5.0 5.5 6.0 3.1 3.6 4.3 5.0 5.7 6.3 6.9 3.4 4.3 5.2 6.1 7.0 7.8 8.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.9 6.0 6.2 6.4 6.7 6.0 6.2 6.6 7.0 7.4 7.8 8.2 6.9 7.3 7.9 8.4 9.0 9.5 10 7.4 7.9 8.5 9.0 9.6 10 11 7.6 8.3 9.1 10 11 12 13 N4 and C2 4 6 8 10 12 14 16 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.8 3.0 3.4 3.8 4.1 4.3 4.6 3.3 3.9 4.6 5.2 5.8 6.3 6.8 4.1 4.9 5.8 6.6 7.4 8.1 8.9 4.5 5.4 6.5 7.5 8.5 9.4 10 5.1 6.3 7.7 9.1 10 12 13 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.6 8.6 8.7 8.7 8.7 8.7 8.7 8.6 8.7 8.8 9.0 9.2 9.6 10 8.9 9.2 9.8 10 11 12 12 10 11 12 13 13 14 15 11 12 13 13 14 15 16 11 12 14 15 16 18 19 N5 and C3 4 6 8 10 12 14 16 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 4.0 4.0 4.0 3.9 3.9 3.9 3.9 4.1 4.5 5.0 5.6 6.0 6.4 6.7 4.9 5.7 6.7 7.7 8.5 9.3 10 6.0 7.3 8.5 9.7 11 12 13 6.7 8.0 9.5 11 12 14 15 7.4 9.3 11 13 15 17 19 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 14 14 15 13 14 14 15 16 17 18 15 16 17 18 20 21 22 16 17 19 20 21 23 24 17 18 20 22 24 26 28 17 Single-Leaf Masonry Design Manual Table 4.2 Wind Force on End of Buildings with Gable End Wind force to be resisted by gable end (kN) Width Width Di r of ecti wi on nd Length Di r of ecti wi on nd Length Single-storey or upper-storey Lower-storey of two storeys Roof slope (degrees) Roof slope (degrees) Wind Class. Building width (m) 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 N1 4 6 8 10 12 14 16 3.4 5.2 6.9 8.6 10 12 14 3.7 5.7 7.8 10 12 15 17 3.9 6.2 8.7 11 14 18 21 4.1 6.7 9.6 13 17 20 25 4.4 7.3 11 14 19 23 29 4.6 7.9 12 16 21 27 33 4.9 8.5 13 18 24 30 37 5.2 9.2 14 20 26 34 42 12 17 23 29 35 41 46 12 18 24 30 37 43 50 12 18 25 32 39 46 54 12 19 26 33 41 49 58 13 20 27 35 43 52 62 13 20 28 37 46 56 66 13 21 29 39 49 59 71 13 22 31 41 52 63 76 N2 4 6 8 10 12 14 16 5.0 7.5 10 12 15 17 20 5.3 8.2 11 14 18 21 25 5.6 8.9 13 17 21 25 30 6.0 9.7 14 19 24 30 36 6.3 10 15 21 27 34 41 6.7 11 17 23 30 38 47 7.1 12 18 26 34 43 54 7.6 13 20 29 38 49 61 16 24 32 40 48 56 64 16 25 33 42 51 60 69 17 26 35 44 54 64 75 17 26 36 46 57 68 80 17 27 37 48 60 73 86 18 28 39 51 64 77 92 18 29 41 53 67 82 98 19 30 42 56 71 88 105 N3 and C1 4 6 8 10 12 14 16 7.8 12 16 19 23 27 31 8.3 13 18 23 28 33 39 8.8 14 20 26 32 40 47 9.3 15 22 29 37 46 56 9.9 16 24 33 42 53 65 10 18 26 36 48 60 74 11 19 29 40 53 68 84 12 21 32 45 60 77 96 25 38 50 63 75 88 100 26 39 52 66 80 94 108 26 40 54 69 84 100 116 27 41 56 72 89 107 125 27 42 58 76 94 113 134 28 44 61 79 99 121 143 28 45 63 83 105 128 153 29 47 66 88 111 137 165 N4 and C2 4 6 8 10 12 14 16 12 17 23 29 35 41 46 12 19 26 34 41 50 58 13 21 29 38 48 59 70 14 23 32 43 55 69 83 15 24 36 48 63 79 96 16 26 39 54 71 89 110 17 28 43 60 79 101 125 18 31 47 66 89 114 142 37 56 75 93 112 131 149 38 58 78 98 119 140 161 39 59 81 103 125 149 173 40 61 84 108 133 159 186 40 63 87 113 140 169 199 41 65 91 118 148 179 213 42 67 94 124 156 191 228 43 69 99 131 166 204 245 N5 and C3 4 6 8 10 12 14 16 17 26 34 43 51 60 68 18 28 38 49 61 73 86 19 31 43 56 71 87 104 20 33 48 64 82 101 122 22 36 52 71 92 116 142 23 39 58 79 104 132 162 24 42 63 88 117 149 185 26 45 69 98 131 168 209 55 82 110 137 165 192 220 56 85 114 144 175 206 237 57 87 119 151 185 219 255 58 90 123 158 195 234 274 59 93 128 166 206 248 293 61 96 133 174 218 264 314 62 99 139 183 230 281 336 64 102 145 192 244 300 361 18 Single-Leaf Masonry Design Manual Table 4.3 Wind Force on End of Buildings with Hip End Wind force to be resisted by hip end (kN) Width Width Di r of ecti wi on nd Length Di r of ecti wi on nd Length Single-storey or upper-storey Lower-storey of two storeys Roof slope (degrees) Roof slope (degrees) Wind Class. Building width (m) 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 N1 4 6 8 10 12 14 16 3.6 5.4 7.2 9.0 11 13 14 3.6 5.4 7.2 9.0 11 13 14 3.6 5.5 7.2 9.0 11 13 14 6.7 5.7 8.1 11 13 16 19 4.0 6.6 9.6 13 17 21 25 4.4 7.3 11 15 19 24 29 4.6 7.8 12 16 21 27 33 4.9 8.6 13 19 25 32 39 12 17 23 29 35 41 46 12 17 23 29 35 41 46 12 17 23 29 35 41 47 12 18 24 30 36 43 50 12 18 25 32 39 47 56 12 19 26 34 42 51 61 13 20 27 35 44 54 64 13 20 29 38 47 58 70 N2 4 6 8 10 12 14 16 5.0 7.5 10 12 15 17 20 5.0 7.5 10 12 15 17 20 5.0 7.6 10 12 15 17 20 5.1 7.9 11 15 19 22 26 5.5 9.1 13 18 23 28 34 6.0 10 15 20 27 33 41 6.4 11 16 22 29 37 45 6.8 12 18 26 34 44 54 16 24 32 40 48 56 64 16 24 32 40 48 56 64 16 24 32 40 49 57 65 16 24 33 41 50 59 69 16 25 34 44 54 65 77 17 26 36 47 59 71 84 17 27 38 49 61 74 88 18 28 39 52 66 81 97 N3 and C1 4 6 8 10 12 14 16 7.8 12 16 19 23 27 31 7.8 12 16 19 23 27 31 7.9 12 16 19 23 27 31 8.0 12 18 23 29 35 41 8.6 14 21 28 36 44 53 9.4 16 23 32 41 52 63 10 17 25 35 46 58 71 11 19 29 40 54 68 85 25 38 50 63 75 88 100 25 38 50 63 75 88 100 25 38 50 63 76 88 101 25 38 51 64 78 93 108 26 39 53 69 85 102 120 26 41 57 73 91 111 131 27 43 59 76 95 116 138 28 44 62 81 103 126 152 N4 and C2 4 6 8 10 12 14 16 12 17 23 29 35 41 46 12 17 23 29 35 41 46 12 18 23 29 35 41 46 12 18 26 35 43 52 62 13 21 31 42 53 66 80 14 24 35 48 62 77 94 15 25 37 52 68 86 106 16 28 42 60 80 102 126 37 56 75 93 112 131 149 37 56 75 93 112 131 149 37 56 75 94 113 131 150 37 56 76 95 116 138 161 38 58 80 102 126 152 179 39 61 84 109 136 165 195 41 63 88 114 142 173 206 41 65 92 121 153 188 226 N5 and C3 4 6 8 10 12 14 16 17 26 34 43 51 60 68 17 26 34 43 51 60 68 17 26 34 43 51 60 68 17 27 39 51 64 77 91 19 31 45 61 79 97 117 21 35 51 70 91 114 139 22 37 55 76 100 127 156 23 41 62 88 117 150 186 55 82 110 137 165 192 220 55 82 110 137 165 192 220 55 83 111 138 166 194 221 55 83 112 140 170 203 236 56 85 117 151 196 224 263 58 89 124 161 200 242 287 60 93 129 168 209 254 303 61 96 135 178 225 277 332 19 Single-Leaf Masonry Design Manual 4.3 Bracing Wall Location Bracing walls must be distributed approximately evenly along the length and width of the building. The maximum distance between bracing walls supporting a roof is given in Table 4.4 for the various wind classifications. Where bracing walls cannot be spaced to comply with Table 4.4, then additional cross bracing needs to be included in the ceiling to distribute the racking forces. The maximum distance between bracing walls supporting a floor is given in Table 4.5. Where the width of floor exceeds the value in Table 4.5, then the spacing of the bracing walls shall be as given in Table 4.4. Table 4.5 Spacing of Bracing Walls Supporting a Floor (Lower Storey) Wind Classification Minimum building width (m) Maximum spacing of bracing walls (m) N1 4.8 14.0 N2 4.8 14.0 N3 and C1 6.0 14.0 N4 and C2 6.0 11.5 N5 and C3 6.0 10.0 Note, these tables are extracts from Australian Standards AS 1684.2–1999 and AS 1684.3–1999. Table 4.4 Spacing of Bracing Walls Under Roofs Maximum spacing of bracing walls (m) Wind Class. Building width (m) N1 Roof slope (degrees) 0 5 10 15 20 25 30 35 4 6 8 10 12 14 16 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 N2 4 6 8 10 12 14 16 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 7.8 9.0 9.0 9.0 9.0 9.0 9.0 6.7 8.6 9.0 9.0 9.0 9.0 9.0 6.4 7.9 8.8 9.0 9.0 9.0 9.0 N3 and C1 4 6 8 10 12 14 16 6.2 9.0 9.0 9.0 9.0 9.0 9.0 6.6 9.0 9.0 9.0 9.0 9.0 9.0 7.4 9.0 9.0 9.0 9.0 9.0 9.0 7.5 9.0 9.0 9.0 9.0 9.0 9.0 6.4 8.8 9.0 9.0 9.0 9.0 9.0 5.1 6.7 7.6 8.4 9.0 9.0 9.0 4.4 5.6 6.7 7.9 7.9 8.3 8.6 4.2 5.1 5.7 6.2 6.6 6.7 6.9 N4 and C2 4 6 8 10 12 14 16 3.9 5.9 7.9 9.0 9.0 9.0 9.0 4.3 6.6 9.0 9.0 9.0 9.0 9.0 4.9 7.3 9.0 9.0 9.0 9.0 9.0 5.0 7.3 9.0 9.0 9.0 9.0 9.0 4.2 5.8 6.7 7.3 7.9 8.2 8.5 3.3 4.4 5.0 5.5 5.9 6.1 6.5 2.9 3.7 4.4 5.2 5.2 5.5 5.7 2.7 3.4 3.8 4.1 4.3 4.4 4.6 N5 and C3 4 6 8 10 12 14 16 2.7 4.1 5.5 6.8 8.2 9.0 9.0 3.0 4.6 6.3 7.9 9.0 9.0 9.0 3.4 5.1 6.7 8.3 9.0 9.0 9.0 3.5 5.1 6.5 7.8 8.5 9.0 9.0 3.0 4.1 4.7 5.1 5.5 5.7 6.0 2.3 3.1 3.5 3.9 4.1 4.3 4.6 2.0 2.6 3.1 3.6 3.7 3.8 4.0 1.9 2.4 2.6 2.9 3.0 3.1 3.2 20 Single-Leaf Masonry Design Manual 4.4 Bracing Wall Capacities Table 4.6 The capacities of masonry acting as bracing walls are given in the following Tables: ■ Table 4.6 for walls that comply with the details shown in Figure 4.1. ■ Table 4.7 for wind at right angles (normal) to reinforced walls. ■ Table 4.8 for reinforced piers. Wall height (≤ 3.0 m) The bracing capacities given in Tables 4.6 to 4.8 rely on the tie-down reinforcement being effectively fixed into the foundations and the foundations being of sufficient size to resist overturning. Bond beam Bracing wall length Bracing wall length Bracing Capacity of Typical Walls(1) up to 3.0-m High Wall length (m) Unreinforced walls Leaf thickness (mm) Walls reinforced with tie-downs Leaf thickness (mm) 90 110 140 190 140 0.4 0.6 0.8 1.0 1.2 1.8 2.4 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 0.1 0.2 0.4 0.6 0.9 2.0 3.5 5.5 10 15 22 30 39 50 61 0.1 0.2 0.4 0.6 0.9 2.1 3.7 5.8 10 16 23 32 41 52 64 0.1 0.3 0.5 0.7 1.1 2.4 4.3 6.7 12 19 27 37 48 61 75 0.1 0.3 0.6 0.9 1.3 2.9 5.1 7.9 14 22 32 43 56 71 88 2.9 5.8 8.7 12 15 24 34 45 64 85 107 130 155 182 210 190 2.9 5.8 8.8 12 15 25 35 46 66 88 111 137 164 192 222 (1) As detailed in Figure 4.1 Floor level BRACING LENGTH FOR EXTERNAL REINFORCED WALLS Bracing wall length Bracing wall length Wall height (≤ 3.0 m) Wall height (≤ 3.0 m) External wall Floor slab A A Masonry mesh, 500 long every second course Floor slab Footing WALL NOT CONNECTED TO AN EXTERNAL WALL – ELEVATION WALL CONNECTED TO AN EXTERNAL WALL – ELEVATION External wall SECTION A–A INTERNAL WALLS WITHOUT TIE-DOWNS (UNREINFORCED) Bracing wall length Bracing wall length External wall Wall height (≤ 3.0 m) Wall height (≤ 3.0 m) 1-N12 bar grouted into top course bond beam and turned down 200 mm into end cores A A L8 ties every second course, bent down 100 mm into grouted cores 1-N12 grouted into end cores Starter bars anchored in slab Slab thickening under wall Slab thickening under wall Footing WALL NOT CONNECTED TO AN EXTERNAL WALL – ELEVATION WALL CONNECTED TO AN EXTERNAL WALL – ELEVATION INTERNAL WALLS WITH TIE-DOWNS Figure 4.1 Typical Bracing Wall Details 21 External wall SECTION A–A Single-Leaf Masonry Design Manual Table 4.7 Bracing Capacity of Walls with Wind Normal to Wall Bracing capacity per reinforced core (kN) Wall details Wind direction 3000 3600 4.4 2.2 1.5 1.1 0.9 0.7 6.2 3.1 2.1 1.6 1.2 1.0 10.9 5.5 3.6 2.7 2.2 1.8 1-N16 bar in grouted core 190 Table 4.8 2400 1-N12 bar in grouted core 190 Wind direction 1800 1-N12 bar in grouted core 140 Wind direction Wall Height (mm) 600 1200 Bracing Capacity of Reinforced Piers with Wind in Either Direction Bracing capacity of reinforced pier (kN) Pier details Pier Height (mm) 600 1200 1800 2400 3000 3600 5.4 2.7 1.8 1.3 1.1 0.9 9.2 4.6 3.1 2.3 1.8 1.5 16 7.8 5.2 3.9 3.1 2.6 27 13 9.1 6.8 5.5 4.5 44 22 15 11 8.8 7.3 38 19 13 10 7.7 6.4 66 33 22 17 13 11 1-N12 bar in grouted core 190 190 290 1-N12 bar in grouted core 290 290 1-N16 bar in grouted core 290 290 4-N12 bars in grouted core 290 290 4-N16 bars in grouted core 290 4-N12 bars in grouted cores 390 390 4-N16 bars in grouted cores 390 390 22 Single-Leaf Masonry Design Manual 5 Connection Details 5.1 Truss Tie-Down Trusses must be tied down to the top bond beam to prevent both uplift and horizontal movement. This can be achieved by either directly fixing the truss to the bond beam (where the walls are 2500 mm or higher) or by bolting a top plate to the bond beam and then attaching the truss to the top plate. Typical details and design capacities are given in the following Tables: ■ Table 5.1, using threaded rod ■ Table 5.2, using timber top plate ■ Table 5.3, using truss plates. Table 5.1 Truss Tie-Down using Threaded Rod Connection detail Threaded rod details Uplift capacity (kN) with following timbers: Unseasoned Seasoned J2 J3 J4 JD4 JD5 JD6 2-M10 rods 36 36 36 30 24 18 2-M12 rods 54 54 52 40 32 24 25 max. 75 x 10-mm GS plate drilled to suit size of rod Threaded rods with end cogged, extending down two courses, bent to suit ELEVATION Table 5.2 Truss Tie-Down using Timber Top Plate Connection detail Description Uplift capacity (kN) with following timbers: Unseasoned Seasoned J2 J3 J4 JD4 JD5 JD6 Single framing anchor 4.9 3.5 2.5 3.5 2.9 2.2 Double framing anchor 8.3 5.9 4.2 5.9 4.9 3.7 Single strap 6.5 4.7 3.3 4.7 3.8 2.9 Double strap 12 8.4 5.9 8.4 6.9 5.2 Single looped strap 13 13 13 13 13 13 Double looped strap 25 25 25 25 25 25 Framing anchor (single or double) with 4-2.8-mm dia. nails to each end NOTE: Refer to AS 1684.3 for top plate tie-down details 30 x 0.8-mm GI strap (single or double) with 3-2.8-mm dia. nails to each end NOTE: Refer to AS 1684.3 for top plate tie-down details 30 x 0.8-mm GI looped strap (single or double) with nails as shown below Nails required for each end of looped strap: 3-2.8-mm dia. for J2 4-2.8-mm dia. for J3 and JD4 5-2.8-mm dia. for J4, JD5 and JD6 NOTE: Refer to AS 1684.3 for top plate tie-down details 23 Single-Leaf Masonry Design Manual Table 5.3 Truss Tie-Down using Truss Plates Connection detail Description Uplift capacity (kN) with following timbers: Unseasoned Seasoned J2 J3 J4 JD4 JD5 JD6 Single truss plate, single roof truss 20 15 10 16 11 8 Single truss plate with overstrap and single roof truss 35 25 16 23 18 15 Double truss plate, double roof truss 49 44 28 44 36 28 54 43 3 roof trusses 34 M16 bolt through head plate 50 x 5 x 200 GS truss plate threaded over bond beam reinforcement 50 x 3-mm GI strap M16 bolt through head plate Overstrap must be tight or packed with noncompressive packing 50 x 5 x 200 GS truss plate threaded over bond beam reinforcement and anchored in second course Double roof trusses M16 bolt through head plates 50 x 5 x 200 GS truss plates threaded over bond beam reinforcement and anchored in second course 50 x 3-mm GI strap M16 bolt through head plates Overstrap must be tight or packed with noncompressive packing Two or three roof trusses 50 x 5 x 200 GS truss plates threaded over bond beam reinforcement and anchored in second course Double truss plate with overstrap and 2 or 3 roof trusses 76 54 2 roof trusses 34 REF: An Investigation of Truss Hold Down TR44 James Cook University, Cyclone Structural Testing Station October 1996. 24 Single-Leaf Masonry Design Manual 5.2 Fixing to Gable Ends Gable walls must be supported by the roof diaphragm by anchoring of end roof trusses at regular centres. The attached end truss must then be braced back to internal trusses with trimming joists. Typical details and design capacities are given in the following Figures: ■ Figure 5.1, for timber gable fixings ■ Figure 5.2, for block gable fixing. Top chord of roof truss Bond beam 50 x 8 GS 'Z' bracket, fixed to truss chord by coach screw and masonry by 12-mm Ramset fixings or equivalent, at spacings not exceeding those given in the table below Bottom chord of roof truss FC sheeting, min. 100 mm below top of blockwork Top chords of trusses Sheeting battens fixed to truss Noggins between end two trusses at fixing points not exceeding spacing given in table below 78 x 38 trimming joist, on flat, screwed to bottom chords of truss Seal blocks before FC sheeting is fixed in place M12 threaded rod cogged in bond beam, passing through trimming joist and nogging at spacings not exceeding those given in table below Approved sealant FC sheeting, min. 100 mm below top of blockwork Top chords of trusses Sheeting battens fixed to truss Ceiling Wind Classification Maximum spacing of fixings (m) N1 N3 N3 3.6 3.6 2.4 N4 and C1 N5 and C2 N6 and C3 1.8 1.2 0.9 Figure 5.2 5.3 METHOD 1 Timber Floor Fixing Timber or steel pole plate Bond beam with 1-N 12 bar Seal blocks before FC sheeting is fixed in place Blockwork Gable Fixing A pole plate supporting a timber floor must have sufficient anchors to carry the shear load imposed by the floor. Typical fixing is shown in Figure 5.3. Noggins between end two trusses at fixing points not exceeding spacing given in table below 78 x 38 trimming joist, on edge Hilti HSA stud anchor or equivalent 50 x 50 x 8 steel angle threaded over bond beam reinforcement and bolted with M12 bolts through bottom chord of truss and trimmer joist at spacings not exceeding those given in table below Approved sealant Figure 5.3 METHOD 2 Wind Classification Maximum spacing of fixings (m) N1 N3 N3 3.6 3.6 3.6 N4 and C1 N5 and C2 N6 and C3 2.4 1.8 1.2 Figure 5.1 50 x 8 GS 'Z' bracket, fixed as above Timber Gable End Fixing 25 Pole Plate Fixing for Timber Floor Single-Leaf Masonry Design Manual 6 6.1 Basement Walls 6.2 General As with all retaining walls it is critical that the backfill is prevented from becoming saturated. Steps to be taken to achieve this include: The foundation slab of a basement can be modified to provide an efficient footing for a retaining wall. In addition, a concrete floor slab will provide a “prop” to the top of the wall, simplifying the wall details compared to a timber floor. All backfill must be with granular material. Details of typical basement walls are shown in the following Figures: ■ Figure 6.1, with concrete floor ■ Figure 6.2, with timber floor. Drainage ■ A drainage system within the backfill. This should preferable take the form of a 300-mm width of gravel immediately behind the wall with a continuous agricultural pipe located at the base of the wall. The pipe must discharge beyond the ends of the wall or be connected to the stormwater drain. ■ Sealing the backfill surface. This can be done by placing a compacted layer of low-permeability material over the backfill and sloping the surface away from the house. It is also important to prevent hydrostatic pressure under the floor slab. Where there is the possibility of groundwater under the slab, then a subfloor drainage system is advisable. Floor slab reinforcement Starter bar to match wall reinforcement above N12 at 200 crs One-course bond beam with N12 bar 20.20 knock-out block saw-cut at floor soffit level Tanking to back face of wall 190-thick blockwork NOTE: Wall blocks and reinforcement as for 'Typical Details' 2700 max. 20.48 'H' blocks at horizontal reinforcement 20.01 standard blocks between Horizontal reinforcement, N12 at 400 crs Vertical reinforcement, N16 at 400 crs, central* NOTE: No tanking required False wall Floor slab reinforcement N16 at 400 crs* 600 min. lap Drained cavity Ag drain 200 N12 at 400 crs 55 cover 200 * N12 at 200 crs may be used instead of N16 at 400 crs 1000 TYPICAL DETAILS Figure 6.1 ALTERNATIVE DETAILS Typical Basement Wall Supporting a Concrete Floor 26 Single-Leaf Masonry Design Manual 6.3 Tanking Where it is required that the basement be kept dry, a proper tanking system needs to be installed behind the wall before backfilling. An alternative to this is to provide a drain and a false wall in front of the wall (see Figures 6.1 and 6.2). 140-thick blockwork Timber floor Timber floor One-course bond beam using 20.20 knock-out block with 1-N12 bar Pole plate fixed to bond beam Vertical reinforcement, N16 at 400 crs, central 20.48 'H' blocks at horizontal reinforcement 190-thick blockwork 190-thick blockwork Horizontal reinforcement, N12 at 400 crs Tanking to back face of wall NOTE: Reinforcement as for 'Typical Details' 2700 max. to ground level 290-thick blockwork 290-thick blockwork NOTE: No tanking required 55 cover to back face 1200 30.48 'H' blocks at horizontal reinforcement Floor slab reinforcement N16 at 200 crs* False wall 600 min. lap Drained cavity Ag drain 300 N12 at 400 crs 55 cover 300 * N20 at 400 crs may be used instead of N16 at 200 crs 1500 TYPICAL DETAILS Figure 6.2 ALTERNATIVE DETAILS Typical Basement Wall Supporting a Timber Floor 27 Single-Leaf Masonry Design Manual 7 7.1 Some alternative coating systems available include: Weatherproofing Recommendations for Housing Textured or architectural finishes. There are an number of proprietary weatherproof coating systems available. ■ 100% acrylic-base exterior quality gloss paint. Three coats are recommended, applied by brush or roller. Suitable paints include Wattyl Solagard, Dulux Weathershield, and Taubmans All Weather Gloss. ■ Cement-based paint, eg Silasec. At least one full coat of cement-based paint followed by two coats of 100% acrylic-based exterior-quality gloss paint, is recommended. ■ Clear coatings. Clear coatings are NOT generally recommended but may be necessary for coloured blockwork. If they are used then special care must be taken to ensure that there are no gaps or cracks that will allow water entry. These coatings will also need more regular maintenance. Joint Finishing It is essential that all mortar joints be filled to the depth of the face shell and the surface compressed by tooling, leaving no voids. Ironing with an ironing tool of 12-mm diameter, 450-mm long, is generally satisfactory. Particular care needs to be taken around openings and window sills to ensure joints are properly filled. 7.2 ■ Weatherproofing Application It is recommended that a weatherproof coating be applied to the outside of houses unless waterproofing additives have been incorporated into the blocks and the mortar. Where waterproofing has been incorporated into the blocks, consult with the manufacturer for advice and construction specifications. 7.3 Window Installation Post fitting of windows is recommended in accordance with Figure 7.1. It is also recommended that the weatherproofing be applied before fixing downpipes, etc and before the windows are installed. The weatherproofing needs to be taken around the window reveals. All coatings must be applied strictly in accordance with the manufacturer’s instructions. RECOMMENDED PROCEDURE Weatherproof coating 1 Weatherproof all of the external wall, including window reveals, before the windows are fixed Lintel beam 2 Fix windows with Ramset ED642 anchors, or equivalent. Before the anchor is inserted, the hole should be filled with sealant Ramset anchors or equivalent Ramset anchors or equivalent Apply weatherproof coating to all of the opening surround before windows are fixed into position Weatherproof coating Ramset anchors or equivalent Sealant each side of window frame 3 Seal the whole perimeter of the window frame on the inside and the jamb and head sections on the outside, with Sikaflex 15LM or equivalent 4 Door frames are to be fixed and sealed as set out for windows, except the anchors should be Ramset ED655 or equivalent. HEAD FIXING Weatherproof coating Ramset anchors or equivalent Sealant each side of window frame JAMB FIXING Ramset anchors or equivalent Sealant on inside Sill unit Sill flap on outside Bond beam Ramset anchors or equivalent Weatherproof coating Weatherproof coating SILL FIXING Figure 7.1 Installation of Windows 28 Concrete Masonry Walling Concrete Masonry Association of Australia Queensland Promotions Committee IBM Centre 348 Edward Street Brisbane QLD 4000 Telephone 07 3831 3288 Besser Masonry 85 Christensen Road Stapylton QLD 4207 Telephone 07 3382 4100 Boral Masonry 62 Industrial Avenue Wacol QLD 4076 Telephone 07 3271 2922 ISBN 0 909407 46 0 March 2001 MA47 DESIGNED AND PRODUCED BY TECHMEDIA PUBLISHING PTY LTD + 61 2 9477 7766