Dedicated outdoor-air systems A dedicated outdoor-air system (DOAS) (dedicated ventilation unit) uses a separate air handler to dehumidify, cool, heat, and sometimes humidify the incoming outdoor air before delivering it to other HVAC units or directly to the occupied zones. In either case, the local HVAC units handle the zone cooling and heating loads. Treating the outdoor air separately from recirculated return air makes it easy to verify sufficient ventilation airflow and enables enforcement of a maximum humidity limit in occupied zones. Figure 4–15 Dedicated outdoor-air systems conditioned air to local terminal units Application considerations ■ Always provide conditioned air that is drier than the air in the space. This practice minimizes the cooling capacity required from the local HVAC terminals and adequately controls the indoor relative humidity without additional, zone-level dehumidification enhancements. ■ Deliver “cold” conditioned air whenever possible, and use recovered energy to reheat during mild weather. Providing “cold” conditioned air from the DOAS minimizes the cooling loads at the local HVAC terminals. During mild weather (spring and fall), modulate the amount of recovered energy used by the DOAS for reheat; only warm the conditioned air enough to minimize inefficient reheat at the local HVAC terminals. “Neutral”temperature conditioned air (which has a dry-bulb temperature approximating that of the air in the space) increases the cooling CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Dedicated outdoor-air systems 4–45 capacity required from the local HVAC terminals and requires more reheat at the dedicated outdoor-air unit. ■ Select equipment to limit indoor relative humidity to 60–65 percent. Targeting a drier condition in the space will require larger equipment and consume more energy. ■ Employ communicating controls to optimize energy use. Dynamically resetting the dew point or dry-bulb temperature delivered by the DOAS can minimize the energy use by the overall system. Related reading ■ “Dedicated Ventilation Systems,” Engineers Newsletter (volume 30, number 3) ■ Dehumidification in HVAC Systems Applications Engineering Manual (Trane literature number SYS-APM004-EN) ■ Designing Dedicated Outdoor-Air Systems Application Guide (Trane literature number SYS-APG001-EN. Sample scenarios Table 4–5 Sample Scenarios Topic Scenario 1 (page 46) Cool/Heat (Fixed Setpoints) Scenario 2 (page 51) Dehumidify and Reheat/Heat (Fixed Setpoints) Scenario 3 (page 56) Dehumidify (Priority) or Cool/Heat (Optimized SADP) Scenario 4 (page 62) Dehumidify and Reheat/Heat (Optimized SADB)) Scenario 1. A building is served by a fan-coil system and a dedicated outdoor-air unit that cools the outdoor air to 70°F dry bulb during the cooling season, or heats the outdoor air to 68°F dry bulb during the heating season, before delivering the conditioned outdoor air directly to the individual spaces. (Note: In non-arid climates, this approach may not adequately dehumidify the outdoor air.) ■ When the outdoor dry-bulb temperature is greater than the cooling supply-air dry-bulb setpoint, the dedicated outdoor-air unit will cool the entering outdoor air to the cooling supply-air dry-bulb setpoint. 4–46 System Design Options Dedicated outdoor-air systems TRACE 700 User’s Manual • CDS-PRM001-EN ■ When the outdoor dry-bulb temperature is less than the cooling supply-air dry-bulb setpoint, the dedicated outdoor-air unit will heat the entering outdoor air to the heating supply-air dry-bulb setpoint. This example will cover how to model the air-distribution system (steps 1–8), model the cooling and heating equipment (steps 9– 11), and assign the loads from the coils to the equipment (step 12). 1 Start by selecting Fan Coil as the system type. 2 On the Dedicated OA tab, select the type of dedicated ventilation unit to be modeled. In this example, the dedicated ventilation unit will supply air to spaces at a specific dry bulb. Therefore, Cool / Heat will be selected. None – no dedicated ventilation unit Cool / heat – a dedicated ventilation unit is used to cool the outdoor air to the user-input cooling dry bulb during the cooling season or heat the outdoor air to the user-input heating dry bulb during the heating season. Dehumidify (priority) or Cool / Heat – a dedicated ventilation unit is used to dehumidify the outdoor air to the user-input cooling dew point (not reheated) during the cooling season or heat the outdoor air to the user-input heating dry bulb during the heating season. Dehumidify and Reheat / Heat – a dedicated ventilation unit is used to dehumidify the outdoor air to the user-input cooling dew point (then reheat it to the user-input cooling dry bulb) during the cooling season or heat the outdoor air to the user-input heating dry bulb during the heating season. CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Dedicated outdoor-air systems 4–47 3 Select the control method for the unit. Because the dedicated ventilation cooling coil cools the outdoor air to the cooling supply-air dry bulb, or the dedicated ventilation heating coil heats the outdoor air to the heating supply-air dry bulb, Fixed Setpoints will be used. Note: For additional information related to the other Control Methods, press F1 and click Control Method. 4 Input the Cooling and Heating Design Setpoints. In this scenario, 70°F should be input for the cooling supply-air dry bulb, and 68°F for the heating supply-air dry bulb. If the ventilation air is to be precooled, the Dedicated Ventilation Cooling Coil schedule defines the hours of available operation of the ventilation cooling coil. The optional ventilation cooling coil is available for any hour that this schedule reads 1 percent or greater. 5 Select the schedule for the coils and fan in the dedicated outdoor-air unit. If the ventilation air is to be preheated, the Dedicated Ventilation Heating Coil schedule defines the hours of available operation of the ventilation heating coil. The optional ventilation heating coil is available for any hour that this schedule reads 1 percent or greater. The Optional ventilation fan schedule defines the hours that the ventilation unit can operate. If the Optional ventilation fan schedule reads 1 percent or greater, the fan is available that hour. Note: If a custom schedule is created for the fan or coils, it is recommended to use values of 0 percent for hours off and 100 percent for hours available to run to avoid confusion. 4–48 System Design Options Dedicated outdoor-air systems TRACE 700 User’s Manual • CDS-PRM001-EN Return/Outdoor Deck – conditioned outdoor air is mixed with the return air in the main unit(s). Plenum – conditioned outdoor air is delivered to the plenum above the spaces. Room Direct – conditioned outdoor air is delivered directly to the spaces. This can also be used to model the delivery of conditioned outdoor air to dual-duct VAV boxes where it mixes locally with recirculated return air. 6 Select the dedicated ventilation-deck location. This tells TRACE 700 where to supply the preconditioned outdoor air. For this scenario, the outdoor air will be delivered directly to the spaces. As a result, Room Direct will be selected. 7 Select the level of the ventilation-deck location. For this scenario, one large dedicated ventilation unit will condition the outdoor air for all of the rooms assigned to the fan-coil system, so the coils should be set at the System level. System – The dedicated ventilation unit will be placed at the system level. It will pretreat the outdoor air for all of the rooms and zones assigned to the airside system. This is the most common choice for dedicated ventilation systems. The System Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Zone – Each zone (or room assigned directly to the system) will get a separate dedicated ventilation system. The Zone Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Room – Each room will get a separate dedicated ventilation system. The Room Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Same level as main cooling coil – The dedicated ventilation unit will be placed at the same level as the main cooling coil. The System Component Selection report should be used to size the dedicated ventilation unit. Same level as main heating coil – The dedicated ventilation unit will be placed at the same level as the main heating coil. The System Component Selection report should be used to size the dedicated ventilation unit. CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Dedicated outdoor-air systems 4–49 8 On the Fans tab, input the fan type and the total static pressure for the primary fan (the fans in the fan-coil units) and the optional ventilation fan (the fan in the dedicated ventilation unit). Next, define the cooling and heating plants represented by the fan-coil system and the rooftop air conditioner: 9 Add two new cooling plants and two new heating plants to the Configuration pane. 10Drag the appropriate icons from the Equipment Category section to define each plant. For cooling, use water-cooled chiller and air-cooled unitary. For heating, use boiler and gas-fired heat exchanger. 11To finish defining this equipment, enter the information from Table 4–6 on page 4–51 on the appropriate equipment tab. Finally, assign the coil loads of the air-distribution system to the proper cooling and heating plants: 12Drag each coil in the Unassigned Systems/ Coils pane to the appropriate plant in the Systems and Plants pane. Before… After… The illustration labeled After shows the completed assignments. 4–50 System Design Options Dedicated outdoor-air systems TRACE 700 User’s Manual • CDS-PRM001-EN Table 4–6 Equipment types Cooling Equipment tab Heating Equipment tab Water-cooled chiller 2-stage centrifugal gas-fired hot water boiler Air-cooled unitary split system RAUC20+ ton scroll rooftop gas heat Scenario 2. A building is served by a water-source heat pump (WSHP) system and a dedicated outdoor-air unit that delivers conditioned outdoor air to the individual heat pumps. During the cooling season, the dedicated outdoor-air unit dehumidifies the outdoor air to 55°F dew point and then reheats it to a “neutral” 70°F dry bulb. During the heating season, the dedicated unit heats the outdoor air to 68°F dry bulb. ■ When the outdoor dew point is greater than the cooling supply- air dew point setpoint, the dedicated outdoor-air unit will dehumidify the entering outdoor air to the cooling supply-air dew point setpoint, then reheat it to the cooling supply-air dry-bulb setpoint. ■ When the outdoor dew point is less than the cooling supply-air dew point setpoint and the outdoor dry-bulb temperature is greater than the cooling supply-air dry-bulb setpoint, the dedicated outdoor-air unit will cool the entering outdoor air to the cooling supply-air dry-bulb setpoint. ■ When the outdoor dew point is less than the cooling supply-air dew point setpoint and the outdoor dry-bulb temperature is less than the cooling supply-air dry-bulb setpoint, the dedicated outdoor-air unit will heat the entering outdoor air to the heating supply-air dry-bulb setpoint. This example will cover how to model the air-distribution system (steps 1–8), model the cooling and heating equipment (steps 9– 11), and assign the loads from the coils to the equipment (step 12) . CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Dedicated outdoor-air systems 4–51 1 Start by selecting Water source heat pump as the system type. 2 On the Dedicated OA tab, select the type of dedicated ventilation unit to be modeled. In this example, the dedicated ventilation unit will supply low dew-point air reheated to a roomneutral dry bulb in cooling mode, and air at a specific dry bulb in heating mode. Therefore, Dehumidify and Reheat / Heat will be selected. 4–52 None – no dedicated ventilation unit Cool / heat – a dedicated ventilation unit is used to cool the outdoor air to the user-input cooling dry bulb during the cooling season, or heat the outdoor air to the user-input heating dry bulb during the heating season. Dehumidify (priority) or Cool / Heat – a dedicated ventilation unit is used to dehumidify the outdoor air to the user-input cooling dew point (not reheated) during the cooling season, or heat the outdoor air to the user-input heating dry bulb during the heating season. Dehumidify and Reheat / Heat – a dedicated ventilation unit is used to dehumidify the outdoor air to the user-input cooling dew point (then reheat it to the user-input cooling dry bulb) during the cooling season, or heat the outdoor air to the user-input heating dry bulb during the heating season. System Design Options Dedicated outdoor-air systems TRACE 700 User’s Manual • CDS-PRM001-EN 3 Select the control method for the unit. Because the dedicated ventilation cooling coil dehumidifies the outdoor air to cooling supply-air dew point and reheats it to room neutral, or the dedicated ventilation heating coil heats the outdoor air to heating supply-air dry bulb, Fixed Setpoints will be used. 4 Input the Cooling and Heating Design Setpoints. In this scenario, 55°F should be input for the cooling supply-air dew point, 70°F for the cooling supply-air dry bulb, and 68°F for the heating supply-air dry bulb. 5 Select the schedule for the coils and fan in the dedicated outdoor-air unit. Note: If a custom schedule is created for the fan or coils, it is recommended to use values of 0 percent for hours off and 100 percent for hours available to run to avoid confusion. CDS-PRM001-EN • TRACE 700 User’s Manual Note: For additional information related to the other Control Methods, press the F1 key and click Control Method. If the ventilation air is to be precooled, the Dedicated Ventilation Cooling Coil schedule defines the hours of available operation of the ventilation cooling coil. The optional ventilation cooling coil is available for any hour that this schedule reads 1 percent or greater. If the ventilation air is to be preheated, the Dedicated Ventilation Heating Coil schedule defines the hours of available operation of the ventilation heating coil. The optional ventilation heating coil is available for any hour that this schedule reads 1 percent or greater. The Optional ventilation fan schedule defines the hours that the ventilation unit can operate. If the Optional ventilation fan schedule reads 1 percent or greater, the fan is available that hour. System Design Options Dedicated outdoor-air systems 4–53 Return/Outdoor Deck – conditioned outdoor air is mixed with the return air in the main unit(s). Plenum – conditioned outdoor air is delivered to the plenum above the spaces. Room Direct – conditioned outdoor air is delivered directly to the spaces. This can also be used to model the delivery of conditioned outdoor air to dual-duct VAV boxes where it mixes with conditioned recirculated return air. 6 Select the dedicated ventilation deck location. This tells TRACE 700 where to supply the preconditioned outdoor air. For this scenario, the outdoor air will be delivered to the heat pumps. As a result, Return/Outdoor Deck will be selected. 7 Select the level of the ventilation deck location. For this scenario, one large dedicated ventilation unit will condition the outdoor air for all of the rooms assigned to the WSHP airside system, so the coils should be set at the System level. Note: For additional details on Systems, refer to the System Type: Characteristics in online Help. 4–54 System – The dedicated ventilation unit will be placed at the system level. It will pretreat the outdoor air for all of the rooms and zones assigned to the airside system. This is the most common choice for dedicated ventilation systems. The System Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Zone – Each zone (or room assigned directly to the system) will get a separate dedicated ventilation system. The Zone Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Room – Each room will get a separate dedicated ventilation system. The Room Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Same level as main cooling coil – The dedicated ventilation unit will be placed at the same level as the main cooling coil. The System Component Selection report should be used to size the dedicated ventilation unit. Same level as main heating coil – The dedicated ventilation unit will be placed at the same level as the main heating coil. The System Component Selection report should be used to size the dedicated ventilation unit. System Design Options Dedicated outdoor-air systems TRACE 700 User’s Manual • CDS-PRM001-EN 8 On the Fans tab, input the fan type and the total static pressure for the primary fan (the fans in the WSHP units) and the optional ventilation fan (the fan in the dedicated ventilation unit). Next, define the cooling and heating plants represented by the WSHP system and the rooftop air conditioner. 9 Add two new cooling plants and two new heating plants to the Configuration pane. For cooling, use water-source heat pump and air-cooled unitary. For heating, use boiler (for the WSHP system) and gas-fired heat exchanger. 10Drag the appropriate icons from the Equipment Category section to define each plant. 11To finish defining this equipment, enter the information from Table 4–7 on page 4–56 on the appropriate equipment tab. Before… Finally, assign the coil loads of the air distribution system to the proper cooling and heating plants. 12Drag each coil in the Unassigned Systems/ Coils pane to the appropriate plant in the Systems and Plants pane. After… The illustration labeled “After” shows the completed assignments. CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Dedicated outdoor-air systems 4–55 Table 4–7 Equipment types Cooling Equipment tab Heating Equipment tab Water-source heat pump water source HP– high efficiency gas-fired hot water boiler Air-cooled unitary split system RAUC20+ ton scroll rooftop gas heat Scenario 3. A building is served by a VAV air-handling system on each floor. A dedicated outdoor-air unit delivers conditioned outdoor air to the intake of each air handler. During the cooling season, the dedicated outdoor-air unit dehumidifies the outdoor air to 55°F dew point, but does not reheat it. During the heating season, the dedicated unit heats the outdoor air to 68°F dry bulb. In addition, the system-level controller polls the humidity sensors located in each room and resets the dew point leaving the dedicated outdoor-air unit, to prevent the relative humidity in the worst-case room from rising above 60% while minimizing energy use. ■ The system controller determines the highest possible cooling supply-air dew point setpoint that still avoids the relative humidity from rising above the maximum upper limit (60%, in our example) in any room. ■ When the outdoor dew point is greater than the current cooling supply-air dew point setpoint, the dedicated outdoor-air unit will dehumidify the entering outdoor air to the cooling supply-air dew point setpoint. ■ When the outdoor dew point is less than the current supply-air dew point setpoint and the outdoor dry-bulb temperature is greater than the cooling supply-air dry-bulb setpoint, the dedicated outdoor-air unit will cool the entering outdoor air to the cooling supply-air dry-bulb setpoint. ■ When the outdoor dew point is less than the current cooling supply-air dew point setpoint and the outdoor dry-bulb temperature is less than the cooling supply-air dry-bulb setpoint, the dedicated outdoor-air unit will heat the entering outdoor air to the heating supply-air dry-bulb setpoint. 4–56 System Design Options Dedicated outdoor-air systems TRACE 700 User’s Manual • CDS-PRM001-EN This example will cover how to model the air-distribution system (steps 1–8), model the cooling and heating equipment (steps 9– 11), and assign the loads from the coils to the equipment (step 12). 1 Start by selecting Variable Volume Reheat as the system type. 2 On the Dedicated OA tab, select the type of dedicated ventilation unit to be modeled. In this example, the dedicated ventilation unit will supply low dew-point air (not reheated) in cooling mode, and air at a specific dry bulb in heating mode. Therefore, Dehumidify (priority) or Cool / Heat will be selected. None – no dedicated ventilation unit Cool / heat – a dedicated ventilation unit is used to cool the outdoor air to the user-input cooling dry bulb during the cooling season, or heat the outdoor air to the user-input heating dry bulb during the heating season. Dehumidify (priority) or Cool / Heat – a dedicated ventilation unit is used to dehumidify the outdoor air to the user-input cooling dew point (not reheated) during the cooling season, or heat the outdoor air to the user-input heating dry bulb during the heating season. Dehumidify and Reheat / Heat – a dedicated ventilation unit is used to dehumidify the outdoor air to the user-input cooling dew point (then reheat it to the user-input cooling dry bulb) during the cooling season, or heat the outdoor air to the user-input heating dry bulb during the heating season. CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Dedicated outdoor-air systems 4–57 3 Select the control method for the unit. Because the dew point delivered by the dedicated ventilation cooling coil is reset based on the worst-case room, Optimize Supply Air Dew Point will be used. 4 Input the Cooling and Heating Design Setpoints. In this scenario, 65°F should be input for the cooling supply-air dry bulb, 68°F for the heating supply-air dry bulb, 65°F for the cooling supply-air dew point high limit, and 55°F for the cooling supply-air dew point low limit. Note: For additional information related to the other Control Methods, press the F1 key and click Control Method. 5 Select the schedule for the coils and fan in the dedicated outdoor-air unit. If the ventilation air is to be precooled, the Dedicated Ventilation Cooling Coil schedule defines the hours of available operation of the ventilation cooling coil. The optional ventilation cooling coil is available for any hour that this schedule reads 1 percent or greater. Note: If a custom schedule is created for the fan or coils, it is recommended to use values of 0 percent for hours off and 100 percent for hours available to run to avoid confusion. If the ventilation air is to be preheated, the Dedicated Ventilation Heating Coil schedule defines the hours of available operation of the ventilation heating coil. The optional ventilation heating coil is available for any hour that this schedule reads 1 percent or greater. The Optional ventilation fan schedule defines the hours that the ventilation unit can operate. If the Optional ventilation fan schedule reads 1 percent or greater, the fan is available that hour. 4–58 System Design Options Dedicated outdoor-air systems TRACE 700 User’s Manual • CDS-PRM001-EN 6 Select the dedicated ventilation deck location. This tells TRACE 700 where to supply the preconditioned outdoor air. For this scenario, the outdoor air will be delivered to the mixing box of the VAV air handler. As a result, Return / Outdoor Deck will be selected. 7 Select the level of the ventilation deck location. For this scenario, one large dedicated ventilation unit will condition the outdoor air for all of the rooms assigned to the VAV airside system, so the coils should be set at the System level. Note: For additional details on Systems, refer to the System Type: Characteristics in online Help. Return/Outdoor Deck – conditioned outdoor air is mixed with the return air in the main unit(s). Plenum – conditioned outdoor air is delivered to the plenum above the spaces. Room Direct – conditioned outdoor air is delivered directly to the spaces. This can also be used to model the delivery of conditioned outdoor air to dual-duct VAV boxes where it mixes with conditioned recirculated return air. System – The dedicated ventilation unit will be placed at the system level. It will pretreat the outdoor air for all of the rooms and zones assigned to the airside system. This is the most common choice for dedicated ventilation systems. The System Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Zone – Each zone (or room assigned directly to the system) will get a separate dedicated ventilation system. The Zone Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Room – Each room will get a separate dedicated ventilation system. The Room Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Same level as main cooling coil – The dedicated ventilation unit will be placed at the same level as the main cooling coil. The System Component Selection report should be used to size the dedicated ventilation unit. Same level as main heating coil – The dedicated ventilation unit will be placed at the same level as the main heating coil. The System Component Selection report should be used to size the dedicated ventilation unit. CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Dedicated outdoor-air systems 4–59 8 On the Temp/Humidity tab, specify a Maximum room relative humidity of 60%. 9 On the Fans tab, input the fan type and the total static pressure for the primary fan (the fans in the VAV air handler) and the optional ventilation fan (the fan in the dedicated ventilation unit). Next, define the cooling and heating plants represented by the VAV system and the rooftop air conditioner. 10Add two new cooling plants and two new heating plants to the Configuration pane. 11Drag the appropriate icons from the Equipment Category section to define each plant. 12To finish defining this equipment, enter the information from Table 4–8 on page 4–61 on the appropriate equipment tab. 4–60 System Design Options Dedicated outdoor-air systems For cooling, use air-cooled chiller and air-cooled unitary. For heating, use boiler (for the WSHP system) and gas-fired heat exchanger. TRACE 700 User’s Manual • CDS-PRM001-EN Finally, assign the coil loads of the air distribution system to the proper cooling and heating plants. 13Drag each coil in the Unassigned Systems/ Coils pane to the appropriate plant in the Systems and Plants pane. Before… The illustration labeled “After” shows the completed assignments. After… Table 4–8 Equipment types Cooling Equipment tab Heating Equipment tab Air-cooled chiller air-cooled helicalrotary chiller gas-fired hot water boiler Air-cooled unitary split system RAUC20+ ton scroll rooftop gas heat CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Dedicated outdoor-air systems 4–61 Scenario 4. A building is served by a fan-coil system and a dedicated outdoor-air unit that delivers conditioned outdoor air directly to the individual spaces. The system-level controller polls the fan-coils and resets the dry-bulb temperature leaving the dedicated outdoor-air unit to avoid overcooling or overheating any room. During the cooling season, the dedicated outdoor-air unit dehumidifies the outdoor air to 55°F dew point and then, if necessary, reheats it just enough to avoid overcooling the room with the lowest sensible cooling load. During the heating season, the dedicated unit heats the outdoor air as much as possible, without overheating the room with the lowest sensible heating load. ■ The system controller determines the current supply-air dry-bulb setpoint needed to avoid overcooling or overheating any room. ■ When the outdoor dew point is greater than the cooling supply- air dew point setpoint, the dedicated outdoor-air unit will dehumidify the entering outdoor air to the cooling supply-air dew point setpoint, then reheat it to the current supply-air dry-bulb setpoint. ■ When the outdoor dew point is less than the cooling supply-air dew point setpoint and the outdoor dry-bulb temperature is greater than the current supply-air dry-bulb setpoint, the dedicated outdoor-air unit will cool the entering outdoor air to the current supply-air dry-bulb setpoint. ■ When the outdoor dew point is less than the cooling supply-air dew point setpoint and the outdoor dry-bulb temperature is less than the current supply-air dry-bulb setpoint, the dedicated outdoor-air unit will heat the entering outdoor air to the current supply-air dry-bulb setpoint. This example will cover how to model the air-distribution system (steps 1–8), model the cooling and heating equipment (steps 9– 11), and assign the loads from the coils to the equipment (step 12). 4–62 System Design Options Dedicated outdoor-air systems TRACE 700 User’s Manual • CDS-PRM001-EN 1 Start by selecting Fan Coil as the system type. 2 On the Dedicated OA tab, select the type of dedicated ventilation unit to be modeled. In this example, the dedicated ventilation unit will supply low dew-point air (and possibly reheated) in cooling mode, and air at a specific dry bulb in heating mode. Therefore, Dehumidify and Reheat / Heat will be selected. 3 Select the control method for the unit. Because the dedicated ventilation cooling coil dehumidifies the outdoor air to cooling supply-air dew point and reheats it based on the worst-case room, or the dedicated ventilation heating coil heats the outdoor air to heating supply-air dry bulb, Optimize SADB will be used. CDS-PRM001-EN • TRACE 700 User’s Manual None – no dedicated ventilation unit Cool / heat – a dedicated ventilation unit is used to cool the outdoor air to the user-input cooling dry bulb during the cooling season, or heat the outdoor air to the user-input heating dry bulb during the heating season. Dehumidify (priority) or Cool / Heat – a dedicated ventilation unit is used to dehumidify the outdoor air to the user-input cooling dew point (not reheated) during the cooling season, or heat the outdoor air to the user-input heating dry bulb during the heating season. Dehumidify and Reheat / Heat – a dedicated ventilation unit is used to dehumidify the outdoor air to the user-input cooling dew point (then reheat it to the user-input cooling dry bulb) during the cooling season, or heat the outdoor air to the user-input heating dry bulb during the heating season. Note: For additional information related to the other Control Methods, press the F1 key and click Control Method. System Design Options Dedicated outdoor-air systems 4–63 4 Input the Cooling and Heating Design Setpoints. In this scenario, 55°F should be input for the cooling supply-air dew point, 55°F for the supply-air dry bulb low limit, and 70°F for the supply-air dry bulb high limit. 5 Select the schedule for the coils and fan in the dedicated outdoor-air unit. Note: If a custom schedule is created for the fan or coils, it is recommended to use values of 0 percent for hours off and 100 percent for hours available to run to avoid confusion. 6 Select the dedicated ventilation deck location. This tells TRACE 700 where to supply the preconditioned outdoor air. For this scenario, the outdoor air will be delivered directly to the spaces. As a result, Room Direct will be selected. 4–64 System Design Options Dedicated outdoor-air systems If the ventilation air is to be precooled, the Dedicated Ventilation Cooling Coil schedule defines the hours of available operation of the ventilation cooling coil. The optional ventilation cooling coil is available for any hour that this schedule reads 1 percent or greater. If the ventilation air is to be preheated, the Dedicated Ventilation Heating Coil schedule defines the hours of available operation of the ventilation heating coil. The optional ventilation heating coil is available for any hour that this schedule reads 1 percent or greater. The Optional ventilation fan schedule defines the hours that the ventilation unit can operate. If the Optional ventilation fan schedule reads 1 percent or greater, the fan is available that hour. Return/Outdoor Deck – conditioned outdoor air is mixed with the return air in the main unit(s). Plenum – conditioned outdoor air is delivered to the plenum above the spaces. Room Direct – conditioned outdoor air is delivered directly to the spaces. This can also be used to model the delivery of conditioned outdoor air to dual-duct VAV boxes where it mixes with conditioned recirculated return air. TRACE 700 User’s Manual • CDS-PRM001-EN 7 Select the level of the ventilation deck location. For this scenario, one large dedicated ventilation unit will condition the outdoor air for all of the rooms assigned to the Fan Coil system, so the coils should be set at the System level. Note: For additional details on Systems, refer to the System Type: Characteristics in online Help. System – The dedicated ventilation unit will be placed at the system level. It will pretreat the outdoor air for all of the rooms and zones assigned to the airside system. This is the most common choice for dedicated ventilation systems. The System Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Zone – Each zone (or room assigned directly to the system) will get a separate dedicated ventilation system. The Zone Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Room – Each room will get a separate dedicated ventilation system. The Room Checksums or System Component Selection reports should be used to size the dedicated ventilation unit. Same level as main cooling coil – The dedicated ventilation unit will be placed at the same level as the main cooling coil. The System Component Selection report should be used to size the dedicated ventilation unit. Same level as main heating coil – The dedicated ventilation unit will be placed at the same level as the main heating coil. The System Component Selection report should be used to size the dedicated ventilation unit. 8 On the Fans tab, input the fan type and the total static pressure for the primary fan (the fans in the Fan Coil units) and the optional ventilation fan (the fan in the dedicated ventilation unit). CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Dedicated outdoor-air systems 4–65 Next, define the cooling and heating plants represented by the fan coil system and the rooftop air conditioner. 9 Add two new cooling plants and two new heating plants to the Configuration pane. For cooling, use water-source hea pump and air-cooled unitary. For heating, use boiler (for the WS system) and gas-fired heat exchanger. 10Drag the appropriate icons from the Equipment Category section to define each plant. 11To finish defining this equipment, enter the information from Table 4–9 on page 4–66 on the appropriate equipment tab. Before… Finally, assign the coil loads of the air distribution system to the proper cooling and heating plants. After… 12Drag each coil in the Unassigned Systems/ Coils pane to the appropriate plant in the Systems and Plants pane. The illustration labeled “After” shows the completed assignments. Table 4–9 Equipment types 4–66 Cooling Equipment tab Heating Equipment tab Water-source heat pump 3-stage centrifugal chiller gas-fired hot water boiler Air-cooled unitary split system RAUC20+ ton scroll rooftop gas heat System Design Options Dedicated outdoor-air systems TRACE 700 User’s Manual • CDS-PRM001-EN