SINAMICS S120 DC Coupling of Booksize and Chassis Modules SINAMICS S120 https://support.industry.siemens.com/cs/ww/en/view/109757730 Siemens Industry Online Support Legal information Legal information Use of application examples Application examples illustrate the solution of automation tasks through an interaction of several components in the form of text, graphics and/or software modules. The application examples are a free service by Siemens AG and/or a subsidiary of Siemens AG (“Siemens”). They are nonbinding and make no claim to completeness or functionality regarding configuration and equipment. The application examples merely offer help with typical tasks; they do not constitute customer-specific solutions. You yourself are responsible for the proper and safe operation of the products in accordance with applicable regulations and must also check the function of the respective application example and customize it for your system. Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the application examples used by technically trained personnel. Any change to the application examples is your responsibility. Sharing the application examples with third parties or copying the application examples or excerpts thereof is permitted only in combination with your own products. The application examples are not required to undergo the customary tests and quality inspections of a chargeable product; they may have functional and performance defects as well as errors. It is your responsibility to use them in such a manner that any malfunctions that may occur do not result in property damage or injury to persons. Copyright Siemens AG 2018 All rights reserved Disclaimer of liability Siemens shall not assume any liability, for any legal reason whatsoever, including, without limitation, liability for the usability, availability, completeness and freedom from defects of the application examples as well as for related information, configuration and performance data and any damage caused thereby. This shall not apply in cases of mandatory liability, for example under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for damages arising from a breach of material contractual obligations shall however be limited to the foreseeable damage typical of the type of agreement, unless liability arises from intent or gross negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens against existing or future claims of third parties in this connection except where Siemens is mandatorily liable. By using the application examples you acknowledge that Siemens cannot be held liable for any damage beyond the liability provisions described. Other information Siemens reserves the right to make changes to the application examples at any time without notice. In case of discrepancies between the suggestions in the application examples and other Siemens publications such as catalogs, the content of the other documentation shall have precedence. The Siemens terms of use (https://support.industry.siemens.com) shall also apply. Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the Internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial security measures that may be implemented, please visit https://www.siemens.com/industrialsecurity. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed at: https://www.siemens.com/industrialsecurity. DC Coupling Booksize Chassis Entry -ID: 109757730, V1.2, May 2018 2 1 Introduction 1 Introduction SINAMICS S120 solves complex drive tasks for a wide range of industrial applications and is designed as a modular system. Users can select from many different harmonized components and functions to create a solution that best meets their requirements. SINAMICS S120 features Line and Motor Modules that cover a broad power range. They are available in different formats: Booksize Modules up to 120kW and Chassis Modules for larger power ranges. In several applications drives are required to be connected to a common DC bus, which allows cost-saving energy balancing between braking and driving axes. Any combination of modules within the existing families, e.g. Chassis Line Modules with any number of Chassis Motor Modules or Booksize Line Modules with any number of Booksize Motor Modules is already sufficiently qualified and described in the existing manuals. The relevant documents can be accessed at following address: https://support.industry.siemens.com/cs/ww/en/ps/13231/man?ml=en Copyright Siemens AG 2018 All rights reserved This document describes the connection of Chassis Line and Motor Modules and Booksize Motor Modules to one common DC bus. In the further text such a system may also be called mixed installation or mixed system. The existing manuals for the S120 system have to be observed as well. Mixed installation of S120 Booksize and Chassis Modules according to this application description is certified by UL (File.No. E192450 / Volume 5 /Section 23). The document is intended for both panel builders and field assembly. Installations that follow these instructions are UL listed and will not require procedure description in the industrial control panel builder report (UL508A and CSA C22.2 No.14). Some sections are marked as IEC requirements. These are not approved by UL. DC Coupling Booksize Chassis Entry -ID: 109757730, V1.2, May 2018 3 2 Overview Hardware Structure 2 Overview Hardware Structure An example of an application using Booksize Motor Modules together with Chassis Modules is shown in the picture below to explain the most important components involved. Details on those components are given in the next chapters. 1) Primary Circuit Conductor Protection Chassis Line Module 3.2 Line reactor DC fuse 3.1 M 3~ Chassis Motor Module M 3~ DC fuses are integrated in Smart Line Modules und Active Line Modules, but not integrated in Basic Line Modules 1) 3.3 Common DC busbar 510...720V DC 4.1.1 Connection from 4.1.1 Common DC Bus to DC Tap Conductor Protection EMC Filter Damping Filter Alternative to line reactor: Active Interface Module Only for Active Line Module 4.1.3 DC Tap Conductors to Motor Module 4.1.2 DC Tap Conductor Protection 4.1.3 4.1.4 DC link adapters 4.1.4 M 3~ M 3~ M 3~ Booksize Motor Module 4.1.2 Booksize Motor Module Group Copyright Siemens AG 2018 All rights reserved Line 3AC 380...480V 4.1.5 Grounding Conductors Picture 1: overview picture All components except the motors have to be located within a common enclosure, which is either a single enclosure or several enclosures mechanically attached such that no wiring between components (other than to the motor) is part of the installation wiring. DC Coupling Booksize Chassis Entry -ID: 109757730, V1.2, May 2018 4 3 System Components for common DC bus 3.1 Primary Circuit Conductor Protection 3 System Components for common DC bus 3.1 Primary Circuit Conductor Protection Primary circuit conductor protection fuses are listed in the manuals for Chassis Line Modules. These documents can be found at https://support.industry.siemens.com/cs/ww/en/view/109754207 for air cooled modules and at https://support.industry.siemens.com/cs/ww/en/view/109746526 for liquid cooled modules. Currently only semiconductor fuses are certified as Primary Circuit Conductor Protection for these Line Modules. The sizing of Primary Circuit Conductor Protection is not part of this document. Copyright Siemens AG 2018 All rights reserved 3.2 Line Modules (Converter Section) Table 1 shows all suitable Line Modules air cooled in Chassis format. If even larger power is required, Chassis Line Modules of any type (Active Line Module, Smart Line Module or Basic Line Module) can be connected in parallel. Only identical modules are permitted for this operation. Maximum number is limited to 4 units in parallel. All Line Modules have to be powered from the same source. Details on parallel connection can also be found in the manual for Chassis Line Modules. For proper and safe operation, line reactors in accordance with table 1 are required to be installed with every Basic or Smart Line Chassis Module as shown in picture 1. Active Line Modules are only permitted to be used together with Active Interface Modules. Line reactors and Active Interface Modules are shown in picture 1. Line Modules might be installed together with Line Connection Modules that are helpful for easier installation of line side components and fuses, details in https://support.industry.siemens.com/cs/ww/en/view/109749470 Abbreviations: BLM: Basic Line Module SLM: Smart Line Module ALM: Active Line Module AIM: Active Interface Module Line voltage Input frequency 380 V … 480 V 3-ph. AC 50 Hz … 60 Hz DC Coupling Booksize Chassis Entry -ID: 109757730, V1.2, May 2018 5 3 System Components for common DC bus 3.2 Line Modules (Converter Section) Copyright Siemens AG 2018 All rights reserved 3.2.1 Air Cooled Line Modules Article Number BLM 400V Chassis 6SL3330-1TE34-2AA3 6SL3330-1TE35-3AA3 6SL3330-1TE38-2AA3 6SL3330-1TE41-2AA3 6SL3330-1TE41-5AA3 6SL3330-1TE41-8AA3 SLM 400V Chassis 6SL3330-6TE35-5AA3 6SL3330-6TE37-3AA3 6SL3330-6TE41-1AA3 6SL3330-6TE41-3AA3 6SL3330-6TE41-7AA3 ALM 400V Chassis 6SL3330-7TE32-1AA3 6SL3330-7TE32-6AA3 6SL3330-7TE33-8AA3 6SL3330-7TE35-0AA3 6SL3330-7TE36-1AA3 6SL3330-7TE37-5AA3 6SL3330-7TE38-4AA3 6SL3330-7TE41-0AA3 6SL3330-7TE41-2AA3 6SL3330-7TE41-4AA3 Power Rating [kW] @400V AC current (line side) [A] 200 250 400 560 710 900 365 460 710 1010 1265 1630 250 355 500 630 800 463 614 883 1093 1430 132 160 235 300 380 450 500 630 800 900 210 260 380 490 605 745 840 985 1260 1405 DC current Line side power [A] components line reactor 420 6SL3000-0CE35-1AA0 530 6SL3000-0CE35-1AA0 820 6SL3000-0CE37-7AA0 1200 6SL3000-0CE41-0AA0 1500 6SL3000-0CE41-5AA0 1880 6SL3000-0CE41-6AA0 line reactor 550 6SL3000-0EE36-2AA0 730 6SL3000-0EE36-2AA0 1050 6SL3000-0EE38-8AA0 1300 6SL3000-0EE41-4AA0 1700 6SL3000-0EE41-4AA0 AIM 235 6SL3300-7TE32–6AA. 291 6SL3300-7TE32–6AA. 425 6SL3300-7TE33–8AA. 549 6SL3300-7TE35–0AA. 678 6SL3300-7TE38–4AA0 835 6SL3300-7TE38–4AA0 940 6SL3300-7TE38–4AA0 1103 6SL3300-7TE41–4AA0 1412 6SL3300-7TE41–4AA0 1574 6SL3300-7TE41–4AA0 Table 1: Air Cooled Line Modules ALM and SLM have integrated DC bus fuses, as shown in picture 1. BLM do not have DC bus fuses integrated. In case that BLMs are connected in parallel, separate DC bus fuses need to be installed for each BLM. The DC bus fuses as shown in table 2 shall be used. The fuses have to be installed for both, the positive and the negative conductor of the DC bus, between the output of each BLM and the common DC bus conductor. Article Number BLM 400V Chassis 6SL3330-1TE34-2AA3 6SL3330-1TE35-3AA3 6SL3330-1TE38-2AA3 6SL3330-1TE41-2AA3 6SL3330-1TE41-5AA3 6SL3330-1TE41-8AA3 Power Rating DC bus fuse for [kW] @400V IEC application Siemens 200 3NE3334-0B 250 3NE3336 400 3NE3333 560 3NE3337-8 710 3NE3340-8 900 3NE3337-8 number of DC bus fuse for UL fuses in parallel or IEC application Siemens 1 3NE3334-0B 1 3NE3336 2 3NB2350-4KK16 2 3NB2355-4KK16 2 3NB2364-4KK17 3 3NB2366-4KK17 Table 2: DC bus fuses for Basic Line Modules DC Coupling Booksize Chassis Entry -ID: 109757730, V1.2, May 2018 6 3 System Components for common DC bus 3.2 Line Modules (Converter Section) 3.2.2 Liquid Cooled Line Modules Article Number BLM 400V Chassis 6SL3335-1TE37-4AA3 6SL3335-1TE41-2AA3 6SL3335-1TE41-7AA3 ALM 400V Chassis 6SL3335-7TE35-0AA3 6SL3335-7TE36-1AA3 6SL3335-7TE38-4AA3 6SL3335-7TE41-0AA3 6SL3335-7TE41-4AA3 Power Rating [kW] @400V AC current (line side) [A] 360 600 830 610 1000 1420 300 380 500 630 900 490 605 840 985 1405 DC current Line side power [A] components line reactor 740 6SL3000-0CE36-3AA0 1220 6SL3000-0CE41-0AA0 1730 6SL3000-0CE41-5AA0 AIM 549 6SL3300-7TE35–0AA. 677 6SL3305-7TE38–4AA5 941 6SL3305-7TE38–4AA5 1100 6SL3305-7TE41–4AA5 1573 6SL3305-7TE41–4AA5 Table 3: Liquid Cooled Line Modules Copyright Siemens AG 2018 All rights reserved At liquid cooled Line Modules, ALM and BLM do not have DC bus fuses integrated. Separate DC bus fuses need to be installed for each module. Article Number BLM 400V Chassis 6SL3335-1TE37-4AA3 6SL3335-1TE41-2AA3 6SL3335-1TE41-7AA3 ALM 400V Chassis 6SL3335-7TE35-0AA3 6SL3335-7TE36-1AA3 6SL3335-7TE38-4AA3 6SL3335-7TE41-0AA3 6SL3335-7TE41-4AA3 Power Rating DC bus fuse for [kW] @400V IEC application Siemens 360 3NE3335 600 3NE3337-8 830 3NE3337-8 number of DC bus fuse for UL fuses in parallel or IEC application Siemens 2 3NB2345-4KK16 2 3NB2355-4KK16 3 3NB2366-4KK17 300 380 500 630 900 1 1 2 2 2 3NE3336 3NE3338-8 3NE3335 3NE3336 3NE3340-8 3NB23454KK16 3NB2345-4KK16 3NB2345-4KK16 3NB2355-4KK16 3NB2364-4KK17 Table 4: DC bus fuses for Basic Line Modules and Active Line Modules liquid cooled DC Coupling Booksize Chassis Entry -ID: 109757730, V1.2, May 2018 7 3 System Components for common DC bus 3.3 Common DC Busbars 3.3 Common DC Busbars In this application, the nominal DC bus voltage has to be between 510V and 720V DC. Active Line Modules must be configured that the maximum DC voltage is limited accordingly. Details about setting the parameters are given in the function manual and in the list manual. Function manual: https://support.industry.siemens.com/cs/ww/en/view/51677403/en List manual: https://support.industry.siemens.com/cs/ww/en/view/56745894/en Busbars connected to the Chassis Line Modules have to be Installed acc. to UL508A (internal wiring only, no field wiring) Protected against mechanical damage Copyright Siemens AG 2018 All rights reserved Example for DC busbars: Siemens Busbar System 8US Details about the Siemens busbar system and its components like connection modules, supports, covers etc. can be found in Siemens Industry Online Support (SIOS) https://support.industry.siemens.com/cs/products?search=8US%20busbar%20power%20distrib ution%20system&lc=en-WW The rated current of the busbars shall not be less than the rated DC current of the Line Module. If Line Modules are connected in parallel, the rated current of the busbar shall not be lower than the sum of the rated output currents of the Line Modules. The sum of the rated DC input currents of all Motor Modules that are connected to the busbars and running at the same time has to be considered as well. The ampacity of the busbars has to be calculated by the factor 2 2 1000A / in (1,55A / mm ). UL certified only if using the following components: Double-T Profile Part No. 8US1948-2AA00 nominal current 1400A Busbar supports: 8US1943-3AA00 Maximum spacing of busbar supports: 800mm For mechanical stability, all three profiles (busbars) have to be assembled. DC connection has to be done with the outer profiles. Once the installation is done with these components, a SCCR of 100kA for the whole system can be achieved. SCCR values of Line and Motor Modules or additional components might limit this to lower values. Other components or busbars with higher or lower current rating might be used as well. In this case, further UL investigation has to be done in the application. To connect the Line Modules to the busbar system the feeder lug 8US1941-2AA04 shall be used, which connects to busbars up to 32mm by 20mm. Together with this feeder lug, the cover 8US1922-1GC00 has to be used. DC Coupling Booksize Chassis Entry -ID: 109757730, V1.2, May 2018 8 4 Connection of Booksize Motor Modules 4.1 General 4 Connection of Booksize Motor Modules 4.1 General The connection of Booksize Motor Modules to the main DC link busbar (common DC bus conductor) requires additional components. The Motor Modules can be connected to the main DC link busbar individually or in groups. This chapter describes the general aspects. Specific selection tables are provided in subsequent chapters. 4.1.1 Connection from Common DC Bus to DC Tap Conductor Protection This connection can be made with either wires or busbars and has to be as short as possible Busbar connections to the DC Tap Conductor Protection Copyright Siemens AG 2018 All rights reserved Busbars can be connected by power terminal assemblies adapter number of terminals 1) 3 pole 8US1941-2AA04 1) Cover required 8US19 22-1GC00 busbar size up to 32 x 20mm 2 2 DC tap busbars shall be sized by the factor 1000A/in (1,55A/mm ). The nominal current of individual Motor Modules can be obtained from table 6, column DC current. Busbars for groups of Motor Modules have to be sized to the sum of the rated input DC currents of all Motor Modules installed in the Booksize Motor Module group and running at the same time. Wire connections to the DC Tap Conductor Protection The wires shall be connected by power terminal assemblies adapter 8US1921-1BA02 wire size mm 2 1,5…16 mm 2 wire size AWG AWG 14 … 6 2 8US1921-1CB02 6…50 mm AWG 10..2/0 2 8US1921-1AA00 35…120 mm AWG 2..250MCM 2) 2 8US1941-2AA03 95…300 mm 3/0…600MCM 2) Cover required 8US19 22-1GC00 current rating [A] 48 A 175 A 600 A 500 A note only up to 50kA SCCR - Table 5: Wire connections to the DC Tap Conductor Protection As a protection against short circuit one of the following measures must be implemented: use wires suitable for enhanced protection maintain adequate clearance, using spacers, for example route the wires in separate cable ducts or conduits The wires shall have a minimum temperature rating of 90°C and a minimum voltage rating of 600VAC. 4.1.2 DC Tap Conductor Protection These protection fuses provide two functions: 1. to limit a fault current in case of a failure in the Motor Module 2. to separate the fault from the remaining devices connected to the common DC bus in case of a failure, so the remaining drives may remain operational. DC Coupling Booksize Chassis Entry -ID: 109757730, V1.2, May 2018 9 4 Connection of Booksize Motor Modules 4.1 General There has to be one DC fuse for each tap conductor, the positive and the negative DC bus. Both fuses shall be identical i.e. shall have the same model number (means same manufacturer, type & rating). Always after the fault and correcting the root cause of the fault, both the fuses shall be replaced, even though only one of them has operated and opened to clear the fault, and the other appears intact. Only the DC fuses and fuse bases specified in table 6 in this manual shall be used. Other fuses shall not be used. These fuses provide short circuit protection only, overload protection is integrated into the power modules. 4.1.3 DC Tap Wires to the Motor Module The wires shall have a minimum temperature rating of 90°C and a minimum voltage rating of 600VAC. 4.1.4 DC link adapters Booksize Motor Modules have to be connected via DC link adapters. Cable lugs or the like shall not be used. Different adapters are available to connect individual Motor Modules or groups of Motor Modules. Copyright Siemens AG 2018 All rights reserved DC link adapters for individual Motor Modules 6SL3162-2BD00-0AA0, 2 2 wire size 0,5mm to 16mm (AWG 20 to 6) Rated current 43 A for 50mm and 100mm modules DC Coupling Booksize Chassis Entry -ID: 109757730, V1.2, May 2018 6SL3162-2BM00-0AA0, 2 2 wire size 35mm to 120mm (AWG 4 to 4/0) Rated current 200A (150A if only one screw is used for connection of DC link) for 150mm, 200mm and 300mm modules 10 4 Connection of Booksize Motor Modules 4.2 Connection of individual Booksize Motor Modules DC link adapters for groups of Motor Modules 6SL3162-2BM01-0AA0 2 2 Wire size: 35mm to 120mm (AWG 4 t 4/0) Rated Current: 200A (150A if only one screw is used for connection of DC link) Copyright Siemens AG 2018 All rights reserved 4.1.5 Grounding conductors According to the NEC (National Electrical Code), the protective conductor for each motor module has to be sized according to the upstream over-current protection device. See tables 6 and 7. IEC requirements for the minimum size of the grounding conductor can be found in the same 2 tables. Grounding conductor for IEC is sized according to I t let through values of the DC fuse. For IEC applications, protective connection via the mounting plate is possible. In this case, the notes on protective connection and equipotential bonding in section 12.9 of https://support.industry.siemens.com/cs/ww/en/view/109754297 or section 6.9 of https://support.industry.siemens.com/cs/ww/en/view/109751877 have to be observed. 4.2 Connection of individual Booksize Motor Modules Detailed information on the installation of Booksize Motor Modules can be found at https://support.industry.siemens.com/cs/ww/en/view/109740021 or https://support.industry.siemens.com/cs/ww/en/view/109480219 Table 6 shows the relevant data for the connection of Booksize Motor Modules to a common DC bus. DC Coupling Booksize Chassis Entry -ID: 109757730, V1.2, May 2018 11 4 Connection of Booksize Motor Modules 4.2 Connection of individual Booksize Motor Modules Copyright Siemens AG 2018 All rights reserved Article Number 2) 6SL312*- 1TE13-0A.. 1TE15-0A.. 1TE21-0A.. 1TE21-8A.. 1TE22-4A.. 1TE23-0A.. 1TE24-5A.. 1TE26-0A.. 1TE28-5A.. 1TE31-3A.. 1TE32-0A.. Current (Motor) AC [A] 3 5 9 18 24 30 45 60 85 132 200 Current DC DC [A] 3,3 5,6 10 20 26,4 33,3 54 72 104 162 200 DC fuse link order no. NomiWire size DC min. grounding Type: URS SQB1 nal Fuse base link (chapter conductor size 1250V current order no. 3.5 and 3.7) according to NEC 2 2 supplier: SIBA fuse supplier: SIBA AWG mm AWG mm 1) 20 71x 32.50 50 21 323 01 14 2,5 14 2,5 1) 20 71x 32.50 50 21 323 01 14 2,5 14 2,5 1) 20 71x 32.50 50 21 323 01 14 2,5 14 2,5 1) 20 71x 32.50 50 21 323 01 10 6 10 6 1) 20 71x 32.63 63 21 323 01 10 6 10 6 1) 20 71x 32.80 80 21 323 01 8 10 8 10 1) 20 71x 32.125 125 21 323 01 2 35 6 16 1) 20 71x 32.160 160 21 323 01 2 35 6 16 1) 20 71x 32.200 200 21 323 01 2 35 6 16 1) 20 71x 32.315 315 21 323 01 2/0 70 3 35 1) 20 71x 32.400 400 21 323 01 3/0 95 3 35 1) 6SL312*- 2TE13-0A.. 2x3 7,2 20 71x 32.50 50 21 323 01 14 2,5 14 2,5 1) 2TE15-0A.. 2x5 12 20 71x 32.50 50 21 323 01 14 2,5 14 2,5 1) 2TE21-0A.. 2x9 22 20 71x 32.50 50 21 323 01 10 6 10 6 1) 2TE21-8A.. 2x18 43 20 71x 32.100 100 21 323 01 8 10 8 10 1) x may be European standard: 3 for flap indicator, 4 for flap indicator with single bracket or 5 for central indicator US standard: 8 for central indicator or 9 without indicator 2) Any Motor Module can be used that is represented by “..” in the Article Number as long as it is rated for up to 720V DC * can be 0 for internal air cooled unit 1 for external air cooled unit 5 for liquid cooled unit min. grounding conductor size according to IEC 2 mm 1,5 1,5 1,5 1,5 1,5 2,5 2,5 2,5 2,5 6 6 1,5 1,5 1,5 2,5 Note: 6 for cold plate unit is not allowed Table 6 Connection of individual Booksize Motor Modules DC Coupling Booksize Chassis Entry-ID: 109757730, V1.2, May 2018 12 4 Connection of Booksize Motor Modules 4.3 Connection of Booksize Motor Module groups Booksize Motor Modules can be connected in groups combined on a separate part of the DC bus. In this case the DC bus included in the modules is used for electrical connection. There is no limitation regarding different types and number of motor modules that can be used for this application The rated DC current of the group is the sum of rated DC input currents of all motor modules installed in the group and running at the same time. The conductors and DC bus fuses must be selected according to the sum current. Table 7 shows the components to be installed based on the sum of the DC current in the group. The row with the next higher current shall be used. The sum current shall not exceed 200A. To connect the DC Tap Wires to a group of Booksize Motor Modules, the DC link adapter for side connection (6SL3162-2BM01-0AA0) must be used. The actual current rating of the internal DC link busbar of the individual Motor Modules must not be exceeded. Copyright Siemens AG 2018 All rights reserved Selection Table: Sum of DC current DC [A] 30 50 85 115 150 175 200 DC fuse link order no. Type: URS SQB1 1250V supplier: SIBA 1) 20 71x 32.80 1) 20 71x 32.100 1) 20 71x 32.160 1) 20 71x 32.250 1) 20 71x 32.315 1) 20 71x 32.350 1) 20 71x 32.400 1) x can be Fuse base order no. Grounding Rated Type: URS DC tap wire conductor current SQB1 size size NEC 2 2 fuse supplier: SIBA AWG mm AWG mm 80 21 323 01 2 35 8 10 100 21 323 01 2 35 8 10 160 21 323 01 2 35 6 16 250 21 323 01 2 35 4 25 315 21 323 01 1/0 70 3 35 350 21 323 01 2/0 70 3 35 400 21 323 01 3/0 95 3 35 Grounding conductor size IEC 2 mm 2,5 2,5 2,5 4 6 6 6 European standard: 3 for flap indicator, 4 for flap indicator with single bracket or 5 for central indicator US standard: 8 for central indicator or 9 without indicator Table 7: Connection of Booksize Motor Module groups DC Coupling Booksize Chassis Beitrags-ID: 109757730, V1.2, May 2018 13