Document generated 25 mayo 2018 01:34 (EST). LIEBERT DS CABINET DIMENSIONAL DATA UPFLOW AIR COOLED 35-42kW (10-12 TONS) W/ SCROLL OR DIGITAL SCROLL COMPRESSORS W/ EC FANS Alternate refrigerant piping entrance 33" 838mm 35" 889mm 5/16" 9mm Bezel High Volt Connection(s) 3 1/4" 83mm 1 3/4" 44mm Handle TOP VIEW Space required for EC Fan Plenum (shipped separately) dependent on height of plenum ordered. Low Volt Connection(s) 73" 1854mm 76" 1930mm 36" 914mm Shaded are indicates a recommended minimum clearance be provided for component access. Clearance required from floor to top of unit and plenum. 2" 51mm FRONT VIEW Form No.: DPN001040_REV4 72" 1829mm APPROXIMATE DRY WEIGHT lb (kg) 3 Air Cooled Dual Cool 1370 (621) 1520 (689) DPN003495 Page :1 /1 Notes: 1. Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN003974. 2. EC fans plenum is not shown. EC fans and plenum are shipped separately. See DPN003458 for unit dimensions with EC fans plenum mounted. 3. Fan weight not included in this unit weight. Fan is installed in plenum. REV : 3 REV DATE : 5/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT DS PRIMARY CONNECTION LOCATIONS UPFLOW AIR COOLED 35-42kW (10-12 TONS) SCROLL OR DIGITAL SCROLL COMPRESSOR MODELS W/ EC FANS ECR ECS 5 2 R1 O X HUM 2 R2 L1L2 35" 889mm CPD 3 EC Fan Outlet G1G2 Y E1 E2 Top View 2 R3 3 7/8" 98mm CGD 14 1/4" 362mm 17 1/8" 434mm 4 9 7/8" 251mm 1 73" 1854mm FRONT OF UNIT LV1 LV2 LV3 L1L2 G1 G2 6 4 CGD Front View (Left Panel Not Shown) Left Side View Notes: 1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm). 2. Field routed alternatives for refrigerant gas & liquid line connection points. 3. EC fan shown. See submittal page DPN003458 for EC fan outlet & plenum dimensional data. 4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes. 5. Supplied on Dual Cooling Systems only. Form No.: DPN001040_REV4 6. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top. POINT R1 R2 R3 L1 L2 G1 G2 CGD CPD HUM ECS ECR E1 E2 LV1 LV2 LV3 DESCRIPTION X in. (mm) REFRIGERANT ACCESS (TOP) 2 60-5/8 (1540) REFRIGERANT ACCESS (BOTTOM) 2 63 (1600) REFRIGERANT ACCESS (SIDE) 2 N/A LIQUID LINE SYSTEM 1 79-3/16 (2011) LIQUID LINE SYSTEM 2 76-1/2 (1943) HOT GAS DISCHARGE 1 6 73-7/8 (1876) HOT GAS DISCHARGE 2 6 70-1/8 (1781) CONDENSATE GRAVITY DRAIN 4 N/A CONDENSATE PUMP DISCHARGE (OPT) 56-1/4 (1429) HUMIDIFIER SUPPLY LINE ECON-O-COIL SUPPLY 5 56 (1422) ECON-O-COIL RETURN 5 52-3/8 (1330) ELECTRICAL CONN. (HIGH VOLT) 47-3/8 (1203) ELECTRICAL CONN. (LOW VOLT) DPN002740 Page :1 /1 8-1/8 (206) Y in. (mm) 2-13/16 (71) 13-13/16 (351) N/A CONNECTION SIZE / OPENING 10-1/8" (257mm) X 4-1/8" (105mm) 16-7/16" (418mm) X 4" (102mm) 6" (152mm) X 17-3/16" (437mm) 16-3/4 (425) 1/2" O.D. Cu 16-5/8 (422) 5/8" O.D. Cu N/A 11-1/8 (283) 9-1/8 (232) 7-5/16 (186) 4-1/2 (114) 3/4" NPT FEMALE 1/2" O.D. Cu 1/4" O.D. Cu 29-15/16 (760) 2-1/2" 29-9/16 (751) 31 (787) 32-7/16 (824) 7/8" 1-5/8" O.D. Cu REV : 3 REV DATE : 5/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT DS DISASSEMBLY DIMENSIONAL DATA UPFLOW 35-42kW (10-12 TONS) MODELS W/ SCROLL & DIGITAL SCROLL COMPRESSORS Unit w/ Scroll/Digital Scroll Compressor Section BLOWER & ELECTRIC BOX ASSEMBLY Compressor Section Assembly 31 1/4" 794mm FILTER & COIL ASSEMBLY 76" 1930mm Assembled Height 76" 1930mm 45 13/16" 1163mm 33" 838mm 59" 1499mm A B Assembled Length Cooling Ty pe A in (mm) B in. (mm) Air Cooled 13 (330) Air Cooled w / Dual Cool Water/Gly col 26 (660) GLYCOOL™/Dual Cool 72 (1829) 85 (2159) Assembly Compressor Assembly APPROXIMATE DRY WEIGHT lb (kg) (Includes Panels) Air Cooled A/C w / Dual Cool Water/Gly col GLYCOOL™/Dual Cool 490 (223) 490 (223) 800 (364) 800 (364) 510 (231) 510 (231) 510 (231) 510 (231) EC Fan & 2 Electric Box Assembly 360 (163) 360 (163) 360 (163) 360 (163) Filter & Coil Assembly 520 (236) 670 (304) 520 (236) 670 (304) Forw ard Curv ed Blow er & Electric Box Assembly Form No.: DPN001040_REV4 Notes: 1. Drawing Views are simplified with panels removed to show overall dimensions. See disassembly and handling instructions in installation manual. EC Fan unit shown. 2. EC Fan wieght not included in this unit weight. Fan is installed in plenum. See DPN003458. DPN003650 Page :1 /1 REV : 3 REV DATE : 5/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT DS PIPING SCHEMATIC W/ LIEBERT MC CONDENSER AIR COOLED SCROLL OR DIGITAL SCROLL COMPRESSOR MODELS Optional Field Installed Fusible Plug Pressure Transducer Check Valve Relief Valve Head Pressure Control Valve Service Valve LIQUID RETURN Pressure Transducer LEE-TEMP RECEIVER Check Valve CONDENSER COIL (Includes factory provided inverted trap. No external trap required) CONDENSER COIL (Includes factory provided inverted trap. No external trap required) LIEBERT MC CONDENSER HOT GAS DISCHARGE LIEBERT MC CONDENSER WITH LEE-TEMP OPTION LIEBERT DS LIQUID Sensing Bulb 35-42kW digital Solenoid Valve SUCTION 53-70kW digital Solenoid Valve Service Valve Check Valve EVAPORATOR COIL 3 For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided 3 COMPRESSOR Service Valve External Equalizer Field installed relief valve(s) required for 50Hz EU CE units rated maximum 480 PSIG (33 Bar). HOT GAS DISCHARGE Sight Expansion Solenoid Glass Valve Valve OPTIONAL FACTORY PIPING FACTORY REFRIGERANT PIPING FIELD PIPING Filter Drier INTERCONNECTING PIPING LIQUID LINE SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE 3 Trap at base of risers over 5ft. (1.5m) SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE Notes: 1. Single refirigeration circuit shown for clarity. 2. Schematic representation shown. Do not use for specific connection locations. Form No.: DPN001040_REV4 3. Components are not supplied by Liebert, but are required for proper operation and maintenance. 4. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow. 5. Do not isolate any refrigerant circuits from over pressurization protection. DPN003730 Page :1 /1 REV : 3 REV DATE : 12/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT DS ELECTRICAL FIELD CONNECTION DESCRIPTION UPFLOW AND DOWNFLOW MODELS STANDARD ELECTRICAL CONNECTIONS 1) Primary high voltage entrance - 2.50” (64mm); 1.75” (44mm); 1.375” (35mm) diameter concentric knockouts located in bottom of box 2) Secondary high voltage entrance - 2.50” (64mm); 1.75” (44mm); 1.375” (35mm) diameter concentric knockouts located in top of box 3) Primary low voltage entrance - Quantity (3) 1.375” (35mm) diameter knockouts located in bottom of unit 4) Secondary low voltage entrance - Quantity (3) 1. 375” (35mm) diameter knockouts located in top of box 5) Three phase electrical service - Terminals are on main fuse block (disregard if unit has optional disconnect switch). Three phase service not by Liebert. 6) Earth ground - Terminal for field supplied earth grounding wire. Earth grounding required for Liebert units. 7) Remote unit shutdown - Replace existing jumper between terminals 37 & 38 with field supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring. 8) Customer alarm inputs - Terminals for field supplied, normally open contacts, having a minimum 75VA, 24VAC rating, between terminals 24 & 50, 51, 55, 56. Use field supplied Class 1 wiring. Terminal availability varies by unit options. 9) Common alarm - On any alarm, normally open dry contact is closed across terminals 75 & 76 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. 10) Heat rejection interlock - On any call for compressor operation, normally open dry contact is closed across terminals 70 & 71(circuit 1), 230 (circuit 2) to heat rejection equipment. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. When DS unit is paired with a Liebert MC series condenser, remove jumper between terminal 71 and terminal 230. Three wires must connect terminals 70, 71 and 230 of the indoor unit to terminals 70, 71 and 230 of the Liebert MC series condenser. 11) Unit factory installed disconnect switch, Fuse Block and Main Fuses – “Locking Type” consists of a non-automatic molded case switch operational from the outside of the unit. Access to the high voltage electric panel compartment can be obtained only with the switch in the “off” position. Units with fused disconnects are provided with a defeater button that allows access to the electrical panel when power is on. The molded case switch disconnect models contain separate main fuses. Form No.: DPN001040_REV4 CANBUS ELECTRICAL CONNECTIONS 12) CANbus Connector– Terminal block with terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH (shield connection). The terminals are used to connect the CANbus communication cable (provided by others) from the indoor unit to the Liebert MC Condenser –Optional Econophase Unit. 13) CANbus Cable – CANbus cable provided by others to connect to the outdoor condenser, and optional PRE unit (DA units only). No special considerations are required when the total external cable connection between the indoor unit and outdoor unit(s) is less than 450FT (137M). For total external cable connections greater than 450FT (137M) but less than 800FT (243M) a CANbus isolator is required. Contact Factory. Cable must have the following specifications: Braided shield or foil shield with drain wire - Shield must be wired to ground at indoor unit - 22-18AWG stranded tinned copper - Twisted pair (minimum 4 twists per foot) - Low Capacitance (15pF/FT or less) - Must be rated to meet local codes and conditions - EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER 14) Do not run in same conduit, raceway, or chase as high voltage wiring. 15) For CANbus network lengths greater than 450FT (137M) call Factory. DPN000807 Page :1 /3 REV : 17 REV DATE : 10/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT DS ELECTRICAL FIELD CONNECTION DESCRIPTION UPFLOW AND DOWNFLOW MODELS OPTIONAL ELECTRICAL CONNECTIONS 16) Smoke sensor alarm - Factory wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-NC. Supervised contacts, 80 & 81, open on sensor trouble indication. This smoke sensor is not intended to function as, or replace, any room smoke detection system that may be required by local or national codes. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. 17) Reheat and humidifier lockout - Remote 24VAC required at terminals 82 & 83 for lockout of reheat and humidifier. 18) Condensate alarm (with condensate pump option) - On pump high water indication, normally open dry contact is closed across terminals 88 & 89 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. 19) Remote humidifier - On any call for humidification, normally open dry contact is closed across terminals 11 & 12 to signal field supplied remote humidifier. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. 20) Auxiliary cool contact - On any call for econ-o-coil operation, normally open dry contact is closed across terminals 72 & 73 on dual cool units only. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. Form No.: DPN001040_REV4 OPTIONAL LOW VOLTAGE TERMINAL PACKAGE CONNECTIONS 21) Remote unit shutdown - Two additional contact pairs available for unit shutdown (labeled as 37B & 38B, 37C & 38C). Replace jumpers with field supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring. 22) Common alarm - On any alarm, two additional normally open dry contacts are closed across terminals 94 & 95 and 96 & 97 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. 23) Main fan auxiliary switch - On closure of main fan contactor, normally open dry contact is closed across terminals 84 & 85 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. 24) LiquiTect shutdown and dry contact - On LiquiTect activation, normally open dry contact is closed across terminals 58 & 59 for remote indication (LiquiTect sensor ordered separately). 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. NOTE: Refer to specification sheet for total unit full load amps, wire size amps, and max overcurrent protective device size. DPN000807 Page :2 /3 REV : 17 REV DATE : 10/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT DS ELECTRICAL FIELD CONNECTION DESCRIPTION UPFLOW AND DOWNFLOW MODELS 2 OVERCURRENT PROTECTION DEVICES Intellislot Housing 4 A B C D 5 Alternate Location 60 Hz P64 6 CONTACTORS P67 CONTACTORS, RELAYS, & OVERLOAD PROTECTORS 11 5 1 6 E 3 50Hz only DOWNFLOW LOW VOLT SECTION Note: Typical orientation of components shown. Component location varies by option and unit size. 18 17 82 83 88 89 9 16 22 19 CAUTION: 75 76 94 95 96 97 91 92 93 80 81 11 12 UPFLOW 3 B A 24 Risk of broken or shorted low volt wiring. Field installed low volt wiring must be routed with loop as shown to allow electric box to swing. 23 58 59 84 85 21 7 10 8 20 37C38C37B38B 37 38 24 50 51 55 56 70 71 230 72 73 D B C D 12 49-3 49-1 SH C A Form No.: DPN001040_REV4 13 Item 13 Installation Conditions E 1. Follow all local installation codes. 2. Do not run CAN cables in same conduit, raceway, or chase as high voltage wires (120-600V). 3. Separate high volt wires from CAN wires by 12 inches. E POINT OF HINGED LOW VOLT ELECTRIC BOX UPFLOW LOW VOLT SECTION DPN000807 Page :3 /3 REV : 17 REV DATE : 10/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT DS PLENUM DIMENSIONAL DATA UPFLOW 35-42kW (10-12 TONS) MODELS W/ EC FANS Notes: 1. All Plenums must be field assembled and EC Fans wired to unit. 7/8" 22mm D 2. Shaded areas indicate a recommended minimum CLEARANCE OF 36" (914mm) from the bottom of the unit to the top of the plenum. 3. Must have access to remove Front Grill or panel to remove EC Fans. 4 C 4. Top duct flanges on plenum top for Supply Air ducting when solid panel plenum is used. 5. Compressor Plenum is optional and must be ordered separately. 6. Air Cooled Scroll or Digital Scroll Compressor. J G 7. Water Cooled Scroll or Digital Scroll Compressor. H L 3 F K 5 E 7/8" 22mm Note: Both top duct opening and grilles shown. See spec sheet for specific application. A F 2 B No. of Fans/Unit 1 EC Fan Assembly Weight lb. (kg) VS028-VS035 VS042 119 (54) 141 (64) Form No.: DPN001040_REV4 Main unit Main Unit Plenum Weight lb. (kg) Plenum Height J Non-grilled Plenum Front Discharge Rear Discharge in. (mm) 24 (610) 85 (39) 126 (57) 29 (59) 30 (762) 105 (48) N/A 36 (914) 123 (56) A 59-1/4 (1505) DPN003458 Page :1 /1 B 33-3/4 (857) C 57-9/16 (1463) Plenum Dimensional Data in. (mm) D E 32-1/16 (815) 56-11/16 (1440) Compressor Plenum Width Height Weight L K lb. (kg) in. (mm) in. (mm) 24 (610) 24 (11) 13 (330) 30 (762) 26 (12) 36 (914) 29 (13) 6 24 (610) 33 (15) 26 (660) 30 (762) 37 (17) 36 (914) 42 (19) 7 F 1-5/16 (33) G 19-11/16 (500) H 4-5/16 (109) REV : 4 REV DATE : 5/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT iCOM™ PRODUCT INFORMATION UNIT MOUNTED DISPLAY The Liebert iCOM™ display is a microprocessor 9 inch color touch screen in an ergonomic, aesthetically pleasing housing. The display and housing will be viewable while the unit accent panels are open or closed. The display can be easily detached to view while the panel is open. Menu Layout- The menus will be broken out into two main menu screens: User screen and Service screen. The User screen contains the menus to access parameters required for basic unit control and setup. The Service screen is designed for service personal and provides access to advanced control setup features and diagnostic information. Password Protection- The display will contain two unique passwords to protect against unauthorized changes. An auto hide/show feature allows the user to see applicable information based on the login used. Unit Backup and Restore- The user shall have the ability to create safety copies of important control parameters. The display has the ability for the user to automatically backup unit configuration settings to internal memory or USB storage drive. Configuration settings may be transferred to another unit for a more streamlined unit startup. Parameter Download- The display has the ability for the user to download a report that lists parameter names, factory default settings and user programmed settings in .csv format for remote reference. Parameter Search- The display has search fields for efficient navigation and parameter lookup. Form No.: DPN001040_REV4 Setup Wizards- The display will contain step by step tutorials or wizards to provide easy setup of the control. DPN003245 Page :1 /2 REV : 5 REV DATE : 7/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT iCOM™ PRODUCT INFORMATION UNIT MOUNTED DISPLAY Context Sensitive Help- The display will have an onboard help database. The database will provide context sensitive help to assist with setup and navigation of the menus. Display Setup- The user has the ability to configure the display information based on the specific user’s preference. Language, units of measure, screen contrast, home screen layout, back light timer and the hide/show of certain readouts will be configurable through the display. Additional Readouts- The display has the ability for the user to configure custom widgets on the main screen. Widget options will include items such as fan speed, call for cooling, call for free cooling, maintenance status, call for hot water reheat, call for electric reheat, call for dehumidification, call for humidification, airflow, static pressure, fluid flow rate and cooling capacity. Status LEDs- The display will provide the user with the unit’s operating status using an integrated LED. The LED will indicate if the unit has an active alarm; if the unit has an active alarm that has been acknowledged; or if the unit is on, off, or in a standby status. Unit Alarms – All unit alarms are annunciated through both audio and visual cues, clearly displayed on the screen, automatically recorded in the event log, and communicated to optional IntelliSlot monitoring cards. Event Log – The display will automatically store the last 400 unit-only events (messages, warnings, and alarms). Service Contact Information – The display has the ability to store the local service or sales contact information. Upgradeable –Display upgrades are performed through a USB connection. Form No.: DPN001040_REV4 Unit-to-Unit (U2U) Communication – Communication via private Ethernet network allows for advanced control functionality (Teamwork modes, sharing sensor data, Standby Rotation, Lead-Lag, and Cascade operation). DPN003245 Page :2 /2 REV : 5 REV DATE : 7/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT CW, DS, DSE, PDX & PCW UNIT TO UNIT NETWORK CONNECTIONS ETHERNET CABLE (FIELD SUPPLIED) DO NOT USE CANBUS CONNECTORS TO P42 ETHERNET CABLE P61 P63 P64 E5 U2U NETWORKING SWITCH (FIELD SUPPLIED) Form No.: DPN001040_REV4 P11 P7 P13 iCOM I/O BOARD P12 P66 P67 P65 DPN003729 Page :1 /2 TO / FROM OTHER NETWORKED UNITS REV : 1 REV DATE : 1/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT CW, DS, DSE, PDX & PCW UNIT TO UNIT NETWORK CONNECTIONS DO NOT USE CANBUS CONNECTORS DO NOT USE CANBUS CONNECTORS ETHERNET CABLE (FIELD SUPPLIED) TO P42 TO P42 ETHERNET CABLE ETHERNET CABLE P61 P64 P63 P64 E5 E5 Form No.: DPN001040_REV4 P66 P7 P7 iCOM I/O BOARD P12 P11 P13 iCOM I/O BOARD P12 P66 P67 P65 P67 P65 P11 P63 P13 P61 DPN003729 Page :2 /2 REV : 1 REV DATE : 1/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT® LIQUI-TECT® 410 POINT LEAK-DETECTION SENSOR Product Specification/Installation Guide The Liebert Liqui-tect 410 (LT410) provides single-point detection of leaks. The point-detection sensor has two gold-plated sensing probes to prevent corrosion and to provide accurate readings. The LT410 constantly monitors for leaks, internal faults, and power failures and warns of any abnormal conditions. Mounting brackets allow for sensor height adjustment and leveling. The LT410 is the ideal solution for sensing leaks under a raised computer floor or air conditioning drip pans. Two independent outputs provide added flexibility with the capacity to signal both a local alarm panel and a remote building-management system or external equipment, such as motorized water shut-off valves. LT410 APPLICATIONS The LT410 is ideally-suited for: • Glycol and chilled-water cooling, • Humidification supply water piping, • Condensate pumps and drains, • Unit and ceiling auxillary drip pans, • Overhead piping troughs. LOCATIONS/PLACEMENT The LT410 is an excellent choice for: COMPONENTS OF THE LIQUI-TECT 410 MODULE The LT410 consists of a metal enclosure with a hinged top door that provides access to the internal wiring termination. It includes side access through a box connector for installation of the power and contact wiring. The mounting brackets attach to the enclosure with adjustable slots to allow custom setting of the height of the sensing probes. • Large-scale network control centers, • Data centers, • Server rooms and closets, • Unattended, remote shelters, • Mechanical equipment rooms, • Sensitive areas with overhead piping, • Industrial process-control rooms. 590-1351-501B/SL-31050_REV2_6-17 1 Document generated 25 mayo 2018 01:34 (EST). LIEBERT® LT410 POINT LEAK-DETECTION SENSOR Product Specification/Installation Guide DIMENSIONS TOP, FRONT AND SIDE TOP VIEW 5.85” (148.5mm) FRONT VIEW SIDE VIEW 4.46” (113.2mm) Form-C relay outputs and power wiring 6.35” (161.2mm) Adjustable probe height 0.0 - 0.5” (0.0 - 12.7mm) SPECIFICATIONS Power Requirements 24 VAC 100 mA, 50/60 Hz, 3 VA (max.) Dimensions, W x D x H 6.35 x 2.25 x 4.46 in (161.2 x 57.2 x 113.2 mm) Weight (assembled) 2.0 lb (0.9 kg) Metal Enclosure NEMA 1, IP 30 ENVIRONMENTAL CONDITIONS Operating Temperature 50°F to 104°F (10°C to 40°C) Operating Humidity 10% to 95% relative humidity (non-condensing) Operating Altitude 0 to 10,000 ft (0 to 3,048 m) Output Relay Contact Rating 2 Form-C; 3 A rating at 24 VAC AGENCY LISTINGS UL UL916 C-UL C22.2, No. 205-M1983 CE Yes FCC Compliance 47 CFR, Part 15 590-1351-501B/SL-31050_REV2_6-17 2 2.25” (57.2mm) Document generated 25 mayo 2018 01:34 (EST). LIEBERT® LT410 POINT LEAK-DETECTION SENSOR Product Specification/Installation Guide PLACEMENT ON SUBFLOOR UNDER COOLING SUPPORT EQUIPMENT To a Liebert environmental unit and an optional monitoring panel To external power supply or directly from unit (see Power Wiring on page 4) 2-COM 2-NC 2-NO 1-COM 1-NC 1-NO POWER POWER Leak detection zone (directly beneath unit) WIRING INTERCONNECTIONS Circuits are shown in powered, non-alarm state. NOTE: All power and alarm connections must be Class 2 circuits. Gold-plated Probes Height adjustable 0-0.5” (0-12.7mm) Red Wires Orange Wires Yellow Wires 24 V, AC/DC @ 0.10A, 50-60 Hz, DC Class 2 Circuit Only Alarm Contact Rating 24 VAC @ 3A Class 2 Circuit Only Alarm Contact Rating 24 VAC @ 3A Class 2 Circuit Only 590-1351-501B/SL-31050_REV2_6-17 3 Document generated 25 mayo 2018 01:34 (EST). LIEBERT® LT410 POINT LEAK-DETECTION SENSOR Product Specification/Installation Guide POWER WIRING WIRING TO AUXILIARY ALARM PANELS The LT410 is rated for 24 VAC, 50/60 Hz, and 0.10 A. The LT410 has two Form-C dry contact alarm output contacts: orange wires (1) and yellow wires (2). Each contact is rated for 24 VAC at 3 amp. Liebert DS, DSE, CW, PDX, or Mini-Mate2 (8 ton) LT410 TB1TB1 T5 (24V) G5 (Ground) Red Location of T5 (24V) connection on main controller board of Liebert unit. TB1 Red Liebert Mini-Mate2 (1 to 5 ton) Orange Wires Environmental Unit 1-NC 1-COM 1-NO LT410 Orange Wires Environmental Unit 1-NC 1-COM Red From 24V Transformer Red 1-NO * Requires external transformer (there are no designated terminal Orange Wires connections on the unit) Liebert CRV Medium Control Board LT410 TB1 6 Red 4 Red 50, 51, 55 or 56 Liebert Mini-Mate2, (1 to 5 ton) TB1 24 (24V) Note: Terminal 50 not available on Mini-Mate2 (8-ton) LT410 Liebert DS, DSE, LT410CW, PDX or Mini-Mate2 (8 ton) LT410 TB1-1 (24V) TB1-2 or TB1-3 Liebert CRV Environmental Unit 1-NC 1-COM 60 1-NO 61 NOTE: In iCOM, use the Service Options menu to add that the Liqui-tect is installed. LT410Liebert contact monitor panel Transformer LT410 TB1 Red From 24V Transformer Red VertivCo.com Yellow Wires 2-NC Alarm Panel 2-COM 2-NO | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice. 590-1351-501B/SL-31050_REV2_6-17 4 Input Contact (N.O.) Document generated 25 mayo 2018 01:34 (EST). LIEBERT® INTELLISLOT™ UNITY PLATFORM CARDS Product Specification/Installation Guide The Liebert IntelliSlot Unity Platform brings SNMP, BACnet IP, BACnet MSTP, Modbus TCP, Modbus RTU, YDN23 and Web management capability to many models of Vertiv’s power and cooling equipment. The cards employ Ethernet and RS-485 networks to monitor and manage a wide range of operating parameters, alarms and notifications. The card also supports communication for LIFE™ Services by VERTIV. ADDITIONAL FEATURES • SNMPv1, SNMPv2c and SNMPv3 with MIB-II support • HTTP/HTTPS 1.1 • BootP • DHCP per RFC2131/2132 • Remote firmware updates via a Web browser • IPv6 support for HTTP/HTTPS, DHCPv6, e-mail, SMS, SNMP v1/v2c/ v3 and Modbus TCP • Liebert SN Environmental Sensor Support (Web, SNMP, SMS and SMTP): Temperature, Humidity, Door Closure, Contact Closure and Leak Detection: Liebert SN-2D, Liebert SN-3C, Liebert SN-L, Liebert SN-T, Liebert SN-TH, Liebert SN-Z01, Liebert SN-Z02 and Liebert SN-Z03 IntelliSlot Unity cards are a form, fit, and function replacement for several Liebert IntelliSlot Web and 485 cards. COMPATABILITY with Liebert Equipment IntellSlot Card Compatible with IS-UNITY-DP Alber BDSU-50™ Liebert Deluxe System/3™ Liebert GXT3™ Liebert PeX™ * IS-UNITY-SNMP Liebert APM™ Liebert DS™ Liebert GXT4™ Liebert PPC™ IS-UNITY-LIFE Liebert APS™ Liebert DSE™ Liebert HPC™ Liebert RDC™ Liebert Challenger Liebert EPM™ Liebert HPC-S/M/R/W/Generic™ Liebert RX™ 3000™ Liebert EXC™ Liebert HPM™ Liebert XDC™ Liebert CRV™ Liebert eXL™ Liebert NX™ 225-600 kVA Liebert XDP™ Liebert CW™ Liebert EXL™ S1 Liebert NXC™ Liebert XDP-Cray™ Liebert DCL™ Liebert eXM™ Liebert NXL™ * Liebert DCP™ Liebert FDC™ Liebert NXR™ Liebert FPC™ Liebert PCW™/PDX™ * YDN23 supported only for Liebert PeX and Liebert NXL. 590-1307-501C/SL-52646_REV11_6-17 1 Document generated 25 mayo 2018 01:34 (EST). LIEBERT® INTELLISLOT™ UNITY PLATFORM CARDS Product Specification/Installation Guide COMPATABILITY with Communication Protocols Life Services Support Liebert IntelliSlot Card Communication Protocol HTTP HTTPS Velocity Protocol Email SMS SNMP v1, v2c, v3 BACnet IP BACnet MSTP Modbus TCP Modbus RTU YDN23* — — — — — — IS-UNITY-DP IS-UNITY-SNMP IS-UNITY-LIFE — * YDN23 supported only for Liebert PeX and Liebert NXL. 4-3/4” (121 mm) DIMENSIONS 1/2” (11 mm) 3” (76 mm) 2-3/8” (60.3 mm) 1-1/2” (38 mm) Front face SPECIFICATIONS Power Requirements Board DC Inputs 7 to 12 VDC Power Consumptions: 3.6 W maximum Dimensions, W x D x H 2.97 x 5.2 x 1.45 in. (75.5 x 15 x 37 mm) Weight (assembled) Net: 7 oz (0.2 kg) Shipping: 1.3 lb (0.6 kg) Ambient Operating Environment 32 to 104°F (0 to 40°C); 10% to 90% RH (non-condensing) Ambient Storage Temperature –4 to 140°F (–20 to 60°C) Communication Ports Ethernet Communication RJ-45 (LIFE™ Services requires a network connection to the Internet) RJ-45 (RJ-45 to 2-position terminal-block adapter) WIRING 10/100 Mb/s Ethernet connector Standard Category 5E Cable 328 ft. (100m) RJ-45 - One-Wire Connector Liebert® Integrated One-Wire Sensor Cable or 2m Cat 5E to Modular 1-Wire 65.6 ft. (20m) VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice. 590-1307-501C/SL-52646_REV11_6-17 2 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER PREMIUM EFFICIENCY CONTROL STANDARD & OPTIONAL FEATURES Form No.: DPN001040_REV4 STANDARD FEATURES COIL Liebert microchannel coils are all‐aluminum construction. Tubes are created by extruding small parallel refrigerant flow paths into aluminum. Full‐depth louvered aluminum fins fill spaces between the tubes. Tubes, fins and aluminum headers are oven‐brazed to form a complete refrigerant‐to‐air heat exchange coil. Baffles are used in the headers to separate one coil slab into multiple passes as needed. Coils are factory leak tested at a minimum of 300 PSIG and dehydrated. Copper stub pipes are electric resistance welded to aluminum coils and joints are protected with polyolefin to seal joint from environmental corrosive elements. Hot gas and liquid lines are brazed to the stub pipes with spun closed ends for customer piping connections. Coil pipe assembles are filled and sealed with a nitrogen holding charge for shipment. One coil is used per fan assembly. FAN/MOTOR ASSEMBLY The fan/motor assembly is complete with external rotor motor, fan blades and fan/finger guard. Fan blades are constructed of stamped aluminum or steel extrusion coated with PP plastic. Fan guards are heavy gauge, close meshed, steel wire, coated with a black corrosion resistant finish. Fan terminal blocks located on the top of the fan guard with IP54 protection class. Fans are factory balanced and tested before shipment. FAN MOTORS Fan motors are specifically designed for variable speed and have ball bearings. The EC fans provide internal overload protection through the built‐in electronics. Each EC fan motor has built‐in controller and communication module, linked via RS485 communication wire to each fan and the Premium Control Board. This allows each fan to receive and respond to precise fan speed inputs from the Premium control board. PREMIUM EFFICIENCY FAN CONTROL The Liebert premium efficiency condenser control system is complete with control board, EC fan motor(s),refrigerant‐pressure transducer(s), refrigerant‐temperature thermistor(s), ambient‐temperature thermistor, and motor overload protection in the factory wired control panel. The control board maintains EC fans on the same circuit to the same speed in order to maintain refrigerant head pressure. The control board receives a run signal from the compressor of the indoor unit via field‐supplied low voltage interlock wires and field‐supplied CANbus communication wires from the indoor unit iCOM. The control system provides refrigerant head pressure and system starting for outdoor ambient temperature as low as -30°F (‐35 °C), provided the total temperature design range (from minimum to maximum) is 125°F (70°C) or less. HOUSING The condenser housing is constructed of bright aluminum sheet and divided into individual fan sections by full width baffles. Internal structural support members, including coil support frame, are galvanized steel for strength and corrosion resistance. Panel doors are provided on two sides of each coil/fan section to provide for coil cleaning. Aluminum legs are provided with rigging holes for hoisting the unit into position. COMMUNICATION The Premium Efficiency Control communicates with the iCOM control of the indoor Liebert unit using field supplied CANbus wires. The communication link allows for condenser alarm condition communication to iCOM, communication of other measurable items on the condenser, and fan control features to improve efficiency, sound and wintertime operation based on iCOM programming. UNIT DISCONNECT SWITCH Locking unit disconnect switch is factory installed and wired in attached condenser control section. OPTIONAL FEATURES LIEBERT LEE‐TEMP LOW AMBIENT CONTROL Lee‐Temp receiver kits can be added to achieve head pressure control down to minimum ambient temperatures of ‐30 °F (‐34 °C). The premium efficiency fan control when used with the Liebert Lee‐Temp receiver kits runs the fan(s) at lower speeds during cold temperatures saving fan energy. 575V POWER SUPPLY The factory installed condenser option will include a secondary enclosure, a 575V-to-480V, 3 phase, step down transformer, secondary fuses for the transformer, and all wiring between the main and secondary electrical enclosures. Site power connections will be made in the main electrical enclosure and the secondary enclosure will be located on the condenser end opposite of the main electrical enclosure. DPN002155 Page :1 /1 REV : 3 REV DATE : 2/18 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER CABINET & ANCHOR DIMENSIONAL DATA 2 FAN (MCS056, MCM080, MCL110) DUAL CIRCUIT 575V Option 575V Option H TOP OF G FAN GUARD A* A F Lee-Temp or DSE Receiver C Entering Hot Gas and Leaving Liquid Piping D A Anchor Plan Main Electric Box End Full height leg supplied for each Lee-Temp or DSE Receiver required M L K 15 1/4" 387mm Left Side of Unit 13/16" 21mm Typ. J Lee-Temp or DSE Only 3 3 5/8" 93mm Typ. Front View (Lee-Temp Shown) DETAIL A F MODEL NUMBER MCS056 MCM080 Form No.: DPN001040_REV4 2 Cross bracing required for legs longer than 18" (457mm). Quantity varies per model & options selected. LIEBERT MODEL NUMBER A A* (575V ONLY) 3 2 (LEG HEIGHT DIMENSIONS) 18 (457) 36 (914) 48 (1219) 60 (1524) DIM "G" 31-5/8 (803) 49-5/8 (1260) 61-5/8 (1565) 73-5/8 (1870) DIM "H" 39-5/8 (1006) 57-5/8 (1464) 69-5/8 (1768) 81-5/8 (2073) MCL110 DIM "G" 35-7/8 (911) 53-7/8 (1368) 65-7/8 (1673) 77-7/8 (1978) DIM "H" 43-5/8 (1108) 61-5/8 (1565) 73-5/8 (1870) 85-5/8 (2175) Typical All Legs Note: 1. Liebert recommends a clearance of 36” (915mm) on each side for proper operation and component access. 3 6 1/2" 165mm Ref. Ref. Dual Circuit Only 15 1/4" K 387mm Dual Circuit Only LIEBERT All primary dimensions in tables are in inches (Secondary are in mm) except where specified 1 7/8" 48mm Typ. 1/2" (13mm) X 1" (25mm) Obround Typ. 7" 178mm Typ. 3 6 1/2" 165mm C D J Lee-Temp or DSE Receivers Only K L M MCS056 MCM080 94-7/8 (2411) 103-1/8 (2619) 88-3/8 (2245) 86-3/4 (2203) 105-1/4 (2674) 113-7/16 (2882) 96-1/16 (2440) 94-7/16 (2398) 42-1/2 (1079) 42-1/2 (1080) 40-7/8 (1038) 35-7/8 (910) 46-5/16 (1177) 46 (1168) 44-3/8 (1127) 39-5/16 (999) 3 For DSE models only, 6-1/2" (165mm) MCL110 dimension is 9-1/4" (235mm) and 15-1/4 (387mm) dimension is not applicable. DPN003437 Page :1 /1 124-1/8 (3152) 133-1/8 (3381) 112-1/8 (2848) 110-1/2 (2806) 54-3/8 (1381) 55-1/2 (1410) 53-7/8 (1368) 48-3/4 (1238) REV : 4 REV DATE : 12/16 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER CONDENSER AND OPTION WEIGHT DATA, lb(kg) Size Condenser Model Refrigerant Circuits Condenser Dry Weight Small (MCS) MCS028 MCS056 MCM040 Medium (MCM) MCM080 MCM160 1 2 1 1 2 2 18" Leg 154 ( 70) 270 ( 122) 231 ( 105) 441 ( 200) 441 ( 200) 860 ( 390) 36" Leg 286 ( 130) 419 ( 190) 363 ( 165) 590 ( 268) 590 ( 268) 1066 ( 484) 48" Leg 318 ( 144) 451 ( 205) 395 ( 179) 622 ( 282) 622 ( 282) 1114 ( 505) 60" Leg 349 ( 158) 482 ( 219) 426 ( 193) 653 ( 296) 653 ( 296) 1160 ( 526) 110 ( 50) PDX-EEV Receiver Lee-Temp DSE Receiver DA050/080/085 DSE Receiver DA125/150/165 575V Transformer Coated Coil Seismic/Wind Bracing 18" legs Size Condenser Model Refrigerant Circuits 18" Leg Condenser Dry 36" Leg weight 48" Leg 60" Leg PDX-EEV Receiver Lee-Temp DSE Receiver DA050/080/085 DSE Receiver DA125/150/165 575V Transformer Coated Coil Seismic/Wind Bracing 18" legs Additional Weight for Options 45 ( 20) 45 ( 20) 55 ( 25) 110 ( 50) 55 ( 25) 55 ( 25) 65 ( 29) 60 ( 27) 45 ( 20) 100 ( 45) 45 (20) 92 (42) 70 ( 32) 70 ( 32) 220 ( 100) 90 (41) 184 ( 83) 80 ( 36) 4 ( 2) 8 ( 4) 5 ( 2) 10 ( 5) 10 ( 5) 20 ( 9) 40 ( 18) 40 ( 18) 40 ( 18) 40 ( 18) 40 ( 18) 57 ( 26) Large (MCL) MCL110 MCL055 MCL165 1 1 2 1 344 ( 156) 602 ( 273) 602 ( 273) 891 ( 404) 486 ( 220) 766 ( 347) 766 ( 347) 1136 ( 515) 518 ( 235) 798 ( 362) 798 ( 362) 1184 ( 537) 549 ( 249) 829 ( 376) 829 ( 376) 1230 ( 558) Additional Weight for Options 45 ( 20) 60 ( 27) 115 ( 52) 120 ( 54) 175 ( 79) 45 ( 20) 90 ( 41) 45 (20) 94 ( 43) 94 ( 43) 67 ( 30) 77 ( 35) 77 ( 35) 118 ( 54) 8 ( 4) 16 ( 7) 16 ( 7) 24 ( 11) 40 ( 18) 40 ( 18) 41 ( 19) 57 ( 26) MCL220 1 2 1186 ( 538) 1186 ( 538) 1453 ( 659) 1453 ( 659) 1501 ( 681) 1501 ( 681) 1547 ( 702) 1547 ( 702) 215 ( 98) 45 ( 20) 94 ( 43) 118 ( 54) 32 ( 15) 57 ( 26) 240 ( 109) 90 ( 41) 188 ( 85) 118 ( 54) 32 ( 15) 57 ( 26) Form No.: DPN001040_REV4 Total weight is the sum of 'Condenser' + ('PDX-EEV Receiver' or 'Lee-Temp' or 'DSE Receiver 050/080/085' or 'DSE Receiver 125/150/165')'+'Coated Coil' + '575V Transformer'.+ 'Seismic/Wind Bracing' DPN003034 Page :1 /1 REV : 4 REV DATE : 4/18 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER PIPING DIMENSIONAL DATA DUAL CIRCUIT 2 FAN & 4 FAN UNITS COVER * VERTICAL INVERTED TRAPS ARE FACTORY PROVIDED INSIDE CONDENSER FIELD PIPING LEAVING LIQUID LINE HORIZONTAL ENTERING HOT GAS LINE DETAIL A CIRCUIT #1 CIRCUIT #2 OPTIONAL FUSIBLE PLUG SERVICE KIT TO BE BRAZED INTO THE LIQUID LINE(S) IN EITHER THE VERTICAL OR HORIZONTAL POSITION (WHERE REQUIRED). (VERTICAL POSITION IS PREFERRED, HORIZONTAL POSITION IS OPTIONAL.) FOR TWO CIRCUIT SYSTEMS, ONE FUSIBLE PLUG KIT WILL NEED TO BE INSTALLED IN EACH CIRCUIT. MODEL NO. Form No.: DPN001040_REV4 MCS 056 MCM 080 MCL 110 MCM 160 MCL 220 A NUMBER CONDENSER CONNECTION SIZES ,OD,IN OF FANS CIRCUITS HOT GAS LINE LIQUID LINE 2 2 7/8 5/8 2 2 7/8 5/8 2 2 1-1/8 7/8 4 2 1-1/8 7/8 4 2 1-3/8 1-1/8 * SHIPPING COVER IS NOT NECESSARY FOR PROPER CONDENSER OPERATION AND MAY BE RECYCLED IF FIELD PIPING INTERFERES WITH PROPER REATTACHMENT. DPN002425 Page :1 /1 REV : 6 REV DATE : 12/16 Document generated 25 mayo 2018 01:34 (EST). LIEBERT AIR COOLED SYSTEMS RECOMMENDED REFRIGERANT LINE SIZES CU, OD LIEBERT AIR-COOLED SYSTEMS USING R-410A System Fluid : R-410A Indoor Model CR019RA/ CR020RA CR035RA PX011 PX018 PX023 PX029 DA050 / DA080/ DA085 DA125 DA150 DA165 DA250 Equivalent Length Hot Gas Line, in. Liquid Line, in. Hot Gas Line, in. Liquid Line, in. Hot Gas Line, in. Liquid Line, in. Hot Gas Line, in. Liquid Line, in. Hot Gas Line, in. Liquid Line, in. Hot Gas Line, in. Liquid Line, in. Hot Gas Line, in. Liquid Line, in. Hot Gas Line, in. Liquid Line, in. Hot Gas Line, in. Liquid Line, in. Hot Gas Line, in. Liquid Line, in. Hot Gas Line, in. Liquid Line, in. System Fluid: R-410A Indoor Model Equivalent Length 50 ft (15m) Suction Line, in. 1-1/8 MT060 Liquid Line, in. 1/2 Suction Line, in. 7/8 MT048 Liquid Line, in. 1/2 50 ft (15m) 3/4 5/8 7/8 3/4 1/2 3/8 5/8 1/2 3/4 5/8 7/8 5/8 1-1/8 7/8 1-3/8 7/8 1-3/8 7/8 1-3/8 7/8 1-5/8 1-3/8 Any Compressor Type 100 ft (30m) 150 ft (45m) 300 ft (91m) 3/4 3/4 7/8 2 5/8 5/8 3/4 7/8 7/8 1-1/8 2 3/4 3/4 7/8 2 2 5/8 5/8 5/8 2 1/2 1/2 1/2 5/8 5/8 3/4 2 1/2 1/2 5/8 3/4 3/4 7/8 2 5/8 5/8 5/8 7/8 7/8 1-1/8 2 5/8 5/8 3/4 1-1/8 1-1/8 1-1/8 7/8 7/8 7/8 1-3/8 1-3/8 1-3/8 7/8 7/8 7/8 1-3/8 1-3/8 1-3/8 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-1/8 1-1/8 1-1/8 4 1-5/8 1-5/8 1-5/8 4 4 1-3/8 1-3/8 1-3/8 4 450ft (137m) 1-1/8 7/8 1-3/8 7/8 1-3/8 1-1/8 1-3/8 1-1/8 3 3 3 3 3 3 3 3 Digital Scroll Models 75 ft (23m) 100 ft (30m) 125 ft (38m) 150 ft (45m) 1-1/8 1-1/8 1-1/8 1-1/8 5/8 5/8 5/8 5/8 2 2 2 1-1/8 1-1/8 1-1/8 1-1/8 2 1/2 5/8 5/8 5/8 Form No.: DPN001040_REV4 Notes: 1. Consult factory for proper line sizing for runs longer than maximum equivalent length shown in table. 2. Must downsize vertical riser one trade size (1-1/8” to 7/8” or 7/8” to 3/4” or 3/4" to 5/8" or 5/8" to 1/2"). 3. Consult factory when actual pipe length between condenser/EconoPhase and Liebert DSE unit will exceed 300 ft (91 m). 4. Liebert DA250 unit can be extended to max 200' linear or 300' equivalent. DPN000788 Page :1 /2 REV : 10 REV DATE : 3/18 Document generated 25 mayo 2018 01:34 (EST). LIEBERT AIR COOLED SYSTEMS RECOMMENDED REFRIGERANT LINE SIZES CU, OD LIEBERT AIR-COOLED SYSTEMS USING R-407C System Fluid : R-407C Indoor Model 50 ft (15m) 100 ft (30m) 150 ft (45m) Hot Gas Line, in. 7/8 7/8 7/8 3/4 7/8 7/8 Liquid Line, in. 1/2 5/8 5/8 1/2 5/8 5/8 Hot Gas Line, in. 7/8 7/8 7/8 7/8 7/8 1-1/8 Liquid Line, in. 1/2 5/8 5/8 5/8 5/8 DS042 DS053 DS070 3 DS105 3 XDC160 200 ft (60m) Hot Gas Line, in. 7/8 1-1/8 1-1/8 7/8 Liquid Line, in. 5/8 7/8 7/8 7/8 5/8 2 1-1/8 2 1-1/8 7/8 2 2 7/8 2 2 Hot Gas Line, in. 1-1/8 1-1/8 1-1/8 Liquid Line, in. 7/8 7/8 7/8 7/8 7/8 7/8 Hot Gas Line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 Liquid Line, in. 7/8 7/8 7/8 7/8 7/8 7/8 Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 Liquid Line, in. 7/8 7/8 1-1/8 7/8 7/8 1-1/8 Hot Gas Line, in. 1-1/8 Liquid Line, in. 7/8 4 1-1/8 4 Indoor Model MMD12 MMD18 / DME020 MMD24 / DME027 MMD36/ MMD35 / DME037 / MMD96-3T / MMD95-3T MMD60/ MMD59 / MMD96-5T /MMD95-5T 1-1/8 4 1-3/8 1-1/8 1-1/8 1-1/8 4 1-3/8 1-1/8 System Fluid : R-407C Form No.: DPN001040_REV4 or Digital Scroll Models 50 ft (15m) 100 ft (30m) 150 ft (45 m) Equivalent Length DS035 DS077 4-Step Semi-Hermetic Standard Scroll Models (Non-Digital Scroll) 1-1/8 Standard Scroll Models (Non-Digital Scroll) Equivalent Length 50 ft (15m) 75 (23m) 100 ft (30m) 125 (38m) 150 ft (45m) Suction Line, in. Liquid Line, in. Suction Line, in. Liquid Line, in. Suction Line, in. Liquid Line, in. Suction Line, in. Liquid Line, in. Suction Line, in. Liquid Line, in. 5/8 5/8 7/8 7/8 7/8 3/8 3/8 3/8 3/8 3/8 5/8 7/8 7/8 7/8 7/8 3/8 3/8 3/8 1/2 1/2 7/8 7/8 7/8 7/8 7/8 3/8 3/8 1/2 1/2 2 1/2 2 2 7/8 7/8 1-1/8 1/2 1/2 1/2 1/2 1/2 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8 1/2 5/8 5/8 5/8 5/8 1-1/8 1-1/8 Note: 1. Consult factory for proper line sizing for runs longer than maximum equivalent length shown in tables above. 2. Downsize vertical riser one trade size (1-1/8" to 7/8"). 3. Digital scroll not available on 077 and 105 models. 4. Double risers are required when hot gas vertical rise is 15 ft (4.6m) or more. Refer to XDC user manual DPN000788 Page :2 /2 REV : 10 REV DATE : 3/18 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER TYPICAL PIPING SCHEMATIC FOR AIR-COOLED DX SYSTEMS Optional Field Installed Fusible Plug Check Valve Relief Valve Service Valve Pressure Transducer LEE-TEMP RECEIVER Head Pressure Control Valve LIQUID RETURN Pressure Transducer Check Valve CONDENSER COIL CONDENSER COIL (Includes factory provided inverted trap. No external trap required) (Includes factory provided inverted trap. No external trap required) HOT GAS DISCHARGE LIEBERT MC CONDENSER LIEBERT MC CONDENSER WITH LEE-TEMP OPTION LIQUID Sensing Bulb EVAPORATOR COIL 3 For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided SUCTION Service Valve Check Valve COMPRESSOR 3 Service Valve Field installed relief valve(s) required for 50Hz EU CE units. External Equalizer HOT GAS DISCHARGE Expansion Solenoid Valve Valve Sight Glass FACTORY REFRIGERANT PIPING FIELD PIPING Filter Drier LIQUID LINE INTERCONNECTING PIPING SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE Notes: 1. Single refrigeration circuit shown for clarity. 2. Schematic representation shown. Do not use for specific connection locations. 3 Trap at base of risers over 5ft. (1.5m) Form No.: DPN001040_REV4 3. Components are not supplied by Liebert, but are required for proper operation and maintenance. 4. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow. 5. Do not islolate any refrigeration circuits from over pressurization protection. DPN002188 Page :1 /1 REV : 7 REV DATE : 12/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER AIR COOLED PIPING SCHEMATIC CONDENSER ABOVE INDOOR UNIT Liquid Gas Gas Notes: 1. Trapping must be practiced at bottom of riser with any rise over 5 feet high. If rise exceeds 25 feet (7.5m), then a trap is required in 20 foot (6 m) increments or evenly divided 2. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow. 3. Single circuit condenser shown. 4. Unit piping entrance varies by unit and may be through the top of the unit. 5. Indoor unit may be Liebert DS, PDX, or CRV and is shown for reference only while demonstrating proper pipe and unit/condenser height differences. 60' 18.3m Maximum Vertical Rise Liquid Indoor Unit Field piping 1 Gas 1 Gas 2 4 Liquid Form No.: DPN001040_REV4 Liquid DPN003954 Page :1/3 REV : 3 REV DATE : 5/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER AIR COOLED PIPING SCHEMATIC CONDENSER AND INDOOR UNIT AT SAME LEVEL Indoor Unit Gas 1 Liquid 3 Field piping Notes: Form No.: DPN001040_REV4 1. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow. 2. Single circuit condenser shown. 3. Unit piping entrance varies by unit and may be through the top of the unit. 4. Indoor unit may be Liebert DS, PDX, or CRV and is shown for reference only. DPN003954 Page :2/3 REV : 3 REV DATE : 5/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER AIR COOLED PIPING SCHEMATIC CONDENSER BELOW INDOOR UNIT Indoor Unit 4 Gas 15' 4.6m Maximum Vertical Drop Liquid Gas Field piping Gas Form No.: DPN001040_REV4 Liquid Notes: 1. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow. 2. This Configuration is not valid for Liebert MC with Lee-Temp or unheated receiver. 3. Single circuit condenser shown. 4. Unit piping entrance varies by unit and may be through the top of the unit. 5. Indoor unit may be Liebert DS, PDX, or CRV and is shown for reference only while demonstrating proper pipe and unit/condenser height differences. DPN003954 Page :3/3 REV : 3 REV DATE : 5/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER ELECTRICAL FIELD CONNECTIONS PREMIUM EFFICIENCY CONTROL FAN 2 FAN 1 8 10 SH 12 9 13 70 71 230 NOTICE ! THIS HOLE FOR FIELD SUPPLIED EXTRA LOW VOLTAGE CONTROL WIRING KEY ELECTRICAL DETAILS: 1) Three phase electrical service – Terminals are on top of disconnect switch for one and two fan units. Terminals are on bottom of Form No.: DPN001040_REV4 disconnect switch for three and four fan units. Three phase service not by Liebert. See note 5. 2) Earth ground – Field lug terminal for earth ground connection. Ground terminal strip for fan motor ground connection. 3) Primary high voltage entrance – Two 7/8” (22.2mm) diameter knockouts located at the bottom of the enclosure. 4) SPD field connection terminals – High voltage surge protective device (SPD) terminals. SPD is an optional device. DPN002169 Page :1 /3 REV : 10 REV DATE : 2/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER ELECTRICAL FIELD CONNECTIONS PREMIUM EFFICIENCY CONTROL 5) CANbus terminal connections – Field terminals for CANbus cable connection. • 5A is the CANbus connectors. o TB49-1 is the input terminal for CANbus high. o TB49-3 is the input terminal for CANbus low. o TB50-1 is output terminal for CANbus high. o TB50-3 is the output terminal for CANbus low. o Each CANbus cable shield is connected to terminal “SH”, item 9. • 5B is the “END OF LINE” jumper. • 5C is the CANbus “DEVICE ADDRESS DIP SWITCH”. CANbus cable not by Liebert. See Note 2. (below) 6) Remote unit shutdown – Replace existing jumper between terminals TB38-1 and TB38-2 with field supplied normally closed switch having a minimum 75VA 24VAC rating. Use field supplied Class 1 wiring. (This is an optional feature that may be owner specified.) 7) Alarm terminal connections – a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common, TB74-2 is normally open, and TB74-3 is normally closed. 1 Amp 24VAC is the maximum load. Use Class 1 field supplied wiring. b. Shutdown Alarm Relay indicates when condenser loses power, or when a critical alarm has occurred that shuts down the condenser unit. TB74-4 is common, TB74-5 is normally open, and TB74-6 is normally closed. 1 Amp 24VAC is the maximum load. Use Class 1 field supplied wiring. 8) Indoor unit interlock and SPD alarm terminals – a. On any call for compressor operation, normally open contact is closed across terminals 70 and 71 for Circuit 1, and normally open contact is closed across terminals 70 and 230 for Circuit 2 from indoor room unit. b. 9) During SPD alarm, normally open contact is closed across terminals 12 & 13. SPD is an optional device. CANbus shield terminal – Terminal for field shield connection of the CANbus field supplied cables. The shield of CANbus field supplied cables must not be connected to ground at the condenser. 10) Primary low voltage entrance – One 7/8” (22.2mm) diameter knockout that is free for customer low voltage wiring. 11) SPD entrance – One 7/8” (22.2mm) diameter knockout hole located at the bottom of the enclosure. High voltage surge protective device (SPD) is optional. NOTES: 1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings. 2. The CANbus wiring is field supplied and must be: - Braided shield or foil shield with drain wire - Shield must be wired to ground at indoor unit - 22-18AWG stranded tinned copper - Twisted pair (minimum 4 twists per foot) - Low Capacitance (15pF/FT or less) - Must be rated to meet local codes and conditions - EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER Form No.: DPN001040_REV4 3. Do not run in same conduit, raceway, or chase as high voltage wiring. 4. For CANbus network lengths greater than 450FT (137M) call Factory. DPN002169 Page :2 /3 REV : 10 REV DATE : 2/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT MC CONDENSER ELECTRICAL FIELD CONNECTIONS PREMIUM EFFICIENCY CONTROL Form No.: DPN001040_REV4 5. 6. 7. 8. 9. 10. All wiring must be sized and selected for insulation case per NEC and other local codes. Do not bend cables to less than four times the diameter of the cable. Do not deform cables when securing in bundles or when hanging them. Avoid running the cables by devices that may introduce noise, such as machines, fluorescent lights, and electronics. Avoid stretching cables. The electrically commutated (EC) motors included in the Liebert MC Condenser are suitable for connection to power supplies with a solidly grounded neutral or high resistance to ground or corner ground. a. Acceptable power supplies for 208 to 575V nominal units: • 208V wye with solidly grounded neutral and 120V line to ground; • 380V wye with solidly grounded neutral and 220V line to ground; • 480V wye with solidly grounded neutral and 277V line to ground; • 575V wye with solidly grounded neutral and 332V line to ground (uses step-down transformer); • Wye with high resistance (or impedance) ground; • Delta with corner ground b. Unacceptable power supplies for 208V to 575V nominal units: • Delta without ground or with floating ground; • Delta with grounded center tap. DPN002169 Page :3 /3 REV : 10 REV DATE : 2/17 Document generated 25 mayo 2018 01:34 (EST). LIEBERT DS CANbus & INTERLOCK CONNECTIONS BETWEEN LIEBERT DS & LIEBERT MC CONDENSER (PREMIUM) CAN L TB50 CAN H D58 J6 L 1 2 3 P15 A 1 TB50 OUTPUT B 1 H 3 J6 TERMINATION JUMPER MUST BE SET TO PINS 1 AND 2. TB49 J4 TB50 L OUTPUT 1 1 2 3 3 TB49 INPUT CONDENSER H P80 ON 3 J6 CANbus ADDRESSING SWITCH 1 2 3 TB49 INPUT 1 2 3 CAN H CAN L 3 CAN SW6 BOOTPSWD SYS APP ON CAN SW6 DETAIL 3 CAN CABLE CONNECTION (A) A SHIELD CONNECTION FACTORY WIRING BETWEEN MC CONTROL BOARD AND TERMINAL STRIP. SH F LOW VOLTAGE FIELD ENTRANCE LOCATED ON BOTTOM LEFT OF CONDENSER ENCLOSURE. DETAIL 2 HEAT REJECTION INTERLOCK (F) SHIELD CABLE NOTES (A): 1. CABLE MUSTHAVE THE FOLLOWING SPECIFICATIONS: CONNECTION - BRAIDED SHIELD OR FOIL SHIELD WITH DRAIN WIRE - SHIELD MUST BE WIRED TO GROUND AT INDOOR UNIT - 22-18AWG STRANDED TINNED COPPER - TWISTED PAIR (MINIMUM 4 TWISTS PER FOOT) - LOW CAPACITANCE (15pF/FT OR LESS) - MUST BE RATED TO MEET LOCAL CODES AND CONDITIONS. - EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA SH WIRE 6454 CATEGORY 5, 5E, OR HIGHER. 2. DO NOT RUN IN SAME CONDUIT, RACEWAY, OR CHASE AS 49-1 HIGH VOLTAGE WIRING. 49-3 3. FOR CANBUS NETWORK LENGTHS GREATER THAN 450FT(137M), CONTACT LIEBERT FACTORY. Form No.: DPN001040_REV4 DPN003267 Page :1 /1 F HEAT REJECTION INTERLOCK HEAT REJECTION INTERLOCK (F) COMPONENT NOTES: 1. COMPONENT APPEARANCE, ORIENTATION , AND POSITION MAY VARY BETWEEN PRODUCT LINES. TERMINAL NAMES AND CALLOUTS REMAIN CONSTANT. 2. ALL CIRCUITS TO THESE CONNECTION POINTS ARE CLASS 2. WIRE NOTES (F): 1. FIELD SUPPLIED WIRE - 3 CONDUCTOR 18AWG OR GREATER - RATED 600V 2. RUN FIELD SUPPLIED WIRES BETWEEN THE INDOOR UNIT AND THE CONDENSER. REMOVE JUMPER FOR DUAL CIRCUIT 70 71 230 70 71 230 F A CANbus CONNECTION 2 1 A DETAIL 1 CAN CABLE CONNECTION (A) FACTORY WIRING BETWEEN ICOM AND TERMINAL STRIP. INDOOR DS UNIT REV : 4 REV DATE : 4/18