SubmittalDocument

Document generated 25 mayo 2018 01:34 (EST).
LIEBERT DS
CABINET DIMENSIONAL DATA
UPFLOW AIR COOLED 35-42kW (10-12 TONS)
W/ SCROLL OR DIGITAL SCROLL COMPRESSORS W/ EC FANS
Alternate refrigerant
piping entrance
33"
838mm
35"
889mm
5/16"
9mm
Bezel
High Volt Connection(s)
3 1/4"
83mm
1 3/4"
44mm
Handle
TOP VIEW
Space required for EC Fan Plenum
(shipped separately) dependent on
height of plenum ordered.
Low Volt Connection(s)
73"
1854mm
76"
1930mm
36"
914mm
Shaded are indicates a
recommended minimum
clearance be provided for
component access. Clearance
required from floor to top of unit
and plenum.
2"
51mm
FRONT VIEW
Form No.: DPN001040_REV4
72"
1829mm
APPROXIMATE DRY WEIGHT lb (kg) 3
Air Cooled
Dual Cool
1370 (621)
1520 (689)
DPN003495
Page :1 /1
Notes:
1. Front air return unit shown. For rear return unit,
in addition to front service area shown, also include
25" (635mm) on one side of unit for access to rear
return filter box. See DPN003974.
2. EC fans plenum is not shown. EC fans and plenum
are shipped separately. See DPN003458 for unit
dimensions with EC fans plenum mounted.
3. Fan weight not included in this unit weight.
Fan is installed in plenum.
REV : 3
REV DATE : 5/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
UPFLOW AIR COOLED 35-42kW (10-12 TONS)
SCROLL OR DIGITAL SCROLL COMPRESSOR MODELS W/ EC FANS
ECR
ECS 5
2 R1
O
X
HUM
2 R2
L1L2
35"
889mm
CPD
3
EC Fan Outlet
G1G2
Y
E1 E2
Top View
2 R3
3 7/8"
98mm
CGD
14 1/4"
362mm
17 1/8"
434mm
4
9 7/8"
251mm
1
73"
1854mm
FRONT OF UNIT
LV1
LV2
LV3
L1L2 G1 G2
6
4 CGD
Front View
(Left Panel Not Shown)
Left Side View
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of ± 1/2" (13mm).
2. Field routed alternatives for refrigerant gas & liquid line connection points.
3. EC fan shown. See submittal page DPN003458 for EC fan outlet & plenum dimensional data.
4. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
5. Supplied on Dual Cooling Systems only.
Form No.: DPN001040_REV4
6. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
POINT
R1
R2
R3
L1
L2
G1
G2
CGD
CPD
HUM
ECS
ECR
E1
E2
LV1
LV2
LV3
DESCRIPTION
X in. (mm)
REFRIGERANT ACCESS (TOP) 2
60-5/8 (1540)
REFRIGERANT ACCESS (BOTTOM) 2
63 (1600)
REFRIGERANT ACCESS (SIDE) 2
N/A
LIQUID LINE SYSTEM 1
79-3/16 (2011)
LIQUID LINE SYSTEM 2
76-1/2 (1943)
HOT GAS DISCHARGE 1 6
73-7/8 (1876)
HOT GAS DISCHARGE 2 6
70-1/8 (1781)
CONDENSATE GRAVITY DRAIN 4
N/A
CONDENSATE PUMP DISCHARGE (OPT)
56-1/4 (1429)
HUMIDIFIER SUPPLY LINE
ECON-O-COIL SUPPLY 5
56 (1422)
ECON-O-COIL RETURN 5
52-3/8 (1330)
ELECTRICAL CONN. (HIGH VOLT)
47-3/8 (1203)
ELECTRICAL CONN. (LOW VOLT)
DPN002740
Page :1 /1
8-1/8 (206)
Y in. (mm)
2-13/16 (71)
13-13/16 (351)
N/A
CONNECTION SIZE / OPENING
10-1/8" (257mm) X 4-1/8" (105mm)
16-7/16" (418mm) X 4" (102mm)
6" (152mm) X 17-3/16" (437mm)
16-3/4 (425)
1/2" O.D. Cu
16-5/8 (422)
5/8" O.D. Cu
N/A
11-1/8 (283)
9-1/8 (232)
7-5/16 (186)
4-1/2 (114)
3/4" NPT FEMALE
1/2" O.D. Cu
1/4" O.D. Cu
29-15/16 (760)
2-1/2"
29-9/16 (751)
31 (787)
32-7/16 (824)
7/8"
1-5/8" O.D. Cu
REV : 3
REV DATE : 5/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT DS
DISASSEMBLY DIMENSIONAL DATA
UPFLOW 35-42kW (10-12 TONS) MODELS
W/ SCROLL & DIGITAL SCROLL COMPRESSORS
Unit w/ Scroll/Digital Scroll
Compressor Section
BLOWER & ELECTRIC BOX ASSEMBLY
Compressor Section Assembly
31 1/4"
794mm
FILTER & COIL ASSEMBLY
76"
1930mm
Assembled
Height
76"
1930mm
45 13/16"
1163mm
33"
838mm
59"
1499mm
A
B Assembled Length
Cooling Ty pe
A in (mm) B in. (mm)
Air Cooled
13 (330)
Air Cooled w / Dual Cool
Water/Gly col
26 (660)
GLYCOOL™/Dual Cool
72 (1829)
85 (2159)
Assembly
Compressor Assembly
APPROXIMATE DRY WEIGHT lb (kg) (Includes Panels)
Air Cooled
A/C w / Dual Cool Water/Gly col GLYCOOL™/Dual Cool
490 (223)
490 (223)
800 (364)
800 (364)
510 (231)
510 (231)
510 (231)
510 (231)
EC Fan & 2
Electric Box Assembly
360 (163)
360 (163)
360 (163)
360 (163)
Filter & Coil Assembly
520 (236)
670 (304)
520 (236)
670 (304)
Forw ard Curv ed Blow er
& Electric Box Assembly
Form No.: DPN001040_REV4
Notes:
1. Drawing Views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual. EC Fan unit shown.
2. EC Fan wieght not included in this unit weight. Fan is installed in plenum. See DPN003458.
DPN003650
Page :1 /1
REV : 3
REV DATE : 5/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT DS
PIPING SCHEMATIC W/ LIEBERT MC CONDENSER
AIR COOLED SCROLL OR DIGITAL SCROLL COMPRESSOR MODELS
Optional Field Installed
Fusible Plug
Pressure Transducer
Check Valve
Relief Valve
Head Pressure
Control Valve
Service
Valve
LIQUID RETURN
Pressure
Transducer
LEE-TEMP RECEIVER
Check Valve
CONDENSER COIL
(Includes factory provided
inverted trap. No
external trap required)
CONDENSER COIL
(Includes factory provided
inverted trap. No
external trap required)
LIEBERT MC CONDENSER
HOT GAS DISCHARGE
LIEBERT MC CONDENSER WITH LEE-TEMP OPTION
LIEBERT DS
LIQUID
Sensing
Bulb
35-42kW digital
Solenoid Valve
SUCTION
53-70kW digital
Solenoid Valve
Service
Valve
Check
Valve
EVAPORATOR
COIL
3
For rises over
25ft. (7.6m), trap
every 20ft. (6m)
or evenly divided
3
COMPRESSOR
Service
Valve
External
Equalizer
Field installed relief valve(s) required
for 50Hz EU CE units rated maximum
480 PSIG (33 Bar).
HOT GAS DISCHARGE
Sight
Expansion Solenoid
Glass
Valve
Valve
OPTIONAL FACTORY PIPING
FACTORY REFRIGERANT PIPING
FIELD PIPING
Filter Drier
INTERCONNECTING
PIPING
LIQUID LINE
SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE
3
Trap at base of risers
over 5ft. (1.5m)
SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
Notes:
1. Single refirigeration circuit shown for clarity.
2. Schematic representation shown. Do not use for specific connection locations.
Form No.: DPN001040_REV4
3. Components are not supplied by Liebert, but are required for proper operation and maintenance.
4. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor. Pitch horizontal hot gas piping at a minimum of
1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
5. Do not isolate any refrigerant circuits from over pressurization protection.
DPN003730
Page :1 /1
REV : 3
REV DATE : 12/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT DS
ELECTRICAL FIELD CONNECTION DESCRIPTION
UPFLOW AND DOWNFLOW MODELS
STANDARD ELECTRICAL CONNECTIONS
1) Primary high voltage entrance - 2.50” (64mm); 1.75” (44mm); 1.375” (35mm) diameter concentric knockouts located in bottom of box
2) Secondary high voltage entrance - 2.50” (64mm); 1.75” (44mm); 1.375” (35mm) diameter concentric knockouts located in top of box
3) Primary low voltage entrance - Quantity (3) 1.375” (35mm) diameter knockouts located in bottom of unit
4) Secondary low voltage entrance - Quantity (3) 1. 375” (35mm) diameter knockouts located in top of box
5) Three phase electrical service - Terminals are on main fuse block (disregard if unit has optional disconnect switch). Three phase service
not by Liebert.
6) Earth ground - Terminal for field supplied earth grounding wire. Earth grounding required for Liebert units.
7) Remote unit shutdown - Replace existing jumper between terminals 37 & 38 with field supplied normally closed switch having a
minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring.
8) Customer alarm inputs - Terminals for field supplied, normally open contacts, having a minimum 75VA, 24VAC rating, between
terminals 24 & 50, 51, 55, 56. Use field supplied Class 1 wiring. Terminal availability varies by unit options.
9) Common alarm - On any alarm, normally open dry contact is closed across terminals 75 & 76 for remote indication. 1 AMP, 24VAC max
load. Use Class 1 field supplied wiring.
10) Heat rejection interlock - On any call for compressor operation, normally open dry contact is closed across terminals 70 & 71(circuit 1),
230 (circuit 2) to heat rejection equipment. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. When DS unit is paired with a
Liebert MC series condenser, remove jumper between terminal 71 and terminal 230. Three wires must connect terminals 70, 71 and 230
of the indoor unit to terminals 70, 71 and 230 of the Liebert MC series condenser.
11) Unit factory installed disconnect switch, Fuse Block and Main Fuses – “Locking Type” consists of a non-automatic molded case
switch operational from the outside of the unit. Access to the high voltage electric panel compartment can be obtained only with the switch
in the “off” position. Units with fused disconnects are provided with a defeater button that allows access to the electrical panel when power
is on. The molded case switch disconnect models contain separate main fuses.
Form No.: DPN001040_REV4
CANBUS ELECTRICAL CONNECTIONS
12) CANbus Connector– Terminal block with terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH (shield connection). The terminals are used to
connect the CANbus communication cable (provided by others) from the indoor unit to the Liebert MC Condenser –Optional Econophase
Unit.
13) CANbus Cable – CANbus cable provided by others to connect to the outdoor condenser, and optional PRE unit (DA units only). No
special considerations are required when the total external cable connection between the indoor unit and outdoor unit(s) is less than
450FT (137M). For total external cable connections greater than 450FT (137M) but less than 800FT (243M) a CANbus isolator is required.
Contact Factory.
Cable must have the following specifications:
Braided shield or foil shield with drain wire
- Shield must be wired to ground at indoor unit
- 22-18AWG stranded tinned copper
- Twisted pair (minimum 4 twists per foot)
- Low Capacitance (15pF/FT or less)
- Must be rated to meet local codes and conditions
- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER
14) Do not run in same conduit, raceway, or chase as high voltage wiring.
15) For CANbus network lengths greater than 450FT (137M) call Factory.
DPN000807
Page :1 /3
REV : 17
REV DATE : 10/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT DS
ELECTRICAL FIELD CONNECTION DESCRIPTION
UPFLOW AND DOWNFLOW MODELS
OPTIONAL ELECTRICAL CONNECTIONS
16) Smoke sensor alarm - Factory wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-NC. Supervised contacts, 80 &
81, open on sensor trouble indication. This smoke sensor is not intended to function as, or replace, any room smoke detection system that
may be required by local or national codes. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
17) Reheat and humidifier lockout - Remote 24VAC required at terminals 82 & 83 for lockout of reheat and humidifier.
18) Condensate alarm (with condensate pump option) - On pump high water indication, normally open dry contact is closed across terminals
88 & 89 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
19) Remote humidifier - On any call for humidification, normally open dry contact is closed across terminals 11 & 12 to signal field supplied
remote humidifier. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
20) Auxiliary cool contact - On any call for econ-o-coil operation, normally open dry contact is closed across terminals 72 & 73 on dual cool
units only. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
Form No.: DPN001040_REV4
OPTIONAL LOW VOLTAGE TERMINAL PACKAGE CONNECTIONS
21) Remote unit shutdown - Two additional contact pairs available for unit shutdown (labeled as 37B & 38B, 37C & 38C). Replace jumpers
with field supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring.
22) Common alarm - On any alarm, two additional normally open dry contacts are closed across terminals 94 & 95 and 96 & 97 for remote
indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
23) Main fan auxiliary switch - On closure of main fan contactor, normally open dry contact is closed across terminals 84 & 85 for remote
indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
24) LiquiTect shutdown and dry contact - On LiquiTect activation, normally open dry contact is closed across terminals 58 & 59 for remote
indication (LiquiTect sensor ordered separately). 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
NOTE: Refer to specification sheet for total unit full load amps, wire size amps, and max overcurrent protective device size.
DPN000807
Page :2 /3
REV : 17
REV DATE : 10/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT DS
ELECTRICAL FIELD CONNECTION DESCRIPTION
UPFLOW AND DOWNFLOW MODELS
2
OVERCURRENT PROTECTION DEVICES
Intellislot
Housing
4
A
B
C
D
5
Alternate
Location
60 Hz
P64
6
CONTACTORS
P67
CONTACTORS, RELAYS, &
OVERLOAD PROTECTORS
11
5
1
6
E
3
50Hz only
DOWNFLOW
LOW VOLT SECTION
Note: Typical orientation of components shown. Component location varies by option and unit size.
18
17
82 83 88 89
9
16
22
19
CAUTION:
75 76 94 95 96 97 91 92 93 80 81 11 12
UPFLOW
3
B
A
24
Risk of broken or shorted low volt
wiring. Field installed low volt wiring
must be routed with loop as shown
to allow electric box to swing.
23
58 59 84 85
21
7
10
8
20
37C38C37B38B 37 38 24 50 51 55 56 70 71 230 72 73
D
B
C
D
12
49-3
49-1
SH
C
A
Form No.: DPN001040_REV4
13
Item 13 Installation Conditions
E
1. Follow all local installation codes.
2. Do not run CAN cables in same conduit, raceway, or
chase as high voltage wires (120-600V).
3. Separate high volt wires from CAN wires by 12 inches.
E
POINT OF HINGED LOW
VOLT ELECTRIC BOX
UPFLOW LOW VOLT SECTION
DPN000807
Page :3 /3
REV : 17
REV DATE : 10/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT DS
PLENUM DIMENSIONAL DATA
UPFLOW 35-42kW (10-12 TONS) MODELS W/ EC FANS
Notes:
1. All Plenums must be field assembled and EC Fans wired to unit.
7/8"
22mm
D
2. Shaded areas indicate a recommended minimum CLEARANCE OF
36" (914mm) from the bottom of the unit to the top of the plenum.
3. Must have access to remove Front Grill or panel to remove EC Fans.
4
C
4. Top duct flanges on plenum top for Supply Air ducting when
solid panel plenum is used.
5. Compressor Plenum is optional and must be
ordered separately.
6. Air Cooled Scroll or Digital Scroll Compressor.
J
G
7. Water Cooled Scroll or Digital
Scroll Compressor.
H
L
3
F
K
5
E
7/8"
22mm
Note:
Both top duct opening
and grilles shown. See
spec sheet for specific
application.
A
F
2
B
No. of
Fans/Unit
1
EC Fan Assembly Weight lb. (kg)
VS028-VS035
VS042
119 (54)
141 (64)
Form No.: DPN001040_REV4
Main unit
Main Unit Plenum Weight lb. (kg)
Plenum Height
J
Non-grilled Plenum Front Discharge Rear Discharge
in. (mm)
24 (610)
85 (39)
126 (57)
29 (59)
30 (762)
105 (48)
N/A
36 (914)
123 (56)
A
59-1/4 (1505)
DPN003458
Page :1 /1
B
33-3/4 (857)
C
57-9/16 (1463)
Plenum Dimensional Data in. (mm)
D
E
32-1/16 (815) 56-11/16 (1440)
Compressor Plenum
Width
Height
Weight
L
K
lb. (kg)
in. (mm)
in. (mm)
24 (610)
24 (11)
13 (330)
30 (762)
26 (12)
36 (914)
29 (13)
6
24 (610)
33 (15)
26 (660)
30 (762)
37 (17)
36 (914)
42 (19)
7
F
1-5/16 (33)
G
19-11/16 (500)
H
4-5/16 (109)
REV : 4
REV DATE : 5/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT iCOM™
PRODUCT INFORMATION
UNIT MOUNTED DISPLAY
The Liebert iCOM™ display is a microprocessor 9 inch color touch screen in an ergonomic, aesthetically
pleasing housing. The display and housing will be viewable while the unit accent panels are open or closed.
The display can be easily detached to view while the panel is open.
Menu Layout- The menus will be broken out into two main menu screens: User screen and Service screen.
The User screen contains the menus to access parameters required for basic unit control and setup.
The Service screen is designed for service personal and provides access to advanced control setup features
and diagnostic information.
Password Protection- The display will contain two unique passwords to protect against unauthorized changes.
An auto hide/show feature allows the user to see applicable information based on the login used.
Unit Backup and Restore- The user shall have the ability to create safety copies of important control parameters.
The display has the ability for the user to automatically backup unit configuration settings to internal memory or USB
storage drive. Configuration settings may be transferred to another unit for a more streamlined unit startup.
Parameter Download- The display has the ability for the user to download a report that lists parameter names,
factory default settings and user programmed settings in .csv format for remote reference.
Parameter Search- The display has search fields for efficient navigation and parameter lookup.
Form No.: DPN001040_REV4
Setup Wizards- The display will contain step by step tutorials or wizards to provide easy setup of the control.
DPN003245
Page :1 /2
REV : 5
REV DATE : 7/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT iCOM™
PRODUCT INFORMATION
UNIT MOUNTED DISPLAY
Context Sensitive Help- The display will have an onboard help database. The database will provide context
sensitive help to assist with setup and navigation of the menus.
Display Setup- The user has the ability to configure the display information based on the specific user’s preference.
Language, units of measure, screen contrast, home screen layout, back light timer and the hide/show of certain
readouts will be configurable through the display.
Additional Readouts- The display has the ability for the user to configure custom widgets on the main screen.
Widget options will include items such as fan speed, call for cooling, call for free cooling, maintenance status,
call for hot water reheat, call for electric reheat, call for dehumidification, call for humidification, airflow, static pressure,
fluid flow rate and cooling capacity.
Status LEDs- The display will provide the user with the unit’s operating status using an integrated LED.
The LED will indicate if the unit has an active alarm; if the unit has an active alarm that has been acknowledged;
or if the unit is on, off, or in a standby status.
Unit Alarms – All unit alarms are annunciated through both audio and visual cues, clearly displayed on the screen,
automatically recorded in the event log, and communicated to optional IntelliSlot monitoring cards.
Event Log – The display will automatically store the last 400 unit-only events (messages, warnings, and alarms).
Service Contact Information – The display has the ability to store the local service or sales contact information.
Upgradeable –Display upgrades are performed through a USB connection.
Form No.: DPN001040_REV4
Unit-to-Unit (U2U) Communication – Communication via private Ethernet network allows for advanced control
functionality (Teamwork modes, sharing sensor data, Standby Rotation, Lead-Lag, and Cascade operation).
DPN003245
Page :2 /2
REV : 5
REV DATE : 7/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT CW, DS, DSE, PDX & PCW
UNIT TO UNIT NETWORK CONNECTIONS
ETHERNET CABLE
(FIELD SUPPLIED)
DO NOT USE CANBUS
CONNECTORS
TO P42
ETHERNET CABLE
P61
P63
P64
E5
U2U NETWORKING SWITCH
(FIELD SUPPLIED)
Form No.: DPN001040_REV4
P11
P7
P13
iCOM
I/O BOARD
P12
P66
P67
P65
DPN003729
Page :1 /2
TO / FROM OTHER
NETWORKED UNITS
REV : 1
REV DATE : 1/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT CW, DS, DSE, PDX & PCW
UNIT TO UNIT NETWORK CONNECTIONS
DO NOT USE CANBUS
CONNECTORS
DO NOT USE CANBUS
CONNECTORS
ETHERNET CABLE
(FIELD SUPPLIED)
TO P42
TO P42
ETHERNET CABLE
ETHERNET CABLE
P61
P64
P63
P64
E5
E5
Form No.: DPN001040_REV4
P66
P7
P7
iCOM
I/O BOARD
P12
P11
P13
iCOM
I/O BOARD
P12
P66
P67
P65
P67
P65
P11
P63
P13
P61
DPN003729
Page :2 /2
REV : 1
REV DATE : 1/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT® LIQUI-TECT® 410
POINT LEAK-DETECTION SENSOR
Product Specification/Installation Guide
The Liebert Liqui-tect 410 (LT410)
provides single-point detection of
leaks. The point-detection sensor
has two gold-plated sensing probes
to prevent corrosion and to provide
accurate readings. The LT410
constantly monitors for leaks, internal
faults, and power failures and warns
of any abnormal conditions. Mounting
brackets allow for sensor height
adjustment and leveling.
The LT410 is the ideal solution for
sensing leaks under a raised computer
floor or air conditioning drip pans. Two
independent outputs provide added
flexibility with the capacity to signal
both a local alarm panel and a remote
building-management system or
external equipment, such as motorized
water shut-off valves.
LT410 APPLICATIONS
The LT410 is ideally-suited for:
• Glycol and chilled-water cooling,
• Humidification supply water piping,
• Condensate pumps and drains,
• Unit and ceiling auxillary drip pans,
• Overhead piping troughs.
LOCATIONS/PLACEMENT
The LT410 is an excellent choice for:
COMPONENTS OF THE
LIQUI-TECT 410 MODULE
The LT410 consists of a metal
enclosure with a hinged top door that
provides access to the internal wiring
termination. It includes side access
through a box connector for installation
of the power and contact wiring. The
mounting brackets attach to the
enclosure with adjustable slots to allow
custom setting of the height of the
sensing probes.
• Large-scale network control centers,
• Data centers,
• Server rooms and closets,
• Unattended, remote shelters,
• Mechanical equipment rooms,
• Sensitive areas with overhead piping,
• Industrial process-control rooms.
590-1351-501B/SL-31050_REV2_6-17
1
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT® LT410 POINT LEAK-DETECTION SENSOR
Product Specification/Installation Guide
DIMENSIONS TOP, FRONT AND SIDE
TOP VIEW
5.85”
(148.5mm)
FRONT VIEW
SIDE VIEW
4.46”
(113.2mm)
Form-C relay outputs
and power wiring
6.35”
(161.2mm)
Adjustable probe
height
0.0 - 0.5”
(0.0 - 12.7mm)
SPECIFICATIONS
Power Requirements
24 VAC 100 mA, 50/60 Hz, 3 VA (max.)
Dimensions, W x D x H
6.35 x 2.25 x 4.46 in (161.2 x 57.2 x 113.2 mm)
Weight (assembled)
2.0 lb (0.9 kg)
Metal Enclosure
NEMA 1, IP 30
ENVIRONMENTAL CONDITIONS
Operating Temperature
50°F to 104°F (10°C to 40°C)
Operating Humidity
10% to 95% relative humidity (non-condensing)
Operating Altitude
0 to 10,000 ft (0 to 3,048 m)
Output Relay Contact Rating
2 Form-C; 3 A rating at 24 VAC
AGENCY LISTINGS
UL
UL916
C-UL
C22.2, No. 205-M1983
CE
Yes
FCC Compliance
47 CFR, Part 15
590-1351-501B/SL-31050_REV2_6-17
2
2.25”
(57.2mm)
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT® LT410 POINT LEAK-DETECTION SENSOR
Product Specification/Installation Guide
PLACEMENT ON SUBFLOOR
UNDER COOLING SUPPORT
EQUIPMENT
To a Liebert environmental
unit and an optional
monitoring panel
To external power
supply or directly
from unit (see Power
Wiring on page 4)
2-COM
2-NC
2-NO
1-COM
1-NC
1-NO
POWER
POWER
Leak detection zone
(directly beneath
unit)
WIRING INTERCONNECTIONS
Circuits are shown in powered, non-alarm
state.
NOTE: All power and alarm connections must
be Class 2 circuits.
Gold-plated
Probes
Height adjustable
0-0.5” (0-12.7mm)
Red Wires
Orange Wires
Yellow Wires
24 V, AC/DC
@ 0.10A, 50-60 Hz, DC
Class 2 Circuit Only
Alarm Contact Rating
24 VAC @ 3A
Class 2 Circuit Only
Alarm Contact Rating
24 VAC @ 3A
Class 2 Circuit Only
590-1351-501B/SL-31050_REV2_6-17
3
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT® LT410 POINT LEAK-DETECTION SENSOR
Product Specification/Installation Guide
POWER WIRING
WIRING TO AUXILIARY ALARM PANELS
The LT410 is rated for 24 VAC, 50/60 Hz, and 0.10 A.
The LT410 has two Form-C dry contact alarm output
contacts: orange wires (1) and yellow wires (2). Each
contact is rated for 24 VAC at 3 amp.
Liebert DS, DSE, CW, PDX,
or Mini-Mate2 (8 ton) LT410
TB1TB1
T5 (24V)
G5 (Ground)
Red
Location of T5 (24V)
connection on main
controller board of
Liebert unit.
TB1
Red
Liebert Mini-Mate2 (1 to 5 ton)
Orange Wires
Environmental
Unit
1-NC
1-COM
1-NO
LT410
Orange Wires
Environmental
Unit
1-NC
1-COM
Red
From 24V Transformer
Red
1-NO
* Requires external transformer (there are no designated terminal
Orange Wires
connections on the unit)
Liebert CRV
Medium Control Board
LT410
TB1
6
Red
4
Red
50, 51, 55 or 56
Liebert Mini-Mate2,
(1 to 5 ton)
TB1
24 (24V)
Note: Terminal 50 not available on Mini-Mate2 (8-ton)
LT410
Liebert DS, DSE, LT410CW, PDX or Mini-Mate2 (8 ton)
LT410
TB1-1 (24V)
TB1-2 or TB1-3
Liebert CRV
Environmental
Unit
1-NC
1-COM 60
1-NO 61
NOTE: In iCOM, use the Service Options menu to add that the Liqui-tect is
installed.
LT410Liebert contact monitor panel
Transformer
LT410
TB1
Red
From 24V Transformer
Red
VertivCo.com
Yellow Wires
2-NC
Alarm
Panel
2-COM
2-NO
| Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or
registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all
liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
590-1351-501B/SL-31050_REV2_6-17
4
Input
Contact
(N.O.)
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT® INTELLISLOT™
UNITY PLATFORM CARDS
Product Specification/Installation Guide
The Liebert IntelliSlot Unity Platform
brings SNMP, BACnet IP, BACnet
MSTP, Modbus TCP, Modbus RTU,
YDN23 and Web management
capability to many models of Vertiv’s
power and cooling equipment. The
cards employ Ethernet and RS-485
networks to monitor and manage a
wide range of operating parameters,
alarms and notifications. The card also
supports communication for LIFE™
Services by VERTIV.
ADDITIONAL FEATURES
• SNMPv1, SNMPv2c and SNMPv3
with MIB-II support
• HTTP/HTTPS 1.1
• BootP
• DHCP per RFC2131/2132
• Remote firmware updates via a Web
browser
• IPv6 support for HTTP/HTTPS,
DHCPv6, e-mail, SMS, SNMP v1/v2c/
v3 and Modbus TCP
• Liebert SN Environmental Sensor
Support (Web, SNMP, SMS and
SMTP): Temperature, Humidity, Door
Closure, Contact Closure and Leak
Detection: Liebert SN-2D, Liebert
SN-3C, Liebert SN-L, Liebert SN-T,
Liebert SN-TH, Liebert SN-Z01,
Liebert SN-Z02 and Liebert SN-Z03
IntelliSlot Unity cards are a form, fit,
and function replacement for several
Liebert IntelliSlot Web and 485 cards.
COMPATABILITY with Liebert Equipment
IntellSlot Card
Compatible with
IS-UNITY-DP
Alber BDSU-50™
Liebert Deluxe System/3™
Liebert GXT3™
Liebert PeX™ *
IS-UNITY-SNMP
Liebert APM™
Liebert DS™
Liebert GXT4™
Liebert PPC™
IS-UNITY-LIFE
Liebert APS™
Liebert DSE™
Liebert HPC™
Liebert RDC™
Liebert Challenger
Liebert EPM™
Liebert HPC-S/M/R/W/Generic™
Liebert RX™
3000™
Liebert EXC™
Liebert HPM™
Liebert XDC™
Liebert CRV™
Liebert eXL™
Liebert NX™ 225-600 kVA
Liebert XDP™
Liebert CW™
Liebert EXL™ S1
Liebert NXC™
Liebert XDP-Cray™
Liebert DCL™
Liebert eXM™
Liebert NXL™ *
Liebert DCP™
Liebert FDC™
Liebert NXR™
Liebert FPC™
Liebert PCW™/PDX™
* YDN23 supported only for Liebert PeX and Liebert NXL.
590-1307-501C/SL-52646_REV11_6-17
1
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT® INTELLISLOT™ UNITY PLATFORM CARDS
Product Specification/Installation Guide
COMPATABILITY with Communication Protocols
Life
Services
Support
Liebert
IntelliSlot Card
Communication Protocol
HTTP
HTTPS
Velocity
Protocol
Email
SMS
SNMP
v1, v2c, v3
BACnet IP
BACnet MSTP
Modbus TCP
Modbus RTU
YDN23*
—
—
—
—
—
—
IS-UNITY-DP
IS-UNITY-SNMP
IS-UNITY-LIFE
—
* YDN23 supported only for Liebert PeX and Liebert NXL.
4-3/4” (121 mm)
DIMENSIONS
1/2” (11 mm)
3” (76 mm)
2-3/8”
(60.3 mm)
1-1/2”
(38 mm)
Front face
SPECIFICATIONS
Power Requirements
Board
DC Inputs
7 to 12 VDC
Power Consumptions:
3.6 W maximum
Dimensions, W x D x H
2.97 x 5.2 x 1.45 in. (75.5 x 15 x 37 mm)
Weight (assembled)
Net:
7 oz (0.2 kg)
Shipping:
1.3 lb (0.6 kg)
Ambient Operating Environment
32 to 104°F (0 to 40°C); 10% to 90% RH (non-condensing)
Ambient Storage Temperature
–4 to 140°F (–20 to 60°C)
Communication Ports
Ethernet Communication
RJ-45 (LIFE™ Services requires a network
connection to the Internet)
RJ-45 (RJ-45 to 2-position terminal-block adapter)
WIRING
10/100 Mb/s Ethernet connector
Standard Category 5E Cable
328 ft. (100m)
RJ-45 - One-Wire Connector
Liebert® Integrated One-Wire Sensor
Cable or 2m Cat 5E to Modular 1-Wire
65.6 ft. (20m)
VertivCo.com
| Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or
registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all
liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
590-1307-501C/SL-52646_REV11_6-17
2
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
PREMIUM EFFICIENCY CONTROL
STANDARD & OPTIONAL FEATURES
Form No.: DPN001040_REV4
STANDARD FEATURES
COIL
Liebert microchannel coils are all‐aluminum construction. Tubes are created by extruding small parallel refrigerant flow paths
into aluminum. Full‐depth louvered aluminum fins fill spaces between the tubes. Tubes, fins and aluminum headers are oven‐brazed to
form a complete refrigerant‐to‐air heat exchange coil. Baffles are used in the headers to separate one coil slab into multiple passes
as needed. Coils are factory leak tested at a minimum of 300 PSIG and dehydrated. Copper stub pipes are electric resistance welded
to aluminum coils and joints are protected with polyolefin to seal joint from environmental corrosive elements. Hot gas and liquid lines
are brazed to the stub pipes with spun closed ends for customer piping connections. Coil pipe assembles are filled and sealed with a
nitrogen holding charge for shipment. One coil is used per fan assembly.
FAN/MOTOR ASSEMBLY The fan/motor assembly is complete with external rotor motor, fan blades and fan/finger guard. Fan blades are
constructed of stamped aluminum or steel extrusion coated with PP plastic. Fan guards are heavy gauge, close meshed, steel wire,
coated with a black corrosion resistant finish. Fan terminal blocks located on the top of the fan guard with IP54 protection class. Fans
are factory balanced and tested before shipment.
FAN MOTORS Fan motors are specifically designed for variable speed and have ball bearings. The EC fans provide internal overload
protection through the built‐in electronics. Each EC fan motor has built‐in controller and communication module, linked via
RS485 communication wire to each fan and the Premium Control Board. This allows each fan to receive and respond to precise fan
speed inputs from the Premium control board.
PREMIUM EFFICIENCY FAN CONTROL The Liebert premium efficiency condenser control system is complete with control board, EC
fan motor(s),refrigerant‐pressure transducer(s), refrigerant‐temperature thermistor(s), ambient‐temperature thermistor, and motor
overload protection in the factory wired control panel. The control board maintains EC fans on the same circuit to the same speed in order
to maintain refrigerant head pressure. The control board receives a run signal from the compressor of the indoor unit via field‐supplied
low voltage interlock wires and field‐supplied CANbus communication wires from the indoor unit iCOM. The control system
provides refrigerant head pressure and system starting for outdoor ambient temperature as low as -30°F (‐35 °C), provided the
total temperature design range (from minimum to maximum) is 125°F (70°C) or less.
HOUSING The condenser housing is constructed of bright aluminum sheet and divided into individual fan sections by full width baffles.
Internal structural support members, including coil support frame, are galvanized steel for strength and corrosion resistance. Panel doors
are provided on two sides of each coil/fan section to provide for coil cleaning. Aluminum legs are provided with rigging holes for hoisting
the unit into position.
COMMUNICATION The Premium Efficiency Control communicates with the iCOM control of the indoor Liebert unit using field supplied CANbus
wires. The communication link allows for condenser alarm condition communication to iCOM, communication of other measurable items
on the condenser, and fan control features to improve efficiency, sound and wintertime operation based on iCOM programming.
UNIT DISCONNECT SWITCH Locking unit disconnect switch is factory installed and wired in attached condenser control section.
OPTIONAL FEATURES
LIEBERT LEE‐TEMP LOW AMBIENT CONTROL Lee‐Temp receiver kits can be added to achieve head pressure control down to minimum
ambient temperatures of ‐30 °F (‐34 °C). The premium efficiency fan control when used with the Liebert Lee‐Temp receiver kits runs
the fan(s) at lower speeds during cold temperatures saving fan energy.
575V POWER SUPPLY The factory installed condenser option will include a secondary enclosure, a 575V-to-480V, 3 phase, step down
transformer, secondary fuses for the transformer, and all wiring between the main and secondary electrical enclosures. Site
power connections will be made in the main electrical enclosure and the secondary enclosure will be located on the condenser end
opposite of the main electrical enclosure.
DPN002155
Page :1 /1
REV : 3
REV DATE : 2/18
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
CABINET & ANCHOR DIMENSIONAL DATA
2 FAN (MCS056, MCM080, MCL110) DUAL CIRCUIT
575V
Option
575V
Option
H
TOP OF
G FAN GUARD
A*
A
F
Lee-Temp or DSE Receiver
C
Entering Hot Gas and
Leaving Liquid Piping
D
A
Anchor Plan
Main
Electric
Box
End
Full height leg supplied for
each Lee-Temp or
DSE Receiver required
M L K
15 1/4"
387mm
Left Side of Unit
13/16"
21mm
Typ.
J
Lee-Temp or DSE Only
3
3 5/8"
93mm
Typ.
Front View (Lee-Temp Shown)
DETAIL A
F
MODEL
NUMBER
MCS056
MCM080
Form No.: DPN001040_REV4
2 Cross bracing required for legs longer
than 18" (457mm). Quantity varies per
model & options selected.
LIEBERT
MODEL
NUMBER
A
A*
(575V ONLY)
3
2
(LEG HEIGHT DIMENSIONS)
18 (457)
36 (914)
48 (1219)
60 (1524)
DIM "G"
31-5/8 (803)
49-5/8 (1260)
61-5/8 (1565)
73-5/8 (1870)
DIM "H"
39-5/8 (1006)
57-5/8 (1464)
69-5/8 (1768)
81-5/8 (2073)
MCL110
DIM "G"
35-7/8 (911)
53-7/8 (1368)
65-7/8 (1673)
77-7/8 (1978)
DIM "H"
43-5/8 (1108)
61-5/8 (1565)
73-5/8 (1870)
85-5/8 (2175)
Typical All Legs
Note:
1. Liebert recommends a clearance of
36” (915mm) on each side for proper
operation and component access.
3
6 1/2"
165mm Ref.
Ref.
Dual Circuit Only
15 1/4"
K
387mm
Dual Circuit Only
LIEBERT
All primary dimensions
in tables are in inches
(Secondary are in mm)
except where specified
1 7/8"
48mm
Typ.
1/2" (13mm) X 1" (25mm)
Obround Typ.
7"
178mm
Typ.
3
6 1/2"
165mm
C
D
J
Lee-Temp
or
DSE Receivers
Only
K
L
M
MCS056
MCM080
94-7/8 (2411) 103-1/8 (2619) 88-3/8 (2245) 86-3/4 (2203)
105-1/4 (2674) 113-7/16 (2882) 96-1/16 (2440) 94-7/16 (2398)
42-1/2 (1079) 42-1/2 (1080) 40-7/8 (1038) 35-7/8 (910)
46-5/16 (1177)
46 (1168) 44-3/8 (1127) 39-5/16 (999)
3 For DSE models only, 6-1/2" (165mm)
MCL110
dimension is 9-1/4" (235mm) and
15-1/4 (387mm) dimension is not applicable.
DPN003437
Page :1 /1
124-1/8 (3152) 133-1/8 (3381) 112-1/8 (2848) 110-1/2 (2806)
54-3/8 (1381)
55-1/2 (1410) 53-7/8 (1368) 48-3/4 (1238)
REV : 4
REV DATE : 12/16
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
CONDENSER AND OPTION WEIGHT DATA, lb(kg)
Size
Condenser Model
Refrigerant Circuits
Condenser Dry
Weight
Small (MCS)
MCS028
MCS056
MCM040
Medium (MCM)
MCM080
MCM160
1
2
1
1
2
2
18" Leg
154 ( 70)
270 ( 122)
231 ( 105)
441 ( 200)
441 ( 200)
860 ( 390)
36" Leg
286 ( 130)
419 ( 190)
363 ( 165)
590 ( 268)
590 ( 268)
1066 ( 484)
48" Leg
318 ( 144)
451 ( 205)
395 ( 179)
622 ( 282)
622 ( 282)
1114 ( 505)
60" Leg
349 ( 158)
482 ( 219)
426 ( 193)
653 ( 296)
653 ( 296)
1160 ( 526)
110 ( 50)
PDX-EEV Receiver
Lee-Temp
DSE Receiver DA050/080/085
DSE Receiver DA125/150/165
575V Transformer
Coated Coil
Seismic/Wind Bracing 18" legs
Size
Condenser Model
Refrigerant Circuits
18" Leg
Condenser Dry
36" Leg
weight
48" Leg
60" Leg
PDX-EEV Receiver
Lee-Temp
DSE Receiver DA050/080/085
DSE Receiver DA125/150/165
575V Transformer
Coated Coil
Seismic/Wind Bracing 18" legs
Additional Weight for Options
45 ( 20)
45 ( 20)
55 ( 25)
110 ( 50)
55 ( 25)
55 ( 25)
65 ( 29)
60 ( 27)
45 ( 20)
100 ( 45)
45 (20)
92 (42)
70 ( 32)
70 ( 32)
220 ( 100)
90 (41)
184 ( 83)
80 ( 36)
4 ( 2)
8 ( 4)
5 ( 2)
10 ( 5)
10 ( 5)
20 ( 9)
40 ( 18)
40 ( 18)
40 ( 18)
40 ( 18)
40 ( 18)
57 ( 26)
Large (MCL)
MCL110
MCL055
MCL165
1
1
2
1
344 ( 156)
602 ( 273) 602 ( 273)
891 ( 404)
486 ( 220)
766 ( 347) 766 ( 347) 1136 ( 515)
518 ( 235)
798 ( 362) 798 ( 362) 1184 ( 537)
549 ( 249)
829 ( 376) 829 ( 376) 1230 ( 558)
Additional Weight for Options
45 ( 20)
60 ( 27)
115 ( 52)
120 ( 54)
175 ( 79)
45 ( 20)
90 ( 41)
45 (20)
94 ( 43)
94 ( 43)
67 ( 30)
77 ( 35)
77 ( 35)
118 ( 54)
8 ( 4)
16 ( 7)
16 ( 7)
24 ( 11)
40 ( 18)
40 ( 18)
41 ( 19)
57 ( 26)
MCL220
1
2
1186 ( 538) 1186 ( 538)
1453 ( 659) 1453 ( 659)
1501 ( 681) 1501 ( 681)
1547 ( 702) 1547 ( 702)
215 ( 98)
45 ( 20)
94 ( 43)
118 ( 54)
32 ( 15)
57 ( 26)
240 ( 109)
90 ( 41)
188 ( 85)
118 ( 54)
32 ( 15)
57 ( 26)
Form No.: DPN001040_REV4
Total weight is the sum of 'Condenser' + ('PDX-EEV Receiver' or 'Lee-Temp' or 'DSE Receiver 050/080/085' or 'DSE Receiver
125/150/165')'+'Coated Coil' + '575V Transformer'.+ 'Seismic/Wind Bracing'
DPN003034
Page :1 /1
REV : 4
REV DATE : 4/18
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
PIPING DIMENSIONAL DATA
DUAL CIRCUIT 2 FAN & 4 FAN UNITS
COVER *
VERTICAL
INVERTED TRAPS
ARE FACTORY PROVIDED
INSIDE CONDENSER
FIELD PIPING
LEAVING LIQUID
LINE
HORIZONTAL
ENTERING HOT
GAS LINE
DETAIL A
CIRCUIT #1
CIRCUIT #2
OPTIONAL FUSIBLE PLUG SERVICE KIT TO
BE BRAZED INTO THE LIQUID LINE(S) IN
EITHER THE VERTICAL OR HORIZONTAL
POSITION (WHERE REQUIRED).
(VERTICAL POSITION IS PREFERRED,
HORIZONTAL POSITION IS OPTIONAL.)
FOR TWO CIRCUIT SYSTEMS, ONE
FUSIBLE PLUG KIT WILL NEED TO
BE INSTALLED IN EACH CIRCUIT.
MODEL NO.
Form No.: DPN001040_REV4
MCS 056
MCM 080
MCL 110
MCM 160
MCL 220
A
NUMBER CONDENSER CONNECTION SIZES ,OD,IN
OF FANS
CIRCUITS HOT GAS LINE LIQUID LINE
2
2
7/8
5/8
2
2
7/8
5/8
2
2
1-1/8
7/8
4
2
1-1/8
7/8
4
2
1-3/8
1-1/8
* SHIPPING COVER IS NOT NECESSARY FOR PROPER CONDENSER OPERATION AND
MAY BE RECYCLED IF FIELD PIPING INTERFERES WITH PROPER REATTACHMENT.
DPN002425
Page :1 /1
REV : 6
REV DATE : 12/16
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT AIR COOLED SYSTEMS
RECOMMENDED REFRIGERANT LINE SIZES CU, OD
LIEBERT AIR-COOLED SYSTEMS USING R-410A
System Fluid : R-410A
Indoor Model
CR019RA/ CR020RA
CR035RA
PX011
PX018
PX023
PX029
DA050 / DA080/
DA085
DA125
DA150
DA165
DA250
Equivalent Length
Hot Gas Line, in.
Liquid Line, in.
Hot Gas Line, in.
Liquid Line, in.
Hot Gas Line, in.
Liquid Line, in.
Hot Gas Line, in.
Liquid Line, in.
Hot Gas Line, in.
Liquid Line, in.
Hot Gas Line, in.
Liquid Line, in.
Hot Gas Line, in.
Liquid Line, in.
Hot Gas Line, in.
Liquid Line, in.
Hot Gas Line, in.
Liquid Line, in.
Hot Gas Line, in.
Liquid Line, in.
Hot Gas Line, in.
Liquid Line, in.
System Fluid: R-410A
Indoor Model Equivalent Length 50 ft (15m)
Suction Line, in.
1-1/8
MT060
Liquid Line, in.
1/2
Suction Line, in.
7/8
MT048
Liquid Line, in.
1/2
50 ft (15m)
3/4
5/8
7/8
3/4
1/2
3/8
5/8
1/2
3/4
5/8
7/8
5/8
1-1/8
7/8
1-3/8
7/8
1-3/8
7/8
1-3/8
7/8
1-5/8
1-3/8
Any Compressor Type
100 ft (30m)
150 ft (45m) 300 ft (91m)
3/4
3/4
7/8 2
5/8
5/8
3/4
7/8
7/8
1-1/8 2
3/4
3/4
7/8
2
2
5/8
5/8
5/8 2
1/2
1/2
1/2
5/8
5/8
3/4 2
1/2
1/2
5/8
3/4
3/4
7/8 2
5/8
5/8
5/8
7/8
7/8
1-1/8 2
5/8
5/8
3/4
1-1/8
1-1/8
1-1/8
7/8
7/8
7/8
1-3/8
1-3/8
1-3/8
7/8
7/8
7/8
1-3/8
1-3/8
1-3/8
1-1/8
1-1/8
1-1/8
1-3/8
1-3/8
1-3/8
1-1/8
1-1/8
1-1/8
4
1-5/8
1-5/8
1-5/8 4
4
1-3/8
1-3/8
1-3/8 4
450ft (137m)
1-1/8
7/8
1-3/8
7/8
1-3/8
1-1/8
1-3/8
1-1/8
3
3
3
3
3
3
3
3
Digital Scroll Models
75 ft (23m) 100 ft (30m) 125 ft (38m) 150 ft (45m)
1-1/8
1-1/8
1-1/8
1-1/8
5/8
5/8
5/8
5/8
2
2
2
1-1/8
1-1/8
1-1/8
1-1/8 2
1/2
5/8
5/8
5/8
Form No.: DPN001040_REV4
Notes:
1. Consult factory for proper line sizing for runs longer than maximum equivalent length shown in table.
2. Must downsize vertical riser one trade size (1-1/8” to 7/8” or 7/8” to 3/4” or 3/4" to 5/8" or 5/8" to 1/2").
3. Consult factory when actual pipe length between condenser/EconoPhase and Liebert DSE unit will exceed 300 ft (91 m).
4. Liebert DA250 unit can be extended to max 200' linear or 300' equivalent.
DPN000788
Page :1 /2
REV : 10
REV DATE : 3/18
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT AIR COOLED SYSTEMS
RECOMMENDED REFRIGERANT LINE SIZES CU, OD
LIEBERT AIR-COOLED SYSTEMS USING R-407C
System Fluid : R-407C
Indoor Model
50 ft (15m)
100 ft (30m)
150 ft (45m)
Hot Gas Line, in.
7/8
7/8
7/8
3/4
7/8
7/8
Liquid Line, in.
1/2
5/8
5/8
1/2
5/8
5/8
Hot Gas Line, in.
7/8
7/8
7/8
7/8
7/8
1-1/8
Liquid Line, in.
1/2
5/8
5/8
5/8
5/8
DS042
DS053
DS070
3
DS105
3
XDC160
200 ft (60m)
Hot Gas Line, in.
7/8
1-1/8
1-1/8
7/8
Liquid Line, in.
5/8
7/8
7/8
7/8
5/8
2
1-1/8
2
1-1/8
7/8
2
2
7/8
2
2
Hot Gas Line, in.
1-1/8
1-1/8
1-1/8
Liquid Line, in.
7/8
7/8
7/8
7/8
7/8
7/8
Hot Gas Line, in.
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
1-1/8
Liquid Line, in.
7/8
7/8
7/8
7/8
7/8
7/8
Hot Gas Line, in.
1-3/8
1-3/8
1-3/8
1-3/8
1-3/8
1-3/8
Liquid Line, in.
7/8
7/8
1-1/8
7/8
7/8
1-1/8
Hot Gas Line, in.
1-1/8
Liquid Line, in.
7/8
4
1-1/8
4
Indoor Model
MMD12
MMD18 / DME020
MMD24 / DME027
MMD36/ MMD35 / DME037 /
MMD96-3T / MMD95-3T
MMD60/ MMD59 / MMD96-5T
/MMD95-5T
1-1/8
4
1-3/8
1-1/8
1-1/8
1-1/8
4
1-3/8
1-1/8
System Fluid : R-407C
Form No.: DPN001040_REV4
or Digital Scroll Models
50 ft (15m)
100 ft (30m)
150 ft (45 m)
Equivalent Length
DS035
DS077
4-Step Semi-Hermetic
Standard Scroll Models (Non-Digital Scroll)
1-1/8
Standard Scroll Models (Non-Digital Scroll)
Equivalent Length
50 ft (15m)
75 (23m)
100 ft (30m)
125 (38m)
150 ft (45m)
Suction Line, in.
Liquid Line, in.
Suction Line, in.
Liquid Line, in.
Suction Line, in.
Liquid Line, in.
Suction Line, in.
Liquid Line, in.
Suction Line, in.
Liquid Line, in.
5/8
5/8
7/8
7/8
7/8
3/8
3/8
3/8
3/8
3/8
5/8
7/8
7/8
7/8
7/8
3/8
3/8
3/8
1/2
1/2
7/8
7/8
7/8
7/8
7/8
3/8
3/8
1/2
1/2
2
1/2
2
2
7/8
7/8
1-1/8
1/2
1/2
1/2
1/2
1/2
1-1/8
1-1/8
1-1/8
1-3/8
1-3/8
1/2
5/8
5/8
5/8
5/8
1-1/8
1-1/8
Note:
1. Consult factory for proper line sizing for runs longer than maximum equivalent length shown in tables above.
2. Downsize vertical riser one trade size (1-1/8" to 7/8").
3. Digital scroll not available on 077 and 105 models.
4. Double risers are required when hot gas vertical rise is 15 ft (4.6m) or more. Refer to XDC user manual
DPN000788
Page :2 /2
REV : 10
REV DATE : 3/18
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
TYPICAL PIPING SCHEMATIC FOR AIR-COOLED DX SYSTEMS
Optional Field Installed
Fusible Plug
Check Valve
Relief Valve
Service
Valve
Pressure
Transducer
LEE-TEMP RECEIVER
Head Pressure
Control Valve
LIQUID RETURN
Pressure
Transducer
Check Valve
CONDENSER COIL
CONDENSER COIL
(Includes factory provided
inverted trap. No
external trap required)
(Includes factory provided
inverted trap. No
external trap required)
HOT GAS DISCHARGE
LIEBERT MC CONDENSER
LIEBERT MC CONDENSER WITH LEE-TEMP OPTION
LIQUID
Sensing
Bulb
EVAPORATOR
COIL
3
For rises over
25ft. (7.6m), trap
every 20ft. (6m)
or evenly divided
SUCTION
Service
Valve
Check
Valve
COMPRESSOR
3
Service
Valve
Field installed relief valve(s) required
for 50Hz EU CE units.
External
Equalizer
HOT GAS DISCHARGE
Expansion Solenoid
Valve
Valve
Sight
Glass
FACTORY REFRIGERANT PIPING
FIELD PIPING
Filter Drier
LIQUID LINE
INTERCONNECTING
PIPING
SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
Notes:
1. Single refrigeration circuit shown for clarity.
2. Schematic representation shown. Do not use for specific connection locations.
3
Trap at base of risers
over 5ft. (1.5m)
Form No.: DPN001040_REV4
3. Components are not supplied by Liebert, but are required for proper operation and maintenance.
4. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor. Pitch horizontal hot gas piping at a minimum of
1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
5. Do not islolate any refrigeration circuits from over pressurization protection.
DPN002188
Page :1 /1
REV : 7
REV DATE : 12/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
AIR COOLED PIPING SCHEMATIC
CONDENSER ABOVE INDOOR UNIT
Liquid
Gas
Gas
Notes:
1. Trapping must be practiced at bottom of riser with any
rise over 5 feet high. If rise exceeds 25 feet (7.5m), then
a trap is required in 20 foot (6 m) increments or evenly divided
2. Pitch horizontal hot gas piping at a minimum of
1/2" per 10 feet (42mm per 10m) so that gravity will
aid in moving oil in the direction of the refrigeration flow.
3. Single circuit condenser shown.
4. Unit piping entrance varies by unit and may be through
the top of the unit.
5. Indoor unit may be Liebert DS, PDX, or CRV and
is shown for reference only while demonstrating proper
pipe and unit/condenser height differences.
60'
18.3m
Maximum
Vertical Rise
Liquid
Indoor Unit
Field piping
1
Gas
1
Gas
2
4
Liquid
Form No.: DPN001040_REV4
Liquid
DPN003954
Page :1/3
REV : 3
REV DATE : 5/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
AIR COOLED PIPING SCHEMATIC
CONDENSER AND INDOOR UNIT AT SAME LEVEL
Indoor Unit
Gas
1
Liquid
3
Field piping
Notes:
Form No.: DPN001040_REV4
1. Pitch horizontal hot gas piping at a minimum of
1/2" per 10 feet (42mm per 10m) so that gravity will
aid in moving oil in the direction of the refrigeration flow.
2. Single circuit condenser shown.
3. Unit piping entrance varies by unit and may be through
the top of the unit.
4. Indoor unit may be Liebert DS, PDX, or CRV and
is shown for reference only.
DPN003954
Page :2/3
REV : 3
REV DATE : 5/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
AIR COOLED PIPING SCHEMATIC
CONDENSER BELOW INDOOR UNIT
Indoor Unit
4
Gas
15'
4.6m
Maximum
Vertical Drop
Liquid
Gas
Field piping
Gas
Form No.: DPN001040_REV4
Liquid
Notes:
1. Pitch horizontal hot gas piping at a minimum of
1/2" per 10 feet (42mm per 10m) so that gravity will
aid in moving oil in the direction of the refrigeration flow.
2. This Configuration is not valid for Liebert MC with Lee-Temp
or unheated receiver.
3. Single circuit condenser shown.
4. Unit piping entrance varies by unit and may be through
the top of the unit.
5. Indoor unit may be Liebert DS, PDX, or CRV and
is shown for reference only while demonstrating proper
pipe and unit/condenser height differences.
DPN003954
Page :3/3
REV : 3
REV DATE : 5/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL
FAN 2
FAN 1
8
10
SH
12
9
13
70
71
230
NOTICE !
THIS HOLE FOR FIELD
SUPPLIED EXTRA LOW
VOLTAGE CONTROL WIRING
KEY ELECTRICAL DETAILS:
1)
Three phase electrical service – Terminals are on top of disconnect switch for one and two fan units. Terminals are on bottom of
Form No.: DPN001040_REV4
disconnect switch for three and four fan units. Three phase service not by Liebert. See note 5.
2)
Earth ground – Field lug terminal for earth ground connection. Ground terminal strip for fan motor ground connection.
3)
Primary high voltage entrance – Two 7/8” (22.2mm) diameter knockouts located at the bottom of the enclosure.
4)
SPD field connection terminals – High voltage surge protective device (SPD) terminals. SPD is an optional device.
DPN002169
Page :1 /3
REV : 10
REV DATE : 2/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL
5)
CANbus terminal connections – Field terminals for CANbus cable connection.
• 5A is the CANbus connectors.
o TB49-1 is the input terminal for CANbus high.
o TB49-3 is the input terminal for CANbus low.
o TB50-1 is output terminal for CANbus high.
o TB50-3 is the output terminal for CANbus low.
o Each CANbus cable shield is connected to terminal “SH”, item 9.
• 5B is the “END OF LINE” jumper.
• 5C is the CANbus “DEVICE ADDRESS DIP SWITCH”. CANbus cable not by Liebert. See Note 2. (below)
6)
Remote unit shutdown – Replace existing jumper between terminals TB38-1 and TB38-2 with field supplied normally closed
switch having a minimum 75VA 24VAC rating. Use field supplied Class 1 wiring. (This is an optional feature that may be owner specified.)
7)
Alarm terminal connections –
a.
Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common, TB74-2 is normally open, and TB74-3 is
normally closed. 1 Amp 24VAC is the maximum load. Use Class 1 field supplied wiring.
b.
Shutdown Alarm Relay indicates when condenser loses power, or when a critical alarm has occurred that shuts down the
condenser unit. TB74-4 is common, TB74-5 is normally open, and TB74-6 is normally closed. 1 Amp 24VAC is the maximum load.
Use Class 1 field supplied wiring.
8)
Indoor unit interlock and SPD alarm terminals –
a.
On any call for compressor operation, normally open contact is closed across terminals 70 and 71 for Circuit 1, and normally open
contact is closed across terminals 70 and 230 for Circuit 2 from indoor room unit.
b.
9)
During SPD alarm, normally open contact is closed across terminals 12 & 13. SPD is an optional device.
CANbus shield terminal – Terminal for field shield connection of the CANbus field supplied cables. The shield of CANbus field supplied
cables must not be connected to ground at the condenser.
10) Primary low voltage entrance – One 7/8” (22.2mm) diameter knockout that is free for customer low voltage wiring.
11) SPD entrance – One 7/8” (22.2mm) diameter knockout hole located at the bottom of the enclosure. High voltage surge protective device
(SPD) is optional.
NOTES:
1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
- Braided shield or foil shield with drain wire
- Shield must be wired to ground at indoor unit
- 22-18AWG stranded tinned copper
- Twisted pair (minimum 4 twists per foot)
- Low Capacitance (15pF/FT or less)
- Must be rated to meet local codes and conditions
- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER
Form No.: DPN001040_REV4
3. Do not run in same conduit, raceway, or chase as high voltage wiring.
4. For CANbus network lengths greater than 450FT (137M) call Factory.
DPN002169
Page :2 /3
REV : 10
REV DATE : 2/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL
Form No.: DPN001040_REV4
5.
6.
7.
8.
9.
10.
All wiring must be sized and selected for insulation case per NEC and other local codes.
Do not bend cables to less than four times the diameter of the cable.
Do not deform cables when securing in bundles or when hanging them.
Avoid running the cables by devices that may introduce noise, such as machines, fluorescent lights, and electronics.
Avoid stretching cables.
The electrically commutated (EC) motors included in the Liebert MC Condenser are suitable for connection to power supplies with a
solidly grounded neutral or high resistance to ground or corner ground.
a. Acceptable power supplies for 208 to 575V nominal units:
•
208V wye with solidly grounded neutral and 120V line to ground;
•
380V wye with solidly grounded neutral and 220V line to ground;
•
480V wye with solidly grounded neutral and 277V line to ground;
•
575V wye with solidly grounded neutral and 332V line to ground (uses step-down transformer);
•
Wye with high resistance (or impedance) ground;
•
Delta with corner ground
b. Unacceptable power supplies for 208V to 575V nominal units:
•
Delta without ground or with floating ground;
•
Delta with grounded center tap.
DPN002169
Page :3 /3
REV : 10
REV DATE : 2/17
Document generated 25 mayo 2018 01:34 (EST).
LIEBERT DS
CANbus & INTERLOCK CONNECTIONS
BETWEEN LIEBERT DS & LIEBERT MC CONDENSER (PREMIUM)
CAN L
TB50
CAN H
D58
J6
L
1
2
3
P15
A
1
TB50
OUTPUT
B
1
H
3
J6 TERMINATION JUMPER
MUST BE SET TO PINS 1 AND 2.
TB49
J4
TB50
L
OUTPUT
1
1
2
3
3
TB49
INPUT
CONDENSER
H
P80
ON
3
J6
CANbus ADDRESSING SWITCH
1
2
3
TB49
INPUT
1
2
3
CAN H
CAN L
3
CAN SW6
BOOTPSWD SYS APP
ON
CAN SW6
DETAIL 3
CAN CABLE CONNECTION (A)
A
SHIELD CONNECTION
FACTORY WIRING BETWEEN
MC CONTROL BOARD AND
TERMINAL STRIP.
SH
F
LOW VOLTAGE FIELD ENTRANCE
LOCATED ON BOTTOM LEFT OF
CONDENSER ENCLOSURE.
DETAIL 2
HEAT REJECTION INTERLOCK (F)
SHIELD
CABLE NOTES (A):
1. CABLE MUSTHAVE THE FOLLOWING SPECIFICATIONS:
CONNECTION
- BRAIDED SHIELD OR FOIL SHIELD WITH DRAIN WIRE
- SHIELD MUST BE WIRED TO GROUND AT INDOOR UNIT
- 22-18AWG STRANDED TINNED COPPER
- TWISTED PAIR (MINIMUM 4 TWISTS PER FOOT)
- LOW CAPACITANCE (15pF/FT OR LESS)
- MUST BE RATED TO MEET LOCAL CODES AND CONDITIONS.
- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA
SH
WIRE 6454 CATEGORY 5, 5E, OR HIGHER.
2. DO NOT RUN IN SAME CONDUIT, RACEWAY, OR CHASE AS
49-1
HIGH VOLTAGE WIRING.
49-3
3. FOR CANBUS NETWORK LENGTHS GREATER THAN
450FT(137M), CONTACT LIEBERT FACTORY.
Form No.: DPN001040_REV4
DPN003267
Page :1 /1
F HEAT REJECTION INTERLOCK
HEAT REJECTION INTERLOCK (F)
COMPONENT NOTES:
1. COMPONENT APPEARANCE, ORIENTATION , AND POSITION MAY VARY
BETWEEN PRODUCT LINES. TERMINAL NAMES AND CALLOUTS REMAIN
CONSTANT.
2. ALL CIRCUITS TO THESE CONNECTION POINTS ARE CLASS 2.
WIRE NOTES (F):
1. FIELD SUPPLIED WIRE
- 3 CONDUCTOR 18AWG OR GREATER
- RATED 600V
2. RUN FIELD SUPPLIED WIRES BETWEEN
THE INDOOR UNIT AND THE CONDENSER.
REMOVE JUMPER
FOR DUAL CIRCUIT
70
71
230
70 71 230
F
A
CANbus CONNECTION
2
1
A
DETAIL 1 CAN CABLE CONNECTION (A)
FACTORY WIRING BETWEEN ICOM AND TERMINAL STRIP.
INDOOR DS UNIT
REV : 4
REV DATE : 4/18