SECTION 26 05 27 TELECOMMUNICATIONS BONDING INFRASTRUCTURE PART 1 1.01 1.02 15-089 GENERAL REQUIREMENTS A. The Division 27 Contractor shall work with the Division 26 Contractor who shall be responsible for the grounding system and shall follow Section 26 05 26, "Grounding & Bonding" requirements and include the telecommunications grounding listed in Section 1.02.B.1, below. The Division 27 Contractor shall be responsible for grounding work identified in Section 1.02.B.2 below. B. The Contractor shall supply a grounding system as shown on the Drawings, specified herein and per ANSI/TIA-607-B Generic Telecommunications Grounding (Earthing) and Bonding for Customer Premises. SCOPE A. The aim of this document is to install a proper grounding system to achieve the following needs: 1. Safety from electrical hazards 2. Reliable signal reference within the network 3. Satisfactory and/or enhanced electromagnetic performance of the network B. The "Grounding System" shall be a shared responsibility between the Division 26 (Electrical) Contractor and Division 27 (Low Voltage) Contractor. See attached schematic diagram. The Division 27 Contractor shall be responsible for coordinating his/her work with the Division 26 Contractor and the General Contractor. 1. The Division 26 Contractor shall supply and install the grounding system as specified in Section 26 05 26, "Grounding & Bonding" and is also to include the following: a. Provide the TMGB (Telecommunication Main Grounding Busbar) in the MTR (Main Technology Room/Demarc room). b. The TMGB shall be connected to an earth ground (ground loop surrounding the building, if available) and the building steel. c. Provide a TGB (Telecommunication Grounding Busbar) in each TR located throughout the facility. d. Each TGB shall be connected to building steel and the equipment ground terminal of the nearest AC electrical panelboard serving the telecommunications equipment in the TR. e. Provide and connect the TBB (Telecommunications Bonding Backbone) from the TMGB to all TGBs. 2. The Division 27 Contractor shall: a. Connect via compression connectors all equipment, ladder rack, basket rack, telecom racks, cabinets, conduits, sleeves, and other equipment, in each TR and/or MTR, green insulated, stranded copper ground conductor to the TGB and/or TMGB located in each TR and/or MTR. These bonding conductors shall minimum conductor size #6 AWG, and sized at 2 kcmil per linear foot up to a maximum size of 750 kcmil per the table below. 26 05 27 - 1 26 05 27 - TELECOMMUNICATIONS BONDING INFRASTRUCTURE Sizing of the Bonding Conductors TBB Length in Linear Feet TBB Size (AWG) Less than 13 6 14-20 4 21-26 3 27-33 2 34-41 1 42-52 1/0 53-66 2/0 67-84 3/0 85-105 4/0 106-125 250 kcmil 126-150 300 kcmil 151-175 350 kcmil 176-250 500 kcmil 251-300 600 kcmil Greater than 301 750 kcmil C. PART 2 2.01 2.02 The Division 27 Contractor shall work with and coordinate with the Division 26 Contractor to ensure that all aspects of the grounding system are complete and operational. PRODUCTS BUSBAR A. The TMGB (Telecommunication Main Grounding Busbar) shall be solid copper grounding busbar, 1/4 inch thick x 4 inches high x 12 inches (minimum) length, as required to be supplied by the Division 26 Contractor. B. The TGB (Telecommunication Grounding Busbar) shall be solid copper grounding busbar, 1/4 inch thick x 2 inches high x 10 inches (minimum) length, as required to be supplied by the Division 26 Contractor. C. The TMGB and TGB shall be drilled with holes per NEMA standard for attaching compression fittings to be supplied by the Division 26 Contractor. D. Vertical grounding strip busbars shall be provided for all equipment racks. Vertical rack busbars provide clean bond to any rack mounted equipment regardless of whether or not equipment has an integrate grounding terminal. Vertical rack busbars shall be a minimum 45U with universal mounting hold pattern. COPPER CABLE A. All wire used for telecommunications grounding purposes shall be identified with green insulation. Non-insulated wire shall use green tape wrap at each termination point. B. If not shown on Drawings, Division 26 Contractor shall size grounding conductors to be used for connecting the TGBs to the TMGB and the building steel. 26 05 27 - 2 15-089 26 05 27 - TELECOMMUNICATIONS BONDING INFRASTRUCTURE C. Telecommunications Bonding Backbone (TBB) Conductors 1. The TBB is a conductor that is intended to equalize potentials between TRs on multiple floors of a building with an ultimate connection to the TMGB. 2. The TBB shall be installed in conduit. 3. The TBB shall be bare or insulated copper, minimum conductor size #6 AWG, and sized at 2 kcmil per linear foot up to a maximum size of 750 kcmil. These sizes are based upon TBB length per ANSI/TIA-607-B recommendations. The Division 26 Contractor shall bring to the attention of the A/E anywhere the TBB sizing appears insufficient per the Table below. Sizing of the TBB TBB Length in Linear Feet TBB Size (AWG) Less than 13 6 14-20 4 21-26 3 27-33 2 34-41 1 42-52 1/0 53-66 2/0 67-84 3/0 85-105 4/0 106-125 250 kcmil 126-150 300 kcmil 151-175 350 kcmil 176-250 500 kcmil 251-300 600 kcmil Greater than 301 750 kcmil 15-089 D. Grounding Equalizer (GE) Conductors 1. The GE is a conductor that is intended to equalize potentials between TRs on the same floor. 2. The GE shall be installed in conduit. 3. Multi-story buildings with multiple risers (multiple TBBs) shall employ a GE between vertical grounding backbones at the top floor of the building and minimally at every third floor in between to the lowest floor level. The GE conductor shall be no smaller than the largest sized TBB. E. Bonding Conductor for Telecommunications (BCT) 1. The BCT is a conductor that is intended to bond the TMGB to the AC grounding (earthing) electrode system. 2. The BCT shall be installed in conduit. 3. The BCT conductor shall be no smaller than the largest sized TBB. F. Telecommunications Equipment Bonding Conductor (TEBC) 1. The TEBC is a conductor that intended to bond the equipment racks to the TGB or TMGB. 2. Racks and cabinets shall have individual rack bonding conductors (RBC) bonding to the TEBC. 3. In smaller TRs (3-5 racks), it is acceptable to have TEBCs that go directly from each individual rack to the TGB. 26 05 27 - 3 26 05 27 - TELECOMMUNICATIONS BONDING INFRASTRUCTURE G. PART 3 3.01 Alternating Current Equipment Ground (ACEG) 1. The ACEG is a conductor that intended to bond the nearest AC electrical panelboard serving the telecommunications equipment in the TR to the TGB or TMGB. EXECUTION WORK TO BE DONE A. The Division 26 Contractor shall provide the TMGB and the TGB in each room requiring grounding. B. The Division 26 Contractor shall provide all grounding cabling required connecting the TMGB to earth and building steel and all cabling required connecting the TGBs to building steel and to the TMGB. C. The Division 26 Contractor shall provide all GE conductors where required. D. The Division 27 Contractor shall provide and connect all grounding cables required in the MTR and TR to properly ground all equipment to the TMGB and TGB. E. The completed installation (from TGB to TMGB to ground) shall be tested by the Division 26 Contractor and a record of test supplied to the Division 27 Contractor and the Engineer. The Division 27 Contractor shall include these test results in the "Record and Information Manual." END OF SECTION 26 05 27 - 4 15-089