Technical Data
EEDEN13-100
RXS-K
• Outdoor Unit • Pair application • RXS-K
TABLE OF CONTENTS
RXS-K
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nominal Capacity And Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3
4
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
18
Cooling/Heating Capacity Tables
5
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensional Drawings
6
8
10
44
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagrams - Single Phase
9
42
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Piping Diagrams
41
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Centre of Gravity
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
46
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Sound Pressure Spectrum - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound Pressure Spectrum - Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
48
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
50
Operation Range
• Split - Sky Air • Outdoor Unit
49
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
1
• Outdoor Unit • Pair application • RXS-K
1
Outdoor units for pair application
•
•
Daikin outdoor units are neat, sturdy and can easily be mounted on a
roof or terrace or simply placed against an outside wall
Outdoor units are fitted with a swing compressor, renowned for its low
noise and high energy efficiency
•
Anti-corrosion treated outdoor heat exchanger fin
•
Outdoor unit silent operation: "silent" button on the remote control
lowers the operation sound of the outdoor unit by 3dBA to ensure a
quiet environment for the neighbourhood.
k ic Sni Ul -p rp oa t o Ki dr - l ti S puaX S•OPR
1
Features
1
Inverter
2
Energy saving Powerful mode Auto cooling- Outdoor unit
silent operation
heating
during standby
changeover
mode
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
2
Specifications
2-1 Nominal Capacity And Nominal Input
Cooling capacity
Min.
FTXS20K/RXS20K
kW
Nom.
Btu/h
4,400
4,800
5,800
kcal/h
-
1,200
2.0 (2)
6,800 (2)
4,300 (2)
2
5.0
5.3
17,100
18,100
4,300
3,440
1.4
1.7
Btu/h
4,400
4,800
5,800
kcal/h
-
1,200
4.00 (3)
5.40 (3)
5.8 (3)
8,500 (3)
9,600 (3)
13,600 (3)
18,400 (3)
19,800 (3)
4,990 (3)
3,440 (3)
4,640 (3)
4.3
4.7
5.2
6.0
6.5
14,700
16,000
17,700
20,500
22,200
5,160
5,590
-
4,470
A+
kW
A++
2.00
2.50
3.50
5.71
6.37
6.97
kWh
123
137
176
223
kW
2.30
2.50
3.60
4.00
4.75
4.63
4.71
4.09
4.10
678
756
1,071
1,371
1,571
Energy label
OD
kWh
kWh
5.00
6.60
265
A+
4.60
4.65
4.39
4.17
3.56
3.55
4.55
4.52
4.76
4.12
4.00
215
285
420
590
705
A
A
mm
Gas
OD
mm
Drain
OD
mm
6.35
9.5
12.7
18.0
Heat insulation
Current
4.20
A++
Heating
Liquid
1,460
2.8 (3)
SCOP
Piping connections
4,560
2.5 (3)
SEER
EER
Nominal efficiency
(cooling at 35º/27º
COP
nominal load, heating
Annual energy consumption
at 7º/20º nominal load)
Energy label
Cooling
17,100 (2)
3,610 (2)
4.0
kcal/h
Annual energy
consumption
14,300 (2)
3,010 (2)
13,600
Energy label
Pdesign
11,900 (2)
-
Btu/h
Heating (Average
climate)
8,500 (2)
3.2
kW
Annual energy
consumption
1
1.3
kW
Pdesign
5.00 (2)
10,900
kcal/h
Cooling
4.20 (2)
2.8
kW
Btu/h
Seasonal efficiency
(according to
EN14825)
3.50 (2)
9,600
kcal/h
Max.
1,460
3
2.5 (2)
-
kW
Btu/h
Nom.
FTXS50K/RXS50K
1.7
kcal/h
Min.
FTXS42K/RXS42K
1.4
Btu/h
Heating capacity
FTXS35K/RXS35K
1.3
kW
Max.
FTXS25K/RXS25K
Both liquid and gas pipes
Nominal running
Cooling
current (RLA) - 50Hz
A
2.4 (4) / 2.3 (5) /
2.2 (6)
3.2 (4) / 3.1 (5) /
3.0 (6)
4.3 (4) / 4.1 (5) /
3.9 (6)
6.0 (4) / 5.7 (5) /
5.5 (6)
6.6 (4) / 6.3 (5) /
6.0 (6)
Heating
A
2.8 (4) / 2.7 (5) /
2.6 (6)
3.3 (4) / 3.2 (5) /
3.1 (6)
4.3 (4) / 4.1 (5) /
3.9 (6)
6.6 (4) / 6.3 (5) /
6.0 (6)
6.8 (4) / 6.5 (5) /
6.2 (6)
Notes
(1) EER/COP according to Eurovent 2012
(2) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m
(3) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m
(4) 220V
(5) 230V
(6) 240V
• Split - Sky Air • Outdoor Unit
3
• Outdoor Unit • Pair application • RXS-K
2
Specifications
2-2 Nominal Capacity And Nominal Input
Cooling capacity
Min.
FVXS25F/RXS25K
kW
Btu/h
1
Nom.
2
Max.
Heating capacity
Max.
Seasonal efficiency
(according to
EN14825)
1.4
4,800
1,120
2.5 (2)
3.5 (2)
5.0 (2)
Btu/h
8,500 (2)
11,900 (2)
17,100 (2)
kcal/h
2,150 (2)
3,010 (2)
4,300 (2)
3.0
3.8
5.6
Btu/h
10,200
13,000
19,100
kcal/h
2,580
3,270
Btu/h
4,400
4,800
kcal/h
1,120
kW
3.4 (3)
4.5 (3)
5.8 (3)
Btu/h
11,600 (3)
15,400 (3)
19,800 (3)
kcal/h
2,920 (3)
3,870 (3)
4,990 (3)
4.5
5.0
8.1
Btu/h
15,400
17,100
27,600
kcal/h
3,870
4,300
6,970
2.50
3.50
5.00
Heating (Average
climate)
kW
4.71
4.93
5.53
186
248
317
kW
2.60
2.90
4.38
3.83
3.62
830
1,060
1,853
4.39
3.43
3.23
4.30
3.69
3.63
285
510
775
A+
SCOP
Annual energy
consumption
EER
Nominal efficiency
(cooling at 35º/27º
COP
nominal load, heating
Annual energy consumption
at 7º/20º nominal load)
Energy label
Cooling
A
kWh
Energy label
Pdesign
1,200
B
SEER
Annual energy
consumption
kWh
kWh
A
A
Liquid
OD
mm
Gas
OD
mm
Drain
OD
mm
6.35
9.5
12.7
20.0
Heat insulation
Current
Both liquid and gas pipes
Nominal running
Cooling
current (RLA) - 50Hz Heating
A
3.5 (4) / 3.3 (5) / 3.2 (6)
4.9 (4) / 4.7 (5) / 4.5 (6)
7.2 (4) / 6.8 (5) / 6.6 (6)
A
4.5 (4) / 4.3 (5) / 4.1 (6)
5.9 (4) / 5.6 (5) / 5.4 (6)
7.3 (4) / 7.0 (5) / 6.7 (6)
Notes
(1) EER/COP according to Eurovent 2012
(2) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m
(3) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
(4) 220V
(5) 230V
(6) 240V
4
4.80
A
Heating
Piping connections
4,820
1.4
Energy label
Pdesign
1,200
1.3
kW
Cooling
1.3
4,400
kW
kW
Nom.
FVXS50F/RXS50K
kcal/h
kW
Min.
FVXS35F/RXS35K
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
2
Specifications
2-3 Nominal Capacity And Nominal Input
Cooling capacity
Min.
kW
Nom.
Btu/h
4,100
3,070
kcal/h
1,030
3.5 (2)
4.9 (2)
1
Btu/h
8,500 (2)
11,900 (2)
16,730 (2)
kcal/h
2,150 (2)
3,010 (2)
4,210 (2)
2
3.0
3.8
5.3
Btu/h
10,200
13,000
18,090
kcal/h
2,580
3,270
4,560
1.2
1.4
Btu/h
Seasonal efficiency
(according to
EN14825)
Cooling
4.0 (3)
6.1 (3)
Btu/h
11,600 (3)
13,600 (3)
20,830 (3)
kcal/h
2,920 (3)
3,440 (3)
5,250 (3)
4.5
5.0
7.5
Btu/h
15,400
17,100
25,610
kcal/h
3,870
4,300
6,450
2.50
3.50
4.90
Energy label
C
kW
SEER
Heating (Average
climate)
4.46
4.49
5.09
196
273
337
kW
2.80
2.90
3.63
3.42
3.68
1,080
1,186
1,708
Energy label
Pdesign
Annual energy
consumption
EER
Nominal efficiency
(cooling at 35º/27º
COP
nominal load, heating
Annual energy consumption
at 7º/20º nominal load)
Energy label
Cooling
A
kWh
kWh
Heating
3.85
3.10
2.85
3.25
3.35
325
565
860
A
B
B
Liquid
OD
mm
Gas
OD
mm
Drain
OD
mm
4.50
3.47
C
C
6.35
9.5
12.7
18.0
Heat insulation
Current
B
kWh
SCOP
Piping connections
770
3.4 (3)
kW
Annual energy
consumption
3,070
1,030
kW
Pdesign
0.9
4,100
kcal/h
Max.
770
3
2.5 (2)
kW
Nom.
FLXS50B/RXS50K
0.9
kW
Min.
FLXS35B/RXS35K
1.2
kW
Max.
Heating capacity
FLXS25B/RXS25K
Both liquid and gas pipes
Nominal running
Cooling
current (RLA) - 50Hz Heating
A
3.7 (4) / 3.6 (5) / 3.4 (6)
5.3 (4) / 5.1 (5) / 4.9 (6)
8.0 (4) / 7.6 (5) / 7.3 (6)
A
4.7 (4) / 4.5 (5) / 4.3 (6)
5.8 (4) / 5.5 (5) / 5.3 (6)
8.4 (4) / 8.0 (5) / 7.7 (6)
Notes
(1) EER/COP according to Eurovent 2012
(2) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m
(3) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
(4) 220V
(5) 230V
(6) 240V
• Split - Sky Air • Outdoor Unit
5
• Outdoor Unit • Pair application • RXS-K
2
Specifications
2-4 Nominal Capacity And Nominal Input
Cooling capacity
Min.
FDXS25F/RXS25K
kW
Btu/h
1
Nom.
2
Max.
Heating capacity
Seasonal efficiency
(according to
EN14825)
1,200
1,460
3.4 (2)
5.0 (2)
Btu/h
8,150 (2)
11,600 (2)
17,100 (2)
kcal/h
2,060 (2)
2,920 (2)
4,300 (2)
3.0
3.8
5.3
Btu/h
10,200
13,000
18,100
kcal/h
2,580
3,260
4,560
1.3
1.4
1.7
4,400
4,800
5,800
kcal/h
1,110
1,200
1,460
kW
3.2 (3)
4.0 (3)
5.8 (3)
Btu/h
10,900 (3)
13,600 (3)
19,800 (3)
kcal/h
2,750 (3)
3,440 (3)
4,990 (3)
4.5
5.0
6.0
Btu/h
15,350
17,100
20,500
kcal/h
3,870
4,300
5,160
2.40
3.40
5.00
Energy label
Pdesign
B
kW
SEER
Annual energy
consumption
Heating (Average
climate)
5.08
4.82
5.12
165
247
342
kW
2.60
2.90
4.19
3.81
3.41
869
1,066
1,438
Energy label
Pdesign
Annual energy
consumption
EER
Nominal efficiency
(cooling at 35º/27º
COP
nominal load, heating
Annual energy consumption
at 7º/20º nominal load)
Energy label
Cooling
A+
kWh
kWh
3.72 (1)
3.21 (1)
3.03 (1)
3.39 (1)
3.10 (1)
530
825
C
D
323
A
Liquid
OD
mm
Gas
OD
mm
3.50
3.90 (1)
B
6.35
9.5
Heat insulation
12.7
Both liquid and gas pipes
Nominal running
Cooling
current (RLA) - 50Hz Heating
A
3.9
4.9
7.1
A
4.2
5.4
8.3
Notes
(1) EER/COP according to Eurovent 2012
(2) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB, 24ºCWB; equivalent piping length: 5m
(3) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m
6
A
A
Heating
Current
A
kWh
SCOP
Piping connections
1.7
5,800
1,110
kW
Cooling
1.4
4,800
2.4 (2)
Btu/h
Max.
1.3
4,400
kW
kW
Nom.
FDXS50F/RXS50K
kcal/h
kW
Min.
FDXS35F/RXS35K
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
2
Specifications
2-5 Nominal Capacity And Nominal Input
Cooling capacity
Nom.
Heating capacity
Nom.
Seasonal efficiency
(according to
EN14825)
Cooling
FHQ35C/RXS35K
FHQ50C/RXS50K
kW
3.4
5.0
kW
4.0
6.0
Energy label
Pdesign
kW
SEER
Annual energy
consumption
Heating (Average
climate)
B
A
3.40
5.00
1
2
4.89
5.48
kWh
243
320
kW
3.10
Energy label
Pdesign
A
SCOP
Annual energy
consumption
EER
Nominal efficiency
(cooling at 35º/27º
COP
nominal load, heating
Annual energy consumption
at 7º/20º nominal load)
Energy label
Cooling
3
kWh
kWh
Heating
4.35
3.98
3.74
1,090
1,627
3.58
3.18
3.96
3.35
475
785
A
B
A
C
Notes
(1) EER/COP according to Eurovent 2012
2-6 Nominal Capacity And Nominal Input
FFQ25C/RXS25K
FFQ35C/RXS35K
FFQ50C/RXS50K
Cooling capacity
Nom.
kW
2.50
3.40
5.00
Heating capacity
Nom.
kW
3.20
4.20
Seasonal efficiency
(according to
EN14825)
Cooling
Energy label
Pdesign
A
kW
2.50
3.40
5.00
5.25
5.60
5.70
kWh
167
212
307
kW
2.31
3.45
4.12
4.09
4.10
784
1,182
1,311
SEER
Annual energy
consumption
Heating (Average
climate)
Energy label
Pdesign
A+
SCOP
Annual energy
consumption
EER
Nominal efficiency
(cooling at 35º/27º
COP
nominal load, heating
Annual energy consumption
at 7º/20º nominal load)
Energy label
Cooling
5.80
A+
kWh
kWh
Heating
3.84
4.46
3.70
3.21
3.81
3.41
3.49
280
460
780
A
A
B
Notes
(1) EER/COP according to Eurovent 2012
• Split - Sky Air • Outdoor Unit
7
• Outdoor Unit • Pair application • RXS-K
2
Specifications
2-7 Nominal Capacity And Nominal Input
1
2
FBQ35C8/RXS35K
FBQ50C8/RXS50K
Cooling capacity
Nom.
kW
3.40
5.00
Heating capacity
Nom.
kW
4.00
5.50
Seasonal efficiency
(according to
EN14825)
Cooling
C
B
kW
3.50
4.90
Energy label
Pdesign
SEER
Annual energy
consumption
Heating (Average
climate)
4.33
4.96
kWh
283
346
kW
2.90
Energy label
Pdesign
A
SCOP
Annual energy
consumption
EER
Nominal efficiency
(cooling at 35º/27º
COP
nominal load, heating
Annual energy consumption
at 7º/20º nominal load)
Energy label
Cooling
kWh
kWh
4.50
3.56
3.53
1,141
1,782
3.21
3.03
3.51
3.42
530
825
A
Heating
B
B
Notes
(1) EER/COP according to Eurovent 2012
2-8 Nominal Capacity And Nominal Input
FCQG35F/RXS35K
Nom.
kW
3.40
5.00
Heating capacity
Nom.
kW
4.20
6.00
Seasonal efficiency
(according to
EN14825)
Cooling
A
A+
kW
3.50
5.00
Energy label
Pdesign
SEER
Annual energy
consumption
Heating (Average
climate)
5.34
5.89
kWh
230
297
A++
A+
kW
3.32
4.36
Energy label
Pdesign
SCOP
Annual energy
consumption
EER
Nominal efficiency
(cooling at 35º/27º
COP
nominal load, heating
Annual energy consumption
at 7º/20º nominal load)
Energy label
Cooling
kWh
kWh
4.74
4.24
981
1,442
3.58
3.55
3.41
3.70
475
705
A
Heating
Piping connections
B
Liquid
OD
mm
Gas
OD
mm
Notes
(1) EER/COP according to Eurovent 2012
8
FCQG50F/RXS50K
Cooling capacity
• Split - Sky Air • Outdoor Unit
A
6.35
9.5
12.7
• Outdoor Unit • Pair application • RXS-K
2
Specifications
2-9 Technical Specifications
Capacity control
Colour
Dimensions
Unit
Packed unit
Heat exchanger
RXS25K
Ivory white
mm
550
735
Width
mm
765
825
1
Depth
mm
285
300
Height
mm
612
797
2
Width
mm
906
992
Depth
mm
364
390
kg
34
39
kg
38
45
52
Length
mm
805
810
845
mm
1.4
1.5
1.8
Quantity
Quantity
24
Type
WF fin
Precoat Fin
1YC23AEXD
1YC23AEXDC
2YC36BXD#C
Hermetically sealed swing compressor
Output
W
Cooling High
Super
low
Heating High
Low
Super
low
Cooling High
Heating High
Super
low
Cooling
Heating
36.0
37.3
50.9
1,183
1,271
1,317
1,797
m³/min
33.5
36.0
37.3
50.9
cfm
1,183
1,271
1,317
1,797
m³/min
30.1
cfm
1,063
-
m³/min
-
30.1
30.6
48.9
cfm
-
1,063
1,080
1,727
m³/min
28.3
31.3
45.0
cfm
999
1,105
1,589
m³/min
25.6
cfm
904
-
m³/min
-
25.6
27.2
43.1
cfm
-
904
960
1,522
D23H-28
D50R-28
KFD-380-50-8D
23
50
53
890
780
rpm
860
920
rpm
780
790
670
rpm
860
890
720
rpm
740
780
670
Nom.
dBA
High
dBA
-
63
61
62
48
High
dBA
46
dBA
43
44
High
dBA
47
48
dBA
44
Cooling
Ambient
Heating
Ambient
Min.
45
ºCDB
-10
Max.
ºCDB
46
Min.
ºCWB
-15
Max.
ºCWB
18
Type
Charge
R-410A
kg
1.0
1.2
GWP
Refrigerant oil
1.3
1.7
1,975
Type
Charged volume
-
Silent operation
Silent operation
Refrigerant
33.5
cfm
W
Super
low
Operation range
m³/min
Model
Output
Cooling
1,100
Propeller fan
Low
Sound pressure level
600
Type
Nom.
Sound power level
ø8 Hi-XA
Waffle louvered fin
Type
Speed
32
ø7 Hi-XA
Model
Air flow rate
47
2
Tube type
Fin
3
Height
Unit
Stages
Fan motor
RXS50K
Inverter controlled
Fin pitch
Fan
RXS42K
Packed unit
Rows
Compressor
RXS35K
Method
Casing
Weight
RXS20K
FVC50K
l
• Split - Sky Air • Outdoor Unit
0.375
0.650
9
• Outdoor Unit • Pair application • RXS-K
2
Specifications
2-9 Technical Specifications
Piping connections
1
2
Liquid
RXS20K
OD
RXS25K
Gas
OD
mm
Drain
ID
mm
OD
mm
Piping length
OU - IU Max.
m
IU - OU Max.
12.7
18.0
20
30
10
m
15
20
Both liquid and gas pipes
2-10 Electrical Specifications
RXS20K
Name
RXS25K
RXS35K
-
RXS42K
RXS50K
V1
Phase
Current
RXS50K
9.5
Heat insulation
Power supply
RXS42K
6.35
System Chargel m
ess
Level difference
1~
Frequency
Hz
50
Voltage
V
220-240
Cooling
A
2.21 (1) / 2.12 (2) / 3.01 (1) / 2.92 (2) / 4.18 (1) / 3.98 (2) / 5.89 (1) / 5.59 (2) / 6.48 (1) / 6.18 (2) /
2.03 (3)
2.83 (3)
3.79 (3)
5.39 (3)
5.89 (3)
Heating
A
2.61 (1) / 2.52 (2) / 3.11 (1) / 3.02 (2) / 4.17 (1) / 3.97 (2) / 6.46 (1) / 6.16 (2) / 6.65 (1) / 6.36 (2) /
2.43 (3)
2.93 (3)
3.78 (3)
5.87 (3)
6.06 (3)
Nominal running
current (RLA)
Starting current
Cooling
A
2.8
3.3
4.3
6.6
6.8
Heating
A
2.8
3.3
4.3
6.6
6.8
Current - 50Hz
Maximum fuse amps (MFA)
A
Current - 60Hz
Maximum fuse amps (MFA)
A
Wiring connections
For power supply
Remark
Notes
(1) 220V
(2) 230V
(3) 240V
(4) SL: The silent fan level of the air flow rate setting
10
RXS35K
mm
• Split - Sky Air • Outdoor Unit
-
10
20
3 for power supply, 4 for interunit wiring (including earth wiring)
• Outdoor Unit • Pair application • RXS-K
3
Electrical data
3-1
Electrical Data
3
1
3
• Split - Sky Air • Outdoor Unit
11
• Outdoor Unit • Pair application • RXS-K
3
Electrical data
3-1
Electrical Data
1
3
12
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
3
Electrical data
3-1
Electrical Data
3
1
3
• Split - Sky Air • Outdoor Unit
13
• Outdoor Unit • Pair application • RXS-K
3
Electrical data
3-1
Electrical Data
1
3
14
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
3
Electrical data
3-1
Electrical Data
3
1
3
• Split - Sky Air • Outdoor Unit
15
• Outdoor Unit • Pair application • RXS-K
3
Electrical data
3-1
Electrical Data
1
3
16
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
3
Electrical data
3-1
Electrical Data
3
1
3
• Split - Sky Air • Outdoor Unit
17
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
18
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
19
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
20
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
21
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
22
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
23
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
24
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
25
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
26
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
27
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
28
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
29
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
30
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
31
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
32
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
33
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
34
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
35
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
36
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
37
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
38
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
3
1
4
• Split - Sky Air • Outdoor Unit
39
• Outdoor Unit • Pair application • RXS-K
4
Capacity tables
4-1
Cooling/Heating Capacity Tables
1
4
40
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
5
Dimensional drawings
5-1
Dimensional Drawings
3
1
5
• Split - Sky Air • Outdoor Unit
41
• Outdoor Unit • Pair application • RXS-K
6
Centre of gravity
6-1
Centre of Gravity
1
6
42
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
6
Centre of gravity
6-1
Centre of Gravity
3
1
6
• Split - Sky Air • Outdoor Unit
43
• Outdoor Unit • Pair application • RXS-K
7
Piping diagrams
7-1
Piping Diagrams
1
7
44
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
7
Piping diagrams
7-1
Piping Diagrams
3
1
7
• Split - Sky Air • Outdoor Unit
45
• Outdoor Unit • Pair application • RXS-K
8
Wiring diagrams
8-1
Wiring Diagrams - Single Phase
1
8
46
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
8
Wiring diagrams
8-1
Wiring Diagrams - Single Phase
3
1
8
• Split - Sky Air • Outdoor Unit
47
• Outdoor Unit • Pair application • RXS-K
9
Sound data
9-1
Sound Pressure Spectrum - Cooling
1
9
48
• Split - Sky Air • Outdoor Unit
• Outdoor Unit • Pair application • RXS-K
9
Sound data
9-2
Sound Pressure Spectrum - Heating
3
1
9
• Split - Sky Air • Outdoor Unit
49
• Outdoor Unit • Pair application • RXS-K
10
Operation range
10 - 1 Operation Range
1
10
50
• Split - Sky Air • Outdoor Unit
The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V.
has compiled the content of this leaflet to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products
and services presented therein. Specifications are subject to change
without prior notice. Daikin Europe N.V. explicitly rejects any liability for
any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.
BARCODE
Daikin products are distributed by:
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
EEDEN13-100 • 05/13 • Copyright Daikin