Parts List Tech Labels Wiring Diagrams Models Single Phase PHAD24N1K6 PHAD30N1K5 PHAD36N1K5 PHAD42N1K5 PHAD47N1K5 PHAD60N1K5 PYMC24G6 PYMC30G5 PYMC36G5 PYMC42G5 PYMC48G5 PYMC60G5 Single Package Heat Pumps Save This Manual For Future Reference 518 04 1003 00 2--14--02 Heating Capacity Balance Chart Balance Chart 2 Ton 12 SEER Package Heat Pump Balance Chart Performance based on 230V Operation 130 120 110 100 Capacity - Btuh X 1000 90 80 70 15 KW 60 50 10 KW 40 5 KW 30 20 Heat Pump 10 Tech Data 0 -10 -5 0 Style No: 2 Ton Pkg. H.P. Voltage 208-230 800 Phase/Cycles 1 -- 60 800 IDB 800 Ampacity 20.2 Wire Ga/Length NEC MBh Delay Fuse 25 S/T Max. Fuse/HACR 30 75 AMPS Compressor COPELAND HI PR RLA 12.1 LO PR LRA 54 MBh Cap MFD/V 35 / 370 S/T CC Heater N/A 80 AMPS Start Kit NAMA001SC HI PR Cond & Evap Cond Evap LO PR Type Fan Blower MBh Size 20 DD10-8A S/T 1/5 PSC 1/3 PSC 85 AMPS Motor-HP Type PSC PSC HI PR FLA 1 2.6 LO PR LRA 2.36 4 Heating RPM 1075 1100 IDB Cap MFD/V 5 / 370 7.5 / 370 MBh PTCR N/A T/R Hi Press N/A KW Low Press N/A 70 AMPS Low Amb N/A COP 20 - 50 EER Low Charge Sw Defrost Timed HI PR Sensor 31/71 LO PR Operating Chg Service Driers Liquid/Chg Suction Unit Weight (R-22 Oz) 120 8 Cu In / 7 oz 30 Sq In 394 75 59 22.5 0.85 7.2 158 64 22.9 0.93 7.2 160 65 23.3 0.97 7.3 161 65 63 23.2 0.76 7.3 170 68 23.4 0.87 7.4 172 69 23.7 0.94 7.5 174 69 67 25.1 0.57 7.6 180 74 25.0 0.71 7.6 181 75 24.9 0.85 7.7 183 76 71 26.9 0.37 7.8 187 79 26.7 0.53 7.9 189 80 26.5 0.69 8.0 191 81 59 22.0 0.87 7.8 180 67 22.3 0.95 7.8 182 67 22.7 1.00 7.9 183 68 65 31.6 36.6 2.36 12.9 3.92 13.4 258 80 60 29.8 34.5 2.31 11.9 3.77 12.9 247 74 55 27.8 32.2 2.27 11.1 3.58 12.2 238 69 50 26.0 30.1 2.23 10.5 3.41 11.7 227 63 47 24.8 28.7 2.20 10.1 3.30 11.3 222 60 5 10 15 17 20 25 30 35 40 45 47 50 55 60 65 Outdoor Temperature - F Outdoor Ambient Temperature - Degrees F. Dry Bulb 85 95 Entering Indoor Temperature - Degrees F. Wet Bulb 63 67 71 59 63 67 71 59 22.6 24.5 26.3 21.4 22.1 23.9 25.6 20.3 0.78 0.59 0.38 0.90 0.80 0.61 0.39 0.93 8.0 8.2 8.5 8.3 8.5 8.8 9.1 8.8 193 204 213 205 220 233 243 230 71 77 82 70 74 81 86 73 22.8 24.4 26.1 21.8 22.3 23.8 25.4 20.7 0.89 0.73 0.54 0.98 0.92 0.75 0.56 1.00 8.0 8.3 8.6 8.4 8.6 8.9 9.2 8.9 195 206 215 207 223 235 245 233 72 78 83 71 75 82 87 74 23.2 24.3 25.9 22.2 22.6 23.7 25.3 21.1 0.96 0.87 0.71 1.00 0.99 0.90 0.73 1.00 8.1 8.4 8.7 8.4 8.6 8.9 9.3 9.0 197 208 217 209 225 237 248 235 72 79 84 71 76 83 88 75 Outdoor Ambient Temperature - Degrees F. Dry Bulb 45 40 35 30 25 20 17 15 24.0 22.1 20.3 18.8 16.8 14.8 13.6 13.1 27.8 25.6 23.5 21.7 19.4 17.1 15.7 15.2 2.18 2.14 2.09 2.11 2.06 2.02 1.99 1.97 9.9 9.3 8.9 8.5 8.1 7.7 7.5 7.4 3.22 3.03 2.83 2.60 2.38 2.15 2.00 1.94 11.0 10.3 9.7 8.9 8.1 7.3 6.8 6.6 218 209 201 192 184 176 172 169 58 53 47 43 38 33 31 30 105 115 63 21.0 0.83 9.0 248 78 21.2 0.96 9.1 250 79 21.5 1.00 9.2 253 80 67 22.7 0.63 9.3 262 85 22.6 0.78 9.4 264 86 22.5 0.93 9.5 267 87 71 24.3 0.40 9.7 273 91 24.2 0.58 9.8 276 92 24.0 0.76 9.9 279 92 59 18.8 0.94 9.3 254 76 19.2 1.00 9.4 257 77 19.5 1.00 9.5 260 77 63 19.4 0.84 9.6 274 81 19.6 0.96 9.6 277 81 19.9 1.00 9.7 279 82 10 11.8 13.6 1.93 7.0 1.79 6.1 163 25 5 10.4 12.1 1.88 6.6 1.62 5.5 157 22 0 9.1 10.5 1.84 6.2 1.45 4.9 150 18 -5 7.8 9.0 1.79 5.7 1.27 4.3 145 16 -10 6.4 7.4 1.75 5.1 1.06 3.6 140 13 Air Delivery in CFM - Dry Coil ( Add .08 static W/Internal Filters - Substract 25 CFM for Wet Coil) 230 Volt Ext. Static Pressure (Inch Water Column) 208 Volt Ext. Static Pressure (Inch Water Column) Motor Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 Motor Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 HI 1314 1282 1243 1196 1142 1080 1010 HI 1178 1156 1127 1090 1049 988 919 MD HI 1077 1062 1041 1012 971 916 844 MD HI 927 919 904 883 849 797 735 MD LO 1020 1007 987 957 917 864 796 MD LO 870 864 853 832 799 757 692 LO 825 816 801 780 749 707 653 LO 696 689 677 660 632 591 542 2 67 21.0 0.63 9.9 289 88 20.9 0.78 10.0 292 89 20.8 0.94 10.1 295 90 Part No: 1110712 518 04 1003 00 71 22.5 0.41 10.2 302 94 22.4 0.59 10.3 305 95 22.2 0.76 10.4 308 96 Heating Capacity Balance Chart Balance Chart Performance based on 230V Operation 140 Balance Chart 2 1/2 Ton 12 SEER Package Heat Pump 130 120 110 100 Capacity - Btuh X 1000 90 80 70 15 KW 60 50 10 KW 40 5 KW 30 20 Heat Pump 10 0 -10 -5 0 Tech Data 2-1/2 Ton Pkg. H.P. Style No: Voltage 208-230 1000 Phase/Cycles 1 -- 60 1000 IDB 1000 Ampacity 23 Wire Ga/Length NEC MBh Delay Fuse 30 S/T Max. Fuse/HACR 35 75 AMPS Compressor COPELAND HI PR RLA 15.2 LO PR LRA 76 MBh Cap MFD/V 45 / 370 S/T CC Heater N/A 80 AMPS Start Kit NAMA001SC HI PR Cond & Evap Cond Evap LO PR Type Fan Blower MBh Size 20 DD10-8A S/T Motor-HP 1/3 PSC 1/3 PSC 85 AMPS Type PSC PSC HI PR FLA 1.4 2.6 LO PR LRA 3.7 4 Heating RPM 1075 1100 IDB Cap MFD/V 5 / 370 7.5 / 370 MBh PTCR N/A T/R Hi Press N/A KW Low Press N/A 70 AMPS Low Amb N/A COP 20 - 50 EER Low Charge Sw Defrost Timed HI PR Sensor 31 / 71 LO PR Operating Chg Service Driers Liquid/Chg Suction Unit Weight (R-22 Oz) 130 8 Cu In / 7 oz 30 Sq In 401 75 59 28.2 0.85 9.5 169 66 28.7 0.93 9.5 171 66 29.2 0.97 9.6 173 67 63 29.0 0.76 9.7 182 70 29.3 0.87 9.8 184 70 29.7 0.94 9.9 186 71 67 31.4 0.57 10.0 193 76 31.3 0.71 10.1 195 77 31.1 0.85 10.2 196 78 71 33.7 0.37 10.4 201 81 33.4 0.53 10.5 203 82 33.2 0.69 10.6 205 83 59 27.5 0.87 10.3 193 68 28.0 0.95 10.4 195 69 28.5 1.00 10.5 197 70 65 37.7 34.9 2.73 15.6 4.04 13.8 237 77 60 35.6 32.9 2.68 14.4 3.88 13.3 227 71 55 33.2 30.7 2.63 13.5 3.69 12.6 218 67 50 31.0 28.7 2.58 12.7 3.52 12.0 209 61 47 29.6 27.4 2.55 12.2 3.40 11.6 204 58 5 10 15 17 20 25 30 35 40 45 47 50 55 60 65 Outdoor Temperature - F Outdoor Ambient Temperature - Degrees F. Dry Bulb 85 95 Entering Indoor Temperature - Degrees F. Wet Bulb 63 67 71 59 63 67 71 59 28.3 30.6 32.9 26.8 27.6 29.9 32.1 25.5 0.78 0.59 0.38 0.90 0.80 0.61 0.39 0.93 10.5 10.9 11.3 11.0 11.3 11.6 12.1 11.7 207 219 228 220 236 249 260 247 73 79 84 72 76 83 89 75 28.6 30.5 32.7 27.3 27.9 29.8 31.9 25.9 0.89 0.73 0.54 0.98 0.92 0.75 0.56 1.00 10.6 11.0 11.4 11.1 11.4 11.8 12.2 11.8 210 221 231 222 239 252 263 249 73 80 85 72 77 84 89 76 29.0 30.4 32.4 27.8 28.3 29.7 31.6 26.4 0.96 0.87 0.71 1.00 0.99 0.90 0.73 1.00 10.7 11.1 11.5 11.2 11.5 11.9 12.3 11.9 212 223 233 224 241 255 265 252 74 81 86 73 78 85 90 77 Outdoor Ambient Temperature - Degrees F. Dry Bulb 45 40 35 30 25 20 17 15 28.7 26.4 24.2 21.8 19.5 17.2 15.8 15.2 26.6 24.4 22.4 20.2 18.1 15.9 14.6 14.1 2.53 2.48 2.43 2.45 2.40 2.35 2.32 2.29 12.0 11.3 10.7 10.2 9.7 9.3 9.0 8.9 3.32 3.12 2.92 2.60 2.38 2.14 2.00 1.94 11.3 10.7 10.0 8.9 8.1 7.3 6.8 6.6 200 192 185 177 169 162 158 155 56 51 46 41 37 32 30 29 105 115 63 26.2 0.83 12.0 266 80 26.5 0.96 12.1 268 81 26.9 1.00 12.2 271 81 67 28.4 0.63 12.4 281 87 28.3 0.78 12.5 284 88 28.2 0.93 12.6 286 89 71 30.5 0.40 12.9 293 93 30.3 0.58 13.0 296 94 30.1 0.76 13.1 299 95 59 23.6 0.94 12.4 273 78 24.0 1.00 12.5 276 78 24.4 1.00 12.6 278 79 63 24.3 0.84 12.7 294 83 24.5 0.96 12.8 297 83 24.9 1.00 13.0 300 84 10 13.7 12.6 2.24 8.5 1.78 6.1 150 25 5 12.1 11.2 2.19 7.9 1.62 5.5 144 21 0 10.6 9.8 2.14 7.4 1.45 4.9 138 18 -5 9.0 8.3 2.08 6.8 1.27 4.3 133 16 -10 7.4 6.8 2.03 6.1 1.06 3.6 128 12 Air Delivery in CFM - Dry Coil ( Add .08 static W/Internal Filters - Substract 25 CFM for Wet Coil) 230 Volt Ext. Static Pressure (Inch Water Column) 208 Volt Ext. Static Pressure (Inch Water Column) Motot Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 Motot Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 HI 1314 1282 1243 1196 1142 1080 1010 HI 1178 1156 1127 1090 1049 988 919 MD HI 1077 1062 1041 1012 971 916 844 MD HI 927 919 904 883 849 797 735 MD LO 1020 1007 987 957 917 864 796 MD LO 870 864 853 832 799 757 692 LO *** *** *** *** *** *** *** LO *** *** *** *** *** *** *** 3 67 26.3 0.63 13.1 310 90 26.2 0.78 13.3 313 91 26.1 0.94 13.4 316 92 *** Do Not Operate on Low Speed Part No: 1113281 518 04 1003 00 71 28.2 0.41 13.6 323 96 28.0 0.59 13.8 327 97 27.8 0.76 13.9 330 98 Heating Capacity Balance Chart Balance Chart Performance based on 230V Operation Balance Chart 3 Ton 12 SEER Package Heat Pump 150 140 130 120 110 Capacity - Btuh X 1000 100 90 20 KW 80 70 15 KW 60 10 KW 50 40 5 KW 30 Heat Pump 20 10 0 -10 -5 0 Tech Data Style No: 3 Ton Pkg. H.P. Voltage 208-230 1200 Phase/Cycles 1 -- 60 1200 IDB 1200 Ampacity 27.4 Wire Ga/Length NEC MBh Delay Fuse 35 S/T Max. Fuse/HACR 45 75 AMPS Compressor COPELAND HI PR RLA 17.9 LO PR LRA 90.5 MBh Cap MFD/V 50 / 370 S/T CC Heater N/A 80 AMPS Start Kit NAMA001SC HI PR Cond & Evap Cond Evap LO PR Type Fan Blower MBh Size 20 DD11-9A S/T Motor-HP 1/3 PSC 1/2 PSC 85 AMPS Type PSC PSC HI PR FLA 1.4 3.6 LO PR LRA 3.7 7.8 Heating RPM 1075 1125 IDB Cap MFD/V 5 / 370 15 / 370 MBh PTCR N/A T/R Hi Press N/A KW Low Press N/A 70 AMPS Low Amb N/A COP 20 - 50 EER Low Charge Sw Defrost Timed HI PR Sensor 31 / 71 LO PR Operating Chg Each Circuit Service Driers Liquid/Chg Suction Unit Weight 75 59 33.3 0.86 11.1 172 65 33.9 0.94 11.2 173 65 34.4 0.99 11.3 175 66 63 34.2 0.77 11.4 185 69 34.6 0.88 11.5 186 70 35.1 0.95 11.6 188 70 67 37.1 0.58 11.7 195 75 37.0 0.72 11.8 197 76 36.8 0.86 12.0 199 77 71 39.8 0.37 12.2 203 80 39.5 0.54 12.3 205 81 39.2 0.70 12.4 207 82 59 32.5 0.88 12.1 195 67 33.0 0.96 12.2 197 68 33.6 1.00 12.3 199 69 65 47.1 36.4 3.40 19.0 4.06 13.9 252 76 60 44.5 34.3 3.34 17.6 3.90 13.3 242 70 55 41.5 32.0 3.28 16.4 3.70 12.6 232 66 50 38.7 29.9 3.22 15.5 3.52 12.0 222 60 47 37.0 28.5 3.19 14.9 3.40 11.6 217 57 5 10 15 17 20 25 30 35 40 45 47 50 55 60 65 Outdoor Temperature - F Outdoor Ambient Temperature - Degrees F. Dry Bulb 85 95 Entering Indoor Temperature - Degrees F. Wet Bulb 63 67 71 59 63 67 71 59 33.4 36.2 38.8 31.7 32.6 35.3 37.9 30.1 0.79 0.60 0.38 0.91 0.81 0.61 0.40 0.94 12.3 12.7 13.2 12.9 13.2 13.6 14.1 13.7 210 222 231 222 239 252 263 250 72 78 83 71 75 82 88 74 33.8 36.1 38.6 32.2 32.9 35.2 37.6 30.6 0.90 0.74 0.55 1.00 0.93 0.76 0.57 1.00 12.5 12.9 13.3 13.0 13.3 13.7 14.2 13.8 212 224 234 224 241 255 266 252 72 79 84 71 76 83 88 75 34.3 35.9 38.3 32.8 33.4 35.0 37.4 31.2 0.98 0.88 0.71 1.00 1.00 0.91 0.74 1.00 12.6 13.0 13.5 13.1 13.4 13.9 14.4 13.9 214 226 236 227 244 258 269 255 73 80 85 72 77 84 89 76 Outdoor Ambient Temperature - Degrees F. Dry Bulb 45 40 35 30 25 20 17 15 35.9 33.0 30.3 27.6 24.7 21.8 20.0 19.3 27.7 25.5 23.4 21.3 19.0 16.8 15.4 14.9 3.16 3.10 3.04 3.09 3.02 2.96 2.93 2.90 14.6 13.8 13.1 12.5 12.0 11.4 11.1 11.0 3.32 3.11 2.91 2.61 2.39 2.15 2.00 1.94 11.3 10.6 10.0 8.9 8.2 7.3 6.8 6.6 213 205 196 188 180 173 168 165 55 50 45 41 36 32 30 29 105 115 63 31.0 0.84 14.0 269 79 31.3 0.97 14.1 272 80 31.8 1.00 14.3 274 80 67 33.5 0.64 14.5 284 86 33.4 0.79 14.6 287 87 33.3 0.94 14.7 290 88 71 36.0 0.41 15.0 296 92 35.7 0.59 15.1 299 93 35.5 0.77 15.3 302 94 59 27.9 0.95 14.5 276 77 28.4 1.00 14.6 279 77 28.9 1.00 14.7 282 78 63 28.7 0.85 14.8 297 82 29.0 0.98 15.0 300 82 29.4 1.00 15.1 303 83 10 17.3 13.3 2.84 10.4 1.78 6.1 159 24 5 15.3 11.8 2.77 9.7 1.62 5.5 153 21 0 13.4 10.3 2.71 9.1 1.44 4.9 147 18 -5 11.4 8.8 2.65 8.4 1.26 4.3 141 15 -10 9.3 7.2 2.59 7.6 1.06 3.6 136 12 67 31.1 0.64 15.3 314 89 31.0 0.80 15.5 317 90 30.8 0.95 15.6 320 91 (R-22 Oz) 135 Air Delivery in CFM - Dry Coil ( Add .08 static W/Internal Filters - Substract 25 CFM for Wet Coil) 230 Volt Ext. Static Pressure (Inch Water Column) 208 Volt Ext. Static Pressure (Inch Water Column) Motot Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 Motot Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70 16 Cu In / 11 oz HI 1602 1547 1489 1428 1363 1291 1211 HI 1541 1490 1435 1380 1315 1237 1159 30 Sq In MD HI 1518 1468 1416 1358 1295 1226 1148 MD HI 1424 1380 1333 1287 1230 1155 1078 410 MD LO 1459 1413 1364 1311 1252 1185 1109 MD LO 1347 1308 1264 1220 1165 1094 1020 LO 1339 1299 1255 1204 1147 1084 1015 LO 1192 1163 1130 1095 1050 987 916 4 Part No: 1113282 518 04 1002 02 71 33.3 0.41 15.9 327 95 33.1 0.59 16.0 331 96 32.9 0.77 16.2 334 97 Heating Capacity Balance Chart Balance Chart Performance based on 230V Operation 170 160 150 140 130 30 KW Capacity - Btuh X 1000 120 25 KW 110 100 20 KW 90 15 KW 80 70 10 KW 60 50 5 KW 40 Heat Pump 30 20 10 0 -10 -5 0 5 10 15 17 20 25 30 35 40 45 47 50 55 60 65 Outdoor Temperature - F 2 THRU 3 1/2 TON MODELS LADDER WIRING DIAGRAM CONNECTION WIRING DIAGRAM DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING BK BK BR OUTDOOR FAN MTR R F S T2 BL CAP H C C T1 COMP R T3 COIL L2 T2 GND 208 / 230 VAC, 60 HZ, 1 PH L1 L1 T1 R R BK BK BK 208 / 230 VAC 60HZ, 1PH USE COPPER CONDUCTORS ONLY L2 (OPTIONAL) CRANKCASE HEATER CONTACTOR COMP C R T1 T3 S T2 CONTACTOR L1 T1 BL Y L2 T2 CAPACITOR H C FAN Y-RV BL F Y S DFC RV DFC DEFROST CONTROL PS1 DF R-RV R C O Y W RVS O Y GY Y Y BK BK PRI 208 / 230 TRANS DFS 24 V SEC BL Y R O W R RV CC ECONOMIZER RELAY DFC CC DEFROST PS2 CONTROL Y 3 LOC R W2 BR CAP BR LO MED LO MED HI HI COM COIL 3 4 1 MIXED AIR SENSOR W Y* OBL R C R O Y1 1 BLACK BLUE BROWN GRAY LVTB G IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE AWM-105°C OR ITS EQUIVALENT. * SEE INSTALLATION INSTRUCTIONS FOR PROPER HEATING AND COOLING CONNECTIONS FOR YOUR UNIT COLOR CODE: DF 2 TDR BK Y COIL W Y O C R R-RV RVS 5 *IFM LINE VOLTAGE FACTORY LINE VOLTAGE FIELD LOW VOLTAGE FACTORY LOW VOLTAGE FIELD DFS 7 R ECONOMIZER PLUG 1 8 * ECONOMIZER (OPTIONAL) 2 PS1 ELECTRIC HEAT PACKAGE (WHEN USED) * 9 W FAN 6 5 W1 Y-RV WHEN USING AN ECONOMIZER, DISCONNECT (Y) AT DEFROST BOARD & CONNECT TO ECONOMIZER RELAY 1 , CONNECT WIRE FROM 2 RELAY TO (Y) DEFROST BOARD. SEE ECONOMIZER INSTALLATION INSTRUCTIONS. 1 W 24V COM 2 Y2 TRANS 4 3 O Y1 BL G R O Y R OFM LO MED LO 4 2 * MED HI C IFMC HEATER PKG HI *IFM WHEN USED 5 CAP 208V TAP 230V BL BL R BL G R * C BK LOC LVTB G R Y BL CC PS2 O C FAN BK BL BR GY GREEN ORANGE RED VIOLET COIL 3 Y2 W1 IFMC G O R V WHITE YELLOW TRANS.....TRANSFORMER COMPR....COMPRESSOR CAP..........CAPACITOR FT.............FREEZE THERMOSTAT CONT.......CONTACTOR JPR..........JUMPER WIRE FCC..........FAN CONTACTOR COIL W Y W W2 LEGEND GND.......GROUND DFS........DEFROST SENSOR DFC........DEFROST CONTROL ER..........ECONOMIZER RELAY HPS........HIGH PRESSURE SWITCH TDR........TIME DELAY RELAY LVTB.......LOW VOLT TERM BOARD IFMC........INDOOR FAN MOTOR CONTROL IFM...........INDOOR FAN MOTOR RVS..........REVERSING VALVE SOLENOID OFM.........OUTDOOR FAN MOTOR LOC..........LOSS OF CHARGE PRESSURE SWITCH CC............COMPRESSOR CONTACTOR COIL 1114116 8 518 04 1002 02 OUTDOOR FAN MTR F CAP C Y-RV H CONNECTION WIRING DIAGRAM BL Y BL S T2 GY Y R BK R R C T1 COMP R T3 LOC BK Y T1 T2 BK L1 L2 BL COIL BK BK 208 / 230 VAC 60HZ, 1PH USE COPPER CONDUCTORS ONLY R Y W Y L1 L1 T1 LADDER WIRING DIAGRAM R F H C * * L2 L2 CONTACTOR T2 CAP LO MED LO C MED HI HI *IFM CAPACITOR (OPTIONAL) CRANKCASE HEATER S T2 4 OFM S COMP R C T1 T3 C IFMC 24V TRANS 230V HEATER PKG WHEN USED * Y 1 COIL 2 3 1 ECONOMIZER (OPTIONAL) ECONOMIZER PLUG 7 MIXED AIR SENSOR 8 G C LVTB O R Y2 Y1 W ECONOMIZER RELAY WHEN USING AN ECONOMIZER, DISCONNECT (Y) AT DEFROST BOARD & CONNECT TO ECONOMIZER RELAY 1 , CONNECT WIRE FROM 2 RELAY TO (Y) DEFROST BOARD. SEE ECONOMIZER INSTALLATION INSTRUCTIONS. 208V TAP FAN R-RV DEFROST CONTROL DFC COM Y-RV RV CC PS2 DF PS1 W Y O C R W Y* OBL R 5 2 GND 208 / 230 VAC, 60 HZ, 1 PH DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING DFC FAN CC DFS 3 W2 W1 1114026-A LVTB.......LOW VOLT TERM BOARD IFMC........INDOOR FAN MOTOR CONTROL IFM...........INDOOR FAN MOTOR RVS..........REVERSING VALVE SOLENOID OFM.........OUTDOOR FAN MOTOR LOC..........LOSS OF CHARGE PRESSURE SWITCH CC............COMPRESSOR CONTACTOR COIL 2 COIL RVS LOC CONTACTOR 1 IFMC LEGEND GND.......GROUND DFS........DEFROST SENSOR DFC........DEFROST CONTROL ER..........ECONOMIZER RELAY HPS........HIGH PRESSURE SWITCH TDR........TIME DELAY RELAY 9 2 WHITE YELLOW TRANS.....TRANSFORMER COMPR....COMPRESSOR CAP..........CAPACITOR FT.............FREEZE THERMOSTAT CONT.......CONTACTOR JPR..........JUMPER WIRE FCC..........FAN CONTACTOR COIL 6 5 5 G O R V TDR GREEN ORANGE RED VIOLET 1 24 V SEC PRI 208 / 230 TRANS BL COIL 4 3 BL Y BL R BL G R BK BL BR GY 4 3 LO MED LO MED HI HI COM R ELECTRIC HEAT PACKAGE (WHEN USED) DFS BK BK Y Y DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING R BR BK FAN RV CC PS2 PS1 BL Y O W DF R C O Y W DFC DEFROST CONTROL R-RV O R BL G R O Y W BR BR *IFM COLOR CODE: BLACK BLUE BROWN GRAY 518 04 1003 00 9 BK O W2 W1 Y2 Y1 O R G C LVTB RVS W CAP LINE VOLTAGE FACTORY LINE VOLTAGE FIELD LOW VOLTAGE FACTORY LOW VOLTAGE FIELD IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE AWM-105°C OR ITS EQUIVALENT. * SEE INSTALLATION INSTRUCTIONS FOR PROPER HEATING AND COOLING CONNECTIONS FOR YOUR UNIT * 4 TON MODEL OUTDOOR FAN MTR R CAP Y-RV RV CC CONNECTION WIRING DIAGRAM CAP BL Y Y BL Y S T2 GY Y BK BK DFS R BK R C T1 COMP R T3 R LOC BK Y T1 T2 BK L1 L2 BL COIL BK W Y BK 208 / 230 VAC 60HZ, 1PH USE COPPER CONDUCTORS ONLY R Y WHITE YELLOW L1 L1 T1 LADDER WIRING DIAGRAM R * * T2 2 3 W ECONOMIZER RELAY 1 COIL ECONOMIZER (OPTIONAL) ECONOMIZER PLUG 7 MIXED AIR SENSOR 8 G C LVTB O R Y1 Y2 W1 W2 1114027-A LVTB.......LOW VOLT TERM BOARD IFMC........INDOOR FAN MOTOR CONTROL IFM...........INDOOR FAN MOTOR RVS..........REVERSING VALVE SOLENOID OFM.........OUTDOOR FAN MOTOR LOC..........LOSS OF CHARGE PRESSURE SWITCH CC............COMPRESSOR CONTACTOR COIL L2 L2 CONTACTOR CAP LO MED LO C MED HI HI *IFM CAPACITOR CAPACITOR (OPTIONAL) CRANKCASE HEATER S T2 4 OFM S COMP C R T1 T3 C IFMC 24V TRANS 230V HEATER PKG WHEN USED * Y WHEN USING AN ECONOMIZER, DISCONNECT (Y) AT DEFROST BOARD & CONNECT TO ECONOMIZER RELAY 1 , CONNECT WIRE FROM 2 RELAY TO (Y) DEFROST BOARD. SEE ECONOMIZER INSTALLATION INSTRUCTIONS. 208V TAP FAN R-RV DEFROST CONTROL DFC COM Y-RV RV CC PS2 DF PS1 W Y* OBL R W Y O C R 5 2 GND 208 / 230 VAC, 60 HZ, 1 PH DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING DFC FAN CC DFS 3 LEGEND GND.......GROUND DFS........DEFROST SENSOR DFC........DEFROST CONTROL ER..........ECONOMIZER RELAY HPS........HIGH PRESSURE SWITCH TDR........TIME DELAY RELAY 9 COIL RVS LOC CONTACTOR 1 IFMC TRANS.....TRANSFORMER COMPR....COMPRESSOR CAP..........CAPACITOR FT.............FREEZE THERMOSTAT CONT.......CONTACTOR JPR..........JUMPER WIRE FCC..........FAN CONTACTOR COIL 6 5 G O R V 2 1 24 V SEC PRI 208 / 230 TRANS BL COIL BL Y BL R BL G R 4 3 5 TDR GREEN ORANGE RED VIOLET 2 1 BK BL BR GY 4 3 LO MED LO MED HI HI COM R ELECTRIC HEAT PACKAGE (WHEN USED) R DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING BR BK FAN DFC DEFROST CONTROL PS2 PS1 BL Y O W DF R C O Y W R BL G R O Y W BR BR *IFM COLOR CODE: BLACK BLUE BROWN GRAY 518 04 1002 02 10 BK O O R-RV W2 W1 Y2 Y1 O R G C LVTB RVS W CAP LINE VOLTAGE FACTORY LINE VOLTAGE FIELD LOW VOLTAGE FACTORY LOW VOLTAGE FIELD IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE AWM-105°C OR ITS EQUIVALENT. * SEE INSTALLATION INSTRUCTIONS FOR PROPER HEATING AND COOLING CONNECTIONS FOR YOUR UNIT * 5 TON MODEL Coil, Condenser Capacitor, 7.5Mfd.,370 Volt 15Mfd.,370 Volt 20Mfd.,440 Volt Mount, Blower Motor Kit Motor, Blower 230 Volt, 1/3 HP 230 Volt, 1/2 HP 230 Volt, 1/2 HP 230 Volt, 1 HP Wheel, Blower 10-8DD 1/2" Bore 11-9DD 5/8" Bore 11-11DD 5/8" Bore Coil, Evaporator Transformer, 230 Volt, 40 VA Sequencer, SPDT Lug, Ground Board, Terminal Control, Defrost Contactor, 25 Amp 35 Amp 40 Amp 11 PHAD60N1K5 PYMC60G5 1 * * * * * 1 * * * 1 * * * 1 * * * * 1 * * 1 * 1 * * * 1 * * 1 * * * * 1 1 1 1 1 1 * * PHAD47N1K5 PYMC48G5 ZR22K4PFV130 ZR28K3PFV130 ZR34K3PFV130 ZR40K3PFV130 ZR46K3PFV130 ZR57K3PFV130 1086598 1065926 1098505 1098501 1099654 1099656 1080795 1080792 1066050 1066560 1066598 1066847 1067435 1094239 1094959 1094968 1004905 1002804 1066420 1066421 1054583 1065129 600587 1065361 1054593 1066069 1066070 1067472 1067471 1067473 1082611 1054372 91590 1066159 1087562 1050699 1050839 1053980 PHAD42N1K5 PYMC42G5 Compressor With Plug Connections Compressor With Plug Connections Compressor With Plug Connections Compressor With Plug Connections Compressor With Plug Connections Compressor With Plug Connections Motor, Condenser Fan 230 Volt, 1/5 HP 230 Volt, 1/3 HP 230 Volt, 1/3 HP 230 Volt, 3/4 HP Fan, Condenser PHAD36N1K5 PYMC36G5 PART NUMBER PHAD30N1K5 PYMC30G5 1 1 1 1 1 1 2 2 2 2 3 3 3 3 5 5 5 5 5 6 6 6 7 7 8 8 8 8 9 9 9 11 11 11 11 11 15 16 19 20 22 24 24 24 DESCRIPTION PHAD24N1K6 PYMC24G6 KEY NO. 1 * * * * 1 * * * 1 * * 1 * 1 1 * * 1 * * 1 * 1 * 1 1 * * 1 * * 1 * 1 * 1 1 * * * 1 * * 1 * 1 * * * 1 * * 1 * * * 1 * * 1 1 * 1 1 1 1 1 1 * 1 1 1 1 * * 1 1 1 * * * 1 1 1 1 1 1 * * 1 * * * 1 1 1 1 1 1 * * 1 * * 1 1 1 1 1 1 * 1 1 1 1 1 1 1 1 1 1 1 1 * 1 1 1 * * 1 1 1 * * 518 04 1003 00 Grommet, Compressor Mounting Switch, Low Pressure Tube, Strainer Valve, Expansion (Evaporator) Sensor, Defrost Valve, Check Capacitor, 35 + 3 Mfd., 370 Volt 45 + 5 Mfd., 370 Volt 50 + 5 Mfd., 370 Volt 55 + 7.5 Mfd., 370 Volt 60 + 7.5 Mfd., 370 Volt 80 Mfd., 370 Volt, Compressor Only Accumulator, Suction Line Port Asy,Valve 1 * * * * 1 * * 1 * * * 1 * * 1 * * * * * * 1 * 1 * * * * * 1 * 1 * * 1 * 1 1 1 1 1 1 1 * * * * 1 * 1 1 * * 1 * * * 1 * 1 1 * * 1 * * 1 * 1 1 * * 1083858 1059730 1065871 1066006 1066007 1066484 1067420 1066347 1066804 1069172 1083811 1083935 1113806 Manifold, Included with Condenser Coil Drier, Filter Muffler Manifold Asy, Evap. Included with Evap Coil Valve, Expansion (Condenser) Tube, Strainer Tube, Drain Plug, Compressor Harness 12 PHAD42N1K5 PYMC42G5 1 * * 1 * 4 1 1 * 1 * * * 1 * 4 1 1 * 1 * * * * * 1 * * 1 * * * * * * * 1 * PHAD60N1K5 PYMC60G5 Coil, Reversing Valve 24V 1 * * 1 * 4 1 1 * 34329020 34329000 1097787 34329030 34329055 1063443 1052060 1085492 1066347 1066804 1066042 1066043 1066044 1066008 1066490 1066819 1066430 1066934 1066803 1082632 1084424 1094993 1084310 1149997 1149998 1053431 1053432 1083939 1083619 PHAD47N1K5 PYMC48G5 Valve, Reversing PHAD36N1K5 PYMC36G5 PART NUMBER PHAD30N1K5 PYMC30G5 25 25 25 25 26 26 27 28 30 30 31 31 31 31 31 31 32 32 35 36 36 36 36 36 36 39 39 41 41 43 45 46 48 49 49 49 49 49 50 50 51 52 52 52 DESCRIPTION PHAD24N1K6 PYMC24G6 KEY NO. 1 1 1 1 1 4 1 4 1 4 1 1 1 1 1 * * 1 * 1 1 1 1 1 1 1 1 * 1 1 1 1 1 1 1 1 1 1 1 1 1 * 1 * 1 1 1 1 1 * 1 * 1 1 * 518 04 1002 02 Panel, Top Partition, Heat/Cool Orifice, Condenser Fan Bracket, Supply Air Housing, Blower Cover, Evaporator Top Deck, Blower Cover, Evaporator Bottom Panel, Blower Access Baffle, Evaporator Blower Plate, Block Off Panel, Divison Grille, Inlet Side (Front) Grille, Inlet Side (Rear) Grille, Inlet End Post, Electrical Corner Nut, Cap Bracket, Low Voltage Terminal Board Mo Baffle, Air Plate, Conduit Plate, Control Mounting Panel, Electrical Access 13 1 * 2 * 1 * 1 1 * 1 * 1 * * 1 1 * 1 1 * 1 * 1 1 * 1 * * 1 * 1 * 4 1 * * 1 1 1 * 1 * 2 * 1 * 1 1 * 1 * 1 * 1 1 * 1 1 * 1 * 1 1 * 1 * * 1 * 1 * 4 1 1 * 1 1 1 * PHAD60N1K5 PYMC60G5 Cover, Duct 1 * 2 * 1 * 1 1 * 1 * 1 * * 1 1 * 1 1 * 1 * 1 1 * 1 * * 1 * 1 * 4 1 * * 1 1 1 * PHAD47N1K5 PYMC48G5 1084490 1064542 1068159 1068158 1068191 1068157 1066331 1065724 1065725 1054524 1054525 1099402 1099239 1099238 1066332 1065949 1065948 1066333 1068180 1068181 1066409 1054522 1066107 1065942 1065943 1082186 1082279 1082280 1082053 1082281 1068192 1068193 1067902 1066106 1066621 1066364 1068179 1066168 1068185 1068186 PHAD42N1K5 PYMC42G5 Grille, Condenser Fan PHAD36N1K5 PYMC36G5 PART NUMBER PHAD30N1K5 PYMC30G5 A A AA AA B B BB C C CC CC D D D DD E E EE F F FF FF G H H HA HA HB HH HH J J JJ K KK KK L LL M M DESCRIPTION PHAD24N1K5 PYMC24G5 KEY NO. 1 1 1 2 2 2 1 1 1 1 1 1 1 1 1 1 * 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 4 1 1 4 1 * 1 1 1 1 1 1 1 1 1 1 1 518 04 1003 00 Post, Return Air Partition, Return Air Clamp, Capacitor Post, Center Pan, Drain Panel, Cutoff Bracket, Evaporator Panel, Supply Air Capacitor, Cond. Fan Mtr. 10 Mfd 440 Vo Coupling Male Pan, Drip Plate, Drip Manual, Parts List Manual, Users Manual, Installation 14 PHAD60N1K5 PYMC60G5 Panel, Filter Access Panel, Return Air PHAD47N1K5 PYMC48G5 Panel, Drain Outlet Rail, Base PHAD42N1K5 PYMC42G5 Support, Filter Top Plate, Pressure Port Panel, Coil Support Panel, Heating Area Baffle, Coil Post, Return Air Corner 1065618 1068182 1068164 1054502 1068189 1098509 1098508 1082435 1068167 1068168 1068162 1113559 1065001 1065001 1084078 1065001 1054464 1113559 1068175 1068166 1068160 1068172 1065033 1054471 1095020 1068163 1065795 1113589 95143 1066448 1065073 1099106 1098999 1068165 1068161 1094965 1054625 1096604 1113541 51804100200 42802110100 51801100100 PHAD36N1K5 PYMC36G5 Bracket, Filter Top Panel, Pressure Port PART NUMBER PHAD30N1K5 PYMC30G5 MM N N NN O OO PP QQ R R RR S S S1 S1 S2 S2 S3 SS U U UU V V W VV X X XX XX XX Y Y Z Z )( )( )( )( )( )( )( DESCRIPTION PHAD24N1K5 PYMC24G5 KEY NO. * 1 * * 1 * * * 2 * * 1 * 1 * 1 * 1 * 1 * * 1 * 1 * 1 * 1 * * 1 * 1 * * * * * 1 1 1 * 1 * * 1 * * * 2 * * 1 * 1 * 1 * 1 * 1 * * 1 * 1 * 1 * 1 * * 1 * 1 * * * * * 1 1 1 * 1 * * 1 * * * 2 * * 1 * 1 * 1 * 1 * 1 * * 1 * 1 * 1 * 1 1 1 1 * 1 * 1 * * * * * 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 * 1 1 1 1 1 1 * 1 1 1 1 1 1 1 * 1 1 1 1 1 1 1 1 1 1 1 1 1 1 518 04 1002 02 Functional Parts -- 2 to 3 Ton This illustration is for reference only, your unit may differ from the illustration. 2 11 3 5 30 32 28 49 50 45 29 26 52 25 47 01 46 52 27 51 41 15 518 04 1003 00 31 Functional Parts -- 3--1/2 to 5 Ton This illustration is for reference only, your unit may differ from the illustration. 52 16 518 04 1002 02 Control Panel -- All Models This illustration is for reference only, your unit may differ from the illustration. 80--50--40 BLOWER ASSEMBLY All Models WW kk 17 518 04 1003 00 Non--Functional Parts -- 2 to 3 Ton This illustration is for reference only, your unit may differ from the illustration. LL S3 S2 S1 HH HA 18 518 04 1002 02 Non--Functional Parts -- 3--1/2 to 5 Ton This illustration is for reference only, your unit may differ from the illustration. HB S3 S HH HA 19 518 04 1003 00