Datasheet SPD II and SPD III AC Surge Protector NEW The SPD II range of surge protectors are used for transient surge protection of single and multi-phase power circuits at the main electrical panel. SPD IIIs are for the protection of individual electrical devices. They provide common-mode protection (between each Line and Ground), with impulse discharge capacity (Imax) 40kA for SPD II and 20kA for SPD III. The SPD design is based on high-energy varistors (MOVs) equipped with thermal disconnects and integral failure indicators. A remote signaling contact for disconnection indication is standard on each unit. For ease of replacement, varistors are housed in pluggable modules with connections that are mechanically keyed to the base to prevent incorrect arrestor module replacement. Typical applications include low voltage distribution, or protection of industrial control systems, equipment assemblies and devices. Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com AC Surge Protector For transient voltage protection of single and multi-phase circuits, in the main electrical panel, downstream of the main circuit breaker, or in control panels. SPD II SPD II 120V/40kA SPD II 230V/40kA Technical data AC Network 120/240V, 120/208V 220/380V, 240/415V Connection Mode 1 Pole, L-N or L-G 1 Pole, L-N or L-G Max. Operating Voltage (MCOV) 150VAC 275VAC TOV Withstand 150VAC 275VAC Leakage Current at Uc <1mA <1mA Follow Current none none UL Nominal Discharge Current (In), 15 impulses 8/20 μs 20kA 20kA Max. Discharge Current (Imax), 1 impulse 8/20 μs 40kA 40kA UL Voltage Protection Rating (VPR) 500V 900V Protection Level (Up) 0.9kV 1.25kV UL Short-Circuit Current Rating (SCCR) 25kAIC 25kAIC AC System Single-phase Single-phase Thermal Disconnector UL 60691 UL 60691 Overcurrent Protection Time Delay - 125A Max. Time Delay - 125A Max. Dimensions (mm) 90 x 18 x 67 90 x 18 x 67 Connection Screw terminals, #4 AWG Max. Screw terminals, #4 AWG Max. Remote Signal Indicator 250VAC Max, 2A 250VAC Max, 2A Mounting Din-rail, TS35 Din-rail, TS35 Operating Temp -50°C to +85°C -50°C to +85°C Operating Altitude (Max.) 13,000 ft (4,000m) 13,000 ft (4,000m) Relative Humidity 5 to 95% non-condensing, up to 100% external 5 to 95% non-condensing, up to 100% external Enclosure Material Thermoplastic UL94-V0 Thermoplastic UL94-V0 Environmental Rating IP20 IP20 Weight 3.4 oz 3.4 oz Approvals 18 IEC 61643-1 - INTERNATIONAL 67 Class EN 61643-11 - EUROPE Class I, Class II NF EN 61643-11 - FRANCE Class I, Class II UL1449 3rd Edition - USA and CANADA Low Voltage SPD RoHS Directive 2002/95/EC I, Class II Ordering Data Class I, Class II Class I, Class II 10.6 Class I, Class II Low Voltage SPD L/N Directive 2002/95/EC 90 Type Surge Protector Bus bars Part No. Type Part No. SPD II 120V/40kA 6720005410 SPD II 230V/40kA6720005411 Type Type Part No. Part No. SPD 2P LINK 6720005417 SPD 2P LINK 6720005417 SPD 3P LINK 6720005418 SPD 3P LINK 6720005418 SPD 4P LINK 6720005419 SPD 4P LINK 6720005419 L/N 10.6 1.4 1.1 1.2 18 67 C L/N Mi Ft o t 90 V V: High-energy varistor Ft: Thermal fuse C: Remote signaling contact t0: Thermal disconnection system Mi: Disconnection indicator L/N 2 1.4 1.1 1.2 SPD II bus bars C Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com Mi Ft o AC Surge Protector For transient voltage protection of single and multi-phase circuits, in the main electrical panel, downstream of the main circuit breaker, or in control panels. SPD II SPD II 277V/40kA SPD II 480V/40kA Technical data AC Network 220/380V, 277V 347/600V, 480V Connection Mode 1 Pole, L-N or L-G 1 Pole, L-N or L-G Max. Operating Voltage (MCOV) 400VAC 550VAC TOV Withstand 400VAC 550VAC Leakage Current at Uc <1mA <1mA Follow Current none none UL Nominal Discharge Current (In), 15 impulses 8/20 μs 20kA 20kA Max. Discharge Current (Imax), 1 impulse 8/20 μs 40kA 40kA UL Voltage Protection Rating (VPR) 1500V 1800V Protection Level (Up) 1.8kV 2.5kV UL Short-Circuit Current Rating (SCCR) 25kAIC 25kAIC AC System Single-phase Single-phase Thermal Disconnector UL 60691 UL 60691 Overcurrent Protection Time Delay - 125A Max. Time Delay - 125A Max. Dimensions (mm) 90 x 18 x 67 90 x 18 x 67 Connection Screw terminals, #4 AWG Max. Screw terminals, #4 AWG Max. Remote Signal Indicator 250VAC Max, 2A 250VAC Max, 2A Mounting Din-rail, TS35 Din-rail, TS35 Operating Temp -50°C to +85°C -50°C to +85°C Operating Altitude 13,000 ft (4,000m) 13,000 ft (4,000m) Relative Humidity 5 to 95% non-condensing, up to 100% external 5 to 95% non-condensing, up to 100% external Enclosure Material Thermoplastic UL94-V0 Thermoplastic UL94-V0 Environmental Rating IP20 IP20 Weight 3.4 oz 3.4 oz Approvals 18 67 IEC 61643-1 - INTERNATIONAL Class I, Class II EN 61643-11 - EUROPE Class I, Class II NF EN 61643-11 - FRANCE Class I, Class II UL1449 3rd Edition - USA and CANADA Low Voltage SPD RoHS Directive 2002/95/EC Class I, Class II Class I, Class II 10.6 Class I, Class II Low Voltage SPD L/N Directive 2002/95/EC 90 Ordering Data Type Surge Protector Bus bars Part No. Type Part No. SPD II 277V/40kA6720005412 SPD II 480V/40kA6720005413 Type Type Part No. Part No. SPD 2P LINK 6720005417 SPD 2P LINK 6720005417 SPD 3P LINK 6720005418 SPD 3P LINK 6720005418 SPD 4P LINK 6720005419 SPD 4P LINK 6720005419 L/N 10.6 1.4 1.1 1.2 18 67 C L/N Mi Ft Ft: Thermal fuse C: Remote signaling contact o t 90 V: High-energy varistor V t0: Thermal disconnection system Mi: Disconnection indicator L/N 1.4 1.1 1.2 SPD II bus bars C Clearwater TechMi- Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com Ft o AC Surge Protector For transient voltage protection of multi-phase circuits with TT grounding systems. SPD II SPD II N/PE 67 18 N Technical data 90 67 Network 230/400V, 120/208V Max. Operating Voltage (MCOV) 255VAC TOV Withstand 400VAC Leakage Current at Uc none Follow Current 100A Nominal Discharge Current (In), 15 impulses 8/20 μs 20kA Max. Discharge Current (Imax), 1 impulse 8/20 μs 40kA Protection Level (Up) 1.5kV UL Short-Circuit Current Rating (SCCR) 25kAIC Dimensions (mm) 90 x 18 x 67 Connection Screw terminals, #4 AWG Max. Mounting Din-rail, TS35 Operating Temp -40°C to +85°C Enclosure Material Thermoplastic UL94-V0 Environmental Rating IP20 18 N 90 N GDT GDT: Specific gas tube Approvals IEC 61643-1 - INTERNATIONAL Class II EN 61643-11 - EUROPE Class II NF EN 61643-11 - FRANCE Class II UL1449 3rd Edition - USA Low Voltage SPD N GDT Ordering data Surge Protector Type Part No. SPD II N/PE6720005414 Bus bars Type SPD S LINK 1/3 Part No. 6720005416 SPD II bus bars 4 Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com AC Surge Protector For transient voltage protection of single-phase circuits with TT grounding systems. SPD II SPD II 120V/G/40kA Imax 40 k Technical data 67 TN-TT Max. Operating Voltage (MCOV) 150VAC TOV Withstand 150VAC Leakage Current at Uc <1mA Protection Mode MC/MD Nominal Discharge Current (In), 15 impulses 8/20 μs 20kA Max. Discharge Current (Imax), 1 impulse 8/20 μs 40kA Protection Level (Up) 1.5/0.9kV Residual Voltage @ 5k 0.6kV Short-Circuit Current Rating (SCCR) 10kAIC AC System Single-phase Thermal Disconnector Internal Overcurrent Protection Fuses type gG 50A Max. Dimensions (mm) 90 x 18 x 58 Connection Screw terminals, #4AWG Max. Disconnection Indicator 2 mechanical indicators Installation Ground Fault Breaker Type S or delayed Mounting Din-rail, TS35 Operating Temp -40°C to +85°C Operating Altitude 13,000 ft (4,000m) Relative Humidity 5 to 95% non-condensing, up to 100% external Enclosure Material Thermoplastic UL94-V0 Environmental Rating IP20 Weight 3.4 oz L L N EN 61643-11 - EUROPE Low Voltage SPD - Test Class II NF EN 61643-11 - FRANCE Low Voltage SPD - Test Class II UL1449 3rd Edition Approval in process C Ft t Ft to t V V L N C Ft Ft o o GDT Low Voltage SPD - Test Class II L/N L/N SPD II bus bars V C Approvals IEC 61643-1 - INTERNATIONAL N 90 1.4 1.1 1.2 Connection Mode 18 10.6 V : High energy varistor GDT : High energy Gas tube Ft : Thermal fuse C : Remote signaling contact t° : Thermal disconnection system 1.4 1.1 1.2 120V 1.4 1.1 1.2 AC Network V: High-energy varistor GDT: High energy gas tube to Ft: Thermal fuse V C: Remote signaling contact Ordering Data Surge Protector GDT Type t0: Thermal disconnection system Part No. SPD II 120V/G/40kA6720005415 Bus bars Type Part No. SPD 2P LINK 6720005417 SPD 3P LINK 6720005418 SPD 4P LINK 6720005419 Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com AC Surge Protector For transient voltage protection of single-phase devices. Local indicator (red LED) warns replacement is needed. SPD III SPD III 120V/10kA Imax 10 kA Imax 10 kA 58 18 Technical data L 18 58 AC Network 120V Connection Mode TN-TT Max. Operating Voltage (MCOV) 150VAC A40 150VAC TOV Withstand Max load current Leakage Current at Uc Follow Current A40 L 90 16A N N L 90 none N A A none Nominal Discharge Current (In), 15 impulses 8/20 μs 5kA Max. Discharge Current (Imax), 1 impulse 8/20 μs 10kA Protection Level (Up) 0.7kV Short-Circuit Current Rating (SCCR) 10kAIC AC System Single-phase Thermal Disconnector UL 60691 Internal Overcurrent Protection Time Delay - 125A Max. Dimensions (mm) 90 x 18 x 58 Connection Screw terminals, #4 AWG Max. Remote Signal Indicator 250VAC Max, 2A Mounting Din-rail, TS35 Operating Temp -40°C to +85°C Operating Altitude 13,000 ft (4,000m) Relative Humidity 5 to 95% non-condensing, up to 100% external Enclosure Material Thermoplastic UL94-V0 Environmental Rating IP20 Weight 3.4 oz L L N N DS98 V: MOV t L Ft to o V t Ft V V GDT Ft to o NFt V L N V : MOV DS98GDT: Gas tube GDT : Gas tube Ft: fuse Ft Thermal : Thermal fuse : Thermal disconnection disconnection mechanism t0t°: Thermal V : MOV GDT : Gasmechanism tube Ft : Thermal fuse t° : Thermal disconnection mechanism GDT L N L 120V AC Approvals N IEC 61643-1 - INTERNATIONAL Class II, Class III EN 61643-11 - EUROPE Class II, Class III NF EN 61643-11 - FRANCE Class II, Class III Ordering data Surge Protector Type Part No. SPD III 120V/10kA6720005416 1 x SPD III 120V/10kA (6720005416) Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com AC Surge Protector SPD II Basic configurations 1 L/N L/N TF L/N TF L1 TF L2 TF TF L3 TF SPD parts needed: Nom. V Description Part Number Qty Qty Qty 110/120V SPD II 120V/40kA 6720005410 1 2 3 230/240V SPD II 230V 40kA 6720005411 1 2 3 277V SPD II 277V 40kA 6720005412 1 2 3 480V SPD II 480V 40kA 6720005413 1 2 3 All SPD 2P Link 6720005417 0 1 0 All SPD 3P Link 6720005418 0 0 1 Basic configurations 2 L1 L2 TF TF L3 TF N TF SPD parts needed: Nom. V Description Part Number Qty 110/120V SPD II 120V/40kA 6720005410 4 230/240V SPD II 230V 40kA 6720005411 4 277V SPD II 277V 40kA 6720005412 4 480V SPD II 480V 40kA 6720005413 4 All SPD 4P Link 6720005419 1 Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com AC Surge Protector SPD II Basic configurations 3 TT network Nom: 120V L1 TT network N L1 TF L2 TF SPD parts needed: TF L3 N TF SPD parts needed: Nom. V Description Part Number Qty Nom. V Description Part Number Qty 120V SPD II 120V/G/40kA 6720005415 1 110/120V SPD II 120V/40kA 6720005410 3 230/240V SPD II 230V 40kA 6720005411 3 277V SPD II 277V 40kA 6720005412 3 480V SPD II 480V 40kA 6720005413 3 All SPD II N/PE 6720005414 1 All SPD S Link 1/3 6720005416 1 8 Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com