Appendix IV CITY OF WADSWORTH ENGINEERING DEPARTMENT Construction Standards For Sanitary Sewer Lift Stations December, 2004 PUMPS .................................................................................................................5 1. GENERAL......................................................................................................5 1.1. SECTION INCLUDES.............................................................................5 1.2. REFERENCES .......................................................................................5 1.3. SYSTEM DESCRIPTION .......................................................................6 1.4. PERFORMANCE CRITERIA ..................................................................6 1.5. SUBMITTALS .........................................................................................7 1.6. QUALITY ASSURANCE .........................................................................8 1.7. MANUFACTURER'S WARRANTY .......................................................11 2. PRODUCT ...................................................................................................12 2.1. PUMP STATION BUILDING.................................................................12 2.2. UNITARY RESPONSIBILITY ...............................................................15 2.3 MANUFACTURER ...............................................................................15 2.4. UNIT BASE...........................................................................................16 2.5. PUMP DESIGN ....................................................................................16 2.6. VALVES AND PIPING ..........................................................................20 2.7 DRIVE UNIT .........................................................................................22 2.8. ENGINE................................................................................................23 2.9. DRIVE TRANSMISSION ......................................................................25 2.10. FINISH ..............................................................................................26 2.11. ELECTRICAL CONTROL COMPONENTS:......................................26 2.12. LIQUID LEVEL CONTROL SYSTEM................................................32 3. EXECUTION................................................................................................43 3.1. EXAMINATION.....................................................................................43 3.2. INSTALLATION ....................................................................................43 3.3. FIELD QUALITY CONTROL.................................................................44 3.4. CLEANING ...........................................................................................44 3.5. PROTECTION ......................................................................................44 SEWAGE FLOW METER: ..................................................................................46 CONDUIT: ..........................................................................................................48 TELEMETRY SYSTEM.......................................................................................49 WET WELL .........................................................................................................51 December, 2004 DESCRIPTION: Under these specifications, the contractor shall furnish all labor, materials, tools, and equipment required to install standard suction lift pump stations as specified herein and as shown on the standard drawings. Sanitary pump stations shall be considered for installation in a proposed development only when there is no practical or physical way to serve the development and connect to City sewers by gravity. All work shall comply with current, applicable codes and standards including, but not limited to, the Ohio Basic Building Code, the National Electric Code, and Recommended Standards for Sewage Works (“Ten States Standards”). GENERAL: A. Pump Station Components: 1. The contractor shall furnish and install one factory built above ground, automatic pump station. The system shall be complete with all equipment specified herein. The principal items of equipment shall include two suction lift sewage pumps with hydraulic sealing flanges; discharge piping and valves, flow meter, emergency pump connections, with cam-lock connections, and any other necessary appurtenances. Pumping systems shall be as manufactured by Gorman-Rupp. 2. The contractor shall furnish and install a precast concrete wet well of sufficient size and capacity for the application. The wet well shall support the modular pumping system and shall meet all requirements of “Recommended Standards For Wastewater Facilities”. The wet well shall be as manufactured by Mack Industries, United Precast, Lindsay Concrete Products, or approved equal. 3. The contractor shall furnish and install a control and telemetry system in the pumping station compatible with the City of Wadsworth control and telemetry system located at the Wastewater Treatment Plant. The system shall include all pump controls (PLC’s) and alarms, level control systems, alarm light, wiring, stainless steel panels, and any other necessary appurtenances. The telemetry system shall transmit pump station operation data and alarms via radio communication to the main computer and control system at the Wadsworth Water Pollution Control Plant. 4.Discharge Bypass Piping - The station header pipe shall incorporate a 2-way plug valve to permit emergency access to the pump station force main after isolation of the pumps. The plug valve shall be non-lubricated, tapered type. Valve body shall be semi-steel with flanged end connections drilled to 125 pound City of Wadsworth, Ohio Page 3 Lift Station Standards 12/2004 standard. Valve shall be furnished with a drip-tight shutoff plug mounted in stainless steel or teflon over phenolic bearings, and shall have a resilient facing bonded to the sealing surface. 5. The Contractor shall furnish a complete building to house the pumps and related equipment. The building shall include plumbing systems for potable water, washdown, and drainage; mechanical systems for heating and ventilation as required by the selected station equipment and applicable codes; appropriate sound attenuation for noise created by pumping, mechanical, or electrical systems, including a standby generator; electrical systems for lighting, power, communications, security, control, and instrumentation. The building shall be of sufficient size to allow a minimum clear area of 48” from all equipment to allow for maintenance. ACCESSIBILITY: The pump station and all associated facilities shall be readily accessible by maintenance vehicles during all weather conditions. The facility shall be located off the traffic way of streets and alleys, but not more than 100 feet from a publicly owned street or right-of-way. When the pump station will be publicly owned, operated and maintained, the developer shall provide the necessary easements. The minimum easement dimensions shall provide 20 feet around the entire pump station and associated facilities. A minimum 30-foot access easement shall also be provided from the publicly owned street or right-of-way to the pump station facilities. A paved access drive with a minimum width of 10 feet shall be provided within the access easement. The minimum pavement section shall be 8” of 304 limestone. If asphalt or concrete drive access is provided, it shall meet City of Wadsworth Standard specifications for residential streets. City of Wadsworth, Ohio Page 4 Lift Station Standards 12/2004 PUMPS 1. PART - GENERAL 1.1. SECTION INCLUDES A. 1.2. Work under this section includes, but is not limited to, furnishing and installing a factory built duplex pump station as indicated on the project drawings, herein specified, as necessary for proper and complete performance. REFERENCES A. Publications listed below form part of this specification to extent referenced in the text by basic designation only. Consult latest edition of publication unless otherwise noted. 1. American National Std. Institute (ANSI) / American Water Works Assoc. (AWWA) a. ANSI B16.1Cast iron pipe flanges and flanged fittings. b. ANSI/AWWA C115/A21.51Cast/ductile iron pipe with threaded flanges. c. ANSI 253.1Safety Color Code for Marking Physical Hazards. d. ANSI B40.1Gages, Pressure and Vacuum. e. AWWA C508Single Swing Check Valves. 2.American Society for Testing and Materials (ASTM) a. ASTM A48 Gray Iron Castings. b. ASTM A126 Valves, Flanges, and Pipe Fittings. c. ASTM A307 Carbon Steel Bolts and Studs. d. ASTM A36 Structural Steel. 3.Institute of Electrical and Electronics Engineers (IEEE) a. ANSI/IEEE Std 100 Standard Dictionary of Electrical Terms. b. ANSI/IEEE Std 112 Test Procedure for Polyphase Induction Motors. c. IEEE Std 242 Protection of Industrial and Control Power Systems. 4. National Electric Code (NEC) / National Electrical Manufacturers Assoc. (NEMA) a. NEC National Electric Code. b. NEC 701National Electric Code article 701. c. NEMA Std MG1Motors and Generators. City of Wadsworth, Ohio Page 5 Lift Station Standards 12/2004 5. Miscellaneous References a. b. c. d. 1.3. 1.4. Ten-State Standards Recommended Standards for Sewage Work Hydraulic InstituteStd for Centrifugal, Rotary and Reciprocating Pumps. NMTBA and JIC Std.National Machine Tool Builders Association and Joint Industrial Council Standards ISO 9001 International Organization for Standardization. SYSTEM DESCRIPTION A. Contractor shall furnish and install one factory built, automatic pump station. The station shall be complete with all equipment specified herein, factory assembled on a common steel baseplate. B. The principal items of equipment shall include two self-priming, horizontal, centrifugal, v-belt motor driven sewage pumps, one water cooled standby engine, valves, and piping. A pump motor control panel with thermal-magnetic circuit breakers, magnetic motor starters, automatic liquid level control systems for normal and standby operation, and internal wiring. C. Factory built pump station design, including materials of construction, pump features, valves and piping, and motor controls shall be in accordance with requirements listed under PART 2 - PRODUCTS of this section. PERFORMANCE CRITERIA A. Pumps must be designed to handle raw, unscreened, domestic sanitary sewage. Pumps shall have 4" suction connection, and 4" discharge connection. Each pump shall be selected to perform under following operating conditions: Capacity (GPM) Total Dynamic Head (FT) Total Dynamic Suction Lift(FT) Maximum Repriming Lift (FT) Maximum Static Suction Lift(FT) B. ______ ______ ______ ______ ______ Station Power Requirements 1. Site power furnished to pump station shall be three phase, 60 hertz, 240 volts, 3 wire, maintained within industry City of Wadsworth, Ohio Page 6 Lift Station Standards 12/2004 standards. Voltage tolerance shall be plus or minus 10 percent. Control voltage shall not exceed 132 volts. 1.5. SUBMITTALS A. Product Data 1. Prior to fabrication, pump station manufacturer shall submit eight (8) copies of submittal data for review and approval. 2. Submittal shall include shop drawings, electrical ladder logic drawings, and support data as follows: Catalog cuts sheets reflecting characteristics for major items of equipment, materials of construction, major dimensions, motor and vbelt drive data, pump characteristic curves showing the design duty point capacity (GPM), head (FT), net positive suction head required (NPSHr), and hydraulic brake horsepower (BHP). Electrical components used in the motor branch and liquid level control shall be fully described. B. Shop drawings shall provide layout of mechanical equipment and anchor bolt locations for equipment baseplate. The electrical ladder logic drawings shall illustrate motor branch and liquid level control circuits to extent necessary to validate function and integration of circuits to form a complete working system. C. Operations Maintenance Manuals 1. Installation shall be in accordance with written instructions provided by the pump station manufacturer. Comprehensive instructions supplied at time of shipment shall enable personnel to properly operate and maintain all equipment supplied. Content and instructions shall assume operating personnel are familiar with pumps, motors, piping and valves, but lack experience on exact equipment supplied. 2. Documentation shall be specific to the pump station supplied and collated in functional sections. Each section shall combine to form a complete system manual covering all aspects of equipment supplied by the station manufacturer. Support data for any equipment supplied by others, even if mounted or included in overall station design, shall be provided by those supplying the equipment. Instructions shall include the following as a minimum: City of Wadsworth, Ohio Page 7 Lift Station Standards 12/2004 3. 1.6. a. Functional description of each major component, complete with operating instructions. b. Instructions for operating pumps, engine and pump controls in all modes of operation. c. Calibration and adjustment of equipment for initial start-up, replacement of level control components, or as required for routine maintenance. d. Support data for commercially available components not produced by the station manufacturer, but supplied in accordance with the specifications, shall be supported by literature from the prime manufacturer and incorporated as appendices. e. Electrical schematic diagram of the pump station circuits shall be in accordance with NFPA70. Schematics shall illustrate, to the extent of authorized repair, pump motor branch, control and alarm system circuits including interconnections. Wire numbers and legend symbols shall be shown. Schematic diagrams for individual components, not normally repairable by the station operator, need not be included. Details for such parts shall not be substituted for an overall system schematic. Partial schematics, block diagrams, and simplified schematics shall not be provided in lieu of an overall system diagram. f. Mechanical layout drawing of the pump station and components, prepared in accordance with good commercial practice, shall provide installation dimensions and location of all pumps, motors, engine, valves and piping. Operation and maintenance instructions which rely on vendor cut-sheets and literature which include general configurations, or require operating personnel to selectively read portions of the manual shall not be acceptable. Operation and maintenance instructions must be specific to equipment supplied in accordance with these specifications. QUALITY ASSURANCE A. The pumps and pump station manufacturer must be certified to ISO 9001 by an accredited certification agency. City of Wadsworth, Ohio Page 8 Lift Station Standards 12/2004 B. Upon request from the engineer, the pump station manufacturer shall prove financial stability and ability to produce the station within the specified delivery schedules. Evidence of facilities, equipment and expertise shall demonstrate the manufacturer's commitment to long term customer service and product support. C. Pump Performance Certifications 1. All internal passages, impeller vanes, and recirculation ports shall pass a 3" spherical solid. Smaller internal passages that create a maintenance nuisance or interfere with priming and pump performance shall not be permitted. Upon request from the engineer, manufacturer’s certified drawings showing size and location of the recirculation port(s) shall be submitted for approval. 2. Reprime Performance a. b. c. City of Wadsworth, Ohio Consideration shall be given to the sanitary sewage service anticipated, in which debris is expected to lodge between the suction check valve and its seat, resulting in the loss of the pump suction leg, and siphoning of liquid from the pump casing to the approximate center line of the impeller. Such occurrence shall be considered normal, and the pump must be capable of automatic, unattended operation with an air release line installed. During unattended operation, the pump shall retain adequate liquid in the casing to insure automatic repriming while operating at its rated speed in a completely open system. The need for a suction check valve or external priming device shall not be required. Pump must reprime ______ vertical feet at the specified speed and impeller diameter. Reprime lift is defined as the static height of the pump suction above the liquid, while operating with only one-half of the liquid remaining in the pump casing. The pump must reprime and deliver full capacity within five minutes after the pump is energized in the reprime condition. Reprime performance must be confirmed with the following test set-up: Page 9 Lift Station Standards 12/2004 1. 1) A check valve to be installed down stream from the pump discharge flange. The check valve size shall be equal (or greater than) the pump discharge diameter. 2) A length of air release pipe shall be installed between pump and the discharge check valve. This line shall be open to atmosphere at all times duplicating the air displacement rate anticipated at a typical pump station fitted with an air release valve. 3) The pump suction check valve shall be removed. No restrictions in the pump or suction piping will prevent the siphon drop of the suction leg. Suction pipe configuration for reprime test shall incorporate a 2 feet minimum horizontal run, a 90o elbow and vertical run at the specified lift. Pipe size shall be equal to the pump suction diameter. 4) Impeller clearances shall be set as recommended in the pump service manual. 5) Repeatability of demonstrated by reprime cycles. Full be achieved within cycle. 6) Liquid to be used for reprime test shall be water. performance shall be testing five consecutive pump capacity (flow) shall five minutes during each d. Upon request from the engineer, certified reprime performance test results, prepared by the manufacturer, and certified by a registered professional engineer, shall be submitted for approval prior to shipment. D. Factory System Test All components including the pumps, motors, engine, valves, piping and controls will be tested as a complete working system at the manufacturer's facility. Tests shall be conducted in accordance with Hydraulic Institute Standards at the specified head, capacity, rated speed and horsepower. Factory operational test shall duplicate actual performance anticipated for the complete station. City of Wadsworth, Ohio Page 10 Lift Station Standards 12/2004 2. E. 1.7. Upon request from the engineer, the operational test may be witnessed by the engineer, and/or representatives of his choice, at the manufacturer's facility. The manufacturers technical representative shall inspect the completed installation, correct or supervise the correction of any defect or malfunction, and instruct operating personnel in the proper operation and maintenance of the equipment as described in Part 3 of this section. MANUFACTURER'S WARRANTY A. The pump station manufacturer shall warrant all equipment to be of quality construction, free of defects in material and workmanship. A written warranty shall include specific details described below. 1. All other equipment, apparatus, and parts furnished shall be warranted for five (5) years, excepting only those items that are normally consumed in service, such as light bulbs, oils, grease, packing, gaskets, O-rings, etc. The pump station manufacturer shall be solely responsible for warranty of the station and all components. 2. Components failing to perform as specified by the engineer, or as represented by the manufacturer, or as proven defective in service during the warranty period, shall be replaced, repaired, or satisfactorily modified by the manufacturer without cost of parts or labor to the owner. B. It is not intended that the station manufacturer assume liability for consequential damages or contingent liabilities arising from failure of any vendor supplied product or part which fails to properly operate, however caused. Consequential damages resulting from defects in design, or delays in delivery are also beyond the manufacturer's scope of liability. C. The warranty shall become effective upon the acceptance by the purchaser or the purchaser's authorized agent, or sixty (60) days after installation, or ninety (90) days after shipment, whichever occurs first. City of Wadsworth, Ohio Page 11 Lift Station Standards 12/2004 2. PART - PRODUCT 2.1. PUMP STATION BUILDING A. Enclosure Construction and Design: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. The pump station configuration shall conform to the attached standard drawing as close as possible. Sizes may be increased due to larger models of equipment or other design changes. The standard drawing is included to show minimum dimensions. Other equipment and materials may be required as part of this standard that are not shown on the drawings. The building shall be above ground construction with a gabled roof. The exterior of the building will be reviewed by the City of Wadsworth Architectural Design Commission and will be similar in appearance to surrounding construction. Water service shall be supplied to the building with a faucet for attachment of hoses to washdown equipment and building. A minimum of 16 feet of hose will be supplied by the contractor. There shall be at least one electrically powered exhaust fan that can be activated by a wall mounted switch. Shelving shall be provided for stacking of maintenance equipment and materials. There shall be a floor drain located in the building with the floor slab sloped to it. Appropriate means of humidity control shall be included, whether an air conditioner of dehumidifier. Electrical GFCI outlets shall be provided on all walls. Adequate lighting will be required. Some installations may require the use of sound deadening material to control nuisance noise. One set of double-entry doors shall be provided and located on the wall opposite of the wet well. The doors shall have no center frame. A single entry man door will be required on a wall adjacent to the double door. When possible, all conduits for the pumps shall be placed below slab. A high capacity station heater shall be provided for the protection of the pumping equipment. The heater shall maintain an inside/outside differential temperature of 60 degrees F while operating on the supplied fuel (natural gas; LPG) to the station. The heater shall be provided with an City of Wadsworth, Ohio Page 12 Lift Station Standards 12/2004 adjustable 15. B. thermostat. The station enclosure shall be furnished with an extra double-wide door, to facilitate removal of equipment. A double hung door design with 3-point locking hardware, door closer, and hinges on each section shall allow complete access to the 6'-0" x 6'-8" full door opening without the need for a center sill. Enclosure Functional Equipment: 1. The interior of the station shall be illuminated by factory installed 120 volt, 40 watt, two (2) lamp fluorescent light fixtures providing two (2) watts illumination per square foot. All lights will be prewired and run to the control panel through PVC conduit and a weatherproof switch shall be installed adjacent to each station entrance. A length of flexible conduit shall provide for quick connection of the lighting circuit to the pump control panel. The lighting circuit shall be protected by a thermal-magnetic circuit breaker. 2. A thermostatically controlled 120 VAC exhaust fan with screen and weatherproof shutters shall be installed in the wall approximately opposite the fresh air intake vent. The fan shall have a minimum capacity of 1600 CFM at free air and be capable of changing the air in the enclosure a minimum of six times per hour. The exhaust fan shall be protected by a thermal-magnetic circuit breaker. 3. Two (2) self-contained, unpowered, thermally actuated fresh air intake vents shall progressively open or close exterior louvers as a result of thermal expansion or contraction of a wax-like material contained in an enclosed plunger actuator. Movement for the plunger rod shall drive the louver vane mechanical linkage. The louvers will progressively open at 75 degrees F, and progressively close at 60 degrees F. Operation of the intake louvers shall not require use of motors, solenoids, or other electrically related devices. The plunger actuator shall be mounted out of the incoming air flow, and shall hold the louvers fully open based on the ambient temperature of the pump station interior. The louver vanes and frame shall be constructed of anodized aluminum, with zinc plated steel actuator mounting and linkage. The louver vanes shall pivot on plastic bearings. City of Wadsworth, Ohio Page 13 Lift Station Standards 12/2004 C. 4. Two (2) sets of unpowered, thermally actuated exhaust vents shall be supplied for each engine used. The louvers will progressively open at 75 degrees F, and progressively close at 60 degrees F. Operation is the result of thermal expansion or contraction of wax in an enclosed plunger which is used to drive the louver vane mechanical linkage. Functional operation is identical to the intake vents, except the plunger actuator is mounted directly in the path of the air flow in order to sense the ambient temperature of the air exiting the pump station interior. 5. A critical grade spiral muffler and flexible exhaust pipe will be supplied for each engine. The pump station enclosure shall incorporate provisions for installation of the exhaust equipment through the wall panel. 6. The pump control panel for the Auto-start Pump station shall be shipped completely prewired to the pumps, motors, and engine(s) through conduit secured to the pump base. Upon installation, the contractor shall remove any temporary shipping hardware and brackets, and anchor the control panel permanently to the concrete station pad. Additional Enclosure Features: 1. A battery back-up 12 volt DC emergency lighting system shall provide 50 watts of illumination for 1-1/2 hours in the event of power outage. The system shall be fully selfcontained for automatic operation of (2) two sealed beam lamps powered by a maintenance free pure-lead 12 volt battery. An automatic solid state battery charger with integral transfer circuit shall maintain the battery in a constant state of readiness. A charge rate pilot light and test switch shall be provided. The charging circuit shall be protected by a thermal-magnetic circuit breaker. 2. A high capacity electric blower type station heater shall be provided for the protection of the pumping equipment. The heater shall maintain an inside/outside differential temperature of 60 degrees F while operating on the primary voltage supplied to the station. The heater shall be provided with an adjustable thermostat, circuit breaker, and contactor. 3. A wall mounted duplex GFI utility receptacle providing 120 volt AC power shall be installed and prewired through PVC City of Wadsworth, Ohio Page 14 Lift Station Standards 12/2004 conduit with the station lighting. The receptacle shall be protected by thermal magnetic circuit breaker. 2.2. 2.3 UNITARY RESPONSIBILITY A. The pump station system integrator must be certified to ISO 9001 by an accredited certification agency. B. In order to unify responsibility for proper operation of the complete pumping station, it is the intent of these Specifications that all system components be furnished by a single supplier (unitary source). The pumping station must be of standard catalog design, totally warranted by the manufacturer. Under no circumstances will a system consisting of parts compiled and assembled by a manufacturer's representative or distributor be accepted. MANUFACTURER A. The specifications and project drawings depict equipment and materials manufactured by The Gorman-Rupp Company which are deemed most suitable for the service anticipated. It is not intended, however, to eliminate other products of equal quality and performance. The contractor shall prepare his bid based on the specified equipment for purposes of determining low bid. Award of a contract shall constitute an obligation to furnish the specified equipment and materials. B. After execution of the contract, the contractor may offer substitutions to the specified equipment for consideration. The equipment proposed for substitution must be superior in construction and performance to that specified in the contract, and the higher quality must be demonstrated by a list of current users of the proposed equipment in similar installations. C. In event the contractor obtains engineer's approval for equipment substitution, the contractor shall, at his own expense, make all resulting changes to the enclosures, buildings, piping or electrical systems as required to accommodate the proposed equipment. Revised detail drawings illustrating the substituted equipment shall be submitted to the engineer prior to acceptance. D. It will be assumed that if the cost to the contractor is less for the proposed substitution, then the contract price shall be reduced by an amount equal to the savings. City of Wadsworth, Ohio Page 15 Lift Station Standards 12/2004 2.4. UNIT BASE A. 2.5. The unit base shall be comprised of structural steel with a perimeter flange and reinforcements. Perimeter flange and reinforcements shall be designed to prevent flexing or warping under operating conditions. Perimeter flange shall be drilled for hardware used to secure unit base to concrete pad as shown on the contract drawings. Unit base shall contain provisions for lifting the complete pump unit during shipping and installation. PUMP DESIGN A. B. General 1. The manufacturer of the pumps must be certified to ISO 9001 by an accredited certification agency. 2. Pumps shall be horizontal, self-priming centrifugal type, designed specifically for handling raw, unscreened, domestic sanitary sewage. Pump solids handling capability and performance criteria shall be in accordance with requirements listed under PART 1 - GENERAL of this section. Materials and Construction Features 1. Pump casing: Casing shall be cast iron Class 30 with integral volute scroll. Casing shall incorporate following features: a. Mounting feet sized to prevent tipping or binding when pump is completely disassembled for maintenance. b. Fill port coverplate, 3 1/2" diameter, shall be opened after loosening a hand nut/clamp bar assembly. In consideration for safety, hand nut threads must provide slow release of pressure, and the clamp bar shall be retained by detent lugs. A Teflon gasket shall prevent adhesion of the fill port cover to the casing. c. Casing drain plug shall be at least 1 1/4" NPT to insure complete and rapid draining. d. Liquid volume and recirculation port design shall be consistent with performance criteria listed under PART 1 - GENERAL of this section. City of Wadsworth, Ohio Page 16 Lift Station Standards 12/2004 2. 3. Coverplate: Coverplate shall be cast iron Class 30. Design must incorporate the following maintenance features: a. Retained by hand nuts for complete access to pump interior. Coverplate removal must provide ample clearance for removal of stoppages, and allow service to the impeller, seal, wearplate or check valve without removing suction or discharge piping. b. A replaceable wearplate secured to the coverplate by weld studs and nuts shall be AISI 1015 HRS. c. In consideration for safety, a pressure relief valve shall be supplied in the coverplate. Relief valve shall open at 75-200 PSI. d. Two O-rings of Buna-N material shall seal coverplate to pump casing. e. Pusher bolt capability to assist in removal of coverplate. Pusher bolt threaded holes shall be sized to accept same retaining capscrews as used in rotating assembly. f. Easy-grip handle shall be mounted to face of coverplate. Rotating Assembly: A rotating assembly, which includes impeller, shaft, mechanical shaft seal, lip seals, bearings, sealplate and bearing housing, must be removable as a single unit without disturbing the pump casing or piping. Design shall incorporate following features: a. Sealplate and bearing housing shall be cast iron Class 30. Separate oil filled cavities, vented to atmosphere, shall be provided for shaft seal and bearings. Cavities must be cooled by the liquid pumped. Three lip seals will prevent leakage of oil. 1) City of Wadsworth, Ohio The bearing cavity shall have an oil level sight gauge and fill plug check valve. The clear sight gauge shall provide easy monitoring of the bearing cavity oil level and condition of oil without removal of the fill plug check valve. The Page 17 Lift Station Standards 12/2004 check valve shall vent the cavity but prevent introduction of moist air to the bearings. 2) The seal cavity shall have an oil level sight gauge and fill/vent plug. The clear sight gauge shall provide easy monitoring of the seal cavity oil level and condition of oil without removal of the fill/vent plug. 3) Double lip seal shall provide an atmospheric path providing positive protection of bearings, with capability for external drainage monitoring. b. Impeller shall be ductile iron, two-vane, semi-open, non-clog, with integral pump out vanes on the back shroud. Impeller shall thread onto the pump shaft and be secured with a lockscrew and conical washer. c. Shaft shall be AISI 4140 alloy steel unless otherwise specified by the engineer, in which case AISI 17-4 pH stainless steel shall be supplied. d. Bearings shall be anti-friction ball type of proper size and design to withstand all radial and thrust loads expected during normal operation. Bearings shall be oil lubricated from a dedicated reservoir. Pump designs which use the same oil to lubricate the bearings and shaft seal shall not be acceptable. e. Shaft seal shall be oil lubricated mechanical type. The stationary and rotating seal faces shall be tungsten titanium carbide alloy. Each mating surface shall be lapped to within three light bands flatness (35 millionths of an inch), as measured by an optical flat under monochromatic light. The stationary seal seat shall be double floating by virtue of a dual O-ring design; an external O-ring secures the stationary seat to the sealplate, and an internal O-ring holds the faces in alignment during periods of mechanical or hydraulic shock (loads which cause shaft deflection, vibration, and axial/radial movement). Elastomers shall be viton. Cage and spring to be AISI 316 stainless steel. Seal shall be oil lubricated from a dedicated reservoir. The same oil shall not lubricate both shaft seal and shaft bearings. Seal shall be warranted in accordance with requirements listed City of Wadsworth, Ohio Page 18 Lift Station Standards 12/2004 under PART 1 - GENERAL of this section. f. 4. Pusher bolt capability to assist in removal of rotating assembly. Pusher bolt threaded holes shall be sized to accept same capscrews as used for retaining rotating assembly. Adjustment of the impeller face clearance (distance between impeller and wearplate) shall be accomplished by external means. a. Clearances shall be maintained by external shimless coverplate adjustment, utilizing collar and adjusting screw design for incremental adjustment of clearances by hand. Requirement of realignment of belts, couplings, etc., shall not be acceptable. Coverplate shall be capable of being removed without disturbing clearance settings. b. There shall be provisions for additional clearance adjustment in the event that adjustment tolerances have been depleted from the coverplate side of the pump. The removal of stainless steel shims from the rotating assembly side of the pump shall allow for further adjustment as described above c. Clearance adjustment which requires movement of the shaft only, thereby adversely affecting seal working length or impeller back clearance, shall not be acceptable. 5. Suction check valve shall be molded Neoprene with integral steel and nylon reinforcement. A blow-out center shall protect pump casing from hydraulic shock or excessive pressure. Removal or installation of the check valve must be accomplished through the coverplate opening, without disturbing the suction piping. Sole function of check valve shall be to save energy by eliminating need to reprime after each pumping cycle. Pumps requiring a suction check valve to assist reprime will not be acceptable. 6. Spool flanges shall be one-piece cast iron, class 30 fitted to suction and/or discharge ports. Each spool shall have one 11/4" NPT and one 1/4" NPT tapped hole with pipe plugs for mounting gauges or other equipment. City of Wadsworth, Ohio Page 19 Lift Station Standards 12/2004 C. D. Serviceability 1. The pump manufacturer shall demonstrate to the engineer's satisfaction that consideration has been given to reducing maintenance costs by incorporating the following features. 2. No special tools shall be required for replacement of any components within the pump. Pump drain kit 1. E. The pump drain kit shall consist of a 10' length of plastic hose with a quick connect female Kamlock fitting on one end of hose and two sets of fittings for pump drains. Each set of fittings for pump drain includes a stainless steel pipe nipple, stainless steel bushing, stainless steel ball valve and an aluminum quick connect male Kamlock fitting. Spare parts kit 1. There shall be furnished with the pump station the following minimum spare parts: a. b. c. d. 2.6. One spare pump mechanical seal (complete), and with it all gaskets, seals, sleeves, "o"-rings, and packing required to be replaced during replacement of the seal. One set of impeller clearance adjustment shims. One set cover plate "o"-ring. One rotating assembly "o"-ring. VALVES AND PIPING A. Each pump shall be equipped with a full flow type check valve capable of passing a 3" spherical solid. Valve shall be constructed with flanged ends and fitted with an external lever and torsional spring. Valve seat shall be constructed of stainless steel, secured to the body to ensure concentricity, sealed by an O-ring, and shall be replaceable. The valve body shall be cast iron incorporating a clean-out port large enough to allow removal and/or replacement of the valve clapper without removing valve or piping from the line. Valve clapper shall have a molded neoprene seating surface incorporating low pressure sealing rings. Valve hinge pin and internal hinge arm shall be stainless steel supported on each end in brass bushings. Shaft nut shall have double O-rings which shall be shall be easily replaceable without requiring access to interior of City of Wadsworth, Ohio Page 20 Lift Station Standards 12/2004 B. C. D. valve body. All internal hardware shall be stainless steel. Valve shall be rated at 175 PSI water working pressure, 350 PSI hydrostatic test pressure. Valves other than full flow type or valves mounted in such a manner that prevents the passage of a 3" spherical solid shall not be acceptable. The discharge header shall include a 3-way plug valve to permit either or both pumps to be isolated from the common discharge header. Valves shall have ports designed to pass spherical solids equal to the pumps capability. The plug valve shall be non-lubricated, tapered type. Valve body shall be semi-steel with flanged end connections drilled to 125 pound standard. Valve shall be furnished with a drip-tight shutoff plug mounted in stainless steel bearings, and shall have a resilient facing bonded to the sealing surface. Valve shall be operated with a single lever actuator providing lift, turn, and reseat action. The lever shall be equipped with a locking device to hold the plug in the desired position. Air Release Valves 1. Each pump shall be equipped with one automatic air release valve, designed to permit the escape of air to the atmosphere during initial priming or unattended repriming cycles. Upon completion of the priming or repriming cycle, the valve shall close to prevent recirculation. Valves shall provide visible indication of valve closure, and shall operate solely on discharge pressure. Valves which require connection to the suction line shall not be acceptable. 2. All valve parts exposed to sewage shall be constructed of cast iron, stainless steel, or similar corrosion resistant materials. Diaphragms, if used, shall be fabric-reinforced neoprene or similar inert material. 3. A clean out port, 3 inches or larger in diameter, shall be provided for ease of inspection, clean out, and service. 4. Valves shall be field adjustable for varying discharge heads. 5. Connection of the air release valves to the station piping shall include stainless steel fittings. Gauge kit 1. Each pump shall be equipped with a glycerin-filled compound gauge to monitor suction pressures, and a glycerin-filled pressure gauge to monitor discharge City of Wadsworth, Ohio Page 21 Lift Station Standards 12/2004 pressures. Gauges shall be a minimum of 4 inches in diameter, and shall be graduated in feet water column. Rated accuracy shall be 1 percent of full scale reading. Compound gauges shall be graduated -34 feet to +34 feet water column minimum. Pressure gauges shall be graduated 0 to 70 feet water column minimum. 2. E. Station Enclosure Low Temperature Alarm 1. F. G. 2.7 Gauges shall be mounted on a resilient panel and frame assembly which shall be firmly secured to pumps or piping. Gauge installations shall be complete with all hoses and stainless steel fittings, and shall include a shutoff valve installed in each gauge inlet at the point of connection to suction and discharge pipes. Pump station shall be supplied with a thermostat which shall monitor interior station temperature. The control shall incorporate an unpowered dry contact wired to terminal blocks for field connection to a remote alarm device. The contact will close in the event that the temperature within the enclosure falls below approximately 35 degrees F. Piping 1. Flanged header pipe shall be centrifugally cast, ductile iron, complying with ANSI/AWWA A21.51/C115 and class 53 thickness. 2. Flanges shall be cast iron class 125 and Comply with ANSI B16.1. 3. Pipe and flanges shall be threaded and suitable thread sealant applied before assembling flange to pipe. 4. Bolt holes shall be in angular alignment within 1/2o between flanges. Flanges shall be faced with a gasket finish. Contractor must insure all pipes connected to the pump station are supported to prevent piping loads from being transmitted to pumps or station piping. Pump station discharge force main piping shall be anchored with thrust blocks where shown on the contract drawings. DRIVE UNIT A. Motors City of Wadsworth, Ohio Page 22 Lift Station Standards 12/2004 1. Pump motors shall be _______ HP, three phase, 60 hertz, 240 VAC, horizontal ODP, 1800 RPM, NEMA design B with cast iron frame with copper windings, induction type, with class F insulation and 1.15 SF for normal starting torque and low starting current characteristics, suitable for continuous service. The motors shall not overload at the design condition or at any head in the operating range as specified. 2. Motors shall be tested in accordance with provisions of ANSI/IEEE Std 112. 3. Motor with engine shall be of a double shaft configuration. 2.8. ENGINE A. Standby engine shall be a four (4) cylinder or six (6) cylinder, (natural gas) fueled water cooled type, and shall have continuous duty power rating suitable for the horsepower requirements of the pump, after derating to factors set forth under performance. Engine shall be cooled by an integral water cooling system capable of maintaining safe engine operating temperature under expected operating loads, and subject to the expected maximum ambient temperatures in the pump station enclosure. B. Equipment 1. The engine shall be equipped with all controls and components required for manual and automatic operation when used with the engine controls and DC level control system described in these specifications. Such components shall include, but not be limited to, the following: a. b. c. d. e. f. g. h. City of Wadsworth, Ohio 12 Volt dc electrical system including starter and alternator Storage battery, 84 ampere-hour capacity minimum Elapsed running time meter Sensors for engine temperature, oil pressure, and overspeed Critical grade exhaust silencer to limit engine exhaust noise. Switch for manual operation of the cranking motor, mounted on or near the engine Voltmeter Solenoid fuel lock-off valve suitable for use with natural gas or LPG service Page 23 Lift Station Standards 12/2004 i. j. k. 2. 3. Lube oil pressure gauge Jacket water temperature gauge Tachometer Engine electrical equipment shall be wired to a terminal board on the engine and pre-wired to the base secured control panel. (Note: If control panel is opted to be shipped loose, connection to matching terminals in the control panel shall be by contractor.) Because the engine shall be required to operate during emergency situations, the following minimum performance standards shall be used for engine selection: a. Engine speed shall be controlled by an electronic, governor-controlled throttle which shall maintain the preset speed over the range of expected pumping loads. This speed shall not be less than 1800 rpm to insure adequate cooling, nor more than 3000 rpm so that internal engine wear is held to a minimum. This governed speed shall not be acceptable if it is greater than that speed at which the engine torque and horsepower curves intersect. Engine manufacturer's published performance curves shall be submitted for review to support engine selection. b. The engine shall develop approximately 95 percent of manufacturer's published performance after a reasonable run-in period. c. For selection of engine size, engine performance shall be derated according to manufacturer's specifications to allow for decreased performance if installed at elevations more than 1000 feet above sea level. d. For selection of engine size, engine performance shall be derated according to manufacturer's specifications to allow for decreased performance in an ambient temperature of 100-degrees f, which can reasonably be expected in the pump station. e. Engine rating shall be further reduced to conform to engine manufacturer's recommendations for continuous service applications. City of Wadsworth, Ohio Page 24 Lift Station Standards 12/2004 C. 2.9. Brake horsepower requirements of pump shall not exceed calculated engine horsepower after derating for power available after run-in, temperature compensation, and altitude compensation. DRIVE TRANSMISSION A. Power shall be transmitted from engine to pump by a v-belt drive assembly through a centrifugal clutch mounted on a jackshaft, which shall be coupled or otherwise interfaced with a shaft extension on the pump motor. Jackshaft shall be constructed of steel, not less than 1 1/2 inches in diameter, and shall be mounted in two pillow blocks furnished with anti-friction roller bearings. B. Each drive assembly shall have a minimum of two v-belts or one synchronized belt system. Each v-belt drive assembly shall be selected on the basis that adequate power will be transmitted from driver to pump based on the data developed in accordance with drive calculations. C. Centrifugal clutch shall be designed to remain disengaged until engine has reached some speed greater than idle speed to reduce starting loads. Once engaged, clutch shall be rated to transmit power continuously until engine speed has been reduced below disengagement speed. Clutch shall disengage completely while engine is not operating. D. Belt guards 1. Pump drive transmissions shall be enclosed on all sides in a guard constructed of any one or combination of materials consisting of expanded, perforated, or solid sheet metal, except that maximum perforated or expanded openings shall not exceed 1/2 inch. 2. Guards shall be manufactured to permit complete removal from the pump unit without interference with any unit component, and shall be securely fastened to the unit base. 3. All metal shall be free of burrs and sharp edges. Structural joints shall be continuously welded. Panels may be riveted to frames with not more than five-inch spacing. Tack welds shall not exceed four-inch spacing. 4. The guard shall be finished with one coat of gray W.R. non-lift primer and one coat of orange acrylic alkyd W.R. enamel in accordance with section 3, Color Definitions of City of Wadsworth, Ohio Page 25 Lift Station Standards 12/2004 ANSI 253.1; Safety Color Code for Marking Physical Hazards. 2.10. FINISH A. Pumps, piping, and exposed steel framework shall be cleaned prior to painting. Exposed surfaces to be coated with one coat gray W.R. non-lift primer and one coat white acrylic alkyd W.R. enamel. Paint shall be low VOC, alkyd based, high solids, semi-gloss white enamel for optimum illumination enhancement, incorporating rust inhibitive additives. The finish coat shall be 1.0 to 1.2 MIL dry film thickness (minimum), resistant to oil mist exposure, solvent contact, and salt spray. The factory finish shall allow for over-coating and touch up after final installation. 2.11. ELECTRICAL CONTROL COMPONENTS: A. The pump station control panel will be tested as an integral unit by the pump station manufacturer. The control panel shall also be tested with the pump station as a complete working system at the pump station manufacturer's facility. B. The electrical control components shall be provided by the pump station supplier and shall be provided with the following features. C. Panel enclosure 1. Enclosure shall be constructed in conformance with applicable section of National Electrical Manufacturers Association (NEMA) standards for type 1 electrical enclosures. Enclosure shall be fabricated of steel having a minimum thickness of not less than 0.075 Inch (14 gauge). All seams shall be continuously welded, and shall be free of burrs and voids. Interior and exterior surfaces shall be white enamel. There shall be no holes through the external walls of the enclosure for mounting the enclosure or any components contained within the enclosure. Panel enclosure up to 60" x 36" x 12" shall be mounted on floor stands and secured to pump base. 2. Enclosure shall be equipped with a door mounted on a continuous steel hinge, and sealed around its perimeter. Door shall be held closed with clamps that are quick and easy to operate. The door shall accommodate the mounting of switches and indicators. City of Wadsworth, Ohio Page 26 Lift Station Standards 12/2004 D. 3. Enclosure shall be furnished with a removable back panel, fabricated of steel having a thickness of not less than 0.106 Inch (12 gauge), which shall be secured to the enclosure with collar studs. Such panel shall be of adequate size to accommodate all basic components. 4. All control components shall be securely fastened to a removable back panel with screws and lock washers. Switches, indicators and instruments shall be mounted through the control panel door. Self-tapping screws shall not be used to mount any components. All connections from the back panel to door mounted or remote devices shall be made through terminal blocks. UL Label Requirement: 1. E. Pump station controls shall conform to third party safety certification. The panel shall bear a serialized UL label listed for "Enclosed Industrial Control Panels". The enclosure, and all components mounted on the sub-panel or control cover shall conform to UL descriptions and procedures. Motor Branch Components: 1. 2. Main connections a. A main terminal block and ground lug shall be furnished for field connection of the electrical supply. The connections shall be designed to accept copper conductors of sufficient size to serve the pump station loads. The main terminal block shall be mounted to allow incoming wire bending space in accordance with article 373 of the National Electric Code (NEC). A separate terminal strip shall be provided for 115 volt, single phase control power and shall be segregated from the main terminal block. Ten percent of the control terminals shall be furnished as spares. b. All motor branch components shall be of the highest industrial quality. Operating coils of all ac control devices shall be rated for 120 volts, and shall be suitable for use in a voltage range of 108 to 132 volts, 60 hertz. Circuit breakers and operating mechanisms City of Wadsworth, Ohio Page 27 Lift Station Standards 12/2004 F. a. A properly sized heavy duty air circuit breaker shall be furnished for each pump motor, and shall have a symmetrical RMS interrupting rating of 10,000 amperes at 230 volts. All circuit breakers shall be sealed by the manufacturer after calibration to prevent tampering. b. A padlocking operating mechanism shall be installed on each motor circuit breaker. Operator handles for the mechanisms shall be located on the exterior of the control compartment door, with interlocks which permit the door to be opened only when circuit breakers are in the "off" position. 3. An open frame, across-the-line, NEMA rated magnetic motor starter shall be furnished for each pump motor. Starters of NEMA size 1 and above shall be designed for addition of at least two auxiliary contacts. Starters rated "0", "00", or fractional sizes shall not be acceptable. Power contacts shall be double-break and made of cadmium oxide silver. All motor starters shall be equipped to provide undervoltage release and overload protection on all three phases. Motor starter contacts shall be easily replaceable without removing the motor starter from its mounted position. 4. Overload relays shall be solid-state block type, having visual trip indication with trip-free operation. Electrically resetting the overload will cause one (1) normally open and one (1) normally closed isolated alarm/control contact to reset, thus re-establishing a control circuit. Trip setting shall be governed by solid-state circuitry and adjustable current setting. Trip classes shall be 10, 15 and 20. Additional features to include phase loss protection, selectable jam/stall protection and selectable ground fault protection. 5. Overload reset pushbuttons shall be mounted through the door of the control panel in such a manner as to permit resetting the overload relays without opening the control panel door. Secondary Lightning Arrestor: 1. The control panel shall be equipped with a secondary lightning arrestor to minimize damage to the pump motors and control from transient voltage surges. The arrestor shall City of Wadsworth, Ohio Page 28 Lift Station Standards 12/2004 utilize silicon-oxide varistors encapsulated in a non-conductive housing. The arrestor shall have a current rating of 60,000 Amps, and a Joule rating of 1500. G. Three Phase Voltage Monitor: 1. H. The control panel shall be equipped to monitor the incoming power and shut down the pump motors when required to protect the motor(s) from damage caused by phase reversal, phase loss, high voltage, low voltage, and voltage unbalance. An adjustable time delay shall be provided to minimize nuisance trips. The motor(s) shall automatically restart, following an adjustable time delay, when power conditions return to normal. Other Control Components: 1. The control circuit shall be fused, and shall be provided with a disconnect switch connected in such a manner as to allow control power to be disconnected from all control circuits. 2. Pump mode selector switches shall be connected to permit manual start and manual stop of each pump motor individually. Manual operation shall override shutdown systems supplied with the level control system except motor overload. 3. Pump alternation shall be integral to the liquid level controller. Provisions for automatic alternation or manual selection shall also be integral to the liquid level controller. 4. A selector switch shall provide manual alternation of the air pumps in the bubbler system. The switch shall be connected in such a manner that either pump may be selected to operate continuously. 5. A pushbutton switch shall be provided to silence one of the 115 volt AC alarm circuits while corrective actions are underway. Depressing the alarm silence pushbutton shall also cause the high water alarm circuit (low water alarm optional) to reset when the liquid level has been lowered. 6. High pump temperature shutdown circuit a. City of Wadsworth, Ohio The control panel shall be equipped with circuitry to override the level control system and shut down the Page 29 Lift Station Standards 12/2004 pump motor(s) when required to protect the pump from damage caused by excessive temperature. b. 7. Six digit elapsed time meters (non-reset type) shall be connected to each pump motor starter to indicate the total running time of each pump in "hours" and "tenths of hours". 8. A duplex ground fault indicating utility receptacle providing 115 VAC, 60 hertz, single phase current shall be mounted on the side of the control enclosure. Receptacle circuit shall be protected by a 15 ampere thermal-magnetic circuit breaker. 9. Indicating lights shall be oil tight type and equipped with integral step-down transformers for long lamp life. Lamps shall be incandescent type rated 14 volts or less. Lamps shall be replaceable from the front without opening the control panel door and without the use of tools. Indicating lights will be provided for the following functions: a. b. c. d. e. f. g. h. i. j. k. I. A thermostat shall be mounted on each pump to detect its temperature. If the pump temperature should rise to a level which could cause pump damage, the thermostat shall cause the shutdown circuit to drop out the motor starter. An indicator, visible on the front of the control panel shall indicate that the pump motor has been stopped because of a high temperature condition. The pump shall remain locked out until the pump has cooled and the circuit has been manually reset. Automatic reset of such a circuit shall not be acceptable. Pump #1 high pump temperature shutdown Pump #2 high pump temperature shutdown High wet well level Alarm silenced Pump #1 run Pump #2 run Engine low oil pressure Engine high temperature Engine overspeed Engine overcrank 115 volt power available Wiring City of Wadsworth, Ohio Page 30 Lift Station Standards 12/2004 1. The pump station components, as furnished by the manufacturer, shall be completely pre-wired. (Note: If control panel is opted to be shipped loose, the pump station as furnished by the manufacturer shall be completely pre-wired except for the power feeder lines and final connections to pump motors, engine, and remote alarm devices. The interconnecting wire, conduit, and other materials required shall be furnished and installed by the electrical contractor.) 2. All wiring, workmanship, and schematic wiring diagrams shall be in compliance with applicable standards and specifications for industrial controls set forth by the Joint Industrial Council (JIC), National Machine Tool Builders Association (NMTBA), and the National Electric Code (NEC). 3. All user serviceable wiring shall be type MTW or THW, 600 volts, and shall be color coded as follows: a. b. c. d. e. f. g. 4. Line and load circuits, AC or DC power black AC control circuit less than line voltage red DC control circuit blue Interlock control circuit, from external sourceyellow Equipment grounding conductor green Current carrying ground white Hot with circuit breaker open orange Wire identification and sizing a. Control circuit wiring inside the panel, with the exception of internal wiring of individual components, shall be 16 gauge minimum, type MTW or THW, 600 volts. Wiring in conduit shall be 14 gauge minimum. Motor branch wiring shall be 10 gauge minimum. b. Motor branch conductors and other power conductors shall not be loaded above the temperature rating of the connected termination. Wires shall be clearly numbered at each end in conformance with applicable standards. All wire connectors in the control panel shall be of the ring tongue type with nylon insulated shanks. All wires on the sub-plate shall be bundled and tied. All wires extending from components mounted on door shall be terminated on a terminal block mounted on the back panel. All wiring outside the panel shall be installed in conduit. City of Wadsworth, Ohio Page 31 Lift Station Standards 12/2004 5. J. K. Control conductors connecting components mounted on the enclosure door shall be bundled and tied in accordance with good commercial practice. Bundles shall be made flexible at the hinged side of the enclosure. Adequate length and flex shall be allowed so that the door can swing to its full open position without undue mechanical stress or abrasion on the conductors or insulation. Bundles shall be clamped and held in place with mechanical fastening devices on each side of the hinge. Conduit requirements are as follows: 1. All conduit and fittings shall be UL listed. 2. Liquid tight flexible metal conduit shall be constructed of a smooth, flexible galvanized steel core with smooth abrasion resistant, liquid tight, polyvinyl chloride cover. 3. Conduit shall be supported in accordance with articles 346, 347, and 350 of the National Electric Code. 4. Conduit shall be sized according to the National Electric Code. Grounding 1. The pump station manufacturer shall ground all electrical equipment to the enclosure back panel. The mounting surface of all ground connections shall have any paint removed before making final connections. 2. The contractor shall provide an earth driven ground connection to the control panel at the main ground lug in accordance with the National Electric Code (NEC). 2.12. LIQUID LEVEL CONTROL SYSTEM A. The manufacturer of the liquid level control system must be certified to ISO 9001 by an accredited certification agency. B. Pump station shall operate on utility power while such power is available, except for exercise periods as specified herein. When operating on utility power, operation of pumps and motors shall be controlled by the level control system as specified herein. During a failure of utility power and during exercise periods, operation of the City of Wadsworth, Ohio Page 32 Lift Station Standards 12/2004 pump with the standby engine shall be controlled by the level control system and engine control system specified herein. Transfer from AC control and to DC control shall occur as follows. 1. 2. C. Relays and other controls shall be provided to accomplish the following functions: a. Time delay after failure of utility power before transfer from AC control to DC control. Relay shall be manually adjustable from 0.2 To 60 seconds. b. Time delay after restoration of utility power before transfer from DC control to AC control. Relay shall be manually adjustable from 0 to 30 minutes. c. Automatic override of time delay after power restoration, upon occurrence of: engine or engine control failure as specified under engine control system. d. Manual override of time delay on restoration of normal power. Momentary pushbutton or similar device shall be acceptable. e. Time delay after transfer from DC control to AC control before application of AC power to motor of pump with standby engine. Such relay shall be preset at approximately 15 seconds to permit engine to stop completely before motor is started. f. Indicate the presence of utility power. Such indicator shall be the press-to-test type to permit the operator to verify failure of utility power. These functions and interlocks shall be applicable only to the motor of the pump furnished with the standby engine. No hindrance shall be included for the motor starter and motor branch circuit for the pump which does not have the standby engine. Immediately upon restoration of utility power after power interruption, and during exercise periods, the pump which does not have the standby engine shall be permitted to run if operation of that pump is required by the AC control system. Controls shall be provided to cause regular use of the DC control system and standby engine. Such exercise of standby components City of Wadsworth, Ohio Page 33 Lift Station Standards 12/2004 shall occur to maintain these components in a ready condition, and to discover malfunctions before emergency conditions arise. D. 1. Exercise periods shall be established by a manually adjustable exercise timer. Timer shall provide a 7-day timing cycle, and shall permit the selection of one or more exercise periods of 15 minute duration, or multiples thereof, which shall repeat every 7 days. 2. During exercise periods, timer shall simulate a loss of utility power to transfer circuits described herein. After transfer from AC control to DC control, the DC control system shall operate the pump with the standby engine through the engine control system as described in these specifications. 3. If the standby engine is operating at the end of the exercise period, it shall continue to operate until one of the following conditions occurs: a. The DC control system stops the engine through the engine control system, or b. The delay on restoration of utility power relay times out. 4. Upon occurrence of either of these conditions, operation of the engine shall cease and revert to control by the AC control system. 5. During exercise periods, utility power shall remain available to the motor of the pump which does not have the standby engine. LIQUID LEVEL CONTROL (AC/DC) 1. The integral AC/DC level control system shall start and stop the pump motors/engine in response to changes in wet well level, as set forth herein. 2. The DC control system shall start and stop the standby engine through the engine control system and in response to changes in the wet well liquid level during a failure of utility power and during exercise periods. 3. The level control system shall be capable of operating as either an air bubbler type level control system, submersible City of Wadsworth, Ohio Page 34 Lift Station Standards 12/2004 transducer type system, or ultrasonic transmitter type system. 4. The level control system shall be designed to accomplish the following tasks: a. Continuously monitor the level of liquid in the wet well. b. Start and stop pump motors/engine as required by the level of liquid in the wet well. c. Select the sequence of pump operation upon operator command for automatic alternation. d. Provide alarm indications predetermined malfunctions. e. Upon restoration of utility power after a power outage, the system shall delay the application of power to the engine driven pump, by a length of time that has been preselected by the operator. upon occurrence of 5. The level control system shall utilize alternation to select first one pump, then the second pump, to run as lead pump for a pumping cycle. Alternation shall occur at the end of a pumping cycle, or in the event of excessive run time. 6. The level control system shall utilize an electronic pressure switch which shall continuously monitor the wet well level, permitting the operator to read wet well level at any time. Upon operator selection of automatic operation, the electronic pressure switch shall start the motor for one pump when the liquid level in the wet well rises to the "lead pump start level". When the liquid is lowered to the "lead pump stop level", the electronic pressure switch shall stop this pump. These actions shall constitute one pumping cycle. Should the wet well level continue to rise, the electronic pressure switch shall start the second pump when the liquid reaches the "lag pump start level" so that both pumps are operating. These levels shall be adjustable as described below. a. City of Wadsworth, Ohio The electronic pressure switch shall include integral components to perform all pressure sensing, signal conditioning, EMI and RFI suppression, DC power supply and 120 volt outputs. Comparators shall be Page 35 Lift Station Standards 12/2004 solid state, and shall be integrated with other components to perform as described below. b. The electronic pressure switch shall be capable of operating on a supply voltage of 12VDC in an ambient temperature range of -10 degrees C (14 degrees F) through 55 degrees C (131 degrees F). Control range shall be 0 to 12.0 feet of water with an overall repeat accuracy of (plus/minus) 0.1 feet of water. Memory shall be retained using a non-volatile lithium battery back-up. c. The electronic pressure switch shall consist of the following integral components: pressure sensor, display, electronic comparators and output relays. 1) The internal pressure sensor shall be a strain gauge transducer and shall receive an input pressure from the air bubbler system. The transducer shall convert the input to a proportional electrical signal for distribution to the display and electronic comparators. The transducer output shall be filtered to prevent control response to level pulsations or surges. The transducer range shall be 0-15 PSI, temperature compensated from -40 degrees C (-40 degrees F) through 85 degrees C (185 degrees F), with a repeat accuracy of (plus/minus) 0.25% full scale about a fixed temperature. Transducer overpressure rating shall be 3 times full scale. 2) City of Wadsworth, Ohio The electronic pressure switch shall incorporate a digital back lighted LCD panel display which, upon operator selection, shall indicate liquid level in the wet well, and the preset start and stop level for both lead and lag pump. The display shall include twenty (20), 0.19" high alpha-numeric characters calibrated to read out directly in feet of water, accurate to within one-tenth foot (0.1 foot), with a full scale indication of not less than 12 feet. The display shall be easily convertible to indicate English or metric units. Page 36 Lift Station Standards 12/2004 3) Level adjustments shall be electronic comparator set-points to control the levels at which the lead and lag pumps start and stop. Each of the level settings shall be easily adjustable with the use of membrane type switches, and accessible to the operator without opening any cover panel on the electronic pressure switch. Controls shall be provided to permit the operator to read the selected levels on the display. Such adjustments shall not require hard wiring, the use of electronic test equipment, artificial level simulation or introduction of pressure to the electronic pressure switch. 4) Each output relay in the electronic pressure switch shall be solid state. Each relay input shall be optically isolated from its output and shall incorporate zero crossover switching to provide high immunity to electrical noise. The "ON" state of each relay shall be indicated by illumination of a light emitting diode. The output of each relay shall be individually fused providing overload and short circuit protection. Each output relay shall have an inductive load rating equivalent to one NEMA size 4 contactor. A pilot relay shall be incorporated for loads greater than a size 4 contactor. d. The electronic pressure switch shall be equipped with an output board which shall include LED status indicators and a connector with cable for connection to the main unit. e. The electronic pressure switch shall be equipped with pump start delay(s) preset at a fixed delay time of five (5) seconds. f. Circuit design in which application of power to the lag pump motor starter is contingent upon completion of the lead pump circuit shall not be acceptable. g. The electronic pressure switch shall be equipped with a simulator system capable of performing system cycle testing functions. City of Wadsworth, Ohio Page 37 Lift Station Standards 12/2004 h. The electronic pressure switch shall be capable of controlling liquid levels in either a pump up or pump down application. i. The electronic pressure switch shall have internal capability of providing automatic alternation, manual selection of pump sequence operation, and alternation in the event of 1-199 hours excessive run time. j. The electronic pressure switch shall be equipped with a security access code to prevent accidental set-up changes and provide liquid level set-point lock-out. k. The electronic pressure switch shall be equipped with one (1) 0-33 ft. W.C. input, one (1) scalable analog input of either 0-5VDC, 0-10VDC, or 4-20mA, and one (1) 4-20mA scalable output. Output is powered by 10VDC supply. Load resistance for 4-20mA output shall be 100-400 ohms. l. The electronic pressure switch shall include a DC power supply to convert 120VAC control power to 12VDC EPS power. The power supply shall be 500 mA (6W) minimum and be UL listed Class II power limited power supply. m. The electronic pressure switch shall be equipped with an electronic comparator and solid state output relay to alert maintenance personnel to a high liquid level in the wet well. In the event that the wet well liquid reaches a preset high water alarm level the alarm output relay shall energize a signal relay. The signal relay shall complete a 12 volt DC circuit for an external alarm device. An indicator, visible on the front of the control panel, shall indicate that a high wet well level exists. The alarm signal shall be maintained until the wet well level has been lowered and the circuit has been manually reset. High water alarm shall be furnished with a dry contact wired to terminal blocks. n. The electronic pressure switch shall be equipped with an electronic comparator and solid state output relay to start and stop the standby engine in response to City of Wadsworth, Ohio Page 38 Lift Station Standards 12/2004 changes in wet well level during a failure of utility power and during exercise periods. o. E. Pressure Transducer System (AC/DC) 1. F. The level control system shall be the pressure transducer type, Ametek mod 5505B006, 4-20mA, 0-13.8ft pressure transducer. There shall be a backup DC control for power interruptions. Operating power for the pressure transducer shall be provided by the storage battery furnished with the standby engine. Alarm Light (External): 1. G. An alarm silence pushbutton and relay shall be provided to permit maintenance personnel to de-energize the audible alarm device while corrective actions are under way. After silencing the alarm device, manual reset of the alarm condition shall clear the alarm silence relay automatically. The pushbutton shall be oil tight design with contacts rated NEMA A300 minimum. Station manufacturer will supply one 12 VDC alarm light fixture with vapor-tight shatter resistant red globe, conduit box, and mounting base. The design must prevent rain water from collecting in the gasketed area of the fixture, between the base and globe. The alarm light will be shipped loose for installation by the contractor. Engine Control System: 1. The engine control system shall be designed to accomplish the following tasks: a. Permit the operator to select mode of engine operation, providing manual start and stop of the engine to override the level control system and cranking circuit if required. b. Crank the engine upon start command from the level control system, and stop the engine upon a stop command. City of Wadsworth, Ohio Page 39 Lift Station Standards 12/2004 c. Stop the cranking sequence if the engine fails to start after a reasonable number of attempts, and provide an alarm indication of failure to start. d. While the engine is operating, continuously monitor engine speed, temperature and oil pressure. e. Stop the engine for excessive speed, excessive engine water temperature, or insufficient oil pressure, and provide an alarm indication of shutdown and its cause, and shall f. Maintain the charge on the engine storage battery. g. Shutdown features shall be wired to the terminal strip to provide a general alarm indication. 2. Upon operator selection of automatic operation, when the standby level control system provides a start command, the engine control system shall start the engine cranking motor for a short period of time. If the engine does not start, the system shall stop the cranking motor for a short period of time, then resume cranking. Typically, 5 10-second cranking periods, each followed by a 10-second rest period, should be considered a reasonable effort to start the engine. When the engine starts, a sensor on the engine or elsewhere in the system shall stop the cranking cycle and reset the cranking circuit for the next start. 3. If the engine does not start within the preset number of attempts, the cranking circuit shall be deenergized, a failure to start indicator on the control panel shall be illuminated, and an external alarm device shall be energized. Control of the pump with the standby engine shall be returned to the AC control system. 4. Once the engine has started normally, the engine control system shall monitor engine speed, cylinder head temperature , and oil pressure. Upon engine failure from any cause, system shall provide an alarm indication, illuminate an indicator, and energize and external alarm device as specified below. City of Wadsworth, Ohio Page 40 Lift Station Standards 12/2004 5. During periods when the DC control system is fully operative, a battery charger shall continuously charge the engine storage battery. 6. Mode of engine operation a. b. 7. Switches or other devices shall be provided and connected to perform as follows: 1) When automatic operation is selected, engine shall start and stop under control of the engine control system. 2) When manual cranking motor pushbutton or Once started, selected. 3) Operator can stop engine if it is running, and prevent it from starting during maintenance or repair. operation is selected, engine shall be controlled by a manual other device on the engine. engine shall run until off is Engine failure circuits shall stop the engine, illuminate a labeled indicator on the control panel, and energize an external alarm device for each of the following conditions: 1) Engine speed exceeds maximum overspeed setting. 2) Engine temperature exceeds safe operating temperature as specified by the engine manufacturer. 3) Engine oil pressure falls below engine manufacturer's specified recommendations. System must override or bypass this function during cranking and several seconds after starting to permit engine to build up oil pressure. Engine control system shall be furnished with one battery charger, designed and connected to operate on 115 volts, AC 60 hertz to maintain the charge on the 12 volt DC City of Wadsworth, Ohio Page 41 Lift Station Standards 12/2004 storage battery supplied with the engine. Battery charger shall incorporate the following design features: 8. H. a. Automatic charge adjustment circuit. sensing and charging b. Integral current limit circuit to limit charging rate. c. Charging rate ammeter. d. Fuse for protection of charging circuit. rate Operating power for the engine control system, except the battery charger, shall be provided by the storage battery furnished with the standby engine. BACKUP LIQUID LEVEL CONTROL 1. A backup level control system shall be provided to operate the pumps, in the event of a failure of the primary solid state level control system. This backup level control will allow for a redundant pump off switch to turn the pump motors off in the event of a primary level control failure. 2. The backup level control system shall start and stop pump motors in response to changes in wet well level. It shall be the mercury float switch type, incorporating intrinsically safe relays. Rising and falling liquid level in the wet well causes switches within the floats to open and close, providing start and stop signals to the remainder of the level control system. 3. The backup level control system shall start and stop the pumps in accordance to the wet well level. The pump start and stop float switches shall be set above and below the normal pump start and stop level settings utilized for the primary level control. Upon operator selection of automatic operation, a float switch shall start one pump motor when water rises to the “pump start level”. When the water is lowered to the “pump stop level”, the system shall stop the pump. These actions shall constitute one pumping cycle. 4. The backup level control system shall work in conjunction with an alternator relay to select first one pump, then the second pump, to run as “Lead” pump. Alternation will occur at the end of each pumping cycle. City of Wadsworth, Ohio Page 42 Lift Station Standards 12/2004 5. Two (2) float switches shall be supplied for installation by the contractor. Each float shall contain a mercury switch sealed in a polypropylene housing, with 50 feet of power cord, and polypropylene mounting hardware. A PVC chain with weight shall be furnished to secure the switches in the wet well. 6. Two intrinsically safe relays shall be supplied in a separate level control enclosure. Relays must be recognized and listed as intrinsically safe by a nationally recognized testing laboratory. Installing contractor shall make connections from relays to motor controls. 3. PART - EXECUTION 3.1. EXAMINATION A. 3.2. Contractor shall off-load equipment at installation site using equipment of sufficient size and design to prevent injury or damage. Station manufacture shall provide written instruction for proper handling. Immediately after off-loading, contractor shall inspect complete pump station and appurtenances for shipping damage or missing parts. Any damage or discrepancy shall be noted in written claim with shipper prior to accepting delivery. Validate all station serial numbers and parts lists with shipping documentation. Notify the manufacturers representative of any unacceptable conditions noted with shipper. INSTALLATION A. Install, level, align, and lubricate pump station as indicated on project drawings. Installation must be in accordance with written instructions supplied by the manufacture at time of delivery. B. Suction pipe connections are vacuum tight. Fasteners at all pipe connections must be tight. Install pipe with supports and thrust blocks to prevent strain and vibration on pump station piping. Install and secure all service lines (level control, air release valve or pump drain lines) as required in wet well. C. Check motor and control data plates for compatibility to site voltage. Install and test the station ground prior to connecting line voltage to station control panel. D. Prior to applying electrical power to any motors or control equipment, check all wiring for tight connection. Verify that protective devices (fuses and circuit breakers) conform to project City of Wadsworth, Ohio Page 43 Lift Station Standards 12/2004 design documents. Manually operate circuit breakers and switches to ensure operation without binding. Open all circuit breakers and disconnects before connecting utility power. Verify line voltage, phase sequence and ground before actual start-up. 3.3. FIELD QUALITY CONTROL A. B. Operational Test 1. Prior to acceptance by owner, an operational test of all pumps, drives, and control systems shall be conducted to determine if the installed equipment meets the purpose and intent of the specifications. Tests shall demonstrate that all equipment is electrically, mechanically, structurally, and otherwise acceptable; it is safe and in optimum working condition; and conforms to the specified operating characteristics. 2. After construction debris and foreign material has been removed form the wet well, contractor shall supply clear water volume adequate to operate station through several pumping cycles. Observe and record operation of pumps, suction and discharge gage readings, ampere draw, pump controls, and liquid level controls. Check calibration of all instrumentation equipment, test manual control devices, and automatic control systems. Be alert to any undue noise, vibration or other operational problems. Manufacturers Start-up Services 1. 3.4. CLEANING A. 3.5. Co-ordinate station start-up with manufactures technical representative. The representative or factory service technician will inspect the completed installation. He will calibrate and adjust instrumentation, correct or supervise correction of defects or malfunctions, and instruct operating personnel in proper operation and maintenance procedures. Prior to acceptance, inspect interior and exterior of pump station for dirt, splashed material or damaged paint. Clean or repair accordingly. Remove from the job site all tools, surplus materials, scrap and debris. PROTECTION City of Wadsworth, Ohio Page 44 Lift Station Standards 12/2004 A. The pump station should be placed into service immediately. If operation is delayed. Station is to be stored and maintained per manufacturers written instructions. City of Wadsworth, Ohio Page 45 Lift Station Standards 12/2004 SEWAGE FLOW METER: The pump station manufacturer shall furnish a Polysonics SX40 Doppler flow meter with the pump station. The flowmeter shall be factory mounted and wired within the above ground building. A 15 amp circuit breaker shall be provided and 1/60/120 volt pump supply shall be connected to the flowmeter. The Doppler transducer sensors shall be field installed on the discharge piping within the building, at the time of station startup. 1. The flow meter shall utilize ultrasonic, Dual Frequency Doppler (DFD) technology, which will transmit a minimum of two independent frequencies through the flow stream, to provide indication, totalization, data logging and signal transmission of liquid rate in full pipes. 2. The flowmeter will measure flow rates of solids bearing and/or aerated fluids over a velocity span of 0.2 to 32 ft/s (0.06 to 10 m/s). The two Dual Frequency transducers will be supplied with the instrument and shall be suitable for pipe sizes from 0.5 to 200 inches (12 to 5000 mm). 3. The instrument will provide a +- 1% total error ban under reference conditions. 4. Configuration will be via a front panel 19 key flat membrane keypad with tactile feedback. Input parameters will be password protected. The nonvolatile memory shall retain totalizer and user parameters for up to five years. Flowmeter diagnostics shall be accessible via the keypad. 5. A 90,000 point data logger, programmable in 30 second, 1, 5, 15, 30, and 50 minute intervals will be included as standard in the flowmeter. HydraLink data retrieval software will be supplied with the instrument. 6. The analog output shall be an opto isolated, 12 bit, 4-40mA DC signal proportional to flow. Output current limited circuitry will be incorporated in the flow meter electronics. An RS232 serial interface will be provided. 7. The flowmeter shall be suitable for either (1)90-132 VAC, 190-250 VAC, 50/60 Hz, switch selectable. 8. The transducers will be encased in stainless steel shrouds and will be suitable for submersion and operation from -70°F to +250°F (-40°C to +122°C). 9. The transducers will attach to the outside of the pipe by means of stainless steel straps. The standard transducer cable length will be 20 feet (6m). 10. The flowmeter electronics shall be designed to operate at temperatures between -5°F to +140°F (-20°C to +60°C). All electronic circuits are to be interchangeable with other flow meters having the same model number. All circuit boards will be conformal coated with an antifungus compound. 11. The display will be a backlit, 240 x 640 dot, high resolutions graphics display. 12. The electronics enclosure will be environmentally protected to NEMA 4X (IP65). City of Wadsworth, Ohio Page 46 Lift Station Standards 12/2004 13. For additional security, the enclosure will provide a facility for the attachment of a padlock to prevent unauthorized access to the display and front panel. 14. The manufacture shall provide a full NIST traceable flow calibration certificate. 15. The instrument shall be manufacture in the USA at an ISO 9001 certified facility. 16. The dual frequency Doppler flow meter will be the Polysonics Hydra SX40 model manufacture by Polysonics, Inc., 10335 Lansbury, Suite 300, Houston, Texas 77099-3407, (281) 879-3700. City of Wadsworth, Ohio Page 47 Lift Station Standards 12/2004 CONDUIT: A. Conduit requirements are as follows: 1. All conduit and fittings shall be UL Listed 2. Liquid tight flexible metal conduit shall be constructed of a smooth, flexible galvanized steel core with smooth abrasion resistant, liquid tight, polyvinyl chloride cover. 3. Conduit shall be supported in accordance with articles 346, 347, and 350 of the national electric code. 4. Conduit shall be sized according to the national electric code. B. Grounding 1. The pump station manufacturer shall ground all electrical equipment to the enclosure back panel. The mounting surface of all ground connections shall have any paint removed before making final connections. 2. The contractor shall provide an earth driven ground connection to the control panel at the main ground lug in accordance with the national electric code (nec). City of Wadsworth, Ohio Page 48 Lift Station Standards 12/2004 TELEMETRY SYSTEM The lift station supplier shall supply an integrated pump control package with its standard offering, complete with the following signals available for incorporation into the Wadsworth Water Treatment SCADA System: Pump status (on/off) High level switch (on/off) Backup High level switch (on/off) Lift station water level (4-20 ma signal from level transmitter) The integrated pump control package supplier shall also provide complete electrical schematics showing all components integrated into its pump control system. These signals will be incorporated into a stand-alone, networked Lift Station SCADA panel using an Allen-Bradley Micrologix 1200 programmable logic controller with Ethernet connectivity allowing this control panel to send its data over the city of Wadsworth's fiber optic backbone to the Wadsworth Water Treatment Plant SCADA System. The SCADA system located at the Wadsworth Water Treatment Plant shall provide the following information to the Water Treatment plant operator from each lift station: Communication active Communication failure alarm Call for pump Pump running Pump run hours Level High-level alarm Backup high level switch alarm Level transmitter fault The Lift Station SCADA Panel will contain the following devices: Allen-Bradley MicroLogix 1200 Programmable Logic Controller Allen-Bradley 4 Channel Analog Input Module Allen-Bradley ENI Serial to Ethernet Converter Serial to ENI Network Cable 24V DC Power Supply Current Switch Terminal Blocks The City of Wadsworth will supply the cable connection to its fiber optic backbone and cable modem. The city will be responsible for network addressing and routers required to facilitate data communication. Once networking is City of Wadsworth, Ohio Page 49 Lift Station Standards 12/2004 implemented and data is available to the Water Treatment Plant, operator graphics will be provided by the operations staff at the Water Treatment Plant. City of Wadsworth, Ohio Page 50 Lift Station Standards 12/2004 WET WELL A. Construction 1. Wet wells shall be constructed of reinforced, precast concrete sections having a 4,000-psi, 28-day compressive strength, and shall conform to ODOT 511, Class “C” concrete. Precast, concrete sections shall conform to ASTM C478, with “O” ring joints per ASTM C443. Walls shall be sized to adequately function for the intended purpose and shall withstand all loadings when full or empty. All walls and joints shall be watertight. The entire wet well shall be coated inside and out with coal tar epoxy or approved equal, and all joints shall be sealed with a butyl sealant sheet around the outside perimeter of the joint, extending 9” on either side of the joint. 2. All reinforcing steel used in wet well construction shall conform to ODOT item 509 and ACI 301-84. All reinforcing bars shall be epoxy coated and have a yield stress of Fy = 60,000 psi. All reinforcing fabric shall be epoxy coated and shall conform to ASTM A 185. B. Floor Slope: The wet well floor shall have a minimum slope of 1:1 from the walls to the hopper bottom. The horizontal area of the hopper bottom shall be not greater than that necessary for proper installation and function of the suction pipe inlets. C. Standard manhole steps shall be installed as indicated on the drawings and shall meet applicable OSHA and D.O.E.S. standards. Steps shall be plastic coated type per M.A. Industries, Inc., PS-1-PF or approved equal. D. Top Slab and Access: The top slab of the pump station wet well shall be designed to support the personnel and equipment needed for maintenance and equipment removal and shall be reinforced concrete, 8” thick minimum. The slab shall be provided with a minimum 36” square wet well access hatch. Access hatch frame and cover shall be aluminum with 300 series stainless steel hinges and hardware. The frame and cover shall be flush with the slab top when closed, have a slip resistant, diamond pattern texture, and be designed for heavy-duty service. The cover shall be provided with a lifting handle and safety latch to hold the cover in an open position, shall have safety grating for fall protection when the doors are open, and shall have recessed padlock hasps with hinged covers. Contractor shall provide two (2) padlocks. Access hatch shall be Bilco Type KD or approved equal. E. Size: City of Wadsworth, Ohio Page 51 Lift Station Standards 12/2004 The wet well size (volume) and control settings for pumps shall be appropriate to avoid excessive on/off cycles and shall also avoid septic conditions due to excessive detention time. As much as is practical, wet well size and pumping rates shall be designed to deliver as uniform a flow as possible. The effective volume of the wet well shall be based on design average flow and filling time not to exceed 30 minutes. In no case shall the well diameter be less than five (5) feet. F. Ventilitation: Air displacement shall be accomplished using an inverted “j” tube or other means. Ventilation for maintenance safety purposes shall provide at least 12 complete air changes per hour if continuous, or 30 complete air changes per hour if intermittent. Air shall be forced into the wet well by mechanical means. Switches for operation of ventilation equipment shall be marked and located conveniently and/or automatic controls installed for intermittent usage. G. Piping: All piping in wet wells shall be ductile iron pipe, Class 53, per ANSI/AWWA C151/A21.51 with flanged or mechanical joints, and of the size shown on the drawings. H. Testing: Wet wells shall be vacuum tested in accordance with the City of Wadsworth, Engineering Construction Standards. City of Wadsworth, Ohio Page 52 Lift Station Standards 12/2004 MANUFACTURER'S RESPONSIBILITIES: A. OPERATIONAL TEST The pumps, motors, and controls shall be given an operational test in accordance with the standards of the hydraulic institute. Recordings of the test shall substantiate the correct performance of the equipment at the design head, capacity, suction lift, speed and horsepower as herein specified. Upon request from the engineer, the engineer or his representative shall be invited to witness the operational test at the manufacturer's facility or other location designated by the manufacturer. B. SUBMITTALS The manufacturer of the pump station shall be responsible for delivery to the engineer of (4) copies of the support literature required herein. C. INSTALLATION INSTRUCTIONS Installation of the pump station and related appurtenances shall be performed in accordance with written instructions by the manufacturer. D. OPERATION AND MAINTENANCE INSTRUCTIONS 1. The pump station manufacturer shall be responsible for supplying written instructions, which shall be sufficiently comprehensive to enable the operator to operate and maintain the pump station and all equipment supplied by the station manufacturer. Said instructions shall assume that the operator is familiar with pumps, motors, piping, and valves, but that he has not previously operated and/or maintained the exact equipment supplied. 2. The instructions shall include, but not limited to, the following: a. Descriptions of, and operating instructions for, each major component of the pump station as supplied. b. Instructions for operation of the pump station in all intended modes of operation. c. Instruction for all adjustments that must be performed at initial start-up of the pump station, adjustments that must be performed after the replacement of the level control system components, and adjustments that must be performed in the course of preventative maintenance as specified by the manufacturer. d. Service instructions for major components not manufactured by the pump station manufacturer but which are supplied by him in City of Wadsworth, Ohio Page 53 Lift Station Standards 12/2004 accordance with these specifications. The incorporation of literature produced by the actual component manufacturer shall be acceptable. e. Electrical schematic diagram of the pump station as supplied, prepared in accordance with NMTBA and JIC standards. Schematics shall show, to the extent of authorized repair, pump motor branch, control, and alarm system circuits, and interconnections among these circuits. Wire numbers shall be shown on the schematic. Schematic diagrams for individual components, the detail parts of which are not normally repairable by the station by the station operator, need not be included, and shall not be substituted for an overall schematic diagram. Partial schematics, block diagrams, and simplified schematics shall not be provided in lieu of overall schematic diagram. f. Layout drawing of the pump station as supplied, prepared in accordance with good commercial practice, showing the locations of all pumps, motors, valves, and piping. 3. Operation and maintenance instructions which are limited to a collection of component manufacturer literature without overall pump station instructions shall not be acceptable. 4. Operation and maintenance instructions shall be specific to the equipment supplied in accordance with these specifications. Instruction manuals applicable to many different configurations and pump stations, and which require the operator to selectively read portions of the instructions shall not be acceptable. MANUFACTURER'S ABILITIES: A. DELIVERY Upon request from the engineer, the pump station manufacturer shall demonstrate proof of financial responsibility with respect to performance and delivery date. B. EXPERIENCE Upon request from the engineer, the pump station manufacturer shall demonstrate proof or evidence of facilities, equipment, and skills required to produce the equipment specified herein. C. MANUFACTURER'S QUALIFICATIONS The Manufacturer of Equipment of this Section shall have five years minimum proven experience in such Equipment and shall have City of Wadsworth, Ohio Page 54 Lift Station Standards 12/2004 satisfactorily completed three jobs of similar size and type within the last year. D. MANUFACTURER'S FIELD REPRESENTATIVE 1. The Manufacturer of the Equipment of this Section shall provide a qualified field representative at the Site. 2. Such Manufacturer's field representative shall instruct the Owner's personnel in the proper handling, installation, start-up, and operation of the equipment. 3. Such Manufacturer's field representative shall instruct the Owner's personnel in the proper start-up, operation, and maintenance of the equipment. The instruction period shall be a minimum of eight hours. E. RESPONSIBILITY It shall be the responsibility of the Manufacturer of the pumps specified in this Section to provide the pumps/motors, level control systems, complete motor control center and all ancillary equipment for the correct operation and performance of each pump. The pump manufacturer shall test the pumps and controls as a system at the factory. MANUFACTURER'S WARRANTY: A. MATERIAL AND WORKMANSHIP The manufacturer of the pump station shall warrant it to be of quality construction, free from defects in material and workmanship. This warranty shall include specific details described below. OVERALL PUMP STATION: A. EQUIPMENT WARRANTY 1. The contractor shall furnish a Maintenance and Guaranty Bond to the City upon completion of the pump station and force main. The equipment, apparatus, and parts furnished shall be warranted for a period of one (1) year, excepting only those items that are normally consumed in service, such as light bulbs, oil, grease, packing, gaskets, o-rings, etc. The contractor shall be solely responsible for the warranty of the station and all components. 2. Components failing to perform as specified by the engineers, or as represented by the manufacturer, or as proven defective in service during City of Wadsworth, Ohio Page 55 Lift Station Standards 12/2004 the warranty period, shall be replaced, repaired, or satisfactorily modified by the manufacturer without cost of parts or labor to the owner. EFFECTIVE DATE: A. INITIAL DATE 1. The warranty shall become effective upon the acceptance by the City of Wadsworth of the entire pumping system. Acceptance shall be made only after all testing is complete and passed, all punch list items addressed by the contractor and/or manufacturer, and all equipment functioning as designed. PERMITS AND APPROVALS: A. The contractor shall obtain and pay for any and all permits and inspections required for the execution of this work. Permits, approvals and other requirements included in this work shall be as follows. 1. Electrical Service a. Contractor shall pay initial installation charges as well as monthly charges until the pump station is accepted by the City of Wadsworth. 2. Natural Gas Service (If Required) a. Contractor shall pay initial installation charges as well as monthly charges until the pump station is accepted by the City of Wadsworth. 3. Ohio Environmental Protection Agency a. Contractor shall pay all plan review fees and other associated fees. b. Contractor shall submit a copy of the EPA Plan Approval Letter to the City. 4. Building Department a. Contractor shall pay all plan review fees and other associated fees. 5. Planning Department City of Wadsworth, Ohio Page 56 Lift Station Standards 12/2004 a. Contractor shall pay all plan review fees and other associated fees. 6. Engineering Department a. Contractor shall pay for any inspection fees associated with the work. b. Contractor shall pay a Pump Station Installation Fee to cover the cost of programming and telemetry system coordination at the Water Pollution Control Plant, which shall be the actual cost of such work, but not to exceed $1500.00. The full $1500 shall be paid up front as a deposit, and any unused portion refunded to the contractor following successful pump station start-up. City of Wadsworth, Ohio Page 57 Lift Station Standards 12/2004