ELECTRICAL SECTION 16510 INTERIOR LIGHTING

THIS IS A DESIGN GUIDE NOT A SPECIFICATION
Montgomery County Public Schools Facilities Guide
DIVISION 16 – ELECTRICAL
SECTION 16510
INTERIOR LIGHTING
PART 1 – GENERAL
A. Standard Lighting Design
1. Lighting: Consultants are directed to utilize Montgomery County Board of
Education guidelines for Average Illumination Levels (FC)/Max LPD (Watts/sq.
ft.) for all lighting application. See Standard Detail E-19.0 for Interior Lighting on
the following pages.
2. Standard Interior Lighting and Switching: Consultants are directed to utilize
Montgomery County Board of Education Lighting and Switching Details for
classrooms, gymnasiums, etc. See Standard Details on the following pages.
3. Fluorescent lighting fixture ballasts shall be on of the following:
a. Universal Triad ULT7 series
b. Advance Optanium series.
4. Ballasts for fluorescent fixtures should be electronic, rapid start and have high
power factor exceeding 90% with a total harmonic distortion shall not exceed
20%
5. Compact fluorescent lamps are limited to the following medium base, screw type,
self ballasted Phillips lamps:
a. SLS 9 watt/ 35
b. SLS 13 watt/ 35
c.
SL/T 40 watt/ 35/ RS
5. Fluorescent down lights – 70% efficient minimum with two SLS 13 watt/35 lamps
and electronic HPF ballast.
6. Lamps for fluorescent lighting fixtures shall be T8-3500K lamps.
7. All light switches shall be toggle switches except boys and girls toilet rooms
which shall key switches. Key operated light switches are not acceptable except
as noted.
7. A maximum of 10% of corridor fixtures and 25% of stairwell fixtures should be
connected to circuits for night and emergency lighting, as needed to meet code.
Wherever possible these fixtures should not be located adjacent to windows,
skylights, and illuminated display cases.
8. Use of incandescent fixtures should be avoided. Exceptions can be made for
stage and low level auditorium lighting.
B. Interior Lighting
1. Lighting fixture efficiency for all fixtures shall be 80% or better.
2. Provide no key-operated type switches.
3. Typical Classroom Lighting Standard See Standard Detail E-14.0 on the
following pages.
4. Classroom lighting fixture – suspended, two lamp direct/indirect fixture with an
open top (Indirect) and a 3” parabolic louver on the bottom (Direct) with 2 lamp.
Revised 4/17/09
INTERIOR LIGHTING
16510 - 1
THIS IS A DESIGN GUIDE NOT A SPECIFICATION
32 watt T-8. Fixture shall have no lenses. Acceptable manufacturer’s: Finelite,
Lightolier, Alera. See Fixture Standard cut sheets on the following pages.
5. Office lighting fixture - Lay-in, 2 lamp. 32 watt T-8, 12 cell, 3” deep parabolic
louver, non-specular. Acceptable manufacturer’s: Lithonia, Columbia, Lightolier.
See Fixture Standard cut sheets on the following pages.
6. Gymnasium lighting fixture – Aluminum dome, 2 circuit, 8 – 32 watt compact
fluorescent lamps with male hook and multi-circuit cord, flat clear lens, safety
cable to ballast box and wire guard. Acceptable Manufacturers’: Sportlite, Voight
Lighting, Vantage. See Fixture Standard cut sheets on the following pages.
7. Gymnasium lighting control: Provide a 16” wide x 30” high x 6” deep NEMA 1
enclosure for each switch bank of Gym lights and motorized backboard switches.
Proved hinged cover and lock. All cabinets shall be keyed alike. Route switch
legs of Gym lights to NEMA 1 switch box. See Standard Details E-16.0 and E17.0 on the following pages
8. Bleacher Area (High and Middle Schools only) - Behind each bleacher bank
provide two surface mount light fixture for maintenance purpose.
9. Exit signs shall be LED type with 6" high, 3/4" red letters on white background.
Provide wire guard for gymnasium fixtures. Connect all exit signs to a separate
circuit. Acceptable, manufacturers - Lithonia, Dual Lite, Hubbell.
10. Switch emergency stair lights with a relay circuit. See Standard Detail E-18.0 on
the following pages.
11. Provide ceiling mounted occupancy sensors in classrooms, See Standard Detail
E-14.0 on the following pages.
12. Provide occupancy sensors in place of light switch in storage rooms and any
other rooms normally unoccupied.
13. Food Areas – Provide a lay-in, gasketed fixture with the lens installed with the
smooth side down.
C. Elementary and Middle Schools - Stage Lighting:
1. Provide (2) three circuit border lights with red, blue and green gels.
2. Provide a ten foot long, two circuit lighting track with seven track lights.
3. Provide a dimming system to control:
a. Red border lights
b. Blue border lights
c.
Green border lights
d. One circuit of track lights
e. Second circuit of track lights
f.
Stage lights
D. High Schools – Stage Lighting: Coordinate design with MCPS
PART 2 – SPECIFICATIONS
A. Warranty: The electrical designer must include the following paragraphs in the
electrical section of project specifications:
1. Ballasts and lamps shall carry five-year warranties as described below, including
labor allowance.
Revised 4/17/09
INTERIOR LIGHTING
16510 - 2
THIS IS A DESIGN GUIDE NOT A SPECIFICATION
2. The contractor shall be responsible for replacement of all defective lamps and
ballast for a period of one year from the date of acceptance. During this one year
period, the contractor shall respond to the owner'
s request to replace defective
lamps and ballasts within one week of receipt of the request. A failure of five
lamps or ballasts, or failure of any lamp or ballast in sensitive areas will cause a
service call.
3. One month before the end of this one-year period, the contractor shall make a
facility wide survey to identify and replace all defective ballasts and lamps. The
contractor shall provide the owner written notice of this survey and warranty
replacement two weeks prior to the survey. In the event that the contractor fails
to accomplish this facility-wide survey to identify and replace all defective ballasts
and lamp, the initial warranty shall be extended until such time as the contractor
fulfills the survey requirements.
4. For the second through fifth year after acceptance, the ballast shall be covered
by a full replacement warranty and a $10 per ballast installation allowance. (This
is the standard warranty provided on electronic ballasts by several
manufactures.)
B. Removal of existing ballasts: The electrical designer must include the follow
paragraph in the electrical section of project specifications:
1. Renovation projects in which existing light fixtures are to be removed, it shall be
the responsibility of the contractor to remove and dispose of all PCB ballasts.
Disposal shall be in accordance with EPA Regulation 40CFR-761.
Revised 4/17/09
INTERIOR LIGHTING
16510 - 3
Catalog Number
Notes
Type
FEATURES & SPECIFICATIONS
PARAMAX® Parabolic Troffer
INTENDED USE — High performance parabolic luminaires for use in open
area applications and electronic offices where optical control, visual
comfort and light cut-off are important.
2PM3N 2'x4'
ATTRIBUTES — Design optimized for use with T8 lamps and low-profile
electronic ballasts.
Choice of diffuse or specular louvers utilizing the latest developments in
louver finishing for minimized louver iridescence.
CONSTRUCTION — Black reveal provides floating louver appearance,
conceals optional air-supply slots.
Square corner end plates improve strength and durability.
Integral T-bar safety clips hold fixture to T-bar securely; no fasteners required.
3" Louver Family
Heavy-gauge hinges die-formed for maximum strength; spring action
latches concealed in black reveal.
Housing formed from cold-rolled steel. Louver formed from anodized
aluminum. No asbestos used in this product.
Overlapping flange and modular ceiling trims available factory installed with
swing gate hangers or field convertible with optional trim and hangers.
FINISH — Five-stage iron-phosphate pretreatment ensures superior paint
adhesion. Painted parts finished with high-gloss, baked white enamel.
ELECTRICAL SYSTEM — Thermally-protected, resetting, Class P, HPF, nonPCB, UL Listed, CSA certified ballast is standard.
Electronic ballasts are sound rated A.
Ballast disconnect provided standard where required to comply with US
and Canadian electrical codes.
Fixture conforms to UL1570 and is suitable for damp locations. AWM, TFN
or THHN wire used throughout, rated for required temperatures.
LISTING — UL Listed (Standard), CSA Certified or NOM Certified (see Options).
Specifications
Length: 48 (1218)
Width: 24 (609)
Depth: 4-1/2 (114)
Weight: 32 lbs (14.5 kg)
48
(1218)
4-1/2
(114)
24
(609)
All dimensions are inches (millimeters). Specifications subject to
change without notice.
WARRANTY — Guaranteed for one year against mechanical defects
in manufacture.
ORDERING INFORMATION
For shortest lead times, configure product using standard options (shown in bold).
Example: 2PM3N G B 3 32 18LD MVOLT 1/3 GEB10IS
32
2PM3N
Series
2PM3N Paramax
3" louver
family
Air function
B No air
function
G Grid
F Overlapping
flange
ST Screw slot
3
2
Fluorescent
120
277
347
Others
available.
Number of
lamps
2
3
4
Not included.
Louver finish
12
18
32
LD
16
24
LS
4
Low
iridescent
anodized
diffuse silver
Low
iridescent
anodized
specular
Some options increase fixture depth. silver
Consult factory if plenum space is a
concern.
2 lamps = 12 cells, diffuse silver
4 lamps = 32 cells, diffuse silver
MVOLT standard for 120V and 277V
applications. Some options require
voltage specified.
MVOLT
Number of cells1
Trim type
3 lamps = 18 cells, diffuse silver
2
32 32W T8
(48")
A Air supply/
return (slots in
side trim)
H Heat removal
(through lamp
cavity,
dampers
available)
D Dual function
supply/return/
removal
NOTES:
1 Standard louver configuration:
Voltage
Lamp type
Must specify circuit wiring. Refer to
www.lithonia.com/Reloc for additional
information.
5
Must specify voltage.
6
Available with 3-lamp 18 or 24 cell only.
Options 3
(blank) Two ballasts (three- and four-lamp only)
1/3 One 3-lamp ballast
1/4 One 4-lamp ballast
1/41/2 Use with LST. One 4-lamp and one 2-lamp ballast.
GEB10IS Electronic ballast, <10% THD, instant start
GEB10RS Electronic ballast, <10% THD, rapid start
EL Emergency battery pack (nominal 300 lumens
EL14 Emergency battery pack (nominal 1400
lumens)
PWS1836 6' prewire, 3/8" dia., 18-gauge, 3 wires
PWS1846 6' prewire, 3/8" dia., 18-gauge, 4 wires
QFC313__ Reloc Quick-Flex 12/3G, 13’ 4,5
LST Tandem fixture pairs (shared ballasts)
LP__ Lamped; specify lamp type and color
LP735 Lamped 700 Series, 3500K
GLR
GMF
ACS
APB
PAF
2R
Internal fast-blow fuse 5
Internal slow-blow fuse5
Air closure strips (A and D models only)
Air-pattern control blades (A and D models only)
Painted after fabrication (white enamel)
Two reflector channel covers 6
JP Palletized and stretch-wrapped (G trim only)
CSA CSA Certified
NOM NOM Certified
Sheet #: 2PM3N-2x4
PAR-130
2PM3N 2'x4' 3" Louver Family
MOUNTING DATA
DIMENSIONS
Continuous row mounting of flanged units requires CRE and CRM trim options. Consult
factory.
Appropriate
Trim Type
Ceiling Type
Exposed grid tee
Concealed grid tee
Concealed Z-spline
Screw slot (consult factory)
Acoustical tile, plaster or plasterboard
on rigid support parallel to lamps
G
G, ST
F
ST
2-13/16
(71)
4-1/2
3-1/2 (114)
(89)
24
(609)
F
2-13/16 3-1/2
(89)
(71)
4-1/2
(114)
24
(609)
4-1/2
2-13/16 3-1/2 (114)
(89)
(71)
NOTE:
1
24
(609)
Recommended rough-in dimensions for F trim fixtures 24"x48" (Tolerance is
+1/4", -O”). Swing-gate range 1-7/16" to 3-7/16", span 23-1/2" to 26-7/16".
PHOTOMETRICS
Energy (Calculated in accordance with NEMA standard LE-5)
Calculated using the zonal cavity method in accordance with IESNA LM41 procedures.
Floor reflectances are 20%. Lamp configurations shown are typical. Full photometric data
on these and other configurations available upon request.
LER.FP
ANNUAL
ENERGY COST *
65 (LD louver) $3.69
66 (LD louver) $3.64
59 (LD louver) $4.07
LAMP
DESCRIPTION
LAMP
LUMENS
BALLAST
FACTOR
WATTS
(2) 32WT8
(3) 32WT8
(4) 32WT8
2850
2850
2850
.88
.88
.88
59
85
112
* Comparative yearly lighting energy cost per 1000 lumens.
Coefficients of Utilization
20%
70%
50% 30% 10%
89 89 89
80 77 75
71 66 63
62 57 53
55 49 45
49 43 38
44 38 33
40 34 29
36 30 26
33 27 23
31 25 21
80%
50% 30% 10%
91 91 91
82 79 76
72 67 63
64 58 53
56 50 45
50 44 39
45 38 34
41 34 29
37 31 26
34 28 23
31 25 21
Zonal Lumen Summary
Zone Lumens % Lamp % Fixture
0° - 30° 1177.9 20.7
26.9
0° - 40° 2015.8 35.4
46.1
0° - 60° 3919.0 68.8
89.6
0° - 90° 4372.0 76.7
100.0
90° - 180° 0.0
0.0
0.0
0° - 180° 4372.0 76.7
100.0
50%
50% 30% 10%
85 85 85
77 75 73
68 64 61
60 56 52
53 48 44
48 42 38
43 37 33
39 33 29
35 30 26
32 27 23
30 25 21
pf
pc
pw
0
1
2
3
4
5
6
7
8
9
10
Coefficients of Utilization
20%
70%
50% 30% 10%
87 87 87
79 76 74
70 66 63
62 57 53
56 50 46
50 44 40
45 39 35
41 35 31
38 32 28
34 29 25
32 26 23
80%
50% 30% 10%
89 89 89
80 78 75
71 67 63
64 58 54
57 51 46
51 45 40
46 40 35
42 36 31
38 32 28
35 29 25
32 26 23
Zonal Lumen Summary
Zone Lumens % Lamp % Fixture
0° - 30° 1982.1 23.2
30.9
0° - 40° 3413.2 39.9
53.1
0° - 60° 5866.8 68.6
91.4
0° - 90° 6422.1 75.1
100.0
90° - 180° 0.0
0.0
0.0
0° - 180° 6422.1 75.1
100.0
50%
50% 30% 10%
83 83 83
76 74 72
67 64 61
60 56 53
54 49 45
49 44 40
44 39 35
40 35 31
37 31 28
34 28 25
31 26 22
pf
pc
pw
0
1
2
3
4
5
6
7
8
9
10
RCR
RCR
pf
pc
pw
0
1
2
3
4
5
6
7
8
9
10
TEST NO: LTL14541
2PM3N 4 32 32LD
LUMENS PER LAMP: 2850
LAMPS PER LUMINAIRE: 4
TEST NO: LTL14671
2PM3N 3 32 18LD
LUMENS PER LAMP: 2850
LAMPS PER LUMINAIRE: 3
RCR
TEST NO: LTL14496
2PM3N 2 32 12LD
LUMENS PER LAMP: 2850
LAMPS PER LUMINAIRE: 2
Coefficients of Utilization
20%
70%
50% 30% 10%
77 77 77
70 68 66
63 59 56
56 52 48
50 46 42
46 41 37
41 36 33
38 33 29
35 30 26
32 27 24
29 25 21
80%
50% 30% 10%
79 79 79
71 69 67
64 60 57
57 53 49
51 46 42
46 41 37
42 37 33
38 33 29
35 30 26
32 27 24
30 25 22
50%
50% 30% 10%
74 74 74
67 65 64
60 57 55
54 51 48
49 45 42
44 40 37
40 36 32
37 32 29
34 29 26
31 27 23
29 24 21
Zonal Lumen Summary
Zone Lumens % Lamp % Fixture
0° - 30° 2650.0 23.2
35.1
0° - 40° 4348.4 38.1
57.6
0° - 60° 7076.5 62.1
93.7
0° - 90° 7551.8 66.2
100.0
90° - 180° 0.0
0.0
0.0
0° - 180° 7551.8 66.2
100.0
Lithonia Lighting
Sheet #: 2PM3N-2x4
©1997 Acuity Brands Lighting, Inc., Rev. 2/26/09
Fluorescent
One Lithonia Way, Conyers, GA 30012
Phone: 800-858-7763 Fax: 770-929-8789
www.lithonia.com
“Putting Technology in a New Lite.”
LX–SERIES
Aluminum Dome
• Cast Aluminum
Housing & Lid
• Snap-In Ballasts
With Pressure Clips
• Instant On
• Stepped Dimming
Up To 4 Level
• No Color Shift
• Twist On Dome With
Thumb-Screw Safety Lock
• Sensor Capable
• White Ballast Housing –
Standard
Patented &
Patents Pending
Now available in standard “RAL” colors
for an additional charge.
DATA SHEET
LX-Aluminum
Designer Series High-Bay
For style, functionality and energy efficiency, the LX Aluminum
Dome High-Bay from Sportlite provides maximum down-light that is
perfect for warehouses, gymnasiums, ice rinks, manufacturing
plants or any application requiring flexible high-bay style fixtures.
The LX800 with 42 watt compact fluorescent lamps (CFL) supplies
an impressive 25,600 lumens and 85 percent lumen maintenance.
Stylish Effect
Sportlite offers a stylish alternative to standard metal
reflector-type HID fixtures with the new LX800 Aluminum Dome
High-Bay. Featuring an eye-pleasing aluminum ballast housing and
reflector, the LX Series provides very even vertical and horizontal
foot-candles, which are highly desirable for televising sporting
events and providing surface light to more effectively sell products,
The LX Series reduces the glare often associated with standard
HID high-bay fixtures.
Mood Lighting
The LX Series sets the tone for any application, offering a wide
variety of lamp color temperatures to create the desired effect or
match existing lighting. These high-CRI (82-84) lamps produce a
more natural lighting effect. The LX Series provides comfortable
even light, a larger light spread, minimal shadowing and no
stroboscopic effects. With maximum lumen output at 30 degrees,
the LX Aluminum Dome produces and efficient “batwing”
photometric configuration, which creates a very smooth lighting
pattern and a favorable spacing to mounting height ratio.
Smart & Functional
The LX Series offers smart features for simple and safe use. Its
modular construction featuring “AMP” snap lock electrical
connectors and “spring-clip” secured ballasts allows easy
installation and maintenance with minimal tools The “instant on”
feature allows control over pairs of lamps within an individual
luminaire. Choose sensor-controlled, four level stepped dimming
for an efficient and inexpensive way to lower light levels and save
energy without changing the photometrics.
Energy Efficient
The energy saving, compact fluorescent LX800 Designer
High-Bay is a must-have replacement for the high energy
consuming, old standard HID style high-bay fixture. Realize an
average 25 to 40 percent energy savings compared to 400 watt HID
fixtures. Eliminate hot spots and color shifts typical of metal halide
lighting fixtures.
SPORTLITE, INC. Tel: 623.930.0074 Fax: 623.930.0045 601 North 44th Avenue Suite 102 Phoenix, AZ 85043
www.sportlite.com
R04/06
“Putting Technology in a New Lite.”
SPECIFICATIONS
Aluminum Dome
Input Watts: 354 Watts +/- 3%
Luminous Efficacy:
42w
88.6 lm/w @ 277V
Initial Lumens ____
26w ____
32w ____
42w ____
57w ____
60w ____
70w ____
85w 120w
____
per Lamp: 1,800 2,400 3,200 4,300 4,000 5,200 6,000 9,000
Total Initial Lumens: 25,600 W/(8) 42 Watt Lamps
Lumen Maintenance: 85%
Efficiency: 78.6% of rated lumens
Color Temperature: 3,000k, 3,500k, 4,100k
Color Rendering Index: 82 - 84
Lamp Life: UP TO 20,000 hours
Base: GX24q-4 + 2G8
Electronic Ballast:.90BF, PF=99, THD<2%
Weight: 16-18lbs depending on Ballast used
Snap-In Ballasts
with Pressure Clips
Modular
Construction
with “AMP”
Electrical
Connectors
Cast Aluminum
Housing & Lid
High CRI
Lamps
Twist-On Dome
with Safety Lock
Spun Aluminum
Dome
21.38”
543.05mm
B
17.13”
435.10mm
C
9.75”
247.65mm
B
A
A
Suitable for 40ºC Ambient
E
x
y
12.00”
12.00”
304.80mm 304.80mm
21.25”
C
D
539.75mm
D
E
Ordering Information
(Example – LX8-T42-41K-21AL-21DLPG-120-4SL-3PEN-EP160-SC)
Series
Lamp Type
Lamp Color
Dome Type
Lens Type
Voltage
Switching
*
LX8
LX8CC
LX6
LX6CC
LX4
LX4CC
LX3
LX3CC
LX2
LX2CC
T26
T32
T42
T57
PLH60
T70
PLH85
PLH120
27k (26w Only)
30k
35k
41k
21AL
21DLCP
21DLPP
21FLP
21FLPP
120
208
277
347 – (Extra Charge)
1SL
2SL
3SL
4SL
PB2S
PB2DS
LX800 (8 Lamps)
LX800 Custom Color
LX600 (6 Lamps)
LX600 Custom Color
LX400 (4 Lamps)
LX400 Custom Color
LX300 (3 Lamps)
LX300 Custom Color
LX200 (2 Lamps)
LX200 Custom Color
26 Watt
32 Watt
42 Watt
57 Watt
60 Watt
70 Watt (Maximum 6 Lamps)
85 Watt (Maximum 4 Lamps)
120 Watt (Maximum 3 Lamps)
21” Spun Aluminum
21” Drop Clear Poly – Vented
21” Drop Poly Prismatic – Vented
21” Flat Clear Poly
21” Flat Poly Prismatic
*Consult Factory for Lamp Compatibility
DM42-2M7 Dimming Ballast) Single Zone
PB2M PulseBloc (1 to 4 switch legs) 2 to 4 Zone
PB2DM PulseBloc (Dimming – To be used with one
DM42-2M7 Dimming Ballast) 2 to 4 Zone
Mounting Options NOTE 1
Emergency Ballast Options (lm=lumens) NOTE 2
Dimming Ballast Options NOTE 3, 4, 5
Accessories
**
3PEN
H
C
CM
HC
HCM
HCP
HCPL
HCMPL
EP42
EP42SD
Pendant by Others
Male Hook
Single Circuit Cord 6’
Multi-Circuit Cord 6’
Male Hook & Single Circuit Cord 6’
Male Hook & Multi-Circuit Cord 6’
Male Hook, Single Circuit Cord 6’ & Straight Plug
Male Hook, Single Circuit Cord 6’ & Locking Plug
Male Hook, Multi-Circuit Cord 6’ & Locking Plug
Note 1
Plug Not Availble with 4 Switch Legs.
NOTE 6
1 Switch Leg
2 Switch Legs
3 Switch Legs
4 Switch Legs
PulseBloc (1 to 4 switch legs) Single Zone
PulseBloc (Dimming – To be used with one
EP420
EP75C
EP160
EP94
EP30
GTD
Note 2
EX = External Mount
IM = Internal Mount
Consult Factory for EM/Cord/Plug
Compatibility
IOTA I-42B, One Lamp, 32w-650 lm, 42w-750 lm, IM
IOTA ISD-420A, One Lamp, 32W-1050lm, 42w-1300 lm,
57w-1160 lm, 70w-1200 lm, Self-Diagnostic, EX
IOTA I-420A, One Lamp, 32w -1050 lm, 42w-130 0lm,
57w-1160 lm, 70w-1200 lm, EX
Bodine B75C, One Lamp, 32w-600 lm, 42w-800 lm, 57w-1150 lm,
70w-1300 lm, EX
IOTA I-160, Two Lamp 42w- 3000 lm, One Lamp 57w-2700 lm,
One Lamp 70w-2800 lm, EX
Bodine B94C, 750 Lumens, 42w-One Lamp, IM
Bodine B30, Two Lamp, 42w-3500 lm, One Lamp, 42w-3200 lm, EX
Bodine, Generator Transfer Device, IM
Note 4
Note 3
Requires a 2-Wire 0-10 Volt Dimmer
Advance Mark X and Lutron Tu-Wire
Ballasts Require a 2-Wire Wall Dimmer. in addition to the Normal Hot, Neutral
and Ground.
SC
6’ Safety Cable to Ballast Box
21WG Wire Guard
21XWG Wire Guard (For Use with Drop Lens)
FWG Full Wireguard (Covers Entire Reflector)
FU
In-Line Fuse (One Per Switch Leg)
DSW Decorative Shroud – White
DSCC Decorative Shroud – Custom Color
DMC Dual Mounting Crossbar
P16W 16 Cell Parabolic – White
**You must specify the quantity of dimming ballasts required per fixture.
P16S 16 Cell Parabolic – Specular
P16G 16 Cell Parabolic – Gold
2X2CPW 2’X2’ Ceiling Pan – White
2X2CPCC 2’X2’ Ceiling Pan – Custom Color
Note 5
Note 6
Requires one control wire in addition to If specifying PulseBloc consult PulseBloc BBSW Ballast Box Shroud – White
specification guide.
the normal hot, neutral & ground.
BBSCC Ballast Box Shroud – Custom Color
DM42-2M7 Advance, Mark VII, 32/42w- Two Lamps,
57/70w-One Lamp, – NOTE 4
DM42-2MX Advance, Mark X, 32/42w-Two Lamp,
57/70w-One Lamp, – NOTE 3
DM42-2SE Lutron Compact SE, 42w – Two Lamps, – NOTE 5
DM32-2SE Lutron Compact SE, 32w – Two Lamps – NOTE 5
DM32-2TU Lutron, Tu-Wire, 32w – Two Lamps – NOTE 3
SPORTLITE, INC. Tel: 623.930.0074 Fax: 623.930.0045 601 North 44th Avenue Suite 102 Phoenix, AZ 85043
www.sportlite.com
R04/06
Finelite Better Lighting: Series10-default-specifications
Page 1 of 2
Series 10 Specifications
2.9" high, 9.5" wide. Distance from Lock and Level™
Assembly to top of fixture is 3".
1, 2, or 3 lamp cross sections w
T5 lamps contact factory.
"
20 gauge die-formed steel body with 14 gauge die-formed
internal joiner system, plug-together wiring standard. All
components hard tooled to tolerances of 0.005".
Electronic instant start ballast <
Optional Adders: Rapid Start, H
T5, Full Size Battery Backup Un
(controls by others).
#
lamping and photometry
1T8:ep
2T8:ep
3T8:ep
1T8:91w
2T8:91w
3T8:91w
1T5ho:91w
1T5ho:ep
2T5ho:ep
1T8:91w
2T8:91w
3T8:91w
1T5ho:ep
1T8:91w
1T5ho:91w
1T8:91w
2T8:91w
3T8:91w
1T5ho:91w
Flat Endcap (FE) standard, 20 gauge die-formed steel
endcaps, adds 0.1" at each end. Optional: Rounded
Endcap (RE), injection molded sculpted endcap with 0.100"
reveal. No exposed fasteners, holes or knockouts.
Rounded Endcap adds 5.125" at each end.
Standard 91% reflective white (91W) side reflectors.
Optional: Extended Performance specular (EP) side
reflectors.
Standard semi-adjustable aircra
lengths of 12", 15", 18", 21", 24"
connects to fixture with factory i
Assembly? which allows side to
locks it into place. NOTE: Level
above top of fixture.
Fully adjustable aircraft cable (F
lengths up to 150".
$
Open - No uplight optical control. CCO - Controlled Center
Optics, covers center lamp, 100% downlight (center only);
STO - Soft Top Optics, 0.063" perforations cover the top
surface; TDO - Totally Direct Optics, solid top above lamps,
0/100.
A12 - A12 Diffuser lens, acrylic UV stabilized, 0.100" thick;
PS - Perf Shield, white, curved shield with 0.063"
perforations covering the surface; WCB - White Cross
Blade Baffle, white cross blades 3.0" apart; PLV Parabolic Louver, semi-specular louvers 3.0" apart; CUB 1.5" Paracube, semi-specular.
Plated steel cable and hardware
%
18 gauge straight cord. 14 gaug
fixture current exceeds 6 amps.
Feed.
%
Finelite White standard. 185 col
Drylac's RAL color chart for a no
!
Optional Lamp Guard, 063 clear acrylic, UV stabilized;
Optional Dust Cover, clear acrylic. NOTE: Will significantly
impact light level performance.
4', 8', 12' section lengths can be
runs.
&
Fixture weight = 3 lb/ft.
120 or 277 volt prewired. Fixture and electrical components
file://C:\Documents and Settings\lmiller\Desktop\Finelite Better Lighting Series10-default-... 3/25/2009
Finelite Better Lighting: Series10-default-specifications
Page 2 of 2
UL/C-UL listed and fixture will bear UL/C-UL labels.
Optional Adders: 347 volt prewired, dual circuit, emergency
circuits, emergency battery packs.
&
#
Complimentary wall mount avai
©2008 Finelite Inc. All Rights Reserved.
file://C:\Documents and Settings\lmiller\Desktop\Finelite Better Lighting Series10-default-... 3/25/2009