Element C Interiors Interior Construction C1031 Fabricated Toilet Partitions PART 1 - GENERAL 1.01 OVERVIEW A. Includes fabricated toilet partitions and urinal screens. PART 2 - DESIGN CRITERIA 2.01 GENERAL A. Typical toilet partitions shall be ceiling hung, plastic laminate faced with black phenolic resin core. Urinal screens shall be supported from the wall, and be of the same construction as toilet partitions. (Painted steel partitions and screens are used only in special cases, such as for vivariums. Project manager approval is required.) B. All partition and urinal screen hardware, including brackets and fasteners, shall be stainless steel with satin finish. C. All fasteners shall be tamper proof, and spaced at approximately 12-inch o. c. along brackets. D. Provide sight-proof continuous piano hinges at stall doors. The strike side of doors shall be sight–proof, through use of a rabbetted edge at door/pilaster, or other similar detail. E. Brackets for urinal screens, divider panels, and end panels shall extend full length of the panel, thru-bolt to panel, and have double ears for attachment to wall. F. Pilasters shall be attached to the wall using continuous brackets. Brackets shall thru-bolt to pilaster, as well as provide a single ear (oriented to inside) for attachment to wall. G. Partition and urinal screen faces shall be Formica #744-58 Lacewood (matte) HGS plastic laminate, and exposed core edges shall be radiused and polished. Plastic laminate grain shall be oriented vertically. H. Partition panels and urinal screens shall be ½-inch - ¾-inch thick, and doors and pilasters shall be ¾-inch thick, minimum. I. Provide 24-inch wide doors at typical stalls, and 36-inch out-swinging doors at accessible stalls. J. Provide a coat hook/rubber bumper at all doors. K. All hardware and brackets shall be free of sharp edges. The University of Texas MD Anderson Cancer Center ODG100908 FABRICATED TOILET PARTITIONS C1031 1 OF 2 Element C Interiors Interior Construction C1031 Fabricated Toilet Partitions PART 3 - SPECIAL CONTRACT DOCUMENT REQUIREMENTS 3.01 GENERAL A. In addition to incorporating all applicable life safety and building code requirements, include provisions described within this Element in the Project Contract Documents. B. Drawings shall indicate dimensions of each toilet stall and urinal screen, and its relationship to the centerline of the associated plumbing fixture. PART 4 - PRODUCTS 4.01 GENERAL A. For renovation projects, refer to Owner’s Master Construction Specifications. These are available on the Owner’s Design Guidelines website: http://www2.mdanderson.org/depts/cpm/standards/specs.html PART 5 - DOCUMENT REVISION HISTORY Issue Rev. 1 Date Revision Description Reviser 08-14-08 Initial Adoption of Element JC 10-09-08 Clarified where steel partitions are allowed, in 2.01, A. JC Rev. 2 Rev. 3 Rev. 4 Rev. 5 END OF ELEMENT C1031 The University of Texas MD Anderson Cancer Center ODG100908 FABRICATED TOILET PARTITIONS C1031 2 OF 2