METHODOLOGY FOR TRANSMISSION LINE CAPACITY ASSESSEMENT BASED ON PMU DATA Anna Mutule [1], Ervin Grebesh [2], Irina Oleinikova [3], Artjoms Obushevs [4] [1]–[4] Smart Grid Research Centre Institute of Physical Energetics Riga, Latvia amutule@edi.lv [1], ervins.grebess@gmail.com [2], irina.oleinikova@edi.lv [3], a.obusev@gmail.com [4] Abstract— This paper reflects the authors’ experience in conductor thermal part (temperature) and mechanical part (sag and clearance) estimation in real Latvian PS conditions using IEEE, CIGRE, Girshin and classical mechanics methods. Both theoretical and practical results of the research are discussed. Theoretical calculations based on real Phasor Measurement Unit (PMU) measurements of 330 kV line and environmental data collected from meteo-websites have shown that deviation is low in conductor thermal calculation methods. The Dynamic Line Rating (DLR) measurements are improved with the PMU data, which permit accurate line current data with GPS timestamps. The authors have calculated the conditions of conductor thermal dynamics at a step of one second; such accuracy together with environmental data can provide an excess of maximum line capacity without harming the conductor life cycle. Index Terms-- Conductor temperature, dynamic line rating (DLR), line sag, phasor measurement unit (PMU). I. INTRODUCTION The electric power industry worldwide is experiencing the need to push more power through existing assets. This is a result of the ever-growing demand for electric power, and it requires continuous investment in new assets. This is all particularly true for overhead transmission lines, which are the limiting circuit components in most cases, and the most expensive and difficult ones to replace or upgrade. However, the industry is recognising that for almost all cases, existing transmission lines have significant extra power capacity, and there is a growing need to take advantage of that extra capacity. To solve the problem of maximum transmission capacity, it is necessary to obtain sag estimation that could be achieved using a PMU. At the same time, PMU application can help in a situation when the line is being operated near its maximum allowable power. This can be considered true in the case when transmission line operator uses permanent throughput and makes necessary corrections depending on the season. This research was supported by Nordic Energy Research Council funding programme for Sustainable Energy Systems 2050 through the Smart Transmission Grids Operation and Control (STRONg2rid) project (No.79). Phasor measurement unit is a device that uses the global positioning system (GPS) to synchronise wide-area measurements in power systems and to stamp the time of measurements of high precision, i.e., less than 1 microsecond. These measurements are then transmitted over a high-speed broadband network to control centres [2]. The result is a highly detailed and synchronised feed of power system data that provides operators with real-time intelligence allowing them to react more quickly to system disturbances and take actions to avoid a blackout or prevent a disturbance from cascading. Apart from the early detection of equipment failures, system monitoring and operation, the PMU application can provide a much clearer view of the entire transmission system parameters in dynamics, such as technical losses, corona losses, line parameters and transmission capacity. II. BACKGROUND Sag and clearance calculations are a topical issue for Latvian and Estonian PS interconnection. In 1960 these lines were put into operation for 220 kV. In 1962 the lines were reconstructed for 330 kV leaving old pylons. Nowadays this transmission line poses difficulties to the power system operation. There is a problem in sag value especially in warm summer time, when temperature increases to 30 °C. This problem leads to a decrease in maximum power throughput capability to avoid a short circuit possibility. This situation creates unnecessary and unacceptable uncertainties about the safe carrying capacity of individual lines on the transmission networks [1], [11]. Instead, utilising online voltage and current phasor measurements by PMU, transmission line parameters and temperature can be estimated. The approach to resolving the issues of sag and maximum conducted power consists of determining the thermal condition of the conductor measured by means of the methods described below. A solution to the problem of high-voltage lines may be DLR, which considers the line under constantly changing conditions: weather, mechanical and electrical load. This issue has been discussed quite extensively in many countries, from both the theoretical and practical perspectives – monitoring of parameters and the behavior of the line for up to several years [8]-[10]. Results of examining the issue of DLR by other countries demonstrate positive ratings. The ratio of static and dynamic evaluation of the line is depicted in Figure 1. equilibrium. For solving DLR questions dynamic thermal condition is used, which means - at some time t0 line conductor stores some heat value, and can be described in the following equation: Pst = dT = PJ + P S − PC − PR . dt (1) where T is the line conductor temperature, Pst is heat stored in the conductor; PJ is Joule heating; PS is solar heating; PC is convective cooling and PR is radiative cooling. The relationship of energy input, output and the following conductor of line No. 301 are shown in Figure 2. Figure 1. General form of capacity increase by DLR Obtaining spare area by DLR and the output of the maximum allowable capacity of the line will depend on these factors: weather conditions, mechanical characteristics of the conductor as well as pylon height and span length. Further, the appropriate use of dynamic line ratings needs to be included in this review because adjusting a line rating according to changes in ambient conditions may enable the line to carry a larger load while still meeting safety requirements. III. METHODOLOGY FORMULATION The algorithm can be divided into two parts: the first part being thermal, which describes the determination of temperature, and the second one being mechanical, which involves the calculation of sag and ground clearance, as shown in Figure 3. Figure 2. Relationship between coming and going energy in conductor It should be noted that IEEE method for conductor thermal calculation is not exclusive; there are also such methods as CIGRE and Girshin. All of them give pretty similar results. Methods comparison was done by authors in their previous work [1], [4], [5]. To find conductor temperature T, at moment of time t the following values should be known (Figure 3) : current value from PMU data, environmental parameters such as wind speed, wind direction, solar radiated heat flux, ambient temperature as well as constant values, such as solar absorptivity, degrees of latitude etc. A. Transmission Line Temperature Estimation Parameter that mainly characterises sag and clearance variation is line temperature. In this case, if temperature estimation is correct, line sag and clearance estimation will have fewer differences from real line sag and clearance, respectively. For line temperature calculation IEEE std. 738-2006 has been chosen, that describes the standard for calculation of the current-temperature relationship of bare overhead conductors [3]. This method is presented in such a way to solve a current value, based on the known conductor temperature and other parameters. To use this equation oppositely Newton`s method was used to express a conductor temperature value if a current value is known. The IEEE standard describes two possible conditions of thermal rate: steady state and dynamic conditions. Steady state is described by equation in thermal balance, where heat value of conductor at any time period is zero. Dynamic conditions describe the same equation without thermal Figure 3. Transmission line sag estimation graph. B. Transmission Line Sag Estimation For calculation of mechanical part equations from classical mechanics are used, which are applied at the design stage [6]. To find sag value fcal after temperature calculation several steps should be performed (Figure 4.). Figure 5. Sag value at pylons with different height. IV. Figure 4. Mechanical part calculation algorithm. First of all, based on conductor data linear and specific mechanical loads should be defined for different conditions. Based on the load value and considered span length, critical span values should be clarified. Their relation will give initial conditions for tension component σ0, specific load γ0 and temperature t0. Using obtained temperature tcal and initial conditions cubic equation of conductor state can be solved. Finally horizontal tension component for temperature tcal and sag value fcal can be estimated. σ cal γ 2 l2E γ 2l 2 E − max = σ 0 − 0 2 − αE (t cal − t 0 ) 24σ cal 24σ 0 f cal γ ⋅l2 = 1 8 ⋅ σ cal To test the theoretical methods, an experiment has been done in collaboration with the Latvian TSO. For experiment line No.301 Valmiera (LV)-Tartu (EE) was chosen, in span No.1143-1142 on 11 August 2015 between 11.00 am and 12.00 am. The measured parameters and their values are given in Table I. Figure 6 shows thermovisor camera measurement. Several values that were not measured by equipment were taken from the Latvian Meteorological Centre (LMC) station, which is located at the distance above 50 km from experiment location. TABLE I. Parameter (2) (3) Conductor temperature Line span clearance Wind speed where, γmax is maximal specific mechanical load, E is conductor flexibility coefficient, α is linear thermal elongation coefficient and γ1 is weight of conductor. Line sag value fcal describes the middle point of pylon span lowest point when the pylon height is the same. In real line topology scenario it is hard to find two pylons with equal conductor suspension height. CASE STUDY Wind direction Ambient temperature MEASUREMENT VALUES Method/ Equipment Description Value FLIR T640 Thermovision camera 30-34 °C Clearance to ground gear KESTREL 4000 LMC Bases on infrared sensor signal 7.23-7.24 m Pocket weather station 1.5-2.0 m/s Historical data 2.0-2.2 m/s LMC FLIR MR77 Line topology Longitudinal line profile Historical data ~90° Thermovision camera option Provided by TSO and digitized in MATLab model 26.4-26.6 °C In such a case the lowest point of conductor is described by point O (Figure 5.). Here, it should be noted that maximum sag value and sag positioning do not change for such a situation [7]. To find y, the length to point O, it is necessary to know: pylon height A and B difference - ∆h, the distance between line sag fcal and the lowest point at y-axis O - yc, correction by x-axis for the clearance lowest point xc. The mentioned parts can be found as follows: σ cal ∆h 2 , 2 ⋅ y1 l σ ⋅ ∆h xc = cal . γ1 ⋅l yc = (4) (5) Figure 6. Thermovision camera measurement. - A. Thermal part PMU current flow for experiment period is shown in Figure 7. Also there are presented conductor temperature results, based on IEEE std. 738-2006 calculated based on dynamic conditions. Due to frequent PMU measurements and relatively smooth changes in thermodynamic conditions PMU data were sieved per 1/60/600 seconds timestamps respectively. Based on the results shown in Figure 7, the most optimal timestamp size is 1 second, where PMU data are reduced 50 times and thermodynamic accuracy does not lost in relatively fast current change. Conductor temperature value calculated with IEEE standard varies from thermovision camera measurements from 0 to 3 °C for all experiment time. Theoretical results are lower than practical measurements. The reason for such difference could be a systematic error when IEEE calculation will give lesser temperature, several coefficients which value could be predetermined wrong - absorptivity and emissivity coefficients, such parameter as wind was not provided in dynamics change for experiment location but was set as constant value for this hour. ground is graphically illustrated in Figure 8. The difference between the theoretical and practical calculations is approximately 20-30 cm, which can be considered a permissible error taking into account the possible error of the device and possible changes in the ground topology [6], [7]. TABLE II. Symol Unit MECHANICAL PARAMETERS DESCRIPTION Description Value Pylon PVS-330A Pylon PVS-330A 70.9 72.4 HA,B m Conductor suspension height on sea level l m m Span length Pylon height difference 326.9 1.5 Weight of conductor 0.0034 Linear thermal elongation 19.85 ⋅ 10 −6 ∆h γ1 α tcal σcal daN mm 2 1 °C °C daN mm 2 fcal m ccal_real m Conductor temperature by IEEE Horizontal tension component Sag value Clearance to ground value 33 5.66 8.01 7.46 Despite theoretical and practical part difference in few degrees such results for the first DLR experience in Latvia give the possibility of considering IEEE std. 738-2006 as reliable for further experiments, with all parameter dynamical monitoring and for long-term DLR monitoring creation [3]. Figure 7. Conductor temperature by IEEE and current value from PMU. B. Mechanical part To calculate the mechanical part of line No. 301, the longitudinal line topology provided by Latvian TSO has been digitised. The need to digitise the line is determined by several reasons: graphical observability of the results, including the ground profile in the mechanical calculation, which in turn is tied to the sea level, as well as the ability to integrate data into other calculations or into the real-time mode. Data on mechanical parameters and pylons used in the experiment are aggregated in Table II. Due to the fact that changes in the conductor temperature are not big, a constant value has been chosen. The situation occurring during the experiment between the pylons and the minimum clearance to Figure 8. a) Whole line topology, b) Experiment pylons and situation model for calculated temperature V. A. DISCUSSION Thermal part Although IEEE Standard 738-2006 can be considered a fairly accurate method for calculating the conductor temperature proved also by other studies, to monitor the line in the continuous mode it is necessary to consider the formation of a neural network, as already performed in. Annual monitoring of DLR provides results on a particular terrain and weather conditions that can be more precise than using common methods [10]. Mechanical part Based on the result shown in Figure 8, it is possible to distinguish a few common features associated with calculations of a particular line and mechanics in general: line clearance to ground value. Based on this restriction optimal conductor temperatures are in the range of 35 – 40°C. B. 1) Provided that the ground topology is taken into account in the calculation of clearance to the ground, it can be stated that the real minimum clearance to the ground will be less than the one in which the ground topology is a straight line. In some cases, a strong deviation from the axis Ox is possible. VI. CONCLUSIONS Taking into account clearance results for line No.301 it can be concluded that line conductor thermal restriction should be set at 35-40°C value to avoid a short circuit possibility, while such type of conductor theoretically can withstand 70°C. Despite these limitations, the use of DLR is possible for such conditions and becomes even more topical, namely: the reduction in the line conductivity in the summer and maximum increase in the line conductivity demonstrated by thermodynamic calculations based on the DLR data. As the next step, in order to refuse the use of thermal standards, it is also necessary to decrease mistake probability based on the predetermined coefficients and in order to clarify results for local conditions the machine learning model should be used. Power companies can use these methodologies to maximise power throughput of existing assets, defer capital expenditures, and simultaneously increase safe and reliable operation of their assets. ACKNOWLEDGEMENT Figure 9. Clearance to ground deviation. As can been seen from Figure 9, clearance to ground value with correction by including ground topology can reach difference about 0.5 m or more that is significant and should be taken into account. 2) Due to the feature of line No. 301, whose pylons were originally supposed to be used for 220kV, a situation occurs when clearance to ground is lower than it is permitted by the Latvian standards on power line transmission operation [11]. Figure 10. Clearance values for different temperature values. As can been seen from Figure 10, clearance to ground values for 70°C exceeds Latvian standards for transmission Authors would like to thank the Latvian Transmission System Operator “Augstsprieguma Tīkls” for the organization and great assistance in conducting experimental part of this research, although they may not agree with all of the interpretations provided in this paper. REFERENCES [1] I. Oleinikova, A. Mutule, E. Grebesh, A. Lvovs, "Line parameter estimation based on PMU application in the power grid," International Conference on Power Engineering, Energy and Electrical Drives, 2015September, art. no. 7266360, pp. 453-457, 2015. [2] D. Kosterev, L. Carter and S. Lissitt, "The Pulse of the Grid," Transmission & Distribution, January ’14, p 44-48. [3] Standard for Calculation the Current-Temperature Relationship of Bare Overhead Conductors, IEEE Std. 738-2006, Jan. 2007. [4] Thermal Behaviour of Overhead Conductors, CIGRE, Technical Brochure 207, Aug. 2007. [5] S. S. Girshin, V. N. Goryunov, A. Y. Bigun, "Calculation of unsteady temperature regimes of overhead power lines, taking into account the nonlinearity of heat transfer processes," Modern Problems of Science and Education, No.5 2014 [Translated from Russian] [6] A.Engelis, R.Arajs, "High Voltage Electrical Lines," Riga, 2004. [7] K. Krykov, B. Novogorodcev, "Design and Mechanical Calculation of Transmission Lines ," St.Petersburg: Energy, 1979 [Translated from russian]. [8] A. Philips, B. Clairmont, D.Childs, D. Reuger, D. Douglass, J. Bell, D. Birrell, "Evaluation of Instrumentation and Dynamic Thermal Ratings for Overhead Lines," EPRI Tech. Report, Oct. 2013. [9] Guide for Selection of Weather Parameters for Bare Overhead Conductor Ratings, CIGRE, Technical Brochure 299, Aug. 2006. [10] D. Morrow, J. Fu, S. Abdelkader, "Experimentally validated partial least squares model for dynamic line rating," IET Renew. Power Gener., 2014, Vol. 8. pp 260-268. [11] Transmission power line No.301 technical documentation, Sep. 1969, Project No. 885-25, Latvian TSO.