S-HJT/3/3W c/w LED/40/NL - No Lens (Wide Angle) S-HJT/3/3W c/w LED/40/OA - Open Area Lens S-HJT/3/3W c/w LED/40/CO - Corridor Lens The kit is a standalone unit designed to provide maintained or non-maintained, three hour duration, emergency lighting using a variety of ceiling mounting 3W LED 700mA Minispot units. The units use a 3.6V 4.0 Ah Nickel Cadmium (NiCd) battery to provide a full 700mA output to the LED Emitter in emergency conditions. Installation Instructions 1. Cut a 43mm diameter hole in the ceiling tile. 2. Connect the LED Bezel to the main assembly via the 4 way connector. 3. At the supply side of the 3 pole mains connector connect the Unswitched (Battery Charging) 240V supply to the 1-L1 Unswitched Live terminal. Connect the Neutral supply to the 2-N Neutral terminal. The unit is class II double insulated and no earth is required. 4. If maintained operation is required connect the Switched Lighting 240V supply to the 3-L Switched Live terminal. 5. Connect both halves of 3 pole mains connector together. 6. Only connect the battery when the Un-switched supply is fully assured. Even though these units are protected with a Deep Discharge Protection Circuit, the Batteries can be damaged by being left in an uncharged state for prolonged periods. Ensure correct polarity. 7. When the supply is present and the battery connected, check that the green LED indicator is illuminated showing that the supply is healthy and the batteries are charging. 8. Pass the whole assembly through the 43mm aperture and clip the LED housing into the ceiling. Technical Information 220-240 Volts AC 50/60 Hz 5.8 Watts – 47mA λ = 0.50 2.7 Watts – 26mA λ = 0.42 3 Hours 3.6V 4Ah Nickel Cadmium 200mA 24 Hours 100% 4V DC 1.0 Amps 70°C Module / 55°C Battery 3 Watts 700mA 43mm 110mm Module 150g/Battery 400g Input Voltage Power Rating – Maintained Power Rating – Non Maintained Emergency Duration Battery Type Charger Recharge Time Ballast Lumen Output Maximum Output Voltage Battery Discharge Current Tc Max Output Load for LED Output Current for LED Ceiling Cut Out Minimum Void Weight No Lens (Wide Angle) Open Area Lens Corridor Lens Colour Cool White Cool White Cool White Temperature 6000K 6000K 6000K Emergency Lumens 194 207 197 Important It is recommended that the unit is installed by a competent person ensuring the installation complies with the necessary standards. Liteplan accept no responsibility for injury, damage or loss, which may arise as a result of incorrect installation, operation or maintenance. The conversion requires an Un-switched supply for charging the battery. ISOLATE THE MAINS SUPPLY AND DISCONNECT THE BATTERY BEFORE INSTALLATION OR MAINTENANCE. Tel +44 (0) 1708 372 223 Issue 1504 www.liteplan.com Fax +44 (0) 1708 371 345 Liteplan reserve the right to change colour, price or specification Page 1 of 2 S-HJT/3/3W c/w LED/40/NL - No Lens (Wide Angle) S-HJT/3/3W c/w LED/40/OA - Open Area Lens S-HJT/3/3W c/w LED/40/CO - Corridor Lens Connect mains supply to 3 way plug 1-L1= Unswitched Live 2-N = Neutral 3-L = Switched Live 1-L1 2-N 3-L Unsw Neutral Switch Live Live 230/240V AC Input 3 Cell 4Ah battery Emergency Module XXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXX XXXXXXXXXXXXXX 2 pole Battery connector 4 pole Low Voltage Plug 3 Watt LED Emitter Please refer to separate data sheets for more information on the heads. Testing/Commissioning Ensure the Load is connected. Connect the battery. Switch on the Unswitched Supply - Check the Charge LED illuminates. Switch off the Unswitched Supply - Check the Charge LED extinguishes and the load LED illuminates at a reduced output. Enter the commissioning date on the Battery Pack. Switch on the Unswitched Supply Luminaire Ref/Location In Case of difficulty, contact the Installation Engineers:- _________________________ _____________________________ Full Recharge Time 24 Hours Tel: __________________ Duration 3 Hours Lamp Type - LED ROUTINE TEST RECORD Year 1 Monthly Test Signed Date Year 2 Signed Date Year 3 Signed Date Year 4 Signed Date Year 5 Signed Date Functional Functional Functional Functional Functional Functional Functional Functional Functional Functional Functional Three Hour Tel +44 (0) 1708 372 223 Issue 1504 www.liteplan.com Fax +44 (0) 1708 371 345 Liteplan reserve the right to change colour, price or specification Page 2 of 2