epc-1-l series

advertisement
UL924 LISTED
TYPE
EPC-1-L SERIES
CATALOG #
Emergency Transfer Switch
for Generator Supplies Power to
Switched Lighting Fixtures
NOTES
FEATURES
SPECIFICATIONS
Housing
•Thermoplastic UL94-5VA suitable for plenum installations
•Compatible with LED, fluorescent and incandescent lamp types including
standard, energy-saving, and electronic ac drivers and ballasts1, 2
Mounting
•Wall and ceiling mount
Lamp Types
•During utility power interruption, automatically connects generator or inverter
circuit to emergency fixture and bypasses switching control to full light output
for duration of inverter or generator supply
Lumen output
•Allows switching control of emergency fixtures during normal operation
•Allows auxiliary generator power on a switched lighting fixture
Power Requirements
•Dual Voltage 120/277V 60hz
Approvals
•Meets or exceeds all National Electrical Code and Life Safety Code Emergency
Lighting Requirements
Warranty (subject to proper installation and maintenance)
•Unit has a three year warranty
The Lightalarms® EPC-1-L Emergency Transfer Switch allows the use of
auxiliary generator power on a switched fixture in power failure situations. The
EPC-1-L senses the loss of normal AC power and switches the AC ballast to the
auxiliary generator supply. The EPC-1-L will operate the lamps at full light output
for as long as the generator is able, and will work in conjunction with any lamp
type and fixture on the generator circuit. Dimming ballasts require one EPC-1-L
for each hot lead. Load dimming required one dimmer for the regular load and
another one for time emergency load.
1
2
Electrical Specifications:
•Model EPC-1-L-120/277V
•120V or 277V Sensing Input
•120V or 277V Load
•1800W Incandescent Load Rating at 120V
•1500W Incandescent Load Rating at 277V
•N.C. Contact
•UL924 Listed
•20 Amp Ballast Load Rating
Excluding LED’s
hen using EPC-1 to control more than 10 emergency ballasts with a high corrective
W
power factor capacitor, consult factory for more information regarding inrush currents.
Mechanical Specifications:
•Mounts in 4-11/16” Junction Box with single gang plaster ring
•UL94-5VA Rating
•Shipping Weight: 8 oz
•Temperature: 32˚F - 140˚F (0˚C - 60˚C) | Color : White
•Flush Mounted Size: 4-3/4” x 2-3/4” x 1/4”
•Body Size: 2-7/8” x 1-3/4” x 1-3/4”
DIMENSIONS
Dimensions are approximate and subject to change.
EPC-1-L Flush Mount Ceiling Installation
2” [5.08cm]
2”
Emergency Operation
The EPC-1-L will operate any lamp type in the designated fixture for the
duration of the generator supply
2” [5.08cm]
2”
1/2” Single Gang
Plaster Ring
2-7/8”
2-7/8”
[5.08cm]
1-3/4”
[2.54cm]
1-3/4”
Initial Illumination
The EPC-1-L will operate the designated lamp at full light output
Weight
8 oz
Approval
UL924 Listed
Plastic is UL94-5VA flame rated
and can be mounted above the
suspended ceiling.
Included in the
product package
UL
®
UL924 LISTED
WIRING DIAGRAMS
20A
#1 BLACK
#5 BLUE
EMERGENCY HOT
120V
20A
REGULAR HOT
#2 ORANGE
EMERGENCY
PANEL OR
INVERTER
#6 YELLOW
EMERGENCY
POWER
TEST
Emergency Light
#7 WHITE/BLUE
SWITCH
UTILITY
POWER
277V
*
#3 RED
#4 WHITE
EMERGENCY NEUTRAL
REGULAR
PANEL
Regular Light (optional)
REGULAR NEUTRAL
Note: Emergency Light is also called
N/E or Normal/Emergency Light
*
Relay Panel, Power Pack, Sensor, or other (optional)
NOTE: Regular room lighting load does not affect EPC-1-L current rating. Room switch is only used to control
EPC-1-E 10 mA relay current coil, and regular lighting load. Regular line HOT connected to breaker and
EPC-1-L is only drawing milli amps to sense if normal power is available.
www.lightalarms.com
127
Download