(EcoCT) Current Transformer
(
Details
The current transformer measures the electrical load in any single phase cable and transmits the values over any range of time period starting at
1 Second intervals.
The device can be configured to output the wireless packets at different intervals. The unit can work from 0.4Amp up to 100Amp.
The device requires NO electrical live installation and is clipped directly around the protected core allowing retrofit applications to be undertaken whilst the system is active and no down time realised.
Used in conjunction with the Eco Smart Appliance manager (Eco-SAM) total power usage can be accurately monitored and load switched over the enocean wireless network.
Eco-Sphere Integration.
The Enocean enabled gateway (Eco-WEG) can be used in conjunction with the Eco-CT to provide
Ethernet connectivity for all enocean enabled devices and by running the Eco-Sphere energy manager dashboard the data can be used in a soft virtual metering application.
No interruption to electrical supply
Split core Application
Operating Range 1A—100A
Inductively powered, No batteries
Enocean Learn button
Compliant with Enocean Standards
Utilises proven sensing technology
3 Clayton Park
Clayton Wood Rise
Leeds LS16 6RF
United Kingdom
(EcoCT)
Current Transformer
Installation
Installation is simple smart and easy for the CT. The locking mechanism on the clamp ensures the device is safe and secure when applied. Simply clip the CT around any single core power cable to start the energy generation. Once the energy has been incorporated the CT will start to harness the power and start the broadcasting of the wireless packets.
Configuring the device
To configure the device you will require an Enocean enabled receiver (See EcoWEG —
UN2) Data sheets for Ecologix recommended receivers for this device. Once the receiver is ready press the learn button on the device — this will enable the learn LED and send the learn telegram to the receiver. Once this signal has been acknowledged and bound to the receiver the unit is ready. The EcoCT will continue to process the
Energy data in the configured format whilst ever there is energy flowing through the device.
Ecologix Controls provides a range of EnOcean products that sense and control all major aspects of light industrial and domestic installation. All our product are fully compliant with all EnOcean device for over 150 worldwide manufacturers. We can either provide individual sensors or complete solutions using our own and other vendors sensor, control products.
EnOcean protocol operates at 868MHz or 315MHz in North America and the wireless range is generally up to 30 meters indoors but this is dependent on the buildings construction.
(EcoCT)
Current Transformer
Electrical Data
Range 1-100Amp
Voltage Universal
Frequency 50 / 60Hz
Response time <20 Cycles
Physical
Size 30mm x 55mm x 12mm
Casing Materials ABS
Antennae Whip Internal
EnOcean Protocol
Sample Rate less than 3Amp 30 Seconds
Sample rate greater than 3Amp 1 Second
Frequency 868MHz or 315MHz
Telegram 4BS
Learn Mode Entered on button press
Telegram Description
Type 1 Learn Sent on depress of learn button
Type 2 Current Value, 16 bit
Learn Telegram Electric Current Telegram
Sensor Data
MSB LSB Not Used
--
Type
0xF9
Data Byte 3 Data Byte 0
Current (AMPS) = [Sensor Data] / 7
Not Used Not Used Not Used
-- -- --
Type
0x08
Data Byte 3 Data Byte 0
Transmitted on learn button depress.
Learn LED Indicates telegram