Guide to Hazardous Locations Explosive Dust Atmospheres Ex Marking Protection Concepts Type of Protection Code Market US (NEC 500) and CA (CEC Section 18) ® Type of protection (not used in CA) Ex Ex Ex CA EU IEC (DIP) US CA US CA US IEC US CA EU IEC US CA EU IEC US CA EU IEC US CA US CA EU IEC US IEC US CA EU IEC US IEC US CA EU IEC US CA US CA US CA US EU IEC US CA US CA EU IEC US EU IEC US CA EU IEC US EU IEC EU IEC US CA Permitted Class Dust-Ignitionproof for Class II, Division 1, Groups E, F, G T5 Permitted Division (optional except for Division 2) Permitted Class AEx US CA US CA US General Requirements Temperature Class (T5 and T6 optional) Dust-Ignitionproof Permitted Group Dust-Protected Ambient temperature ranges other than standard (-25°C ≤ Ta ≤ +40°C) must be marked. Protection by Enclosure AEx tD Ex tD AEx ta Ex ta Ex ta Ex ta AEx tb Ex tb Ex tb Ex tb AEx tc Ex tc Ex tc Ex tc Fiber + Flying Protection (DIP) US (NEC® 506 per 61241) American National Standard Temperature Classification Zone 21 AEx tD T120°C Permitted Zone Type of Protection Ambient temperature ranges other than standard (-20°C ≤ Ta ≤ +40°C) must be marked. US (NEC® 506 per 60079) American National Standard Temperature Class Zone 21, AEx tb IIIC T120°C Permitted Zone Encapsulation Equipment Group Type of Protection Ambient temperature ranges other than standard (-20°C ≤ Ta ≤ +40°C) must be marked. IEC (61241) Test Protocol & Intended Zone of Installation (only used for tD) Max Surface Temperature Ex tD A21 T120°C IP66 Type of Protection Explosion Protected Ingress Protection Ambient temperature ranges other than standard (-20°C ≤ Ta ≤ +40°C) must be marked. Pressurization EU and IEC (per 60079) Equipment Group Temperature Class Ex tb IIIC T120°C Db Type of Protection Equipment Protection Level Intrinsic Safety Ambient temperature ranges other than standard (-20°C ≤ Ta ≤ +40°C) must be marked. EU (Directive 94/9/EC) ATEX CE Conformity Marking Explosion Protection Marking Category (including “D” for dusts) 1725 II 2 D . Equipment Group Identification Number of Notified Body Involved in Production Control Stage EPL/Category Definition Dust atmospheres, “very high” level of protection (NI) AEx ma Ex ma Ex ma Ex ma AEx maD Ex maD AEx mb Ex mb Ex mb Ex mb AEx mbD Ex mbD AEx mc Ex mc Ex mc Ex mc (PX) (PX) (PY) (PY) (PZ) (PZ) AEx pD Ex pD Ex pD (I.S.) (I.S.) AEx ia Ex ia Ex ia Ex ia AEx iaD Ex iaD Ex iaD AEx ib Ex ib Ex ib Ex ib AEx ibD Ex ibD Ex ibD Ex ic Ex ic (I.S.) (I.S.) Application Class II, Division 1 & 2 Class II, Division 1 & 2 Class III, Division 1 & 2 Class III, Division 1 & 2 Zone 20, 21, & 22 Class II/III Category 1D, 2D, & 3D Zone 20, 21, 22 EPL Da, Db, & Dc Class II, Division 1 Class II, Division 1 Class II, Division 2 Class II, Division 2 Zone 21 EPL Db Zone 20 Class II/III, Division 1+ Category 1D EPL Da Zone 21 Class II/III, Division 1+ Category 2D EPL Db Zone 22 Class II/III, Division 2+ Category 3D EPL Dc Class III, Division 1 & 2 Class III, Division 1 & 2 Zone 20 Class II/III, Division 1+ Category 1D EPL Da Zone 20 EPL Da Zone 21 Class II/III, Division 1+ Category 2D EPL Db Zone 21 EPL Db Zone 21 Class II/III, Division 2+ Category 2D EPL Dc Class II, Division 1 Class II, Division 1 Class II, Division 1 Class II, Division 1 Class II, Division 2 Class II, Division 2 Zone 21 Category 2D EPL Db Class II, Division 1 Class II, Division 1 Zone 20 Class II/III, Division 1+ Category 1D EPL Da Zone 20 Category 1D EPL Da Zone 21 Class II/III, Division 1+ Category 2D EPL Db Zone 21 Category 2D EPL Db Category 3D EPL Dc Class III, Division 1 Class III, Division 1 Standard FM 3600 CSA C22.2 No. 0 FM 3600 CSA C22.2 No. 0 ISA 61241-0 or ISA 60079-0 CSA C22.2 No. 60079-0 EN 60079-0 IEC 61241-0 or IEC 60079-0 FM 3616 CSA C22.2 No. 25 FM 3611 CSA C22.2 No. 25 ISA 61241-1 IEC 61241-1 ISA 60079-31 CSA C22.2 No. 60079-31 EN 60079-31 IEC 60079-31 ISA 60079-31 CSA C22.2 No. 60079-31 EN 60079-31 IEC 60079-31 ISA 60079-31 CSA C22.2 No. 60079-31 EN 60079-31 IEC 60079-31 FM 3611 CSA C22.1 ISA 61241-18 CSA C22.2 No. 60079-18 EN 60079-18 IEC 60079-18 ISA 61241-18 IEC 61241-18 ISA 60079-18 CSA C22.2 No. 60079-18 EN 60079-18 IEC 60079-18 ISA 61241-18 IEC 61241-18 ISA 60079-18 CSA C22.2 No. 60079-18 EN 60079-18 IEC 60079-18 FM 3620 (NFPA 496) NFPA 496 FM 3620 (NFPA 496) NFPA 496 FM 3620 (NFPA 496) NFPA 496 ISA 61241-2 EN 61241-4 IEC 61241-4 FM 3610 CSA C22.2 No. 157 ISA 60079-11 CSA C22.2 No. 60079-11 EN 60079-11 IEC 60079-11 ISA 61241-11 EN 61241-11 IEC 61241-11 ISA 60079-11 CSA C22.2 No. 60079-11 EN 60079-11 IEC 0079-11 ISA 61241-11 EN 61241-11 IEC 61241-11 EN 60079-11 IEC 60079-11 FM 3610 CSA C22.2 No. 157 Protection Principle Equipment Grouping EU (60079) US (NEC 506 Typical material Metal dusts Carbonaceous dusts Non-conductive dusts Fibers and flyings Dust atmospheres, “enhanced” level of protection Dc III 2D II 3D 21 Keep combustible dust out In the United Kingdom: 1 Windsor Dials, Windsor, Berkshire SL4 1RS Phone: +44 (0)1753 750 476 Fax: +44 (0)1753 868 700 E-mail: europe@fmapprovals.com P08298 © 2012 FM Approvals (Rev. 11/2012) All rights reserved. www.fmapprovals.com N/A D Class II, Group E IIIB D D Class II, Group F IIIB D D Class II, Group G IIIA D D Class III IIIC US NEC 500 Class II or III 450°C 300°C 280°C 260°C 230°C 215°C 200°C 180°C 165°C 160°C 135°C 120°C 100°C 85°C No temperture marking For Class II, the temperature class is determined with a maximum dust layer* on the equipment. For installation, that temperature class must not be greater than the dust layer or dust cloud ignition temperature. For organic dusts that may dehydrate or carbonize, temperature classes greater than “T3B” (165°C) are not permitted. Not Recognized For Class III, the temperature is determined with a maximum dust layer* on the equipment. The temperature must not be greater 120°C for equipment that can be overloaded and 165°C for equipment not subject to overloading. For Class II or III, the temperature is determined with a maximum dust layer* on the equipment. The temperature must not be greater 120°C for equipment that can be overloaded and 165°C for equipment not subject to overloading. Marking US NEC 506 EU/IEC Temperature is determined with no dust layer on the equipment. Temperature is determined For installations with layers with a maximum dust layer* up to 5mm thick, that temon the equipment. perature must be at least 75K below the dust layer ignition For installation, that temperatemperature and no more 2/3 ture must not be greater than the of the dust cloud ignition dust layer or dust cloud ignition temperature. For installations temperature. with layers up to 50mm thick, IEC/EN 61241-14 provides information on reduction of temperature. T___°C Temperature class in degrees Celsius preceded by a “T” e.g. T120°C Limit energy of sparks and surface temperature CA CEC Sect 18 Class II or III TL ___°C Temperature class in degrees Celsius preceded by a “TL” with a dust layer of “L” where “L” is the layer depth in mm e.g. T500120°C Temperature is determined with specified layer depth, (> 50 mm) on all sides of the equipment. That temperature must be at least 75K below the dust layer ignition temperature and no more 2/3 of the dust cloud ignition temperature. Not recognized * A maximum dust layer is a layer or blanket of wheat flour, corn flour, or grain dust that results from the equipment being covered with dust until no more will stay on the equipment. Ingress Protection (IP) Codes First characteristic Numeral Second characteristic Numeral Protection against solid bodies Protection against liquid 0 1 2 No protection No protection Objects greater than 50mm Vertical (90˚) dripping water Objects greater than 12mm 70˚ to 90˚ dripping water 3 4 5 6 7 8 Objects greater than 2.5mm Sprayed water Objects greater than 1mm Splashed water Dust-protected Water jets Dust-tight Heavy seas Effects of immersion Indefinite immersion + The Canadian Electrical Code (through 2012) does not recognize Zone 20, 21, or 22. Therefore, in addition to the Type of Protection Code, the Class, Division and Group of the application is also marked. Approximate U.S. enclosure type equivalent to IPXX Type FM Approvals is your global conformity assessment solution Recognized product certification marks Market FM Approvals 1151 Boston-Providence Turnpike, Norwood, MA 02062-9102 Phone: +1 (1)781 255 4851 Fax: +1 (1)781 762 9375 E-mail: information@fmapprovals.com T1 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6 22 Level of protection assigned to equipment based on its likelihood of becoming a source of ignition US (NEC 500) CA (CEC Section 18) per 61241) Marking Da Db IEC (61241) IEC (60079) US (NEC 506 per 60079) Temperature Note 2: For associated intrinsically safe apparatus not suitable for installation in a hazardous location, both the symbol “Ex” or “AEx” and the symbol for the type of protection “iaD” “ibD”, “ia”, or “ib” are enclosed within the same square brackets, e.g. [AEx iaD] or [AEx ia] IIIC; in this case, a temperature class is not included. Dust atmospheres, “high” level of protection Combustible Dust Present Abnormally Zone 22 Zone 22 Division 2 Division 2 61241 did not differentiate between different materials, but referred to all with a “D” suffix on the Type of Protection. Note 1: For associated intrinsically safe apparatus suitable for installation in a hazardous location, the symbol for the type of protection “iaD”, “ibD”, “ia”, or “ib” are enclosed within square brackets, e.g. AEx tb [ia] IIIC T135 °C or AEx tD [iaD] T135°C. 20 Combustible Dust Present Dust Present Continuously Intermittently Zone 20 Zone 21 IEC / EU Zone 20 Zone 21 US NEC 500 US NEC 506 Division 1 Division 1 CA CEC Section 18 US area classification per ANSI/NFPA 70 National Electrical Code® (NEC®) Article 500 or Article 506 CA area classification per CSA C22.1 Canadian Electrical Code (CEC) Section 18 EU area classification per EN 60079-10-2 or EN 61241-10 IEC area classification per IEC 60079-10-2 or IEC 61241-10 Typical Zone IEC EU (ATEX) of Application EPL Group Category Group 1D Area Classification Combustible US Canada C C C US US EU (ATEX) FM Approvals can also issue IECEx Test Reports, Quality Assessment Reports and Certificates of Conformity. IP Type IP Type IP 1 10 3S 54 6 and 6P 67 2 11 4 and 4X 55 12 and 12K 52 3 54 5 52 13 54 3R 14 Acronyms ATEX Atmosphère explosible IEC International Electrotechnical Commission CA Canada I.S. Intrinsic Safety CEC Canadian Electrical Code (CSA C22.1) NFPA National Fire Protection Association EPL Equipment Protection Level NEC National Electrical Code (NFPA 70) EU European Union US United States of America