U-MH and U-MHT Series

advertisement

U-MH and U-MHT Series

Models U-MH and U-MHT- Horns and Horn Strobes

• The Adapter feature offers four field selectable candela strobe values – 15/75, 30/75, 75 or 110

• Strobe only operates in either sync or non-sync modes

• Steady-tone or temporal horn (92 dB @ 10 ft.

typical) with 15 mA horn current

• Single gang and universal mount configurations

• UL 1971 & UL 464 listed,

ULC, CSFM and NYMEA

• UL 1971 listed for both wall and ceiling mount

• ADA/NFPA/ANSI compliant

• Screw terminals accept 12 awg wire

• Strobe synchronization requires the Dual Sync

Control Module or PAD 3.

• Made in U.S.A., ISO 9001 quality crafted

Description

All models of the U-MH series & U-MHT Series horns and horn/strobes provide a continuous or coded horn signal, depending on the pattern of the voltage applied.

Additionally models U-MHT-1G, U-MHT-1G-W, U-MHT, U-

MHT-W and U-MHT-MCS, U-MHT-MCS-W provide a field selectable temporal tone.

The Adapter feature offers four field selectable candela settings – 15/75, 30/75, 75 or 110

Detail – Adapter selector switch

Models U-MH-1G, U-MH-1G-W & U-MHT-1G, U-MHT-1G-

W mount on a single gang box while the U-MH, U-MH-

W, U-MHT, U-MHT-W, U-MH-MCS, U-MH-MCS-W &

U-MHT-MCS, U-MHT-MCS-W have a universal mounting plate to mount on a single gang, double gang or 4" square back box.

Siemens Fire Safety notification devices are designed with the installer in mind. They are constructed with all of the electronics inside the housing and not in the box. This design helps eliminate possible ground faults from crowded electrical boxes.

The strobe construction consists of a Xenon flashtube with solid state circuitry for maximum reliability and efficiency. The full range of strobes have a rounded dome shape made of clear Polycarbonate.

Strobe synchronization requires the Dual Sync Control

Module or PAD-3.

CATALOG NUMBER

Replaces Catalog Sheet Number 2543

2552

Engineering Specifications

The audible/visual notification appliances shall be

Siemens Fire Safety Series U-MH-MCS, U-MH-MCS-W or U-MHT-MCS, U-MHT-MCS-W Selectable Candela

Strobe - Mini-Horns, or approved equal. The audible appliances shall be Siemens Fire Safety Series

U-MH-1G, U-MH-1G-W, U-MH, U-MH-W, U-MHT-1G,

UMHT-1G-W, or U-MHT, U-MHT-W Mini-Horns, or approved equal. The Series U-MH-MCS, U-MH-MCS-W and U-MHT-MCS, U-MHT-MCS-W visual segment shall be the Adapter Selectable Candela Strobe and shall be listed to UL1971 (Standard for Safety Signaling Devices for the Hearing Impaired). The Series U-MH-MCS,

U-MH-MCS-W, U-MHT-MCS, U-MHT-MCS-W, U-MH-1G,

U-MH-1G-W, U-MH, U-MH-W, U-MHT-1G, U-MHT-1G-W, and U-MHT, U-MHT-W audibles shall be UL listed under

Standard 464 (Fire Protective Signaling). The appliances shall be listed for indoor applications and shall be ADA/

NFPA/ANSI compliant.

The strobe segment of the Series U-MH-MCS,

U-MH-MCS-W and U-MHT-MCS, U-MHT-MCS-W shall produce a flash rate of one (1) flash per second over the

Operating Voltage Range Limits. The strobe shall consist of a xenon flash tube enclosed in a rugged clear polycarbonate lens. The strobe shall be of a low current design, and shall provide a minimum of four (4) field selectable strobe intensity settings, 15/75, 30/75, 75, and 110candela. All settings shall be UL1971 listed for both wall and ceiling mount applications. The selector switch shall be tamper resistant. It shall not be necessary to remove the appliance from the mounting surface to select the strobe intensity. When strobe synchronization is required, the Strobe shall be compatible with the Siemens Fire

Safety 5406 Sync Module, or other source of

Siemens Fire Safety Sync Protocol, and shall not drift out of synchronization.

The Series U-MH-MCS, U-MH-MCS-W audible segment, and the Series U-MH-1G, U-MH-1G-W and U-MH,

U-MH-W audibles, shall provide a continuous or coded tone signal, depending upon the pattern of the voltage applied. In addition, the Series U-MHT-MCS, U-MHT-

MCS-W audible segment, and the Series U-MHT-1G,

U-MHT-1G-W and U-MHT, U-MHT-W audibles shall also provide a field selectable temporal tone.

The Series U-MH-MCS, U-MH-MCS-W, U-MHT-MCS,

U-MHT-MCS-W, U-MH, U-MH-W, and U-MHT,

U-MHT-W shall include a Universal Mounting Plate that shall allow mounting to single -gang, two-gang, and 4" square backboxes, as well as Siemens Fire

Safety FBX-S and FBX-F Surface Boxes.

The Series U-MH-1G, U-MH-1G-W and U-MHT-1G,

U-MHT-1G-W shall be designed specifically for mounting to a single-gang backbox.

NOTE: These notification appliances are UL listed and rated as “special application’’, which represents appliances which have been investigated to operate as described in the product’s installation instructions over the voltage range of

16-32 VDC or VFWR.

Environmental

32°F to 120°F (0°C to 49°C) at 85% RH

Operating Voltage Range Limits

Horn: 16-32 Vdc or VFWR

Strobe: 16-32 Vdc or VFWR

Horn Current at 24VDC or FFWR

18mA

Typical dB @ 10 Feet

92 dB

Note : Typical readings are frontal sound readings taken with a dB meter with signal mounted on wall.

Mounting

U-MH-1G, U-MH-1G-W & U-MHT-1G, U-MHT-1G-W: mount to 1 gang box,

U-MH, U-MH-W, U-MH-MCS, U-MH-MCS-W, UMHT,

U-MHT-W & U-MHT-MCS, U-MHT-MCS-W: universal mounting plate for 1 gang, 2 gang or 4" square box

Shipping Weights

U-MH-1G, U-MH-1G-W & U-MHT-1G, U-MHT-1G-W: 5 oz. approx.

U-MH, U-MH-W & U-MHT, U-MHT-W: 8 oz. approx.

U-MH-MCS, U-MH-MCS-W & U-MHT-MCS, U-MHT-

MCS-W: 12 oz. approx.

Dimensions

Strobe Intensity Setting

15/75 cd

30/75 cd

75 cd

110 cd

Strobe Current Draw

63 mA

84 mA

143 mA

178 mA

Ordering Information

U-MH & U-MHT Series Mini Horn Wall Mount

Canadian Ordering Information

CU-MH & CU-MHT Series Mini Horn Wall Mount

U-MH & U-MHT Series Mini Horn/Strobe

Wall Mount

CU-MH & CU-MHT Series Mini Horn/Strobe

Wall Mount

Listed operating range is 16 to 32 Vdc/FWR 75.9 - 83.8 dB UL measurements are taken in free air at 360° around the device and averaged.

Typical readings are frontal sound readings taken with a dB meter with signal mounted on wall. Rated for indoor use at 32°F to 120°F, (0°C to

49°C) with 85% RH.

Wiring Diagrams

Siemens Building Technologies

Fire Safety

Fire Safety

8 Fernwood Road

Florham Park, NJ 07932

Tel: (973) 593-2600

FAX: (973) 593-6670

Website: www.sbt.siemens.com/fis

3/05

5M

SFS-IG

Printed in U.S.A.

Fire Safety

2 Kenview Boulevard

Brampton, Ontario

Canada L6T 5E4

Tel: (905) 799-9937

FAX: (905) 799-9858

March 2005

Supersedes sheet dated 6/04

Download